Plan Review Details - Permit 04121896
Plan Review Stops For Permit 04121896
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-12-22 Cont ID  
Sent By jgomez Date 2005-12-22 Time 17:24 Rev Time 1.00
Received By jgomez Date 2005-12-22 Time 17:24 Sent To  
Notes
2005-12-22 00:00:00BUILDING REVIEW CHECKLIST:
 1- MISSING SHEET A-7 SHOWING REVISED
 ROOF SHEATHING NAILING.
  
 2- MISSING SHEET A-7 SHOWING REVISED
 THD210 FASTENERS.
  
 3- MISSING SHEET A-9 SHOWING BBQ
 REVISION.
  
 4- RE-SUBMITTED REVISED SHEETS WILL HAVE
 THE REVISION FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-08-23 Cont ID  
Sent By jgomez Date 2005-08-23 Time 17:31 Rev Time 0.75
Received By jgomez Date 2005-08-23 Time 17:31 Sent To E
Notes
2005-08-23 00:00:00BUILDING REVIEW CHECKLIST:
 1- STAIRS WERE REVISED: HANDRAIL HEIGHT
 WAS CHANGED TO 34" FROM 38". WHEN
 RAILING WAS 38" HIGH IT ALSO SERVED AS A
 GUARDRAIL AS REQ'D BY 1015.1 FBC 2001.
 NOW, THAT RAILING HEIGHT IS 34" HIGH,
 THEN NEED TO PROVIDE A GUARDRAIL. OR,
 MIN. RAILING HEIGHT TO BE 36" MIN. SO IT
 CAN SERVE ALSO AS A GUARDRAIL. REVISE.
  
 2- MEAN ROOF HEIGHT IS GREATER THAN
 25"-0". (MEAN ROOF HEIGHT IS TAKEN FROM
 GRADE NOT FROM FIRST FLOOR FINISH
 ELEVATION). REVISE MEAN ROOF HEIGHT IN
 SHEET A-3 AND REVISE NAILING TYPE AND
 SPACING IN ROOF ZONE 3 AS REQ'D BY TABLE
 2306.1CITY AMENDMENTS TO FBC 2001.
 NOTE: ZONE 3 IS NOT ONLY AT GABLE ENDS.
 IT ALSO INCLUDES ALL CORNERS. SEE FIGURE
 1606.2(C) FBC 2001.
  
 3- NUMBER OF RISERS SHOWN ON STAIR SHOP
 DRAWINGS ARE DIFFERENT THAN THOSE SHOWN
 ON PLANS. REVISE PLANS AS REQUIRED TO
 VERIFY COMPLIANCE WITH SEC. 1007.8.3 FBC
  
  
 4- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 5- PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR 8'-0" X 8'-0" GARAGE DOOR
 THAT MEETS THE DESIGN PRESSURES SHOWN ON
 DRAWING #5.
  
 6- TRUSS ANCHOR SCHEDULE: REVISE THD210
 FASTENERS. SEE TECHNICAL REPORT FOR
 TESTED FASTENERS.
  
 7- PROVIDE COMPLETE APPROVED LISTING FOR
 BBQ TO BE INSTALLED IN THE PORCH.
 INCLUDING, HOOD FOR EXTERIOR USE.
  
 8- SHEET A3: CLARIFY WHY NOTE AT BOTTOM
 LEFT OF THE PAGE REGARDING IMPACT GLASS
 WAS ADDED IF THE PRODUCT APPROVALS
 SUBMITTED ARE FOR SHUTTERS & NON-IMPACT
 DOORS AND WINDOWS.
  
 9- DETAIL B/A-13: REVISE PICKETS
 SPACING. 2X WOOD PICKETS @ 6" OF CENTER
 WILL ALLOW A 4" SPHERE TO PASS THRU.
 NEED TO REDUCE SPACING. SEC. 1015.3 FBC.
  
 10- RE-SUBMITTAL AND REVISION FEES FEES
 WILL APPLY AT TIME OF RE-RESUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-06-06 Cont ID  
Sent By jgomez Date 2005-06-06 Time 12:12 Rev Time 1.00
Received By jgomez Date 2005-06-06 Time 12:12 Sent To PC
Notes
2005-06-06 00:00:00SUBMITTAL CHECKLIST:
 1- PROVIDE ATTIC ACCESS AT MASTER
 BEDROOM WING. SEC. 2309.6 FBC 2001.
  
 2- ROOF SHEATHING:A) MEAN ROOF HEIGHT IS
 GREATER THAN 25'-0". REVISE NAILING TYPE
 AND SPACING IN ROOF ZONE 3 AS REQUIRED
 BY TABLE 2306.1 CITY AMENDMENTS TO FBC
 2001.
 B) DIAPHRAGM FOR ROOF ZONES INSHEET
 A-7 CALLS FOR 6" AREA. REVISE AS
 REQUIRED. SEE TABLE 2306.1 OF CITY
 AMENDMENTS TO FBC 2001.
  
 3- STAIR SHOP DRAWINGS NEED TO BE
 REVIEWED AND APPROVED BY ARCHITECT PRIOR
 TO SUBMITTAL TO THIS OFFICE.
  
 4- STAIR DETAIL B/A-13 CALLS FOR 36"
 HIGH RAILING. NOTES ON FLOOR PLANS CALL
 FOR 38" HIGH RAILING. REVISE AS REQUIRED
  
 5- ARCHITECT TO SPECIFY ROOF TILE
 FASTENING AS REQUIRED BY SEC. 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
  
 6- DESIGN PRESSURES FOR 8'-0" GARAGE
 DOOR WERE REVISED FROM PREVIOUS
 SUBMITTAL. DESIGN PRESSURES CANN'T BE
 EQUAL FOR A 8'-0" AND A 16'-0" DOOR.
 PROVIDE CALCULATIONS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 7- REVISE TRUSS ANCHOR SCHEDULE. USP
 THD210 OR THD210-2 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY MASONRY
 CONNECTOR. SEE CATALOGUE FOR MASONRY
 CONNECTORS AND REVISE AS REQUIRED.
  
 8- INFORMATION SUBMITTED FOR OUTDOOR BBQ
 NEEDS TO BE APPROVED BY THE BUILDING
 OFFICIAL. HE IS OUT THIS WEEK. I WILL
 FORWARD INFORMATION TO HIM WHEN HE'S
 BACK.
  
 9- DESIGN PARAMETERS CHART ON PAGE A-3:
 CLARIFY WHERE IS THE BASIC VELOCITY
 PRESSURE TAKEN FROM. SEE SECTION 1606
 FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-25 Cont ID  
Sent By jgomez Date 2005-03-25 Time 16:59 Rev Time 2.00
Received By jgomez Date 2005-03-25 Time 16:59 Sent To  
Notes
2005-03-25 00:00:00BUILDING REVIEW PROVISO:
 PROVIDE INFORMATION PRIOR TO
 INSTALLATION OR CONTRUCTION TO AVOID
 DELAYS OR CONFLICTS.
 1- PROVIDE MANUFACTURER'S SPECS THAT
 ALLOW BBQ IN THE PORCH. OTHERWISE, BBQ
 WILL NOT BE ALLOWED TO BE INSTALLED IN
 PORCH SINCE THEY ARE DESIGNED FOR
 OUTDOOR USE ONLY.
  
 2- PROVIDE ATTIC ACCESS AT BEDROOM #2
 WING AND AT MASTER BEDROOM WING AS
 REQUIRED BY SEC. 2309.6 FBC 2001.
  
 3- PROVIDE SMOKE DETECTOR ON FIRST FLOOR
 IN CLOSE PROXIMITY TO THE STAIRWAY. AS
 REQUIRED BY SEC. 905.2.2 FBC 2001.
  
 4- ROOF SHEATHING: MEAN ROOF HEIGHT IS
 GREATER THAN 25'. REVISE FASTENER TYPE
 AND SPACING FOR ZONES 3. SEE TABLE
 2306.1 CITY AMENDMENTS TO FBC 2001.
  
 5- PROVIDE STAIR SECTION THAT MATCHES
 STAIRS SHOWN ON PLANS.
  
 6- A) PLANS CALL FOR FLAT CEMENT TILE.
 PRODUCT APPROVAL SUBMITTED IS FOR "S".
 TILE. REVISE TO MATCH.
 B) DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 7- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR 8-0" WIDE GARAGE DOOR.
  
 8- UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE
 COMPLETE ENGINEERING CALCS FOR TYPE AND
 NUMBER OF FASTENERS THAT DIFFER FROM
 THOSE TESTED AND PUBLISHED BY
 MANUFACTURER.
 NOTE: CALCS TO COMPLY WITH SEC. 1609.4.3
 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-02-03 Cont ID  
Sent By jgomez Date 2005-02-03 Time 14:26 Rev Time 3.50
Received By jgomez Date 2005-02-03 Time 14:26 Sent To PC
Notes
2005-02-03 00:00:00BUILDING REVIEW CHECKLIST:
 1- SHEET A-2: A) REVISE FOUNDATION NOTE
 #2. SEE CHAPTER 19 FBC 2001 FOR PROPER
 ACI REFERENCE.
 B OVERLAPPING INFORMATION SHOWN BY THE
 INTERIOR BEARING WALL MAKES INFORMATION
 NOT LEGIBLE TO READ. REVISE AS REQ'D.
  
 2- SHEET A-3: A) HANDRAIL TO BE BETWEEN
 34" AND 38" AS REQ'D BY SEC. 1007.5.1
 FBC 2001 (EXEMPTION #3). REVISE NOTES ON
 SHEETS A-3 AND A-4 AS REQUIRED.
 B) REVISE AREA CALCULATIONS. WHERE IS
 THE 2ND FLOOR BALCONY?
 C) OPENINGS ARE NOT ALLOWED ON ZERO LOT
 LINE WALL. TABLE 600 FBC 2001. REVISE
 LOCATION OF GARAGE VENTILATION OPENING.
 D) NEED COMPLETE BATHROOM WITH DOOR THAT
 ALLOWS 29"MIN. OPENING. SEC. 11-11 FBC.
 BEDROOM #2 HAS THIS NOTE, BUT DOOR SIZE
 SPECIFIED ON BATHROOM IS 2680. REVISE.
 E) REVISE NAME FOR GARAGE NEXT TO BEDRM
 #2. THIS IS ONE CAR GARAGE NOT THREE.
 F) PROVIDE ATTIC ACCESS AT MASTER SUITE
 WING AND AT BEDROOM #2 WING. SECTION
 2309.6 FBC 2001.
 G) NOTE AT BOTTOM OF PAGE CALLS FOR
 MISSILE IMPACT GLAZING, BUT THERE ARE
 STORM SHUTTERS PRODUCT APPROVAL
 SUBMITTED. CLARIFY AS REQUIRED.
  
 3- PROVIDE SMOKE DETECTOR ON FIRST FLOOR
 IN CLOSE PROXIMITY TO THE STAIRWAY
 LEADING TO THE 2ND FL. SEC. 905.2.2
 FBC.
  
 4- ROOF SHEATHING: REVISE FASTENER TYPE
 AND SPACING FOR ROOF AREAS THAT ARE ON
 ZONE 3 WHEN MEAN ROOF HEIGHT IS GREATER
 THAN 25'. SEE TABLE 2306.1 OF CITY
 AMENDMENTS TO FBC 2001.
  
 5- STAIR SECTION ON SHEET A-13 DOESN'T
 MATCH STAIRS SHOWN ON PLANS. PROVIDE
 COMPLETE STAIR SECTION/DETAIL AND SPECS
 THAT MATCH PLANS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 6- ENERGY CALCULATIONS: A) CONDITIONED
 AREA TO MATCH PLANS. REVISE AS
 REQUIRED.
 B) OWNER/AGENT TO SIGN AND DATE FORM.
  
