Plan Review Details - Permit 04120934
Plan Review Stops For Permit 04120934
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-06 Cont ID  
Sent By jgomez Date 2005-01-06 Time 14:39 Rev Time 2.50
Received By jgomez Date 2005-01-06 Time 14:39 Sent To Z
Notes
2005-01-06 00:00:00CHECKLIST:
 1-PROVIDE ATTIC ACCESS AT GUEST HOUSE
 AREA. SEC. 2309.6 FBC 2001.
  
 2-PROVIDE COMPLETE SECTION/DETAIL THRU
 BAY WINDOW AT GARAGE AREA. SPECIFY ALL
 MATERIALS AND FASTENERS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 3-SPECIFY ROOF TILE NUMBER AND TYPE OF
 FASTENING AS REQUIRED BY SEC. 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
  
 4-SPECIFY ROOF AREAS TO HAVE 10PSF OR
 30PSF ATTIC LIVE LOAD AS REQUIRED BY
 TABLE 1604.1 FBC 2001. AND INCLUDE THIS
 INFORMATION WHEN DESIGNING TRUSSES.
  
 5-REVISE ROOF SHEATHING NOTE WHEN
 REFERING TO ZONE #3. SEE FIGURE
 1606.2(C) FOR AREAS TO BE CONSIDERED IN
 ZONE 3
  
 6-PROVIDE COMPLETE DETAILS AND SPECS FOR
 CONSTRUCTION OF ARCHED OPENINGS TO
 RECEIVE WINDOWS/DOORS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 7-PROVIDE COMPLETE DETAILS/SPECS FOR
 INSTALLATION OF CEILINGS AT ENTRY AND
 SIDE PORCH. SPECIFY ALL FASTENERS AND
 SPACING. SEE ASTM C926 AND C1063.
  
 8-OWES $1761.38 FOR UPDATED VALUATION,
 RADON FEES AND OWED BALANCE.
  
 9-GARAGE DOOR PRODUCT APPROVAL: CLEARLY
 IDENTIFY WHICH DOORS ARE GOING TO BE
 USED AND PROVIDE ONLY DRAWINGS THAT ARE
 RELATED TO SUCH DOORS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-30 Cont ID  
Sent By dpalmer Date 2004-12-30 Time 17:41 Rev Time 0.75
Received By dpalmer Date 2004-12-30 Time 17:41 Sent To M
Notes
2004-12-30 00:00:00**************** UNSAT ****************
  
  
  
 1)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE SEE PLANS STILL NOTE ONLY
 RECEPTS.
  
 2)NOTE: PLEASE SEE MIN KW FOR WASHER.
 PER 220.16B A LOAD OF NOT LESS THAN 1500
 VOLT-AMPERES SHALL BE INCLUDED FOR EACH
 2-WIRE LAUNDRY BRANCH CIRCUIT INSTALLED
 AS REQUIRED BY 210.11(C)(2).
  
 3)NOTE: PLEASE SEE RECEPTS MISSING PER
 2' OF WALL SPACE PER 210.52
  
 4)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 5)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOTED FROM METER
 TO MAIN "B". PLEASE SEE 250.6,250.24 AN
  
 EQUIPMENT GROUNDING CONDUCTOR IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISC.
  
 6)NOTE: PLEASE SEE 250.66/ 310.15B6 FOR
 MIN GROUNDING ELECTRODE CONDUCTOR FOR
 300A SERVICE. MIN #2.
  
 7)NOTE: PLEASE SEE PERMIT APPLICATION
 IS
 BEING RETAINED FOR RECORD.
 ALL SUB CONTRACTORS SIGNED ON
 APPLICATION IS ACTUALLY PHOTOCOPIED OF
 ORIG SIGNATURES.ALL SUB CONTRACTORS
 SIGNED AND DATED ON APPLICATIONS MUST BE
 ORIGINAL SIGNATURE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-30 Cont ID  
Sent By mmclean Date 2005-01-12 Time 14:27 Rev Time 0.00
Received By mjacobs Date 2004-12-30 Time 14:53 Sent To E
Notes
2004-12-30 00:00:00TO "SFD" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2004-12-20 Time 08:13 Rev Time 0.00
Received By mjacobs Date 2004-12-20 Time 08:12 Sent To Z
Notes
2004-12-20 00:00:00SENT TO"Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-01-03 Cont ID  
Sent By prafter Date 2005-01-03 Time 10:14 Rev Time 0.45
Received By prafter Date 2005-01-03 Time 10:13 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-03 Cont ID  
Sent By jleech Date 2005-01-03 Time 08:33 Rev Time 0.33
Received By jleech Date 2005-01-03 Time 08:33 Sent To M
Notes
2005-01-03 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW NOTE #7
 2.PAGE A-4, WATER HEATER PIPING DIAGRAM
 IS NOT CORRECT. FLOOR PLAN CALLS FOR
 RECIRC. PUMP NOT SHOWN ON WHPD. W/H PAN
 AND DRAIN NOT REQUIRED ON GROUND FLOOR
 INSTALLATIONS. THERMAL EXPANSION CONTROL
 IS REQUIRED BUT NOT SHOWN FBC PLUMBING
 SEC.607.3.2
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2005-01-12 Cont ID  
Sent By mmclean Date 2005-01-12 Time 14:14 Rev Time 0.00
Received By mmclean Date 2005-01-12 Time 14:25 Sent To  
Notes
2005-01-12 00:00:00DENIED, SITEPLAN & SURVEY DOES MATCH,
 SETBACKS ARE OFF.CALLED CONTR FILE D
 FOR P/U MM
2004-12-30 00:00:00PLEASE ROUTE TO ZONING LAST.THANKS MR.
 JACOBS


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved