| Plan Review Stops For Permit 04121896 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2005-12-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-12-22 |
Time |
17:24 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2005-12-22 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2005-12-22 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- MISSING SHEET A-7 SHOWING REVISED | | | ROOF SHEATHING NAILING. | | | | | | 2- MISSING SHEET A-7 SHOWING REVISED | | | THD210 FASTENERS. | | | | | | 3- MISSING SHEET A-9 SHOWING BBQ | | | REVISION. | | | | | | 4- RE-SUBMITTED REVISED SHEETS WILL HAVE | | | THE REVISION FEES. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561) 805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2005-08-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-08-23 |
Time |
17:31 |
Rev Time |
0.75 |
| Received By |
jgomez |
Date |
2005-08-23 |
Time |
17:31 |
Sent To |
E |
|
| Notes |
| 2005-08-23 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- STAIRS WERE REVISED: HANDRAIL HEIGHT | | | WAS CHANGED TO 34" FROM 38". WHEN | | | RAILING WAS 38" HIGH IT ALSO SERVED AS A | | | GUARDRAIL AS REQ'D BY 1015.1 FBC 2001. | | | NOW, THAT RAILING HEIGHT IS 34" HIGH, | | | THEN NEED TO PROVIDE A GUARDRAIL. OR, | | | MIN. RAILING HEIGHT TO BE 36" MIN. SO IT | | | CAN SERVE ALSO AS A GUARDRAIL. REVISE. | | | | | | 2- MEAN ROOF HEIGHT IS GREATER THAN | | | 25"-0". (MEAN ROOF HEIGHT IS TAKEN FROM | | | GRADE NOT FROM FIRST FLOOR FINISH | | | ELEVATION). REVISE MEAN ROOF HEIGHT IN | | | SHEET A-3 AND REVISE NAILING TYPE AND | | | SPACING IN ROOF ZONE 3 AS REQ'D BY TABLE | | | 2306.1CITY AMENDMENTS TO FBC 2001. | | | NOTE: ZONE 3 IS NOT ONLY AT GABLE ENDS. | | | IT ALSO INCLUDES ALL CORNERS. SEE FIGURE | | | 1606.2(C) FBC 2001. | | | | | | 3- NUMBER OF RISERS SHOWN ON STAIR SHOP | | | DRAWINGS ARE DIFFERENT THAN THOSE SHOWN | | | ON PLANS. REVISE PLANS AS REQUIRED TO | | | VERIFY COMPLIANCE WITH SEC. 1007.8.3 FBC | | | | | | | | | 4- DESIGNER OF RECORD TO SPECIFY ROOF | | | TILE FASTENING AS REQUIRED BY SECTION | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | | | | | 5- PROVIDE FLORIDA/LOCAL PRODUCT | | | APPROVAL FOR 8'-0" X 8'-0" GARAGE DOOR | | | THAT MEETS THE DESIGN PRESSURES SHOWN ON | | | DRAWING #5. | | | | | | 6- TRUSS ANCHOR SCHEDULE: REVISE THD210 | | | FASTENERS. SEE TECHNICAL REPORT FOR | | | TESTED FASTENERS. | | | | | | 7- PROVIDE COMPLETE APPROVED LISTING FOR | | | BBQ TO BE INSTALLED IN THE PORCH. | | | INCLUDING, HOOD FOR EXTERIOR USE. | | | | | | 8- SHEET A3: CLARIFY WHY NOTE AT BOTTOM | | | LEFT OF THE PAGE REGARDING IMPACT GLASS | | | WAS ADDED IF THE PRODUCT APPROVALS | | | SUBMITTED ARE FOR SHUTTERS & NON-IMPACT | | | DOORS AND WINDOWS. | | | | | | 9- DETAIL B/A-13: REVISE PICKETS | | | SPACING. 2X WOOD PICKETS @ 6" OF CENTER | | | WILL ALLOW A 4" SPHERE TO PASS THRU. | | | NEED TO REDUCE SPACING. SEC. 1015.3 FBC. | | | | | | 10- RE-SUBMITTAL AND REVISION FEES FEES | | | WILL APPLY AT TIME OF RE-RESUBMITTAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-06-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-06-06 |
Time |
12:12 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2005-06-06 |
Time |
12:12 |
Sent To |
PC |
|
| Notes |
| 2005-06-06 00:00:00 | SUBMITTAL CHECKLIST: | | | 1- PROVIDE ATTIC ACCESS AT MASTER | | | BEDROOM WING. SEC. 2309.6 FBC 2001. | | | | | | 2- ROOF SHEATHING:A) MEAN ROOF HEIGHT IS | | | GREATER THAN 25'-0". REVISE NAILING TYPE | | | AND SPACING IN ROOF ZONE 3 AS REQUIRED | | | BY TABLE 2306.1 CITY AMENDMENTS TO FBC | | | 2001. | | | B) DIAPHRAGM FOR ROOF ZONES INSHEET | | | A-7 CALLS FOR 6" AREA. REVISE AS | | | REQUIRED. SEE TABLE 2306.1 OF CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 3- STAIR SHOP DRAWINGS NEED TO BE | | | REVIEWED AND APPROVED BY ARCHITECT PRIOR | | | TO SUBMITTAL TO THIS OFFICE. | | | | | | 4- STAIR DETAIL B/A-13 CALLS FOR 36" | | | HIGH RAILING. NOTES ON FLOOR PLANS CALL | | | FOR 38" HIGH RAILING. REVISE AS REQUIRED | | | | | | 5- ARCHITECT TO SPECIFY ROOF TILE | | | FASTENING AS REQUIRED BY SEC. 104.2.1.1 | | | CITY AMENDMENTS TO FBC 2001. | | | | | | 6- DESIGN PRESSURES FOR 8'-0" GARAGE | | | DOOR WERE REVISED FROM PREVIOUS | | | SUBMITTAL. DESIGN PRESSURES CANN'T BE | | | EQUAL FOR A 8'-0" AND A 16'-0" DOOR. | | | PROVIDE CALCULATIONS. SEC. 104.2.1.2 | | | CITY AMENDMENTS TO FBC 2001. | | | | | | 7- REVISE TRUSS ANCHOR SCHEDULE. USP | | | THD210 OR THD210-2 IS A WOOD TO WOOD | | | CONNECTOR. NEED TO SPECIFY MASONRY | | | CONNECTOR. SEE CATALOGUE FOR MASONRY | | | CONNECTORS AND REVISE AS REQUIRED. | | | | | | 8- INFORMATION SUBMITTED FOR OUTDOOR BBQ | | | NEEDS TO BE APPROVED BY THE BUILDING | | | OFFICIAL. HE IS OUT THIS WEEK. I WILL | | | FORWARD INFORMATION TO HIM WHEN HE'S | | | BACK. | | | | | | 9- DESIGN PARAMETERS CHART ON PAGE A-3: | | | CLARIFY WHERE IS THE BASIC VELOCITY | | | PRESSURE TAKEN FROM. SEE SECTION 1606 | | | FBC 2001. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-03-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-03-25 |
Time |
16:59 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
2005-03-25 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2005-03-25 00:00:00 | BUILDING REVIEW PROVISO: | | | PROVIDE INFORMATION PRIOR TO | | | INSTALLATION OR CONTRUCTION TO AVOID | | | DELAYS OR CONFLICTS. | | | 1- PROVIDE MANUFACTURER'S SPECS THAT | | | ALLOW BBQ IN THE PORCH. OTHERWISE, BBQ | | | WILL NOT BE ALLOWED TO BE INSTALLED IN | | | PORCH SINCE THEY ARE DESIGNED FOR | | | OUTDOOR USE ONLY. | | | | | | 2- PROVIDE ATTIC ACCESS AT BEDROOM #2 | | | WING AND AT MASTER BEDROOM WING AS | | | REQUIRED BY SEC. 2309.6 FBC 2001. | | | | | | 3- PROVIDE SMOKE DETECTOR ON FIRST FLOOR | | | IN CLOSE PROXIMITY TO THE STAIRWAY. AS | | | REQUIRED BY SEC. 905.2.2 FBC 2001. | | | | | | 4- ROOF SHEATHING: MEAN ROOF HEIGHT IS | | | GREATER THAN 25'. REVISE FASTENER TYPE | | | AND SPACING FOR ZONES 3. SEE TABLE | | | 2306.1 CITY AMENDMENTS TO FBC 2001. | | | | | | 5- PROVIDE STAIR SECTION THAT MATCHES | | | STAIRS SHOWN ON PLANS. | | | | | | 6- A) PLANS CALL FOR FLAT CEMENT TILE. | | | PRODUCT APPROVAL SUBMITTED IS FOR "S". | | | TILE. REVISE TO MATCH. | | | B) DESIGNER OF RECORD TO SPECIFY ROOF | | | TILE FASTENING AS REQUIRED BY SECTION | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | | | | | 7- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR 8-0" WIDE GARAGE DOOR. | | | | | | 8- UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE | | | COMPLETE ENGINEERING CALCS FOR TYPE AND | | | NUMBER OF FASTENERS THAT DIFFER FROM | | | THOSE TESTED AND PUBLISHED BY | | | MANUFACTURER. | | | NOTE: CALCS TO COMPLY WITH SEC. 1609.4.3 | | | FBC 2001. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-02-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2005-02-03 |
Time |
14:26 |
Rev Time |
3.50 |
| Received By |
jgomez |
Date |
2005-02-03 |
Time |
14:26 |
Sent To |
PC |
|
| Notes |
| 2005-02-03 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- SHEET A-2: A) REVISE FOUNDATION NOTE | | | #2. SEE CHAPTER 19 FBC 2001 FOR PROPER | | | ACI REFERENCE. | | | B OVERLAPPING INFORMATION SHOWN BY THE | | | INTERIOR BEARING WALL MAKES INFORMATION | | | NOT LEGIBLE TO READ. REVISE AS REQ'D. | | | | | | 2- SHEET A-3: A) HANDRAIL TO BE BETWEEN | | | 34" AND 38" AS REQ'D BY SEC. 1007.5.1 | | | FBC 2001 (EXEMPTION #3). REVISE NOTES ON | | | SHEETS A-3 AND A-4 AS REQUIRED. | | | B) REVISE AREA CALCULATIONS. WHERE IS | | | THE 2ND FLOOR BALCONY? | | | C) OPENINGS ARE NOT ALLOWED ON ZERO LOT | | | LINE WALL. TABLE 600 FBC 2001. REVISE | | | LOCATION OF GARAGE VENTILATION OPENING. | | | D) NEED COMPLETE BATHROOM WITH DOOR THAT | | | ALLOWS 29"MIN. OPENING. SEC. 11-11 FBC. | | | BEDROOM #2 HAS THIS NOTE, BUT DOOR SIZE | | | SPECIFIED ON BATHROOM IS 2680. REVISE. | | | E) REVISE NAME FOR GARAGE NEXT TO BEDRM | | | #2. THIS IS ONE CAR GARAGE NOT THREE. | | | F) PROVIDE ATTIC ACCESS AT MASTER SUITE | | | WING AND AT BEDROOM #2 WING. SECTION | | | 2309.6 FBC 2001. | | | G) NOTE AT BOTTOM OF PAGE CALLS FOR | | | MISSILE IMPACT GLAZING, BUT THERE ARE | | | STORM SHUTTERS PRODUCT APPROVAL | | | SUBMITTED. CLARIFY AS REQUIRED. | | | | | | 3- PROVIDE SMOKE DETECTOR ON FIRST FLOOR | | | IN CLOSE PROXIMITY TO THE STAIRWAY | | | LEADING TO THE 2ND FL. SEC. 905.2.2 | | | FBC. | | | | | | 4- ROOF SHEATHING: REVISE FASTENER TYPE | | | AND SPACING FOR ROOF AREAS THAT ARE ON | | | ZONE 3 WHEN MEAN ROOF HEIGHT IS GREATER | | | THAN 25'. SEE TABLE 2306.1 OF CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 5- STAIR SECTION ON SHEET A-13 DOESN'T | | | MATCH STAIRS SHOWN ON PLANS. PROVIDE | | | COMPLETE STAIR SECTION/DETAIL AND SPECS | | | THAT MATCH PLANS. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 6- ENERGY CALCULATIONS: A) CONDITIONED | | | AREA TO MATCH PLANS. REVISE AS | | | REQUIRED. | | | B) OWNER/AGENT TO SIGN AND DATE FORM. | | | | | | 7- SPECIFICATIONS FOR BBQ SAYS "DO NOT | | | INSTALL A GRILL BELOW OVERHEAD | | | UNPROTECTED COMBUSTIBLE CONSTRUCTION". | | | HOW IS REAR PORCH PROTECTED TO SATISFY | | | THIS REQUIREMENT? AND PROVIDE | | | MANUFACTURER'S DECLARATION SAYING THAT | | | INSTALLATION OF THIS GRILL ON PORCHES IS | | | ADEQUATE AND SAFE. SECTION 104.2.1.2 | | | CITY AMENDMENTS TO FBC 2001. | | | | | | 8- CONCRETE LINTELS: PROVIDE COPY OF | | | SAME DADE COUNTY NOA SUBMITTED FOR | | | FLORIDA PRODUCT APPROVAL. | | | | | | 9- STORM SHUTTERS: A) REVISE MIN. AND | | | MAX. PANEL SPAN ALLOWED. SEE ENGINEERED | | | DRAWINGS FOR LIMITATIONS. | | | B) REVISE DESIGN PRESSURES FOR OPENINGS. | | | SEE PLANS FOR CALCULATED PRESSURES. | | | | | | 10- PLANS CALL FOR FLAT CEMENT TILE. | | | PRODUCT APPROVAL SUBMITTED IS FOR "S" | | | TILE. CLARIFY AS REQUIRED. | | | | | | 11- GARAGE DOORS: A) PROVIDE PRODUCT | | | APPROVAL FOR 8'-0" WIDE GARAGE DOOR THAT | | | MEETS DESIGN PRESSURES CALCULATED ON | | | PLANS. | | | B) PROVIDE PRODUCT APPROVAL FOR 16'-0" | | | WIDE GARAGE DOOR. | | | | | | 12-PROVIDE SAME DADE COUNTY NOA | | | SUBMITTED FOR CASEMENT WINDOW FLORIDA | | | PRODUCT APPROVAL. | | | | | | 13- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR "INSWING" DOOR AT CABANA | | | BATH. | | | | | | 14- SPECIFY ROOF TILE FASTENING. SECTION | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | | | | | 15- UPDATE TRUSS ANCHOR SCHEDULE. | | | PROVIDE COMPLETE ENGINEERING CALCS FOR | | | TYPE AND NUMBER OF FASTENERS THAT DIFFER | | | FROM THOSE TESTED AND PUBLISHED BY THE | | | MANUFACTURER TO COMPLY WITH SECTION | | | 1609.4.3 FBC 2001. | | | | | | 16- PROVIDE COMPLETE DETAIL/SPECS FOR | | | INSTALLATION OF CEILING AT ENTRY AND | | | REAR PORCHES. SPECIFY ALL FASTENERS AND | | | SPACING. SEE ASTM C926 AND ASTM C1063. | | | SECTION 2504.2 FBC 2001. | | | | | | 17- SHEET A-8: REVISE CONNECTOR G | | | SPECIFIED AT MASONRY WALL ON LEFT SIDE | | | OF ROOF. NEED WOOD TO MASONRY CONNECTOR. | | | | | | SEC. 104.2.1.2 CITY AMENDEMNTS TO FBC | | | 2001. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ AT (561)805-6712. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-01-20 |
Time |
20:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-01-20 |
Time |
20:44 |
Sent To |
|
|
| Notes |
| 2006-01-20 00:00:00 | REDLINED: | | | | | | RISER STILLS SHOWS 2/0'S TO 150A PANELS, | | | THIS IS OK. | | | | | | 2ND FLR ROOM/TECH AREA HAS NOW REMOVED | | | THE RECEPT ON ORIGIANL PLANS. | | | PLEASE SEE RAIL AREA IN A ROOM IS STILL | | | CONSIDERED WALL SPACE PER 210.52 | | | | | | OCP FOR AHU'S, 5KW SHOWS 45A'S? | | | | | | MISSING SD. FIRST FLR, WALL MOUNTED? | | | NFPA-72 8-1.4.2 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2006-01-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-01-13 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-01-13 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2006-01-13 00:00:00 | 2/0'S SHOWN FOR 150A PANELS, OK | | | 45A OCP FOR 5KW HEAT.VIF> |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2005-12-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-21 |
Time |
21:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-21 |
Time |
20:36 |
Sent To |
PC |
|
| Notes |
| 2005-12-21 00:00:00 | **** PROVISO/REVISION **** | | | | | | PLEASE SEE "PROVISO" GIVEN ON PREVIOUS | | | REVIEW AND NEW NOTES DUE TO CHANGES IN | | | PLANS. | | | | | | | | | 1)NOTE: PLEASE SEE 3#6'S , 1-#10 GRND | | | AND 1#10 NEUTRAL TO POOL SUB PANEL. | | | PLEASE VERIFY THE NUMBER AND SIZE OF | | | CONDUCTORS SHOWN. (SHOWN AS 3-PHASE). | | | | | | 2)NOTE: PLEASE ALSO SEE A #1 GROUNDING? | | | CONDUCTOR SHOWN ON FEEDERS TO SUB | | | PANELS?? | | | | | | 3)NOTE: PLEASE VERIFY OCP FOR BOTH 5KW | | | HEAT STRIPS, AS 45A'S SEEMS HIGH. PLEASE | | | VERIFY. NO CORRECTION NEEDED IF | | | MANUFACTURES NAMEPLATE CORRELATES. | | | | | | 4)NOTE: PLEASE SEE REDLINED PLANS FOR | | | MISSING RECEPTS. | | | PLEASE SEEE WHAT APPEARS TO BE 2' OF | | | WALL IN FAMILY ROOM. | | | PLEASE ALSO SEE 2ND FLR BEDRM #3 , | | | WITHIN 6' OF DOOR. | | | | | | | | | PLEASE REVISE THE ABOVE , SUBMIT FOR | | | REVIEW AND STAMPING BEFORE ROUGH | | | ELECTRICAL INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-11-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-11-30 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-11-30 |
Time |
09:50 |
Sent To |
B |
|
| Notes |
| 2005-11-30 00:00:00 | REDLINED PLANS/PROVSIO | | | | | | | | | | | | 1)NOTE: PLEASE SEE 200A OCP FEEDING | | | 1/0'S (150A) TO 200A PANEL. | | | PLEASE SIZE PER 31015B6, 240.4 | | | | | | 2)NOTE: PLEASE SEE 3#6'S , 1-#10 GRND | | | AND 1#10 NEUTRAL TO POOL SUB PANEL. | | | PLEASE VERIFY THE NUMBER AND SIZE OF | | | CONDUCTORS SHOWN. (SHOWN AS 3-PHASE). | | | | | | | | | | | | | | | PLEASE REVISED AND SUBMIT BEFORE FINAL. | | | IF ROUGH INSPECTION IS NOT DONE AS OF | | | YET, PLEASE REVISE AT THIS TIME. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-24 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-08-24 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2005-08-24 00:00:00 | ******** UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE SERVICE IS NOW | | | INCREASED TO 400'S, PLEASE SEE GROUNDING | | | ELECTRODE CONDUCTORSHALL BE INCREASED | | | TO 1/0 MIN PER 250.66/310.15B6 | | | | | | 2)NOTE: PLEASE SEE PANEL "A" PANEL | | | SCHEDULE INDICATES PANEL TO BE 200A'? | | | PLEASE SEE RISER SHOWS 150A'S? | | | PLEASE CORRELATE. | | | PLEASE ADJUST ANY FEEDERS ETC FOR ANY | | | INCREASES FOR PANEL SIZE. | | | 310.15B6,240.4 ETC | | | | | | 3)NOTE: PLEASE SEE BOTH PANEL SCHEDULES | | | LIST AHU/SYSTEM #2. (MISPRINT). | | | | | | | | | 4)NOTE: PLEASE SEE WHIRLPOOL TUB IS | | | BEING SHOWN AS FUTURE, IF THIS FOR ROUGH | | | OR ELECTRICAL FINAL, THIS MUST INDICATE | | | OF THIS IS INSTALLED AT THIS TIMEOR | | | NOT. | | | | | | 5)NOTE: PLEASE SEE ONLY ONE ELECTRICAL | | | PANEL SHOWN IN GARAGE AND PLEASE SEE | | | POOL PANEL NOT SHOWN ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-03-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-03-08 |
Time |
08:39 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2005-03-07 |
Time |
18:59 |
Sent To |
B |
|
| Notes |
| 2005-03-07 00:00:00 | IN FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-01-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-07 |
Time |
14:09 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-01-07 |
Time |
14:09 |
Sent To |
M |
|
| Notes |
| 2005-01-07 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN | | | COUNTERSPACE GFI RECEPTS. | | | | | | 2)NOTE: PLEASE SEE HI-HAT LOAD SHOWN AT | | | 48.0KW. PLEASE SEE 64@75W EACH. | | | PLEASE SEE THIS MAY AFFECT SIZE OF | | | SERVICE. | | | | | | 3)NOTE: PLEASE SEE MIN GROUNDING | | | ELECTRODE CONDUCTOR PER 310.15B6, | | | 250.66 | | | #2 MIN. (IFF 300A SERVICE REMAINS. ) | | | | | | 4)NOTE: PLEASE SEE PANEL SCHEDULE | | | INDICATESBRKFST NOOK AS GFI. THIS IS | | | NOT REQUIRED,, YET PERMITTED. IF SHOWN | | | ON PLANS THEN THIS IS REQUIRED TO BE | | | DONE. | | | | | | 5)NOTE: PLEASE CORRELATE RISER WITH | | | PLANS. PLANS INDICATE METER/MAIN ON | | | OUTSIDE OF HOUSE, PANEL IN GARAGE AND | | | PANEL IN LAUNDRY RM? | | | 215.5 | | | | | | | | | 6)NOTE: PLEASE SEE OCP IS NOT CLEAR ON | | | PANEL SCHEDULE/LOAD CALCS FOR AHU 5KE | | | HEAT. APPEARS TO BE 50A? | | | PLEASE SEE 424.3B 125% MIN AND 150% | | | USUALLY MAX. IS THIS 30A OCP? | | | PLEASE ALSO SEE RISER SHOWS 60A OCP FOR | | | COND UNITS. PLEASE VERIFY THE OCP WITH | | | MECH PLANS FOR SIZE OF CU. | | | | | | 7)NOTE: PLEASE SEE 210.52 FOR RECEPT | | | LOCATIONS MISSING ON PLANS. BEDRM #2, | | | #3, AND DEN. | | | | | | 8)NOTE: PLEASE SEE PLANS INDICATE POOL | | | EQUIPMENT, YET THIS IS NOT ON PANEL | | | SCHEDULE. IF "FUTURE" PLEASE JUST PLACE | | | NOTE ON PLANS FOR "FUTURE". | | | | | | PLEASE SEE ALL OF THESE ABOVE ITEMS HAVE | | | BEEN REDLINED ON ONE SET OF PLANS FOR | | | AREAS OF CONCERN. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE COPY OF OLD SET MAY BE SUBMITTED FOR | | | REFERENCE ONLY. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-01-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-09 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-09 |
Time |
16:20 |
Sent To |
E |
|
| Notes |
| 2006-01-09 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-12-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-16 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-16 |
Time |
16:41 |
Sent To |
E |
|
| Notes |
| 2005-12-16 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-11-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-23 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-23 |
Time |
14:06 |
Sent To |
E |
|
| Notes |
| 2005-11-23 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-07-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-05 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-05 |
Time |
10:55 |
Sent To |
B |
|
| Notes |
| 2005-07-05 00:00:00 | TO "JGOMEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-05-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-26 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-26 |
Time |
08:54 |
Sent To |
B |
|
| Notes |
| 2005-05-26 00:00:00 | TO "JGOMEZ" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-03-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-07 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-07 |
Time |
16:08 |
Sent To |
E |
|
| Notes |
| 2005-03-07 00:00:00 | TO DPALMER DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-01-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-06 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-06 |
Time |
07:55 |
Sent To |
E |
|
| Notes |
| 2005-01-06 00:00:00 | TO "SFD" RACK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-01-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-03 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-03 |
Time |
10:47 |
Sent To |
Z |
|
| Notes |
| 2005-01-03 00:00:00 | TO "Z" BOX. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-01-11 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-01-11 |
Time |
11:34 |
Rev Time |
0.45 |
| Received By |
prafter |
Date |
2005-01-11 |
Time |
11:34 |
Sent To |
B |
|
| Notes |
| 2005-01-11 00:00:00 | NO A/C PLANS. | | | PAT RAFTER 561/805/6725 OR 805/6719 . |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2005-01-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-01-11 |
Time |
10:33 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2005-01-11 |
Time |
10:33 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-01-05 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-01-05 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-01-05 |
Time |
17:13 |
Sent To |
I |
|
| Notes |
| 2005-01-05 00:00:00 | MUST PULL SEPERATE PERMIT FOR POOL/DECK |
|
|