Plan Review Details - Permit 04121866
Plan Review Stops For Permit 04121866
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-11-10 Cont ID  
Sent By jgomez Date 2005-11-10 Time 19:59 Rev Time 0.50
Received By jgomez Date 2005-11-10 Time 19:59 Sent To PC
Notes
2005-11-10 00:00:00STORM SHUTTERS REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-09-23 Cont ID  
Sent By jgomez Date 2005-09-23 Time 17:44 Rev Time 0.33
Received By jgomez Date 2005-09-23 Time 17:44 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-08-24 Cont ID  
Sent By jgomez Date 2005-08-24 Time 16:06 Rev Time 0.50
Received By jgomez Date 2005-08-24 Time 16:05 Sent To E
Notes
2005-08-24 00:00:00SUBMITTAL BUILDING REVIEW CHECKLIST:
  
 1- REVISE ANCHOR FASTENERS FOR THD210.
 SEE TECHNICAL BULLETIN FOR TESTED
 FASTENERS.
  
 2- SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-29 Cont ID  
Sent By jgomez Date 2005-04-29 Time 11:25 Rev Time 0.00
Received By jgomez Date 2005-04-29 Time 11:25 Sent To PC
Notes
2005-04-29 00:00:00BUILDING REVIEW PROVISO:
 NOTE: PROVIDE INFORMATION PRIOR TO
 INSTALLATION OR CONSTRUCTION TO AVOID
 DELAYS OR CONFLICTS.
  
 1- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR FRENCH DOORS WITH SIDELITES
 ASSEMBLY AS SHOWN ON PLANS. SIZE OF
 DOORS SUBMITTED IS NOT THE SAME SIZE AS
 SHOWN ON PLANS.
  
 2- DESIGN PARAMETERS: CLARIFY WHERE IS
 THE BASIC VELOCITY PRESSURE TAKEN FROM.
 THERE IS NOT SUCH INFORMATION GIVEN ON
 CHAPTER 16 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-10 Cont ID  
Sent By jgomez Date 2005-03-10 Time 15:27 Rev Time 2.50
Received By jgomez Date 2005-03-10 Time 15:27 Sent To PC
Notes
2005-03-10 00:00:00BUILDING REVIEW CHECKLIST:
 1- FLOOR PLAN AND REAR ELEVATION DON'T
 MATCH. REVISE TYPE OF DOORS USED. AND
 SPECIFYDESIGN PRESSURES FOR FRENCH
 DOORS.
  
 2- STORM SHUTTERS:
 A) OPENING #11 EXCEEDS THE MAX. PANEL
 SPAN ALLOWED. SEE ENGINEERED DRAWINGS.
 B) CLEARLY MARK ON ENGINEERED DRAWINGS
 SPECIFIC ANCHOR AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES, EDGE
 DISTANCE, CONNECTION TYPE, PANEL SPAN
 AND STRUCTURE TO BE ATTACHED TO (MASONRY
 OR 2500PSI CONCRETE).
 **NOTE: SEE PLANS AND CHECK WHEN
 OPENINGS ARE END OR INTERIOR ZONES.
  
 2- UPDATE/REVISE TRUSS ANCHOR SCHEDULE
 AND CALCULATIONS IF CAPACITY OF ANCHORS
 AND NAIL TYPE AND SPACING IS DIFFERENT
 FROM THAT PUBLISHED IN THE FLORIDA
 PRODUCT APPROVAL FOR SUCH CONNECTOR.
 **NOTE: ENGINEER SHALL CONSIDER SECTION
 1609.4.3 FBC 2001 WHEN PERFORMING
 CALCULATIONS.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ENTRY DOORS (SOLID OR WITH IMPACT
 GLAZING BECAUSE USED FOR EMERGENCY
 EGRESS. SEC. 1005.4.5 FBC 2001.).
 SEE SIZE AND SWING DIRECTION ON PLANS.
 **NOTE: SUBMITT THE EXACT SAME DRAWINGS
 THAT WERE SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL.
  
 B) CASEMENT WINDOWS ASSEMBLY AS SHOWN ON
 BEDROOM #2. SEE PLANS.
  
 C) FRENCH DOORS. SEE SIZE AND SWING
 DIRECTION SHOWN ON PLANS. PROVIDE DWGS
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
  
 D) FRENCH DOORS WITH SIDELITES AS SHOWN
 ON PLANS. PROVIDE EXACT SAME DRAWINGS
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
  
 E) USP TRUSS ANCHORS SPECIFIED ON PLANS
 AND TRUSS ANCHOR SCHEDULE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-26 Cont ID  
Sent By jgomez Date 2005-01-26 Time 14:53 Rev Time 2.00
Received By jgomez Date 2005-01-26 Time 14:52 Sent To PC
Notes
2005-01-26 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE COMPLETE BATHROOM WITH A DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING. SEC.
 11-11 FBC 2001.
  
 2- SPECIFY ROOF TILE FASTENING. SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 3- UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE & NUMBER OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER TO COMPLY WITH SECTION
 1609.4.3 FBC 2001.
  
 4- A)TITLE BLOCK NEEDS NAME OF ARCHITECT
 SEALING PLANS. CHAPTER 61G1-16004 FAC.
 B) STATE REGISTRATION NUMBER IS
 INCORRECT. REVISE AS REQUIRED.
  
 5- PROVIDE DETAIL/SPECS FOR INSTALLATION
 OF CEILING AT ENTRY AND REAR PORCHES.
 SPECIFY FASTENERS AND SPACING. SEE ASTM
 C926 AND ASTM C1063. SEC. 2504.2 FBC.
  
 6- ENERGY CALCULATIONS: OWNER/AGENT TO
 SIGN AND DATE FORM.
  
 7-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) ENTRY DOORS.
 B) FRENCH DOORS. SEE SIZES ON PLANS.
 C) CONCRETE LINTELS: NEED DADE COUNTY
 NOA THAT MATCHES ONE SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
 D) FIXED WINDOWS THAT MEET THE DESIGN
 PRESSURES CALCULATED ON PLANS. SEE PLANS
 FOR SIZES AND DESIGN PRESSURES.
 E) ARABESQUE WINDOW AS SHOWN ON PLANS.
  
 8- A) PROVIDE COMPLETE UL LISTING AND
 SPECS FOR FIREPLACE. SEC. 2806 FBC.
 B) PROVIDE COMPLETE APPROVED BBQ SPECS.
 SEC. 2808 FBC 2001.
  
 9- STORM SHUTTERS: A) KEY PLAN DOESN'T
 MATCH PLANS.
 B) REVISE MINIMUM PANEL SIZE. SEE
 ENGINEERED DRAWINGS FOR LIMITATIONS.
 C) REVISE INTERIOR AND END ZONES. SEE
 PLANS FOR LOCATION.
 D) REVISE DESIGN PRESSURES. SEE PLANS.
  
 10- PROVIDE COMPLETE FRAMING DETAILS FOR
 ARABESQUE WINDOW. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 11- OWES $866.23 FOR UPDATED VALUATION.
  
 12- REVISE FOUNDATION NOTE #2 ON SHEET
 A-2. SEE CHAPTER 19 FBC 2001 FOR PROPER
 ACI REFERENCE.
  
 13- REVISE DETAIL CONNECTORS SHOWN ON
 DETAIL 2/A-9. "SEMCO" IS OUT OF
 BUSINESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-12-14 Cont ID  
Sent By btrobaug Date 2005-12-14 Time 11:21 Rev Time 0.50
Received By btrobaug Date 2005-12-14 Time 11:20 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-11-22 Cont ID  
Sent By dpalmer Date 2005-11-22 Time 13:56 Rev Time 0.33
Received By dpalmer Date 2005-11-22 Time 13:20 Sent To  
Notes
2005-11-22 00:00:00**** UNSAT ****
  
  
 1)NOTE: PLEASE SEE 250.66,310.15B6 FOR
 MIN SIZE OF THE GROUNDING ELECTRODE
 CONDUCTOR.
 ** PLEASE SEE SERVICE NOW INCREASED FROM
 300A TO 400A'S.
  