 7- SPECIFICATIONS FOR BBQ SAYS "DO NOT
 INSTALL A GRILL BELOW OVERHEAD
 UNPROTECTED COMBUSTIBLE CONSTRUCTION".
 HOW IS REAR PORCH PROTECTED TO SATISFY
 THIS REQUIREMENT? AND PROVIDE
 MANUFACTURER'S DECLARATION SAYING THAT
 INSTALLATION OF THIS GRILL ON PORCHES IS
 ADEQUATE AND SAFE. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 8- CONCRETE LINTELS: PROVIDE COPY OF
 SAME DADE COUNTY NOA SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
  
 9- STORM SHUTTERS: A) REVISE MIN. AND
 MAX. PANEL SPAN ALLOWED. SEE ENGINEERED
 DRAWINGS FOR LIMITATIONS.
 B) REVISE DESIGN PRESSURES FOR OPENINGS.
 SEE PLANS FOR CALCULATED PRESSURES.
  
 10- PLANS CALL FOR FLAT CEMENT TILE.
 PRODUCT APPROVAL SUBMITTED IS FOR "S"
 TILE. CLARIFY AS REQUIRED.
  
 11- GARAGE DOORS: A) PROVIDE PRODUCT
 APPROVAL FOR 8'-0" WIDE GARAGE DOOR THAT
 MEETS DESIGN PRESSURES CALCULATED ON
 PLANS.
 B) PROVIDE PRODUCT APPROVAL FOR 16'-0"
 WIDE GARAGE DOOR.
  
 12-PROVIDE SAME DADE COUNTY NOA
 SUBMITTED FOR CASEMENT WINDOW FLORIDA
 PRODUCT APPROVAL.
  
 13- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR "INSWING" DOOR AT CABANA
 BATH.
  
 14- SPECIFY ROOF TILE FASTENING. SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 15- UPDATE TRUSS ANCHOR SCHEDULE.
 PROVIDE COMPLETE ENGINEERING CALCS FOR
 TYPE AND NUMBER OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER TO COMPLY WITH SECTION
 1609.4.3 FBC 2001.
  
 16- PROVIDE COMPLETE DETAIL/SPECS FOR
 INSTALLATION OF CEILING AT ENTRY AND
 REAR PORCHES. SPECIFY ALL FASTENERS AND
 SPACING. SEE ASTM C926 AND ASTM C1063.
 SECTION 2504.2 FBC 2001.
  
 17- SHEET A-8: REVISE CONNECTOR G
 SPECIFIED AT MASONRY WALL ON LEFT SIDE
 OF ROOF. NEED WOOD TO MASONRY CONNECTOR.
  
 SEC. 104.2.1.2 CITY AMENDEMNTS TO FBC
 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 20:59 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 20:44 Sent To  
Notes
2006-01-20 00:00:00REDLINED:
  
 RISER STILLS SHOWS 2/0'S TO 150A PANELS,
 THIS IS OK.
  
 2ND FLR ROOM/TECH AREA HAS NOW REMOVED
 THE RECEPT ON ORIGIANL PLANS.
 PLEASE SEE RAIL AREA IN A ROOM IS STILL
 CONSIDERED WALL SPACE PER 210.52
  
 OCP FOR AHU'S, 5KW SHOWS 45A'S?
  
 MISSING SD. FIRST FLR, WALL MOUNTED?
 NFPA-72 8-1.4.2

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-01-13 Cont ID  
Sent By dpalmer Date 2006-01-13 Time 13:26 Rev Time 0.00
Received By dpalmer Date 2006-01-13 Time 13:09 Sent To  
Notes
2006-01-13 00:00:002/0'S SHOWN FOR 150A PANELS, OK
 45A OCP FOR 5KW HEAT.VIF>

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 21:07 Rev Time 0.00
Received By dpalmer Date 2005-12-21 Time 20:36 Sent To PC
Notes
2005-12-21 00:00:00**** PROVISO/REVISION ****
  
 PLEASE SEE "PROVISO" GIVEN ON PREVIOUS
 REVIEW AND NEW NOTES DUE TO CHANGES IN
 PLANS.
  
