Plan Review Details - Permit 04121254
Plan Review Stops For Permit 04121254
Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2006-07-13 Cont ID  
Sent By jwitmer Date 2006-07-13 Time 16:08 Rev Time 2.00
Received By jwitmer Date 2006-07-13 Time 16:08 Sent To M
Notes
2006-07-13 00:00:00DELETE WALL RATING OF STAIR AT
 MEZZANINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2006-06-01 Cont ID  
Sent By jwitmer Date 2006-06-01 Time 10:05 Rev Time 0.77
Received By jwitmer Date 2006-06-01 Time 10:05 Sent To ENG
Notes
2006-06-01 00:00:00REVISION CHANGE IN HANDICAPPED ACCESS
 RAMP AND SIDEWALK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2006-05-02 Cont ID  
Sent By jwitmer Date 2006-05-02 Time 12:43 Rev Time 0.66
Received By jwitmer Date 2006-05-02 Time 12:27 Sent To PC
Notes
2006-05-02 00:00:00ROOFING 04121255 BUTLER VSR METAL ROOF

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status F Date 2006-04-19 Cont ID  
Sent By jwitmer Date 2006-04-19 Time 17:53 Rev Time 0.77
Received By jwitmer Date 2006-04-19 Time 17:53 Sent To  
Notes
2006-04-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04121254
 ADD: 1318 MERCER AV
 CONT:SOUTHERN CONSTRUCTION
 TEL: (561)718-8876
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ROOF SUBMITTAL
 ACTION: DENIED
  
 1) SUBMIT THE PTID 4897 I BUTLER NS ROOF
 UL TEST . PDF FILE FOR THE APPLICATION
 TO BE USED ON THIS PROJECT. EITHER
 SYSTEM TEST:
 345
 345A
 483.2
 2) DESIGN PROFESSIONAL TO REVIEW PRODUCT
 TESTING. DESIGN PRESSURE OF 52.5
 ZONES 2 & 3 TO BE REVIEWED BY THE DESIGN
 PROFESSIONAL INCREASED DESIGN PRESSURE
 AT PERIMETER AND CORNERS MAY BE MET BY
 RATIONAL ANALYSIS BY DESIGN
 PROFESSIONAL.
 BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION:
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2006-04-03 Cont ID  
Sent By jwitmer Date 2006-04-03 Time 10:55 Rev Time 0.77
Received By jwitmer Date 2006-04-03 Time 10:55 Sent To PC
Notes
2006-04-03 00:00:00REVISION: 14' WIDE ROLL UP DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2006-02-27 Cont ID  
Sent By jwitmer Date 2006-02-27 Time 12:11 Rev Time 1.00
Received By jwitmer Date 2006-02-27 Time 12:11 Sent To  
Notes
2006-02-27 00:00:00DETAIL LG02 FLANGE W BRACE TO "W"
 SECTION
  
 STRUCTURAL ROOF DETAIL , 18 GA MTL
 TRUSSES & TAPCONS
  
 WALL SECONDARY STRUCTURAL ELEVARION
 DETAIL10-24-05

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2006-02-06 Cont ID  
Sent By jwitmer Date 2006-02-06 Time 11:03 Rev Time 1.00
Received By jwitmer Date 2006-02-06 Time 11:03 Sent To  
Notes
2006-02-06 00:00:00REV SK1-12 JAN 06, SK 1-4 JAN 06

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2006-01-17 Cont ID  
Sent By jwitmer Date 2006-01-17 Time 09:51 Rev Time 0.55
Received By jwitmer Date 2006-01-17 Time 09:51 Sent To PC
Notes
2006-01-17 00:00:00STRUCTURAL DETAIL SHEET8-21-05

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2005-12-23 Cont ID  
Sent By jwitmer Date 2005-12-23 Time 10:45 Rev Time 2.22
Received By jwitmer Date 2005-12-23 Time 10:45 Sent To PC
Notes
2005-12-23 00:00:0012-23-05 REVISIONS:
 1) YKK STOREFRONT
 2) YKK EXT DOORS
 3) STRUCTURAL REPAIR12-14-05SHEET "A-B"

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2005-12-16 Cont ID  
Sent By jwitmer Date 2005-12-16 Time 15:53 Rev Time 2.22
Received By jwitmer Date 2005-12-16 Time 15:53 Sent To PC
Notes
2005-12-16 00:00:00VARIOUS SUBMITTALSDAILY REPORTS,
 CORRECTION REPORTS,

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2005-11-29 Cont ID  
Sent By jwitmer Date 2005-11-29 Time 15:02 Rev Time 0.77
Received By jwitmer Date 2005-11-29 Time 15:02 Sent To PC
Notes
2005-11-29 00:00:00SUBMITTAL# 10 PURLIN BRACES
 PURLIN CONN TO TILT WALL
 LETTER FOR MODIFICATIONS GIRT CLIP
 6"X6" WALL ANGLE APPROVAL FROM ENG
 1/2" FASTENER APPROVAL
 SHIM APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-08-20 Cont ID  
Sent By jwitmer Date 2005-08-20 Time 13:14 Rev Time 1.11
Received By jwitmer Date 2005-08-20 Time 13:14 Sent To PC
Notes
2005-08-20 00:00:008-20-05 SUBMITTALS
 REV PANEL P57
 ROOF SECONDARY FRAMING PLAN
 123135

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2005-08-20 Cont ID  
Sent By jwitmer Date 2005-08-20 Time 11:18 Rev Time 1.11
Received By jwitmer Date 2005-08-20 Time 11:18 Sent To PC
Notes
2005-08-20 00:00:0008-20-05 THE FOLLOWING SUBMITTALS WERE
 REVIEWED:
 1) TIT WALL ENGINEERING BOOK PANELS
 2) TILT WALL SHOP DRAWINGS 4-21-05
 3) TILT WALL PANEL REVISIONS 7-27-05
 4) REV: 7-12-05 RFI 15
 5) TILT WALL REV 8-08-05
 6) REV 8-03-05 REFS5.0-5.1.-.2-5.3
 7) REV 5-18-05 LDT ANCHORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-07-20 Cont ID  
Sent By jwitmer Date 2005-07-20 Time 07:40 Rev Time 0.55
Received By jwitmer Date 2005-07-20 Time 07:40 Sent To PC
Notes
2005-07-20 00:00:00STRUCTURAL STEEL CLARIFICATIONS,
 REVISED SECTION 1/S2.0,
 FIELD REPORT #2

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-06-28 Cont ID  
Sent By jwitmer Date 2005-06-28 Time 07:17 Rev Time 0.55
Received By jwitmer Date 2005-06-28 Time 07:17 Sent To PC
Notes
2005-06-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04121254
 ADD: 1318 MERCER AVE
 CONT: SOUTHERN CONST
 TEL: (561)881-8091
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET SKI-22MAY05 PEIR DETAIL HAS
 HAND WRITTEN INFORMATION NOT SIGNED BY
 P.E.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-05-04 Cont ID  
Sent By jwitmer Date 2005-05-04 Time 14:25 Rev Time 0.55
Received By jwitmer Date 2005-05-04 Time 14:25 Sent To PC
Notes
2005-05-04 00:00:0005-04-05 SHOP DRAWINGSOK JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-04-19 Cont ID  
Sent By jwitmer Date 2005-04-19 Time 07:02 Rev Time 0.50
Received By jwitmer Date 2005-04-19 Time 07:02 Sent To  
Notes
2005-04-19 00:00:00BUILDING PLAN REVIEW
 PERMIT:04121254
 ADD:1318 MERCER AV
 CONT:SOUTHERN CONSTRUCTION
 TEL: (561)881-8091
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) SHOP DRAWINGS ARE REQUIRED TO BE
 REVIEWED BY THE DESIGNER OF RECORD AND
 APPROVED, APPROVED WITH CORRECTIONS
 BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-04-04 Cont ID  
Sent By jwitmer Date 2005-04-04 Time 09:32 Rev Time 2.22
Received By jwitmer Date 2005-04-04 Time 09:32 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-21 Cont ID  
Sent By jwitmer Date 2005-03-21 Time 16:38 Rev Time 0.00
Received By jwitmer Date 2005-03-21 Time 16:38 Sent To  
Notes
2005-03-21 00:00:00PERMIT: 04121254
 ADD: 1318 MERCER AVE
 CONT: SOUTHERN CONSTRUCTION
 TEL: (561)718-8876
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 IT MAY REQUIRE REPLATTING, SINCE THE
 SURVEY INDICATES 6 LOTS THAT WOULD
 REQUIRE COMBINING INTO ONE LOT.
  
 2) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA (805-6711),
 DIRECTOR OF THE RESIDENT INSPECTOR
 PROGRAM.A RESIDENT INSPECTOR PROGRAM
 IS REQUIRED, ON THIS PROJECT, DUE TO ONE
 OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION.
  
 3) SINCE THIS BUILDING REQUIRES A
 SPECIAL INSPECTOR, SUBMIT (3) SETS OF
 ALL DOCUMENTS, PLANS, REPORTS, PRODUCT
 APPROVALS, LETTERS AND OR SUBMITTALS .
  
  
 4) THE PLANS SUBMITTED FROM BUTLER
 MANUFACTURING COMPANY SHALL REQUIRE THE
 PLANS TO BE SIGNED WITH ORIGINAL
 SIGNATURE OF THE P.E., ALL 3 SETS NOT
 COPIES OF SIGNATURES.SIGNED & SEALED.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) A2.2 ROOF RACK HEIGHT:THE A?C RACK
 DETAIL INDICATES A MINIMUM OF 18" BUT
 DOES NOT PROVIDE INFORMATION IF THE UNIT
 IS 38" WIDE AS PROVIDED BY TABLE 1511.7.
 1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 6) TABLE 600 ISSUES SEE TYPEIV BLDG
 UNPROTECTED, FOOTNOTE (E) UNDER ROOF &
 ROOF CEILING ASSEMBLIES. ONLY FIRE
 RETARDANT TREATED WOOD CAN BE USED FOR
 SHEATHING ON BUILDINGS 2 STORIES OR
 LESS. SEE SHEET S0.2 NOTES PLYWOOD ROOF
 DECKING, ALSO S2.1 SECTION 5&6 PLEASE
 ANNOTE PLANS.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 3 COPIES OF THE
 PRODUCT APPROVAL FOR THRESHOLD OR
 RESIDENT INSPECTOR PROGRAM BUILDING.
  
 8) PROVIDE THE PALM BEACH COUNTY IMPACT
 FEE RECEIPT, PART OF PERMIT PACKAGE
 REQUIREMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-20 Cont ID  
Sent By jwitmer Date 2005-01-20 Time 13:36 Rev Time 3.33
Received By jwitmer Date 2005-01-20 Time 13:36 Sent To  
Notes
2005-01-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04121254
 ADD: 1318 MERCER AVE
 CONT: SOUTHERN CONSTRUCTION
 TEL: (561)718-8876
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
 IT MAY REQUIRE REPLATTING, SINCE THE
 SURVEY INDICATES 6 LOTS THAT WOULD
 REQUIRE COMBINING INTO ONE LOT.
  
 2) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA (805-6711),
 DIRECTOR OF THE RESIDENT INSPECTOR
 PROGRAM.A RESIDENT INSPECTOR PROGRAM
 IS REQUIRED, ON THIS PROJECT, DUE TO ONE
 OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION.
  
 3) SINCE THIS BUILDING REQUIRES A
 SPECIAL INSPECTOR, SUBMIT (3) SETS OF
 ALL DOCUMENTS, PLANS, REPORTS, PRODUCT
 APPROVALS, LETTERS AND OR SUBMITTALS .
  
  
 4) SUBMIT A THIRD SET OF ENERGY
 CALCULATIONS.
  
 5) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
 A SINGLE SIGNED & SEALED REPORT WAS
 SUBMITTED, (3) ORIGINAL SIGNED AND
 SEALED REPORTS ARE REQUIRED.
  
 6) THE PLANS SUBMITTED FROM BUTLER
 MANUFACTURING COMPANY SHALL REQUIRE THE
 PLANS TO BE SIGNED WITH ORIGINAL
 SIGNATURE OF THE P.E., ALL 3 SETS NOT
 COPIES OF SIGNATURES.SIGNED & SEALED.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 7) SEE SHEETS A-2.1 & A-3 FOR REQUIRED
 CLEARENCES AT THE PULL SIDE DOORS:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 8) A2.2 ROOF RACK HEIGHT SEE:
 1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 9) FBC* F102.2.7ARCHITECTURAL TRIM, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL BE CONSTRUCTED OF APPROVED
 NON-COMBUSTIBLE MATERIALS OR FIRE
 RETARDANT TREATED WOOD.ANNOTATE THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 10A) SHEET A-8 PROVIDE U.L. LISTING#
 G350 FOR A 2 HR FLOOR/ CEILING ASSEMBLY
 NOT IN 2004 LISTINGS.
 10B) THE SAME SHEET MISSING WALL DESIGN
 U.L. LISTING# U-465 FOR A (2)HR RATING,
 U.L. INDICATES A 1 HR RATING.
  
 11) A-9 STEEL BEAM PROTECTION PROVIDE
 THE U.L. LISTING FOR N306 , NOT IN 2004
  
 LISTING BOOK.
  
 12) TABLE 600 ISSUES SEE TYPEIV BLDG
 UNPROTECTED, FOOTNOTE (E) UNDER ROOF &
 ROOF CEILING ASSEMBLIES. ONLY FIRE
 RETARDANT TREATED WOOD CAN BE USED FOR
 SHEATHING ON BUILDINGS 2 STORIES OR
 LESS. SEE SHEET S0.2 NOTES PLYWOOD ROOF
 DECKING, ALSO S2.1 SECTION 5&6 PLEASE
 ANNOTE PLANS.
  
 13) S-2.1 DETAIL# 4, ADD INFORMATION AS
 WHAT TYPE OF MATERIAL IS USED ON THE END
 OF THE GIRDER TRUSS.
  
 14) SHEET S4.0 HEADER FOR PREENGINEERED
  
 METAL BUILDING DESIGN BASIS- MISSING
 WHAT BUILDING CODE DESIGNED UNDER?
  
 15)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 16) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 3 COPIES OF THE
 PRODUCT APPROVAL FOR THRESHOLD OR
 RESIDENT INSPECTOR PROGRAM BUILDING.
  
 17) PROVIDE THE PALM BEACH COUNTY IMPACT
 FEE RECEIPT, PART OF PERMIT PACKAGE
 REQUIREMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-03-04 Cont ID  
Sent By dpalmer Date 2005-03-04 Time 07:27 Rev Time 0.75
Received By dpalmer Date 2005-03-04 Time 06:57 Sent To  
Notes
2005-03-04 00:00:00SITE LIGHTING UNDER SEPARATE PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-05 Cont ID  
Sent By dpalmer Date 2005-01-05 Time 16:53 Rev Time 1.50
Received By dpalmer Date 2005-01-05 Time 16:53 Sent To  
Notes
2005-01-05 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE NOTE ON PLANS
 MENTIONS WIND LOADING FOR LT POLES AND
 FIXTURES TO BE PROVIDED BY CONTRACTOR.
 THIS SI REQUIRED AT THIS TIME AND TO BE
 A PART OF THIS PLAN REVIEW PROCESS.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE 700.12E FOR CIRCUTING OF
 EM/EXT LTS. PANEL SCHEDULE INDICATES
 EM/EXT LTS ON INDIVIDUAL CIRCUIT.THE
 BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 3)NOTE: PLEASE SEE FAC 61G15-23.002,
 WHICH ALSO REQUIRES THE PRINTED ANEM OF
 THE ENGINEER ON TITLE BLOCK.
  
 4)NOTE:PLEASE SEE 600.5 FOR REQUUIRED
 SIGN CIRCUIT.EACH COMMERCIAL BUILDING
 AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE
 TO PEDESTRIANS SHALL BE PROVIDED WITH AT
 LEAST ONE OUTLET IN AN ACCESSIBLE
 LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING
 SYSTEM USE. THE OUTLET(S) SHALL BE
 SUPPLIED BY A BRANCH CIRCUIT RATED AT
 LEAST 20 AMPERES THAT SUPPLIES NO OTHER
 LOAD. SERVICE HALLWAYS OR CORRIDORS
 SHALL NOT BE CONSIDERED ACCESSIBLE TO
 PEDESTRIANS.
  
 PLEASE REMOVE ALL OLD/ VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2006-06-01 Time   Rev Time 0.75
Received By   Date 2006-06-01 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-03-15 Cont ID  
Sent By mamini Date 2005-03-15 Time 12:08 Rev Time 1.00
Received By mamini Date 2005-03-15 Time 09:41 Sent To  
Notes
2005-03-01 00:00:00PASSED WITH PROVISOS:
  
 1. THE SURVEY DATA FOR THE EXISTING
 WATER, SEWER, AND STORM WATER AS
 REQUESTED BY THE PUBLIC UTILITIES AND
 ENGINEERING MUST BE SUBMITTED PRIOR TO
 OR AT PRE-CONSTRUCTION MEETING , SEE
 LETTER BY MR. KEVIN E. KRUT OF EAST BAY
 GROUP,LLC.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-12-30 Cont ID  
Sent By mamini Date 2004-12-30 Time 09:43 Rev Time 0.50
Received By mamini Date 2004-12-30 Time 09:42 Sent To  
Notes
2004-12-30 00:00:00FAILED:
  
 1. PLEASE SUBMIT CIVIL PLANS FOR OUR
 REVIEW AND APPROVAL, INCLUDE STORM WATER
 CALCULATION FOR THE PROPOSED SITE
 IMPROVEMENTS.
 2. PLEASE CONTACT MR. MANNY GONZALEZ @
 494-1085, PUBLIC UTILITIES AND
 ENGINEERING SERVICES FOR ALL THE
 CONNECTIONS TO THE CITY SERVICES.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-03-24 Cont ID  
Sent By mwennerg Date 2005-03-24 Time 14:54 Rev Time 0.00
Received By mwennerg Date 2005-03-24 Time 14:53 Sent To  
Notes
2005-03-28 00:00:00P-PROVISO
  
 1) PLEASE BE ADVISED THAT ALL WORK MUST
 COMPLY WITH NFPA 13, 2002 EDITION WHEN
 SEPARATE SHOP DRAWINGS ARE SUBMITTED.
 THIS OFFICE ADOPTED THE 2002 EDITION
 AFTER JAN. 1, 2005.
  
 2) A WRENCH SHALL BE PROVIDED WITH THE
 SPARE SPRINKLER HEADS.
  
 3) PLEASE BE ADVISED THAT THE FIRE
 SPRINKLER SYSTEM SHALL BE MONITORED BY A
 MONITORING COMPANY APPROVED AS A UL
 LISTED CENTRAL STATION SERVICE.
  
 4) PLEASE BE ADVISED THAT SEPARATE SHOP
 DRAWINGS AND PERMITS ARE REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR (561) 835-2910
2005-03-24 00:00:00P-PROVISO
  
 THANK YOU FOR YOUR EXPLANATIONS
 RERGARDING THE ORIGINAL REVIEW, HOWEVER
 ITEM #8 REQUIRES ADDITIONAL
 CLARIFICATION.
  
 1) PLEASE BE ADVISED THAT SEPARATE SHOP
 DRAWINGS AND PERMITS ARE REQUIRED FOR
 BOTH THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS. SHEET E-2 ONLY REFERS TO THE
 FIRE ALARM SYSTEM.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-24 Cont ID  
Sent By nmccray Date 2005-01-24 Time 15:07 Rev Time 0.00
Received By nmccray Date 2005-01-24 Time 12:13 Sent To  
Notes
2005-01-24 00:00:001) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3) BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 4) PLEASE PROVIDE ENGINEERED FIRE
 SPRINKLER DRAWINGS AND FLOW
 CALCULATIONS.
  
 5) THE FIRE ALARM SYSTEM SHALL BE
 MONITORED BY A LICENSED UL LISTED FIRE
 ALARM COMPANY FOR CENTRAL STATION
 SERVICE.
  
 6) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
 7) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 8) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 15:02 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 15:02 Sent To M
Notes
2006-08-11 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2006-06-26 Cont ID  
Sent By adarroug Date 2006-06-26 Time 15:02 Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 15:02 Sent To M
Notes
2006-06-26 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2006-05-30 Cont ID  
Sent By adarroug Date 2006-05-30 Time 15:52 Rev Time 0.00
Received By adarroug Date 2006-05-30 Time 15:52 Sent To M
Notes
2006-05-30 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2006-05-30 Cont ID  
Sent By adarroug Date 2006-05-30 Time 15:51 Rev Time 0.00
Received By adarroug Date 2006-05-30 Time 15:51 Sent To B
Notes
2006-05-30 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2006-04-29 Cont ID  
Sent By adarroug Date 2006-04-29 Time 15:44 Rev Time 0.00
Received By adarroug Date 2006-04-29 Time 15:44 Sent To B
Notes
2006-04-29 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2006-04-11 Cont ID  
Sent By adarroug Date 2006-04-11 Time 09:04 Rev Time 0.00
Received By adarroug Date 2006-04-11 Time 09:04 Sent To B
Notes
2006-04-11 00:00:00TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2006-04-03 Cont ID  
Sent By adarroug Date 2006-04-03 Time 11:12 Rev Time 0.00
Received By adarroug Date 2006-04-03 Time 11:11 Sent To M
Notes
2006-04-03 00:00:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2006-03-28 Cont ID  
Sent By adarroug Date 2006-03-28 Time 15:50 Rev Time 0.00
Received By adarroug Date 2006-03-28 Time 15:50 Sent To B
Notes
2006-03-28 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2006-02-17 Cont ID  
Sent By adarroug Date 2006-02-17 Time 14:58 Rev Time 0.00
Received By adarroug Date 2006-02-17 Time 14:58 Sent To B
Notes
2006-02-17 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 12:01 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 12:01 Sent To B
Notes
2006-01-22 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2006-01-04 Cont ID  
Sent By adarroug Date 2006-01-04 Time 13:46 Rev Time 0.00
Received By adarroug Date 2006-01-04 Time 13:46 Sent To B
Notes
2006-01-04 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2005-12-20 Cont ID  
Sent By adarroug Date 2005-12-20 Time 17:09 Rev Time 0.00
Received By adarroug Date 2005-12-20 Time 17:09 Sent To B
Notes
2005-12-20 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 14:43 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 14:42 Sent To B
Notes
2005-12-16 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2005-11-18 Cont ID  
Sent By adarroug Date 2005-11-18 Time 13:56 Rev Time 0.00
Received By adarroug Date 2005-11-18 Time 13:56 Sent To B
Notes
2005-11-18 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 16:01 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 16:01 Sent To B
Notes
2005-10-19 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 15:57 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 15:57 Sent To B
Notes
2005-08-18 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 16:02 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 16:02 Sent To B
Notes
2005-08-09 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-08-04 Cont ID  
Sent By adarroug Date 2005-08-04 Time 16:06 Rev Time 0.00
Received By adarroug Date 2005-08-04 Time 16:06 Sent To B
Notes
2005-08-04 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 13:02 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 13:02 Sent To B
Notes
2005-08-03 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 10:30 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 10:30 Sent To B
Notes
2005-07-29 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-07-26 Cont ID  
Sent By adarroug Date 2005-07-26 Time 13:43 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 13:43 Sent To B
Notes
2005-07-26 00:00:00TO "JWITMER" DESK/SUBMITTAL
 1 ROLL SHOP DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-07-26 Cont ID  
Sent By adarroug Date 2005-07-26 Time 11:50 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 11:50 Sent To B
Notes
2005-07-26 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-07-26 Cont ID  
Sent By adarroug Date 2005-07-26 Time 11:15 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 11:15 Sent To B
Notes
2005-07-26 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-07-14 Cont ID  
Sent By adarroug Date 2005-07-14 Time 16:36 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 16:36 Sent To B
Notes
2005-07-14 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-07-13 Cont ID  
Sent By adarroug Date 2005-07-13 Time 10:50 Rev Time 0.00
Received By adarroug Date 2005-07-13 Time 10:50 Sent To I
Notes
2005-07-13 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-01 Cont ID  
Sent By adarroug Date 2005-07-01 Time 14:26 Rev Time 0.00
Received By adarroug Date 2005-07-01 Time 14:26 Sent To B
Notes
2005-07-01 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-24 Cont ID  
Sent By adarroug Date 2005-06-24 Time 08:29 Rev Time 0.00
Received By adarroug Date 2005-06-24 Time 08:29 Sent To B
Notes
2005-06-24 00:00:00TO "JWITMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 10:28 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 10:28 Sent To B
Notes
2005-04-22 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 09:20 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 09:20 Sent To B
Notes
2005-04-15 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-28 Cont ID  
Sent By lmartine Date 2005-03-03 Time 15:37 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 11:31 Sent To  
Notes
2005-02-28 00:00:00TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-22 Cont ID  
Sent By mjacobs Date 2005-01-22 Time 15:37 Rev Time 0.00
Received By lmartine Date 2004-12-22 Time 16:27 Sent To  
Notes
2004-12-22 00:00:00SENT TO "COMM BD#56

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-08-15 Cont ID  
Sent By hmoser Date 2006-08-15 Time 09:11 Rev Time 0.00
Received By hmoser Date 2006-08-15 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-07-14 Cont ID  
Sent By tgordon Date 2006-07-14 Time 08:26 Rev Time 0.30
Received By tgordon Date 2006-07-14 Time 08:26 Sent To  
Notes
2006-07-14 00:00:00REVISION TO MECH. PAGE M-2.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-06-27 Cont ID  
Sent By tgordon Date 2006-06-27 Time 09:31 Rev Time 0.45
Received By tgordon Date 2006-06-27 Time 09:31 Sent To  
Notes
2006-06-27 00:00:00REVISION TO MACH. PAGE M-1 PASSED.
 *** REVISION TO MECH PAGE M-2 DENIED ***
 1) MECHANICAL ROOM ON MEZZANINE HAS A 1
 HOUR RATED WALL AND REQUIRES FIRE
 DAMPERS, PLEASE SEE ARCHITECTURAL PLANS
 PAGE A-2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-06-02 Cont ID  
Sent By tgordon Date 2006-06-02 Time 09:57 Rev Time 0.35
Received By tgordon Date 2006-06-02 Time 09:57 Sent To  
Notes
2006-06-02 00:00:00REVISION TO MECH. PLANS PAGE M-2.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-04-04 Cont ID  
Sent By tgordon Date 2006-04-04 Time 09:29 Rev Time 0.30
Received By tgordon Date 2006-04-04 Time 09:29 Sent To  
Notes
2006-04-04 00:00:00REVISION TO MECH. PLANS BY A SUBMITTAL
 LETTER.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2005-03-25 Time   Rev Time 0.00
Received By hmoser Date 2005-03-25 Time 08:35 Sent To  
Notes
2005-03-25 00:00:00REFER TO SECTION 307.2.3 AUXILIARY DRAIN
 PANS FLORIDA BUILDING CODE (M)
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-05 Cont ID  
Sent By pkrauss Date 2005-01-05 Time 11:20 Rev Time 0.00
Received By pkrauss Date 2005-01-05 Time 11:07 Sent To  
Notes
2005-01-05 00:00:00DENIED:
 1.PLAN SHEET A-8 DETAIL OF BUILDING
 SECTION A SHOWS 2 HR RATED FLOOR/CEILING
 ASSEMBLY UL #G350.THIS UL ASSEMBLY
 NUMBER IS NOT SHOWN IN THE UL FIRE
 RESISTANCE DIRECTORY.
  
 2.PENDING THE ASSEMBLY OF THIS AREA,
 FIRE DAMPERS AND RO RADIATION DAMPERS
 MAY BE REQURIED.
  
 3.PLEASE INDICATE WHAT TYPE OF WORK
 AND STORAGE WILL BE IN THE WAREHOUSE
 AREA AND AND THE DOOR SHOP AREA.PLEASE
 INDICATE AND GASES, CHEMICALS OR
 COMBUSTIBLES STORED OR USED IN THESE
 AREAS.
  
 4.PLEASE CLARIFY THE "WELDER" IN THE
 "WOOD DOOR ASSEMBLY" AREA.
  
 5.PLAN SHEET M-4 AHU HANGING DETAIL 1"
 GALVENIZED DRAIN PAN, PER 2001
 FBC(M)307.2.3 AUXILIARY DRAIN PAN SHALL
 BE A MINIMUM OF 1 1/2" DEEP AND NOT 1"
 AS SHOWN ON THE PLAN.
  
 6.PLAN SHEET M-4 INDICATES AHU HANGING
 DETAIL SHOWS THE AHU SUPPORT TO THE
 BOTTOM OF THE BAR JOIST.PROVIDE
 ENGINEER LETTER AND MANUFACTURER'S
 INSTALLATION SPECIFICATIONS SHOWING THIS
 IS ACCEPTABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-03-21 Cont ID  
Sent By kstevens Date 2005-03-21 Time 10:18 Rev Time 1.00
Received By kstevens Date 2005-03-21 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-17 Cont ID  
Sent By kstevens Date 2005-03-17 Time 16:10 Rev Time 1.50
Received By kstevens Date 2005-03-17 Time 16:10 Sent To  
Notes
2005-03-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 A) FROM PREVIOUS REVIEW: THE COMMENT
 NUMBER SHALL STAY THE SAME TO AVOID
 CONFUSTION.
 3) SUBMIT A DETAIL FOR THE KITCHEN AND
 BREAK ROOM SINKS. SHOW COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. THE
 FOLLOWING SUBSECTIONS WERE NOT SHOWN.
 A) 11-4.24.4 SINK DEPTH
 B) 11-R.24.5 27" MIN. HEIGHT FOR KNEE
 CLEARANCE.
 C) 11-4.24.6 EXPOSED PIPES & SURFACES.
 D) 11-4.24.7 FAUCETS.
 4) SUBMIT A DETAIL FOR THE URINALS
 SHOWING COMPLIANCE WITH SECTION 11-4.18
 AND ALL SUBSECTIONS. NOT SHOWN WAS:
 A) 11-4.18.4 FLUSH CONTROLS.
 5) SUBMIT A DETAIL FOR THE SHOWER
 SHOWING COMPLIANCE WITH SECTION 11-4.21
 AND ALL SUBSECTIONS. NOT SHOWN WAS:
 A) 11-4.21.5 CONTROLS (HEIGHT NOT
 SHOWN)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-22 Cont ID  
Sent By kstevens Date 2005-01-22 Time 17:18 Rev Time 1.75
Received By kstevens Date 2005-01-22 Time 17:18 Sent To  
Notes
2005-01-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) TABLE 403.1 MINIMUM FACILITIES
 INDICATE THAT 3 DRINKING FOUNTAINS ARE
 REQUIRED. PLANS INDICATE 2 SUPPLIED.
 ALSO SEE SECTION 410.1.
 2) SUBMIT A DETAIL FOR DRINKING
 FOUNTAINS SHOWING COMPLIANCE WITH
 SECTION 11-4.15 AND ALL SUBSECTIONS.
 ALSO SHOW COMPLIANCE WITH SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 3) SUBMIT A DETAIL FOR THE KITCHEN AND
 BREAK ROOM SINKS. SHOW COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. A
 FORWARD APPROACH CLEAR FLOOR SPACE IS
 REQUIRED.
 4) SUBMIT A DETAIL FOR THE URINALS
 SHOWING COMPLIANCE WITH SECTION 11-4.18
 AND ALL SUBSECTIONS.
 5) SUBMIT A DETAIL FOR THE SHOWER
 SHOWING COMPLIANCE WITH SECTION 11-4.21
 AND ALL SUBSECTIONS.
 6) SHT A-4 OF 14 SHOWS THE CLEAR FLOOR
 SPACE AS 36"X42". MIN. CLEAR FLOOR SPACE
 FOR SINKS IS 30"X48". SECTION 11-4.24.5.
 THE CLEAR FLOOR SPACE ALSO INDICATES THE
 CLEAR FLOOR SPACE AS A PARALLEL APPROACH
 WHEN A FORWARD APPROACH IS REQUIRED.
 7) SHT A-5 OF 14 (SEE ABOVE COMMENT).
 8) SHTS P-1 & P-2 SANT. RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN. NO HAND
 SINK IS SHOWN ON THE RISER DIAGRAM.
 9) SHT P-2 WATER RISER DIAGRAM. FULL
 OPEN VALVES ARE REQUIRED ON TOP OF ALL
 WATER DOWN-FEED PIPES. SEE ROOM 120 AND
 JANITOR SINK BY STAIRS NEAR ROOM 120.
 10) SHT P-2 WATER RISER AND SANT. RISER
 DIAGRAMS, THE P&T RELIEF LINES SHALL NOT
 DRAIN INTO FUNNEL FLOOR DRAINS. FLOOR
 DRAINS ARE NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. A FLOOR SINK OR A HUB
 DRAIN IS REQUIRED. SECTIONS 802.3 AND
 802.3.2.
 11) SUBMIT MANUF. SPECIFICATION SHEETS
 FOR THE INSTA-HOT WATER HEATER SHOWN ON
 THE WATER RISER DIAGRAM SHT P-2. LISTING
 REQUIRED. SECTION 303.4.
 12) A SEPARATE PERMIT AND PLANS ARE
 REQUIRED FOR THE IRRIGATION. PLUMBING
 CONTRACTOR SHALL INSTALL BACKFLOW FOR
 IRRIGATION. SECTION 104.3.1.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-03-28 Cont ID  
Sent By lmartine Date 2005-03-28 Time 09:17 Rev Time 0.00
Received By lmartine Date 2005-03-28 Time 09:17 Sent To  
Notes
2005-03-28 00:00:00APPROVED BY RANDELL SEE PLANS FOR
 SIGNATURE

Review Stop Z ZONING
Rev No 1 Status F Date 2005-01-13 Cont ID  
Sent By mmclean Date 2005-01-13 Time 10:21 Rev Time 0.00
Received By mmclean Date 2005-01-13 Time 10:21 Sent To  
Notes
2005-01-18 00:00:00AWAITING PLANS FROM RECORDS RETENTION
 FOR REVIEWING.CALLED RGRANBERRY AT
 822-1454 MM
2005-01-13 00:00:00WAITING FOR THE LETTER THAT EXTENDS THE
 DSI. CALL RANDALL GRANBERRY, PLANNER
 822-1454 MM