Plan Review Details - Permit 04121358
Plan Review Stops For Permit 04121358
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-06-09 Cont ID  
Sent By alange Date 2005-06-09 Time 14:21 Rev Time 0.50
Received By alange Date 2005-06-09 Time 14:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-05-31 Cont ID  
Sent By alange Date 2005-05-31 Time 07:48 Rev Time 1.00
Received By alange Date 2005-05-27 Time 16:26 Sent To  
Notes
2005-05-31 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 4.PRODUCT APPROVALS:
 ALL PRODUCT APPROVALS SUBMITTED REQUIRE
 THE FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-11 Cont ID  
Sent By pkrauss Date 2005-03-11 Time 13:33 Rev Time 0.66
Received By alange Date 2005-03-11 Time 11:32 Sent To M
Notes
2005-03-11 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.DESCRIPTION OF PROJECT ON
 APPLICATION DOES NOT REFLECT THE WORK ON
 PLANS.SUBMIT A SCOPE OF WORK FOR THIS
 PROJECT IN DETAIL.
 WHAT BUILDING IS THIS WORK TO BE
 COMPLETED ON.THERE ARE TWO BUILDINGS
 ON THE PROPERTY.
 PLANS SHOULD SHOW NEW AND EXISTING
 WORK.
  
 3.VALUE OF PROJECT IS TO LOW BASED ON
 INFORMATION ON PLANS, REVISE PERMIT
 VALUE AND PAY ADDITIONAL PERMIT FEES.
  
 4.PRODUCT APPROVALS:
 PRODUCT APPROVALS WITH QUALITY ASSURANCE
 ARE MISSING FOR WINDOWS AND EXTERIOR
 DOORS.
 ALL PRODUCT APPROVALS SUBMITTED REQUIRE
 THE FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEW NOTE:AS PER BUILDING INSPECTOR TOM
 MOORE, WORK WAS DONE ON PORCH AND STEP
 ALONG WITH WINDOW WORK.PLANS TO NOT
 SHOW ANY DETAILS FOR THIS WORK.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-26 Cont ID  
Sent By alange Date 2005-01-26 Time 10:22 Rev Time 1.00
Received By alange Date 2005-01-26 Time 10:04 Sent To  
Notes
2005-01-26 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.DESCRIPTION OF PROJECT ON
 APPLICATION DOES NOT REFLECT THE WORK ON
 PLANS.SUBMIT A SCOPE OF WORK FOR THIS
 PROJECT IN DETAIL.
 WHAT BUILDING IS THIS WORK TO BE
 COMPLETED ON.THERE ARE TWO BUILDINGS
 ON THE PROPERTY.
 PLANS SHOULD SHOW NEW AND EXISTING
 WORK.
  
 3.VALUE OF PROJECT IS TO LOW BASED ON
 INFORMATION ON PLANS, REVISE PERMIT
 VALUE AND PAY ADDITIONAL PERMIT FEES.
  
 4.PRODUCT APPROVALS:
 PRODUCT APPROVALS WITH QUALITY ASSURANCE
 ARE MISSING FOR WINDOWS AND EXTERIOR
 DOORS.
 ALL PRODUCT APPROVALS SUBMITTED REQUIRE
 THE FOLLOWING TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.TYPES OF WINDOWS USED NOT MENTIONED
 ON WINDOW SCHEDULE.
  
 6.ENERGY CALCS NOT SIGNED BY
 OWNER/AGENT.
  
 7.ATTIC ACCESS SIZE SHALL COMPLY WITH
 FBC 2309.6
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-05-03 Cont ID  
Sent By dpalmer Date 2005-05-03 Time 13:18 Rev Time 0.50
Received By dpalmer Date 2005-05-03 Time 13:18 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-02 Cont ID  
Sent By dpalmer Date 2005-03-02 Time 17:42 Rev Time 0.50
Received By dpalmer Date 2005-03-02 Time 17:33 Sent To P
Notes
2005-03-02 00:00:00****** UNSAT 2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 NO
  
 3)NOTE: NOTE #3 NO.
  
