Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date 2004-12-20 Cont ID  
Sent By lsmith Date 2004-12-20 Time 13:22 Rev Time 0.00
Received By lsmith Date 2004-12-20 Time 13:21 Sent To  
Notes
2004-12-20 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. SUBMIT A DRAWING (FOOTPRINT ) OF THE
 BUILDING SHOWING THE WINDOWS & DOORS.
 THE ROOMS MUST BE LABELED TO ASSURE
 MEANS OF EGRESS. SHOW SIZES OF WINDOWS.
  
 2. THE TRACO 2100 SERIES IS NOT IMPACT.
 IF MORE THAN 25% OF THE GLASS AREA IS
 BEING REPLACED YOU MUST PROVIDE
 HURRICANE PROTECTION.
  
 3. SUBMIT 2 COPIES OF THE FLORIDA
 PRODUCT APPROVAL FOR THE
 MASONITE/PREMDOR. HIGHLIGHT THE DOORS
 YOU ARE USING.ONLY ONE COPY OF THE
 MIAMI-DADE PRODUCT APPROVAL WAS
 SUBMITTED.THE DOORS ARE NOT IMPACT
 RATED.HURRICANE PANELS WOULD BE
 REQUIRED. DO THE DOORS HAVE SIDELITES?
  
 3. SUBMIT A DESCRIPTION OF THE AREA
 WHERE PLASTER WORK IS TO BE DONE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-17 Cont ID  
Sent By mjacobs Date 2004-12-17 Time 14:35 Rev Time 0.00
Received By mjacobs Date 2004-12-17 Time 14:35 Sent To B
Notes
2004-12-17 00:00:00SENT TO "MISC" BOX.