Plan Review Details - Permit 04121860
Plan Review Stops For Permit 04121860
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-06-03 Cont ID  
Sent By jgomez Date 2005-06-03 Time 16:19 Rev Time 0.25
Received By jgomez Date 2005-06-03 Time 16:19 Sent To PC
Notes
2005-06-03 00:00:00HEXAGONAL WINDOW PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-05-26 Cont ID  
Sent By jgomez Date 2005-05-26 Time 10:58 Rev Time 0.25
Received By jgomez Date 2005-05-26 Time 10:58 Sent To PC
Notes
2005-05-26 00:00:00FRENCH DOORS WITH SIDELITES PRODUCT
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-05-25 Cont ID  
Sent By jgomez Date 2005-05-25 Time 13:10 Rev Time 0.25
Received By jgomez Date 2005-05-25 Time 12:03 Sent To PC
Notes
2005-05-25 00:00:00REVISION CHECKLIST:
  
 1- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR HEXAGONAL WINDOW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-04-25 Cont ID  
Sent By jgomez Date 2005-04-25 Time 15:03 Rev Time 1.00
Received By jgomez Date 2005-04-25 Time 15:03 Sent To PC
Notes
2005-04-25 00:00:00BUILDING SUBMITTAL CHECKLIST:
  
 1- NEED FLORIDA/LOCAL PRODUCT APPROVAL
 FOR FRENCH DOORS WITH SIDELITES ASSEMBLY
 AS SHOWN ON PLANS.
 NEED 8-0" DOORS WITH OUTSIDE SWING.
 (PRODUCT APPROVAL SUBMITTED IS FOR 6'8"
 DOORS).
  
 2- NEED TO APPLY FOR SEPARATE PERMIT FOR
 STORM SHUTTERS AS AGREED UPON ON PROVISO
 DATED 3-29-05.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-03-29 Cont ID  
Sent By jgomez Date 2005-03-29 Time 12:42 Rev Time 2.00
Received By jgomez Date 2005-03-29 Time 12:42 Sent To  
Notes
2005-03-29 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 PROVIDE THE FOLLOWING INFORMATION PRIOR
 TO INSTALLATION OR CONSTRUCTION TO AVOID
 CONFLICTS OR DELAYS.
 1- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1..1 CITY AMENDMENTS TO FBC.
  
 2- UPDATE TRUSS ANCHOR SCHEDULE. SEE
 LATEST CATALOGUE. PROVIDE COMPLETE
 ENGINEERING CALCULATIONS THAT COMPLY
 WITH SEC. 1609.4.3 FBC 2001 IF TYPE AND
 NUMBER OF FASTENERS DIFFER FROM THOSE
 TESTED AND PUBLISHED BY MANUFACTURER.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) FRENCH DOORS WITH
 SIDELITES AS SHOWN ON PLANS.
 B)"OUTSWING" FRENCH DOORS AS SHOWN ON
 PLANS. PRODUCT APPROVAL SUBMITTED IS FOR
 "INSWING" FRENCH DOORS.
 C) USP OR SIMPSON TRUSS CONNECTORS USED.
  
 4- PROVIDE COMPLETE & CORRECT INFO. FOR
 STORM SHUTTERS UNDER A SEPARATE PERMIT.
 CHECK SIZE AND NUMBER OF OPENINGS WITH
 PLANS AND CLEARLY INDICATE ON SHUTTER
 DWGS SPECIFIC MOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING TO BE USED.
  
 5- PLANS CALL FOR FLAT CEMENT TILE.
 PRODUCT APPROVAL SUBMITTED WAS FOR "S"
 TILE. CLARIFY/REVISE AS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-28 Cont ID  
Sent By jgomez Date 2005-01-28 Time 09:24 Rev Time 2.00
Received By jgomez Date 2005-01-28 Time 09:21 Sent To PC
Notes
2005-01-28 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE COMPLETE BATHROOM WITH DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING.
 SECTION 11-11 FBC 2001.
  
 2- SPECIFY ROOF TILE FASTENING. SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 3- UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE AND NUMBER OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER TO COMPLY WITH SECTION
 1609.4.3 FBC 2001.
  
 4- A) NEED NAME OF ARCHITECT SEALING THE
 PLANS. CHAPTER 61G1-16004 F.A.C.
 B) STATE REGISTRATION NUMBER IS
 INCORRECT. REVISE AS REQUIRED.
  
 5- PROVIDE DETAIL/SPECS FOR INSTALLATION
 OF CEILING AT ENTRY AND REAR PORCHES.
 SPECIFY FASTENERS AND SPACING. SEE ASTM
 C926 AND ASTM C1063. SEC. 2504.2 FBC
  
 6- OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS.
  
 7- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ENTRY DOORS.
 B) FRENCH DOORS.
 C) CONCRETE LINTELS: PROVIDE COPIES OF
 SAME DADE COUNTY NOA SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
 D) FIXED WINDOWS THAT MEET THE DESIGN
 PRESSURES AND SIZES SHOWN ON PLANS.
 E) ARABESQUE WINDOW. SEE PLANS.
  
 8- A) PROVIDE COMPLETE UL LISTING AND
 SPECS FOR FIREPLACE. SEC. 2806 FBC.
 B) PROVIDE COMPLETE APPROVED SPECS FOR
 BBQ. SECTION 2808 FBC 2001.
  
 9-STORM SHUTTERS: A) KEY PLAN DOESN'T
 MATCH PLANS.
 B) REVISE MIN. PANEL SIZE. SEE
 ENGINEERED DRAWINGS.
 C) REVISE END AND INTERIOR ZONES. SEE
 PLANS.
 D) REVISE DESIGN PRESSURES. SEE PLANS.
  
 10- PROVIDE COMPLETE FRAMING DETAILS FOR
 ARABESQUE WINDOW. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 11- OWES $866.23 FOR UPDATED VALUATION.
  
 12- REVISE FOUNDATION NOTE #2 ON SHEET
 A-2. SEE CHAPTER 19 FBC 2001 FOR PROPER
 ACI REFERENCE.
  
 13- REVISE CONNECTORS SPECIFIED ON
 DETAIL 2/A9. "SEMCO" IS OUT OF
 BUSINESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-11-07 Cont ID  
Sent By dpalmer Date 2005-11-07 Time 17:41 Rev Time 0.33
Received By dpalmer Date 2005-11-07 Time 17:41 Sent To  
Notes
2005-11-07 00:00:00REDLINED GROUNDING ELECTRODE CONDUCTOR,
 MIN #2, 250.66,31.15B6, SHOWS #1

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 06:18 Rev Time 0.25
Received By dpalmer Date 2005-05-18 Time 06:18 Sent To  
Notes
2005-05-18 00:00:00************ UNSAT ************
  
 **PLEASE SEE PLANS AND RISER DIAGRAM
 HAVE COMPLETELY CHANGED FROM ORIG PLANS.
  
 1)NOTE: PLEASE SEE NEW RISER NOW
 INDICATES THREE ELECTRICAL PANELS,
 HOWEVER NO OCP IS SHOWN ON RISER FOR NEW
 PANELS.
 IS THERE NOW A PANEL SCHEDULE FOR NEW
 METER/MAIN COMBO.
 215.5,240.4, 310.16 ETC.
  
 2)NOTE: PLEASE SEE ONLY ONE PANEL IS
 SHOWN ON ELECTRICAL PLANS AND RISER
 SHOWS 3.
 215.5
  
 3)NOTE: PLEASE SEE NUMEROUS ITEMS ON
 PANEL SCHEDULE INDICATE 20A OCP ON #14
 AWG. PLEASE SEE 310.16,240.4.
  
 4)NOTE:
  
 5)NOTE: PLEASE SEE A JACUZZI/WHIRLPOOL
 TUB IS NOW ADDED TO PANEL SCHEDULE,
 HOWEVER NO ELECTRICAL IS SHOWN ON PLANS.
 PLEASE ALSO SEE 680.71 FOR REQUIRED
 INDICATION OF GFI PROTECTION.
  
 6)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THE # OF
 RECESSED LTS INDICATED ON PANEL
 SCHEDULE/LOAD CALCULATIONS.
 PLEASE SEE SOME MODELS SHOW THESE AS
 "OPT". EACH PLAN MUST REFLECT THE ACTUAL
 INSTALLATION PER WHICH ARE INSTALLED OR
 NOT INSTALLED.
 215.5
  
 7)NOTE:
  
 8)NOTE:
  
 PLEASE SEE MANY OF THESE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS ON PLANS AT
 LOCATIONS OF NOTES.
  
 *** PLEASE BE SURE ALL PLANS ARE SIGNED
 BY THE ARCHITECT OF RECORD.
 FS 481.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-03-14 Cont ID  
Sent By btrobaug Date 2005-03-14 Time 16:25 Rev Time 0.50
Received By btrobaug Date 2005-03-14 Time 13:11 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 08:04 Rev Time 0.75
Received By btrobaug Date 2005-01-06 Time 18:54 Sent To M
Notes
2005-01-06 00:00:00 
 .PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2 AT 60 AMPS IS TOO LARGE TO PROTECT A
 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30
 AMP OCP). ALSO 60 AMP OCP SHOWN INTHE
 MAIN PANEL SEEM TOOLARGE FOR THE
 CONDENSING UNIT. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 3} IF NOTE #15 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 4} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-10-17 Cont ID  
Sent By adarroug Date 2005-10-17 Time 16:42 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 16:42 Sent To E
Notes
2005-10-17 00:00:00TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 14:34 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 14:34 Sent To B
Notes
2005-05-16 00:00:00TO "JGOMEZ" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-06 Cont ID  
Sent By adarroug Date 2005-05-06 Time 13:26 Rev Time 0.00
Received By adarroug Date 2005-05-06 Time 13:26 Sent To B
Notes
2005-05-06 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 09:52 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 09:52 Sent To B
Notes
2005-04-18 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 16:49 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 16:49 Sent To E
Notes
2005-04-15 00:00:00TO "BTOBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-07 Cont ID  
Sent By adarroug Date 2005-03-07 Time 16:03 Rev Time 0.00
Received By adarroug Date 2005-03-07 Time 16:03 Sent To E
Notes
2005-03-07 00:00:00TO "BTROBAUG/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 07:30 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 07:30 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 11:57 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 11:57 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By prafter Date 2005-01-11 Time 15:17 Rev Time 0.45
Received By prafter Date 2005-01-11 Time 15:17 Sent To B
Notes
2005-01-11 00:00:00NO A/C PLANS.
 PAT RAFTER 561/8056725 OR 8056719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By jleech Date 2005-01-10 Time 17:12 Rev Time 0.33
Received By jleech Date 2005-01-10 Time 17:12 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 18:15 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 18:15 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK