Plan Review Details - Permit 04121374
Plan Review Stops For Permit 04121374
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-11-15 Cont ID  
Sent By jwitmer Date 2006-11-15 Time 12:48 Rev Time 1.77
Received By jwitmer Date 2006-11-15 Time 12:48 Sent To PC
Notes
2006-11-15 12:49:38ROOF REVISION 05090092 MET ROOFING METAL STANDING SEAM
 ROOF PANEL 04-0518.04.
 FL S S 489.113(B) METAL ROOFING TO BE INSTALLED BY A
 LICENSED ROOFING CONTRACTOR, NOT G.C.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-07-03 Cont ID  
Sent By jwitmer Date 2006-07-03 Time 13:28 Rev Time 1.11
Received By jwitmer Date 2006-07-03 Time 13:28 Sent To PC
Notes
2006-07-03 00:00:00RESTAMP TRUSS PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-06-14 Cont ID  
Sent By jwitmer Date 2006-06-14 Time 15:52 Rev Time 2.22
Received By jwitmer Date 2006-06-14 Time 15:52 Sent To PC
Notes
2006-06-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04121374
 ADD: 2216 PALM BEACH LAKES BLVD
 CONT: ODUM CONSTRUCTION
 TEL: (561)997-6698
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW- REVISION
 ACTION: DENIED
  
 REVISION TO INCREASE THE WINDOW SIZES
 FROM (14) 3'-0"X4'-0" TO (14)
 3'-0"X5'-0" WINDOWS DENIED. SEE REVISION
  
 FILED MAY 31,2006, 2 MONTHS AFTER THE
 DENIEL FROM THE CONSTRUCTION BOARD OF
 AJUSTMENT & APPEAL. THE OWNER FILED FOR
 A VARIANCE FOR THE MARCH MARCH 16, 2006
 BOARD MEETING, OUTCOME DENIED FOR THE
 ENLARGEMENT OF EAST WINDOWS, CASE# 1293.
  
 MARCH 17,2005, BOARD OF ADJUSTMENT AND
 APPEAL CASE# 1272 IN THE DOCUMENT THE
 APPLICANT PROPOSES THE FOLLOWING
 VARIANCE. CODE SECTION 705.1.1.2CODE
 REQUIRES OPENINGS WITHIN 15 FT OF THE
 PROPERTY LINE TO OPENING PROTECTIVES.
 REQUEST FIRE SPRINKLERS INSIDE AND OUT
 IN LEU OF FIRE RATED GLASS. THERE IS NO
 MENTION OF BEING OVER THE ALLOWED 10%
 OPENINGS. THE CASE IS GRANTED FOR THE
 USE OF A FIRE CURTAIN INSIDE AND OUT
 INSTEAD OF FIRE RATED GLASS.
  
  
 1/06/06 THIRD REVIEW
 FOURTH COMMENT:
 4) PLANS A-12 INDICATE THAT THE WINDOWS
 ON THE EAST SIDE HAVE INCREASED.WHEN THE
 APPLICANT WENT TO THE BOARD OF
 ADJUSTMENT AND APPEAL FOR TABLE 600 AS
 WELL AS OPENING PROTECTIVES (705.1.1.2)
 THE DESIGN WAS 23% OVER THE ALLOWABLE
 OPENING SIZE FOR 5'-10' FROM THE
 PROPERTY LINE. WITH THE INCREASE IN
 OPENING SIZE THE OVERAGE HAS INCREASED
 TO 50% OVER THE ALLOWABLE SIZE AND A 27%
 ALLOWABLE OPENINGS APPROVED BY THE
 BOARD.
  
 1/21/05 FIRST REVIEW
 SIXTH COMMENT:
 6) DEMO PLAN INDICATES EITHER NEW OR
 ENLARGED OPENINGS ON THE EAST SIDE OF
 THE BUILDING:
  
 6A) SITE PLAN INDICATES THE EAST SIDE OF
 THE BUILDING IS APPROXIMATELY 5'-0"
 AWAY FROM THE PROPERTY LINE. 705.1.1.2.
 REQUIRES AT ALL OPENINGS WITHIN 15' OF
 THE PROPERTY LINE SHALL BE EQUIPPED WITH
 APPROVED OPENING PROTECTIVES.
  
 6B) THE EAST WALL OF THE BUILDING SHALL
 HAVE NO MORE THAN 10% OPENINGS IN THE
 WALL , THE PROPOSED OPENINGS ARE AT
 APPROXIMATELY 27%. SEE TABLE 600, TYPE
 VBUILDING. WALL AREA IS FIGURED FLOOR TO
 CEILING THE LENGTH OF THE BUILDING.
  
 6C) NOTE FOR FIRE RATED GLASS THERE IS
 NO LARGE MISSLE IMPACT TESTED WINDOWS OR
 DOORS. STORM SHUTTERS WILL BE REQUIRED
 FOR THESE OPENINGS. THE REMAINDER OF THE
 BUILDING COULD BE EITHER SHUTTERED OF
 LARGE MISSLE IMPACT TESTED GLAZING.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-02-03 Cont ID  
Sent By jwitmer Date 2006-02-03 Time 14:55 Rev Time 2.22
Received By jwitmer Date 2006-02-03 Time 14:55 Sent To PC
Notes
2006-02-03 00:00:00REVISION STRUCTURAL 11-30-05

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-01-20 Cont ID  
Sent By jwitmer Date 2006-01-20 Time 07:55 Rev Time 3.33
Received By jwitmer Date 2006-01-20 Time 07:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-01-06 Cont ID  
Sent By jwitmer Date 2006-01-06 Time 08:19 Rev Time 2.22
Received By jwitmer Date 2006-01-06 Time 08:19 Sent To PC
Notes
2006-01-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04121374
 ADD: 2216 PALM BEACH LAKES BLVD
 CONT: K & M COMMERCIAL
 TEL: (561)383-2817
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY.
 ***********IMPORTANT***********
 CORALATE PLANS INTO TWO COMPLETE
 "STAPLED SETS OF PLANS.
 A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT#7 FROM THE PEVIOUS REVIEW,
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STRUCTURAL COMPONENTS- TRUSS ABCHORS
 B1) ROOF- THERE IS (2) SEPERATE TYPES OF
 METAL ROOF REPORTS SUBMITTED. AEICOR
 SS-2-21 STANDING METAL ROOF PANEL,
 PRESSURES ARE LOW, SEE SYSTEMS
 LIMITATION. REMOVE THE REPORTS NOT USED.
 B2) ULTRAGUARD PVC WOOD DECK, PICK WHICH
 SYSTEM IS TO BE USED SEE PAGES 11-17,
 ALSO NOTE ON EACH SYSTEM THE SYSTEM
 LIMITATION NOTE MAXIMUM DESIGN PRESSURE
 OF 45 PSF AND SYSTEM LIMITATION# 9 NO
 INCREASE ALLOWED !!!!!!!!!! SEE TABLE
 1606.2B ZONE# 310 SQ FT= -89PSF
 ZONE# 3 20 SQ FT = -73.8PSF REQUIRED!!!!
  
 4) PLANS A-12 INDICATE THAT THE WINDOWS
 ON THE EAST SIDE HAVE INCREASED.WHEN THE
 APPLICANT WENT TO THE BOARD OF
 ADJUSTMENT AND APPEAL FOR TABLE 600 AS
 WELL AS OPENING PROTECTIVES (705.1.1.2)
 THE DESIGN WAS 23% OVER THE ALLOWABLE
 OPENING SIZE FOR 5'-10' FROM THE
 PROPERTY LINE. WITH THE INCREASE IN
 OPENING SIZE THE OVERAGE HAS INCREASED
 TO 50% OVER THE ALLOWABLE SIZE AND A 27%
 ALLOWABLE OPENINGS APPROVED BY THE
 BOARD.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-02 Cont ID  
Sent By jwitmer Date 2005-09-02 Time 16:28 Rev Time 0.00
Received By jwitmer Date 2005-09-02 Time 15:17 Sent To  
Notes
2005-09-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04121374
 ADD: 2216 PALM BEACH LAKES BLVD
 CONT: K & M COMMERCIAL
 TEL: (561)383-2817
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT#7 FROM THE PEVIOUS REVIEW,
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SKYLIGHTS
 B) STRUCTURAL COMPONENTS- TRUSS ABCHORS
 C) ROOF- AEICOR SS-2-21 STANDING METAL
 ROOF PANEL, PRESSURES ARE LOW, SEE
 SYSTEMS LIMITATION ENHANCED FASTENING
 BY A LICENSED ARCHITECT, ENGINEER OR
 REGISTERED ROOF CONSULTANT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-21 Cont ID  
Sent By jwitmer Date 2005-01-21 Time 09:56 Rev Time 4.55
Received By jwitmer Date 2005-01-21 Time 09:12 Sent To  
Notes
2005-01-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04121374
 ADD: 2216 PALM BEACH LAKES BLVD
 CONT: K & M COMMERCIAL
 TEL: (561)383-2817
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SEE SHEET A-7 DOOR 152A MISSING THE
 REQUIRED 18" ON PULL SIDE.11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARENCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARENCES
 SHALL BE CLEAR & LEVEL.
  
 3) ELECTRIC PLAN INDICATES A GENERATOR
 AND FUEL TANK BUT NO INDICATION IS ON
 THE SITE PLAN?
  
 4) DISCEPANCY STRUCTURAL PLANS INDICATE
 A DRIVE THROUGH BUT A-6 DOESN'T INDICATE
  
 ANY FOOTERS, COLUMNS ETC
  
 5) THE PLANS SUBMITTED SHALL BE
 REVIEWED
 AS A NEW BUILDING. CHAPTER 3401.7.2.6
 WHEN OVER 50% OF THE EXISTING BUILDING
 ARE MADE DURING ANY 12 MONTH PERIOD, THE
 BUILDING SHALL BE MADE TO CONFORM TO THE
  
 REQUIREMENTS FOR A NEW BUILDING OR BE
 ENTIRELY DEMOLISHED.
  
 6) DEMO PLAN INDICATES EITHER NEW OR
 ENLARGED OPENINGS ON THE EAST SIDE OF
 THE BUILDING:
 6A) SITE PLAN INDICATES THE EAST SIDE OF
 THE BUILDING IS APPROXIMATELY 5'-0"
 AWAY FROM THE PROPERTY LINE. 705.1.1.2.
 REQUIRES AT ALL OPENINGS WITHIN 15' OF
 THE PROPERTY LINE SHALL BE EQUIPPED WITH
  
 APPROVED OPENING PROTECTIVES.
 6B) THE EAST WALL OF THE BUILDING SHALL
  
 HAVE NO MORE THAN 10% OPENINGS IN THE
 WALL , THE PROPOSED OPENINGS ARE AT
 APPROXIMATELY 27%. SEE TABLE 600, TYPE
 V
 BUILDING. WALL AREA IS FIGURED FLOOR TO
 CEILING THE LENGTH OF THE BUILDING.
 6C) NOTE FOR FIRE RATED GLASS THERE IS
 NO LARGE MISSLE IMPACT TESTED WINDOWS OR
  
 DOORS. STORM SHUTTERS WILL BE REQUIRED
 FOR THESE OPENINGS. THE REMAINDER OF THE
 BUILDING COULD BE EITHER SHUTTERED OF
 LARGE MISSLE IMPACT TESTED GLAZING.
  
 7) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED & OPERTABLE
 B) MULLIONS
 C) EXTERIOR DOORS
 D) SKYLIGHTS
 E) STRUCTURAL COMPONENTS- TRUSS
 ANCHORS
 F) ROOFING ASSEMBLIES
  
 9) 1707.4.5.1 MULLIONS OCCURRING BETWEEN
 INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11) 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 12) PROVIDE POSITIVE & NEGATIVE
 PRESSURES FOR ALL OPENINGS, INCLUDE
 END ZONES.
  
 13) A-21 INDICATES THE USE OF 5/8" CDX
 PLYWOOD FOR WALLS OD CUPALO, THIS IS A
 TYPE V BUILDING, WALLS TO BE
 NONCOMBUSTIBLE., ALSO IN A FIRE DISTRICT
  
 NO TYPE VI CONSTRUCTION.
  
 14) 3106.2 CANOPIES. WHEN LOCATED LESS
 THAN 30" FROM AN INTERIOR LOT LINE OR
 OTHER STUCTURE, THE CANOPY FRAME AND ITS
 SUPPORTS SHALL BE OF NONCOMBUSTILE
 MATERIAL, FIRE RESISTANT TREATED
 CONSTRUCTION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-01-19 Cont ID  
Sent By dpalmer Date 2006-01-19 Time 14:34 Rev Time 0.00
Received By dpalmer Date 2006-01-19 Time 14:34 Sent To  
Notes
2006-01-19 00:00:00REDLINED ESP SHEETS TO SEE WIND LOAD
 CALCS DONE BY ENGINEER.
 PER FBC 140 MPH.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-12-09 Cont ID  
Sent By btrobaug Date 2005-12-09 Time 09:15 Rev Time  
Received By dpalmer Date 2005-12-09 Time 07:26 Sent To  
Notes
2005-12-09 00:00:00** UNSAT **
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
  
  
 1)NOTE: NOTE #1 NO.
 PLEASE SUBMIT MANUFACTURES CUT/SPEC
 SHEETS WHICH WILL CORRELATE WITH PLANS
 DRAWING SUBMITTED.
 PLEASE SEE GENERATOR SPECS SUBMITTED DO
 NOT INDICATE A 75KW GEN, PLEASE SEE THE
 ONLY REFERENCE TO ANY 75KW GEN,
 INDICATES AMPERAGE RATING AT 142A'S,
 WHEN DERATED LOAD IS 189A'S?
 PLEASE ALSO BEAR IN MIND, THE RATING OF
 A NATURAL GAS GENERATOR IS TYPICALLY
 LESS THAN THE KW LISTED FOR LP.
 PLEASE ALSO SEE NO SPECS/SHEETS FOR ATS
 COULD BE LOCATED ON PACKAGES.
  
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO,
 PLEASE SUBMIT THE SIGNED, DATED AND
 SEALED WIND LOADING CALCULATIONS AS
 REQUESTED.
 IT WAS NOTED THAT THERE IS A LIGHTING
 SUBMITTIAL PACKAGE, HOWEVER THIS ONLY
 REFERENCES TO FIXTURES,POLES ETC WITH
 OUT PROVIDING INFORMATION NEEDED.
 PLEASE KNOW, IF SITE LIGHTING PLAN MAY
 BE DELETED FROM PACKAGE, HOWEVER,A
 SEPARATE PERMIT APPLICATION, PLANS, FEES
 ETC WILL BE REQUIRES BEFORE ANY SITE
 LIGHTING MAY START.
 NOTE WAS ADDED TO ESP SHEETS WITH
 REFERENCE TO FBC 140.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 NO, PLEASE SEE ALL SETS
 ARE STILL SUBMITTED AS INDIVIDUAL SHEETS
 AND SETS ARE NOT PLACED AND ATTACHED
 TOGETHER.
  
 6)NOTE: NOTE #6 OK, HOWEVER PLEASE SEE
 NOTE #1, AS RATING OF GEN IS STILL TO BE
 VERIFIED.
  
 7)NOTE: NOTE #7 OK.
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE: NOTE #12 NO, TO BE VERIFIED,
 SEE NOTE #1.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK.
  
 PLEASE BE SURE TO SUBMIT THE ABOVE
 INFORMATION FOR REVIEW.
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-01 Cont ID  
Sent By dpalmer Date 2005-09-04 Time 13:08 Rev Time 1.75
Received By dpalmer Date 2005-09-01 Time 13:08 Sent To  
Notes
2005-09-04 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SUBMIT MANUFACTURE
 SPEC/CUT SHEETS FOR GENERATOR, AUTOMATIC
 TRANSFER SWITCH, AND ANY SUB-BASE FUEL
 TANK.
 PLEASE BE SURE ALL INDICATE LISTINGS
 FROM A NRTL.
 PLEASE BE SURE DISCONNECTING MEANS IS
 RATED AS "SERVICE EQUIPMENT" 225.36.
  
 2)NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTS PERTAING TO CHAPTER 34 OF THE
 FBC. PLEASE SEE ANY REQUIREMENTS WHICH
 MAY AFFECT ELECTRICLA PLANS.
  
 3)NOTE: PLEASE SUBMITWIND LOADING
 CALCULATIONS FOR NEW SITE LIGHTING
 POLES.
 MUST MEET FBC 140 MPH.
  
 4)NOTE: PLEASE SEE THAT ARCHITECTS TITLE
 BLOCK CONTAINS THE "PRINTED NAME AND
 LICENSE NUMBER" FOR THE ARCHITECT. FAC
 61G1-16.004
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 5)NOTE: PLEASE SUBMIT SETS OF PLANS
 ATTACHED TOGETHER INTO SETS. PLEASE SEE
 PLANS WERE SUBMITTED AS INDIVIDUAL
 SHEETS.
 PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE
 REMOVED AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 6)NOTE: PLEASE SEE LOADS INDICATED FOR
 RTU'S ON EDP, MUST BE FIGURED AS ALL
 LOADS ON AND UNDER HEAT UNLESS AN
 AUTOMATIC MEANS OF LOAD SHEDDING IS
 PROVIDED.
 IF LOAD SHEDDING WILL BE USED, PLEASE
 PROVIDE A WIRING DETAIL (ETC) FOR
 METHOD, WIRING TO BE USED.
 702.5
  
 7)NOTE: PLEASE SEE LOADS ON OPTIONAL
 BACK -UP POWER. PLEASE SEE GENERAL
 LTS.RECEPTS LOADS ARE PERMITTED TO BE
 DE-RATED, HOWEVER ANY CONNECT MOTOR
 LOADS, APPLIANCE LOADS, MUST BE FIGURED
 AT 100%.
  
 8)NOTE: PLEASE SEE 210.8B3 IN KITCHENS
 OTHER THAN IN DWELLING UNITS WHICH
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 9)NOTE: PLEASE SEE THAT PLANS SHOULD
 ALSO INDICATE SIGNAGE REQUIRED AT
 DISCONNECTING MEANS AT ELECTRICAL ROOM
 FOR GENERATOR FEED.
 PLEASE VERIFY HOW NEW GENERATOR WILL GET
 TO EXISTING ELECTRICAL RM?
 PLEASE SEE A DISCONNECTING MEANS AT BLDG
 MAY ALSO BE REQUIRED IF FED OVERHEAD
 INTO BLDG.. IF GEN IS FED FROM OUTSIDE
 BLDG (AROUND) OR UNDER GROUND, THIS DISC
 AT ELECTRICAL ROOM WILL BE OK.
 225.31,225.34,110.27
  
 10)NOTE: PLEASE SEE NOTES ON ELECTRICAL
 RISER DIAGRAM PAGE WHICH NOTES PANEL
 "MPD", THIS SEEMS TO BE A MISPRINT?
 PLEASE CORRECT.
  
 11)NOTE: PLEASE SEE FIRE REVIEW NOTES:
 PLEASE SEE A "KNOX BOX" MAY BE REQUIRED
 AND LOCATION DETERMINED BY FIRE MARSHALS
 OFFICE.
 PLEASE SEE FIRE ALARM CONTROL PANEL AND
 GENERATOR ANNUNCIATOR PANEL SHALL BE
 GROUPED. THIS LOCATION WILL ALSO BE
 NOTED BY TH FMO.
 PLEASE SHOW GAP ON PLANS.
  
 12)NOTE: PLEASE VERIFY OCP AT GENERATOR,
 AS 70KW 3/0 120/208V DOES NOT SEEM TO
 PROVIDE 250A'S???
 215.5
  
 13)NOTE: PLEASE CORRELATE ELECTRICAL RM
 LAYOUT WITH ELECTRICAL POWER PLANS FOR
 LOCATIONS OF EQUIPMENT.
 215.5
  
 14)NOTE: PLEASE CORRELATE WATER HEATERS
 AND LOADS SHOWN.
 PLEASE SEE LOAD CALCS SHOWS 24KW, YET
 PANEL "C" ALSO SHOWS AN 11KW WH?
 PLEASE ALSO SEE CIRCUITING SHOWS PUMP
 AND WH?
 PLEASE SEE 422.11F FOR UNITS OVER 48A'S.
 SHOWS A SINGLE OCP FOR UNIT??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 REVIEW WAS UNDER 05080456

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-10 Cont ID  
Sent By dpalmer Date 2005-01-10 Time 13:28 Rev Time 2.00
Received By dpalmer Date 2005-01-10 Time 07:59 Sent To  
Notes
2005-01-10 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE CORRELATE ITEMS SHOWN ON
 PLANS WITH PANEL SCHEDULE.
 PLEASE SEE PLANS INDICATE A 30KW WATER
 HEATER, YET THIS COULD NOT BE LOCATED?
 PLEASE SEE 422 FOR MANY ITEMS REQUIRED
 FOR LARGE WATER HEATER UNITS OVER 48A'S.
 MIN OCP 125%, MAX 150%.
  
 2)NOTE: PLEASE VERIFY REQUIRED SIGN
 CIRCUIT PER 600.5EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY
 ACCESSIBLE TO PEDESTRIANS SHALL BE
 PROVIDED WITH AT LEAST ONE OUTLET IN AN
 ACCESSIBLE LOCATION AT EACH ENTRANCE TO
 EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING SYSTEM USE. THE OUTLET(S) SHALL
 BE SUPPLIED BY A BRANCH CIRCUIT RATED AT
 LEAST 20 AMPERES THAT SUPPLIES NO OTHER
 LOAD.
  
 3)NOTE: PLEASE SEE ONE OF THE ELECTRICAL
 RMS SHOWN ON PLANS FOR ATS MENTIONS
 "CLOSET". PLEASE SEE 110.26, 408.7,
 240.24 FOR PANELS NOT PERMITTED ON
 CLOSETS/ STORAGE AREAS. ETC.
  
 4)NOTE: PLEASE SEE225.31,.32,.36 FOR
 MISSING MEANS OF DISC FOR FEEDER FROM
 GENERATOR.
 PLEASE ALSO SEE GROUPING OF
 MAINS.230.72
  
 5)NOTE: PLEASE SUBMIT MALL MANUFACTURE
 SPECS FOR GEN/ ATS/ FUEL TANKS ETC
 PLEASE BE SURE A LISTING FROM A NRTL IS
 SHOWN.
 PLEASE SEE 700.8, 702.8 FOR NOTE TO
 PLACED ON PLANS.
 A SIGN SHALL BE PLACED AT THE SERVICE
 ENTRANCE EQUIPMENT INDICATING TYPE AND
 LOCATION OF ON-SITE EMERGENCY POWER
 SOURCES.
  
 6)NOTE: PLEASE CORRELATE RTU'S ON PLANS
 AND PANEL SCHEDULES.
 KW RATINGS DO NOT SEEM TO CORRELATE.
 RTU#1, #2
  
  
 7 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 8)NOTE: PLEASE SUBMIT WIND-LOADING FOR
 NEW POLES/ FIXTURES.
 MUST BE AT THIS TIME AND MUST MEET FBC
 140 MPH.
  
 9)NOTE: PLEASE PROVIDE NOTE/ INFORMATION
 ON TYPE OF ENCLOSURE FOR GEN.
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-12-06 Cont ID  
Sent By mcarsill Date 2005-12-06 Time 12:46 Rev Time 0.00
Received By mcarsill Date 2005-12-06 Time 12:38 Sent To  
Notes
2005-12-06 00:00:001. ALL PREVIOUSLY CITED PLAN REVIEW
 NOTES BY FIRE RESCUE HAVE BEEN ANSWERED
 ON THE PLANS WITH COMMENTS PROVIDED ON
 THE OCTOBER 12, 2005 LETTER FROM THE
 ARCHITECT.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-09-13 Cont ID  
Sent By mwennerg Date 2005-09-13 Time 11:07 Rev Time 0.00
Received By mwennerg Date 2005-09-13 Time 11:07 Sent To  
Notes
2005-09-13 00:00:00******DENIED******
  
 1) PLEASE SEE FIRST FIRE REVIEW
 COMMENTS. IT DOES NOT APPEAR THAT
 COMMENTS HAVE BEEN ADDRESSED. PLEASE
 RESPOND TO ALL COMMENTS WITH A RESPONSE
 LETTER AND SHOW REVISIONS ON DRAWINGS TO
 HELP EXPEDITE THIS PROCESS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By nmccray Date 2005-01-24 Time 11:44 Rev Time 0.00
Received By nmccray Date 2005-01-24 Time 09:49 Sent To  
Notes
2005-01-24 00:00:001) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 4) INTERIOR WALL AND CEILING FINISH
 SHALL COMPLY WITH NFPA 101 LIFE SAFETY
 CODE 2000 EDITION CHAPTER 38.3.3.2.
 INTERIOR WALL AND CEILING FINISH
 COMPLYING WITH 10.2.3 SHALL BE CLASS A
 OR CLASS B IN EXITS AND IN ENCLOSED
 CORRIDORS FURNISHING ACCESS TO EXITS;
 AND CLASS A, CLASS B, OR CLASS C IN
 OFFICE AREAS.
  
 5) ALL EXIT DOORS SHALL COMPLY WITH NFPA
 101 CHAPTER 7.2.1.
  
 6) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
 7) ALL FIRE ALARM SYSTEMS THAT SUPERVISE
 FIRE SPRINKLER SYSTEMS SHALL BE UL
 CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 8) PLEASE PROVIDE CUT SHEETS FOR CANVAS
 AWING SHOWING PROOF FIRE RESISTANT
 TREATED.
  
 9) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS REMODEL.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-06-12 Cont ID  
Sent By pschmitz Date 2006-06-12 Time 10:58 Rev Time 0.00
Received By pschmitz Date 2006-06-12 Time 10:58 Sent To  
Notes
2006-06-12 00:00:00REVISION SUBMITTED.
 SIGNED AND SEALED BY ENG OF RECORD
 CHANGE U/G PIPING TO PE 1-1/4"
 CHANGE TO 2# PSI SSSTEM

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-04-25 Cont ID  
Sent By pschmitz Date 2006-04-25 Time 14:43 Rev Time 0.00
Received By pschmitz Date 2006-04-25 Time 14:42 Sent To  
Notes
2006-04-25 00:00:00APPROVED PLANS CHANGED TO 2#PSI
 ENGINEER OF RECORD SEAL REQUIRED.
 PERMIT APPLICATION #06041057

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By pschmitz Date 2006-01-20 Time 14:30 Rev Time 0.00
Received By pschmitz Date 2006-01-20 Time 14:31 Sent To  
Notes
2006-01-20 00:00:00OK TO ISSUE GAS PERMIT PER REVIEWED
 PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 15:26 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 15:26 Sent To M
Notes
2006-12-17 15:27:51TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 14:44 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 14:44 Sent To M
Notes
2006-11-21 14:44:53TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 11:24 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 11:23 Sent To B
Notes
2006-10-24 11:24:19TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-06-28 Cont ID  
Sent By adarroug Date 2006-06-28 Time 11:25 Rev Time 0.00
Received By adarroug Date 2006-06-28 Time 11:25 Sent To B
Notes
2006-06-28 00:00:00TO "JWITMER" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-05 Cont ID  
Sent By adarroug Date 2006-06-05 Time 13:46 Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 13:46 Sent To B
Notes
2006-06-05 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-01 Cont ID  
Sent By adarroug Date 2006-02-01 Time 17:41 Rev Time 0.00
Received By adarroug Date 2006-02-01 Time 17:41 Sent To B
Notes
2006-02-01 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-31 Cont ID  
Sent By adarroug Date 2006-01-31 Time 16:21 Rev Time 0.00
Received By adarroug Date 2006-01-31 Time 16:21 Sent To Z
Notes
2006-01-31 00:00:00TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-17 Cont ID  
Sent By adarroug Date 2006-01-20 Time 10:19 Rev Time 0.00
Received By rbrown Date 2006-01-17 Time 10:19 Sent To  
Notes
2006-01-20 00:00:00GIVEN TO PAUL SCHMITZ FOR LAST REVIEW.
 AFTER REVIEW, PAUL WILL GIVE TO LUIS
 MARTINEZ FOR PROCESSING.
  
  
2006-01-17 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 08:20 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 08:20 Sent To  
Notes
2005-11-15 00:00:00TO "COMM" BD#54
2005-10-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2005-09-04 Time   Rev Time 0.00
Received By dpalmer Date 2005-09-04 Time 13:08 Sent To  
Notes
2005-09-04 00:00:00TO COMM BOARD ON 8/11 SPACE #40

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-28 Cont ID  
Sent By mjacobs Date 2005-01-21 Time   Rev Time 0.00
Received By mjacobs Date 2004-12-28 Time 07:12 Sent To  
Notes
2004-12-28 00:00:00TO COMM BD#54

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-01-03 Cont ID  
Sent By pkrauss Date 2007-01-03 Time 13:17 Rev Time 0.00
Received By pkrauss Date 2007-01-03 Time 13:17 Sent To  
Notes
2007-01-03 13:18:30REVISION / DUCT SIZES PLAN SHEET M-1 & M-2

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-11-30 Cont ID  
Sent By pkrauss Date 2006-11-30 Time 06:55 Rev Time 0.00
Received By pkrauss Date 2006-11-30 Time 06:55 Sent To  
Notes
2006-11-30 06:59:27DENIED:
 PLANS MUST BE SIGNED, SEALED AND DATED BY THE ENGINEER
 OF RECORD IN ACCORDANCE WITH FS471.025.SHOP DRAWINGS
 ARE NOT ACCEPTABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2006-01-19 Cont ID  
Sent By pkrauss Date 2006-01-19 Time 16:52 Rev Time 0.00
Received By pkrauss Date 2006-01-19 Time 16:30 Sent To P
Notes
2006-01-19 00:00:00NEW M-3 SHEET / ROOF DRAINAGE CALCS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-12-13 Cont ID  
Sent By pkrauss Date 2005-12-13 Time 06:52 Rev Time 0.55
Received By pkrauss Date 2005-12-13 Time 06:38 Sent To  
Notes
2005-12-13 00:00:00HVAC PLANS ARE APPROVED.ADDITIONAL
 INFORMATION REQUIRED FOR THE GENERATOR.
 SEE COMMENTS BY DEWEY PALMER, ELECTRICAL
 PLANS EXAMINER.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-09-22 Cont ID  
Sent By pkrauss Date 2005-09-22 Time 07:50 Rev Time 2.00
Received By pkrauss Date 2005-09-22 Time 07:50 Sent To  
Notes
2005-09-22 00:00:00DENIED:
 1.PLAN SHEET A-11 INDICATES 19'8" TO
 THE TOP OF THE PARAPET.PLEASE INDICATE
 ROOF ACCESS FOR EQUIPMENT MAINTENANCE.
 PER 2001 FBC(M)306.5 EQUIPMENT LOCATED
 ON A ROOF AT A HEIGHT GREATER THAN 16FT,
 A PERMANENT MEANS OF ACCESS WILL BE
 REQUIRED.PLEASE INDICATE ACCESS.
  
 2.PLAN SHEET P-2 INDICATES EMERGENCY
 GENERATOR.PLEASE PROVIDE DISTANCE FROM
 OPENINGS (DOORS, & WINDOWS) 2001
 FBC(M)401.5.2.SITE PLAN DOES NOT
 INDICATE LOCATION OF EMERGENCY
 GENERATOR.PLEASE NOTE PER 2001 FBC(M)
 EQUIPMENT INSTALLED IN LOCATION WHERE
 SUBJECT TO DAMAGE SHALL BE PROTECTED BY
 APPROVED BARRIERS.PLEASE PROVIDE
 SUBMITTAL FOR THE GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2005-01-13 Time   Rev Time 0.00
Received By hmoser Date 2005-01-13 Time 08:34 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By pschmitz Date 2006-01-20 Time 14:36 Rev Time 0.00
Received By pschmitz Date 2006-01-20 Time 14:33 Sent To  
Notes
2006-01-20 00:00:00 
 PROVISO:
 SEPERATE PERMIT REQUIRED.
 CERTIFIED OR REGISTERED PLUMBING
 CONTRACTOR ONLY.
 MED GAS CERTIFICATES WITH APPLICATION
 FOR PERMIT.
 PLUMBING COMPANY,
 INSTALLER,
 BRAZER.
 WITH PHOTO ID FOR EACH WORKER TO COMPLY
 WITH NFPA 99-C TO OBTAIN A PERMIT.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-01-20 Cont ID  
Sent By pschmitz Date 2006-01-20 Time 14:45 Rev Time 0.00
Received By pschmitz Date 2006-01-20 Time 14:45 Sent To  
Notes
2006-01-20 00:00:00PROVISO:
 1) SHT A-24ELEVATION DETAILS:
 COMPLLY WITH FBC 2001 ACCESSIBILITY CODE
 CH 11, SEC 11-4.22.2 DOORS
 ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH SEC 11-4.13 DOORS,
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
  
 2) SEPERATE IRRIGATION PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-12-17 Cont ID  
Sent By pschmitz Date 2005-12-17 Time 15:50 Rev Time 0.00
Received By pschmitz Date 2005-12-17 Time 15:51 Sent To  
Notes
2005-12-21 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
  
 REVIEW COMMENTS DATED SEPT. 23 2005
 (ORIGINAL COMMENTS)
 3. ROOF DRAINAGE REF TO SHT M-3
 NOT IN ROLL PLANS NOR DRAWING INDEX.
 4.5.7. SAYS SEE ARCHITECTURAL.
 NOT ADDRESSED.
 8.DATA SUPPLIED BY PLBG CONTRACTOR,
 DENIED. NOT AS SPECIFIED ON SHT P-1
 11.WATER FEATURE HOSE BIBB.
 REF TO SHT P-4, SHT-4 NOT IN ROLL PLANS
 NOR DRAWING INDEX.
 (NEW COMMENTS)
 1B.PROVIDE INFORMATION AS REQUESTED,
 SEC 104.2.1
 2B MEDICAL GAS SHALL BE NOTED, SEPETATE
 PLANS AND PERMIT TO COMPLY WITH THE
 LATEST EDITIONNFPA 99-C
 3B,4BA,B,C,D,E,F,G ALL REFERE TO A WATER
 HEATER LISTED ON SHT P-4, NOT IN THE
 ROLL PLANS NOR IN THE DRAWING INDEX.
  
 WHEN RE- SUBMITTING PLANS PLEASE SUBMITT
 A TRANSMITTAL LETTER FOR ALL DISCIPLINES
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE. IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-09-19 Cont ID  
Sent By kstevens Date 2005-09-19 Time 10:51 Rev Time 6.25
Received By kstevens Date 2005-09-10 Time 23:59 Sent To  
Notes
2005-09-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 NFPA 99C GAS & VACUUM SYSTEMS
  
 A. FROM PREVIOUS REVIEW: COMMENT NUMBERS
 TO STAY THE SAME AS FIRST REVIEW:
 3) SHT A-9 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, AND 1107 AND ALL
 SUBSECTIONS. SHOW TOTAL SQUARE FOOTAGE
 FOR ROOF, AND SHOW 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS ADDED
 TO SQUARE FOOTAGE. ALSO IN CALCULATION,
 SHOW THE AREA OF ANY ROOF DRAINING ONTO
 THE ROOF FROM ABOVE. SHOW THE LOCATION
 OF ALL PRIMARY AND SECONDARY ROOF
 DRAINS. SECTION 104.2.1. - COMMENT
 RESPONSE NOTED ON SHT A-9 NOTE #3.
 ALTHOUGH NO NEW ROOF AREA IS ADDED, NEW
 VERTICAL AREAS FROM THE MANSARD ROOF ON
 THREE SIDES OF ROOF AND THE VERTICAL
 WALLS OF THE CUPOLA WILL ADD TO THE
 SQUARE FOOTAGE PER SECTION 1106.4. ALSO
 AS INDICATED IN NOTE #3 THE ROOF HAS NO
 ROOF DRAINS, BUT THE GUTTER AND
 DOWNSPOUTS SHALL BE SIZED PER SF OF THE
 ROOF, TABLE 1106.6 AND DOWNSPOUTS PER
 TABLE 1106.2.
 4) SHTS A-16 & A-17 LOUNGE SINKS SHALL
 COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. (FORWARD APPROACH CLEAR
 FLOOR SPACE REQUIRED). SUBMIT DETAILS. -
 RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS REQUIRED:
 DETAILS #9 & 10 SHT A-16 & #11 A-17
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH - SINK MODEL
 INDICATED IS 7-11/16", AND MAX DEPTH IS
 6-1/2"
 D. 11-4.24.5 CLEAR FLOOR SPACE -
 FORWARD APPROACH IS REQUIRED AND SHALL
 EXTEND A MAXIMUM 19" UNDERNEATH THE SINK
 - CABINET DOORS ARE NOT ALLOWED IN THE
 CLEAR FLOOR SPACE.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 (N1) GARBAGE DISPOSAL CAN NOT BE IN THE
 CLEAR FLOOR SPACE FOR THE SINK.
 SHT A-5 INDICATES A SINK IN THE OWNERS
 LOUNGE, BUT DETAIL #9 SHT A-16 DOES NOT
 SHOW THE SINK. PLEASE CLARIFY. SECTION
 104.2.1.
 5) SHT A-24 DETAILS 1, 2, 3, & 4 THE
 WATER CLOSETS SHALL BE 18" FROM
 CENTERLINE OF THE FIXTURE TO THE WALL.
 SEE FIG 28. THE LAV SHALL BE MINIMUM 15"
 FROM THE CENTERLINE OF THE FIXTURE TO
 THE WALL. (CENTERED ON CLEAR FLOOR SPACE
 30" MEASUREMENT). - DETAIL #4
 INFORMATION REQUIRED NOT SHOWN.
 7) SHT A-24 DETAIL 5, PRIVATE RESTROOM
 TO BE ADAPTABLE. SECTION 11-4.1.3(11).
 SUBMIT DETAILS SHOWING BACKING FOR GRAB
 BARS AT W/C & SHOWER. SHOW W/C AT 18" TO
 CENTERLINE OFF WALL, LAV TO BE MINIMUM
 15" TO CENTERLINE OFF WALL, SHOWER SHALL
 SHOW BACKING FOR SEAT (IF REQUIRED -
 INDICATE SIZE OF SHOWER), SHOW LOCATION
 OF CONTROLS, AND SHOW CURB SIZE, (MAX.
 1/2") IF PROVIDED. ALSO SHOW 5' TURNING
 AREA. SEE SECTIONS 11-4.16, 11-4.19,
 11-4.21. 11-4.22. - PER SECTION
 11-4.21.2 THE SIZE OF THE SHOWER STALL
 SHALL COMPLY WITH FIGURE 35(A) OF 35(B).
 THE SIZE OF THE SHOWER STALL SHOWN DOES
 NOT COMPLY WITH EITHER. - NO CURB HEIGHT
 IS SHOWN.
 ***NOTE ALL PLUMBING SHEETS HAVE BEEN
 RENUMBERED****
 8) SHT P0.1 PLUMBING FIXTURE SCHEDULE,
 SUBMIT MANUF SPECIFICATION SHEETS FOR
 THE TANKLESS WATER HEATERS. LISTING IS
 REQUIRED. SECTION 303.4. - NOW ON SHEET
 P-4, NO MANUF. SHEETS SUBMITTED.
 11) SHT P1.2 WATERFALL, INDICATE METHOD
 OF BACKFLOW PREVENTION REQUIRED ON THE
 WATER SUPPLY OF THE WATERFALL. SECTION
 608. KEYED NOTES #2. - NO RESPONSE
 NOTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 NO RESPONSE TO THIS REQUEST.
  
 ***************NEW COMMENTS*************
 1B. SHT P-1 SUBMIT MANUF. SPECIFICATION
 SHEETS FOR THE SCAVANGER SYSTEM. PLEASE
 SUBMIT MORE INFORMATION ON THE SYSTEM,
 AS IN THE INSTALLATION INSTRUCTIONS.
 SECTION 104.2.1.
 2B. SHT P-2 PLEASE INDICATE THE NUMBER
 OF OXYGEN TANKS AND THE AMOUNT OF OXYGEN
 TO BE STORED IN THE CLOSET. - IF MORE
 THAN ONE TANK TO BE USED ON THE MANIFOLD
 THAN AN AUTOMATIC SWITCH OVER WITH
 EXPLOSION PROOF VALVES ARE REQUIRED. - A
 VENT TO THE OUTSIDE IS REQUIRED FROM THE
 REGULATOR AND SHALL BE OF COPPER
 MATERIAL. - THE CLOSET SHALL BE VENTED.
 - A MASTER ALARM IS REQUIRED WITH
 PRESSURE INDICATOR AND RESERVE IN USE
 INDICATOR. - SOLID DOOR REQUIRED WITH A
 1 HOUR OR 2 HOUR FIRE RATING. (TO BE
 DETERMINED BY AMOUNT OF OXYGEN).
 CONTRACTOR SHALL APPLY FOR SEPARATE MED
 GAS PERMIT AND SHALL BE CERTIFIED AS A
 CONTRACTOR AND THE INSTALLER SHALL BE
 CERTIFIED WITH PICTURE I.D. AND
 CERTIFICATION AT TIME OF APPLICATION.
 3B. SHT P-2 THE FLOOR DRAIN FOR THE
 WATER HEATER IS NOT APPROVED AS AN
 INDIRECT WASTE RECEPTOR. A FLOOR SINK OR
 A HUB DRAIN WILL BE REQUIRED PER
 SECTIONS 802.3 & 802.3.2.
 4B. SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - NO ALL CUT SECTION
 LENGTHS SHOWN.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 5B. PLANS SHALL BE SUBMITTED AS SETS OF
 PLANS. LOOSE SHEETS NOT APPROVED.
 SECTION 104.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By kstevens Date 2005-01-24 Time 13:13 Rev Time 5.00
Received By kstevens Date 2005-01-22 Time 18:54 Sent To  
Notes
2005-01-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) IRRIGATION PLANS AND PERMIT ARE
 REQUIRED. SECTION 104.3.1.1.
 2) SHT A-3 IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINATE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5.
 3) SHT A-9 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106, AND 1107 AND ALL
 SUBSECTIONS. SHOW TOTAL SQUARE FOOTAGE
 FOR ROOF, AND SHOW 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS ADDED
 TO SQUARE FOOTAGE. ALSO IN CALCULATION,
 SHOW THE AREA OF ANY ROOF DRAINING ONTO
 THE ROOF FROM ABOVE. SHOW THE LOCATION
 OF ALL PRIMARY AND SECONDARY ROOF
 DRAINS. SECTION 104.2.1.
 4) SHTS A-16 & A-17 LOUNGE SINKS SHALL
 COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. (FORWARD APPROACH CLEAR
 FLOOR SPACE REQUIRED). SUBMIT DETAILS.
 5) SHT A-24 DETAILS 1, 2, 3, & 4 THE
 WATER CLOSETS SHALL BE 18" FROM
 CENTERLINE OF THE FIXTURE TO THE WALL.
 SEE FIG 28. THE LAV SHALL BE MINIMUM 15"
 FROM THE CENTERLINE OF THE FIXTURE TO
 THE WALL. (CENTERED ON CLEAR FLOOR SPACE
 30" MEASUREMENT).
 6) SHT A-24 DETAIL 4, TOILET ROOM 129
 SHALL BE ACCESSIBLE. "IF TOILET ROOMS
 ARE PROVEDED. THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH
 SECTION 11-4.22. SECTIONS 11-4.1.2(6) &
 11-4.1.3(11). SUBMIT DETAILS.
 7) SHT A-24 DETAIL 5, PRIVATE RESTROOM
 TO BE ADAPTABLE. SECTION 11-4.1.3(11).
 SUBMIT DETAILS SHOWING BACKING FOR GRAB
 BARS AT W/C & SHOWER. SHOW W/C AT 18" TO
 CENTERLINE OFF WALL, LAV TO BE MINIMUM
 15" TO CENTERLINE OFF WALL, SHOWER SHALL
 SHOW BACKING FOR SEAT (IF REQUIRED -
 INDICATE SIZE OF SHOWER), SHOW LOCATION
 OF CONTROLS, AND SHOW CURB SIZE, (MAX.
 1/2") IF PROVIDED. ALSO SHOW 5' TURNING
 AREA. SEE SECTIONS 11-4.16, 11-4.19,
 11-4.21. 11-4.22.
 8) SHT P0.1 PLUMBING FIXTURE SCHEDULE,
 SUBMIT MANUF SPECIFICATION SHEETS FOR
 THE TANKLESS WATER HEATERS. LISTING IS
 REQUIRED. SECTION 303.4.
 9) SHT P1.1 DEMO NOTES. NO DEAD ENDS ON
 THE SANT. SYSTEM. SECTION 704.5
 10) SHTS P1.1 & P5.1 ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 SECTION 909.1 (SEE ALL BATHROOM GROUPS -
 AND REDLINE EXAMPLES ON ONE SET OF SANT.
 RISERS). SECTION 909.1
 11) SHT P1.2 WATERFALL, INDICATE METHOD
 OF BACKFLOW PREVENTION REQUIRED ON THE
 WATER SUPPLY OF THE WATERFALL. SECTION
 608. KEYED NOTES #2.
 12) SHT P1.2 KEYED NOTES #1 BACKFLOW
 PREVENTER SHALL BE INSTALLED MINIMUM OF
 12" ABOVE GRADE TO BOTTOM OF OUTLET.
 13) SHT P5.1 SANT. RISER DIAGRAM, DOUBLE
 SANITARY TEE PATTERNS SHALL NOT RECEIVE
 THE DISCHARGE OF FIXTURES OR APPLIANCES
 WITH PUMPING ACTION DISCHARGE. SECTION
 706.3. (SEE WASHERS ROOM 149).
 14) SHT P5.2 WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASHERS. SECTION 604.9.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2006-02-07 Cont ID  
Sent By lshapiro Date 2006-02-07 Time 10:56 Rev Time 0.00
Received By lshapiro Date 2006-02-07 Time 10:56 Sent To  
Notes
2006-02-07 00:00:00APPROVED - SHEETS A-4 AND A-4.1 PLANS
 RECEIVED AS REQUESTED.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-01-03 Cont ID  
Sent By lshapiro Date 2006-01-03 Time 09:15 Rev Time 0.00
Received By lshapiro Date 2006-01-03 Time 09:16 Sent To  
Notes
2006-01-03 00:00:00APPROVED.ZONING REVIEW OF RELEVENT
 PAGES A-4 AND A-4.1.
  
 APPLICANT SHALL PROVIDE 3 SETS OF 24X36
 PLANS AND TWO REDUCTIONS OF EACH OF THE
 PAGES.
 DEPUTY DIRECTOR OKAY WITH PLANS NOT
 MATCHING APPROVED SPECIAL USE PERMIT.

Review Stop Z ZONING
Rev No 2 Status N Date 2006-01-20 Cont ID  
Sent By rbrown Date 2006-01-20 Time 08:26 Rev Time 0.00
Received By rbrown Date 2006-01-20 Time 08:27 Sent To  
Notes
2006-01-20 00:00:002ND REVIEW STOP NOT USED

Review Stop Z ZONING
Rev No 1 Status F Date 2005-01-31 Cont ID  
Sent By eschneid Date 2005-01-31 Time 11:08 Rev Time 0.00
Received By lshapiro Date 2006-01-03 Time 09:14 Sent To  
Notes
2005-01-31 00:00:00SITE PLAN DOES NOT MATCH PLAN APPROVED
 WITH THE CLASS B SPECIAL USE PERMIT.
 NORTHEAST PARKING ROW/DUMPSTER
 DIFFERENT-NEW PARKING SPACE LAYOUT
 REQUIRES INTERIOR ISLAND.
 28 PARKING SPACES SHALL BE MAINTIANED.
 DUMPSTER DETATIL IS NOT TO CODE-SECTION
 94-444(B) FIGURE XIV-3, TO INCLUDE
 LANDSCAPING.
 DATA TABLE SHOWING PERCENTAGE OF OPEN
 SPACE, LANDSCAPING, BUILDING COVERAGE,
 IMPERVIOUS AREA, FLOOR AREA RATIO, ETC.
 IS REQUIRED.
 LANDSCAPE PLAN MEETING CODE REQUIREMENTS
 IS REQUIRED.
 PHOTOMETRIC PLAN SHOWING NO MORE THAN
 0.5 FOOTCANDLES AT THE CENTERLINE OF THE
 ALLEY IS REQUIRED-NO GLARE MAY SHINE TO
 RESIDENTIAL BUILDING.
 ADA WALKWAY SHALL CONNECT THE BUILDING
 TO THE SIDEWALK AT FRONT OF PROPERTY.
 THE DRIVE AISLE FOR THE WEST (FRONT)
 PARKING AREA SHALL BE A MINIMUM OF 24
 FEET WIDE FOR 2-WAY TRAFFIC.SUGGEST
 SHORTENING PARKING STALLS FROM 20 FEET
 TO 18 FEET TO MEET REQUIREMENT.
 SIGNAGE DETAILS FOR AWNING AND BUILDING
 SIGNS WILL BE APPROVED UNDER A SEPERATE
 PERMIT.
 CONTACT DAVID KANNING, PLANNER @ (561)
 822-1435.