Plan Review Details - Permit 04121817
Plan Review Stops For Permit 04121817
Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2006-02-09 Cont ID  
Sent By alange Date 2006-02-09 Time 09:48 Rev Time 0.75
Received By alange Date 2006-02-09 Time 09:26 Sent To  
Notes
2006-02-09 00:00:00DOOR REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2005-12-16 Cont ID  
Sent By alange Date 2005-12-16 Time 09:30 Rev Time 0.66
Received By alange Date 2005-12-16 Time 09:30 Sent To E
Notes
2005-12-16 00:00:00BBQ REVISION OK SENT TO BT DESK

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2005-11-29 Cont ID  
Sent By alange Date 2005-11-29 Time 09:46 Rev Time 0.50
Received By alange Date 2005-11-29 Time 09:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status N Date 2005-11-10 Cont ID  
Sent By alange Date 2005-11-10 Time 08:00 Rev Time 0.66
Received By alange Date 2005-11-09 Time 16:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-07-26 Cont ID  
Sent By alange Date 2005-07-26 Time 09:00 Rev Time 1.50
Received By alange Date 2005-07-26 Time 09:00 Sent To  
Notes
2005-07-26 00:00:00BUIDING REVISIONS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-07-22 Cont ID  
Sent By alange Date 2005-07-22 Time 09:28 Rev Time 0.75
Received By alange Date 2005-07-22 Time 09:14 Sent To  
Notes
2005-07-22 00:00:00ROOF FRAMING SHOP DRAWING REVIEWED.
 ENGINNERING REPORT RECEIVED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-05-06 Cont ID  
Sent By alange Date 2005-05-06 Time 09:05 Rev Time 1.00
Received By alange Date 2005-05-06 Time 09:05 Sent To  
Notes
2005-05-06 00:00:00REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-04-28 Cont ID  
Sent By alange Date 2005-04-28 Time 08:46 Rev Time 0.75
Received By alange Date 2005-04-28 Time 08:46 Sent To  
Notes
2005-04-28 00:00:00REVISIONS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-03-25 Cont ID  
Sent By alange Date 2005-03-25 Time 14:48 Rev Time 0.66
Received By alange Date 2005-03-25 Time 14:48 Sent To  
Notes
2005-03-25 00:00:00REV TO S-2OKALANGE

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-03-14 Cont ID  
Sent By alange Date 2005-03-14 Time 15:21 Rev Time 1.00
Received By alange Date 2005-03-14 Time 14:53 Sent To  
Notes
2005-03-14 00:00:00REVISION NOTES
  
 1.HISTORIC REVIEW REQUIRED.
  
 2. SUBMIT 2 SETS OF PRODUCT APPROVALS
 WITH QUALITY ASSURANCE FOR GARAGE DOORS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3. A/7 GARAGE GABLE.IS IT FLAT?
 IT APPEARED FLAT.
  
 4. A-9 #1 SOFFIT VENT MISSING.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-24 Cont ID  
Sent By prafter Date 2005-02-24 Time 07:52 Rev Time 1.66
Received By alange Date 2005-02-23 Time 14:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By alange Date 2005-01-24 Time 08:02 Rev Time 0.00
Received By prafter Date 2005-02-16 Time 08:05 Sent To  
Notes
2005-01-24 00:00:00DENIED
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 3.EXISTING BUILDING SHALL COMPLY WITH
  
 FBC 3401.7.2.6WHEN REPAIR AND
 ALTERATIONS AMOUNTING TO MORE THAN 50%
 OF THE VALUE OF THE EXISTING BUILDING
 ARE MADE DURING ANY 12 MONTH PERIOD,
 THE
 BUILDINGSHALL BE MADE TO CONFORM TO
 THE REQUIREMENTS OF A NEW BUILDING.
 SHOW HOW THIS WILL BE COMPLETED.
  
 4.BUILDING IS IN A FLOOD ZONE.SUBMIT
 2 COPIES OF AN ELEVATION CERTIFICATE
 SHOWING BASE FLOOD ELAVATION AND FINISH
 FLOOR HEIGHT.ALSO SHOW HOW BUILDING
 WILL COMPLY WITH SEC 94546 OF THE WPB
 MUNI-CODE
  
 5.SUBMIT TWO COPIES OF SOILS REPORT.
  
