Plan Review Details - Permit 04121162
Plan Review Stops For Permit 04121162
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-05 Cont ID  
Sent By jwitmer Date 2005-04-05 Time 15:54 Rev Time 1.55
Received By jwitmer Date 2005-04-05 Time 15:54 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-14 Cont ID  
Sent By jwitmer Date 2005-02-14 Time 08:42 Rev Time 1.50
Received By jwitmer Date 2005-02-14 Time 08:42 Sent To P
Notes
2005-02-14 00:00:00BUILDING PLAN REVIEW
 PERMIT:04121162
 ADD:525 OKEECHOBEE BLVD
 CONT:CENTEX ROONEY
 TEL:(561)478-0381
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT #5 FROM THE PREVIOUS REVIEW:
 2A) THE DOCUMENTS SUBMITTED FOR THE
 RAMP, STAIR AND HANDRAIL DO NOT MEET THE
 REQUIREMENTS OF FL S S 471.025.1 BOTH
 SETS OF PLANS REQUIRE A ORIGINAL
 SIGNATURE (NOT COPIES)AND SEALED.
 FL S S 471.025.1 DOCUMENTS BEING FILED
 FOR PUBLIC RECORD AND ALL FINAL
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE SHALL BE SIGNED
 BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL.
  
 2B) RULE 9B-72(G) DEALS WITH THE
 REQUIREMENT OF STATEWIDE PRODUCT
 APPROVALS. THE HANDRAIL/GAURDRAIL
 REQUIRES THE MANUFACTURER TO SUBMIT TO
 THE STATE EITHER A) PRODUCT APPROVAL
 STATEWIDE,
 B) LOCAL OR C) SITE SPECIFIC. A COPY OF
 THE CITIES LOCAL AND SITE SPECIFIC
 APPROVAL IS ATTACHED. FOR LOCAL APPROVAL
  
 THE MANUFACTURER MUST INDICATE WHO THEY
 HAVE CONTRACTED WITH TO DO THE THIRD
 PARTY QUALITY ASSURANCE PROGRAM, MUST BE
 ON THE STATE PRODUCT QUALITY ASSURANCE
 ENTITY LIST.FILL OUT ALL LINES OF LOCAL
 APPROVAL.
 FOR A SITE SPECIFIC APPROVAL THIS MUST
 BE FROM THE ENGINEER, FOR SITE SPECIFIC
 ENGINEERING THIS IS FOR A ONE OF A KIND
 ITEM, NOT MASS PRODUCED. THE ENGINEER
 SHALL TAKE THE RESPONSIBILITY OF
 INSPECTING AT THE FACTORY AS WELL AS THE
 INSTALLATION AT THE JOB SITE. HE WILL
 SUBMIT A AFFIDAVIT BEFORE THE C.O. THAT
 SAID HANDRAIL/ GAURDRAIL WAS FABRICATED
 / INSTALLED TO HIS SPECIFICATIONS. AGAIN
 ALL ENGINEERING LETTERS,REPORTS AND
 PLANS SUBMITTED SHALL BEAR THE ENGINEERS
 SIGNATURE/ SEAL AND DATE.
 2C) NO "WHITE OUT" :
 104.2.1.3* THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT".
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-20 Cont ID  
Sent By jwitmer Date 2005-01-20 Time 16:27 Rev Time 1.55
Received By jwitmer Date 2005-01-20 Time 16:26 Sent To  
Notes
2005-01-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04121162
 ADD: TO BE DETERMINED
 CONT:CENTEX ROONEY
 TEL: (561)478-0381
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) F102.1* SALES TRAILER IS LOCATED IN
 A FIRE DISTRICT NO TYPE VI CONSTRUCTION
 IS ALLOWED.
  
 2A)SOILS LETTER FROM TIERRA
 GEOTECHNICAL
 INDICATES SOME TYPE OF TESTING
 PREFORMED
 AT THE SITE TO DETERMINE THE MINIMUM
 SOIL BEARING CAPACITY, PROVIDE
 DOCUMENTATION.1804.2.2.
 2B) THE CODE SECTION 1818 REFRENCED IN
 YOUR LETTER DEALS SOILS IN HIGH
 VELOCITY HURRICANE ZONES, THIS PROJECT
 ISN'T IN A HVHZ.
  
 3) THE PLANS FOR THE SALES TRAILER ARE
 TO BE STATE APPROVED, STAMPED BY THE
 ATATE AND A ACCOMPANING LETTER FROM THE
  
 DCA.
 3B) IS THIS BUILDING IS NEW OR IS THE
 BUILDING BEING MOVED?
 3C) PLANS INDICATE ENVOKING RULLE 9B-72
  
 WHICH IS UNDER THE 2001 FL CODE BUT THE
  
 WIND SPEEDS REFLECTA 130 MPH WIND
 SPEED.
 THE LOCATION OF TRAILER IS A 140 MPH/
 3 SECOND GUST WIND SPEED.
 3D) PLANS ALSO INDICATE WINDOWS ARE NOT
 LARGE MISSLE IMPACT RESISTANT. GENERAL
 NOTES (12) STATEAS PER LOCAL
 JURISDICTION.
 4) PLANS FROM THE MANUFACTURED BUILDING
  
 INDICATE ON THE FRONT PAGE UNDER
 FOUNDATION THAT "THESE BUILDING PLANS DO
 NOT CONTAIN FOUNDATION SUPPORTS AND TIE
 DOWN SYSTEM SDETAILS AND
 SPECIFICATIONS"
 THE DESIGNER OF RECORD SHALL DESIGN
  
 THE FOUNDATION AND TIE DOWNS AND
 INDICATE THE FOLLOWING ON THE PLAN:
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5) THE PLANS WITH EXTERIOR STAIRS AND
 RAMP INDICATE THE 2001 FL CODE BUT
 NOTHING ABOUT RULE 9B-72 (29)(G)
 REQUIRES PRODUCT APPROVAL W/ FL COVER
 SHEET. STRUCTURAL COMPONENTS- RAILINGS.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STORM SHUTTERS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-05-23 Cont ID  
Sent By btrobaug Date 2005-05-23 Time 15:14 Rev Time 0.50
Received By btrobaug Date 2005-05-23 Time 14:45 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2005-05-17 Cont ID  
Sent By dpalmer Date 2005-05-17 Time 08:37 Rev Time 0.25
Received By dpalmer Date 2005-05-17 Time 08:36 Sent To  
Notes
2005-05-17 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE REVISED SITE PLAN FOR
 CONDUIT INSATLLED UNDER PARKING
 LOT/DRIVE.
 PLANS REQUIRED TO BE SIGNED,DATED AND
 SEALED BY ENGINEER.
 FS 471.025
  
  
 NO FEE WHEN RETURNED AS LONG AS NO OTHER
 CHANGES ARE MADE TO SITE PLAN.
 ELECTRICAL RISER DIAGRAM ATTACHED IS NOT
 REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-04-05 Cont ID  
Sent By dpalmer Date 2005-04-05 Time 10:08 Rev Time 0.30
Received By dpalmer Date 2005-04-05 Time 10:08 Sent To  
Notes
2005-04-05 00:00:00NEW ELECTRICAL SHEETS LOCATED IN
 STRUCTUAL CALCS SHEETS.
 REMOVED OLD ELECTRICAL PLANS AND
 INSERTED NEW SHEETS INTO SETS.
 STAMPED.
  
 FEILD VERIFICATION FOR STATE APPROVAL TO
 BE VERIFIED BY INSPECTORS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-03-17 Cont ID  
Sent By dpalmer Date 2005-03-17 Time 15:54 Rev Time 0.33
Received By dpalmer Date 2005-03-17 Time 14:01 Sent To  
Notes
2005-03-17 00:00:00**** UNSAT *****
  
 1)NOTE: PLEASE SEE COMMENTS FROM
 PREVIOUS REVIEW.
 STATE APPROVAL OF TRAILER IS NO LONGER
 IN EFFECT SINCE MODIFICATIONS TO TRAILER
 HAVE BEEN MADE.
  
 PLEASE SEE PREVIOUS COMMENTS FOR PLANS
 REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-02-11 Cont ID  
Sent By dpalmer Date 2005-02-11 Time 10:56 Rev Time 0.00
Received By dpalmer Date 2005-02-11 Time 10:56 Sent To  
Notes
2005-02-11 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE REVIEW WHICH WAS
 PASSED ON 2/3 HAS NOW BEEN REVOKED DUE
 TO CHANGES TO STATE APPROVED TRAILER.
  
 2)NOTE:PLEASE PROVIDE PLANS SIGNED,
 DATED AND SEALED FOR ALL NEW ELECTRICAL
 WORK BEING PERFORMED.
 PLEASE INLCUDED ALL CIRCUITING AND PANEL
 SCHEDULES.215.5
 PLEASE SEE 700.12E FOR EM/EXT LTS.
  
  
  
 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 PLEASE BE AWARE OF ANY POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-03 Cont ID  
Sent By dpalmer Date 2005-02-11 Time 10:56 Rev Time 0.00
Received By dpalmer Date 2005-02-03 Time 10:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-28 Cont ID  
Sent By dpalmer Date 2004-12-28 Time 19:00 Rev Time 0.25
Received By dpalmer Date 2004-12-28 Time 19:00 Sent To  
Notes
2004-12-28 00:00:00******** UNSAT ***********
  
 1)NOTE: PLEASE SEE ONE SET OF STATE
 APPROVED TRAILER PLANS ARE SEALED
 PHOTOCPY OF THE ENGINEERS SIGNATURE.
 PLEASE SEE FAC 61G15-23.002 AND FS
 471.025. ALL SETS MUST HAVE ORIG
 SIGNATURE AND SEAL ALONG WITH DATE.
  
 NOTES FOR RISER DIAGRAM ON 8/12X 11
  
 1)NOTE: PLEASE PROVIDE OCP FOR FEED TO
 TRAILER.
 215.5,240.4
  
 2)NOTE: PLEASE SEE RISER ONLY SHOWS ONE
 FEEDER TO TRAILER, HOWEVER, PLANS FOR
 TRAILER SHOW TWO PANELS TO FEED? 215.5
  
 3)NOTE: PLEASE SHOW GROUNDING FOR
 TRAILERS PER 250
 PLEASE SEE RISER MENTIONS TWO GRND RODS
 (IF NEEDED)?A MIN OF TWO IS REQUIRED
 UNLESS TESTING IS PROVIDED FOR 25OHMS OR
 LESS.
  
 4)NOTE: PLEASE SEE FBC 104.2.1, ALL
 PLANS MUST CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS AND/OR DESIGN.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-12-23 Cont ID  
Sent By mamini Date 2004-12-23 Time 10:53 Rev Time 0.50
Received By mamini Date 2004-12-23 Time 10:53 Sent To  
Notes
2004-12-23 00:00:00PASSED WITH PROVISOS:
  
 1. PLEASE SUBMIT CIVIL PLANS ONLY TO
 THE PUBLIC UTILITIES AND ENGINEERING
 SERVICES ATT; MANNY GONZALEZ 494-1085,
 PRIOR TO CONNECTION TO THE SERVICES.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-04-05 Cont ID  
Sent By mwennerg Date 2005-04-05 Time 09:18 Rev Time 0.00
Received By mwennerg Date 2005-04-05 Time 09:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-02-09 Cont ID  
Sent By mcarsill Date 2005-02-09 Time 16:35 Rev Time 0.00
Received By mcarsill Date 2005-02-09 Time 16:35 Sent To  
Notes
2005-02-09 00:00:001. SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER
 SYSTEM. SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM MONITORING
 EQUIPMENT. MUST BE MONITORED BY
 A UL LISTED CENTRAL STATION
 APPROVED FOR CENTRAL STATION SERVICE.
  
 2. EMERGENCY LIGHTING SHOWN ON
 PLANS. THEY SHOULD BE A COMBINATION
 FIXTURES INCLUDING EXIT SIGNS AND
 EMERGENCY LIGHTS.
  
 3. ADDRESS REQUIRED ON PROPER
 ELEVATION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By mcarsill Date 2005-01-07 Time 15:05 Rev Time 0.00
Received By mcarsill Date 2005-01-07 Time 15:04 Sent To  
Notes
2005-01-07 00:00:001. BUILDING ADDRESS IS REQUIRED
 ON PROPER ELEVATION. A MINIMUM
 OF 6" HIGH NUMBERS ARE REQUIRED.
  
 2. PLEASE INDICATE IN WRITING HOW
 LONG THE SALES TRAILER WILL BE
 LOCATED ON SITE.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM.
  
 4. NO EMERGENCY LIGHTING SHOWN ON
 THE PLANS.
  
 5. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL
 HANDRAILS AND GUARDRAILS.
  
 6. PLEASE ILLUSTRATE FIRE EXTINGUISHER
 LOCATIONS.
  
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-20 Cont ID  
Sent By adarroug Date 2005-05-20 Time 10:49 Rev Time 0.00
Received By adarroug Date 2005-05-20 Time 10:49 Sent To E
Notes
2005-05-20 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-05-09 Time 11:11 Rev Time 0.00
Received By adarroug Date 2005-05-09 Time 11:11 Sent To E
Notes
2005-05-09 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-17 Cont ID  
Sent By adarroug Date 2005-03-17 Time 11:16 Rev Time 0.00
Received By adarroug Date 2005-03-17 Time 11:16 Sent To  
Notes
2005-03-17 00:00:00TO "COMM" BD#25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-01-28 Time 16:32 Rev Time 0.00
Received By mjacobs Date 2005-01-28 Time 16:32 Sent To  
Notes
2005-01-28 00:00:00TO "COMM BD#46" RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-22 Cont ID  
Sent By mjacobs Date 2005-01-22 Time 15:55 Rev Time 0.00
Received By kstevens Date 2004-12-22 Time 11:24 Sent To  
Notes
2004-12-22 00:00:00SENT TO "COMM BD#9

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-02-07 Cont ID  
Sent By pkrauss Date 2005-02-07 Time 10:00 Rev Time 0.40
Received By pkrauss Date 2005-02-07 Time 10:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-19 Cont ID  
Sent By pkrauss Date 2005-01-19 Time 15:55 Rev Time 0.40
Received By pkrauss Date 2005-01-19 Time 15:55 Sent To  
Notes
2005-01-19 00:00:00DENIED:
 IT APPEARS THAT TWO DIFFERENT SETS OF
 PLANS WERE SUBMITTED. DUCT SIZES ARE NOT
 THE SAME BUT THE EQUIPMENT IS.PLEASE
 SUBMIT TWO IDENTICAL SET OF PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-17 Cont ID  
Sent By kstevens Date 2005-02-17 Time 08:04 Rev Time 0.33
Received By kstevens Date 2005-02-17 Time 08:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-22 Cont ID  
Sent By kstevens Date 2005-01-22 Time 15:47 Rev Time 0.60
Received By kstevens Date 2005-01-22 Time 15:47 Sent To  
Notes
2005-01-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 SHT C-4 WATER & FIRE SERVICE CONNECTION
 DETAIL, BACKFLOW SHALL BE THE SAME SIZE
 AS THE WATER SERVICE PER TABLE 603.1
 FOOTNOTE D.
  
 SEPARATE IRRIGATION PLANS/PERMIT
 REQUIRED. PLUMBING CONTRACTOR SHALL
 INSTALL BACKFLOW FOR IRRIGATION SYSTEM.
 SECTION 104.3.1.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-02-16 Cont ID  
Sent By eschneid Date 2005-02-16 Time 15:10 Rev Time 0.10
Received By eschneid Date 2005-02-16 Time 15:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-02-17 Cont ID  
Sent By mmclean Date 2005-02-14 Time 08:14 Rev Time 0.00
Received By mmclean Date 2005-02-14 Time 14:45 Sent To  
Notes
2005-02-14 00:00:00NEED MINOR AMENDMENT

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-27 Cont ID  
Sent By mmclean Date 2004-12-27 Time 15:40 Rev Time 0.00
Received By mmclean Date 2004-12-27 Time 15:40 Sent To  
Notes
2004-12-27 00:00:00DENIED, NEED MINOR AMENDMENT.CALL ERIC
 SCHNEIDER, P PLANNER 822-1446 MM