Plan Review Details - Permit 04121884
Plan Review Stops For Permit 04121884
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-11-10 Cont ID  
Sent By jgomez Date 2005-11-10 Time 19:22 Rev Time 0.50
Received By jgomez Date 2005-11-10 Time 19:22 Sent To PC
Notes
2005-11-10 00:00:00STORM SHUTTERS REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-29 Cont ID  
Sent By jgomez Date 2005-04-29 Time 15:10 Rev Time 2.00
Received By jgomez Date 2005-04-29 Time 15:10 Sent To PC
Notes
2005-04-29 00:00:00BUILDING REVIEW PROVISO:
 1- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 2- CLARIFY WHERE IS THE BASIC VELOCITY
 PRESSURE TAKEN FROM. THERE ARE NOT
 TABLES SHOWN IN CHAPTER 16 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-11 Cont ID  
Sent By jgomez Date 2005-03-11 Time 15:09 Rev Time 2.50
Received By jgomez Date 2005-03-11 Time 15:09 Sent To PC
Notes
2005-03-11 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- MISSING SHEET A-4.
 THERE ARE 2 A-5 SHEETS. ONE OF THE IS
 FOR A 2 STORY HOUSE.
 THERE ARE 2 CV-1 SHEETS. PROVIDE ONLY
 ONE PER SET.
  
 2- UPDATE TRUSS ANCHOR SCHEDULE TO MATCH
 CAPACITY AND TYPE & NUMBER OF FASTENERS
 AS SHOWN ON FLORIDA PRODUCT APPROVAL
 PACKAGE. OR PROVIDE COMPLETE ENGINEERING
 ANALYSIS AND CALCULATIONS THAT COMPLY
 WITH SECTION 1609.4.3 FBC 2001.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) USP TRUSS ANCHORS SPECIFIED ON PLANS.
  
 B) ENTRY DOORS WITH SIZE AND DIRECTION
 OF SWING AS SHOWN ON PLANS. AND EXACT
 SAME DRAWINGS THAT WERE SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
 NEED SOLID DOOR OR IMPACT GLAZING
 BECAUSE DOOR IS TO BE USED FOR EMERGENCY
 EGRESS. SEC. 1005.4.5 FBC 2001.
  
 C) FRENCH DOORS WITH SIZE AND SWING
 DIRECTION AS SHOWN ON PLANS. AND WITH
 EXACT SAME DRAWINGS THAT WERE SUBMITTED
 FOR FLORIDA PRODUCT APPROVAL.
  
 D) CASEMENT WINDOWS WITH EXACT SAME
 DRAWINGS THAT WERE SUBMITTED FOR FLORIDA
 PRODUCT APPROVAL.
  
 4- DELETE BBQ AND FIREPLACE FROM
 DRAWINGS IF OPTION IS NOT GOING TO BE
 BUILT OR PROVIDE COMPLETE INFORMATION
 FOR THEM AS REQUIRED BY SEC. 2806 AND
 2808 FBC 2001.
  
 5- STORM SHUTTERS: A) BOTH COPIES NEED
 TO HAVE ORIGINAL SEAL, SIGNATURE AND
 DATE AS REQUIRED BY ENGINEER ON NOTE #6.
  
 B) SOME PANELS EXCEED MAX. PANEL SPAN
 ACCORDING TO THE DESIGN PRESSURES. SEE
 ENGINEERED DRAWINGS AND REVISE AS
 REQUIRED.
  
 C) CLEARLY MARK ON ENGINEERED DRAWINGS
 THE SPECIFIC ANCHOR TYPE AND SPACING TO
 BE USED ACCORDING TO THE EDGE DISTANCE,
 PANEL SPAN, DESIGN PRESSURES, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO
 (MASONRY OR 2500PSI CONCRETE).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By jgomez Date 2005-01-25 Time 09:22 Rev Time 2.00
Received By jgomez Date 2005-01-25 Time 09:22 Sent To PC
Notes
2005-01-25 00:00:00CHECKLIST:
 1-PROVIDE COMPLETE BATHROOM WITH A DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING.
 SECTION 11-11 FBC 2001.
  
 2-SPECIFY ROOF TILE FASTENING. SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 3-UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE AND NUMBER OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER TO COMPLY WITH SECTION
 1609.4.3 FBC 2001.
  
 4- A) TITLE BLOCK NEEDS NAME OF
 ARCHITECT SEALING THE PLANS. SEE CHAPTER
 61G1-16004 OF F.A.C.
 B) STATE REGISTRATION NUMBER IS
 INCORRECT. REVISE AS REQUIRED.
  
 5-PROVIDE COMPLETE DETAIL/SPECS FOR
 INSTALLATION OF CEILING AT ENTRY AND
 REAR PORCH. SPECIFY ALL FASTENERS AND
 SPACING. SEE ASTM C926 AND ASTM C1063.
 SEC. 2504.2 FBC 2001.
  
 6-OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS.
  
 7-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ENTRY DOORS. SEE SIZE ON PLANS.
 B) FRENCH DOORS. SEE SIZE ON PLANS.
 C) CONCRETE LINTELS: NEED DADE COUNTY
 NOA THAT MATCHES ONE SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
 D) FIXED WINDOWS THAT MEET THE DESIGN
 PRESSURES CALCULATED ON PLANS. SEE PLANS
 FOR SIZE AND LOCATION.
 E) ARABESQUE WINDOW AS SHOWN ON PLANS.
  
 8- A) PROVIDE COMPLETE UL LISTING AND
 SPECS FOR FIREPLACE. SEC. 2806 FBC
 2001.
 B) PROVIDE APPROVED BBQ SPECS. SECTION
 2808 FBC 2001.
  
 9-STORM SHUTTERS: A) KEY PLAN DOESN'T
 MATCH PLANS.
 B) REVISED MIN. PANEL SIZE. SEE
 ENGINEERED DRAWINGS.
 C) REVISE INTERIOR AND END ZONES. SEE
 PLANS.
 D) REVISE DESIGN PRESSURES. SEE PLANS.
  
 10- PROVIDE COMPLETE FRAMING DETAILS FOR
 ARABESQUE WINDOW. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 11-OWES $866.23 FOR UPDATED VALUATION.
  
 12-REVISE FOUNDATION NOTE #2 ON SHEET
 A-2. SEE CHAPTER 19 FBC 2001 FOR PROPER
 ACI REFERENCE.
  
 13- REVISE CONNECTORS SPECIFIED ON
 DETAIL 2/A-9. "SEMCO" IS OUT OF
 BUSINESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-07 Cont ID  
Sent By dpalmer Date 2005-11-07 Time 17:12 Rev Time 0.33
Received By dpalmer Date 2005-11-07 Time 17:03 Sent To  
Notes
2005-11-07 00:00:00REDLINED GROUNDING ELECTRODE CONDUCTOR,
 MIN #2, 250.66,31.15B6, SHOWS #1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-17 Cont ID  
Sent By btrobaug Date 2005-02-17 Time 11:43 Rev Time 0.50
Received By btrobaug Date 2005-02-17 Time 11:05 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 15:07 Rev Time 0.50
Received By btrobaug Date 2005-01-07 Time 15:03 Sent To M
Notes
2005-01-07 00:00:00 
  
 .PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2 AT 60 AMPS IS TOO LARGE TO PROTECT A
 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30
 AMP OCP). ALSO 60 AMP OCP SHOWN INTHE
 MAIN PANEL SEEM TOOLARGE FOR THE
 CONDENSING UNIT. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 3} IF NOTE #15 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 4} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
 5} A RECEPTACLE NEEDS TO BE ADDED TO
 THE
 MASTER BEDROOM TO COMPLY WITH
 210.52(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 10:27 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 10:27 Sent To B
Notes
2005-10-22 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-17 Cont ID  
Sent By adarroug Date 2005-10-17 Time 16:38 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 16:38 Sent To E
Notes
2005-10-17 00:00:00TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-25 Cont ID  
Sent By adarroug Date 2005-04-25 Time 10:29 Rev Time 0.00
Received By adarroug Date 2005-04-25 Time 10:29 Sent To B
Notes
2005-04-25 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 09:23 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 09:23 Sent To E
Notes
2005-02-15 00:00:00TO BTROBAUG DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 07:34 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 07:34 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 10:52 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 10:52 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By prafter Date 2005-01-11 Time 16:19 Rev Time 0.45
Received By prafter Date 2005-01-11 Time 16:19 Sent To B
Notes
2005-01-11 00:00:00ON A/C PLANS.
 PAT RAFTER561/805/6725 OR 805/6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By jleech Date 2005-01-10 Time 18:11 Rev Time 0.33
Received By jleech Date 2005-01-10 Time 18:11 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 17:58 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 17:58 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK