Plan Review Details - Permit 04121854
Plan Review Stops For Permit 04121854
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-08-17 Cont ID  
Sent By rmcdouga Date 2005-08-17 Time 07:15 Rev Time 0.00
Received By rmcdouga Date 2005-08-17 Time 07:15 Sent To  
Notes
2005-08-17 00:00:00REVISED SHEETS A2,A3 AND A6 ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-07-20 Cont ID  
Sent By rmcdouga Date 2005-07-20 Time 13:02 Rev Time 0.00
Received By rmcdouga Date 2005-07-20 Time 13:02 Sent To  
Notes
2005-07-20 00:00:00REVISED LOCATION OF STRUCTURE ON LOT IS
 OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-06-29 Cont ID  
Sent By rmcdouga Date 2005-06-29 Time 12:26 Rev Time 0.00
Received By rmcdouga Date 2005-06-29 Time 12:26 Sent To P
Notes
2005-06-29 00:00:00PROVISO
  
 1) REVISE THE USP ANCHOR SCHEDULE ON
 SHEET A6 SO THAT THE NUMBER AND SIZE OF
 MASONRY FASTENERS IS THE SAME AS
 SPECIFIED ON THE USP TECHNICAL
 BULLETINS.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE BUILT IN
 BBQ. INCLUDE INSTALLATION INSTRUCTIONS,
 CLEARANCES, ETC.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE
 12'X 8' SLIDING GLASS DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-06-06 Cont ID  
Sent By jgomez Date 2005-06-06 Time 17:49 Rev Time 2.00
Received By jgomez Date 2005-06-06 Time 17:49 Sent To E
Notes
2005-06-06 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- NOTE ON DRAWING A-3 CALLS FOR IMPACT
 GLAZING IN DOORS AND WINDOWS. SHUTTERS
 INSTALLATION SCHEDULE SHOWSMISSILE
 IMPACT GLAZING IN DOORS AND WINDOWS.
 PRODUCT APPROVALS SUBMITTED FOR DOORS
 AND WINDOWS ARE FOR NON IMPACT GLAZING.
 NEED TO CLARIFY WHICH METHOD OF GLASS
 PROTECTION IS GOING TO BE USED AND
 PROVIDE COMPLETE INFORMATION FOR EITHER
 METHOD.
  
 2- FRONT ELEVATION TO SHOW EXACT TYPE OF
 ENTRY DOORS FOR WHICH PRODUCT APPROVAL
 WILL BE SUBMITTED.
  
  
 3- REVISED ENERGY CALCULATIONS WERE
 REQUIRED BECAUSE A/C AREA WAS INCREASED.
 REVISED ENERGY CALCULATIONS WERE NOT
 SUBMITTED.
  
 4- TRUSS ANCHOR SCHEDULE: REVISE
 CONNECTOR THD210 AND THD210-2. THIS IS A
 WOOD TO WOOD CONNECTOR. NEED A MASONRY
 TO WOOD CONNECTOR. SEE CATALOGUE FOR
 PROPER MASONRY CONNECTOR.
  
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR: A) FRENCH DOORS THAT MATCH
 SIZE OF DOORS SHOWN ON PLANS. PRODUCT
 APPROVAL SUBMITTED IS FOR 6'-8" HIGH
 DOORS. NEED 8'-0" HIGH DOORS.
  
 B) CASEMENT WINDOWS: DADE COUNTY NOA
 REPORT DOESN'T MATCH REPORT SUBMITTED
 FOR FLORIDA PRODUCT APPROVAL. RESUBMIT
 CORRECT DADE COUNTY NOA REPORT.
  
 6- SPECIFICATIONS FOR BBQ WERE FORWARDED
 TO BUILDING OFFICIAL FOR APPROVAL. BLDG
 OFFICIAL IS OUT THIS WEEK.
 NOTE: THERE ARE COMPANIES WHO HAVE
 DESIGNED BBQ TO BE SPECIFICALLY
 INSTALLED IN PORCHES OR LANAIS AND THE
 PACKAGE INCLUDES EXHAUST HOOD.
 ADDITIONAL INFORMATION OR TESTING MAY BE
 REQUIRED BY THE BUILDING OFFICIAL TO
 SUPPORT STATEMENT FROM ALFRESCO GRILLS
 LETTER. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 7- DESIGN PARAMETERS ON SHEET A-3:
 CLARIFY WHERE IS THE BASIC VELOCITY
 PRESSURE TAKEN FROM. THERE ARE NOT
 TABLES REFERENCED IN CHAPTER 16 FBC
 2001. (THIS WAS THE STANDARD BUILDING
 CODE TABLE NOT THE FBC). SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 8- EXTERIOR ELEVATIONS CALL FOR FLAT
 CEMENT TILE. PRODUCT APPROVAL SUBMITTED
 IS FOR "S" TILE. CLARIFY/REVISE AS REQ'D
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-11 Cont ID  
Sent By jgomez Date 2005-03-11 Time 17:55 Rev Time 3.00
Received By jgomez Date 2005-03-11 Time 10:59 Sent To PC
Notes
2005-03-10 00:00:00BUILDING REVIEW CHECKLIST:
 1- MISSING SHEET A-2.
  
 2- A/C AREA WAS INCREASED. NEED TO BRING
 DWGS TO THE PALM BEACH COUNTY TO UPDATE
 INFORMATION AND RE-STAMP DRAWINGS AND
 PAID RECEIPT.
  
 3- PLANS WERE REVISED ADDING A/C AREA.
 REVISE THE ENERGY CALCULATIONS
 ACCORDINGLY.
  
 4- UPDATE/REVISE TRUSS ANCHOR SCHEDULE
 TO MATCH CAPACITY AND TYPE & NUMBER OF
 NAILS PUBLISHED ON THE FLORIDA PRODUCT
 APPROVAL. OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS AND CALCULATIONS
 THAT COMPLY WITH SECTION 1609.4.3 FBC
 WHERE THE STRESS INCREASE IS NO ALLOWED.
  
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ENTRY DOORS. VERIFY SIZE AND SWING
 DIRECTION ON PLANS. ALSO, NEED TO BE
 SOLID OR HAVE IMPACT GLASS IF THIS IS
 THE DOOR USED FOR EMERGENCY EGRESS AS
 REQ'D BY SEC. 1005.4.5 FBC 2001.
  
 B) FRENCH DOOR. SEE SIZES ON PLANS.
  
 5- SHEET A-3 NOTE CALLS FOR IMPACT
 GLAZING IN ALL DOORS AND WINDOWS. BUT,
 STORM SHUTTERS INFORMATION IS SUBMITTED.
 REVISE PLANS AS REQUIRED TO MATCH
 PROTECTION OF GLASS BY SHUTTERS OR
 IMPACT GLASS IN DOORS AND WINDOWS.
  
 6- BBQ SPECS SAY THAT GRILLWAS
 DESIGNED FOR OUTDOOR USE ONLY & CANN'T
 BE INSTALLED IN THE BUILDING AND BELOW
 OVERHEAD UNPROTECTED CONSTRUCTION.
 PROVIDE CERTIFICATION FROM MANUFACTURER
 THAT BBQ GRILL WILL BE OK TO INSTALL IN
 THE PORCH. SEC. 2808 FBC 2001.
  
 7- STORM SHUTTERS: A) ENGINEER'S GENERAL
 NOTE #6 REQUIRES DRAWINGS TO BE SIGNED,
 SEALED AND DATED BY HIM.
  
 B) THERE ARE SOME PANELS THAT EXCEED
 MAX. PANEL SPAN ACCORDING TO THE DESIGN
 PRESSURES. REVISE AS REQUIRED.
  
 C) CLEARLY MARK ON ENGINEERED DRAWINGS
 ANCHOR SCHEDULE SPECIFIC ANCHOR TO BE
 USED ACCORDING TO THE EDGE DISTANCE,
 DESIGN PRESSURES, PANEL SPAN, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO
 (MASONRY OR 2500PSI CONCRETE).
  
 8- NOTICE OF COMMENCEMENT EXPIRES AFTER
 90 DAYS WITHOUT WORK. NEED RE-RECORDED
 NOTICE OF COMMENCEMENT.
  
 9- OWES $83.45 FOR INCREASED A/C AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-31 Cont ID  
Sent By jgomez Date 2005-01-31 Time 16:07 Rev Time 2.00
Received By jgomez Date 2005-01-31 Time 16:07 Sent To PC
Notes
2005-01-31 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE COMPLETE BATHROOM WITH DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING.
 SECTION 11-11 FBC 2001.
  
 2- SPECIFY ROOF TILE FASTENING. SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
  
 3- UPDATE TRUSS ANCHOR SCHEDULE.
 PROVIDE
 COMPLETE ENGINEERING CALCULATIONS FOR
 TYPE AND NUMBER OF FASTENERS THAT
 DIFFER
 FROM THOSE TESTED AND PUBLISHED BY
 MANUFACTURER TO COMPLY WITH SECTION
 1609.4.3 FBC 2001.
  
 4- A) NEED NAME OF ARCHITECT WHO IS
 SEALING THE PLANS. CHAPTER 61G1-16004
 FAC.
 B) STATE REGISTRATION NUMBER IS
 INCORRECT. REVISE AS REQUIRED.
  
 5- PROVIDE COMPLETE DETAIL/SPECS FOR
 CEILING INSTALLATION AT ENTRY AND REAR
 PORCHES. SPECIFY FASTENERS SIZE AND
 SPACING. SEE ASTM C926 AND ASTM C1063.
 SECTION 2504.2 FBC 2001.
  
 6- OWNER/AGENT TO SIGN AND DATE THE
 ENERGY CALCULATIONS.
  
 7- PROVIDE FLORIDA OR APPLY FOR LOCAL
 PRODUCT APPROVAL FOR:
 A) ENTRY DOORS.
 B) FRENCH DOORS.
 C) CONCRETE LINTELS: NEED EXACT DADE
 COUNTY NOA THAT MATCHES ONE SUBMITTED
 FOR FLORIDA LOCAL APPROVAL.
 D) FIXED WINDOWS THAT MEET THE SIZES
 AND
 DESIGN PRESSURES SHOWN ON PLANS.
 E) ARABESQUE WINDOW. SEE PLANS.
  
 8- A) PROVIDE COMPLETE UL LISTING AND
 SPECS FOR FIREPLACE. SEC. 2806 FBC
 2001.
 B) PROVIDE COMPLETE APPROVED BBQ SPECS.
 SECTION 2808 FBC 2001.
  
 9- STORM SHUTTERS: A) KEY PLAN DOESN'T
 MATCH PLANS.
 B) REVISE MIN. PANEL SIZE. SEE
 ENGINEERED DRAWINGS FOR LIMITATIONS.
 C) REVISE INTERIOR AND END ZONES. SEE
 PLANS.
 D) REVISE DESIGN PRESSURES. SEE PLANS.
  
 10- PROVIDE COMPLETE FRAMING DETAILS
 FOR
 ARABESQUE WINDOW. SECTION 104.2.1.2
 CITY
 AMENDMENTS TO FBC 2001.
  
 11- OWES $866.23 FOR UPDATED
 CALCULATION.
  
 12- REVISE FOUNDATION NOTE #2 ON SHEET
 A-2. SEE CHAPTER 19 FBC 2001 FOR PROPER
 ACI REFERENCE.
  
 13- REVISE CONNECTORS SPECIFIED ON
 DETAIL 2/A-9. "SEMCO" IS OUT OF
 BUSINESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-03-10 Cont ID  
Sent By btrobaug Date 2006-03-10 Time 07:53 Rev Time 0.50
Received By btrobaug Date 2006-03-10 Time 07:37 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-12-14 Cont ID  
Sent By btrobaug Date 2005-12-14 Time 12:42 Rev Time 0.50
Received By btrobaug Date 2005-12-14 Time 12:22 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-06-30 Cont ID  
Sent By btrobaug Date 2005-06-30 Time 07:57 Rev Time 0.50
Received By btrobaug Date 2005-06-30 Time 07:01 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-17 Cont ID  
Sent By btrobaug Date 2005-02-17 Time 11:04 Rev Time 0.50
Received By btrobaug Date 2005-02-17 Time 10:58 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By btrobaug Date 2005-01-07 Time 14:08 Rev Time 0.50
Received By btrobaug Date 2005-01-07 Time 14:05 Sent To M
Notes
2005-01-07 00:00:00 
  
 .PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2 AT 60 AMPS IS TOO LARGE TO PROTECT A
 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30
 AMP OCP). ALSO 60 AMP OCP SHOWN INTHE
 MAIN PANEL SEEM TOOLARGE FOR THE
 CONDENSING UNIT. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 3} IF NOTE #15 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 4} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
 5} A RECEPTACLE NEEDS TO BE ADDED TO
 THEMASTER BEDROOM TO COMPLY WITH
 210.52(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 15:52 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 15:52 Sent To E
Notes
2006-03-09 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-15 Cont ID  
Sent By adarroug Date 2005-08-15 Time 15:26 Rev Time 0.00
Received By adarroug Date 2005-08-15 Time 15:26 Sent To B
Notes
2005-08-15 00:00:00TO "RMCDOUGAL"DESK/SUBMITTAL
2005-07-20 00:00:00PER P TJOMSTOL/L MARTINEZ ROUTE TO
 INCOMING - ZONING HAS APPROVED BLDG
 STILL NEEDS TO REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 08:51 Rev Time 0.00
Received By shill Date 2005-06-20 Time 08:51 Sent To B
Notes
2005-06-20 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 17:16 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 17:16 Sent To B
Notes
2005-05-24 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 09:37 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 09:37 Sent To B
Notes
2005-02-15 00:00:00TO BTROBAUG DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 08:27 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 08:27 Sent To E
Notes
2005-01-06 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 11:50 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 11:50 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By prafter Date 2005-01-11 Time 13:16 Rev Time 0.00
Received By prafter Date 2005-01-11 Time 13:32 Sent To B
Notes
2005-01-11 00:00:00NO A/C PLANS.
 PAT RAFTER 561/805/6725 OR 805/6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-29 Cont ID  
Sent By jleech Date 2005-06-29 Time 15:50 Rev Time 0.25
Received By jleech Date 2005-06-29 Time 15:50 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By jleech Date 2005-01-10 Time 18:34 Rev Time 0.33
Received By jleech Date 2005-01-10 Time 18:34 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-20 Cont ID  
Sent By mmclean Date 2005-07-20 Time 12:29 Rev Time 0.00
Received By mmclean Date 2005-07-20 Time 12:29 Sent To PC
Notes
2005-07-20 00:00:00APPROVED RE-STAMP OF SURVEY, MOVING THE
 HOUSE ON LOT. GIVEN TO WANDAL, PERMIT &
 LICENSE SPECIALIST.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-05 Cont ID  
Sent By mmclean Date 2005-01-05 Time 18:44 Rev Time 0.00
Received By mmclean Date 2005-01-05 Time 18:44 Sent To I
Notes
2005-01-05 00:00:00MUST PULL SEPERATE PERMIT FOR POOL/DECK