Plan Review Details - Permit 04121040
Plan Review Stops For Permit 04121040
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-05-26 Cont ID  
Sent By dwise Date 2009-05-26 Time 20:42 Rev Time 0.00
Received By dwise Date 2009-05-26 Time 20:42 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-04-06 Cont ID  
Sent By jwitmer Date 2009-04-06 Time 15:59 Rev Time 0.77
Received By jwitmer Date 2009-04-06 Time 15:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-01-14 Cont ID  
Sent By jwitmer Date 2009-01-14 Time 12:55 Rev Time 2.22
Received By jwitmer Date 2009-01-14 Time 12:36 Sent To  
Notes
2009-01-14 13:28:54BUILDING PLAN REVIEW
 PERMIT: 04121040
 ADD: 533 CLEMATIS ST
 CONT: FIVE STAR CONTRACTING GROUP
 TEL: (561)436-8508
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 W/ * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2001 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) PLANS WERE SUBMITTED AS A RESTAMP, BUT IN PULLING
 THE ORIGINAL ISSUED PLANS, THIS IS NOT AN EXACT RESTAMP
 BUT A REDESIGN BY THE NEW DESIGN TEAM, ADDITIONAL FEES
 ARE DUE.
  
 1E) NOTE THAT IN THE ISSUED SET OF DOCUMENTS ENERGY
 CALCULATIONS WERE SUBMITTED, NO SUCH INFORMATION WAS
 SUBMITTED UNDER THIS REVIEW. LOOK FOR MORE COMMENTS AS
 TO THE REQUIREMENTS FROM EACH OF THE TRADES.
  
 1F) PLLANS TO BE SUBMITTED FOR HISTORIC REVIEW AND
 PLANS STAMPED BEFORE ISSUANCE.
  
 2) COVERSHEET GENERAL NOTES:
  
 2A) PLEASE REVISE THE EDITION OF THE CODE WHICH THE
 PLANS WERE DESIGNED TO. THIS IS A 2004 PERMIT UNDER THE
 2001 FBC. PLEASE REVISE CODE RELATED ISSUES.
  
 2B) THE DESIGNER IS INDICATING THE BUILDING TO BE FULLY
 SPRINKLERED INCLUDING THIS SPACE BUT NO FIRE SPRINKLER
 PLANS ARE INCLUDED WITHIN THIS PERMIT PACKAGE. 2001 FBC
 104.3.1.1(5) FIRE SPRINKLERS.
  
 2C) THE COVER SHEET INDICATES THAT INTERIOR DESIGN
 DRAWINGS ARE NOT REQUIRED, THE ONLY INFORMATION
 PROVIDED IS MINIMUM INTERIOR FINISH CLASSIFICATION
 TABLE 803.3. SECTION 803.3.1 THE MINIMUM FLAMESPREAD
 CLASSIFICATION OF INTERIOR FINISH OTHER THAN FLOOR
 FINISH AND FLOOR COVERINGS SHALL BE BASED ON THE USE OR
 OCCUPANCY AS SET FORTH IN TABLE 803.3. NO INFORMATION
 WAS SUPPLIED UNDER THIS REVIEW FOR FLOOR, WALL, TRIM
 NOR CEILINGS.
  
 2D) OCCUPANCY IS INDICATED AS 170 SEATS, OR IS THAT TO
 BE THE TOTAL OCCUPANT LOAD?
  
 3) SHEET 1.0A
  
 3A) IT APPEARS THAT THE COOLER DOOR HAS BEEN CHANGED TO
 A OUTSWING DOOR COVERING MORE THAN ONE HALF OF THE
 REQUIRED EGRESS 2001 FBC 1012.1.4.
  
 3B) PLEASE REVIEW 11-5.1 FIVE PER CENT OF SEATING ARE
 TO BE ACCESSIBLE SEATS PLANS INDICATE 170 SEATS OR 9
 ACCESSIBLE SEATS, PLEASE RECOUNT SEATING IT APPEARS
 THAT THERE ARE 146 SEATS REQUIRING 8 ACCESSABLE SEATS.
  
 3C) PLEASE INDICATE THE ACCESIBLE ROUTE FOR THE
 ACCESIBLE SEATING AREAS , THE MINIMUM CLEAR WIDTH OF AN
 ACCESSIBLE ROUTE SHALL BE 36". 11-4.3.3.
  
 3D) CONSTRUCTION NOTE# 5 INDICATES NEW FIXED STOREFRONT
 WITH PRECAST LINTELS. THE PERMITED SET OF PLANS DID NOT
 MENTION ANY WORK ON THE EXTERIOR OF THE BUILDING.
 PLEASE PROVIDE INFORMATION AS TO WHERE THE NEW OPENINGS
 AND LINTELS WILL BE INSTALLED. COMPONENTS AND CLADDING,
 1606.2.5, PROTECTION OF OPENINGS LARGE MISSILE IMPACT
 GLAZING OR STORM PANELS 1606.1.4.
  
 3E) FL BLD CODE 1609.1.4: & RULE 9B-72, COMPONENTS &
 CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS
 ,MISSING REPORTS ARE AS FOLLOWS:
 LINTELS
 STOREFRONT- WINDOWS AND DOORS
  
 3F) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72.
  
 3G) SINCE SHEET 1.0A NOTE 5 DOES INDICATE NEW
 STOREFRONT PLEASE INDICATE WHERE THE FRONT PROPERTY
 LINE IS LOCATED, SECTION 3203.
  
 4) PLANS FAIL TO INDICATE OCCUPANCY SEPERATION BETWEEN
 THE A2 OCCUPANCY AND THAT ABOVE. PLEASE PROVIDE
 WHATTYPE OF OCCUPANCY IS LOCATED ON THE SECOND FLOOR.
 TABLE 704.1 A2 ASSEMBLY 2HR.
 PLEASE PROVIDE DETAILS.
  
 5) HVAC PLAN INDICATES NEW WORK THROUGH THE HORIZONTAL
 FLOOR/ CEILING ASSEMBLY PLEASE INDICATE COMPLIANCE WITH
 705.6 PENETRATIONS OF HORIZONTAL ASSEMBLIES.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-25 Cont ID  
Sent By jwitmer Date 2005-02-25 Time 11:30 Rev Time 0.88
Received By jwitmer Date 2005-02-25 Time 07:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-21 Cont ID  
Sent By jwitmer Date 2005-01-21 Time 08:06 Rev Time 4.00
Received By jwitmer Date 2005-01-21 Time 08:06 Sent To  
Notes
2005-01-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04121040
 ADD: 533 CLEMATIS STREET
 CONT: SHAKMAN CONSTRUCTION
 TEL: (561)705-8288
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEET A2.0 FIRE RATING NOTE
 INDICATES
 THAT THE COLUMNS WILL BE FIRE PROTECTED
 WITH SPRAY APPLIED FIRE RESISTANT
 MATERIALS ONTO THE STEEL COLUMN. PLANS
 INDICATE USING U.L. X827 FOR THE FIRE
 RATING BUT THE SIZE OF THE COLUMN IS NOT
  
 STATED NOR THE MINIMUM THICKNESS OF
 INSULATION OR TYPE OF SPRAY INSULATION.
  
 3) SHEET M6.1 CONDENSING UNIT DETAILS:
 A) CORRECT CODE AND REFENCE NUMBER,
 2001 FL BLDG CODE, 1511.7.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2009-10-08 Cont ID  
Sent By dpalmer Date 2009-10-08 Time 18:51 Rev Time 0.00
Received By dpalmer Date 2009-10-08 Time 18:51 Sent To PC
Notes
2009-10-08 18:51:58** REDLINED PLANS **
  
 1) NOTE: RISER IS BACK TO INDICATING AN EQUIPMENT
 GROUNDING CONDUCTOR FROM THE GUTTER TO THE FIRST MEANS
 OF DISCONNECT WHICH IS PARALLELING THE NEUTRAL.
 250.6, 250.24
  
 2) NOTE: RISER INDICATES THE PANELS K1 AND K2 AS BOTH
 BEING 250MLO, YET THE PANEL SCHEDULES FOR EACH OF THESE
 SAME TWO PANELS ARE SHOWN AS 225AMP.
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2009-09-24 Cont ID  
Sent By dpalmer Date 2009-09-24 Time 08:09 Rev Time 0.00
Received By dpalmer Date 2009-09-24 Time 08:09 Sent To  
Notes
2009-09-24 08:09:18** DENIED **
  
  
  
 1) NOTE: PLEASE SUBMIT A REVISED RISER DIAGRAM TO
 COORDINATE WITH REVISED PANELS.
 PLEASE COORDINATE PANELS. AS REDLINED ON PREVIOUS PLANS
 PANEL K1 WAS NOT A 42 CIRCUIT PANEL IN FIELD HOWEVER
 PLANS ARE STILL THE SAME. HAS THE PANEL NOW CHANGED IN
 THE FIELD?
 IF THIS PANEL IS IN FACT A 30 CIRCUIT PANEL THEN ALL
 THE CIRCUITING ABOVE 30 ON THE SCHEDULE WOULD NOT BE
 CORRECT.
  
 2) NOTE: PLEASE SUBMIT THE REVISED RISER DIAGRAM SHEET.
 215.5,230, ETC
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2009-04-30 Cont ID  
Sent By dpalmer Date 2009-04-30 Time 14:02 Rev Time 0.00
Received By dpalmer Date 2009-04-30 Time 14:02 Sent To PC
Notes
2009-04-30 14:03:23VIF SOME CHANGES WHICH WERE NOT AS INSTALLED ON SITE AT
 LAST INSPECTION.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2009-04-12 Cont ID  
Sent By dpalmer Date 2009-04-12 Time 10:38 Rev Time 0.00
Received By dpalmer Date 2009-04-12 Time 10:38 Sent To PC
Notes
2009-04-12 10:41:03** PLANS WERE REDLINED TO EXCLUDE THE SERVICE AND
 PANELS. PLANS ARE FOR ROUGH CEILING AND WALLS ONLY.
 MET ON SITE WITH JAKE LEAHY, GC, EC AND DESIGNER. PLANS
 NEED TO BE REVISED SUBSTANTIALLY FOR SERVICE, PANELS,
 FEEDERS AND OCP DEVICES.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2009-04-07 Cont ID  
Sent By dpalmer Date 2009-04-07 Time 21:19 Rev Time 0.00
Received By dpalmer Date 2009-04-07 Time 21:19 Sent To  
Notes
2009-04-07 21:19:57** DENIED REVIEW **
  
 ** REDLINED PLANS.
  
 1) NOTE: RISER SHOWS A 150AMP BREAKER FEEDING PANEL
 K-1. THE RISER CONTAINS A NOTE WHICH STATES THE PANEL
 K-2 IS FED FROM KI BY A 250AMP BREAKER. EVEN IF THIS
 BREAKER IS PART OF A FEED-THRU BREAKER SCENARIO, THE
 FEEDERS FROM PANEL K ARE STILL ONLY RATED FOR 150AMPS
 AS THEY ARE 1/0 CONDUCTORS. WHY WOULD THERE BE 250MCM
 FROM PANEL K-1 TO K-2 WHEN THE CONDUCTORS FROM PANEL K
 ARE ONLY RATED FOR 150AMPS. THE LOAD ON PANEL K2 ALONE
 EXCEEDS THE RATING OF THE 150AMP FEEDERS.
 310.16, 240.4.
 220
  
 ** CALLED AND LEFT MESSAGE AT ELECTRICAL DESIGNER'S
 OFFICE AND CONTRACTOR PHONE NUMBER. PLANS MAY BE
 REDLINED FOR INSPECTIONS OF ELECTRICAL DEVICES ONLY
 INCLUDING LIGHTING HOWEVER IT WOULD NOT INCLUDE
 ELECTRICAL SERVICE EQUIPMENT UNTIL CORRECTIONS ARE
 MADE.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-03-27 Cont ID  
Sent By dpalmer Date 2009-03-27 Time 16:50 Rev Time 0.00
Received By dpalmer Date 2009-03-27 Time 16:50 Sent To  
Notes
2009-03-27 16:50:56** DENIED REVIEW **
  
 REVISION
  
  
  
 1) NOTE: PLEASE COORDINATE CALCULATIONS, PLANS, LIGHT
 FIXTURES AND FIXTURE LEGEND. COMPLIANCE CAN NOT BE
 VERIFIED AS THE 2X4 LAY IN FIXTURES FOR EXAMPLE ARE NOT
 SPECIFIC ON PLANS. THE SYMBOL LEGEND INDICATES ONLY ONE
 FIXTURE FOR THIS SYMBOL YET THE FIXTURE LEGEND
 INDICATES TWO SEPARATE FIXTURES. ONE FIXTURE CONSUMES
 TWICE THE WATTAGE OF THE OTHER.
 13-415.2
 ** IT IS IMPORTANT TO KNOW THAT CEILING FANS ARE NOT
 PERMITTED TO CONTAIN LIGHT FIXTURES OR KITS UNLESS PART
 OF THE CALCULATIONS.
  
 2) NOTE: THE DEVICE LEVELS FOR HORNS, STROBES ARE NOT
 ON SYMBOL LEGEND. THESE MUST MEET FBC 11-4.28.1, .2 AND
 .3.
 FS 633 REQUIRES THE BASE PLANS TO MEET REQUIRED DESIGN
 INTENT FOR ALL BUILDING CODE REQUIREMENTS INCLUDING
 NFPA-72.
 THE HEIGHTS WHICH WERE ADDED IS NOT THE ONLY THING
 REQUIRED.
  
 3) NOTE: PLEASE COORDINATE RISER AND ELECTRICAL PANELS.
 THE RISER SHOWS THE K2 PANEL BEING FED FROM K PANEL
 HOWEVER K PANEL SCHEDULE ONLY INDICATES ONE PANEL BEING
 FED WHICH IS THE K1 PANEL.
 K PANEL CAN NOT BE A FEED-THRU PANEL AS K IS 400AMP
 RATED AND K2 IS ONLY 250AMP RATED AND K IS FED BY
 400AMP OVER CURRENT PROTECTION.
 240.4, 310.16, 230.76, 110.3, ETC.
  
 4) NOTE: PLEASE SEE 310.16 AS THE RISER SHOWS 350MCM
 FEEDERS FROM THE 400AMP MCB DISCONNECT TO THE PANEL K.
 HOWEVER BASED ON 310.16, 110.14, THE 350MCM ARE ONLY
 RATED FOR 310AMPS.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTES THE NFPA-101 IN
 EFFECT AT THE TIME OF PERMIT APPLICATION IS THE 2000.
 PLANS STATE 2003 WHICH DID HAVE CHANGES TO EGRESS PATHS
 IN DESIGN.
  
 6) NOTE: A FORM 400C-04 WAS SUBMITTED AS PART OF THE
 PACKAGE FOR PRESCRIPTIVE REQUIREMENTS.
 THE FIRST ITEM WOULD BE THE FACT THE FORM WAS NOT
 SIGNED, DATED OR SEALED BY THE ARCHITECT LISTED.
 SECOND: THE FORM IS FROM THE 2004 FBC. PLANS ARE STATED
 TO BE UNDER THE 2001
 THIRD: THE FORM IS NOT COMPLETE.
 FORTH: THE FORM IS METHOD *C*, WHERE PLANS FOR LIGHTING
 ANYWAY MENTIONS SPACE BY SPACE WHICH IS *B*. PLEASE SEE
 THE CODE AS IT DOES NOT PERMIT THE USE OF TWO DIFFERENT
 METHODS FOR THE SAME SPACE/PERMIT.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-01-16 Cont ID  
Sent By dpalmer Date 2009-01-16 Time 10:50 Rev Time 0.00
Received By dpalmer Date 2009-01-16 Time 10:50 Sent To  
Notes
2009-01-16 10:50:23** DENIED PLANS**
  
  
 ** PLANS SUBMITTED DO CONTAIN REVISIONS AND NOT ALL ARE
 A RE-STAMP.
  
  
 1) NOTE: PROJECT IS UNDER THE 2001 FBC. PLEASE ADJUST
 CODES FOR OTHER AS WELL.
 DESIGN MAY STILL BE UNDER 2004 AS SHOWN, HOWEVER AS
 LONG AS THE DESIGN MEETS THE 2001 THIS IS THE CODE
 WHICH NEEDS TO BE PLACED ON THE PLANS.
  
 2) NOTE: PLEASE COORDINATE ALL ITEMS ON THE PANELS WITH
 THE RISER DIAGRAM. THERE ARE SEVERAL ITEMS WHICH HAVE
 BEEN COMPLETELY REVISED FROM ORIGINAL PLANS AS WELL AS
 SEVERAL ITEMS WHICH DO NOT CORRELATE.
 RISER SHOWS 600AMP MAIN TO 600AMP MAIN PANEL.
 THIS PANEL IS NOTED AS PANEL *A* ON RISER YET PANEL *K*
 ON PANEL SCHEDULE.
 THIS PANEL IS ALSO 400AMP MLO ON SCHEDULE.
 PANEL *K* SCHEDULE DOES NOT INDICATE THE
 BREAKERS/CIRCUIT FEEDING BOTH PANELS AS SHOWN ON RISER.
 IN FACT THE RISER SHOWS ONE PANEL AS PANEL *C* WHICH IS
 125AMPS AND PANEL *B* IS SHOWN AS 225AMP MLO.
 THERE IS IN FACT NO PANEL *C* OR *B* SCHEDULE EVEN
 SUBMITTED. THERE IS HOWEVER A NEW *K1*.
  
 ** THESE ITEMS AS NOTED ABOVE ARE A FEW EXAMPLES OF
 ITEMS WHICH DO NOT COORDINATE. PLEASE REVISE AND SHOW
 COMPLIANCE FOR ALL FEEDERS, OVER CURRENT PROTECTION,
 REVISED SCHEDULES, REVISED PANELS ETC.
 240.4,310.16,408.4,250,230,225,215,
  
 3) NOTE: PLEASE INCLUDE ALL HORN/STROBE LEVELS PER
 11-4.28.1,.2 AND .3.
  
 4) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY
 AND EXIT LIGHTS. THERE ARE SOME ON PLANS MISSING
 CIRCUITING.
  
 5) NOTE: PLEASE SEE THE EGRESS PATHS ALONG THE BOOTHS
 DO NOT SHOW ANY EMERGENCY BACK UP LIGHTS. WHEN THIS
 PROJECT WAS ORIGINALLY PERMITTED THE REVIEW OF EGRESS
 LIGHTING WAS NOT UNDER THE ELECTRICAL REVIEW. THIS IS
 NOT PART OF THE ELECTRICAL REVIEW SO PLEASE REVISE TO
 MEET THE LIFE SAFETY CODE IN EFFECT AT THE TIME OF
 PERMIT APPLICATION.
 PLEASE SEE NFPA-101 2000, 7.8 AND 7.9.
 ** NOTED FOR INFORMATION: THE LIGHTING LEVELS FOR ALL
 EGRESS WALKING SURFACES WHICH ARE FLAT ARE THE SAME AS
 THE CURRENT CODES. ONLY STAIRS CHANGED IN THE 2003 LIFE
 SAFETY CODE.
  
 6) NOTE: PLEASE PROVIDE OR REVISE THE SYMBOL LEGEND AS
 SUBMITTED. THERE ARE ITEMS ON PLANS WHICH CAN NOT BE
 DETERMINED AT THIS TIME. SEE DEVICE WHICH SEEMS TO BE
 HALF OF A HORN/STROBE WHICH IS SHOWN CIRCUITED TO A
 LIGHT FIXTURE. WHAT IS THIS?
 THERE ALSO SEEMS TO BE HORN/STROBES IN OTHER LOCATION
 CONNECTED TO EMERGENCY AND EXIT LIGHTS. THIS IS NO
 POSSIBLE. SEE NEC 760 FOR WIRING AND OTHER ADOPTED
 CODES SUCH AS NFPA-13 FOR REQUIRED SYSTEMS.
 NEC 1999
 FBC 104.1.2
  
 7) NOTE: PLEASE BE SURE TO IDENTIFY ALL FIXTURES ON
 PLANS AND COORDINATE WITH THE FIXTURE LEGEND.
 COMPLIANCE WITH FBC 13-415.2 WILL BE VERIFIED ONCE
 THESE ARE DESIGNATED.
 PLEASE ALSO COORDINATE DESIGNATIONS. FOR EXAMPLE:
 EXTERIOR FIXTURES WHICH ARE NOTED AS *D* AS IDENTIFIED
 AS FLOOR LAMPS ON THE FIXTURE LEGEND.
  
 8) NOTE: PLEASE SEE 13-415.1.ABCD.1.1.5 FOR CONTROLS OF
 EXTERIOR LIGHTING.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-23 Cont ID  
Sent By dpalmer Date 2005-02-23 Time 08:53 Rev Time 0.50
Received By dpalmer Date 2005-02-23 Time 08:53 Sent To  
Notes
2005-02-23 00:00:00REDLINED NOTES:
  
  
 EQUIPMENT GROUNDING CONDUCTOR STILL
 SHOWN FROM GUTTER TO METER AND METER TO
 FIRST MEANS OF DISCONNECT.
 THIS SHALL NOT BE INSTALLED.
 250.6,250.24
  
 BAR AREA RECEPTS TO BE GFI 210.8

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-29 Cont ID  
Sent By dpalmer Date 2004-12-29 Time 15:57 Rev Time 1.00
Received By dpalmer Date 2004-12-29 Time 15:57 Sent To  
Notes
2004-12-29 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE RISER INDICATES
 EQUIPMENT GROUNDING CONDUCTORS FROM
 GUTTER TO METER AND THEN TO THE FIRST
 MEANS OF DISC?
 PLEASE SEE 250.6,250.24, AN EQUIPMENT
 GRND IS ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISC.
 EXIST SERVICE EQUIPMENT IS SHOWN AS
 HAVING THIS EG ALSO? PLEASE VERIFY. IF
 THIS INSATLLED, THEN IT WILL BE REQUIRED
 TO BE REMOVED WHEN SERVICE
 WORK/CONNECTION IS DONE.
  
 2)NOTE: PLEASE VERIFY LOAD SHOWN FOR NEW
 SERVICE. PLEASE VERIFY 88.86 KVA =
 213A'S.
 215/220
  
 3)NOTE: PLEASE SEE CONDUCTORS FROM MAIN
 DISC ARE 3/0'S WHICH ARE RATED FOR
 200A'S PER 310.16, YET MAIN DISC IS
 SHOWING 300A FUSES? LOAD ON MAIN ALSO
 EXCEEDS CONDUCTOR RATING.
 PLEASE VERIFY. 310.16,240.4B
  
 4)NOTE: PLEASE SEE 424.3B FOR "MIN" OCP
 FOR AHU'S.THE AMPACITY OF THE
 BRANCH-CIRCUIT CONDUCTORS AND THE RATING
 OR SETTING OF OVERCURRENT PROTECTIVE
 DEVICES SUPPLYING FIXED ELECTRIC
 SPACE-HEATING EQUIPMENT CONSISTING OF
 RESISTANCE ELEMENTS WITH OR WITHOUT A
 MOTOR SHALL NOT BE LESS THAN 125 PERCENT
 OF THE TOTAL LOAD OF THE MOTORS AND THE
 HEATERS.
  
 5)NOTE: PLEASE SEE 2002 NEC 210.8B3
 WHICH REQUIRES ALL RECEPTS IN KITCHEN TO
 BE GFI/GFI PROTECTED. THIS IS NOT ONLY
 FOR COUNTERSPACE OUTLETS. THIS WOULD
 INCLUDE FRIG'S ETC.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-05-27 Cont ID  
Sent By mawillia Date 2009-05-27 Time 11:00 Rev Time 0.00
Received By mawillia Date 2009-05-27 Time 10:41 Sent To  
Notes
2009-05-27 10:59:54*****REVISION, DATED 5/15/2009, APPROVED*****
  
  
 REVISED PLAN SHEET 1.5A STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-03-25 Cont ID  
Sent By mawillia Date 2009-03-25 Time 13:24 Rev Time 0.00
Received By mawillia Date 2009-03-25 Time 12:59 Sent To  
Notes
2009-03-25 13:23:45*****APPROVED*****
  
  
 PLAN SHEETS 1.0A, 1.4A, 1.5A, 2.0E, AND 2.1E WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-02-03 Cont ID  
Sent By mwennerg Date 2009-02-03 Time 14:55 Rev Time 0.00
Received By mwennerg Date 2009-02-03 Time 14:55 Sent To  
Notes
2009-02-03 14:59:58***DENIED***
  
 1) PLEASE SEE MECHANICAL REVIEW COMMENT #3 REGARDING
 HOOD/SUPPRESSION SYSTEMS. IN ADDITION, SEPARATE SHOP
 DRAWINGS AND PERMITS REQUIRED PRIOR TO EQUIPMENT
 INSTALLATION.
  
 2) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 3) OCCUPANT LOAD SIGN IS REQUIRED PRIOR TO FINAL
 INSPECTION. CONTACT BUREAU OF FIRE PREVENTION AT (561)
 804-4724 FOR ASSISTANCE.
  
 4) PLEASE ADD NOTE FROM FIRST FIRE PLAN REVIEW ON DOOR
 SCHEDULE REGARDING PANIC HARDWARE.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-03-22 Cont ID  
Sent By mwennerg Date 2005-03-22 Time 17:20 Rev Time 0.00
Received By mwennerg Date 2005-03-22 Time 17:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-21 Cont ID  
Sent By mcarsill Date 2005-01-21 Time 09:21 Rev Time 0.00
Received By mcarsill Date 2005-01-21 Time 09:21 Sent To  
Notes
2005-01-21 00:00:001. PLEASE PROVIDE DIMENSIONS FOR THE
 LOOS CHAIRS LOCATED AT THE TABLES.
 SOME OF THE LOOSE CHAIRS APPEAR TO
 BE LOCATED TOO CLOSE TOGETHER.
  
 2. ALL WALK-IN COOLERS AND FREEZERS
 ARE TO BE FIRE SPRINKLER PROTECTED.
  
 3. DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 4. PANIC HARDWARE REQUIRED ON ALL
 EXIT DOORS SUBJECT TO AN OCCUPANCY
 OF 100 OR MORE PERSONS.
  
 5. HOOD EXHAUST DUCT TERMINATION
 POINT APPEARS TO BE DIRECTLY
 ADJACENT TO THE REAR EXIT DOOR.
  
 6. PLEASE PROVIDE PRODUCT APPROVALS
 FOR THE HOOD EXHAUST DUCT WRAP.
  
 7. SEPARATE PLANS AND PERMITS
 REQUIRED FOR ANY FIRE SPRINKLER
 REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-10-15 Cont ID  
Sent By kstevens Date 2009-10-15 Time 17:37 Rev Time 0.00
Received By kstevens Date 2009-10-15 Time 17:37 Sent To  
Notes
2009-10-15 18:00:36REVISION SHEET 3.2A OK -- NEW GAS APPLIANCES IN KITCHEN
 AREA -- DELETED OTHER APPLIANCES.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2009-09-21 Cont ID  
Sent By kstevens Date 2009-09-21 Time 08:05 Rev Time 0.00
Received By kstevens Date 2009-09-21 Time 08:05 Sent To  
Notes
2009-09-21 08:06:13REVISION OK -- SHT 3.2A(P)

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-10-08 Cont ID  
Sent By lmartine Date 2009-10-08 Time 16:50 Rev Time 0.00
Received By lmartine Date 2009-10-08 Time 16:50 Sent To  
Notes
2009-10-08 16:51:09*****************EXPEDITED***************
 GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-09-15 Cont ID  
Sent By lmartine Date 2009-09-15 Time 17:50 Rev Time 0.00
Received By lmartine Date 2009-09-15 Time 17:50 Sent To  
Notes
2009-09-16 08:02:09REVIEW COMPLETE, PASSED TO KSTEVENS
2009-09-15 17:51:10*****************EXPEDITED*********************
 GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2009-05-19 Time   Rev Time 0.00
Received By jgomez Date 2009-05-19 Time 13:13 Sent To  
Notes
2009-05-19 13:20:17SENT TO BOB BOX #B10

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-04-21 Cont ID  
Sent By dpalmer Date 2009-04-21 Time 17:01 Rev Time 0.00
Received By dpalmer Date 2009-04-21 Time 17:01 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-02-26 Cont ID  
Sent By adarroug Date 2009-02-26 Time 16:38 Rev Time 0.00
Received By adarroug Date 2009-02-26 Time 16:38 Sent To  
Notes
2009-02-26 16:38:43TO "COMM" BD#36

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-30 Cont ID  
Sent By adarroug Date 2008-12-30 Time 16:22 Rev Time 0.00
Received By adarroug Date 2008-12-30 Time 16:22 Sent To B
Notes
2009-01-05 10:25:561/5/09--TO "COMM" BD#32---BROUGHT IN AS A RESTAMP, BUT
 PER "JWITMER" IS ACTUALLY A REV. FEE'S ARE TO BE ADDED
 ON ACCORDINGLY.
2008-12-30 16:23:28TO "JWITMER" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-29 Cont ID  
Sent By adarroug Date 2005-03-29 Time 14:39 Rev Time 0.00
Received By adarroug Date 2005-03-29 Time 14:38 Sent To P
Notes
2005-03-29 00:00:00TO "KSTEVENS" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-08 Cont ID  
Sent By adarroug Date 2005-02-08 Time 16:43 Rev Time 0.00
Received By adarroug Date 2005-02-08 Time 16:43 Sent To  
Notes
2005-02-08 00:00:00TO "COMM" BD #42/RESUBMISSION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2005-01-21 Time 14:06 Rev Time 0.00
Received By rregueir Date 2004-12-20 Time 13:43 Sent To  
Notes
2004-12-20 00:00:00SENT TO "COMM BD#47

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2009-10-08 Cont ID  
Sent By rregueir Date 2009-10-08 Time 20:37 Rev Time 0.00
Received By rregueir Date 2009-10-08 Time 20:37 Sent To P
Notes
2009-10-08 20:38:03REVISED 3.1M "AS-BUILTS"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-09-16 Cont ID  
Sent By rregueir Date 2009-09-16 Time 08:00 Rev Time 0.00
Received By rregueir Date 2009-09-16 Time 07:38 Sent To P
Notes
2009-09-16 08:00:58PAGE 3.1M REVISION #2

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-04-02 Cont ID  
Sent By rregueir Date 2009-03-30 Time 15:14 Rev Time 0.00
Received By rregueir Date 2009-03-30 Time 15:13 Sent To  
Notes
2009-04-02 15:17:36PAGE 3.1M PROVIDED BY NEW DESIGNER OF RECORD. THIS PAGE
 REPLACES ALL PREVIOUS MECHANICAL PAGES FROM PREVIOUS
 DESIGNER OF RECORD.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2009-02-01 Cont ID  
Sent By rregueir Date 2009-02-01 Time 14:20 Rev Time 0.00
Received By rregueir Date 2009-02-01 Time 14:08 Sent To  
Notes
2009-02-01 14:20:32REVIEW #: REVISION - CHANGE OF DESIGNER
 ACTION: DENIED
  
 FBC 2001 CODE FAMILY
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. GENERAL NOTES INDICATE THIS PROJECT IS UNDER THE
 2004 FBC. THIS PROJECT IS PERMITTED UNDER THE 2001 FBC.
 PLEASE ADJUST ALL PLAN NOTES AND DESIGN REQUIREMENTS
 ACCORDINGLY.
  
 2. THESE PLANS WERE SUBMITTED AS A RESTAMP. HOWEVER, IN
 CONJUNCTION WITH THE CHANGES IN DESIGN PROFESSIONALS,
 THE HVAC SYSTEMS HAVE BEEN COMPLETELY REDESIGNED. THAT
 MEANS THESE PLANS CONSTITUTE A REVISION. PLEASE PAY ALL
 APPLICABLE FEES FOR A REVISION BASED ON THE CITY'S
 CURRENT FEE SCHEDULE.
  
 3. THE RE-CREATED PLANS BY METRO ARCHITECTURE HAVE
 OMITTED THE COMMERCIAL KITCHEN EXHAUST SYSTEM.
 COMMERCIAL KITCHEN GREASE HOOD, GREASE EXHAUST DUCT AND
 ASSOCIATED VENTILATION SYSTEMS SHALL BE PROVIDED IN
 ACCORDANCE WITH FBCM 506 AND 507.
  
 4. SHOW HEIGHT OF ROOF STANDS TO BE IN COMPLIANCE WITH
 FBCB TABLE 1511.7.
  
 5. NOTE ON PAGE 3.1A CALLS FOR DUCTS PENETRATING
 FLOOR/CEILING ASSEMBLY TO BE PROTECTED WITH "EXPANDING
 COLLARS." DUCTS CONNECTING MORE THAN 2 FLOORS SHALL BE
 ENCLOSED IN SHAFT CONSTRUCTION IN ACCORDANCE WITH FBCM
 607 AND FBCB CHAPTER 7. DUCT PENETRATIONS OF SHAFT
 ENCLOSURES SHALL BE PROTECTED IN ACCORDANCE WITH FBCM
 SECTION 607.
  
 6. NOTE ON 3.1A CALLS FOR SMOKE DETECTORS ON EACH AHU.
 THERE IS NO SMOKE DETECTOR SHOWN ON AHU 2 ON FLOOR
 PLAN. PLEASE CORRECT IN ACCORDANCE WITH FBCM 606.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2005-03-08 Time   Rev Time 0.00
Received By   Date 2005-03-08 Time   Sent To  
Notes
2005-03-08 00:00:00PASS PRIVISO
 1) HOOD EXHAUST MUST TERMINATE 40
 IN.ABOVE ROOF NFPA 96 FIGURE A.4.2(D)
 2) SUPPLY HANGING DETAL FOR HOOD BEFOR
 ROUGH INSPECTION
 3) YOU NEED HORN & STROBE FOR FAN
 SHUTDOWN NOT A KEY SWITCH.THE MINIMUM
 SOUND PRESSURE SHALL BE 60DBA MAXIMUM
 SOUND PRESSURE SHALL BE 130DBA.STROBE
 MUST BE SEEN FROM ANY PART OF THE
 RESTAURANT.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-20 Cont ID  
Sent By pkrauss Date 2005-01-20 Time 06:53 Rev Time 1.00
Received By pkrauss Date 2005-01-20 Time 06:53 Sent To  
Notes
2005-01-20 00:00:00DENIED:
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPPRESSION, WALK-IN COOLERS AND
 FREEZERS.PLEASE PROVIDE
 MANUFACTURER'S
 CUT SHEETS & INSTALLATION INSTRUCTIONS
 FOR THE WALK-IN COOLERS/FREEZERS.
  
 HOOD REVIEW:
 1. PROVIDE DISTANCE TO PROPERTY LINES,
 PARKING LOT, SIDE WALK OR ADJACENT
 BUILDINGS AND FRESH AIR INTAKES IN
 ACCORDANCE WITH 2001 FBC(M)506.3.14.3.
  
 2. PLAN SHEET M2.1 KEF-1 IS TERMINATING
 TO THE EXTERIOR WALL.PER 2001
 FBC(M)506.3.14.2, OPENINGS SHALL NOT BE
 LOCATED WITHIN 3 FEET OF THE
 TERMINATION.PROVIDE INFORMATION ON
 THE
 EXTERIOR WALL WHERE EXHAUST TERMINATES.
 PLEASE NOTE, TERMINATION CAN NOT BE
 LOCATED WHERE PROTECTED OPENINGS ARE
 REQUIRED.
  
 3.INDICATE ELEVATION FOR TERMINATION
 OF THE KEF-1.PLAN SHEET A2.0 SHOWS
 THE
 KEF-1 TERMINATING ABOVE THE CAN WASH.
 PLEASE CLARIFY.
  
 4. PROVIDE INFORMATION ON THE "WRAP"
 INDICATED FOR THE GREASE DUCT.
  
 PLEASE NOTE PLANS FOR THE HOOD MAY BE
 SUBMITTED WITH THE HOOD PERMIT
 APPLICATION.NO PLANS SUBMITTED FOR
 THE
 FIRE SUPPRESSION.PLEASE PROVIDE PLANS
 WITH FIRE SUPPRESSION PERMIT
 APPLICATION.
  
 HVAC REVIEW:
 1.PLEASE INDICATE HEIGHT OF THE
 BUILDING.PLAN SHEET A2.0 INDICATES
 THERE IS MORE THAN 1 STORY.PER 2001
 FBC(M)607.4, FIRE DAMPERS ARE REQUIRED
 ON DUCTS THAT PENETRATE A CEILING FLOOR
 ASSEMBLY.WHERE DUCTS EXTEND THROUGH
 MORE THAN ONE FLOOR/CEILING A SHAFT
 WILL
 BE REQUIRED.
  
 2.CONDENSING UNIT STANDS LOCATED ON
 THE ROOF SHALL COMPLY WITH 2001
 FBC(M)1511.7 FOR CLEARANCE BETWEEN THE
 ROOF SURFACE AND THE BOTTOM OF THE
 SUPPORT RAIL.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS.2001 FBC(M)
 606.2.1 & 606.4.1 #2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-04-03 Cont ID  
Sent By kstevens Date 2009-04-03 Time 09:45 Rev Time 0.00
Received By kstevens Date 2009-04-03 Time 09:45 Sent To  
Notes
2009-04-03 09:46:15NEW DESIGNER OF RECORD -- REVISIONS FOR ALL SHEETS
 APPROVED

Review Stop P PLUMBING
Rev No 4 Status F Date 2009-01-30 Cont ID  
Sent By kstevens Date 2009-01-30 Time 11:09 Rev Time 0.00
Received By kstevens Date 2009-01-30 Time 11:09 Sent To  
Notes
2009-01-30 13:34:31DENIED
 REFERENCE:
 FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1. PLANS WERE SUBMITTED AS A RESTAMP. THERE ARE CHANGES
 TO THE ORIGINAL PLANS AND THE ORIGINAL SET OF PLANS HAS
 5 PLUMBING SHEETS WHEREAS THERE WERE ONLY 3 PLUMBING
 SHEETS. PLEASE SUBMIT ALL SHEETS. PER THE LETTER THERE
 IS A NEW ARCHITECT OF RECORD SO ALL SHEETS SHALL BE
 REPRODUCED BY THE NEW ARCHITECT OF RECORD. FAC
 61G1-18.002.
  
 2. SHT 3.0P THE FLOOR SINK FOR THE 3 COMPARTMENT SINK
 SHOWS NO CONNECTION TO THE BUILDING DRAIN OR BRANCH
 LINE. SECTION 701.1. PLEASE INDICATE WHERE THE FLOOR
 SINK CONNECTS TO THE SANITARY DRAINAGE. SECTION
 104.2.1.
  
 3. SHT 3.0P THE HOT WATER SUPPLY TO THE LAVS IN THE
 MEN'S & WOMEN'S TOILET ROOMS SHALL BE INDICATED ON THE
 LEFT SIDE OF THE FIXTURE. SECTION 607.4. PLANS SHOW HOT
 ON RIGHT SIDE OF FIXTURE.
  
 4. SHT 3.2A NOTES NUMBER 3 INDICATES THE PLUMBING CODE
 AS 2004. THE CODE IN EFFECT AT THE TIME THE PERMIT WAS
 ISSUED WAS 2001. PLEASE CORRECT CODE REFERENCE. SECTION
 104.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-04-14 Cont ID  
Sent By kstevens Date 2005-04-14 Time 11:03 Rev Time 2.50
Received By kstevens Date 2005-04-14 Time 11:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-21 Cont ID  
Sent By kstevens Date 2005-03-21 Time 10:02 Rev Time 1.85
Received By kstevens Date 2005-03-09 Time 17:04 Sent To  
Notes
2005-03-21 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
  
 1. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2 -
 SHEETS REQUESTED ON 3-09-5 WERE FAXED
 OVER ON 3-14-5 - CALLED CONTRACTOR
 ADVISING NEW APPLIANCES WERE SHOWN AND
 SHEET WERE REQUIRED FOR THOSE AND THAT A
 DIFFERENT GAS APPLIANCE LAYOUT WAS FAXED
 WITH SHEETS. NEW SHEETS DO NOT CORRELATE
 WITH BTU'S LISTED ON PLANS AND SOME
 SHEETS SHOW APPLIANCES NOT SHOWN ON THE
 GAS RISER DIAGRAM. ED BRAHMAN INDICATED
 ON 3-14-5 HE WILL GET BACK TO ME ON THIS
 BUT DID NOT.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-20 Cont ID  
Sent By kstevens Date 2005-01-20 Time 17:52 Rev Time 1.55
Received By kstevens Date 2005-01-20 Time 17:52 Sent To  
Notes
2005-01-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) GREASE INTERCEPTORS SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE
 PER WASTE ORD. #2938-96. (561) 837-4074
 2) SHT A2.0 EQUIPMENT SCHEDULE #3 NOT
 FOUND ON THE FLOOR PLAN. PLEASE CLARIFY
 SECTION 104.2.1.
 3) SHT A2.0 FIRST FLOOR PLAN. RED LINE
 MARKINGS FROM THE FDBR HOTEL AND
 RESTURANT DIV. INDICATES THAT 2 NEW HAND
 SINKS ARE REQUIRED AND ONE OTHER HAND
 SINK SHALL BE DELETED. PLEASE REVISE
 SHT
 A2.0 SHOWING THESE REQUIREMENTS.
 RESUBMIT STAMPED SHEET A2.0 WITH NEW
 SHT
 A2.0 AND INDICATE ON SHEET FOR DBPR
 STAMP ONLY.
 4) RPZ BACKFLOW IS REQUIRED ON THE WATER
 SERVICE. SECTION 608.13.2.
 5) SHTS P2.1, P5.1, & P5.2 DO NOT SHOW
 NEW HAND SINKS REQUIRED BY DBPR, NOR DO
 THEY SHOW THE HAND SINK DELETED BY DBPR.
 PLEASE REVISE AS REQUIRED. SECTION
 104.2.1.
 6) SHT P5.1 GAS RISER DIAGRAM. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 THE REQUIRED GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 D. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 7) SHT P6.2 WATER FILTER FOR ICE MAKER
 SHALL COMPLY WITH NSF-42. PLEASE SUBMIT
 MANUF. SPECIFICATION SHEET SHOWING
 COMPLIANCE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2009-03-12 Cont ID  
Sent By mflis Date 2009-03-12 Time 08:44 Rev Time 0.00
Received By mflis Date 2009-03-12 Time 08:44 Sent To  
Notes
2009-03-12 08:45:44ZONING REVIEW: NOT REQUIRED
  
 ** INTERIOR RENOVATIONS ONLY
  
 NOTE: THIS PROPERTY IS LOCATED IN A HISTORIC DISTRICT;
 ANY FUTURE REVISIONS TO THESE DRAWING WHICH ALTER THE
 EXTERIOR OF BUILDING WILL REQUIRE ZONING AND HISTORIC
 REVIEW.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status N Date 2009-01-30 Cont ID  
Sent By mflis Date 2009-01-30 Time 14:23 Rev Time 0.00
Received By mflis Date 2009-01-30 Time 14:23 Sent To  
Notes
2009-01-30 14:24:24ZONING REVIEW: NOT REQUIRED
  
 ** INTERIOR RENOVATION ONLY
  
 MATT FLIS - 822-1445