 2)NOTE: PLEASE SEE AHU#2 ON PANEL "B"
 WHICH SHOWS A 5KW UNIT WITH 60A OCP.
 PLEASE ALSO SEE #6 SHOWN.
 PLEAS KNOW, THE #6 IS OK, BUT NOT
 REQUIRED. IF SHOWN AS #6, THEN IT WILL
 BE REQUIRED. PLEASE SEE THE OCP IS TOO
 LARGE FOR A 5KWAHU. (MAX
 150%/MANUFACTURES NAMEPLATE).
  
 3)NOTE: PLEASE SEE DISH/DISP SHOWN AS
 2-POLE, HOWEVER PANEL SCHEDULE ONLY
 SHOWS A SINGLE SPACE/CIRCUIT ON
 SCHEDULE.215.5
 PLEASE CORRELATE.
  
 4)NOTE: PLEASE SEE MICRO,FRIG,DISH/DISP
 LOADS ON PANEL SCHEDULE AND NEUTRAL
 LOADS NEED TO CORRELATE.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PELASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-08-24 Cont ID  
Sent By dpalmer Date 2005-08-24 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2005-08-24 Time 17:06 Sent To  
Notes
2005-08-24 00:00:00REDLINED GROUNDING ELECTRODE PER 250.66,
 310.15B6

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-18 Cont ID  
Sent By btrobaug Date 2005-04-18 Time 12:31 Rev Time 0.50
Received By btrobaug Date 2005-04-18 Time 11:55 Sent To B
Notes
2005-04-18 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE CORRECT AND RESUBMIT THE
 FOLLOWING CORRECTIONS FOR REVIEW PRIOR
 TO CALLING A ROUGH ELECTRICAL
 INSPECTION.
  
 1} PUT ALL PANELS ON THE PLAN AT CORRECT
 LOCATION.
  
 2} CIRCUITS 12,13 PANEL "A" AND
 12,13,14, AND 15, PANEL "B", NEED TO
 HAVE #12CU FOR THE OCP 20 AMP BREAKER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-17 Cont ID  
Sent By btrobaug Date 2005-02-17 Time 12:39 Rev Time 0.50
Received By btrobaug Date 2005-02-17 Time 12:22 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 14:27 Rev Time 0.00
Received By btrobaug Date 2005-01-07 Time 14:19 Sent To M
Notes
2005-01-07 00:00:00 
 .PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2 AT 60 AMPS IS TOO LARGE TO PROTECT A
 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30
 AMP OCP). ALSO 60 AMP OCP SHOWN INTHE
 MAIN PANEL SEEM TOOLARGE FOR THE
 CONDENSING UNIT. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 3} IF NOTE #15 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 4} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
 5} A RECEPTACLE NEEDS TO BE ADDED TO
 THE MASTER BEDROOM TO COMPLY WITH
 210.52(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-11-17 Cont ID  
Sent By adarroug Date 2005-11-17 Time 16:26 Rev Time 0.00
Received By adarroug Date 2005-11-17 Time 16:26 Sent To E
Notes
2005-11-17 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 10:37 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 10:37 Sent To B
Notes
2005-10-22 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-06 Cont ID  
Sent By adarroug Date 2005-09-06 Time 15:22 Rev Time 0.00
Received By adarroug Date 2005-09-06 Time 15:22 Sent To B
Notes
2005-09-06 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 11:00 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 11:00 Sent To B
Notes
2005-07-05 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 16:54 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 16:54 Sent To E
Notes
2005-04-15 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 08:44 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 08:44 Sent To E
Notes
2005-02-15 00:00:00TO BTROBAUG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 07:54 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 07:54 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 12:00 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 12:00 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By prafter Date 2005-01-11 Time 13:06 Rev Time 0.00
Received By prafter Date 2005-01-11 Time 13:40 Sent To B
Notes
2005-01-11 00:00:00NO A/C PLANS.
 PAT RAFTER 561/805/6725 OR 8056719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-26 Cont ID  
Sent By jleech Date 2005-09-26 Time 07:32 Rev Time 0.33
Received By jleech Date 2005-09-26 Time 07:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By jleech Date 2005-01-10 Time 18:45 Rev Time 0.33
Received By jleech Date 2005-01-10 Time 18:45 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 17:32 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 17:32 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK