Plan Review Details - Permit 04121825
Plan Review Stops For Permit 04121825
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-01-21 Cont ID  
Sent By jwitmer Date 2005-01-21 Time 12:13 Rev Time 0.55
Received By jwitmer Date 2005-01-21 Time 12:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By dpalmer Date 2005-01-03 Time 08:27 Rev Time 0.00
Received By dpalmer Date 2005-01-03 Time 08:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-01-21 Cont ID  
Sent By mcarsill Date 2005-01-21 Time 09:12 Rev Time 0.00
Received By mcarsill Date 2005-01-21 Time 09:12 Sent To  
Notes
2005-01-21 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 3. EXITS SHALL REMAIN AND ACCESSIBLE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-03 Cont ID  
Sent By adarroug Date 2005-02-03 Time 16:46 Rev Time 0.00
Received By adarroug Date 2005-02-03 Time 16:46 Sent To P
Notes
2005-02-03 00:00:00TO KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-25 Cont ID  
Sent By mjacobs Date 2005-01-25 Time 10:04 Rev Time 0.00
Received By kstevens Date 2004-12-30 Time 15:08 Sent To  
Notes
2004-12-30 00:00:00TO "COMM BD#5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-14 Cont ID  
Sent By pkrauss Date 2005-01-14 Time 08:39 Rev Time 0.15
Received By pkrauss Date 2005-01-14 Time 08:36 Sent To  
Notes
2005-01-14 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-16 Cont ID  
Sent By kstevens Date 2005-02-16 Time 10:17 Rev Time 1.33
Received By kstevens Date 2005-02-15 Time 18:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-25 Cont ID  
Sent By kstevens Date 2005-01-25 Time 10:04 Rev Time 1.00
Received By kstevens Date 2005-01-25 Time 10:04 Sent To  
Notes
2005-01-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) IN THE INSTALLATION OR REMOVAL OF ANY
 PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. SECTION 704.5
 2) THE PERSONAL SIGNATURE IS REQUIRED ON
 THE SEAL. INITIALS ARE NOT ACCEPTABLE.
 IF THIS IS THE LEGAL SIGNATURE, SUBMIT A
 SIGNED, SEALED, DATED, NOTORIZED LETTER
 SHOWING LEGAL SIGNATURE FOR OUR FILES.
 FAC 61G1-16.003.
 3) A TITLE BLOCK MUST, AT A MINIMUM,
 CONTAIN THE FOLLOWING INFORMATION:
 2) FIRM LICENSE NUMBER. (CERTIFICATE OF
 AUTHORIZATION).
 6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 FAC 61G1-16.004, FS 481.2055, & FS
 481.219((3).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]