Plan Review Details - Permit 04121878
Plan Review Stops For Permit 04121878
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-27 Cont ID  
Sent By rmcdouga Date 2005-09-27 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2005-09-27 Time 12:33 Sent To  
Notes
2005-09-27 00:00:00PROVISO
  
 1) STORM PANEL REVISION INDICATES THAT
 IMPACT RATED WINDOWS AND DOORS WILL BE
 INSTALLED IN ALL BUT TWO OPENINGS.
 PRODUCT APPROVALS SUBMITTED WITH THE
 BUILDING PERMIT ARE FOR NON-IMPACT
 GLAZING. SUBMIT NEW PRODUCT APPROVALS
 FOR IMPACT GLAZING FOR ALL OPENINGS AS
 REVISIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-02 Cont ID  
Sent By rmcdouga Date 2005-03-02 Time 15:53 Rev Time 0.00
Received By rmcdouga Date 2005-03-02 Time 15:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-18 Cont ID  
Sent By rmcdouga Date 2005-01-18 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2005-01-18 Time 11:22 Sent To  
Notes
2005-01-18 00:00:00DENIED
  
 1) NO OPENINGS ARE ALLOWED IN THE WALLS
 ON THE ZERO LOT LINE SIDE PER FBC TABLE
 600. REMOVE THE GARAGE VENT AT ZERO LOT
 SIDE ON SHEET A3.
  
 2) SPECIFY ONE HOUR FIRE RATED GLASS
 BLOCK AT ZERO LOT LINE ON FLOOR PLAN.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 4) THE GLASS BLOCK DETAIL ON A9
 INCORRECTLY REFERENCES ASCE 7-88. THE
 CORRECT REFERENCE IS ASCE 7-98.
  
 5) CHAPTER 11 OF THE 2001 FBC REQUIRES
 AT LEAST ONE FULL BATHROOM WITH A DOOR
 THAT HAS A 29" CLEAR OPENING.
  
 6) DETAIL 2 ON A9 SPECIFIES "SEMCO"
 TRUSS CONNECTORS. SEMCO IS NO LONGER IN
 BUSINESS AND DOES NOT HAVE STATE PRODUCT
 APPROVAL.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE BBQ AND
 PREFAB FIREPLACE.
  
 8) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALCULATION FORM PER FBC
 CHAPTER 13.
  
 9) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS HAS AN
 EXTRA WINDOW THAT IS NOT SHOWN ON THE
 PLANS. THE SINGLE FRENCH DOOR IS SHOWN
 AS A DOUBLE DOOR ON THE KEY PLAN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-08-26 Cont ID  
Sent By dpalmer Date 2005-08-26 Time 18:56 Rev Time 0.33
Received By dpalmer Date 2005-08-26 Time 18:43 Sent To  
Notes
2005-08-26 00:00:00***** REDLINED *****
  
 1) MISSING THE REQUIRED DEDICATED
 BATH(S) CIRCUIT(S). MUST BE 20A, #12,
 210.52D,210.11C3

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 05:59 Rev Time 0.25
Received By dpalmer Date 2005-05-18 Time 05:59 Sent To  
Notes
2005-05-18 00:00:00************ UNSAT ************
  
 **PLEASE SEE PLANS AND RISER DIAGRAM
 HAVE COMPLETELY CHANGED FROM ORIG PLANS.
  
 1)NOTE: PLEASE SEE NEW RISER NOW
 INDICATES THREE ELECTRICAL PANELS,
 HOWEVER NO OCP IS SHOWN ON RISER FOR NEW
 PANELS.
 IS THERE NOW A PANEL SCHEDULE FOR NEW
 METER/MAIN COMBO.
 215.5,240.4, 310.16 ETC.
  
 2)NOTE: PLEASE SEE ONLY ONE PANEL IS
 SHOWN ON ELECTRICAL PLANS AND RISER
 SHOWS 3.
 215.5
  
 3)NOTE: PLEASE SEE NUMEROUS ITEMS ON
 PANEL SCHEDULE INDICATE 20A OCP ON #14
 AWG. PLEASE SEE 310.16,240.4.
  
 4)NOTE:
  
 5)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL
 TUB IS NOW ADDED TO PANEL SCHEDULE,
 HOWEVER NO ELECTRICAL IS SHOWN ON PLANS.
 PLEASE SEE A GFI IS SHOWN, HOWEVER THIS
 APPEARS TO BE FOR LAV.?
 PLEASE ALSO SEE 680.71 FOR REQUIRED
 INDICATION OF GFI PROTECTION.
  
 6)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THE # OF
 RECESSED LTS INDICATED ON PANEL
 SCHEDULE/LOAD CALCULATIONS.
 215.5
  
 7)NOTE: PLEASE SEE MISSING GFI IN BATH
 RM REQUIRED PER 210.52D.
  
 8)NOTE: PLEASE SEE MISSING RECEPT
 REQUIED ALONG KITCHEN COUNTERSPACE.
 210.52C1
  
 PLEASE SEE MANY OF THESE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS ON PLANS AT
 LOCATIONS OF NOTES.
  
 *** PLEASE BE SURE ALL PLANS ARE SIGNED
 BY THE ARCHITECT OF RECORD.
 FS 481.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-28 Cont ID  
Sent By btrobaug Date 2005-02-28 Time 10:52 Rev Time 0.50
Received By btrobaug Date 2005-02-28 Time 10:44 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 15:47 Rev Time 0.50
Received By btrobaug Date 2005-01-07 Time 15:45 Sent To M
Notes
2005-01-07 00:00:00 
  
 .PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2 AT 60 AMPS IS TOO LARGE TO PROTECT A
 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30
 AMP OCP). ALSO 60 AMP OCP SHOWN INTHE
 MAIN PANEL SEEM TOOLARGE FOR THE
 CONDENSING UNIT. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 3} IF NOTE #14 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 4} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-27 Cont ID  
Sent By adarroug Date 2005-09-27 Time 09:13 Rev Time 0.00
Received By adarroug Date 2005-09-27 Time 09:13 Sent To B
Notes
2005-09-27 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 18:38 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 18:38 Sent To E
Notes
2005-08-23 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 16:50 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 16:50 Sent To E
Notes
2005-04-15 00:00:00TO "TROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-24 Cont ID  
Sent By adarroug Date 2005-02-24 Time 12:59 Rev Time 0.00
Received By adarroug Date 2005-02-24 Time 12:59 Sent To E
Notes
2005-02-24 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mmclean Date 2005-02-23 Time 11:12 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 07:43 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 12:05 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 12:05 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 15:48 Rev Time 0.45
Received By prafter Date 2005-01-11 Time 14:00 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-01 Cont ID  
Sent By kstevens Date 2005-03-01 Time 18:21 Rev Time 0.45
Received By kstevens Date 2005-03-01 Time 18:21 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-11 Cont ID  
Sent By jleech Date 2005-01-11 Time 11:41 Rev Time 0.50
Received By jleech Date 2005-01-11 Time 11:41 Sent To M
Notes
2005-01-11 00:00:00DENIED;
 1.TUB IN BATH 3 IS NOT VENTED. WET VENT
 SHALL BE UPSTREAM OF THE WATER CLOSET.
 2.PLEASE CHANGE PLUMBING NOTE 3 TO
 COMPLY WITH FBC PLUMBING TABLE 704.1.
 3.PLEASE DELETE PLUMBING NOTE 6. A/C
 CONDENSATE IS NOT PERMIITED TO DRAIN
 INTO THE SEWER SYSTEM. THIS WATER
 DOESNOT NEED TO BE TREATED.
 4.LAUNDRY TRAY TO DRAIN ABOVE CLOTHS
 WASHER AND THE C.O. SHALL BE 58" OFF
 FINISH FLOOR.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-23 Cont ID  
Sent By mmclean Date 2005-01-05 Time 18:22 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 18:22 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK