Plan Review Details - Permit 04121827
Plan Review Stops For Permit 04121827
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-11-15 Cont ID  
Sent By alange Date 2005-11-15 Time 07:16 Rev Time 1.00
Received By alange Date 2005-11-15 Time 07:16 Sent To  
Notes
2005-11-15 00:00:00SHUTTER REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-10-06 Cont ID  
Sent By alange Date 2005-10-06 Time 08:01 Rev Time 0.50
Received By alange Date 2005-10-06 Time 07:52 Sent To Z
Notes
2005-10-06 00:00:00WALL REVISION OKALANGE

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-09-09 Cont ID  
Sent By alange Date 2005-09-09 Time 09:45 Rev Time 1.00
Received By alange Date 2005-09-09 Time 09:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-09-07 Cont ID  
Sent By alange Date 2005-09-07 Time 16:21 Rev Time 1.00
Received By alange Date 2005-09-07 Time 15:42 Sent To  
Notes
2005-09-07 00:00:00DENIED
 FOURTH PLAN REVIEW SAME COMMENT:
  
 3.KOLBE AND KOLBE PRODUCT APPROVALS
 SUBMITTED ARE MISSING THE APPROPRIATE
 STATE PRODUCT APPROVALS.
  
 THE FOLLOWING STATE PRODUCT APPROVAL
 INFORMATION IS REQUIRED WITH EACH
 PRODUCT APPROVAL WITH QUALITY ASSURANCE.
 * PLEASE READ THE FOLLOWING THIS IS THE
 FOURTH TIME THIS SAME COMMENT HAS BEEN
 MADE*
  
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-16 Cont ID  
Sent By alange Date 2005-08-16 Time 15:31 Rev Time 1.00
Received By alange Date 2005-08-16 Time 15:15 Sent To  
Notes
2005-08-16 00:00:00DENIED
  
 3.PRODUCT APPROVALS:
 **SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS WITH QUALITY ASSURANCE FOR THE
 FOLLOWING WITH STATE APPROVALS
 ATTACHED.** STRAPS AND TIE DOWNS OK.
 PRODUCT APPROVALS ARE REQUIRED FOR THE
 FOLLOWING:EXTERIOR DOORS, WINDOWS,
 IMPACT PROTECTION, TILE ROOF AND FLAT
 ROOF.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-15 Cont ID  
Sent By alange Date 2005-07-15 Time 14:11 Rev Time 1.50
Received By alange Date 2005-07-15 Time 09:47 Sent To  
Notes
2005-07-15 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS:
 **SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS WITH QUALITY ASSURANCE FOR THE
 FOLLOWING WITH STATE APPROVALS
 ATTACHED.** STRAPS AND TIE DOWNS OK.
 PRODUCT APPROVALS ARE REQUIRED FOR THE
 FOLLOWING:EXTERIOR DOORS, WINDOWS,
 IMPACT PROTECTION, TILE ROOF AND FLAT
 ROOF.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 4.SIGN OWNER/AGENT ON ENERGY CALCS.
 SUBMIT 2 COPIES OF ENERGY CALCS.
  
 NEW COMMENT:
 A:ARCHITECT TO SIGN AND SEAL ALL PAGES
 SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-21 Cont ID  
Sent By alange Date 2005-01-21 Time 09:33 Rev Time 2.25
Received By alange Date 2005-01-21 Time 09:23 Sent To  
Notes
2005-01-21 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS:
 PRODUCT APPROVALS ARE REQUIRED FOR THE
 FOLLOWING:STRAPS AND TIE-DOWNS,
 EXTERIOR DOORS, WINDOWS, IMPACT
 PROTECTION, TILE ROOF AND FLAT ROOF.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 4.1015.2 HEIGHT. GUARDRAILS SHALL FORM
 A VERTICAL PROTECTIVE BARRIER NOT LESS
 THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.SEE ALSO A-8 #1
  
  
 5. FBC 2309.6ACCESS TO ATTIC SPACE
 EACH ATTIC SPACE WITH A CLEAR HEIGHT OF
 24" OR GREATER SHALL BE PROVIDED WITH AN
 INTERIOR ATTIC ACCESS OPENING NOT LESS
 THAN 20"X 36".PLEASE SHOW LOCATIONS ON
 PLANS.
  
 6. SHOW HANDRAILS AT STAIRS ON S-3 #1
  
 7.SHOW HOW EXISTING BUILDING WILL
 COMPLY FOR GFCI OUTLETS AND SMOKE
 DETECTORS. FBC 3401.7.1.2.1
  
 8.SUBMIT 2 COPIES OF ENERGY CALCS.
  
 9.SHOW SIZE AND TYPE OF BEDROOM
 WINDOWS AND SILL HEIGHT FROM FLOOR.
 FBC 1005.4
  
 10. CHIMNEY HEIGHT SHALL COMPLY WITH
 FBC 2804.2.4
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2006-10-16 Cont ID  
Sent By dpalmer Date 2006-10-16 Time 20:19 Rev Time 0.00
Received By dpalmer Date 2006-10-16 Time 19:51 Sent To PC
Notes
2006-10-16 20:19:21REDLINED TO VERIFY THE GROUNDING ELECTRODE CONDUCTOR ,
 PER 250.66, SHOWS #1, SEEMS TO BE MISPRINT? SEC'S NOT
 SHOWN AT THIS TIME.

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2006-10-06 Cont ID  
Sent By dpalmer Date 2006-10-06 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2006-10-06 Time 16:05 Sent To PC
Notes
2006-10-06 00:00:00***** UNSAT *****
  
 1) NOTE: PLEASE SEE RISER IS SHOWING
 DISONNECT AS WHAT IS REALLY AND "PANEL"
 FOR THE HWH. PLEASE INDICATE ON RISER AS
 "PANEL HWH", AND ON PANEL "B" SCHEDULE
 "PANEL HWH" OR ANY LABELING WHICH CALLS
 FOR THIS BEING A PANEL.
 PLEASE SEE NO DISCONNECTING MEANS IS
 BEING SHOWN FOR THE UNIT. THE PANEL IS
 LOCATED IN THE HALL WHICH IS OK, HOWEVER
 IS NOT WITHINSIGHT OF UNIT FOR
 DISCONNECTING MEANS.
 422.31, 422.31.
 PLEASE SEE KNOW, MIN CLEARENCES STILL
 MUST BE MET FOR UNIT(S) FROM
 COMBUSTIBLES AS REQUIRED PER
 MANUFACTURES SPEC(THIS IS TO BE
 VERIFIED).
  
 ** PLEASE KNOW, ANY USE OF BREAKERS FOR
 A MEANS OF DISCONNECT, PLEASE KNOW THE
 "LOCK-OFF" DEVICE, MUST BE AN "INTEGRAL"
 PART OF THE BREAKER. THE "SNAP" ON
 DEVICES WHICH READILY FALL OFF ARE NOT
 PERMITTED OR ACCEPTABLE.
  
 ** PLEASE SEE THEN KW RATING ON LOAD
 CALCS AND DISC/PANEL HWH SHOW TWO
 DIFFERENT LOADS.
 PLEASE CORRELATE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2006-09-28 Cont ID  
Sent By dpalmer Date 2006-09-28 Time 07:11 Rev Time 0.00
Received By dpalmer Date 2006-09-27 Time 19:32 Sent To PC
Notes
2006-09-28 00:00:00********** UNSAT ***********
  
 ***** PLEASE SEE ELECTRICAL RISER
 DIAGRAM HAS NOW BEEN COMPLETELY REVISED
 WHICH IS NOT CODE COMPLIANT.
  
  
  
 1) NOTE: PLEASE SEE RISER NOW SHOWS THE
 DISCONNECT ON THE LOAD SIDE OF THE ATS
 AS 100A'S, WHEN THE OCP AND LOAD THROUGH
 THIS DISCONNECT IS GREATER AND EXCEEDS
 THAT OF ITS RATING.
 240. 408 ETC.
  
 2) NOTE: PLEASE SEE NOW A NEW PANEL "C"
 IS BEING INTRODUCED BEING FED FROM THE
 GARAGE WHICH IS A DETACHED BLUIDING.
 PLEASE SEE THIS PANEL IS BEING SHOWN
 UPSTAIRS AND MLO.
 PLEASE SEE THIS IS NOT PERMITTED.
 PLEASE SEE 225.31-225.39.
 PLEASE ALSO SEE THIS PANEL IS BEING
 SHOWN AS NO MEETING 110.26.
  
 3) NOTE: PLEASE SEE LOAD ON PANEL "C"
 FOR TANKLESS WATER HEATER DOES NOT
 CORRELATE WITH LOAD CALCULATIONS.
 220.31
  
 4) NOTE: PLEASE COMPLETE AND PROVIDE
 LOADCALULATIONS ON EACH OF THE PANELS
 AS SHOWN.220.31, 215.5
 FBC106.1.2 ADMIN SECT.
  
 5) NOTE: PLEASE SEE 250.32, 250.50 FOR
 NON COMPLIANCE FOR NEW PANEL.
  
  
 ** PLEASE KNOW, BASED ON THE NEW REVISED
 PLANS SUBMITTED, IT IS THE HOPE OF THIS
 OFFICE THAT THE INSTALLATION IN FIELD IS
 NOT WHAT IS SHOWN ON PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-09-19 Cont ID  
Sent By dpalmer Date 2006-09-19 Time 20:34 Rev Time 0.00
Received By dpalmer Date 2006-09-19 Time 20:28 Sent To PC
Notes
2006-09-19 00:00:00****** UNSAT 3RD REVIEW OF REVSIONS***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW.
  
 REVIEW FOR REV #5 AND 6.
  
 1) NOTE: PLEASE SEE LOAD FOR TANKLESS
 WATER HEATER IS NOW BEING SHOWN AT
 27KVA?? < YET, PLEASE SEE OCP IS STIL
 BEING SHOWN AT 100A'S?
 LOAD WAS INCREASED, YET THE OCP IS NOW
 NOT LARGE ENOUGH FOR THE NEW 27KW SHOWN.
 PLEASE ALSO SEE PLANS SHOW A "GAS "
 UNIT? IS THE UNIT #1, AS THE ONE LOCATED
 ON THE PANEL SCHEDULE IS UNIT #2.??
 PLEASE SEELOAD CALCULATIONS STILL DO
 NOT SHOWN THIS 27KW LOAD.
 220.31,240.4,310.16, ETC.
  
 2) NOTE: PLEASE SEE PANELS A AND B IN
 MAIN HOUSE APPEARS TO SHOW SOME SORT OF
 COUNTER /WALL OR SOMETHING LOCATED IN
 FRONT OF THESE. PLEASE SEE 110.26.240.24
 408.7 ETC.
  
 3) NOTE: PLEASE SEE NOT ALL SHEETS ARE
 SEALED BY THE ARCHITECT.
 FBC 106.1, FS 481.221
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-04-13 Cont ID  
Sent By dpalmer Date 2006-04-13 Time 12:17 Rev Time 0.00
Received By dpalmer Date 2006-04-13 Time 10:43 Sent To PC
Notes
2006-04-13 00:00:00** UNSAT **
  
 PLEASE SEE SOME NOTE FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF
 CORECTING.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
 *********** UNSAT *****************
  
  
 1) NOTE: OK
  
 2) NOTE: OK.
  
 3) NOTE: OK
  
 4) NOTE:NO, PLEASE SEE SIZE HAS NOT
 INCREASED AND PLEASE SEE MULTIPLE
 LOCATIONS OF ATTACHMENT SHOWN ON RISER..
 PLEASE SEE 250.6,250.24B.
  
 ** PRE-NOTE**
 PLEASE SEE THE EXISTING
 GROUNDING ELECTRODE CONDUCTOR IS NO
 LONGER LARGE ENOUGH DUR TO THE INCREASE
 OF SERVICE. PLEASE SEE TABLE IN250.66
 AND ADJUST.
  
 5)NOTE: OK.
  
 6) NOTE: OK
  
 7) NOTE: OK.
  
 8) NOTE:NO, PLEASE SEE NO CHANGE WAS
 MADE TO THE KVA LOADS ON PANEL SCHEDULE
 OR IN LOAD CALCS.
  
 ** PRE- NOTES**
 PLEASE SEE 100A BRKR IS BEING
 SHOWN FOR NEW ELECTRIC TANKLESS UNIT,
 HOWEVER THE LOAD IS SHOWN AS 1.2VA PER
 PHASE AND IS NOT SHOWN IN LOAD CALCS.
 THIS WILL GREATLY AFFECT LOAD CALCS.
 215.5, 220
  
 9) NOTE: OK
  
 10) NOTE: OK
  
 11) NOTE:
  
 12) NOTE:
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLANREVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 07:46 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 20:48 Sent To PC
Notes
2006-03-24 00:00:00*********** UNSAT *****************
  
  
 1) NOTE: PLEASE SEE PLANS ARE COMING IN
 WITH HAND DRAWN CHANGES MADE ON PLANS
 WHICH ARE SIGNED, DATED AND SEALED BY AN
 ARCHITECT WHICH IS NOT PERMITTED UNDER
 FS 481.221
 PLEASE REVISE, RE-PRINT AND HAVE
 ARCHITECT SIGN,DATE AND SEAL PLANS.
  
 2) NOTE: PLEASE SEE RISER IS COMING IN
 COMPLETELY DIFFERENT FROM PREVIOUS
 PLANS. PLEASE SEE NOW, SERVICE HAS BEEN
 INCREASED FROM THE PREVIOUS 300A'S TO
 NOW A 500A SERVICE. PLEASE SEE EXST,
 PREVIOUS SEC'S WERE SHOWN AS 350 MCM'S,
 HOWEVER THESE CONDUCTORS HAVE NOW BEEN
 REMOVED FROM THE PLANS.
 PLEASE SHOW THE SIZE OF THE NEW SEC'S IN
 RISER AND THE INCREASE OF THE SIZE OF
 RISER. PLEASE SHOW THE CONDUCTORS NOW
 BEING USED FROM THE GUTTER TO THE NEW
 MAINS AND EXIST.
 PLEASE INCLUDE THE SIZE OF THE GUTTER,
 IS THE EXST ONE LARGE ENOUGH? SHOW NEW
 SIZE.
 240.4,310.15B6, 215.5
  
 3) NOTE: PLEASE SUBMITAIC RATINGS FOR
 NEW EQUIPMENT.
 215.5,110.9
  
 4) NOTE: PLEASE SEE THE EXISTING
 GROUNDING ELECTRODE CONDUCTOR IS NO
 LONGER LARGE ENOUGH DUR TO THE INCREASE
 OF SERVICE. PLEASE SEE TABLE IN250.66
 AND ADJUST.
  
 5)NOTE: PLEASE SEE NEW PLANS DO NOT
 GROUP MAINS AT MAIN HOUSE AS REQUIRED
 PER 225.34. PLEASE SEE PLANS INDICATE
 ONE MAIN UPSTAIRS AND ONE DOWNSTAIRS????
 PLEASE SEE ORIG PLANS CALLED FOR ONE
 PANEL, (EXIST)
 IT IS THIS OFFICE'S HOPE THIS IS NOT
 INSTALLED THIS WAY.
 PLEASE ALSO SEE THE EFFECT THIS WOULD
 AHVE FOR LOCATION OF GROUNDING THE
 SYSTEM AT THE MAIN HOUSE FOR THE NEW
 MAINS WHICH WILL BE REQUIRED. 250.32
  
 6) NOTE: PLEASE SEE MIN OCP FORAHU'S
 TO BE 125%. 424.3B, PLEASE SEE 50A OCP
 FOR 10KW UNIT.
  
 7) NOTE: PLEASE SEE MIN VA FOR LAUNDRY /
 WASHER CIRCUIT. 210.11C2, 220.16B
 1.5MIN
  
 8) NOTE: PLEASE SEE 100A BRKR IS BEING
 SHOWN FOR NEW ELECTRIC TANKLESS UNIT,
 HOWEVER THE LOAD IS SHOWN AS 1.2VA PER
 PHASE AND IS NOT SHOWN IN LOAD CALCS.
 THIS WILL GREATLY AFFECT LOAD CALCS.
 215.5, 220
  
 9) NOTE: PLEASE SEE REDLINED PLANS FOR
 LOAD CALCULATIONS FROM PREVIOUS PLANS
 PER 220.31B
  
 10) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52 , SOME OF THESE WERE REMOVED FROM
 PREVIOUS PLANS AND SOME WHICH WERE
 REDLINED FROM ORIG PLANS ARE STILL NOT
 IMPLEMENTED INTO PLANS.
  
 11) NOTE: PLEASE SEE MANY AREAS/ROOMS
 WHERE THE REQUIRED EGRESS LT FIXTURE IS
 KNOW ONLY SHOWN AS A "J-BOX" , PLEASE
 KNOW, A MIN FIXTURE OF SOME SORT WILL BE
 REQUIRED FOR MIN EGRESS. 210.70,
 NFPA-101 7.8
 PLEASE REVISE PLANS.
  
 12) NOTE: PLEASE VERIFY THE MAINS AND
 SPACES AT THE 400A METER/MAIN. PLEASE
 KNOW, NO MORE THAN 6 MAINS ARE
 PERMITTED, PLEASE ALSO SEE NO MORE THAN
 5 SPACES WOULD BE PERMITTED IN
 METER/MAIN. PLEASE PROVIDE SCHEDULE FOR
 M/M OR PROVIDE INFORMATION IS INDEED
 THERE IS A 400A MAIN BRKR.
 230.70, 230.71
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLANREVIEW
 561-805-6717
 [email protected]
  
  
2006-03-23 00:00:00NOTES

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 10:33 Rev Time 0.50
Received By dpalmer Date 2005-09-03 Time 10:27 Sent To B
Notes
2005-09-03 00:00:00** REDLINED NOTES, PLAN OK AND STAMPED**
  
  
  
 PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS,
 1ST 8KW AT 100%
 REMAINDER @ 40%,. 35% SHOW.
  
 PLEASE SEE LOAD CALCS INDICATE SERVICE
 AT 300A'S. PLEASE SEE 310.15B6, FOR
 350MCM, IS RATED FOR 350A'S. SF
 DWELLING.
  
 110.26 FOR A/C DISC.
 210.52 FOR MASTER BEDRM RECEPT MISSING
 WITHIN 6' OF DOOR.
 ***************************************
 NO CORRECTIONS NEEDED AT THIS TIME> IF
 PLANS COME ABCK IN FOR REVISIONS DURING
 BLDG, PLEASE MAKE ABOVE ADUSTMENTS AT
 THAT TIME.
 ***************************************

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-08-01 Cont ID  
Sent By dpalmer Date 2005-08-01 Time 07:00 Rev Time 1.00
Received By dpalmer Date 2005-08-01 Time 06:44 Sent To P
Notes
2005-08-01 00:00:00************ UNSAT 3RD REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS TWO
 REVIEWS STILL NEED TO BE ADDRESSED.
 PLEASE SEENEW NOTES DUE TO CHANGES IN
 PLANS.
  
 1)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT ON PLANS. PLEASE SEE PREVIOUS
 PLANS SHOWED TWO PANELS, NOW ONE PANEL
 "K" HAS BEEN REMOVED AND METER/MAINS,
 ETC ARE NOT SHOWN?
 PLEASE SEE RISER NOW SHOWS PANEL "H" AS
 EXISTING? HOW IS THIS POSSIBLE IF THIS
 PANEL IS BEING SHOWN BEING LOCATED IN
 NEW ADDTION SECTION OF HOUSE?
 IF SERVICE IS LOCATED AT A DEATCHED BLDG
 AS NOW SHOWN ON RISER DIAGRAM, THEN
 PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM ETC AT DETACHED BLDG'S.
 PLEASE ALSO SEE NEW COMMENTS BASED ON A
 RISER DIAGRAM NOW BEING SUBMITTED.
  
 2)NOTE: PLEASE SEE RISER NOW SUBMITTED,
 HOWEVER PLEASE SEE THAT PANEL SCHEDULES
 WHICH WERE SUBMITTED FOR THE LAST TWO
 REVIEWS HAVE NOW BEEN REMOVED FROM
 PLANS?
 PREVIOUS PLANS CALLED FOR A 400A
 SERVICE, PLANS NOW INDICATE A 300A
 SERVICE. PREVIOUS COMMENT REQUIRING A
 1/0 MIN FOR GROUNDING ELECTRODE IS NO
 LONGER RELEVENT.
 PLEASE SUBMIT. UNABLE TO VERIFY SOME
 PREVIOUS NOTES.
 NEED TO VERIFY OVER CURRENT PROTECTION,
 CONDUCTOR SIZES, ARC FAULT PROTECTION,
 ETC.215.5
  
 3)NOTE: PLEASE SEE NEW RISER SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR FROM
 GUTTER TO GARAGE MAIN. PLEASE SEE 250.6,
 250.24, "EQUIPMENT GROUNDING" CONDUCTORS
 ARE ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 4)NOTE: PLEASE SEE "NEW FOOTER" STEEL IS
 STILL NOT SHOWN TO BE A PART OF THE
 GROUNDING ELECTRODE SYSTEM. 250.50
  
 5)NOTE: PLEASE SEE BOTTOM OF LOAD
 CALCULATIONS STILL SHOW "EXISTING
 SERVICE" 200A'S.?? PLEASE SEE RISER
 SHOWS SERVICE AS 300A'S.
 PLEASE SEE LOAD FOR "GARAGE PANEL" CAN
 NOT BE VERIFIED AS NO PANEL SCHEDULE(S)
 OR IDENTIFICATION IS SHOWN.
 215.5
  
 6)NOTE: PLEASE SEE PREVIOUS PLANS SHOWED
 ALL CIRCUITING, HOWEVER PLANS DO NOT
 SHOW THIS NOW?
 215.5
  
 7)NOTE: PLEASE SEE PREVIOUS NOTES
 REFERENCED ARC FAULT PROTECTION FOR SD'S
 ALSO, HOWEVER "RESPONSE LTR" MENTIONS,
 "WHERE APPLICABLE" ??
 PLEASE KNOW, SD'S ARE ALL WIRED IN-LINE
 AS REQUIRED IN NFPA-72 8-1.4 .ALL SD'S
 SHALL BE ON AN ARC FAULT PROTECTED
 CIRCUIT.
  
 8)NOTE: PLEASE SEE FS 553.80(2)B)
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO A
 MIN OF TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE COPY OF OLD/VOIDED SHEETS
 SHALL BE SUBMITTED FOR REFERENCE.
 ONE COPY OF ELECTRICAL PLANS HAVE BEEN
 RETAINED FOR FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
  
  
 250.50

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-20 Cont ID  
Sent By dpalmer Date 2005-06-20 Time 16:30 Rev Time 1.00
Received By dpalmer Date 2005-06-20 Time 16:11 Sent To P
Notes
2005-06-20 00:00:00******* UNSAT 2ND REVIEW *****
  
 PLEASE SEE SOME NOTES FROM
 PREVIOUS/FIRST REVIEW STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: NOTE#1 OK.
  
 2)NOTE: NOTE #2, NO, NO RISER SUBMITTED
 ON E-1
  
 3)NOTE: NOTE #3 NO, NO RISER.
  
 4)NOTE: NOTE #4 NO, NO RISER, ALTHOUGH
 A-SHEET APPEARS TO SHOW SERVICE GROUPED?
  
 5)NOTE: NOTE #5 NO, NO RISER.
  
 6)NOTE: NOTE #6 NO, NO RISER.
  
 7)NOTE: NOTE #7 NO, NO RISER.
  
 8)NOTE: NOTE# 8 OK, HOWEVER PLEASE SEE
 ONE AHU IS SHOWN WITH NO INFORMATION ON
 PANEL SCHEDULE? "BLANK".
  
 9)NOTE: NOTE #9 NO, NO RISER.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE #13 NO, PLEASE SEE SOME
 MISSING. BATH GFI.
  
 14)NOTE: NOTE #14 OK, HOWEVER PLEASE SEE
 210.12 2002 NEC FOR ARC FAULT
 PROTECTION.
  
 15)NOTE: NOTE #15 NO, NO RISER.
  
 16)NOTE: NOTE #16 NO, PLEASE SEE
 220.31B
  
 17)NOTE: NOTE #17 NO,PLEASE SEE FIRST
 FLR.
  
 18)NOTE: NOTE #18 NO, PLEASE SEE SD'S
 AND NOTE ABOVE.
  
 19)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF ELECTRICAL IS BEING RETAINED
 FOR FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-12 Cont ID  
Sent By dpalmer Date 2005-01-12 Time 09:17 Rev Time 1.00
Received By dpalmer Date 2005-01-12 Time 08:55 Sent To P
Notes
2005-01-12 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SHOW LOCATION OF ALL
 SERVICE EQUIPMENT ON PLANS INCLUDING
 PANELS AND IDENTIFY PANELS. 215.5
  
 2)NOTE: PLEASE SEE 310.15B6 FOR MIN
 SEC'S FOR A 400A SERVICE. 240.4B
 MIN 400MCM.
  
 3)NOTE: PLEASE SEE #4'S SHOWN FROM
 GUTTER TO 200A METERS.? PLEASE SEE
 310.15B6, #4 IS RATED FOR 100A'S ONLY.
  
 4)NOTE: PLEASE SEE 230.72 FOR GROUPING
 OF MAINS REQUIRED.
  
 5)NOTE: PLEASE SEE ONE OF THE 200A
 METER
 CANS DO NOT INDICATE WHERE THIS IS
 FEEDING?? 215.5
  
 6)NOTE: PLEASE SEE 250.6,250.24 AND
 EQUIPMENT GROUNDING CONDUCTOR IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 7)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANELS. RISER INDICATES 60A SUB
 PANEL AS MLO AND PANEL IS SHOWN AS MCB.
 PLEASE ALSO SEE PANEL H SHOWS A 2P20A
 FEED TO 60A SUB PANEL.
 PLEASE ALSO SEE OCP FROM PANEL "H" TO
 PANEL K, SHOWN AS 2P20A 1KW LOAD.
  
 8)NOTE: PLEASE SEE 424.3B FIR MIN OCP
 FOR AHU'S. PLEASE SEE THESE ARE SHOWN
 AS
 2P20A W/ 1KW LOAD??
  
 9)NOTE: PLEASE SEE NEW FOOTER STEEL
 REQUIRED TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM. 250.50
  
 10)NOTE: PLEASE SEE CIRCUITING FOR BATH
 GFI'S THESE ARE TO BE 20A, #12 PER
 210.11C3.
 PLEASE SEE SOME SHOWN AS 15A ETC.
  
 11)NOTE: PLEASE SEE 210.52C1 FOR
 KITCHEN
 COUNTERSPACE.
  
 12)NOTE: PLEASE SEE 210.8A6, ALL
 KITCHEN
 COUNTERSPACE RECEPTS TO BE SHOWN AS
 GFI.
  
 13)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS AND REMODELS TO EXISTING
 DWELLINGS.
 SD'S AND GFI'S TO BE BROUGHT UP TO
 CODE.
 PLEASE SHOW ALL NEW AND ANY EXISTING
 WHICH MEET CURRENT CODE.
  
 14)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 15)NOTE: PLEASE SEE 250.66 FOR MIN GEC.
 1/0 MIN.
  
 16)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS.
  
 17)NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS ON PLANS.
  
 18)NOTE: PLEASE SEE ARC FAULT PROTECTION
 IS TO BE UNDER THE 2002 NEC.210.12
 AFCI PROTECTION IS FOR ALL "OUTLETS,
 SD'S LTS , FANS ETC. PLEASE SEE
 CIRCUITING.
  
 PLEASE SEE MANY OF THESE ITEMS HAVE
 BEEN REDLINED ON ONE SET OF PLANS FOR
 AREAS OF NOTES.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOWULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 18:14 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 18:14 Sent To E
Notes
2006-10-12 18:14:41TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 16:42 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 16:42 Sent To E
Notes
2006-09-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-09-13 Cont ID  
Sent By adarroug Date 2006-09-13 Time 10:49 Rev Time 0.00
Received By adarroug Date 2006-09-13 Time 10:49 Sent To E
Notes
2006-09-13 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 14:08 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 14:07 Sent To E
Notes
2006-04-10 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-03-31 Cont ID  
Sent By adarroug Date 2006-03-31 Time 16:14 Rev Time 0.00
Received By adarroug Date 2006-03-31 Time 16:14 Sent To M
Notes
2006-03-31 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 19:53 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 19:53 Sent To E
Notes
2006-03-21 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-03-14 Cont ID  
Sent By adarroug Date 2006-03-14 Time 10:21 Rev Time 0.00
Received By adarroug Date 2006-03-14 Time 10:21 Sent To B
Notes
2006-03-14 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-28 Cont ID  
Sent By adarroug Date 2005-09-28 Time 15:18 Rev Time 0.00
Received By adarroug Date 2005-09-28 Time 15:18 Sent To B
Notes
2005-09-28 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 17:58 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 17:58 Sent To E
Notes
2005-09-01 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 11:04 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 11:04 Sent To E
Notes
2005-07-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 11:57 Rev Time 0.00
Received By shill Date 2005-06-17 Time 11:57 Sent To E
Notes
2005-06-17 00:00:00TO ELEC BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 15:46 Rev Time 0.00
Received By shill Date 2005-06-08 Time 15:46 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-05 Cont ID  
Sent By mjacobs Date 2005-01-05 Time 08:38 Rev Time 0.00
Received By mjacobs Date 2005-01-05 Time 08:38 Sent To E
Notes
2005-01-05 00:00:00TO "E" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 10:15 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 10:15 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-04-03 Cont ID  
Sent By tgordon Date 2006-04-03 Time 09:47 Rev Time 0.45
Received By tgordon Date 2006-04-03 Time 09:47 Sent To  
Notes
2006-04-03 00:00:00*** PROVISO ***
 1) PROVIDE COMBUSTION AIR FOR GAS
 CLOTHES DRYER, PER 2004 FBC/R M1701.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-08-16 Cont ID  
Sent By prafter Date 2005-08-16 Time 09:53 Rev Time 0.50
Received By prafter Date 2005-08-16 Time 09:53 Sent To B
Notes
2005-08-16 00:00:00MECH.PLAN REVIEW: PROVISO:
  
 CHECK LIST 1/18/05 PRAFTER.
  
 1. O/K
  
 2. O/K
  
 3. RETURN AIR OUT OF BEDROOM #2 AND #3
 TO 18/18 HALLR/A GRILL MUST CONTINUE
 TO AHU #2. .
  
 4. O/K
  
 5. O/K
  
 6. BEDROOM #1 BATH MUST HAVE EXHAUST.
 2003 FBC/M 402.3.1.ARCH. A.2 REFLECT
 BATH ROOM TO BE LOCATED INT. WITH NO
 EXHAUST.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-15 Cont ID  
Sent By pkrauss Date 2005-07-15 Time 07:50 Rev Time 0.35
Received By pkrauss Date 2005-07-15 Time 07:41 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 1.50
Received By prafter Date 2005-01-18 Time 11:38 Sent To B
Notes
2005-01-18 00:00:001. NO ENERGY INFORMATION.
  
 2. FIRST FLOOR SITTING ROOM REQUIRES
 RETURN AIR.FBC/M 2001 601.4 .
  
 3. RETURN AIR OUT OF BEDROOM #2 AND
 #3 MUST BE EQUEAL TO TOTAL SUPPLY DUCTS
 INTO BEDROOM AND CLOSIT/BATHROOM AREA.
 FBC/M 2001 601.4.
  
 4. RETURN AIR OUT OF BEDROOM #1 AND
 OFFICE ARE TRANSFER DUCT, WITCH REQUIRE
 1.5 TIMES THE CROSS SECTINAL AREA OF
 SUPPLY AIR DUCTS.FBC/M 2001 601.4
 EXCEPTION #1 .
  
 5. A/C COMP. UNIT FOR MASTER BEDROOM
 AREA NOT REFLECTED ON PLAN .
  
 6.WINDOW IN BATHROOM #1 MUST CONFORM
 WITH FBC/M 402.3.1 EXCEPTION, WITH MIN.
 OF 3 SQ. FT. OF OPENING SPACE.
 PAT RAFTER 561/805/6725 OR 8056719 .

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-08-09 Cont ID  
Sent By jleech Date 2005-08-09 Time 07:57 Rev Time 0.00
Received By prafter Date 2005-08-16 Time 09:52 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-06-25 Cont ID  
Sent By jleech Date 2005-06-25 Time 09:20 Rev Time 1.00
Received By jleech Date 2005-06-25 Time 09:20 Sent To M
Notes
2005-06-25 00:00:00DENIED;
 IS WATER HEATER GAS OR ELECTRIC? P.1
 SHOWS 40 GAL. LOW BOY, E.1 SHOWS GAS
 WATER HEATER. WATER HEATER IS UNDER
 SIZED FOR A 4 AND 1/2 BATHROOM HOME. IS
 THERE ANOTHER WATER HEATER?
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-15 Cont ID  
Sent By jleech Date 2005-01-15 Time 07:21 Rev Time 1.00
Received By jleech Date 2005-01-15 Time 07:20 Sent To M
Notes
2005-01-15 00:00:00DENIED;
 RISER DIAGRAMS;
 A.FIRST FLOOR, KITCHEN AND W/M TO
 DISCHARGE DOWN STREAM OF 1/2 BATH.
 TOILET NOT VENTED.
 B.BATH 2 LAV. TO VENT WATER CLOSET SEE
 RED LINE ON RISER DIAGRAM.
 C.MASTER BATH, TUB TO DRAIN TO VENTED
 LINE SEE RED LINE.
 SHOWLOCATION OF 2ND FLOOR RISERS ON
 1ST FL FLAT PLAN PAGE P.1
 PLEASE PUT PAGES IN ORDER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2006-04-03 Cont ID  
Sent By mmclean Date 2006-04-03 Time 11:49 Rev Time 0.00
Received By mmclean Date 2006-04-03 Time 11:48 Sent To I
Notes
2006-04-03 00:00:00REVISION - CHANGE IN DRIVEWAY/PATIO TYPE
 TO PAVERS AND CHANGE IN DIMENSION OF
 DRIVEWAY ONLY.
  
 NOTE: CALL TWICE FOR CLARIFICATION AND
 NO RETURNED CALL.

Review Stop Z ZONING
Rev No 3 Status F Date 2005-10-17 Cont ID  
Sent By mmclean Date 2005-10-17 Time 11:38 Rev Time 0.00
Received By mmclean Date 2005-10-17 Time 11:38 Sent To  
Notes
2005-10-17 00:00:00DENIED,
 1. MUST PULL A SEPERATE PERMIT FOR SITE
 WALL WITH EASEMENT APPROVAL FROM THE
 CITY OF WEST PALM UTILITY DEPT.
 2. PLEASE PROVIDE A COPY OF A SURVEY FOR
 THE PROPOSED SITE WALL.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2005-06-16 Cont ID  
Sent By mmclean Date 2005-06-16 Time 19:05 Rev Time 0.00
Received By mmclean Date 2005-06-16 Time 19:05 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-01-04 Cont ID  
Sent By mmclean Date 2005-01-04 Time 16:44 Rev Time 0.00
Received By mmclean Date 2005-01-04 Time 16:44 Sent To I
Notes
2005-01-04 00:00:00DENIED, MUST PROVIDE TWO COPY OF SURVEY
 SHOWING THE EXISTING STRUCTURE TO
 COMPARE WHAT'S BEING ADDED.CALLED
 OWNER LEFT MSG ON VOICE MAIL.