 4)NOTE: NOTE #4 NO.
  
 NEW NOTES.
  
 1)NOTE: PLEASE SEE SERVICE IS NOW SHOWN
 AS 300A'S, PLEASE SEE PREVIOUS NOTES AND
 VERIFY AND SHOW EXSITING SEC'S.
 310.16,240.4
  
 2)NOTE: PLEASE SEE PANEL "B" IS SHOWN
 "OUTSIDE" OF UNIT. PLEASE SEE DOORS.
 PANEL "B" INDICATES PANEL IN LAUNDRY RM.
  
 3)NOTE: PLEASE CORRELATE MECHANICAL
 PLANS WITH ELECTRICAL PLANS FOR AHU KW
 LOADS. ONE FOR UNIT IS SHOWN AS 7KW AND
 ELECTRICAL SHOWS 4.5KW.
  
 4)NOTE: PLEASE SEE 220.31B, AHU, HEAT IS
 FIGURED AT 100% AND MAY NOT TAKE A
 DERATING OF 65% ON EXISTING
 SERVICES/DWELLINGS.
  
 5)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED. THIS IS ONLY A
 NOTICE THAT IS GIVEN AT THIS TIME.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-28 Cont ID  
Sent By dpalmer Date 2004-12-28 Time 17:48 Rev Time 0.33
Received By dpalmer Date 2004-12-28 Time 17:48 Sent To  
Notes
2004-12-28 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE SD'S ARE INDICATED AS
 WIRED TO LT CIRCUIT IN LIV RM ETC.
 THIS IS FINE HOWEVER, PLEASE BE AWARE
 UNDER THE 2002 NEC 210.12, "ALL OUTLETS"
 IN BEDRMS ARE REQUIRED TO HAVE ARC FAULT
 PROTECTION. THIS WOULD INCLUDE THESE
 ADDITIONAL CIRCUITS UNLESS SD'S ARE
 PLACED ON WITH BEDRM CIRCUIT(S).
  
 2)NOTE: PLEASE VERIFY AND/OR NOTE SIZE
 OF EXISTING SEC'S FOR 250A SERVICE AS
 SHOWN.
 PLEASE SEE MIN SEC'S PER 310.16, 240.4B
  
 3)NOTE: PLEASE VERIFY EXISTING GROUNDING
 ELECTRODE SYSTEM TO MEET 250.50 WITH THE
 EXCEPTION OF EXISTING FOOTER STEEL.
  
 4)NOTE: PLEASE SEE MISSING RECEPT ON 2'
 OF WALL SPACE IN BEDRM #2 SECOND FLR.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 16:08 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 16:08 Sent To M
Notes
2006-08-08 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-07-12 Cont ID  
Sent By adarroug Date 2006-07-12 Time 11:39 Rev Time 0.00
Received By adarroug Date 2006-07-12 Time 11:39 Sent To M
Notes
2006-07-12 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-03 Cont ID  
Sent By shill Date 2005-06-03 Time 15:20 Rev Time 0.00
Received By shill Date 2005-06-03 Time 15:20 Sent To B
Notes
2005-06-03 00:00:00TO AL DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-26 Cont ID  
Sent By adarroug Date 2005-04-26 Time 16:40 Rev Time 0.00
Received By adarroug Date 2005-04-26 Time 16:40 Sent To E
Notes
2005-04-26 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-11 Cont ID  
Sent By adarroug Date 2005-03-11 Time 13:11 Rev Time 0.00
Received By adarroug Date 2005-03-11 Time 13:11 Sent To P
Notes
2005-03-11 00:00:00TO "KSTEVENS" BOX(SFR)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-02 Cont ID  
Sent By adarroug Date 2005-03-02 Time 10:51 Rev Time 0.00
Received By adarroug Date 2005-03-02 Time 10:51 Sent To E
Notes
2005-03-02 00:00:00TO DPALMER DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-27 Cont ID  
Sent By mjacobs Date 2004-12-27 Time 08:00 Rev Time 0.00
Received By mjacobs Date 2004-12-27 Time 08:00 Sent To E
Notes
2004-12-27 00:00:00SENT TO "E" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-08-10 Cont ID  
Sent By tgordon Date 2006-08-10 Time 14:10 Rev Time 0.25
Received By tgordon Date 2006-08-10 Time 14:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-08-03 Cont ID  
Sent By tgordon Date 2006-08-03 Time 08:43 Rev Time 0.30
Received By tgordon Date 2006-08-03 Time 08:43 Sent To  
Notes
2006-08-03 00:00:00MECHANICAL REVISION
 *** DENIED ***
 1) FIRST FLOOR BEDROOM #1 (MASTER SUITE)
 9" RETURN AIR TRANSFER DUCT NEEDS TO BE
 13" OR LARGER, SEE NOTE #4.
  
 2) FIRST FLOOR BEDROOM #2, 9" RETURN AIR
 TRANSFER DUCT NEEDS TO BE 11" OR LARGER,
 SEE NOTE #4.
  
 3) SECOND FLOOR BEDROOM #1 (MASTER
 SUITE) 9" RETURN AIR TRANSFER DUCT NEEDS
 TO BE 11" OR LARGER, SEE NOTE #4.
  
 4) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-07-12 Cont ID  
Sent By tgordon Date 2006-07-12 Time 16:36 Rev Time 0.20
Received By tgordon Date 2006-07-12 Time 16:36 Sent To P
Notes
2006-07-12 00:00:00REVISION TO MECH. PLANS PAGE M-1 .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-05-27 Cont ID  
Sent By pkrauss Date 2005-05-27 Time 16:04 Rev Time 0.35
Received By pkrauss Date 2005-05-27 Time 16:04 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-01-10 Cont ID  
Sent By pkrauss Date 2005-01-10 Time 07:36 Rev Time 0.35
Received By pkrauss Date 2005-01-10 Time 07:03 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-07-18 Cont ID  
Sent By jleech Date 2006-07-18 Time 13:24 Rev Time 0.00
Received By jleech Date 2006-07-18 Time 13:23 Sent To  
Notes
2006-07-18 00:00:00REVISED RISER DIAGRAM AND FLAT DRAWING
 OK

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-05-17 Cont ID  
Sent By jleech Date 2005-05-17 Time 08:19 Rev Time 0.50
Received By jleech Date 2005-05-17 Time 08:19 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-05-14 Cont ID  
Sent By jleech Date 2005-05-14 Time 07:00 Rev Time 0.50
Received By jleech Date 2005-05-14 Time 06:59 Sent To M
Notes
2005-05-14 00:00:00DENIED;
 PAGE P-1 FLOOR PLAN IS NOT THE SAME AS
 PAGE 1. PAGE 1 FLOOR PLAN HAS 1 BATHROOM
 FOR EACH APARTMENT, PAGE P-1 HAS 2
 BATHROOMS FOR EACH APARTMENT. SANITARY
 RISER DIAGRAM ON PAGE P-2 ALSO SHOWS 2
 BATHROOMS FOR EACH APARTMENT. PLEASE FIX
 AND RESUB.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-03-11 Cont ID  
Sent By kstevens Date 2005-03-11 Time 09:55 Rev Time 0.25
Received By kstevens Date 2005-03-11 Time 09:55 Sent To M
Notes
2005-03-11 00:00:00NO PLUMBING PLANS SUBMITTED - REPLACE
 PLUMBING FIXTURES ONLY.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-01-01 Cont ID  
Sent By jleech Date 2005-01-01 Time 13:15 Rev Time 0.50
Received By jleech Date 2005-01-01 Time 13:15 Sent To M
Notes
***NONE***