| 2004-12-30 00:00:00 | **************** UNSAT **************** |
| | |
| | |
| | |
| | 1)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | PLEASE SEE PLANS STILL NOTE ONLY |
| | RECEPTS. |
| | |
| | 2)NOTE: PLEASE SEE MIN KW FOR WASHER. |
| | PER 220.16B A LOAD OF NOT LESS THAN 1500 |
| | VOLT-AMPERES SHALL BE INCLUDED FOR EACH |
| | 2-WIRE LAUNDRY BRANCH CIRCUIT INSTALLED |
| | AS REQUIRED BY 210.11(C)(2). |
| | |
| | 3)NOTE: PLEASE SEE RECEPTS MISSING PER |
| | 2' OF WALL SPACE PER 210.52 |
| | |
| | 4)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 5)NOTE: PLEASE SEE AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS NOTED FROM METER |
| | TO MAIN "B". PLEASE SEE 250.6,250.24 AN |
| | |
| | EQUIPMENT GROUNDING CONDUCTOR IS ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISC. |
| | |
| | 6)NOTE: PLEASE SEE 250.66/ 310.15B6 FOR |
| | MIN GROUNDING ELECTRODE CONDUCTOR FOR |
| | 300A SERVICE. MIN #2. |
| | |
| | 7)NOTE: PLEASE SEE PERMIT APPLICATION |
| | IS |
| | BEING RETAINED FOR RECORD. |
| | ALL SUB CONTRACTORS SIGNED ON |
| | APPLICATION IS ACTUALLY PHOTOCOPIED OF |
| | ORIG SIGNATURES.ALL SUB CONTRACTORS |
| | SIGNED AND DATED ON APPLICATIONS MUST BE |
| | ORIGINAL SIGNATURE. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |