Plan Review Details - Permit 04120965
Plan Review Stops For Permit 04120965
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-04-14 Cont ID  
Sent By jwitmer Date 2005-04-14 Time 12:01 Rev Time 1.11
Received By jwitmer Date 2005-04-14 Time 12:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-04-14 Cont ID  
Sent By jwitmer Date 2005-04-14 Time 11:43 Rev Time 1.11
Received By jwitmer Date 2005-04-14 Time 11:41 Sent To  
Notes
2005-04-14 00:00:00BUILDING PROVISO:
 11-5.2 COUNTERS AND BARS
 WHERE FOOD OR DRINK IS SERVED @ COUNTERS
 EXCEEDING 34" IN HEIGHT FOR CONSUMPTION
 BY CUSTOMERS SEATED ON STOOLS OR STAND-
 ING AT THE COUNTER, A PORTION OF THE
 MAIN COUNTER WHICH IS 60" IN LENGTH MIN-
 IMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH 11-4.32 OR SERVICE SHALL BE AVAIL-
 ABLE AT ACCESSIBLE TABLES WITHIN THE
 SAME AREA.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-28 Cont ID  
Sent By jwitmer Date 2005-02-28 Time 14:37 Rev Time 1.11
Received By jwitmer Date 2005-02-28 Time 14:37 Sent To  
Notes
2005-02-28 00:00:00BUILDING PROVISO:
 11-5.2 COUNTERS AND BARS
 WHERE FOOD OR DRINK IS SERVED @ COUNTERS
 EXCEEDING 34" IN HEIGHT FOR CONSUMPTION
 BY CUSTOMERS SEATED ON STOOLS OR STAND-
 ING AT THE COUNTER, A PORTION OF THE
 MAIN COUNTER WHICH IS 60" IN LENGTH MIN-
 IMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH 11-4.32 OR SERVICE SHALL BE AVAIL-
 ABLE AT ACCESSIBLE TABLES WITHIN THE
 SAME AREA.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-14 Cont ID  
Sent By jwitmer Date 2005-01-14 Time 11:05 Rev Time 1.11
Received By jwitmer Date 2005-01-14 Time 11:05 Sent To  
Notes
2005-01-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04120965
 ADD: 5705 S DIXIE BAY E
 CONT: SUNDOWN
 TEL: (561)743-4420
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)CONTACT JOHN HIGGINS @ (561)822-1239
 TO CORRECT ADDRESS. CITY INDICATES 5705
 S DIXIE NOT 5707.
 1A) USPS POSTAL STANDARD DOESN'T ALLOW
 BAYS TO BE IDENTIFIED BY ALPHABETICAL
 TERMS (BAY-A).
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) 1511.7 ROOF MOUNTED MECHANICAL UNIT S
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 5)FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 6) 11-5.2 COUNTERS AND BARS
 WHERE FOOD OR DRINK IS SERVED @ COUNTERS
 EXCEEDING 34" IN HEIGHT FOR CONSUMPTION
 BY CUSTOMERS SEATED ON STOOLS OR STAND-
 ING AT THE COUNTER, A PORTION OF THE
 MAIN COUNTER WHICH IS 60" IN LENGTH MIN-
 IMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH 11-4.32 OR SERVICE SHALL BE AVAIL-
 ABLE AT ACCESSIBLE TABLES WITHIN THE
 SAME AREA.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-11 Cont ID  
Sent By dpalmer Date 2005-04-11 Time 19:56 Rev Time 0.30
Received By dpalmer Date 2005-04-11 Time 19:56 Sent To  
Notes
2005-04-11 00:00:00REDLINES PLANS FOR MISSING EQUIPMENT
 GROUNDING AND FEEDER CONDUCTORS FROM
 MAIN TO GUTTER.
 310.16,250.24,250.122

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-01 Cont ID  
Sent By dpalmer Date 2005-03-01 Time 06:33 Rev Time 0.15
Received By dpalmer Date 2005-03-01 Time 06:33 Sent To  
Notes
2005-03-01 00:00:00********* UNSAT 2ND REVIEW **********
  
 ***************************************
  
 1)NOTE: PLEASE SEE THE SAME PLANS FOR
 ELECTRICAL WERE RESUBMITTED?
 PLEASE SEE ALL NOTES FROM PREVIOUS
 REVIEW.
 PLEASE DISREGARD NOTE #3 FROM PREVIOUS
 REVIEW.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE DO NOT LEAVE OLD SHEETS IN SETS.
 THIS WILL ONLY DELAY PROCESS.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-29 Cont ID  
Sent By dpalmer Date 2004-12-29 Time 07:45 Rev Time 0.25
Received By dpalmer Date 2004-12-29 Time 07:45 Sent To  
Notes
2004-12-29 00:00:00*** UNSAT ***
  
  
 1)NOTE: PLEASE SEE NOTE TO SERVICE LOAD
 MENTIONS THIS IS AN ESTIMATED LAOD OF
 20WP/SQ FT. PLEASE SEE THIS IS SHOWN
 FOR
 GEN LT LOADS AND EST FOR LOADS NOT
 KNOWN.
 PLEASE SEE SOME UNIT ARE KNOW AT THIS
 TIME AND INCLUDING ONE AS A REST. FIT
 UP.
 KNOWN LOADS MUST BE FIGURED INTO
 SERVICE
 LOAD CALCULATIONS.220.3B
  
 2)NOTE: PLEASE PROVIDE A NOTE ON RISER
 FOR A "FLOATING NEUTRAL REQUIRED" IN
 TENANT METERS. PLEASE SEE 250.6,
 250.24.
  
 3)NOTE: PLEASE SEE PLANS REFERENCE 5707
 S DIXIE, YET SYSTEM SHOWS 5707? PLEASE
 SEE BLDG REVIEW COMMENTS AND POSSIBLE
 ADDRESS CORRELATION.
  
 4)NOTE: PLEASE SEE 210.8B3 FOR GFI
 PROTECTION REQUIRED FOR KITCHEN
 RECEPTS.
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-12 Cont ID  
Sent By mwennerg Date 2005-04-12 Time 13:19 Rev Time 0.00
Received By mwennerg Date 2005-04-12 Time 13:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-01-07 Cont ID  
Sent By mcarsill Date 2005-01-07 Time 13:48 Rev Time 0.00
Received By mcarsill Date 2005-01-07 Time 13:48 Sent To  
Notes
2005-01-07 00:00:001. INTERIOR FINISH CLASSIFICATIONS
 FOR WALLS AND CEILINGS SHALL
 COMPLY WITH APPLICABLE REQUIREMENTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-04 Cont ID  
Sent By adarroug Date 2005-04-04 Time 15:03 Rev Time 0.00
Received By adarroug Date 2005-04-04 Time 15:03 Sent To  
Notes
2005-04-04 00:00:00TO "COMM" BD#10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 11:14 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 11:14 Sent To  
Notes
2005-02-28 00:00:00TO "COMM" BD#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 15:46 Rev Time 0.00
Received By kstevens Date 2004-12-20 Time 07:57 Sent To  
Notes
2004-12-20 00:00:00SENT TO "COMM BD#7

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-05-02 Cont ID  
Sent By pkrauss Date 2005-05-02 Time 07:06 Rev Time 0.40
Received By pkrauss Date 2005-04-29 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-03-16 Cont ID  
Sent By pkrauss Date 2005-03-16 Time 06:34 Rev Time 0.35
Received By pkrauss Date 2005-03-16 Time 06:24 Sent To  
Notes
2005-03-16 00:00:00DENIED:
 COMMENTS FROM REVIEW DATED 1-19-05 WERE
 NOT ADDRESSED.PLANS ARE DATED NOV 12,
 2004 (ORIGINAL PLANS SUBMITTED). SEE THE
 ATTACHED COMMENTS AND REVISE PLANS
 ACCORDINGLY.
  
 IF YOU HAVE ANYQUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-19 Cont ID  
Sent By pkrauss Date 2005-01-19 Time 11:06 Rev Time 0.35
Received By pkrauss Date 2005-01-19 Time 10:37 Sent To  
Notes
2005-01-19 00:00:00DENIED:
 1. PLAN SHEET M-1 & P-1, AUXILIARY DRAIN
 LINE IS SHOWN TERMINATING OUTSIDE OF THE
 BUILDING AREA.PER 2001 FBC(M)307.2.3,
 AUXILIARY DRAIN LINE IS TO TERMINATE AT
 A CONSPICUOUS POINT TO SERVE AS AN ALARM
 THAT THE PRIMARY DRAIN IS RESTRICTED.
 PLEASE REVISE ACCORDINGLY.
  
 2. PLAN M-1 KEYNOTE #3 INDICATES O.A.
 STUBBED FROM THE ADJACENT TENANT.
 PLEASE CLARIFY THE FOLLOWING:
 - FIRE DAMPER BETWEEN THE TENANT
 SEPARATION.
 - INDICATE WHERE THE O.A. INTAKE IS
 LOCATED.
 - O.A. CAN NOT BE TAKEN FROM THE
 ADJACENT SPACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-04-27 Cont ID  
Sent By kstevens Date 2005-04-27 Time 13:35 Rev Time 1.50
Received By kstevens Date 2005-04-26 Time 14:25 Sent To  
Notes
2005-04-27 00:00:00PASSED/PROVISO
  
  
 INDIRECT WASTE REQUIRED FOR 3
 COMPARTMENT SINK PER 802.1.1. - A SAMPLE
 POINT IS REQUIRED PER R.COMPO - A
 REVISION IS REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-16 Cont ID  
Sent By kstevens Date 2005-03-16 Time 18:35 Rev Time 0.50
Received By kstevens Date 2005-03-16 Time 18:35 Sent To  
Notes
2005-03-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A) FROM PREVIOUS REVIEW: (SAME NUMBER
 FROM FIRST REVIEW):
 4) SHT P-1 THREE COMPARTMENT SINK IN THE
 FOOD PREP AREA SHALL DRAIN INDIRECTLY
 INTO AN APPROVED INDIRECT WASTE RECEPTOR
 PER SECTIONS 802.1.1& 802.3.
 ***********NEW COMMENT***********
 1B) A SEPARATE GREASE LINE SHALL BE
 INSTALLED FOR THE GREAS INTERCEPTOR
 REQUIRED BY RODNEY COMPO. (SEE ATTACHED
 SHEET). SEPARATE SANITARY LINE REQUIRED
 FOR TOILET ROOM. SECTION 1003.2.
 2B) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-20 Cont ID  
Sent By kstevens Date 2005-01-20 Time 15:46 Rev Time 1.25
Received By kstevens Date 2005-01-19 Time 18:58 Sent To  
Notes
2005-01-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SEE BUILDING REVIEW CONCERNING THE
 ADDRESS.
 2) SHT A-1 BATHROOM DETAIL. THE
 FOLLOWING INFORMATION IS REQUIRED TO
 SHOW COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, AND 11-4.22:
 A) CLEAR FLOOR SPACE 11-4.16.2
 B) FLUSH CONTROLS 11-4.16.5
 C) CLEAR FLOOR SPACE 11-4.19.3
 D) EXPOSED PIPES & SURFACES 11-4.19.4
 E) FAUCETS 11-4.19.6
 F) THE WATER CLOSET SHALL BE 18" FROM
 THE CENTERLINE OF THE FIXTURE TO THE
 WALL. FIG. 28
 G) THE LAV SHALL CENTER ON THE 30"
 MEASURMENT OF THE 30"X48" CLEAR FLOOR
 SPACE AND SHALL BE MIN. OF 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE.
 3) MORE INFORMATION IS REQUIRED ON THE
 OCCUPANCY. INDICATE TYPE OF BUSINESS
 WILL BE IN THE SPACE. - MORE COMMENTS
 MAY FOLLOW AFTER COMMENT RESPONSE IS
 RECIEVED. SECTION 104.2.1.
 4) SHT P-1 THREE COMPARTMENT SINK IN THE
 FOOD PREP AREA SHALL DRAIN INDIRECTLY
 INTO AN APPROVED INDIRECT WASTE
 RECEPTICAL PER SECTION 802.1.1 & 802.3.
 5) GREASE INTECEPTOR MAY BE REQUIRED.
 CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE @ (561) 837-4074. WASTE ORD.
 NUMBER 2938-96.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]