  
 1)NOTE: PLEASE SEE 3#6'S , 1-#10 GRND
 AND 1#10 NEUTRAL TO POOL SUB PANEL.
 PLEASE VERIFY THE NUMBER AND SIZE OF
 CONDUCTORS SHOWN. (SHOWN AS 3-PHASE).
  
 2)NOTE: PLEASE ALSO SEE A #1 GROUNDING?
 CONDUCTOR SHOWN ON FEEDERS TO SUB
 PANELS??
  
 3)NOTE: PLEASE VERIFY OCP FOR BOTH 5KW
 HEAT STRIPS, AS 45A'S SEEMS HIGH. PLEASE
 VERIFY. NO CORRECTION NEEDED IF
 MANUFACTURES NAMEPLATE CORRELATES.
  
 4)NOTE: PLEASE SEE REDLINED PLANS FOR
 MISSING RECEPTS.
 PLEASE SEEE WHAT APPEARS TO BE 2' OF
 WALL IN FAMILY ROOM.
 PLEASE ALSO SEE 2ND FLR BEDRM #3 ,
 WITHIN 6' OF DOOR.
  
  
 PLEASE REVISE THE ABOVE , SUBMIT FOR
 REVIEW AND STAMPING BEFORE ROUGH
 ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-11-30 Cont ID  
Sent By dpalmer Date 2005-11-30 Time 12:18 Rev Time 0.00
Received By dpalmer Date 2005-11-30 Time 09:50 Sent To B
Notes
2005-11-30 00:00:00REDLINED PLANS/PROVSIO
  
  
  
 1)NOTE: PLEASE SEE 200A OCP FEEDING
 1/0'S (150A) TO 200A PANEL.
 PLEASE SIZE PER 31015B6, 240.4
  
 2)NOTE: PLEASE SEE 3#6'S , 1-#10 GRND
 AND 1#10 NEUTRAL TO POOL SUB PANEL.
 PLEASE VERIFY THE NUMBER AND SIZE OF
 CONDUCTORS SHOWN. (SHOWN AS 3-PHASE).
  
  
  
  
 PLEASE REVISED AND SUBMIT BEFORE FINAL.
 IF ROUGH INSPECTION IS NOT DONE AS OF
 YET, PLEASE REVISE AT THIS TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-08-24 Cont ID  
Sent By dpalmer Date 2005-08-24 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2005-08-24 Time 16:08 Sent To  
Notes
2005-08-24 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SEE SERVICE IS NOW
 INCREASED TO 400'S, PLEASE SEE GROUNDING
 ELECTRODE CONDUCTORSHALL BE INCREASED
 TO 1/0 MIN PER 250.66/310.15B6
  
 2)NOTE: PLEASE SEE PANEL "A" PANEL
 SCHEDULE INDICATES PANEL TO BE 200A'?
 PLEASE SEE RISER SHOWS 150A'S?
 PLEASE CORRELATE.
 PLEASE ADJUST ANY FEEDERS ETC FOR ANY
 INCREASES FOR PANEL SIZE.
 310.15B6,240.4 ETC
  
 3)NOTE: PLEASE SEE BOTH PANEL SCHEDULES
 LIST AHU/SYSTEM #2. (MISPRINT).
  
  
 4)NOTE: PLEASE SEE WHIRLPOOL TUB IS
 BEING SHOWN AS FUTURE, IF THIS FOR ROUGH
 OR ELECTRICAL FINAL, THIS MUST INDICATE
 OF THIS IS INSTALLED AT THIS TIMEOR
 NOT.
  
 5)NOTE: PLEASE SEE ONLY ONE ELECTRICAL
 PANEL SHOWN IN GARAGE AND PLEASE SEE
 POOL PANEL NOT SHOWN ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-03-08 Cont ID  
Sent By dpalmer Date 2005-03-08 Time 08:39 Rev Time 0.33
Received By dpalmer Date 2005-03-07 Time 18:59 Sent To B
Notes
2005-03-07 00:00:00IN FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By dpalmer Date 2005-01-07 Time 14:09 Rev Time 0.30
Received By dpalmer Date 2005-01-07 Time 14:09 Sent To M
Notes
2005-01-07 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN
 COUNTERSPACE GFI RECEPTS.
  
 2)NOTE: PLEASE SEE HI-HAT LOAD SHOWN AT
 48.0KW. PLEASE SEE 64@75W EACH.
 PLEASE SEE THIS MAY AFFECT SIZE OF
 SERVICE.
  
 3)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR PER 310.15B6,
 250.66
 #2 MIN. (IFF 300A SERVICE REMAINS. )
  
 4)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATESBRKFST NOOK AS GFI. THIS IS
 NOT REQUIRED,, YET PERMITTED. IF SHOWN
 ON PLANS THEN THIS IS REQUIRED TO BE
 DONE.
  
 5)NOTE: PLEASE CORRELATE RISER WITH
 PLANS. PLANS INDICATE METER/MAIN ON
 OUTSIDE OF HOUSE, PANEL IN GARAGE AND
 PANEL IN LAUNDRY RM?
 215.5
  
  
 6)NOTE: PLEASE SEE OCP IS NOT CLEAR ON
 PANEL SCHEDULE/LOAD CALCS FOR AHU 5KE
 HEAT. APPEARS TO BE 50A?
 PLEASE SEE 424.3B 125% MIN AND 150%
 USUALLY MAX. IS THIS 30A OCP?
 PLEASE ALSO SEE RISER SHOWS 60A OCP FOR
 COND UNITS. PLEASE VERIFY THE OCP WITH
 MECH PLANS FOR SIZE OF CU.
  
 7)NOTE: PLEASE SEE 210.52 FOR RECEPT
 LOCATIONS MISSING ON PLANS. BEDRM #2,
 #3, AND DEN.
  
 8)NOTE: PLEASE SEE PLANS INDICATE POOL
 EQUIPMENT, YET THIS IS NOT ON PANEL
 SCHEDULE. IF "FUTURE" PLEASE JUST PLACE
 NOTE ON PLANS FOR "FUTURE".
  
 PLEASE SEE ALL OF THESE ABOVE ITEMS HAVE
 BEEN REDLINED ON ONE SET OF PLANS FOR
 AREAS OF CONCERN.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SET MAY BE SUBMITTED FOR
 REFERENCE ONLY.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2006-01-09 Time 16:20 Rev Time 0.00
Received By adarroug Date 2006-01-09 Time 16:20 Sent To E
Notes
2006-01-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 16:41 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 16:41 Sent To E
Notes
2005-12-16 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-11-23 Cont ID  
Sent By adarroug Date 2005-11-23 Time 14:06 Rev Time 0.00
Received By adarroug Date 2005-11-23 Time 14:06 Sent To E
Notes
2005-11-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 10:55 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 10:55 Sent To B
Notes
2005-07-05 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-26 Cont ID  
Sent By adarroug Date 2005-05-26 Time 08:54 Rev Time 0.00
Received By adarroug Date 2005-05-26 Time 08:54 Sent To B
Notes
2005-05-26 00:00:00TO "JGOMEZ" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-07 Cont ID  
Sent By adarroug Date 2005-03-07 Time 16:08 Rev Time 0.00
Received By adarroug Date 2005-03-07 Time 16:08 Sent To E
Notes
2005-03-07 00:00:00TO DPALMER DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 07:55 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 07:55 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 10:47 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 10:47 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By prafter Date 2005-01-11 Time 11:34 Rev Time 0.45
Received By prafter Date 2005-01-11 Time 11:34 Sent To B
Notes
2005-01-11 00:00:00NO A/C PLANS.
 PAT RAFTER 561/805/6725 OR 805/6719 .

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-11 Cont ID  
Sent By jleech Date 2005-01-11 Time 10:33 Rev Time 0.33
Received By jleech Date 2005-01-11 Time 10:33 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 17:13 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 17:13 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK