| Plan Review Stops For Permit 04121374 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2006-11-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-11-15 |
Time |
12:48 |
Rev Time |
1.77 |
| Received By |
jwitmer |
Date |
2006-11-15 |
Time |
12:48 |
Sent To |
PC |
|
| Notes |
| 2006-11-15 12:49:38 | ROOF REVISION 05090092 MET ROOFING METAL STANDING SEAM | | | ROOF PANEL 04-0518.04. | | | FL S S 489.113(B) METAL ROOFING TO BE INSTALLED BY A | | | LICENSED ROOFING CONTRACTOR, NOT G.C. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2006-07-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-07-03 |
Time |
13:28 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2006-07-03 |
Time |
13:28 |
Sent To |
PC |
|
| Notes |
| 2006-07-03 00:00:00 | RESTAMP TRUSS PACKAGE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2006-06-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-06-14 |
Time |
15:52 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2006-06-14 |
Time |
15:52 |
Sent To |
PC |
|
| Notes |
| 2006-06-14 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04121374 | | | ADD: 2216 PALM BEACH LAKES BLVD | | | CONT: ODUM CONSTRUCTION | | | TEL: (561)997-6698 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW- REVISION | | | ACTION: DENIED | | | | | | REVISION TO INCREASE THE WINDOW SIZES | | | FROM (14) 3'-0"X4'-0" TO (14) | | | 3'-0"X5'-0" WINDOWS DENIED. SEE REVISION | | | | | | FILED MAY 31,2006, 2 MONTHS AFTER THE | | | DENIEL FROM THE CONSTRUCTION BOARD OF | | | AJUSTMENT & APPEAL. THE OWNER FILED FOR | | | A VARIANCE FOR THE MARCH MARCH 16, 2006 | | | BOARD MEETING, OUTCOME DENIED FOR THE | | | ENLARGEMENT OF EAST WINDOWS, CASE# 1293. | | | | | | MARCH 17,2005, BOARD OF ADJUSTMENT AND | | | APPEAL CASE# 1272 IN THE DOCUMENT THE | | | APPLICANT PROPOSES THE FOLLOWING | | | VARIANCE. CODE SECTION 705.1.1.2CODE | | | REQUIRES OPENINGS WITHIN 15 FT OF THE | | | PROPERTY LINE TO OPENING PROTECTIVES. | | | REQUEST FIRE SPRINKLERS INSIDE AND OUT | | | IN LEU OF FIRE RATED GLASS. THERE IS NO | | | MENTION OF BEING OVER THE ALLOWED 10% | | | OPENINGS. THE CASE IS GRANTED FOR THE | | | USE OF A FIRE CURTAIN INSIDE AND OUT | | | INSTEAD OF FIRE RATED GLASS. | | | | | | | | | 1/06/06 THIRD REVIEW | | | FOURTH COMMENT: | | | 4) PLANS A-12 INDICATE THAT THE WINDOWS | | | ON THE EAST SIDE HAVE INCREASED.WHEN THE | | | APPLICANT WENT TO THE BOARD OF | | | ADJUSTMENT AND APPEAL FOR TABLE 600 AS | | | WELL AS OPENING PROTECTIVES (705.1.1.2) | | | THE DESIGN WAS 23% OVER THE ALLOWABLE | | | OPENING SIZE FOR 5'-10' FROM THE | | | PROPERTY LINE. WITH THE INCREASE IN | | | OPENING SIZE THE OVERAGE HAS INCREASED | | | TO 50% OVER THE ALLOWABLE SIZE AND A 27% | | | ALLOWABLE OPENINGS APPROVED BY THE | | | BOARD. | | | | | | 1/21/05 FIRST REVIEW | | | SIXTH COMMENT: | | | 6) DEMO PLAN INDICATES EITHER NEW OR | | | ENLARGED OPENINGS ON THE EAST SIDE OF | | | THE BUILDING: | | | | | | 6A) SITE PLAN INDICATES THE EAST SIDE OF | | | THE BUILDING IS APPROXIMATELY 5'-0" | | | AWAY FROM THE PROPERTY LINE. 705.1.1.2. | | | REQUIRES AT ALL OPENINGS WITHIN 15' OF | | | THE PROPERTY LINE SHALL BE EQUIPPED WITH | | | APPROVED OPENING PROTECTIVES. | | | | | | 6B) THE EAST WALL OF THE BUILDING SHALL | | | HAVE NO MORE THAN 10% OPENINGS IN THE | | | WALL , THE PROPOSED OPENINGS ARE AT | | | APPROXIMATELY 27%. SEE TABLE 600, TYPE | | | VBUILDING. WALL AREA IS FIGURED FLOOR TO | | | CEILING THE LENGTH OF THE BUILDING. | | | | | | 6C) NOTE FOR FIRE RATED GLASS THERE IS | | | NO LARGE MISSLE IMPACT TESTED WINDOWS OR | | | DOORS. STORM SHUTTERS WILL BE REQUIRED | | | FOR THESE OPENINGS. THE REMAINDER OF THE | | | BUILDING COULD BE EITHER SHUTTERED OF | | | LARGE MISSLE IMPACT TESTED GLAZING. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-02-03 |
Time |
14:55 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2006-02-03 |
Time |
14:55 |
Sent To |
PC |
|
| Notes |
| 2006-02-03 00:00:00 | REVISION STRUCTURAL 11-30-05 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-01-20 |
Time |
07:55 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2006-01-20 |
Time |
07:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-01-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-01-06 |
Time |
08:19 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2006-01-06 |
Time |
08:19 |
Sent To |
PC |
|
| Notes |
| 2006-01-06 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04121374 | | | ADD: 2216 PALM BEACH LAKES BLVD | | | CONT: K & M COMMERCIAL | | | TEL: (561)383-2817 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RD REVIEW | | | ACTION: DENIED | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. | | | ***********IMPORTANT*********** | | | CORALATE PLANS INTO TWO COMPLETE | | | "STAPLED SETS OF PLANS. | | | A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A | | | DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) COMMENT#7 FROM THE PEVIOUS REVIEW, | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 3)FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) STRUCTURAL COMPONENTS- TRUSS ABCHORS | | | B1) ROOF- THERE IS (2) SEPERATE TYPES OF | | | METAL ROOF REPORTS SUBMITTED. AEICOR | | | SS-2-21 STANDING METAL ROOF PANEL, | | | PRESSURES ARE LOW, SEE SYSTEMS | | | LIMITATION. REMOVE THE REPORTS NOT USED. | | | B2) ULTRAGUARD PVC WOOD DECK, PICK WHICH | | | SYSTEM IS TO BE USED SEE PAGES 11-17, | | | ALSO NOTE ON EACH SYSTEM THE SYSTEM | | | LIMITATION NOTE MAXIMUM DESIGN PRESSURE | | | OF 45 PSF AND SYSTEM LIMITATION# 9 NO | | | INCREASE ALLOWED !!!!!!!!!! SEE TABLE | | | 1606.2B ZONE# 310 SQ FT= -89PSF | | | ZONE# 3 20 SQ FT = -73.8PSF REQUIRED!!!! | | | | | | 4) PLANS A-12 INDICATE THAT THE WINDOWS | | | ON THE EAST SIDE HAVE INCREASED.WHEN THE | | | APPLICANT WENT TO THE BOARD OF | | | ADJUSTMENT AND APPEAL FOR TABLE 600 AS | | | WELL AS OPENING PROTECTIVES (705.1.1.2) | | | THE DESIGN WAS 23% OVER THE ALLOWABLE | | | OPENING SIZE FOR 5'-10' FROM THE | | | PROPERTY LINE. WITH THE INCREASE IN | | | OPENING SIZE THE OVERAGE HAS INCREASED | | | TO 50% OVER THE ALLOWABLE SIZE AND A 27% | | | ALLOWABLE OPENINGS APPROVED BY THE | | | BOARD. | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-09-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-09-02 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2005-09-02 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2005-09-02 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04121374 | | | ADD: 2216 PALM BEACH LAKES BLVD | | | CONT: K & M COMMERCIAL | | | TEL: (561)383-2817 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) COMMENT#7 FROM THE PEVIOUS REVIEW, | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 3)FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) SKYLIGHTS | | | B) STRUCTURAL COMPONENTS- TRUSS ABCHORS | | | C) ROOF- AEICOR SS-2-21 STANDING METAL | | | ROOF PANEL, PRESSURES ARE LOW, SEE | | | SYSTEMS LIMITATION ENHANCED FASTENING | | | BY A LICENSED ARCHITECT, ENGINEER OR | | | REGISTERED ROOF CONSULTANT. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-01-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-01-21 |
Time |
09:56 |
Rev Time |
4.55 |
| Received By |
jwitmer |
Date |
2005-01-21 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2005-01-21 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04121374 | | | ADD: 2216 PALM BEACH LAKES BLVD | | | CONT: K & M COMMERCIAL | | | TEL: (561)383-2817 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) SEE SHEET A-7 DOOR 152A MISSING THE | | | REQUIRED 18" ON PULL SIDE.11-4.13.6 | | | MANEUVERING CLEARENCES AT DOORS. MINIMUM | | | MANEUVERING CLEARENCES AT DOORS THAT ARE | | | NOT AUTOMATIC OR POWER-ASSISTED SHALL BE | | | AS SHOWN IN FIG. 25. THE FLOOR OR GROUND | | | AREA WITH IN THE REQUIRED CLEARENCES | | | SHALL BE CLEAR & LEVEL. | | | | | | 3) ELECTRIC PLAN INDICATES A GENERATOR | | | AND FUEL TANK BUT NO INDICATION IS ON | | | THE SITE PLAN? | | | | | | 4) DISCEPANCY STRUCTURAL PLANS INDICATE | | | A DRIVE THROUGH BUT A-6 DOESN'T INDICATE | | | | | | ANY FOOTERS, COLUMNS ETC | | | | | | 5) THE PLANS SUBMITTED SHALL BE | | | REVIEWED | | | AS A NEW BUILDING. CHAPTER 3401.7.2.6 | | | WHEN OVER 50% OF THE EXISTING BUILDING | | | ARE MADE DURING ANY 12 MONTH PERIOD, THE | | | BUILDING SHALL BE MADE TO CONFORM TO THE | | | | | | REQUIREMENTS FOR A NEW BUILDING OR BE | | | ENTIRELY DEMOLISHED. | | | | | | 6) DEMO PLAN INDICATES EITHER NEW OR | | | ENLARGED OPENINGS ON THE EAST SIDE OF | | | THE BUILDING: | | | 6A) SITE PLAN INDICATES THE EAST SIDE OF | | | THE BUILDING IS APPROXIMATELY 5'-0" | | | AWAY FROM THE PROPERTY LINE. 705.1.1.2. | | | REQUIRES AT ALL OPENINGS WITHIN 15' OF | | | THE PROPERTY LINE SHALL BE EQUIPPED WITH | | | | | | APPROVED OPENING PROTECTIVES. | | | 6B) THE EAST WALL OF THE BUILDING SHALL | | | | | | HAVE NO MORE THAN 10% OPENINGS IN THE | | | WALL , THE PROPOSED OPENINGS ARE AT | | | APPROXIMATELY 27%. SEE TABLE 600, TYPE | | | V | | | BUILDING. WALL AREA IS FIGURED FLOOR TO | | | CEILING THE LENGTH OF THE BUILDING. | | | 6C) NOTE FOR FIRE RATED GLASS THERE IS | | | NO LARGE MISSLE IMPACT TESTED WINDOWS OR | | | | | | DOORS. STORM SHUTTERS WILL BE REQUIRED | | | FOR THESE OPENINGS. THE REMAINDER OF THE | | | BUILDING COULD BE EITHER SHUTTERED OF | | | LARGE MISSLE IMPACT TESTED GLAZING. | | | | | | 7) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 8)FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS FIXED & OPERTABLE | | | B) MULLIONS | | | C) EXTERIOR DOORS | | | D) SKYLIGHTS | | | E) STRUCTURAL COMPONENTS- TRUSS | | | ANCHORS | | | F) ROOFING ASSEMBLIES | | | | | | 9) 1707.4.5.1 MULLIONS OCCURRING BETWEEN | | | INDIVIDUAL WINDOW AND GLASS | | | DOOR ASSEMBLIES. TESTING REPORTS ARE | | | REQUIRED BY AN APPROVED TESTING | | | LABORATORY OR BE ENGINEERED. | | | | | | 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN- | | | ED TO TRANSFER THE DESIGN PRESSURE LOADS | | | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES | | | TO THE ROUGH OPENING SUBTRATE. | | | | | | 11) 1707.4.3 EACH EXTERIOR DOOR ASSEMBLY | | | NOT COVERED BY 1707.4.2 | | | (GLAZED DOORS) SHALL BE LISTED AND TEST- | | | ED FOR A PERIOD EQUAL TO THE QUANITY | | | 3600/ V WHERE THE TIME PERIOD IS IN | | | SECTIONS AND V IS IN MILES PER HR TAKEN | | | FROM FIGURE 1606. THE TIME PERIOD SHALL | | | ALSO INCLUDE A 10 SECOND PERIOD AT A | | | LOAD EQUAL TO 1.5 TIMES THE DESIGN | | | PRESSURE. DADE COUNTY & SBCCI REPORTS | | | ARE ACCEPTED. | | | | | | 12) PROVIDE POSITIVE & NEGATIVE | | | PRESSURES FOR ALL OPENINGS, INCLUDE | | | END ZONES. | | | | | | 13) A-21 INDICATES THE USE OF 5/8" CDX | | | PLYWOOD FOR WALLS OD CUPALO, THIS IS A | | | TYPE V BUILDING, WALLS TO BE | | | NONCOMBUSTIBLE., ALSO IN A FIRE DISTRICT | | | | | | NO TYPE VI CONSTRUCTION. | | | | | | 14) 3106.2 CANOPIES. WHEN LOCATED LESS | | | THAN 30" FROM AN INTERIOR LOT LINE OR | | | OTHER STUCTURE, THE CANOPY FRAME AND ITS | | | SUPPORTS SHALL BE OF NONCOMBUSTILE | | | MATERIAL, FIRE RESISTANT TREATED | | | CONSTRUCTION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-01-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-01-19 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-01-19 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2006-01-19 00:00:00 | REDLINED ESP SHEETS TO SEE WIND LOAD | | | CALCS DONE BY ENGINEER. | | | PER FBC 140 MPH. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-12-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-12-09 |
Time |
09:15 |
Rev Time |
|
| Received By |
dpalmer |
Date |
2005-12-09 |
Time |
07:26 |
Sent To |
|
|
| Notes |
| 2005-12-09 00:00:00 | ** UNSAT ** | | | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | | REVIEW WHICH STILL NEED TO BE ADDRESSED. | | | | | | | | | 1)NOTE: NOTE #1 NO. | | | PLEASE SUBMIT MANUFACTURES CUT/SPEC | | | SHEETS WHICH WILL CORRELATE WITH PLANS | | | DRAWING SUBMITTED. | | | PLEASE SEE GENERATOR SPECS SUBMITTED DO | | | NOT INDICATE A 75KW GEN, PLEASE SEE THE | | | ONLY REFERENCE TO ANY 75KW GEN, | | | INDICATES AMPERAGE RATING AT 142A'S, | | | WHEN DERATED LOAD IS 189A'S? | | | PLEASE ALSO BEAR IN MIND, THE RATING OF | | | A NATURAL GAS GENERATOR IS TYPICALLY | | | LESS THAN THE KW LISTED FOR LP. | | | PLEASE ALSO SEE NO SPECS/SHEETS FOR ATS | | | COULD BE LOCATED ON PACKAGES. | | | | | | | | | 2)NOTE: NOTE #2 OK. | | | | | | 3)NOTE: NOTE #3 NO, | | | PLEASE SUBMIT THE SIGNED, DATED AND | | | SEALED WIND LOADING CALCULATIONS AS | | | REQUESTED. | | | IT WAS NOTED THAT THERE IS A LIGHTING | | | SUBMITTIAL PACKAGE, HOWEVER THIS ONLY | | | REFERENCES TO FIXTURES,POLES ETC WITH | | | OUT PROVIDING INFORMATION NEEDED. | | | PLEASE KNOW, IF SITE LIGHTING PLAN MAY | | | BE DELETED FROM PACKAGE, HOWEVER,A | | | SEPARATE PERMIT APPLICATION, PLANS, FEES | | | ETC WILL BE REQUIRES BEFORE ANY SITE | | | LIGHTING MAY START. | | | NOTE WAS ADDED TO ESP SHEETS WITH | | | REFERENCE TO FBC 140. | | | | | | 4)NOTE: NOTE #4 OK. | | | | | | 5)NOTE: NOTE #5 NO, PLEASE SEE ALL SETS | | | ARE STILL SUBMITTED AS INDIVIDUAL SHEETS | | | AND SETS ARE NOT PLACED AND ATTACHED | | | TOGETHER. | | | | | | 6)NOTE: NOTE #6 OK, HOWEVER PLEASE SEE | | | NOTE #1, AS RATING OF GEN IS STILL TO BE | | | VERIFIED. | | | | | | 7)NOTE: NOTE #7 OK. | | | | | | 8)NOTE: NOTE #8 OK. | | | | | | 9)NOTE: NOTE #9 OK. | | | | | | 10)NOTE: NOTE #10 OK. | | | | | | 11)NOTE: NOTE #11 OK. | | | | | | 12)NOTE: NOTE #12 NO, TO BE VERIFIED, | | | SEE NOTE #1. | | | | | | 13)NOTE: NOTE #13 OK. | | | | | | 14)NOTE: NOTE #14 OK. | | | | | | 15)NOTE: NOTE #15 OK. | | | | | | PLEASE BE SURE TO SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE IF THERE ARE ANY QUESTIONS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-04 |
Time |
13:08 |
Rev Time |
1.75 |
| Received By |
dpalmer |
Date |
2005-09-01 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2005-09-04 00:00:00 | ************ UNSAT ************** | | | | | | 1)NOTE: PLEASE SUBMIT MANUFACTURE | | | SPEC/CUT SHEETS FOR GENERATOR, AUTOMATIC | | | TRANSFER SWITCH, AND ANY SUB-BASE FUEL | | | TANK. | | | PLEASE BE SURE ALL INDICATE LISTINGS | | | FROM A NRTL. | | | PLEASE BE SURE DISCONNECTING MEANS IS | | | RATED AS "SERVICE EQUIPMENT" 225.36. | | | | | | 2)NOTE: PLEASE SEE BUILDING REVIEW | | | COMMENTS PERTAING TO CHAPTER 34 OF THE | | | FBC. PLEASE SEE ANY REQUIREMENTS WHICH | | | MAY AFFECT ELECTRICLA PLANS. | | | | | | 3)NOTE: PLEASE SUBMITWIND LOADING | | | CALCULATIONS FOR NEW SITE LIGHTING | | | POLES. | | | MUST MEET FBC 140 MPH. | | | | | | 4)NOTE: PLEASE SEE THAT ARCHITECTS TITLE | | | BLOCK CONTAINS THE "PRINTED NAME AND | | | LICENSE NUMBER" FOR THE ARCHITECT. FAC | | | 61G1-16.004 | | | PLEASE KNOW, THIS IS REQUIRED ON ALL | | | SHEETS AND FOR ALL TRADES WHETHER OR NOT | | | COMMENT IS MADE BY OTHER REVIEWER(S). | | | | | | 5)NOTE: PLEASE SUBMIT SETS OF PLANS | | | ATTACHED TOGETHER INTO SETS. PLEASE SEE | | | PLANS WERE SUBMITTED AS INDIVIDUAL | | | SHEETS. | | | PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE | | | REMOVED AND ONLY INSERT NEW REVISED | | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | ONE SET OF OLD/VOIDED SHEETS SHOULD BE | | | SUBMITTED FOR REFERENCE. | | | | | | 6)NOTE: PLEASE SEE LOADS INDICATED FOR | | | RTU'S ON EDP, MUST BE FIGURED AS ALL | | | LOADS ON AND UNDER HEAT UNLESS AN | | | AUTOMATIC MEANS OF LOAD SHEDDING IS | | | PROVIDED. | | | IF LOAD SHEDDING WILL BE USED, PLEASE | | | PROVIDE A WIRING DETAIL (ETC) FOR | | | METHOD, WIRING TO BE USED. | | | 702.5 | | | | | | 7)NOTE: PLEASE SEE LOADS ON OPTIONAL | | | BACK -UP POWER. PLEASE SEE GENERAL | | | LTS.RECEPTS LOADS ARE PERMITTED TO BE | | | DE-RATED, HOWEVER ANY CONNECT MOTOR | | | LOADS, APPLIANCE LOADS, MUST BE FIGURED | | | AT 100%. | | | | | | 8)NOTE: PLEASE SEE 210.8B3 IN KITCHENS | | | OTHER THAN IN DWELLING UNITS WHICH | | | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT | | | RECEPTACLES IN NONDWELLING-TYPE KITCHENS | | | TO BE GFCI PROTECTED. THIS REQUIREMENT | | | APPLIES TO EACH AND EVERY 15- AND | | | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, | | | WHETHER OR NOT THE RECEPTACLE SERVES | | | COUNTERTOP APPLIANCES. | | | | | | 9)NOTE: PLEASE SEE THAT PLANS SHOULD | | | ALSO INDICATE SIGNAGE REQUIRED AT | | | DISCONNECTING MEANS AT ELECTRICAL ROOM | | | FOR GENERATOR FEED. | | | PLEASE VERIFY HOW NEW GENERATOR WILL GET | | | TO EXISTING ELECTRICAL RM? | | | PLEASE SEE A DISCONNECTING MEANS AT BLDG | | | MAY ALSO BE REQUIRED IF FED OVERHEAD | | | INTO BLDG.. IF GEN IS FED FROM OUTSIDE | | | BLDG (AROUND) OR UNDER GROUND, THIS DISC | | | AT ELECTRICAL ROOM WILL BE OK. | | | 225.31,225.34,110.27 | | | | | | 10)NOTE: PLEASE SEE NOTES ON ELECTRICAL | | | RISER DIAGRAM PAGE WHICH NOTES PANEL | | | "MPD", THIS SEEMS TO BE A MISPRINT? | | | PLEASE CORRECT. | | | | | | 11)NOTE: PLEASE SEE FIRE REVIEW NOTES: | | | PLEASE SEE A "KNOX BOX" MAY BE REQUIRED | | | AND LOCATION DETERMINED BY FIRE MARSHALS | | | OFFICE. | | | PLEASE SEE FIRE ALARM CONTROL PANEL AND | | | GENERATOR ANNUNCIATOR PANEL SHALL BE | | | GROUPED. THIS LOCATION WILL ALSO BE | | | NOTED BY TH FMO. | | | PLEASE SHOW GAP ON PLANS. | | | | | | 12)NOTE: PLEASE VERIFY OCP AT GENERATOR, | | | AS 70KW 3/0 120/208V DOES NOT SEEM TO | | | PROVIDE 250A'S??? | | | 215.5 | | | | | | 13)NOTE: PLEASE CORRELATE ELECTRICAL RM | | | LAYOUT WITH ELECTRICAL POWER PLANS FOR | | | LOCATIONS OF EQUIPMENT. | | | 215.5 | | | | | | 14)NOTE: PLEASE CORRELATE WATER HEATERS | | | AND LOADS SHOWN. | | | PLEASE SEE LOAD CALCS SHOWS 24KW, YET | | | PANEL "C" ALSO SHOWS AN 11KW WH? | | | PLEASE ALSO SEE CIRCUITING SHOWS PUMP | | | AND WH? | | | PLEASE SEE 422.11F FOR UNITS OVER 48A'S. | | | SHOWS A SINGLE OCP FOR UNIT?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | REVIEW WAS UNDER 05080456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-01-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-10 |
Time |
13:28 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2005-01-10 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2005-01-10 00:00:00 | *********** UNSAT ***************** | | | | | | 1)NOTE: PLEASE CORRELATE ITEMS SHOWN ON | | | PLANS WITH PANEL SCHEDULE. | | | PLEASE SEE PLANS INDICATE A 30KW WATER | | | HEATER, YET THIS COULD NOT BE LOCATED? | | | PLEASE SEE 422 FOR MANY ITEMS REQUIRED | | | FOR LARGE WATER HEATER UNITS OVER 48A'S. | | | MIN OCP 125%, MAX 150%. | | | | | | 2)NOTE: PLEASE VERIFY REQUIRED SIGN | | | CIRCUIT PER 600.5EACH COMMERCIAL | | | BUILDING AND EACH COMMERCIAL OCCUPANCY | | | ACCESSIBLE TO PEDESTRIANS SHALL BE | | | PROVIDED WITH AT LEAST ONE OUTLET IN AN | | | ACCESSIBLE LOCATION AT EACH ENTRANCE TO | | | EACH TENANT SPACE FOR SIGN OR OUTLINE | | | LIGHTING SYSTEM USE. THE OUTLET(S) SHALL | | | BE SUPPLIED BY A BRANCH CIRCUIT RATED AT | | | LEAST 20 AMPERES THAT SUPPLIES NO OTHER | | | LOAD. | | | | | | 3)NOTE: PLEASE SEE ONE OF THE ELECTRICAL | | | RMS SHOWN ON PLANS FOR ATS MENTIONS | | | "CLOSET". PLEASE SEE 110.26, 408.7, | | | 240.24 FOR PANELS NOT PERMITTED ON | | | CLOSETS/ STORAGE AREAS. ETC. | | | | | | 4)NOTE: PLEASE SEE225.31,.32,.36 FOR | | | MISSING MEANS OF DISC FOR FEEDER FROM | | | GENERATOR. | | | PLEASE ALSO SEE GROUPING OF | | | MAINS.230.72 | | | | | | 5)NOTE: PLEASE SUBMIT MALL MANUFACTURE | | | SPECS FOR GEN/ ATS/ FUEL TANKS ETC | | | PLEASE BE SURE A LISTING FROM A NRTL IS | | | SHOWN. | | | PLEASE SEE 700.8, 702.8 FOR NOTE TO | | | PLACED ON PLANS. | | | A SIGN SHALL BE PLACED AT THE SERVICE | | | ENTRANCE EQUIPMENT INDICATING TYPE AND | | | LOCATION OF ON-SITE EMERGENCY POWER | | | SOURCES. | | | | | | 6)NOTE: PLEASE CORRELATE RTU'S ON PLANS | | | AND PANEL SCHEDULES. | | | KW RATINGS DO NOT SEEM TO CORRELATE. | | | RTU#1, #2 | | | | | | | | | 7 )NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW PER | | | 220.3,220.10,220.11,220.13 ETC. | | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | | AT 125% PER 215.3,230.42 | | | | | | 8)NOTE: PLEASE SUBMIT WIND-LOADING FOR | | | NEW POLES/ FIXTURES. | | | MUST BE AT THIS TIME AND MUST MEET FBC | | | 140 MPH. | | | | | | 9)NOTE: PLEASE PROVIDE NOTE/ INFORMATION | | | ON TYPE OF ENCLOSURE FOR GEN. | | | | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE SET OF OLD VOIDED SHEETS SHOULD BE | | | SUBMITTED FOR REFERENCE ONLY. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2005-12-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-12-06 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-12-06 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2005-12-06 00:00:00 | 1. ALL PREVIOUSLY CITED PLAN REVIEW | | | NOTES BY FIRE RESCUE HAVE BEEN ANSWERED | | | ON THE PLANS WITH COMMENTS PROVIDED ON | | | THE OCTOBER 12, 2005 LETTER FROM THE | | | ARCHITECT. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-09-13 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-09-13 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-09-13 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2005-09-13 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE SEE FIRST FIRE REVIEW | | | COMMENTS. IT DOES NOT APPEAR THAT | | | COMMENTS HAVE BEEN ADDRESSED. PLEASE | | | RESPOND TO ALL COMMENTS WITH A RESPONSE | | | LETTER AND SHOW REVISIONS ON DRAWINGS TO | | | HELP EXPEDITE THIS PROCESS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-01-24 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-01-24 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-01-24 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2005-01-24 00:00:00 | 1) DEMOLITION, RENOVATION AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3) BUILDING ADDRESS REQUIRED. A MINIMUM | | | OF AT LEAST 6" HIGH NUMBERS ARE | | | REQUIRED. | | | | | | 4) INTERIOR WALL AND CEILING FINISH | | | SHALL COMPLY WITH NFPA 101 LIFE SAFETY | | | CODE 2000 EDITION CHAPTER 38.3.3.2. | | | INTERIOR WALL AND CEILING FINISH | | | COMPLYING WITH 10.2.3 SHALL BE CLASS A | | | OR CLASS B IN EXITS AND IN ENCLOSED | | | CORRIDORS FURNISHING ACCESS TO EXITS; | | | AND CLASS A, CLASS B, OR CLASS C IN | | | OFFICE AREAS. | | | | | | 5) ALL EXIT DOORS SHALL COMPLY WITH NFPA | | | 101 CHAPTER 7.2.1. | | | | | | 6) THE FIRE ALARM SYSTEM SHALL BE CLASS | | | "A" OR FULLY ADDRESSABLE. | | | | | | 7) ALL FIRE ALARM SYSTEMS THAT SUPERVISE | | | FIRE SPRINKLER SYSTEMS SHALL BE UL | | | CERTIFICATED AND HAVE DOCUMENTS | | | ATTESTING TO THIS CERTIFICATION PRIOR TO | | | FINAL APPROVAL OF THE FIRE ALARM | | | SYSTEM. | | | | | | 8) PLEASE PROVIDE CUT SHEETS FOR CANVAS | | | AWING SHOWING PROOF FIRE RESISTANT | | | TREATED. | | | | | | 9) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM SYSTEMS REMODEL. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2006-06-12 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-06-12 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-06-12 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2006-06-12 00:00:00 | REVISION SUBMITTED. | | | SIGNED AND SEALED BY ENG OF RECORD | | | CHANGE U/G PIPING TO PE 1-1/4" | | | CHANGE TO 2# PSI SSSTEM |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2006-04-25 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-04-25 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-04-25 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2006-04-25 00:00:00 | APPROVED PLANS CHANGED TO 2#PSI | | | ENGINEER OF RECORD SEAL REQUIRED. | | | PERMIT APPLICATION #06041057 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-01-20 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-01-20 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2006-01-20 00:00:00 | OK TO ISSUE GAS PERMIT PER REVIEWED | | | PLANS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2006-12-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-17 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-17 |
Time |
15:26 |
Sent To |
M |
|
| Notes |
| 2006-12-17 15:27:51 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-21 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-21 |
Time |
14:44 |
Sent To |
M |
|
| Notes |
| 2006-11-21 14:44:53 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-10-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-24 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-24 |
Time |
11:23 |
Sent To |
B |
|
| Notes |
| 2006-10-24 11:24:19 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-06-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-28 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-28 |
Time |
11:25 |
Sent To |
B |
|
| Notes |
| 2006-06-28 00:00:00 | TO "JWITMER" DESK/RESTAMP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-06-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-05 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-05 |
Time |
13:46 |
Sent To |
B |
|
| Notes |
| 2006-06-05 00:00:00 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-02-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-01 |
Time |
17:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-01 |
Time |
17:41 |
Sent To |
B |
|
| Notes |
| 2006-02-01 00:00:00 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-01-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-31 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-31 |
Time |
16:21 |
Sent To |
Z |
|
| Notes |
| 2006-01-31 00:00:00 | TO "Z" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-01-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-20 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-01-17 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2006-01-20 00:00:00 | GIVEN TO PAUL SCHMITZ FOR LAST REVIEW. | | | AFTER REVIEW, PAUL WILL GIVE TO LUIS | | | MARTINEZ FOR PROCESSING. | | | | | | | | 2006-01-17 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-10-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-19 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-19 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2005-11-15 00:00:00 | TO "COMM" BD#54 | | 2005-10-19 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2005-09-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-09-04 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2005-09-04 00:00:00 | TO COMM BOARD ON 8/11 SPACE #40 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-12-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-21 |
Time |
|
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-28 |
Time |
07:12 |
Sent To |
|
|
| Notes |
| 2004-12-28 00:00:00 | TO COMM BD#54 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2007-01-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2007-01-03 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2007-01-03 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2007-01-03 13:18:30 | REVISION / DUCT SIZES PLAN SHEET M-1 & M-2 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2006-11-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-11-30 |
Time |
06:55 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-11-30 |
Time |
06:55 |
Sent To |
|
|
| Notes |
| 2006-11-30 06:59:27 | DENIED: | | | PLANS MUST BE SIGNED, SEALED AND DATED BY THE ENGINEER | | | OF RECORD IN ACCORDANCE WITH FS471.025.SHOP DRAWINGS | | | ARE NOT ACCEPTABLE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
N |
Date |
2006-01-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-01-19 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-01-19 |
Time |
16:30 |
Sent To |
P |
|
| Notes |
| 2006-01-19 00:00:00 | NEW M-3 SHEET / ROOF DRAINAGE CALCS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-12-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-12-13 |
Time |
06:52 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2005-12-13 |
Time |
06:38 |
Sent To |
|
|
| Notes |
| 2005-12-13 00:00:00 | HVAC PLANS ARE APPROVED.ADDITIONAL | | | INFORMATION REQUIRED FOR THE GENERATOR. | | | SEE COMMENTS BY DEWEY PALMER, ELECTRICAL | | | PLANS EXAMINER. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-09-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-22 |
Time |
07:50 |
Rev Time |
2.00 |
| Received By |
pkrauss |
Date |
2005-09-22 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2005-09-22 00:00:00 | DENIED: | | | 1.PLAN SHEET A-11 INDICATES 19'8" TO | | | THE TOP OF THE PARAPET.PLEASE INDICATE | | | ROOF ACCESS FOR EQUIPMENT MAINTENANCE. | | | PER 2001 FBC(M)306.5 EQUIPMENT LOCATED | | | ON A ROOF AT A HEIGHT GREATER THAN 16FT, | | | A PERMANENT MEANS OF ACCESS WILL BE | | | REQUIRED.PLEASE INDICATE ACCESS. | | | | | | 2.PLAN SHEET P-2 INDICATES EMERGENCY | | | GENERATOR.PLEASE PROVIDE DISTANCE FROM | | | OPENINGS (DOORS, & WINDOWS) 2001 | | | FBC(M)401.5.2.SITE PLAN DOES NOT | | | INDICATE LOCATION OF EMERGENCY | | | GENERATOR.PLEASE NOTE PER 2001 FBC(M) | | | EQUIPMENT INSTALLED IN LOCATION WHERE | | | SUBJECT TO DAMAGE SHALL BE PROTECTED BY | | | APPROVED BARRIERS.PLEASE PROVIDE | | | SUBMITTAL FOR THE GENERATOR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2005-01-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-01-13 |
Time |
08:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
MEDGAS |
MEDICAL GAS |
| Rev No |
1 |
Status |
P |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-01-20 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-01-20 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2006-01-20 00:00:00 | | | | PROVISO: | | | SEPERATE PERMIT REQUIRED. | | | CERTIFIED OR REGISTERED PLUMBING | | | CONTRACTOR ONLY. | | | MED GAS CERTIFICATES WITH APPLICATION | | | FOR PERMIT. | | | PLUMBING COMPANY, | | | INSTALLER, | | | BRAZER. | | | WITH PHOTO ID FOR EACH WORKER TO COMPLY | | | WITH NFPA 99-C TO OBTAIN A PERMIT. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-01-20 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-01-20 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2006-01-20 00:00:00 | PROVISO: | | | 1) SHT A-24ELEVATION DETAILS: | | | COMPLLY WITH FBC 2001 ACCESSIBILITY CODE | | | CH 11, SEC 11-4.22.2 DOORS | | | ALL DOORS TO ACCESSIBLE TOILET ROOMS | | | SHALL COMPLY WITH SEC 11-4.13 DOORS, | | | SHALL NOT SWING INTO THE CLEAR FLOOR | | | SPACE REQUIRED FOR ANY FIXTURE. | | | | | | 2) SEPERATE IRRIGATION PERMIT REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-12-17 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-12-17 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-12-17 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2005-12-21 00:00:00 | PAUL SCHMITZ | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | REVIEW | | | DENIED | | | | | | REVIEW COMMENTS DATED SEPT. 23 2005 | | | (ORIGINAL COMMENTS) | | | 3. ROOF DRAINAGE REF TO SHT M-3 | | | NOT IN ROLL PLANS NOR DRAWING INDEX. | | | 4.5.7. SAYS SEE ARCHITECTURAL. | | | NOT ADDRESSED. | | | 8.DATA SUPPLIED BY PLBG CONTRACTOR, | | | DENIED. NOT AS SPECIFIED ON SHT P-1 | | | 11.WATER FEATURE HOSE BIBB. | | | REF TO SHT P-4, SHT-4 NOT IN ROLL PLANS | | | NOR DRAWING INDEX. | | | (NEW COMMENTS) | | | 1B.PROVIDE INFORMATION AS REQUESTED, | | | SEC 104.2.1 | | | 2B MEDICAL GAS SHALL BE NOTED, SEPETATE | | | PLANS AND PERMIT TO COMPLY WITH THE | | | LATEST EDITIONNFPA 99-C | | | 3B,4BA,B,C,D,E,F,G ALL REFERE TO A WATER | | | HEATER LISTED ON SHT P-4, NOT IN THE | | | ROLL PLANS NOR IN THE DRAWING INDEX. | | | | | | WHEN RE- SUBMITTING PLANS PLEASE SUBMITT | | | A TRANSMITTAL LETTER FOR ALL DISCIPLINES | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE. IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-09-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-09-19 |
Time |
10:51 |
Rev Time |
6.25 |
| Received By |
kstevens |
Date |
2005-09-10 |
Time |
23:59 |
Sent To |
|
|
| Notes |
| 2005-09-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | NFPA 99C GAS & VACUUM SYSTEMS | | | | | | A. FROM PREVIOUS REVIEW: COMMENT NUMBERS | | | TO STAY THE SAME AS FIRST REVIEW: | | | 3) SHT A-9 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS PER | | | SECTIONS 1106, AND 1107 AND ALL | | | SUBSECTIONS. SHOW TOTAL SQUARE FOOTAGE | | | FOR ROOF, AND SHOW 1/2 AREA OF ALL | | | VERTICAL WALLS, INCLUDING PARAPETS ADDED | | | TO SQUARE FOOTAGE. ALSO IN CALCULATION, | | | SHOW THE AREA OF ANY ROOF DRAINING ONTO | | | THE ROOF FROM ABOVE. SHOW THE LOCATION | | | OF ALL PRIMARY AND SECONDARY ROOF | | | DRAINS. SECTION 104.2.1. - COMMENT | | | RESPONSE NOTED ON SHT A-9 NOTE #3. | | | ALTHOUGH NO NEW ROOF AREA IS ADDED, NEW | | | VERTICAL AREAS FROM THE MANSARD ROOF ON | | | THREE SIDES OF ROOF AND THE VERTICAL | | | WALLS OF THE CUPOLA WILL ADD TO THE | | | SQUARE FOOTAGE PER SECTION 1106.4. ALSO | | | AS INDICATED IN NOTE #3 THE ROOF HAS NO | | | ROOF DRAINS, BUT THE GUTTER AND | | | DOWNSPOUTS SHALL BE SIZED PER SF OF THE | | | ROOF, TABLE 1106.6 AND DOWNSPOUTS PER | | | TABLE 1106.2. | | | 4) SHTS A-16 & A-17 LOUNGE SINKS SHALL | | | COMPLY WITH SECTION 11-4.24 AND ALL | | | SUBSECTIONS. (FORWARD APPROACH CLEAR | | | FLOOR SPACE REQUIRED). SUBMIT DETAILS. - | | | RESPONSE NOTED, BUT THE FOLLOWING | | | INFORMATION IS REQUIRED: | | | DETAILS #9 & 10 SHT A-16 & #11 A-17 | | | A. 11-4.24.2 HEIGHT | | | B. 11-4.24.3 KNEE CLEARANCE | | | C. 11-4.24.4 SINK DEPTH - SINK MODEL | | | INDICATED IS 7-11/16", AND MAX DEPTH IS | | | 6-1/2" | | | D. 11-4.24.5 CLEAR FLOOR SPACE - | | | FORWARD APPROACH IS REQUIRED AND SHALL | | | EXTEND A MAXIMUM 19" UNDERNEATH THE SINK | | | - CABINET DOORS ARE NOT ALLOWED IN THE | | | CLEAR FLOOR SPACE. | | | E. 11-4.24.6 EXPOSED PIPES & SURFACES | | | (N1) GARBAGE DISPOSAL CAN NOT BE IN THE | | | CLEAR FLOOR SPACE FOR THE SINK. | | | SHT A-5 INDICATES A SINK IN THE OWNERS | | | LOUNGE, BUT DETAIL #9 SHT A-16 DOES NOT | | | SHOW THE SINK. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | 5) SHT A-24 DETAILS 1, 2, 3, & 4 THE | | | WATER CLOSETS SHALL BE 18" FROM | | | CENTERLINE OF THE FIXTURE TO THE WALL. | | | SEE FIG 28. THE LAV SHALL BE MINIMUM 15" | | | FROM THE CENTERLINE OF THE FIXTURE TO | | | THE WALL. (CENTERED ON CLEAR FLOOR SPACE | | | 30" MEASUREMENT). - DETAIL #4 | | | INFORMATION REQUIRED NOT SHOWN. | | | 7) SHT A-24 DETAIL 5, PRIVATE RESTROOM | | | TO BE ADAPTABLE. SECTION 11-4.1.3(11). | | | SUBMIT DETAILS SHOWING BACKING FOR GRAB | | | BARS AT W/C & SHOWER. SHOW W/C AT 18" TO | | | CENTERLINE OFF WALL, LAV TO BE MINIMUM | | | 15" TO CENTERLINE OFF WALL, SHOWER SHALL | | | SHOW BACKING FOR SEAT (IF REQUIRED - | | | INDICATE SIZE OF SHOWER), SHOW LOCATION | | | OF CONTROLS, AND SHOW CURB SIZE, (MAX. | | | 1/2") IF PROVIDED. ALSO SHOW 5' TURNING | | | AREA. SEE SECTIONS 11-4.16, 11-4.19, | | | 11-4.21. 11-4.22. - PER SECTION | | | 11-4.21.2 THE SIZE OF THE SHOWER STALL | | | SHALL COMPLY WITH FIGURE 35(A) OF 35(B). | | | THE SIZE OF THE SHOWER STALL SHOWN DOES | | | NOT COMPLY WITH EITHER. - NO CURB HEIGHT | | | IS SHOWN. | | | ***NOTE ALL PLUMBING SHEETS HAVE BEEN | | | RENUMBERED**** | | | 8) SHT P0.1 PLUMBING FIXTURE SCHEDULE, | | | SUBMIT MANUF SPECIFICATION SHEETS FOR | | | THE TANKLESS WATER HEATERS. LISTING IS | | | REQUIRED. SECTION 303.4. - NOW ON SHEET | | | P-4, NO MANUF. SHEETS SUBMITTED. | | | 11) SHT P1.2 WATERFALL, INDICATE METHOD | | | OF BACKFLOW PREVENTION REQUIRED ON THE | | | WATER SUPPLY OF THE WATERFALL. SECTION | | | 608. KEYED NOTES #2. - NO RESPONSE | | | NOTED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. - | | | NO RESPONSE TO THIS REQUEST. | | | | | | ***************NEW COMMENTS************* | | | 1B. SHT P-1 SUBMIT MANUF. SPECIFICATION | | | SHEETS FOR THE SCAVANGER SYSTEM. PLEASE | | | SUBMIT MORE INFORMATION ON THE SYSTEM, | | | AS IN THE INSTALLATION INSTRUCTIONS. | | | SECTION 104.2.1. | | | 2B. SHT P-2 PLEASE INDICATE THE NUMBER | | | OF OXYGEN TANKS AND THE AMOUNT OF OXYGEN | | | TO BE STORED IN THE CLOSET. - IF MORE | | | THAN ONE TANK TO BE USED ON THE MANIFOLD | | | THAN AN AUTOMATIC SWITCH OVER WITH | | | EXPLOSION PROOF VALVES ARE REQUIRED. - A | | | VENT TO THE OUTSIDE IS REQUIRED FROM THE | | | REGULATOR AND SHALL BE OF COPPER | | | MATERIAL. - THE CLOSET SHALL BE VENTED. | | | - A MASTER ALARM IS REQUIRED WITH | | | PRESSURE INDICATOR AND RESERVE IN USE | | | INDICATOR. - SOLID DOOR REQUIRED WITH A | | | 1 HOUR OR 2 HOUR FIRE RATING. (TO BE | | | DETERMINED BY AMOUNT OF OXYGEN). | | | CONTRACTOR SHALL APPLY FOR SEPARATE MED | | | GAS PERMIT AND SHALL BE CERTIFIED AS A | | | CONTRACTOR AND THE INSTALLER SHALL BE | | | CERTIFIED WITH PICTURE I.D. AND | | | CERTIFICATION AT TIME OF APPLICATION. | | | 3B. SHT P-2 THE FLOOR DRAIN FOR THE | | | WATER HEATER IS NOT APPROVED AS AN | | | INDIRECT WASTE RECEPTOR. A FLOOR SINK OR | | | A HUB DRAIN WILL BE REQUIRED PER | | | SECTIONS 802.3 & 802.3.2. | | | 4B. SEPARATE GAS PERMIT REQUIRED. THE | | | FOLLOWING INFORMATION IS REQUIRED: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. - NO ALL CUT SECTION | | | LENGTHS SHOWN. | | | B. TYPE OF GAS, (LP OR NATURAL) | | | C. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SECTION 304. | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | E. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | F. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | 5B. PLANS SHALL BE SUBMITTED AS SETS OF | | | PLANS. LOOSE SHEETS NOT APPROVED. | | | SECTION 104.2.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-01-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-01-24 |
Time |
13:13 |
Rev Time |
5.00 |
| Received By |
kstevens |
Date |
2005-01-22 |
Time |
18:54 |
Sent To |
|
|
| Notes |
| 2005-01-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) IRRIGATION PLANS AND PERMIT ARE | | | REQUIRED. SECTION 104.3.1.1. | | | 2) SHT A-3 IN THE INSTALLATION OR | | | REMOVAL OF ANY PART OF A DRAINATE | | | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. | | | SECTION 704.5. | | | 3) SHT A-9 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS PER | | | SECTIONS 1106, AND 1107 AND ALL | | | SUBSECTIONS. SHOW TOTAL SQUARE FOOTAGE | | | FOR ROOF, AND SHOW 1/2 AREA OF ALL | | | VERTICAL WALLS, INCLUDING PARAPETS ADDED | | | TO SQUARE FOOTAGE. ALSO IN CALCULATION, | | | SHOW THE AREA OF ANY ROOF DRAINING ONTO | | | THE ROOF FROM ABOVE. SHOW THE LOCATION | | | OF ALL PRIMARY AND SECONDARY ROOF | | | DRAINS. SECTION 104.2.1. | | | 4) SHTS A-16 & A-17 LOUNGE SINKS SHALL | | | COMPLY WITH SECTION 11-4.24 AND ALL | | | SUBSECTIONS. (FORWARD APPROACH CLEAR | | | FLOOR SPACE REQUIRED). SUBMIT DETAILS. | | | 5) SHT A-24 DETAILS 1, 2, 3, & 4 THE | | | WATER CLOSETS SHALL BE 18" FROM | | | CENTERLINE OF THE FIXTURE TO THE WALL. | | | SEE FIG 28. THE LAV SHALL BE MINIMUM 15" | | | FROM THE CENTERLINE OF THE FIXTURE TO | | | THE WALL. (CENTERED ON CLEAR FLOOR SPACE | | | 30" MEASUREMENT). | | | 6) SHT A-24 DETAIL 4, TOILET ROOM 129 | | | SHALL BE ACCESSIBLE. "IF TOILET ROOMS | | | ARE PROVEDED. THEN EACH PUBLIC AND | | | COMMON USE TOILET ROOM SHALL COMPLY WITH | | | SECTION 11-4.22. SECTIONS 11-4.1.2(6) & | | | 11-4.1.3(11). SUBMIT DETAILS. | | | 7) SHT A-24 DETAIL 5, PRIVATE RESTROOM | | | TO BE ADAPTABLE. SECTION 11-4.1.3(11). | | | SUBMIT DETAILS SHOWING BACKING FOR GRAB | | | BARS AT W/C & SHOWER. SHOW W/C AT 18" TO | | | CENTERLINE OFF WALL, LAV TO BE MINIMUM | | | 15" TO CENTERLINE OFF WALL, SHOWER SHALL | | | SHOW BACKING FOR SEAT (IF REQUIRED - | | | INDICATE SIZE OF SHOWER), SHOW LOCATION | | | OF CONTROLS, AND SHOW CURB SIZE, (MAX. | | | 1/2") IF PROVIDED. ALSO SHOW 5' TURNING | | | AREA. SEE SECTIONS 11-4.16, 11-4.19, | | | 11-4.21. 11-4.22. | | | 8) SHT P0.1 PLUMBING FIXTURE SCHEDULE, | | | SUBMIT MANUF SPECIFICATION SHEETS FOR | | | THE TANKLESS WATER HEATERS. LISTING IS | | | REQUIRED. SECTION 303.4. | | | 9) SHT P1.1 DEMO NOTES. NO DEAD ENDS ON | | | THE SANT. SYSTEM. SECTION 704.5 | | | 10) SHTS P1.1 & P5.1 ONLY THE FIXTURES | | | WITHIN THE BATHROOM GROUPS SHALL CONNECT | | | TO THE WET-VENTED HORIZONTAL BRANCH | | | DRAIN. ANY ADDITIONAL FIXTURES SHALL | | | DISCHARGE DOWNSTREAM OF THE WET VENT. | | | SECTION 909.1 (SEE ALL BATHROOM GROUPS - | | | AND REDLINE EXAMPLES ON ONE SET OF SANT. | | | RISERS). SECTION 909.1 | | | 11) SHT P1.2 WATERFALL, INDICATE METHOD | | | OF BACKFLOW PREVENTION REQUIRED ON THE | | | WATER SUPPLY OF THE WATERFALL. SECTION | | | 608. KEYED NOTES #2. | | | 12) SHT P1.2 KEYED NOTES #1 BACKFLOW | | | PREVENTER SHALL BE INSTALLED MINIMUM OF | | | 12" ABOVE GRADE TO BOTTOM OF OUTLET. | | | 13) SHT P5.1 SANT. RISER DIAGRAM, DOUBLE | | | SANITARY TEE PATTERNS SHALL NOT RECEIVE | | | THE DISCHARGE OF FIXTURES OR APPLIANCES | | | WITH PUMPING ACTION DISCHARGE. SECTION | | | 706.3. (SEE WASHERS ROOM 149). | | | 14) SHT P5.2 WATER HAMMER ARRESTORS ARE | | | REQUIRED AT THE WASHERS. SECTION 604.9. | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
lshapiro |
Date |
2006-02-07 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
lshapiro |
Date |
2006-02-07 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2006-02-07 00:00:00 | APPROVED - SHEETS A-4 AND A-4.1 PLANS | | | RECEIVED AS REQUESTED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2006-01-03 |
|
|
Cont ID |
|
| Sent By |
lshapiro |
Date |
2006-01-03 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
lshapiro |
Date |
2006-01-03 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2006-01-03 00:00:00 | APPROVED.ZONING REVIEW OF RELEVENT | | | PAGES A-4 AND A-4.1. | | | | | | APPLICANT SHALL PROVIDE 3 SETS OF 24X36 | | | PLANS AND TWO REDUCTIONS OF EACH OF THE | | | PAGES. | | | DEPUTY DIRECTOR OKAY WITH PLANS NOT | | | MATCHING APPROVED SPECIAL USE PERMIT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2006-01-20 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-01-20 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2006-01-20 00:00:00 | 2ND REVIEW STOP NOT USED |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-01-31 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2005-01-31 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
lshapiro |
Date |
2006-01-03 |
Time |
09:14 |
Sent To |
|
|
| Notes |
| 2005-01-31 00:00:00 | SITE PLAN DOES NOT MATCH PLAN APPROVED | | | WITH THE CLASS B SPECIAL USE PERMIT. | | | NORTHEAST PARKING ROW/DUMPSTER | | | DIFFERENT-NEW PARKING SPACE LAYOUT | | | REQUIRES INTERIOR ISLAND. | | | 28 PARKING SPACES SHALL BE MAINTIANED. | | | DUMPSTER DETATIL IS NOT TO CODE-SECTION | | | 94-444(B) FIGURE XIV-3, TO INCLUDE | | | LANDSCAPING. | | | DATA TABLE SHOWING PERCENTAGE OF OPEN | | | SPACE, LANDSCAPING, BUILDING COVERAGE, | | | IMPERVIOUS AREA, FLOOR AREA RATIO, ETC. | | | IS REQUIRED. | | | LANDSCAPE PLAN MEETING CODE REQUIREMENTS | | | IS REQUIRED. | | | PHOTOMETRIC PLAN SHOWING NO MORE THAN | | | 0.5 FOOTCANDLES AT THE CENTERLINE OF THE | | | ALLEY IS REQUIRED-NO GLARE MAY SHINE TO | | | RESIDENTIAL BUILDING. | | | ADA WALKWAY SHALL CONNECT THE BUILDING | | | TO THE SIDEWALK AT FRONT OF PROPERTY. | | | THE DRIVE AISLE FOR THE WEST (FRONT) | | | PARKING AREA SHALL BE A MINIMUM OF 24 | | | FEET WIDE FOR 2-WAY TRAFFIC.SUGGEST | | | SHORTENING PARKING STALLS FROM 20 FEET | | | TO 18 FEET TO MEET REQUIREMENT. | | | SIGNAGE DETAILS FOR AWNING AND BUILDING | | | SIGNS WILL BE APPROVED UNDER A SEPERATE | | | PERMIT. | | | CONTACT DAVID KANNING, PLANNER @ (561) | | | 822-1435. |
|
|