 6.PRODUCT APPROVALS:
 A.DESIGNER DOORS MISSING DCA STATE
 APPROVAL.
 B.THE FOLLOWING ARE MISSING PRODUCT
 APPROVAL WITH QUALITY ASSURANCE, EXAMPLE
 (MIAMI-DADE).
 THERMA-TRU EXTERIOR DOORS, KOLBE AND
 KOLBE MILLWORK PRODUCTS,
 C. NO PRODUCT APPROVALS HAVE BEEN
 SUBMITTED FOR THE FOLLOWING, MULLIONS,
 SIDING, AND STRAPS AND TIE-DOWNS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING TO BE ATTACH TO THE QUALITY
 ASSURANCE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 7.1015.2 HEIGHT. GUARDRAILS SHALL FORM
 A VERTICAL PROTECTIVE BARRIER NOT LESS
 THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2006-07-03 Cont ID  
Sent By dpalmer Date 2006-07-03 Time 07:25 Rev Time 0.00
Received By dpalmer Date 2006-07-03 Time 07:04 Sent To PC
Notes
2006-07-03 00:00:00REV FOR PANEL SCHEDULES,
  
 REDLINED #5 AWG SHOWN FOR AHU#4. #5 IS
 NOT A STANDARD WIRE SIZE.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2006-06-25 Cont ID  
Sent By dpalmer Date 2006-06-25 Time 15:18 Rev Time 0.00
Received By dpalmer Date 2006-06-25 Time 14:53 Sent To PC
Notes
2006-06-25 00:00:00********** UNSAT *********
  
  
 1) NOTE: PLEASE SEE LANDSCAPE LIGHTING
 WAS NO PART OF ORIGINAL PLANS AND SHALL
 BE SUBMITTED UNDER A NEW PERMIT AND NEW
 PERMIT APPLICATION.
 FBC 105.1 ADMIN SECT.
 106.1.2
  
 2) NOTE: PLEASE SEE PANEL STP IS SHOWING
 WRONG CONDUCTOR SIZES. THE OCP AND AWG
 WAS REDLINED ON THREE SETS OF PREVIOUS
 PLANS AND MUST BE CORRECTED.
 PLEASE ALSO SEE CU LOAD IS SHOWN AS
 10.4KW, YET THE OCP IS ONLY 30A'S??
 PLEASE REVISE AND ADJUST.
 240.4,310.16, 424.3B, ETC
  
 3) NOTE: PLEASE SEE PANEL SCHEDULES ARE
 NOW MISSING ALL REQUIRED KVA INDICATIONS
 FOR APPLIANCES/MOTOR/ AND A/C LOADS.
 CAN NOT VERIFY OCP AND CORRECT CONDUCTOR
 SIZES AT THIS TIME.
 PLEASE COMPLETE.
 408.4,310.16,240.4, 215.5
  
 4) NOTE: PLEASE SEE PANEL SCHEDULE SHALL
 INCLUDE ALL CIRCUITS SPECIFIC TO AREAS
 AND ROOMS IN WHICH THEY FEED. GEN
 LTS/GEN RECEPTS IS NO ACCEPTABLE FOR
 FINAL.
 IE; BEDRM #3 RECEPTS, FAMILY RM LTS,
 KITCHEN LTS, ETC
 ALL ROOMS AND AREAS SHALL CONTAIN
 DESIGNATIONS TO CORRELATE WITH PANEL
 SCHEDULE.
 408.4, 215.5, 106.1.2
  
 5) NOTE: PLEASE SEE WATER HEATER IS
 SHOWING 310AWG, WITH A 2-POLE 20?
 PLEASE VERIFY OCP AN AWG.
 240.4,310.16,
  
 6) NOTE: PLEASE VERIFY MANY CIRCUITS ARE
 SHOWING #12 AWG WITH 15A OCP? THIS IS
 OK, HOWEVER IF SHOWN THIS WAY , THIS IS
 WHAT WILL BE REQUIRED TO BE INSTALLED.
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2006-01-09 Cont ID  
Sent By dpalmer Date 2006-01-09 Time 08:47 Rev Time 0.00
Received By dpalmer Date 2006-01-09 Time 08:47 Sent To M
Notes
2006-01-09 00:00:00REDLINED OCP AND AWG FOR AHU ON PANEL.
 REDLINED #8 SHOWN ON 20A OCP.?

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2005-12-30 Cont ID  
Sent By dpalmer Date 2005-12-30 Time 06:34 Rev Time 0.00
Received By dpalmer Date 2005-12-30 Time 06:32 Sent To P
Notes
2005-12-30 00:00:00REDLINED OCP AND AWG FOR AHU IN
 STAND-BY PANEL./
 THIS IS CORRCTED FOR THE SAME PANEL
 UNDER THE GENERATOR PERMIT.
 424.3

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-12-21 Cont ID  
Sent By btrobaug Date 2005-12-21 Time 13:21 Rev Time 0.50
Received By btrobaug Date 2005-12-21 Time 13:17 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-12-20 Cont ID  
Sent By btrobaug Date 2005-12-20 Time 08:55 Rev Time 0.50
Received By btrobaug Date 2005-12-20 Time 06:40 Sent To PC
Notes
2005-12-20 00:00:00 
 PLEASE NOTE THAT THE SHEET DESIGNATED
 "A.1" ON THE ORIGINAL DRAWINGS DOES NOT
 CONTAIN THE SAME DRAWING AS THIS PLAN.
 PLEASE CHANGE THE SHEET DESIGNATION.
  
 THE ELECTRICAL REVISION IS COMPLIANT,
 WHEN THE SHEET NUMBER IS CORRECTED BY
 THE ARCHITECT, RETURN THE REVISION
 DIRECTLY TOME FOR EXPEDITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-10-09 Cont ID  
Sent By dpalmer Date 2005-10-09 Time 19:12 Rev Time 0.40
Received By dpalmer Date 2005-10-09 Time 18:54 Sent To M
Notes
2005-10-09 00:00:00GENERATOR IS UNDER PERMIT # 05081409

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-07-05 Cont ID  
Sent By dpalmer Date 2005-07-05 Time 11:17 Rev Time 1.00
Received By dpalmer Date 2005-07-01 Time 20:51 Sent To Z
Notes
2005-07-05 00:00:00********** UNSAT ************
  
  
 1)NOTE: PLEASE SEE PLANS ARE NOW COMING
 IN WITH A NEW GEN ETC BEING ADDED.
 PLEASE SEE THIS IS REQUIRED TO BE UNDER
 A SEPARATE PERMIT. PLEASE SUBMITTHE
 REVISED RISER DIAGRAM, MANUFACTURES
 SPECS FOR GEN, ATS, PANEL ETC.
 PLEASE GEN MENTIONS GAS?, HOWEVER LP PR
 NATURAL.?
 PLEASE PROVIDE LOAD CALCUALTIONS, PANEL
 SCHEDULE FOR GEN SUB PANEL AND INTENDED
 LOADS. 702.5, 225.36
 GEN LOADS MUST BE SPECIFIC AND SHALL NOT
 HAVE THE SAME DERATINGS AS GEN LTS/
 RECEPTS. PLEASE SEE ALL CONNECTED MOTOR,
 APPL LOADS ARE 100%, AND CONTINUOUS
 LOADS ARE 125%
 PLEASE ALSO SEE ZONING COMMENTS.
 215.5
  
 2)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT ON PLANS. DISC ETC.
 PLEASE SEE 225.34 FOR GROUPING OF MAINS.
  
 PLEASE SEE DISC FOR PANEL "H" COULD NOT
 BE LOCATED ON PLANS NEXT TO PANEL A?C
 ETC.
  
 3)NOTE: PLEASE SUBMIT REVISED PLANS FOR
 MAIN HOUSE DENOTING GEN UNDER SEPARATE
 PERMIT. PLEASE ALSO SUBMIT THIS REVISION
 AFTERGEN IS APPLIED AND ISSUED FOR
 PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
2005-07-01 00:00:00IN ELECTRCIAL FOR REVIEW.
 NOTES TO FOLLOW.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-01 Cont ID  
Sent By dpalmer Date 2005-03-01 Time 19:33 Rev Time 0.50
Received By dpalmer Date 2005-03-01 Time 19:16 Sent To M
Notes
2005-03-01 00:00:00PLANS REDLINED:
 LANDSCPAE LIGHTING TO BE UNDER SEPARATE
 PERMIT. LL PERMIT WILL REQUIRE
 SUBMITTALS FOR FIXTURES ETC.
  
 PLEASE SEE UPPER AREA OF SECOND FLR HALL
 MAY NEED ADDITIONAL SD. PLANS REDLINED
 FOR THIS TO BE VERIFIED IN FIELD.
  
  
 ** PLANS SENT TO MECHANICAL REVIEW,
 M-SHEETS NOT STAMPED, YET COMPUTER SHOWS
 "P".??
 PLEASE ALSO SEE ENERGY CALCS NOT
 STAMPED. OK?

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-10 Cont ID  
Sent By dpalmer Date 2005-02-10 Time 15:08 Rev Time 1.00
Received By dpalmer Date 2005-02-10 Time 15:08 Sent To M
Notes
2005-02-10 00:00:00*************** UNSAT 2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 OK
  
 2)NOTE: NOTE #2 NO, PLEASE SEE MIN SEC'S
  
 PER 310.16/310.15B6, 240.4B.
 ** NOTE** IF SEC'S ARE BEING SUPPLIED BY
 FPL, THEN THEY DO NOT NEED TO BE SHOWN.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE 250.66
 FOR SIZING OF GEC. MIN 1/0
  
 4)NOTE: NOTE#4 OK, SEE PREVIOUS COMMENT
 FOR SEC'S.
  
 5)NOTE: NOTE#5 OK
  
 6)NOTE: NOTE #6 OK
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8 OK, HOWEVER THERE ARE
 NOW TWO KITCHEN COUNTERSPACES SHOWN
 W/OUT ANY GFI RECEPTS REQUIRED PER
 210.52C1
  
 9)NOTE: NOTE #9 OK
  
 10)NOTE: NOTE #10 OK
  
 11)NOTE: NOTE #11 OK
  
 12)NOTE: NOTE #12 NO, SEE NOTE #8
  
 13)NOTE: NOTE #13 NO, PLEASE SEE COTTAGE
 AND CIRCUITING FOR SLEEPING AREAS PER
 210.12 2002 NEC.
  
 14)NOTE: NOTE #14 NO, PLEASE SEE COTTAGE
 FIRST AND SECOND FLOOR.
 NFPA-72 8-1.4.1.6.2
  
 15)NOTE: NOTE#15 NO, PLEASE SEE 220.31B
 FOR LOAD CALCUALTIONS.
  
 *************************************
 PLEASE SEE NEW NOTE:
  
 1)NOTE: PLEASE SEE 250.50,250.32 FOR
 GROUNDING ELECTRODE SYSTEM AND REQUIRED
 GROUNDING AT DETACHED BLDGS.
 PLEASE INCLUDE NEW FOOTER STEEL PER
 250.50 AND DETACHED BLDG PER 250.32.
  
 2)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL. THIS IS GIVEN AS A
 NOTICE ONLY.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 INSERT ONLY NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING. AS
 REQUESTED ON PREVIOUS REVIEW, PLEASE
 SUBMIT ONE SET OF OLD SHEETS FOR
 REFERENCE. OLD SET WAS NOT RESUBMITTED
 FOR REFERENCE WITH THIS RESUB.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-12 Cont ID  
Sent By dpalmer Date 2005-01-12 Time 14:12 Rev Time 1.50
Received By dpalmer Date 2005-01-12 Time 08:55 Sent To P
Notes
2005-01-12 00:00:00************* UNSAT *******************
 ***************************************
  
 PLEASE SEE FBC CHAPTER 34 FOR REMODEL OF
 EXISTING DWELLINGS AND ALL REQUIRED TO
 BE BROUGHT UP TO CODE.
 ***************************************
 ***************************************
  
 PLEASE SEE PLANS ARE REDLINED WITH AREAS
 OF CONCERN AS NOTED BELOW.
  
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANELS. MCB ? MLO? PANEL "C".
  
 2)NOTE: PLEASE SEE 310.15B6 FOR MIN
 SEC'S. 400 MCM FOR 400A SERVICE.
 240.4
  
 3)NOTE: PLEASE SEE 250.66 FOR SIZING OF
 GEC. MIN 1/0.
 BASED ON 310.15B6
  
 4)NOTE: PLEASE SEE 400A METER CAN DOES
 NOT INDICATE A SECOND 200A MCB TO FEED
 TWO 200A PANELS?
 PLEASE ALSO VERIFY METER SHOWN WITH
 3/0'S??
  
 5)NOTE: PLEASE SEE 110.26 FIR MIN
 CLEARENCE FOR DISC FOR A/C UNITS.
  
 6)NOTE: PLEASE SEE 210.63 FOR MISSING
 GFI FOR COND UNITS.
  
 7)NOTE: PLEASE SEE 210.70 FOR MISSING
 CONTROL OF EGRESS LIGHTING. SEE REDLINES
 FOR LOCATIONS.
  
 8)NOTE: PLEASE SEE 210.8A6 FOR ALL
 RECEPTS SERVING KITCHEN COUNTERSPACE TO
 BE SHOWN AS GFI.
  
 9)NOTE: PLEASE ALSO SEE ALL OTHERS
 REQUIRED TO BE GFI PER 210.8, GARAGE,
 OUTSIDE, BATHS ETC.
  
 10)NOTE: PLEASE SEE MISSING FRONT AND
 REAR RECEPTS PER 210.52E
  
 11)NOTE: PLEASE SEE MANY ITEMS ON PANEL
 SCHEDULE WHICH OCP DOES NOT MEET AWG OR
 VICE/VERSA.
 PLEASE SEE 1-POLE 30A BRKRS FOR 2-POLE
 CIRCUITS, RANGE ON 1-P20A AND 1-P30A ETC
 ETC.
 REDLINED:
  
 12)NOTE: PLEASE SEE 210.52C1 FOR RECEPT
 SPACING ALONG KITCHEN COUNTERSPACE.
  
 13)NOTE: PLEASE SEE WE ARE UNDER THE
 2002 NEC FOR 210.12 AND ARC FAULT
 PROTECTION. PLEASE SEE CIRCUITING AND
 ALL "OUTLETS" REQUIRED TO BE ARC-FAULT
 PROTECTED.
  
 14)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 15)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCULATIONS.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 *** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHOULD BE SUBMITTED FOR
 REFERENCE ONLY.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-01-06 Cont ID  
Sent By mmclean Date 2005-01-06 Time 15:04 Rev Time 0.00
Received By mmclean Date 2005-01-06 Time 15:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2006-06-30 Cont ID  
Sent By adarroug Date 2006-06-30 Time 10:24 Rev Time 0.00
Received By adarroug Date 2006-06-30 Time 10:24 Sent To E
Notes
2006-06-30 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 16:43 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 16:43 Sent To E
Notes
2006-06-23 00:00:00TO "DPALMER" DESK/ 2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 15:12 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 15:12 Sent To M
Notes
2006-01-27 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 15:09 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 15:09 Sent To B
Notes
2006-01-27 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2006-01-03 Cont ID  
Sent By adarroug Date 2006-01-03 Time 13:53 Rev Time 0.00
Received By adarroug Date 2006-01-03 Time 13:53 Sent To E
Notes
2006-01-03 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2005-12-28 Cont ID  
Sent By adarroug Date 2005-12-28 Time 09:14 Rev Time 0.00
Received By adarroug Date 2005-12-28 Time 09:14 Sent To E
Notes
2005-12-28 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2005-12-19 Cont ID  
Sent By adarroug Date 2005-12-19 Time 14:30 Rev Time 0.00
Received By adarroug Date 2005-12-19 Time 14:30 Sent To M
Notes
2005-12-19 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 13:09 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 13:09 Sent To B
Notes
2005-12-10 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2005-11-22 Cont ID  
Sent By adarroug Date 2005-11-22 Time 08:33 Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 08:33 Sent To M
Notes
2005-11-22 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2005-11-16 Cont ID  
Sent By adarroug Date 2005-11-16 Time 14:17 Rev Time 0.00
Received By adarroug Date 2005-11-16 Time 14:17 Sent To M
Notes
2005-11-16 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 16:18 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 16:18 Sent To P
Notes
2005-10-06 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 16:27 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 16:27 Sent To B
Notes
2005-07-21 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-07-12 Cont ID  
Sent By adarroug Date 2005-07-12 Time 15:20 Rev Time 0.00
Received By adarroug Date 2005-07-12 Time 15:20 Sent To M
Notes
2005-07-12 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-06-30 Cont ID  
Sent By adarroug Date 2005-06-30 Time 10:28 Rev Time 0.00
Received By adarroug Date 2005-06-30 Time 10:28 Sent To E
Notes
2005-06-30 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-06-16 Cont ID  
Sent By shill Date 2005-06-16 Time 13:31 Rev Time 0.00
Received By shill Date 2005-06-16 Time 13:31 Sent To B
Notes
2005-06-16 00:00:00TO AL DESK

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-05-10 Cont ID  
Sent By adarroug Date 2005-05-10 Time 08:36 Rev Time 0.00
Received By adarroug Date 2005-05-10 Time 08:36 Sent To Z
Notes
2005-05-10 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 13:14 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 13:14 Sent To B
Notes
2005-04-29 00:00:00TO "ALANGE" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 14:26 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 14:26 Sent To P
Notes
2005-04-26 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 14:55 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 14:55 Sent To Z
Notes
2005-04-22 00:00:00TO "Z" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-04-06 Cont ID  
Sent By adarroug Date 2005-04-06 Time 15:50 Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 15:50 Sent To B
Notes
2005-04-06 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-24 Cont ID  
Sent By adarroug Date 2005-03-24 Time 10:32 Rev Time 0.00
Received By adarroug Date 2005-03-24 Time 10:32 Sent To B
Notes
2005-03-24 00:00:00TO "ALANGE" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 14:39 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 14:39 Sent To B
Notes
2005-03-09 00:00:00TO "ALANGE" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-01 Cont ID  
Sent By adarroug Date 2005-03-01 Time 11:05 Rev Time 0.00
Received By adarroug Date 2005-03-01 Time 10:54 Sent To E
Notes
2005-03-01 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-07 Cont ID  
Sent By adarroug Date 2005-02-07 Time 13:01 Rev Time 0.00
Received By adarroug Date 2005-02-07 Time 13:01 Sent To E
Notes
2005-02-07 00:00:00TO DPALMER DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 15:51 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 15:51 Sent To E
Notes
2005-01-06 00:00:00TO "E" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 10:13 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 10:13 Sent To Z
Notes
2005-01-03 00:00:00TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2006-01-30 Cont ID  
Sent By tgordon Date 2006-01-30 Time 16:04 Rev Time 0.30
Received By tgordon Date 2006-01-30 Time 16:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 9 Status F Date 2006-01-09 Cont ID  
Sent By tgordon Date 2006-01-09 Time 11:24 Rev Time 0.45
Received By tgordon Date 2006-01-09 Time 11:24 Sent To  
Notes
2006-01-09 00:00:00*** DENIED ***
 1) NEED TO SUPPLY COMBUSTION AIR, OR
 COMBUSTION AIR CALCULATIONS FOR GAS
 WATER HEATER, GAS CLOTHES DRYER, AND GAS
 (?) FIREPLACE IN FLORIDA ROOM. PER 2004
 FBC/M 701.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2006-01-03 Cont ID  
Sent By tgordon Date 2006-01-03 Time 10:03 Rev Time 0.30
Received By tgordon Date 2006-01-03 Time 10:03 Sent To  
Notes
2006-01-03 00:00:00REV. TO MECH. PLANS PAGE M-1 & M-2.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2005-12-20 Cont ID  
Sent By tgordon Date 2005-12-20 Time 09:37 Rev Time 0.30
Received By tgordon Date 2005-12-20 Time 09:37 Sent To  
Notes
2005-12-20 00:00:00MECH. REV. TO MECH. PLAN PAGE M-1,
 E-CAL'S, AND MANUAL J ..

