Plan Review Details - Permit 04120970
Plan Review Stops For Permit 04120970
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-16 Cont ID  
Sent By alange Date 2005-03-16 Time 15:24 Rev Time 1.00
Received By alange Date 2005-03-16 Time 07:20 Sent To  
Notes
2005-03-16 00:00:00DENIED
  
 1.PROJECT DESCRIPTION DOES NOT REFLECT
 WORK ON PLANS. A CARPORT CONVERSION TO
 GARAGE AND NEW ROOF TRUSSES WERE NOT
 MENTIONED.
  
 2. SHOW HOW MANY TRUSSES ARE BEING
 REPAIRED.
  
  
 4.VALUATION ON APPLICATION IS TOO
 LOW.
 REVISE VALUE TO REFLECT ALL MATERIALS
 AND LABOR. IF NOT IT WILL BE ADJUSTED
 ACCORDING TO MARSHALLS AND SWIFTS
 ESTIMATING GUIDE.ADDITIONAL PERMIT
 FEES ARE DUE.
  
 11.CONTRACTOR REQUIRED TO PULL
 PERMIT.
 THIS IS NOT A PRIMARY RESIDENCE.
 SEVERAL PROPERTIES LISTED.FS 489
  
 ************
 12.THIS BUILDING HAS A STOP WORK ORDER
 ISSUED ON IT FROM 5-29-03. ROOM ADDITION
 BUILT WITH NO PERMITS.THIS PERMIT WILL
 NOT BE ISSUED UNTIL A PERMIT HAS BEEN
 APPROVED FOR THE EXISTING ROOM
 ADDITION.
 PLEASE SUBMIT PLANS FOR ROOM ADDITION
 AND APPLY FOR A PERMIT.
 ************
  
 NEW COMMENTS:
 A. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 B.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-06 Cont ID  
Sent By alange Date 2005-01-06 Time 10:19 Rev Time 2.00
Received By alange Date 2005-01-06 Time 10:19 Sent To Z
Notes
2005-01-06 00:00:00DENIED
  
 1.PROJECT DESCRIPTION DOES NOT REFLECT
 WORK ON PLANS. A CARPORT CONVERSION TO
 GARAGE AND NEW ROOF TRUSSES WERE NOT
 MENTIONED.
  
 2.SHOW HOW MANY TRUSSES ARE BEING
 REPLACED AMD LOCATION OF WORK.THIS
 DOES NOT APPEAR TO BE A REPAIR BUT A
 DESIGN CHANGE. SUBMIT ROOF FRAMING PLAN
 SHOWING TIE DOWNS AND BRACING.
  
 3.PRODUCT APPROVALS:
  
 ONE SET MISSING FOR JELD-WEN EXTERIOR
 DOOR.PLEASE SUBMIT SECOND COPY.
  
 SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR
 ROOFING AND STRAPS AND TIE-DOWNS.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.VALUATION ON APPLICATION IS TOO
 LOW.
 REVISE VALUE TO REFLECT ALL MATERIALS
 AND LABOR. IF NOT IT WILL BE ADJUSTED
 ACCORDING TO MARSHALLS AND SWIFTS
 ESTIMATING GUIDE.ADDITIONAL PERMIT
 FEES ARE DUE.
  
 5.SHOW HOW MUCH ROOFING WILL BE
 REPLACED.
  
 6.SHEATHING SHALL COMPLY WITH FBC WPB
 AMMENDMENTS 2306.1 THICKNESS SHALL BE
 19/32" FOR SHEATHING. PLEASE REVISE ON
 PLANS. ALSO CHECK THIS SECTION FOR
 SPACING OF FASTENERS.
  
 7.NOTES REFER TO CODE ACCORDING TO
 PALM BEACH COUNTY, SHOULD BE WEST PALM
 BEACH AMMENDMENTS.
  
 8.FBC 104.2.1 PERSON RESPOSIBLE FOR
 PLANS TO HAVE PRINTED NAME AND SIGNATURE
 ON ALL PLANS.
  
 9.DETAIL "A" WOOD TO CMU CONNECTION.
 PT WOOD REQUIRED AT MASONARY CONTACT.
 PLEASE SHOW ON DETAIL.
  
 10. SHOW SIZE AND LOCATION OF ATTIC
 ACCESS FBC 2309.6
  
 11.CONTRACTOR REQUIRED TO PULL
 PERMIT.
 THIS IS NOT A PRIMARY RESIDENCE.
 SEVERAL PROPERTIES LISTED.FS 489
  
 ************
 12.THIS BUILDING HAS A STOP WORK ORDER
 ISSUED ON IT FROM 5-29-03. ROOM ADDITION
 BUILT WITH NO PERMITS.THIS PERMIT WILL
 NOT BE ISSUED UNTIL A PERMIT HAS BEEN
 APPROVED FOR THE EXISTING ROOM
 ADDITION.
 PLEASE SUBMIT PLANS FOR ROOM ADDITION
 AND APPLY FOR A PERMIT.
 ************
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-01 Cont ID  
Sent By dpalmer Date 2005-03-01 Time 05:57 Rev Time 0.50
Received By dpalmer Date 2005-02-28 Time 17:52 Sent To P
Notes
2005-03-01 00:00:00********* UNSAT 2ND REVIEW *********
  
 **PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW , STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NO.
 PLEASE SEE REDLINED PLANS.
  
 2)NOTE: OK
  
 3)NOTE: NO,
 PLEASE SEE THERE ARE MANY ITEMS WHICH
 CONTAIN #14 AWG ON 20A OCP ETC.
  
 4)NOTE: NO.
  
 5)NOTE: OK.
  
 6)NOTE: NO, PLEASE SEE PLANS INDICATE AH
 OUTSIDE? MISPRINT?
  
 7)NOTE: OK.
  
 8)NOTE: OK
  
 9)NOTE: NO. THIS IS NOT PRIMARY
 RESIDENCE FOR OWNER. MUST OBTAIN
 HOMESTEAD AT THIS LOCATION.
 PLEASE SEE ATTACHED SHEETS FROM PALM
 BEACH COUNTY.
  
 10)NOTE: OK
  
 11)NOTE: OK
  
 12)NOTE: OK.
  
 13)NOTE: OK
  
  
 14)NOTE: NEW NOTE: PLEASE SEE ATTACHED
 COPY OF FS 553.80(2)(B) WITH RESPECT TO
 THE DESIGN PROFESSIONAL. IF PLANS COME
 BACK FOR ANY COMMENTS NOT ADDRESSED FROM
 TWO PREVIOUS REVIEW. A 4X FEE FOR PLAN
 REVIEW SHALL BE ACCESED.
 THIS IS NOTICE ONLY GIVEN AT THIS TIME.
  
 PLEASE SEE ONE SET OF PLANS HAS MOST
 ITEMS ABOVE REDLINED FOR LOCATIONS OF
 NOTES.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-28 Cont ID  
Sent By dpalmer Date 2004-12-28 Time 15:49 Rev Time 0.00
Received By DPALMER Date 2005-01-06 Time 10:18 Sent To P
Notes
2004-12-28 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE PLANS, RISER
 AND PANEL SCHEDULE. ONE SHOWS 150A PANEL
 THE OTHER 200A ETC.
 PLEASE ALSO SEE PLANS INDICATE ALL AS
 EXISTING YET, PERMIT APPLICATION
 MENTIONS NEW PANEL?
 PLEASE CLARIFY.
  
 2)NOTE: PLEASE SEE 210.52C1-5 FOR
 RECEPTS IN KITCHEN/ PENINSULAR.
  
 3)NOTE: PLEASE SEE NUMEROUS 15/20A
 CIRCUITS ON PANEL SCHEDULE WHICH ARE
 SHOWN WITH LOADS EXCEEDING 80% MAX.
 15A MAX 1440, 20A MAX 1920
 PLEASE ALSO SEE 20A ON #14 AWG.
 240.4
  
  
 4) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5)NOTE: PLEASE SEE MIN OCP FOR WATER
 HEATER IS TO BE 125%. PLEASE VERIFY TYPE
 OF WATER HEATER. 422.13
  
 6)NOTE: PLEASE SHOW NEW A/C SYSTEMA ND
 DISC'S PER 440.11
 PLEASE ALSO SEE 210.63 FOR REQUIRED
 GFI.
  
 7)NOTE: PLEASE INDICATE GFI PROTECTED
 RECEPTS WHERE REQUIRED, PER 210.8
 PLEASE SEE DUE TO REMODEL THESE WILL BE
 REQUIRED TO BE RBOUGHT UP TO CODE.
  
 8)NOTE: PLEASE SEE PLANS REFERENCE PALM
 BEACH COUNTY. THIS JOB IS IN THE CITY OF
 WEST PALM BEACH.
  
 9)NOTE: PLEASE SEE COPIES OF PRINT OUTS
 FRO PAPA, WHICH INDICATE THIS NOT THE
 PRIMARY RESIDENCE OF THE PERSON APPLYING
 FOR O/B PERMIT. ATTACHED IS FOUR OTHER
 PROPERTIES.
 PLEASE SEE FS 489, THIS MUST BE A
 PRIMARY RESIDENCE IN ORDER TO PULL AND
 O/B PERMIT.
  
 10)NOTE: PLEASE SUBMIT THE AIC RATING
 FOR AN NEW SERVICE EQUIPMENT BEING
 INSTALLED.
 110.9/215.5
  
 11)NOTE: PLEASE SEE EXISTING CARPORT
 APPEARS TO BE GETTING CLOSED INTO A
 GARAGE. PLEASE SEE 210.70 FOR SW/LT
 REQUIED FOR DOOR EGRESS LEAVING GARAGE
 TO GRADE LEVEL ACCESS.
  
 12)NOTE: PLEASE SEE GDO DOES NOT APPEAR
 TO BE ON PANEL SCHEDULE. THIS WOULD BE A
 DEDICATED CIRCUIT.
  
 13)NOTE: PLEASE SEE FBC 104.2.1, WHICH
 REQUIRES THE PERSON RESPONSIBLE FOR
 PLANS TO HAVE PRINTED NAME AND SIGNATURE
 ON PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 14:24 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 14:24 Sent To E
Notes
2005-02-28 00:00:00TO "DP" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-23 Cont ID  
Sent By adarroug Date 2005-02-23 Time 16:58 Rev Time 0.00
Received By adarroug Date 2005-02-23 Time 16:58 Sent To Z
Notes
2005-02-23 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-20 Cont ID  
Sent By mmclean Date 2005-01-12 Time 14:10 Rev Time 0.00
Received By mjacobs Date 2004-12-20 Time 10:51 Sent To E
Notes
2004-12-20 00:00:00SENT TO "E" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-03-15 Cont ID  
Sent By pkrauss Date 2005-03-15 Time 13:57 Rev Time 0.25
Received By pkrauss Date 2005-03-15 Time 13:55 Sent To B
Notes
2005-03-15 00:00:00MECHANICAL PLAN SUBMITTED WITHOUT THE
 CONTRACTORS INFORMATION ON THE PLAN.NO
 CHANGES TO THE DUCTLAYOUT AND EQUIPMENT
 SCHEDULE.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2005-03-09 Time   Rev Time 0.00
Received By hmoser Date 2005-03-15 Time 08:55 Sent To B
Notes
2005-03-09 00:00:00PLAN DENIED
 SAME AS BEFOR. THE NAME OF CONTRACTOR ON
 THE MACHANICAL PLAN IS NOT DOING THE
 JOB.KEEP COOL AIRCONDITIONING ASKED ME
 TO VOID OUT THE MECHANICAL PLAN.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-04 Cont ID  
Sent By hmoser Date 2005-01-04 Time 10:17 Rev Time 0.00
Received By hmoser Date 2005-01-04 Time 08:57 Sent To B
Notes
2005-01-04 00:00:00PLAN DENIED
 AIRCONDITIONING CONTRACTOR NAME ON PLAN
 IS NOT DOING THE JOB.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-03-05 Cont ID  
Sent By kstevens Date 2005-03-05 Time 12:38 Rev Time 0.25
Received By kstevens Date 2005-03-05 Time 12:38 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-01 Cont ID  
Sent By jleech Date 2005-01-01 Time 06:44 Rev Time 0.25
Received By jleech Date 2005-01-01 Time 06:44 Sent To M
Notes
2005-01-01 00:00:00DENIED;
 1.PLEASE CHANGE NOTE #1 TO READ FBC
 PLUMBING.
 2.PLUMBING PLANS TO HAVE PERSON
 RESPONSIBLE FOR PLANS TO SIGH AND PRINT
 NAME. SEE ELECTRICAL PLAN REVIEW NOTE
 13.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2005-02-28 Cont ID  
Sent By mmclean Date 2005-02-28 Time 11:00 Rev Time 0.00
Received By mmclean Date 2005-02-28 Time 11:00 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-01-12 Cont ID  
Sent By mmclean Date 2005-01-12 Time 14:04 Rev Time 0.00
Received By mmclean Date 2005-01-12 Time 14:04 Sent To  
Notes
2005-01-12 00:00:00DENIED, NEED TO PROVIDE TWO COPY OF
 SURVEY OF PROPERTY SHOWING THE WORK WITH
 SETBACKS.CALLED OWNER FOR P/U FILE S
 MM