Plan Review Details - Permit 04121387
Plan Review Stops For Permit 04121387
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-02-16 Cont ID  
Sent By alange Date 2005-02-16 Time 11:40 Rev Time 0.25
Received By alange Date 2005-02-16 Time 11:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-11 Cont ID  
Sent By alange Date 2005-02-11 Time 13:38 Rev Time 0.66
Received By alange Date 2005-02-11 Time 11:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-13 Cont ID  
Sent By alange Date 2005-01-13 Time 13:08 Rev Time 0.75
Received By alange Date 2005-01-13 Time 13:06 Sent To Z
Notes
2005-01-13 00:00:00DENIED
  
  
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.WINDOWS 2-4 SH DO NOT MEET EGRESS
 REQUIREMENTS. FBC 1005.4.4
  
 3.WINDOW AT TUB LOCATION REQUIRED TO
 BE SAFTEY GLAZING FBC 2405.2.1
  
 4.SUBMIT 2 COPIES OF PRODUCT
 APPROVALS
 FOR THE FOLLOWING:
 WINDOWS, STRAPS AND TIE-DOWNS AND
 IMPACT
 PROTECTION.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.IMPACT PROTECTION OR IMPACT GLASS
 REQUIRED.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-15 Cont ID  
Sent By dpalmer Date 2005-02-15 Time 04:37 Rev Time 0.15
Received By dpalmer Date 2005-02-15 Time 04:33 Sent To B
Notes
2005-02-15 00:00:00PLANS REDLINED FOR 210.52 AND 110.26
  
 PLANS SENT TO BLDG FOR PROCESSING. (NEW
 BLDG SHEET).

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-08 Cont ID  
Sent By dpalmer Date 2005-02-08 Time 17:57 Rev Time 0.30
Received By dpalmer Date 2005-02-08 Time 17:57 Sent To B
Notes
2005-02-08 00:00:00********* UNSAT ***********
  
 PLEASE SEE NOTES # 2 AND 4 FROM
 PREVIOUS REVIEW.
  
 1)NOTE: PLEASE SEE PLANS NEED TO
 INDICATE ALL ITEMS EITHER NEW OR
 EXISTING. SOME ELECTRICAL SHOWN BUT
 THERE IS NO INDICATION? APPL MENTIONS
 NEW CEILING FANS LTS TECYET, NOTHING
 IS SHOWN FOR ANY OF THESE. LOCATIONS OF
 BOXES, SWITCHES?
  
 2)NOTE: PLEASE SEE2002 NEC FOR MIN
 REQUIRED. 210.12 FOR ARC FAULT FOR NEW
 IN BEDRMS.
 210.70 FOR EGRESS LIGHTING, NEW ?
 EXISTING? LOCATIONS?
 210.52 FOR RECEPT SPACING TO BE BROUGHT
 UP TO CODE OR EXISTING MEETS CODE?
 PLANS DO NOT INDICATE RECEPT SPACING
 MEETING CODE.
  
 3)NOTE: **NOTE** PANEL LOCATION SHOWN
 DOES NOT MEETS 110.26, PLEASE VERIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-30 Cont ID  
Sent By dpalmer Date 2004-12-30 Time 14:50 Rev Time 0.30
Received By dpalmer Date 2004-12-30 Time 14:50 Sent To P
Notes
2004-12-30 00:00:00**************** UNSAT ***************
  
  
 1)NOTE:SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLANS ONLY SHOWN ONE SD?
  
 2)NOTE: PLEASE SEE 210.52 FOR MIN RECEPT
 SPACING. PLANS SHOWS MANY WALLS TO BE
 DRYWALLED W/OUT NAY VERIFICATION ON
 WHEATHER RECEPTS ARE EXISITNG OR TO BE
 NEW.?
  
 3)NOTE: PLEASE SEE BATH RMS ARE SHOWN W/
 NEW GFI'S. THESE NEED TO NOTED FOR
 #12,20A. 210.11C3
  
 4)NOTE: PLEASE SEE DUE TO WORK AS
 DESCRIBED ON APPLICATION, IT APPEARS
 HOUSE MAY BE GETTTING RE-WIRED? IF SO
 PLEASE SHOW MIN ELECTRICAL PER 2002 NEC
 PLEASE INDICATE NEW OR EXISTING PANEL
 AND SIZE.?
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-14 Cont ID  
Sent By adarroug Date 2005-02-14 Time 09:07 Rev Time 0.00
Received By adarroug Date 2005-02-14 Time 09:07 Sent To E
Notes
2005-02-16 00:00:00TO DPALMER DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-07 Cont ID  
Sent By adarroug Date 2005-02-07 Time 08:39 Rev Time 0.00
Received By adarroug Date 2005-02-07 Time 08:39 Sent To Z
Notes
2005-02-07 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-02 Cont ID  
Sent By adarroug Date 2005-02-02 Time 10:55 Rev Time 0.00
Received By adarroug Date 2005-02-02 Time 10:56 Sent To E
Notes
2005-02-02 00:00:00TO "E"BOX/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-28 Cont ID  
Sent By mjacobs Date 2004-12-28 Time 08:24 Rev Time 0.00
Received By mjacobs Date 2004-12-28 Time 08:24 Sent To E
Notes
2004-12-28 00:00:00TO "E" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-01-04 Cont ID  
Sent By hmoser Date 2005-01-04 Time   Rev Time 0.00
Received By hmoser Date 2005-01-04 Time 16:21 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-01-03 Cont ID  
Sent By jleech Date 2005-01-03 Time 11:00 Rev Time 0.25
Received By jleech Date 2005-01-03 Time 11:00 Sent To M
Notes
2005-01-03 00:00:00FIXTURE CHANGEOUT ONLY.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-02-08 Cont ID  
Sent By mmclean Date 2005-02-08 Time 13:31 Rev Time 0.00
Received By mmclean Date 2005-02-08 Time 13:31 Sent To I
Notes
2005-02-08 00:00:00NO ADDITION TO STRUCTURE.MUST PULL
 SEPERATE PERMIT FOR FENCE.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-01-18 Cont ID  
Sent By mmclean Date 2005-01-18 Time 15:12 Rev Time 0.00
Received By mmclean Date 2005-01-18 Time 15:12 Sent To  
Notes
2005-01-18 00:00:00DENIED, NEED TO PROVIDE TWO COPY OF
 SURVEY SHOWING THE ADDITION.(NEW
 BAYWINDOW ADDITION).NEED TO PULL
 SEPERATE PERMIT FOR FENCE & PROVIDE
 EASEMENT RELEASE (UTILITY) APPROVAL WITH
 SURVEY SHOWING THE LOCATION OF FENCE.
 CALLED CONTR FILE N FOR P/U MM