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2005-11-22 Cont ID  
Sent By tgordon Date 2005-11-22 Time 14:07 Rev Time 0.35
Received By tgordon Date 2005-11-22 Time 14:07 Sent To B
Notes
2005-11-22 00:00:00*** DENIED ***
 1) AS NOTED IN LAST MECH. REVIEW. NEED
 NEW ENERGY CAL'S. AND MANUAL J, OLD ONES
 CALL FOR THREE A/C SYSTEMS TOTALING
 110,000 BTU'S. MECH. PLANS ARE CALLING
 FOR FOUR A/C SYSTEMS TOTALING 145,600
 BTU'S, THE THREE MUST COINCIDE.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2005-10-21 Cont ID  
Sent By tgordon Date 2005-10-21 Time 14:35 Rev Time 0.35
Received By tgordon Date 2005-10-21 Time 14:34 Sent To B
Notes
2005-10-21 00:00:00*** DENIED ***
 1) NEED NEW ENERGY CAL'S. AND MANUAL J,
 OLD ONES ON FILE DO NOT COINCIDE WITH
 A/C EQUIPMENT LIST ON REVIVED MECHANICAL
 PLANS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-07-14 Cont ID  
Sent By prafter Date 2005-07-14 Time 07:47 Rev Time 0.50
Received By prafter Date 2005-07-14 Time 07:47 Sent To P
Notes
2005-07-14 00:00:00MECH. PLAN REV.
  
 REV. 7/29/05 (OK)
 PAT RAFTER 561/805/6728

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-02-17 Cont ID  
Sent By prafter Date 2005-02-17 Time 10:03 Rev Time 0.45
Received By prafter Date 2005-02-17 Time 10:03 Sent To P
Notes
2005-02-17 00:00:00SECOND MECH. REVIEW REVISED 2/17/05.
  
  
 DUCT WORK IN COTTAGE SIZED. (OK) .
  
 PAT RAFTER 561/805/6728 .
 PLEASE CALL IF THEAR ENY QUESTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-02-17 Cont ID  
Sent By prafter Date 2005-02-16 Time 08:27 Rev Time 1.00
Received By prafter Date 2005-02-17 Time 09:57 Sent To P
Notes
2005-02-16 00:00:00SECOND MECH. REVIEW:
  
 FIRST FLOOR
 DUCT WORK IN FIRST FLOOR SIZED. (OK)
  
 SECOND FLOOR
  
 DUCT WORK IN SECOND FLOOR SIZE. (OK)
  
 DUCT WORK IN COTTAGE NOT SIZED,TO BE
 SIZED.
  
 PAT RAFTER 561/805/6728 .
 PLEASE CALL IF THEAR ENY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-02-24 Cont ID  
Sent By prafter Date 2005-02-24 Time 07:45 Rev Time 0.45
Received By prafter Date 2005-02-24 Time 07:45 Sent To B
Notes
2005-01-18 00:00:00FIRST FLOOR.
 SUPPLY AND RETURN AIR DUCTS NOT SIZES
 IN DINNING ROOM.
 SUPPLY AIR DUCT TO BREAKFAST ROOM NOT
 SIZED.
  
 SECOND FLOOR.
 RETURN AIR DUCT SIZE OUT OF MASTER
 BEDROOM AREA TO BE EQUEAL TO SUPPLY DUCT
 SIZE.F.B.C./M 2001 601.4 .
 RETURN DUCT SIZE OUT OF OFFICE TO BE
 EQUEAL TO SUPPLY AIR DUCT SIZE. F.B.C.
 /M 2001 601.4 .
 DUCT NOT SIZED IN COTTAGE.
 PAT RAFTER 561/805/6725 OR 8056719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-01-03 Cont ID  
Sent By jleech Date 2006-01-03 Time 08:18 Rev Time 0.33
Received By jleech Date 2006-01-03 Time 08:18 Sent To M
Notes
2006-01-03 00:00:00REVISION TO PLUMBING PAGES.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-10-07 Cont ID  
Sent By jleech Date 2005-10-07 Time 08:35 Rev Time 0.50
Received By jleech Date 2005-10-07 Time 08:35 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-07-23 Cont ID  
Sent By jleech Date 2005-07-23 Time 13:55 Rev Time 0.50
Received By jleech Date 2005-07-23 Time 13:55 Sent To B
Notes
2005-07-23 00:00:00DENIED;
 1.TUB AND SHOWER SECOND FLOOR BATHROOMS
 ARE NOT VENTED. SEE SEC. 909.1 WET VENT.
 2.CARRIAGE HOUSE SHOWER NOT VENTED.
 3.SHOW M.V. ON FLAT DRAWING P.1 FOR
 WASHING MACHINE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-17 Cont ID  
Sent By jleech Date 2005-02-17 Time 17:09 Rev Time 0.50
Received By jleech Date 2005-02-17 Time 17:09 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-15 Cont ID  
Sent By prafter Date 2005-02-17 Time 09:58 Rev Time 1.00
Received By jleech Date 2005-01-15 Time 09:29 Sent To M
Notes
2005-01-15 00:00:00DENIED;
 1.P.1 DISHWASHERS TO TIE INDIRECT INTO
 KITCHEN SINK.
 2.OUTSIDE SHOWER NOT PERMITED TO HAVE A
 DRAIN TO SANITARY SEWER. RAIN WATER NOT
 TO DISCHARGE INTO SEWER SYSTEM.
 3.MASTER BATHROOM RISER DIAGRAM, SHOWER
 NOT VENTED. SEE RED LINES.
 4.SANITARY RISER # 2 SHOWER NOT VENTED
 SEE RED LINE.
 5.FIRST FLOOR RISER DIAGRAM. W/M DRAIN
 REQUIRES A VENT.
 6.TWO WAY C.O. REQUIRED 3' OUTSIDE OF
 HOUSE AND OUTSIDE GUEST HOUSE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status F Date 2005-07-12 Cont ID  
Sent By mmclean Date 2005-07-12 Time 07:44 Rev Time 0.00
Received By mmclean Date 2005-07-12 Time 07:44 Sent To I
Notes
2005-07-12 00:00:00DENIED - 2ND REQUEST- REVISION
 1. MUST PROVIDE TWO COPY OF SURVEY
 SHOWING THE ADDITION.
 2. SURVEY MUST SHOW THE SETBACKS (SIDE &
 REAR)
 3. NEED TO PROVIDE TWO COPY OF FLOOR
 PLANS SHOWING THE INTERIOR ACCESS OF THE
 NEW STRUCTURE WITH THE EXISTING.
 4. NEED TO PULL A SEPERATE PERMIT FOR
 GATE/WALL/COLUMS WITH THE CITY OF WEST
 PALM BEACH UTILITY DEPT EASMENT APPROVAL
 AND 2 COPY OF SURVEY SHOWING THE
 LOCATION OF THE GATE WITH THE HEIGHT.
 **GATE/WALL/FENCE/COLUMNS CAN ONLY BE A
 MAX 4FT HIGH WITHIN 25FT FRONT SETBACK
 AND BEYOND 25FT SETBACK MAX 6FT**.
 5. MUST SHOW THE GENERATOR LOCATION ON
 TWO COPY OF SURVEY, PROVIDING THE
 DIMENSION (SETBACK FROM STRUCTURE AND
 PROPERTY LINE)
 **CAN ONLY ENCROACH 4FT INTO SETBACK**
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2005-04-28 Cont ID  
Sent By mmclean Date 2005-04-28 Time 17:59 Rev Time 0.00
Received By mmclean Date 2005-04-28 Time 17:59 Sent To I
Notes
2005-04-28 00:00:00DENIED REVISION,
 1. MUST PROVIDE TWO COPY OF SURVEY
 SHOWING THE ADDITION.
 2. SURVEY MUST SHOW THE SETBACKS (SIDE &
 REAR)
 3. NEED TO PROVIDE TWO COPY OF FLOOR
 PLANS SHOWING THE INTERIOR ACCESS OF THE
 NEW STRUCTURE WITH THE EXISTING.
 4. NEED TO PULL A SEPERATE PERMIT FOR
 GATE/WALL WITH THE CITY OF WEST PALM
 BEACH UTILITY DEPT EASMENT APPROVAL AND
 2 COPY OF SURVEY SHOWING THE LOCATION OF
 THE GATE WITH THE HEIGHT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-04 Cont ID  
Sent By mmclean Date 2005-01-04 Time 16:19 Rev Time 0.00
Received By mmclean Date 2005-01-04 Time 16:19 Sent To I
Notes
***NONE***