Plan Review Details - Permit 04120964
Plan Review Stops For Permit 04120964
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-10-05 Cont ID  
Sent By jwitmer Date 2005-09-21 Time 10:38 Rev Time 2.22
Received By jwitmer Date 2005-10-05 Time 10:38 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-09-15 Cont ID  
Sent By jwitmer Date 2005-09-15 Time 08:33 Rev Time 0.55
Received By jwitmer Date 2005-09-15 Time 08:33 Sent To PC
Notes
2005-09-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04120964
 ADD: 5707 S DIXIE/ SIUTE 8
 CONT: SUNDOWN
 TEL: (561)662-4124
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 RESTAMP REVIEW
 ACTION: DENIED
  
 1) PLANS DO NOT REFLECT WHAT WAS
 PERMITED:
 MISSING ELEC WATER COOLER
 REVISIONS MADE IN PURPLE ,NOT REVIEWED
 BY ARCHETECT, HAS NO DATE OF
 REVISIONDELTA OR CLOUD
  
 A RESTAMP PLAN IS THE SAME PLAN AS
 PERMITTED!!!!!!!!!!!!!!!!!!!!
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-06-15 Cont ID  
Sent By jwitmer Date 2005-06-15 Time 17:41 Rev Time 0.77
Received By jwitmer Date 2005-06-15 Time 17:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-03 Cont ID  
Sent By jwitmer Date 2005-02-03 Time 12:03 Rev Time 0.77
Received By jwitmer Date 2005-02-03 Time 11:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-14 Cont ID  
Sent By jwitmer Date 2005-01-14 Time 11:40 Rev Time 1.11
Received By jwitmer Date 2005-01-14 Time 11:40 Sent To  
Notes
2005-01-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04120964
 ADD: 5705 S DIXIE BAY H"
 CONT: SUNDOWN
 TEL: (561)743-4420
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) CONTACT JOHN HIGINS @ (561)822-1239
 TO CORRECT ADDRESS. CITY INDICATES 5705
 S DIXIE NOT 5707.
 1A) BAYS TO HAVE NUMERIC FIGURES.
  
 2) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 3) MISSING EXIT SIGN FRONT OF BUILD
 OUT.
 1016.3.1. EXIT SIGNS:
 EXIT SIGNS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLE ILLUMINATED BY A
 RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE
 VISIBLE IN BOTH THE NORMAL & EMERGENCY
 LIGHTING.
  
 4) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 5) 1511.7 ROOF MOUNTED MECHANICAL UNIT S
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 60 704.2.1.4 CORRIDOR PARTITIONS,
 SMOKE STOP PARTITIONS, HORIZONTAL EXIT
 PART- ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-12-19 Cont ID  
Sent By dpalmer Date 2005-12-19 Time 07:49 Rev Time 0.00
Received By dpalmer Date 2005-12-19 Time 07:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 18:44 Rev Time 0.25
Received By dpalmer Date 2005-06-13 Time 18:40 Sent To  
Notes
2005-06-13 00:00:00THREE SETS OF PLANS SUBMITTED. ONLY TWO
 SETS HAD PME'S SIGNED AND SEALED BY
 ENGINEER.
 STAMPED ONLY TWO SETS OF ELECTRICAL
 PLANS.
 THIRD SET NOT STAMPED/PASSED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-03 Cont ID  
Sent By dpalmer Date 2005-02-03 Time 13:43 Rev Time 0.25
Received By dpalmer Date 2005-02-03 Time 13:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-29 Cont ID  
Sent By dpalmer Date 2004-12-29 Time 07:56 Rev Time 0.10
Received By dpalmer Date 2004-12-29 Time 07:56 Sent To  
Notes
2004-12-29 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE PLANS REFERENCE 5707
 S DIXIE, YET SYSTEM SHOWS 5707? PLEASE
 SEE BLDG REVIEW COMMENTS AND POSSIBLE
 ADDRESS CORRELATION.
  
 2)NOTE: PLEASE SEE NO ELECTRICAL PLANS
 WERE SUBMITTED FOR REVIEW, HOWEVER AN
 ELECTRICAL PERMIT IS BEING APPLIED FOR.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-06-14 Cont ID  
Sent By mwennerg Date 2005-06-14 Time 09:49 Rev Time 0.00
Received By mwennerg Date 2005-06-14 Time 09:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-02-03 Cont ID  
Sent By mcarsill Date 2005-02-03 Time 11:45 Rev Time 0.00
Received By mcarsill Date 2005-02-03 Time 11:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By mcarsill Date 2005-01-07 Time 14:19 Rev Time 0.00
Received By mcarsill Date 2005-01-07 Time 14:19 Sent To  
Notes
2005-01-07 00:00:001. EXIT SIGNS APPEAR TO BE MISSING
 FROM PLANS.
  
 2. NO INTERIOR FINISH CLASSIFICATION
 FOR WALLS AND CEILINGS.
  
 3. EMERGENCY LIGHTING APPEARS TO
 BE MISSING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-12-13 Cont ID  
Sent By adarroug Date 2005-12-13 Time 19:20 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 19:20 Sent To E
Notes
2005-12-13 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 10:26 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 10:26 Sent To B
Notes
2005-09-20 00:00:00TO "JWITMER" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-13 Cont ID  
Sent By adarroug Date 2005-09-13 Time 09:10 Rev Time 0.00
Received By adarroug Date 2005-09-13 Time 09:10 Sent To B
Notes
2005-09-13 00:00:00TO "JWITMER" DESK/RESTAMP AND DUPLICATE
 PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 13:19 Rev Time 0.00
Received By shill Date 2005-05-31 Time 13:19 Sent To  
Notes
2005-06-08 00:00:00COMM BOARD 47
2005-05-31 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD
 NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-01-28 Time 16:56 Rev Time 0.00
Received By mjacobs Date 2005-01-28 Time 16:56 Sent To  
Notes
2005-01-28 00:00:00TO "COMM BD#31/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2005-01-19 Time 18:10 Rev Time 0.00
Received By kstevens Date 2004-12-20 Time 08:03 Sent To  
Notes
2004-12-20 00:00:00SENT TO "COMM BD#7

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-29 Cont ID  
Sent By hmoser Date 2005-06-29 Time 14:43 Rev Time 0.00
Received By hmoser Date 2005-06-29 Time 14:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-19 Cont ID  
Sent By pkrauss Date 2005-01-19 Time 09:58 Rev Time 0.15
Received By pkrauss Date 2005-01-19 Time 09:58 Sent To  
Notes
2005-01-19 00:00:00DENIED:
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS AND
 EQUIPMENT SCHEDULE.INDICATE IF THE
 EQUIPMENT IS NEW OR EXISTING.PROVIDE
 DUCT/GRILLE SIZE, MATERIAL AND LAYOUT.
  
 PROVIDE OUTSIDE AIR CALCULATIONS AND
 INDICATE OUTSIDE AIR DUCT INTAKE,
 MATERIAL AND LAYOUT ON THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-06-24 Cont ID  
Sent By kstevens Date 2005-06-24 Time 18:55 Rev Time 0.65
Received By kstevens Date 2005-06-24 Time 18:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-02-19 Cont ID  
Sent By kstevens Date 2005-02-19 Time 12:36 Rev Time 1.00
Received By kstevens Date 2005-02-19 Time 12:36 Sent To  
Notes
2005-02-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) PLANS SHALL BE ROUTED TO DBPR HOTEL
 AND BUSINESS DIVISION FOR REVIEW PRIOR
 TO RESUBMITTING TO WPB CONST. SERVICES
 FOR RESUBMITTING. PLANS SHALL BE STAMPED
 BY DBPR AND WORKSHEETS ATTACHED.
 2) GREASE INTECEPTOR MAY BE REQUIRED.
 CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR DETERMINATION. WASTE ORD.
 2938-96 (561) 837-4074. WORK SHEET FROM
 MR. COMPO SHALL ACCOMPANY PLANS WHEN
 RESUBMITTING.
 3) SHT A-1 BATHROOM DETAIL. THE
 FOLLOWING INFORMATION IS REQUIRED TO
 CHOW COMPLIANCE.
 A) FLUSH CONTROLS 11-4.16.5
 B) FAUCETS 11-4.19.6
 4) SHT P-1 SANITARY RISER DIAGRAM AND
 PLUMBING FLOOR PLAN, 3 COMPARTMENT SINK
 SHALL DRAIN TO AN INDIRECT WASTE (FLOOR
 SINK) PER SECTION 802.1.1.
 5) INDICATE IF SEATING WILL BE AVAILABLE
 OR WILL THIS BE TAKE OUT ONLY.
 6) AN RPZ BACKFLOW WILL BE REQUIRED ON
 THE WATER SERVICE. SECTION 608.13.2.
 7) THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2.
 8) TOILET ROOMS SHALL NOT OPEN DIRECTLY
 INTO FOOD SERVING AREAS OR DINING AREAS.
 SECTION 423.16.10.1 BUILDING CODE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-19 Cont ID  
Sent By kstevens Date 2005-01-19 Time 18:14 Rev Time 0.50
Received By kstevens Date 2005-01-19 Time 18:11 Sent To  
Notes
2005-01-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SEE BUILDING REVIEW CONCERNING THE
 ADDRESS.
 2) SHT A-1 BATHROOM DETAIL. THE
 FOLLOWING INFORMATION IS REQUIRED TO
 SHOW COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, AND 11-4.22:
 A) CLEAR FLOOR SPACE 11-4.16.2
 B) FLUSH CONTROLS 11-4.16.5
 C) CLEAR FLOOR SPACE 11-4.19.3
 D) EXPOSED PIPES & SURFACES 11-4.19.4
 E) FAUCETS 11-4.19.6
 F) THE WATER CLOSET SHALL BE 18" FROM
 THE CENTERLINE OF THE FIXTURE TO THE
 WALL. FIG. 28
 G) THE LAV SHALL CENTER ON THE 30"
 MEASURMENT OF THE 30"X48" CLEAR FLOOR
 SPACE AND SHALL BE MIN. OF 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE.
 3) SUBMIT A SANITARY AND A WATER RISER
 DIAGRAM. SHOW ALL PIPE SIZES AND SHOW
 WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9 LOCATED NEAR THE FIXTURE,
 NOT IN THE CEILING PER PDI-WH 201. AIR
 CHAMBERS ARE NOT APPROVED.
 4) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE SECTION 410.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]