Plan Review Details - Permit 04120902
Plan Review Stops For Permit 04120902
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2004-12-17 Cont ID  
Sent By jhiggins Date 2004-12-17 Time 12:53 Rev Time 0.00
Received By jhiggins Date 2004-12-17 Time 12:53 Sent To  
Notes
2005-01-06 00:00:00LOT ADDRESS CHANGED TO:110 BEVERLY
 RD,
 LOT PCN IS NOW:74434410220001421
2004-12-17 00:00:00ADDREES LOCATED: 117 BEVERLY RD, WPB

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2006-09-29 Cont ID  
Sent By rmcdouga Date 2006-09-29 Time 13:30 Rev Time 0.00
Received By rmcdouga Date 2006-09-29 Time 13:30 Sent To  
Notes
2006-09-29 00:00:00REVISION DENIED BY BUILDING
  
 1) SITE DRAINAGE PLAN ON SHEET SP-1
 SPECIFIES A RETAINING WALL (DETAIL 2)
 THAT WILL REQUIRE A SEPARATE PERMIT. THE
 SITE PLAN SUBMITTED WITH PERMIT
 #06060255 FOR THE PRIVACY WALL/RETAINING
 DOES NOT INDICATE THE RETAINING WALL
 SHOWN ON THIS SITE PLAN. A SEPARATE
 PERMIT IS REQUIRED FOR THE NEW SECTION
 OF RETAINING WALL.
  
 2) WHEN SUBMITTING FOR PERMIT THE
 FOLLOWING ITEMS WILL BE REQUIRED:EASMENT
 RELEASES, SITE PLANS, NOTICE OF
 COMMENCEMENT. THE RETAINING WALL IS
 REQUIRED TO COMPLY WITH THE FOLLOWING
 SECTIONS OF THE 2004 FBC 1806.1 GENERAL.
  
 WALLS BUILT TO RETAIN OR SUPPORT THE
 LATERAL PRESSURE OF EARTH OR WATER OR
 OTHER SUPERIMPOSED LOADS SHALL BE
 DESIGNED AND CONSTRUCTED OF MASONRY,
 CONCRETE, STEEL SHEET PILING OR OTHER
 APPROVED MATERIALS.
 1806.2 DESIGN.
 RETAINING WALLS SHALL BE DESIGNED TO
 RESIST THE DESIGN LATERAL SOIL LOADS IN
 SECTION 1610 , INCLUDING BOTH DEAD AND
 LIVE LOAD SURCHARGES TO WHICH SUCH WALLS
 ARE SUBJECTED, AND TO ENSURE STABILITY
 AGAINST OVERTURNING, SLIDING, EXCESSIVE
 FOUNDATION PRESSURE AND WATER UPLIFT.
  
 3) THE DRAINAGE PLAN FOR PERMIT
 #04120902 CAN BE DONE AS A SUBMITTAL.
 HOWEVER, THE INFORMATION SHOWN ON THE
 DRAWINGS MUST BE ACCURATE AND BEEN DONE
 WITH PERMITS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status N Date 2006-08-09 Cont ID  
Sent By rmcdouga Date 2006-08-09 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2006-08-09 Time 16:09 Sent To  
Notes
2006-08-09 00:00:00PLAN RESTAMP DENIED
  
 PLANS SUBMITTED ARE NOT EXACT MATCH OF
 APPROVED FILE SET.
  
 1) SHEET SP-1 DOES NOT HAVE PRIVACY
 WALLS AND WALL AND GATE ON RIGHT SIDE
 HAS BEEN MOVED. FILE PLANS ONLY HAVE
 REVISIONS 1 AND 2.
  
 2) SHEET A-1 DOES NOT REFLECT THE
 REDLINE CHANGES MADE BY J. BRASSEUR TO
 GAME ROOM ENERGY CALC. NOTES. CHANGED
 CEILING INSULATION TO R-20 AND INDICATED
 CEILING FANS.
  
 3) SHEET S-5 HAS REDLINE CHANGE BY
 D.O.R. TO R-20 AT GARAGE WALL SECTION.
  
 4)SHEET S-8 HAS REDLINE CHANGE BY D.O.R.
 TO R-20 FOR ICYENE R-VALUE AT GARAGE
 PARAPET DETAIL.
  
 5) CONTRACTOR NEEDS TO SUBMIT REVISED
 SHEET A-3 SPECIFYING THE CHANGE FROM
 SLOPED ROOF TO FLAT AT THE GARAGE. THIS
 SHEET WAS NOT SUBMITTED WHEN GARAGE ROOF
 WAS CHANGED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status N Date 2006-08-09 Cont ID  
Sent By rmcdouga Date 2006-07-28 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2006-07-28 Time 08:47 Sent To Z
Notes
2006-07-28 00:00:00DENIED
  
 1) A SEPARATE PERMIT IS REQUIRED FOR
 FENCES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status N Date 2006-08-09 Cont ID  
Sent By rmcdouga Date 2006-05-31 Time 07:29 Rev Time 0.00
Received By rmcdouga Date 2006-05-31 Time 07:29 Sent To  
Notes
2006-05-31 00:00:00REVISION DENIED
  
 REVISION FOR FENCES, SITE WALLS,
 RETAINING WALLS IS DENIED. A SEPARATE
 PERMIT IS REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-12-23 Cont ID  
Sent By rmcdouga Date 2005-12-23 Time 13:06 Rev Time 0.00
Received By rmcdouga Date 2005-12-23 Time 13:05 Sent To  
Notes
2005-12-23 00:00:00REVISED ROOF OF GAME ROOM
  
 PROVISO
  
 SUBMIT NEW ENERGY CALCULATIONS FOR THE
 GAME ROOM ABOVE THE DETACHED GARAGE
 REFLECTING THE CHANGE IN INSULATION
 R-VALUE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-09-15 Cont ID  
Sent By rmcdouga Date 2005-09-15 Time 12:51 Rev Time 0.00
Received By rmcdouga Date 2005-09-15 Time 10:51 Sent To  
Notes
2005-09-15 00:00:00BUILDING REVISION
 DENIED
  
  
 1) BOTH SETS OF REVISED DRAWINGS ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT AND THE ENGINEER THAT SIGNED
 AND SEALED THE ORIGINAL PLANS. FS 471
 AND 481.
  
 2) REMOVE THE 4:12 ROOF PITCH INDICATION
 FROM THE REAR GARAGE ELEVATION ON A5.
  
 3) THE GARAGE FLOOR FRAMING PLAN ON S-7
 INDICATES A GARAGE WALL SECTION 1 ON S5.
 THIS SECTION SPECIFIES A PITCHED ROOF.
 PLEASE CORRECT.
  
 4) SPECIFY THE SECOND FLOOR CEILING
 INSULATION AS REQUIRED BY FBC CHAPTER
 13. MUST CORRESPOND TO ENERGY CALC.
 FORMS.
  
 5) SPECIFY ATTIC VENTILATION PER FBC
 2309.7.
  
  
  
 6) ATTIC ACCESS IS NO LONGER REQUIRED
 PER FBC 2309.6. REVISE SHEET A2 OR SHOW
 THE 22" WIDE SPACE BETWEEN TRUSSES THAT
 ARE 16"OC ON THE ROOF FRAMING PLAN ON
 S7.
  
 7) THE PARAPET DETAIL ON S8 SPECIFIES A
 SIMPSON RT16 ATTACHED TO A CONCRETE BEAM
 WITH TAPCONS. SIMPSON DOES NOT LIST THIS
 CONNECTOR IN THEIR 2005 CATALOG. USP
 DOES HAVE A RT16 CONNECTOR, HOWEVER IT
 IS NOT SPECIFIED FOR ATTACHMENT TO
 CONCRETE BEAMS. IF THERE IS A TECHNICAL
 BULLETIN THAT SPECIFES THIS APPLICATION,
 PLEASE SUBMIT TWO COPIES OR REVISE PLANS
 TO SPECIFY A CONNECTOR DESIGNED AND
 TESTED FOR THIS APPLICATION.
  
 8) SPECIFY THE TYPE AND NUMBER OF
 FASTENERS FOR THE SIMPSON U212 HANGER
 SPECIFIED ON S8. SUBMIT THE FLORIDA
 PRODUCT APPROVAL FOR THIS CONNECTOR.
  
 9) SPECIFY THE WELD TYPE THAT WILL BE
 USED TO ATTACH THE THREADED RODS TO THE
 BRACKET IN DETAIL 4A ON S8. WHY ARE
 THREADED RODS BEING USED RATHER THAN
 NELSON STUDS.
  
 10) THE ROOF DOWN SPOUTS SHALL DISCHARGE
 AT LEAST 1 FOOT AWAY FROM THE STRUCTURE
 SIDEWALL PER FBC 1503.4.4.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-05-11 Cont ID  
Sent By rmcdouga Date 2005-05-11 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2005-05-11 Time 09:23 Sent To  
Notes
2005-05-11 00:00:00PROVISO
  
 1) SUBMIT A RERECORDED COPY OF THE NOC
 WHICH EXPIRES 90 DAYS AFTER BEING
 RECORDED IF THE WORK HAS NOT COMMENCED.
 SEE FS 713.13
  
 2) STRUCTURE IS LOCATED IN AN "A5" FLOOD
 ZONE AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 3) SUBMIT SHOP DRAWINGS FOR THE ALUMINUM
 GUARDRAILS BEFORE INSTALLING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-04-14 Cont ID  
Sent By rmcdouga Date 2005-04-14 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2005-04-14 Time 15:58 Sent To  
Notes
2005-04-14 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE COUNTY IMPACT FEES.
  
 2) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALCULATION FORMS
 FOR BOTH STRUCTURES.
  
 4) SHOP DRAWINGS WILL BE REQUIRED FOR
 THE ALUMINUM GUARDRAILS.
  
 5) SHEET A1 OF THE PLANS SPECIFIES
 IMPACT GLAZING FOR THE STRUCTURE. REMOVE
 THE PRODUCT APPROVALS FOR THE NON-IMPACT
 WINDOWS AND DOORS.
  
 6) SUBMIT FLORIDA PRODUCT APPROVALS FOR
 THE CONC."S" TILE ROOF.
  
 7) SUBMIT PRODUCT FLORIDA APPROVALS FOR
 THE ROOFING MATERIAL FOR THE FLAT
 PORTIONS OF THE ROOF THAT WILL NOT BE
 COVERED WITH TILE.
  
 8) THE NOA SUBMITTED FOR THE MODIFIED
 BITUMEN ROOFING FOR INSTALLATION UNDER
 THE MECHANICALLY FASTENED TILE DOES NOT
 CORRESPOND WITH THE NOA ATTACHED TO IT.
 SUBMIT THE CORRECT NOA.
  
 9) THE NOAS SUBMITTED WITH THE STATE
 PRODUCT APPROVALS FOR THE PGT FD101
 DOORS AND THE SH 701 AND PW 701 WINDOWS
 DO NOT CORRESPOND. THE CORRECT NOA
 NUMBERS ARE LISTED ON THE FL PRODUCT
 COVER SHEET.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-03-09 Cont ID  
Sent By rmcdouga Date 2005-03-09 Time 11:53 Rev Time 0.00
Received By rmcdouga Date 2005-03-09 Time 07:37 Sent To  
Notes
2005-03-09 00:00:00DENIED
  
 1) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE COUNTY IMPACT FEES.
  
 2) STRUCTURE IS LOCATED IN AN "A5" FLOOD
 ZONE.
  
 3) THE SUBSURFACE SOIL INVESTIGATION
 REPORT HAS THE WRONG ADDRESS.
  
 4) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC.FORMS FOR THE GAME ROOM.
  
 5) SHOP DRAWINGS FOR THE ALUMINUM
 GUARDRAILS WILL BE REQUIRED.
  
 6) THE DOOR FROM THE EGRESS STAIRS CAN
 NOT OPEN INTO THE GARAGE. FBC 1001.1.3
 REQUIRES AN UNOBSTRUCTED PATH OF TRAVEL
 TO THE EXTERIOR OF THE BUILDING. THE
 MEANS OF EGRESS SHALL NOT BE THROUGH
 KITCHENS, CLOSETS, RESTROOMS OR SIMULAR
 AREAS.
  
 7) FLORIDA PRODUCT APPROVAL COVER SHEETS
 HAVE NOT BEEN PROVIDED FOR ALL OF THE
 PRODUCTS THAT WERE SUBMITTED. SOME OF
 THE FL PRODUCT COVERS DO NOT CORRESPOND
 TO THE NOAS SUBMITTED. THE INFORMATION
 SUBMITTED MUST MATCH THE INFORMATION
 LISTED ON THE STATE WEBSITE. SEE THE
 NOTES ON THE PRODUCT APPROVALS THAT WERE
 SUBMITTED. TWO COPIES OF EVERYTHING IS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By rmcdouga Date 2005-01-07 Time 09:32 Rev Time 0.00
Received By rmcdouga Date 2005-01-07 Time 07:20 Sent To  
Notes
2005-01-07 00:00:00DENIED
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
  
 2) STRUCTURE IS LOCATED IN AN "A5" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED. THE MINIMUM ELEVATION IS
 7.5',WHICH INCLUDES AN ADDITIONAL 6"
 ABOVE BASE FLOOD ELEVATION PER CITY OF
 WPB ORDINANCE.
  
 3) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 4) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORM. THE SQUARE
 FOOTAGE OF CONDITIONED SPACE ON THE FORM
 DOES NOT AGREE WITH THE AMOUNT SPECIFIED
 ON THE PLANS. SECTION A ON S4 AND THE
 ENERGY CALC. INFO ON A1 SPECIFIES FOAM
 BOARD INSULATION AND THE ENERGY CALCS.
 LIST R-4.1.PLEASE CORRECT.
  
 5) SPECIFY ON THE PLANS THAT THE
 INTERMEDIATE RAILS OF THE GUARDRAILS AT
 THE STAIRS AND BALCONIES ARE REQUIRED TO
 REJECT A 4" SPHERE AND THE BOTTOM RAIL
 SHALL REJECT A 2" SPHERE. SEE FBC 1015.3
  
  
 6) SPECIFY FIREBLOCKING AT THE ENCLOSED
 SPACES BETWEEN STAIR STRINGERS AT THE
 TOP AND BOTTOM OF RUNS. SEE FBC
 2305.1.4
  
 7) THE STAIR CALCS ON A1 AND A2 CONTAIN
 ERRORS. PLEASE CORRECT.
  
 8) SHOP DRAWINGS WILL BE REQUIRED FOR
 THE ALUMINUM GUARDRAILS AT THE STAIRS
 AND BALCONIES.
  
 9) THE CITY OF WPB AMENDMENTS TO FBC
 TABLE 2306.1 REQUIRES ROOF SHEATHING TO
 BE NAILED AT 4"OC AT EDGES AND 6"OC
 INTERMEDIATE IN ZONE THREE WITH 8D RING
 SHANK NAILS WHEN MEAN ROOF HEIGHT IS
 25'-35'. THE OUTSIDE CORNERS OF HIP
 ROOFS ARE ZONE 3.
  
 10) FBC 1006.2.4 REQUIRES THE WALLS
 ADJACENT TO THE EXTERIOR EXITWAY STAIRS
 AND COVERED PORCH TO HAVE A ONE HOUR
 RATING WITH OPENING PROTECTIVES.
  
 11) SUBMIT MANUFACTURER'S SPECS. AND
 LISTING INFORMATION FOR THE BUILT-IN
 GAS
 BBQ.
  
 12) THE PLANS SHOW VENTED PREFAB
 FIREPLACES WITH FLUES TO THE ROOF. THE
 PRODUCT APPROVAL SUBMITTED IS FOR
 VENTLESS FIREPLACES. PLEASE CLARIFY.
  
 13) FBC 1707.4.4.2 REQUIRES WINDOW AND
 DOOR FRAMES TO BE FASTENED THROUGH 1X
 BUCKS AND INTO THE STRUCTURAL SUBSTRATE.
 PLEASE CORRECT BUCK NOTE ON A1.
  
 14) PROVIDE A FOOTING DETAIL AT THE
 GARAGE DOOR OPENING.
  
 15) THE SPECIFIED THICKNESS OF THE
 FOOTER IN DETAIL G ON S1 IS NOT
 CORRECT.
  
 16) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 17) SUBMIT (2) COMPLETE, CLEAN AND
 LEGIBLE COPIES OF PRODUCT APPROVALS.
 THE FOLLOWING SUBMITTALS HAVE SOME PAGES
 THAT ARE ILLEGIBLE:
 - PGT PW 701
 - WINDSOR GARAGE DOOR
 - MULE-HIDE ROOFING
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2006-10-06 Cont ID  
Sent By dpalmer Date 2006-10-06 Time 15:53 Rev Time 0.00
Received By dpalmer Date 2006-10-06 Time 15:53 Sent To PC
Notes
2006-10-06 00:00:00REDLINED, 250.66 FIR MIN GEC.
 PLEASE SEE ORIG PLANS SHOWED #2 WHICH
 WAS CORRECT FOR SIZE, HOWEVER PLANS
 SINCE HAVE SHOWN #4 WHICH WAS MISSED BY
 REVIEWER. IN EITHER CASE, MUST BE #2 AND
 MEET 250.66

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2006-09-28 Cont ID  
Sent By dpalmer Date 2006-09-28 Time 09:41 Rev Time 0.00
Received By dpalmer Date 2006-09-28 Time 09:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2006-09-27 Cont ID  
Sent By dpalmer Date 2006-09-27 Time 18:55 Rev Time 0.00
Received By dpalmer Date 2006-09-27 Time 18:55 Sent To PC
Notes
2006-09-27 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SEE PLANS ARE OK,
 HOWEVER ONLY ONE SET IS SIGNED, DATED
 AND SEALED BY THE ARCHITECT.
 FS 481.221.
  
 CONTRACTOR MAY PICK UP THE UN-STAMPED
 SET ONLY TO GET SIGNED AND SEALED, OR A
 NEW ONE CANE BE BROUGHT IN W/OUT A FEED.
 SEE DEWEY.
  
 IF THERE ARE ANY QUESTIONS , PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2006-08-20 Cont ID  
Sent By dpalmer Date 2006-08-20 Time 09:17 Rev Time 0.00
Received By dpalmer Date 2006-08-20 Time 09:11 Sent To PC
Notes
2006-08-20 00:00:00********* UNSAT ********
  
 1) NOTE: PLEASE CORRELATE PANELS, RISER
 AND PLANS.
 PLEASE SEE PANEL WHICH IS SHOWN ON RISER
 AS A 200 FEED-THRU PANEL, YET NO PANEL
 SCHEDULE ETC WAS SUBMITTED.
 PLEASE ALSO SEE THIS IS NOT SHOWN ON
 PLANS.
 THIS SHOUDL AHVE A MCB.
 225.31, FBC 106.1.2
  
 2) NOTE: PLEASE CORRELATE SIZES OF
 PANELS ON PANEL SCHEDULES AND WHAT IS
 BEING SHOWN ON RISER.
  
 3) NOTE: PLEASE CORRELATE FEEDERS ON
 RISER AND PANEL SCHEDULES. PLEASE SEE
 3/0, AND #1'S ETC FOR 100A BRKR FEED TO
 THE SUB PANEL.
  
  
 4) NOTE: PLEASE SEE PANEL SCHEDULE
 CIRCUTING DOES NOT SEEM TO START UNTIL
 ABOUT 1/3 THE WAY DOWN THE PANEL.
 PLEASE VERIFY THIS AS THIS IS NOT THE
 WAY IT IS ON THE JOBSITE.
  
  
 ** PLEASE KNOW, MANY ITEMS ON THE
 JOBSITE DOES NOT MATCH WITH PLANS.
 PLEASE KNOW, A PLAN REVIEW WAS DONE WITH
 THE ELECTRICAL INPECTOR AND CONTRACTOR
 ON THE PHONE AND MANY ITEMS SHOWN ON
 THESE PLANS DO NOT MATCH WITH WHAT IS
 INSTALLED IN FIELD. PLEASE GET WITH THE
 CONTRACTOR AND VERIFY ALL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-08-16 Cont ID  
Sent By dpalmer Date 2006-08-16 Time 19:37 Rev Time 0.00
Received By dpalmer Date 2006-08-16 Time 19:36 Sent To PC
Notes
2006-08-16 00:00:00** UNSAT **
  
 1) NOTE: PLEASE KNOW PLANS WHICH WERE
 SUBMITTED FOR A RE-STAMP DO NOT
 CORRELATE WITH THE LATEST REVISION #5 ON
 RECORD.
  
 PLEASE SUBMIT NEW REVISED SHEETS ALONG
 WITH CORRECTIONS FROM TWO PREVIOUS
 REVIEWS.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-08-09 Cont ID  
Sent By dpalmer Date 2006-08-09 Time 13:12 Rev Time 0.00
Received By dpalmer Date 2006-08-09 Time 13:12 Sent To B
Notes
2006-08-09 00:00:00**** UNSAT ******
  
  
  
 1) NOTE: THIS SEE THIS IS NOT A
 RE-STAMP.
 SUBMIT TWO COMPLETE COPIES FOR REVISIONS
 AND PAY REVISION FEES.
 PLEASE ALSO SEE NOTES FROM PREVIUOUS
 REVIEW WHICH FAILED.
 NOTES BELOW ARE ATTACHED.
  
  
 ******** UNSAT ******** FROM 7/27/06
  
  
 1) NOTE: PLEASE KNOW THAT THE PREVIOUS
 PLANS WERE REDLINED AS THE GENERATOR
 SHOWN ON PLANS WAS NOT PART OF THE
 PERMIT FOR THE HOUSE AND NO PERMIT TO
 DATE HAS BEEN APPLIED FOR THE
 RESIDENTIAL GEN. PLEASE REMOVE FROM
 PLANS.
 (SHOWS 5KW UNIT, IS THIS NOT A PRTABLE
 UNIT? )
  
 2) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 WITH ALL CIRCUITS SPECIFIC TO AREAS AND
 ROOMS IN WHICH THEY FEED. PLEASE SEE
 408.4. IE, MASTER BEDRN LTS, LIVING RM
 RECEPTS, HALL LTS, ETC.
  
 3) NOTE: PLEASE SEE PLANS SHOWS A
 "TANKLESS" WATER HEATER FOR THE MAIN
 HOUSE. PLEASE SEE HOWEVER THE KW RATING
 SEEMS TO BE FOR A STANDARD WH UNIT.??
 PLEASE SEE TL WH'S FOR A HOUSE THIS SIZE
 IS TPICALLY MUCH LARGER. PLEASE VERIFY
 AND ADJUST LOAD CALCS.
 220
  
 4) NOTE: PLEASE SEE THERE ARE A FEW
 LOCATIONS ON PLANS WHERE LV UC PUCK LT
 ARE NOTED , HOWEVER HOW MANY AND
 LOCATIONS ARE NOT SHOWN. PLEASE CLARIFY.
  
 5) NOTE: PLEASE SHOW LOAD CALCULATIONS
 FOR PANELS A AND B. 215.5,220.31.
  
 6) NOTE: PLEASE CORRELATE RISER AND
 PANELS. PLEASE SEE RISER SHOWS 20CIRCUIT
 PANELS FOR "C" AND "B", HOWEVER THESE
 ARE SHOWN AS 40 CIRCUIT PANELS ON
 SCHEDULES.
  
 7) NOTE: PLEASE KNOW IF THESE PLANS ARE
 FOR FINAL WHICH THEY APPEAR TO BE.
 PLEASE SEE TAHT ANY "OPT" LISTED ON
 PLANS EITHER ARE IN OR ARE REMOVED AS
 OPTIONAL.
 PLANS SHALL CONTAIN AN ACCUREATE RECORD
 OF THE SCOPE OF WORK PERFORMED ON JOB
 SITE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-07-27 Cont ID  
Sent By dpalmer Date 2006-07-27 Time 07:41 Rev Time 0.00
Received By dpalmer Date 2006-07-27 Time 07:05 Sent To B
Notes
2006-07-27 00:00:00**** UNSAT ******
  
 1) NOTE: PLEASE KNOW THAT THE PREVIOUS
 PLANS WERE REDLINED AS THE GENERATOR
 SHOWN ON PLANS WAS NOT PART OF THE
 PERMIT FOR THE HOUSE AND NO PERMIT TO
 DATE HAS BEEN APPLIED FOR THE
 RESIDENTIAL GEN. PLEASE REMOVE FROM
 PLANS.
 (SHOWS 5KW UNIT, IS THIS NOT A PRTABLE
 UNIT? )
  
 2) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 WITH ALL CIRCUITS SPECIFIC TO AREAS AND
 ROOMS IN WHICH THEY FEED. PLEASE SEE
 408.4. IE, MASTER BEDRN LTS, LIVING RM
 RECEPTS, HALL LTS, ETC.
  
 3) NOTE: PLEASE SEE PLANS SHOWS A
 "TANKLESS" WATER HEATER FOR THE MAIN
 HOUSE. PLEASE SEE HOWEVER THE KW RATING
 SEEMS TO BE FOR A STANDARD WH UNIT.??
 PLEASE SEE TL WH'S FOR A HOUSE THIS SIZE
 IS TPICALLY MUCH LARGER. PLEASE VERIFY
 AND ADJUST LOAD CALCS.
 220
  
 4) NOTE: PLEASE SEE THERE ARE A FEW
 LOCATIONS ON PLANS WHERE LV UC PUCK LT
 ARE NOTED , HOWEVER HOW MANY AND
 LOCATIONS ARE NOT SHOWN. PLEASE CLARIFY.
  
 5) NOTE: PLEASE SHOW LOAD CALCULATIONS
 FOR PANELS A AND B. 215.5,220.31.
  
 6) NOTE: PLEASE CORRELATE RISER AND
 PANELS. PLEASE SEE RISER SHOWS 20CIRCUIT
 PANELS FOR "C" AND "B", HOWEVER THESE
 ARE SHOWN AS 40 CIRCUIT PANELS ON
 SCHEDULES.
  
 7) NOTE: PLEASE KNOW IF THESE PLANS ARE
 FOR FINAL WHICH THEY APPEAR TO BE.
 PLEASE SEE TAHT ANY "OPT" LISTED ON
 PLANS EITHER ARE IN OR ARE REMOVED AS
 OPTIONAL.
 PLANS SHALL CONTAIN AN ACCUREATE RECORD
 OF THE SCOPE OF WORK PERFORMED ON JOB
 SITE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-11-30 Cont ID  
Sent By dpalmer Date 2005-11-30 Time 09:28 Rev Time 0.00
Received By dpalmer Date 2005-11-30 Time 09:10 Sent To P
Notes
2005-11-30 00:00:00REDLINED:
  
 GENERATOR SHOWN ON PLANS IS NOT IN SCOPE
 OF WORK FOR THIS PERMIT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-29 Cont ID  
Sent By dpalmer Date 2005-03-29 Time 16:54 Rev Time 0.50
Received By dpalmer Date 2005-03-29 Time 16:13 Sent To P
Notes
2005-03-29 00:00:00REDLINED ONE MISSING RECEPT FOR 210.52.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-03-01 Cont ID  
Sent By dpalmer Date 2005-03-01 Time 18:56 Rev Time 1.00
Received By dpalmer Date 2005-03-01 Time 18:24 Sent To Z
Notes
2005-03-01 00:00:00********** UNSAT **************
  
 PLEASE SEE DUE TO ADDRESS CHANGE AND
 PLANS SUBMITTED FOR THIS PERMIT #
 ORIGINALLY, PLEASE SEE COMMENTS BELOW
 WHICH STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE MAIN HOUSE PANEL IS
 SHOWN AT DETACHED BLDG.
 PLEASE SEE 225.31,32,36,250.32
 PLEASE SEE RISER NOW INDICATES A 300A
 DISC FEEDING A 200A RATED PANEL AND A
 150A RATED PANEL.
 PLEASE VERIFY OCP FOR EACH OF THESE
 PANELS.
 300A OCP MAY NOT FEED THESE.
 PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM AT DETACHED BLDGS.
 MEANS SHALL BE PROVIDED FOR
 DISCONNECTING ALL UNGROUNDED CONDUCTORS
 THAT SUPPLY OR PASS THROUGH THE BUILDING
 OR STRUCTURE.
 THE DISCONNECTING MEANS SHALL BE
 INSTALLED EITHER INSIDE OR OUTSIDE OF
 THE BUILDING OR STRUCTURE SERVED OR
 WHERE THE CONDUCTORS PASS THROUGH THE
 BUILDING OR STRUCTURE. THE DISCONNECTING
 MEANS SHALL BE AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE
 OF THE CONDUCTORS. FOR THE PURPOSES OF
 THIS SECTION, THE REQUIREMENTS IN 230.6
 SHALL BE PERMITTED TO BE UTILIZED.
  
 2)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2
 FOR MISSING SD'S REQUIRED AT SECOND FLR
 GUEST SUITE/RM AND ALSO AT FLR AREA
 LEADING TO FLR ABOVE.
  
 3)NOTE: PLEASE SEE PLANS CALL FOR SECOND
 FLR AREA TO BE A "GAME ROOM" HOWEVER,
 PANEL SCHEDULES INDICATE GUEST SUITE.
 PLEASE SEE POSSIBLE ZONING COMMENTS FOR
 THIS.
  
 4)NOTE: PLEASE SEE SMALL APPLIANCE
 CIRCUIT SHOWN AS 15A/ #12 AWG.
 PLEASE SEE 210.11C1,220.16 FOR MIN 20A
 #12.
  
 5)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS AFTER THE FIRST
 MEANS OF DISCONNECT. 250.24. PLEASE SIZE
 PER 250.122
  
 6)NOTE: PLEASE SEE ALL CIRCUITING ON
 PANEL SCHEDULES ARE TO BE REVISED.
 PLEASE SEE PANEL "B" WHICH SHOULD BE
 DETACHED GARAGE/GM RM/GUEST SUITE IS
 SHOWING 17 LIGHTING CIRCUITS, WHICH MOST
 SHOULD BE ON PANEL FOR MAIN HOUSE.
  
  
 PLEASE SEE DUE TO PLANS SUBMITTED FOR
 DIFFERENT HOUSES ON DIFFERENT LOTS. SOME
 OF THESE COMMENTS MAY ALSO BE ON PERMIT
 #04120901
  
  
 PLEASE CALL TO GO OVER ANY QUESTIONS FOR
 ELECTRICAL COMMENTS AND POSSIBLE
 CORRECTION OPTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 08:37 Rev Time 0.60
Received By dpalmer Date 2004-12-23 Time 08:26 Sent To M
Notes
2004-12-23 00:00:00********** UNSAT ****************
  
  
 1) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
  
 2)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 COMMON TEXT NOTE: PLEASE SEE MISSING SD
 LEADING TO FLR ABOVE.
  
  
 3)NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
 SHOWN AS #4
  
  
 4)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
  
  
 5) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E MISSING FRONT.
  
  
 6)NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE MISSING.
  
 7)NOTE: PLEASE SPACING FOR A/C DISC'S
 PER 110.26
  
 8)NOTE: PLEASE VERIFY KW LOAD SHOWN FOR
 WATER HEATER AND OVENS. WH IS SHOWN AS
 80 GAL YET ONLY SHOWS 5KW HEAT?
 PLEASE ALSO SEE DOUBLE OVENS ARE SHOWN
 WITH 50A OCP YET TWO OVENS ARE ONLY
 SHOWN WITH 6KW LOAD??
 PLEASE VERIFY THE ABOVE AND ADJUST AS
 NEEDED.
  
 9)NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS
 ON PLANS.
  
 10)NOTE: PLEASE INDICATE GFI FOR
 JACUZZI/SPA TUB. PER 680
  
  
 11 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY
 NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 12)NOTE: PLEASE SEE ZONING COMMENTS FOR
 APT AREA SHOWN ABOVE GARAGE.
 THIS WILL AFFECT ELECTRICAL PLANS.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHOULD BE SUBMITTED FOR
 REFERENCE ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-10-05 Cont ID  
Sent By adarroug Date 2006-10-05 Time 16:17 Rev Time 0.00
Received By adarroug Date 2006-10-05 Time 16:17 Sent To E
Notes
2006-10-05 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-09-28 Cont ID  
Sent By adarroug Date 2006-09-28 Time 13:39 Rev Time 0.00
Received By adarroug Date 2006-09-28 Time 13:39 Sent To B
Notes
2006-09-28 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 17:44 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 17:44 Sent To E
Notes
2006-09-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-08-17 Cont ID  
Sent By adarroug Date 2006-08-17 Time 10:29 Rev Time 0.00
Received By adarroug Date 2006-08-17 Time 10:29 Sent To E
Notes
2006-08-17 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 17:52 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 17:52 Sent To E
Notes
2006-08-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 18:27 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 18:22 Sent To Z
Notes
2006-07-31 00:00:00TO "Z BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-07-25 Cont ID  
Sent By adarroug Date 2006-07-25 Time 14:04 Rev Time 0.00
Received By adarroug Date 2006-07-25 Time 14:04 Sent To E
Notes
2006-07-25 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-05-27 Cont ID  
Sent By adarroug Date 2006-05-27 Time 13:18 Rev Time 0.00
Received By adarroug Date 2006-05-27 Time 13:18 Sent To B
Notes
2006-05-27 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-11-22 Cont ID  
Sent By adarroug Date 2005-11-22 Time 10:13 Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 10:13 Sent To E
Notes
2005-11-22 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 13:52 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 13:52 Sent To B
Notes
2005-09-13 00:00:00SENT TO MCDOUGLE FOR REVIEW
2005-09-08 00:00:00TO "KCONRAD" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-04-25 Cont ID  
Sent By adarroug Date 2005-04-25 Time 16:10 Rev Time 0.00
Received By adarroug Date 2005-04-25 Time 16:09 Sent To P
Notes
2005-04-25 00:00:00TO "KSTEVENS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-28 Cont ID  
Sent By adarroug Date 2005-03-28 Time 14:20 Rev Time 0.00
Received By adarroug Date 2005-03-28 Time 14:20 Sent To E
Notes
2005-03-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-22 Cont ID  
Sent By adarroug Date 2005-03-22 Time 15:07 Rev Time 0.00
Received By adarroug Date 2005-03-22 Time 15:07 Sent To Z
Notes
2005-03-22 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-07 Cont ID  
Sent By adarroug Date 2005-03-07 Time 09:05 Rev Time 0.00
Received By adarroug Date 2005-03-07 Time 09:05 Sent To P
Notes
2005-03-07 00:00:00TO KSTEVENS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 13:34 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 13:33 Sent To E
Notes
2005-02-28 00:00:00TO "DPALMER"DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-22 Cont ID  
Sent By mjacobs Date 2004-12-22 Time 08:40 Rev Time 0.00
Received By mjacobs Date 2004-12-22 Time 08:39 Sent To E
Notes
2004-12-22 00:00:00SENT TO "SFR" RACK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-12-30 Cont ID  
Sent By hmoser Date 2004-12-30 Time   Rev Time  
Received By hmoser Date 2004-12-30 Time   Sent To B
Notes
2004-12-30 00:00:00NO MECHANICAL PLANS.

Review Stop P PLUMBING
Rev No 6 Status P Date 2005-12-13 Cont ID  
Sent By jleech Date 2005-12-13 Time 15:02 Rev Time 0.33
Received By jleech Date 2005-12-13 Time 15:02 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-05-11 Cont ID  
Sent By kstevens Date 2005-05-11 Time 18:25 Rev Time 0.50
Received By kstevens Date 2005-05-11 Time 18:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-05-07 Cont ID  
Sent By kstevens Date 2005-05-07 Time 07:02 Rev Time 2.00
Received By kstevens Date 2005-05-07 Time 07:02 Sent To B
Notes
2005-05-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW:
 1) SHT E-2 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A. MINIMUM TRAP SIZE FOR THE WASH
 MACHINE IS 2" TABLE 709.1
 B. A CLEANOUT R' ABOVE THE FLOOR IS
 REQUIRED FOR THE WASH MACHINE. SECTION
 708.10
 C. A STANDPIPE IS REQUIRED ON THE WASH
 MACHINE. SECTION 1002.1
 D. BATH #3 A CROSS FITTING IS NOT
 APPROVED BETWEEN THE LAV AND TUB.
 SECTION 706.3.
 **********NEW COMMENTS**********
 1B) THE CLEANOUT REQUIRED BY SECTION
 708.3.5 OUTSIDE THE CABANA HAS BEEN
 DELETED ON THIS LATEST RISER DIAGRAM.
 2B) RISER DIAGRAM NOW DOES NOT REFLECT
 THE FLOOR PLAN. THE MORNING KITCHEN
 SHALL BE DOWNSTREAM OF THE MASTER BATH
 AS SHOWN ON THE FLOOR PLAN, AND THE
 FIXTURES IN THE MASTER BATH DO NOT
 REFLECT THE FLOOR PLAN AND WILL NOT BE
 INSTALLED AS SHOWN. RISER DIAGRAMS SHALL
 REFLECT THE FLOOR PLAN AND INDICATE HOW
 THE PIPING WILL BE INSTALLED. SECTION
 104.2.1.
 3B) BATH #2 IS SHOWN AS CONNECTING INTO
 THE 2ND FLOOR LEVEL. THIS IS NOT A DRAIN
 LINE. PLEASE CONNECT BATH #2 INTO A
 STACK OR BRANCH LINE. SECTION 104.2.1.
 4B) THE TUB & SHOWER IN THE MASTER BATH
 SHALL NOT BE CONNECTED TO THE BRANCH
 LINE BY A SANT. CROSS FITTING. SECTION
 706.3.
 4B) EACH SET OF PLANS SUBMITTED SHOWS
 THE SAME DATE ON THE SEAL OF THE
 ARCHITECT. PER SECTION 481.221(B) THE
 DATE THAT THE SHEETS WERE SEALED SHALL
 BE AFFIXED TO THE SEAL & SIGNATURE.
 5B) AS INDICATED IN THE PREVIOUS REVIEW,
 A 4 TIMES THE FEE SHALL BE IMPOSED ON
 THE DESIGN PROFESSIONAL FOR THE AMOUNT
 OF THE PORTION OF THE PERMIT FEE
 ATTRIBUTED TO PLAN REVIEW. THIS FEE IS
 NOT BEING IMPOSED AND WILL BE REQUIRED
 TO BE PAID PRIOR TO SUBMITTING FOR
 REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-04-12 Cont ID  
Sent By kstevens Date 2005-04-12 Time 06:43 Rev Time 0.75
Received By kstevens Date 2005-04-12 Time 06:43 Sent To B
Notes
2005-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA STATUTES
  
 1) SHT E-2 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A) MINIMUM TRAP SIZE FOR THE WASH
 MACHINE IS 2". TABLE 709.1
 B) A CLEANOUT 4' ABOVE THE FLOOR IS
 REQUIRED FOR THE WASH MACHINE. SECTION
 708.10.
 C) A STANDPIPE IS REQUIRED ON THE WASH
 MACHINE. SECTION 1002.1.
 D) BATH #3 A CROSS FITTING IS NOT
 APPROVED BETWEEN THE LAV AND TUB.
 SECTION 706.3.
 E) BATH #2 SHOWS A TUB ON THE FLOOR
 PLAN, BUT IS SHOWN AS A SHOWER ON THE
 RISER DIAGRAM. SECTION 104.2.1.
 F) CROSS BETWEEN THE WATER CLOSET AND
 THE SHOWER IN THE MASTER BATH IS NOT
 APPROVED. SECTION 706.3.
 G) DRY HORIZONTAL VENT IN THE MASTER
 BATH UPSTREAM OF THE TUB IS NOT
 APPROVED. SECTIONS 905.3 & 905.4.
 H) POWDER ROOM ON THE FIRST FLOOR OF
 THE CABANA SHOWN ON THE FLOOR PLAN IS
 NOT SHOWN ON THE RISER DIAGRAM. SECTION
 104.2.1.
 I) SEE EXAMPLES ON RISER DIAGRAM IN RED
 SHOWING HOW TO CORRECT RISER TO MEET
 CODE REQUIREMENTS AND REFLECT THE FLOOR
 PLAN.
 2) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-03-07 Cont ID  
Sent By jleech Date 2005-03-07 Time 18:13 Rev Time 0.50
Received By jleech Date 2005-03-07 Time 18:13 Sent To B
Notes
2005-03-07 00:00:00DENIED;
 RISER DIAGRAM DOESNOT REFLECT FLOOR PLAN
 PLEASE HAVE PLUMBING CONTRACTOR DRAW
 RISER DIAGRAM FOR YOU TO SEAL.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-27 Cont ID  
Sent By jleech Date 2004-12-27 Time 14:24 Rev Time 0.75
Received By jleech Date 2004-12-27 Time 13:54 Sent To M
Notes
2004-12-27 00:00:00PLUMBING PLAN REVIEW DENIED
 PLUMBINGT RISER DIAGRAM NOT TO CODE AND
 CANNOT BE INSTALLED AS DRAWN.SHOW ON
 RISER DIAGRAM WHERE 3" RISES ARE TO BE
 INSTALLED.MASTER BATHROOM, LAV'S ARE ON
 DIFFERENT WALL CAN NOT US SAMEVENT
 STACK. THERE IS NO PVC FITTING FOR
 MASTER BATH CIRCLED IN RED. BATH
 #2MARKED ON RISER DIAGRAM AS MST BATH,
 THERE IS NO SHR. IN BATH # 2 AND THE
 LAVS. ARE TOO FAR APART TO BE ON SAME
 STACK. BATH NUMBER # 3 THE WET BAR IS
 NOT ON SAME WALL AS LAV. ADDITIONAL
 STACK REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 5 Status F Date 2006-08-08 Cont ID  
Sent By rmcdouga Date 2006-08-09 Time 16:10 Rev Time 0.00
Received By mmclean Date 2006-08-08 Time 13:26 Sent To B
Notes
2006-08-08 00:00:00DENIED,
 1. THE PLANS SUBMITTED FOR RE-STAMP DOES
 NOT MATCH THE ORIGINAL PLANS THAT WAS
 APPROVED.
 2. THE DRIVEWAY DOES NOT MATCH WHAT WAS
 ORIGINAL APPROVED. NEED TO PROVIDE THE
 DIMENSION FOR THE NEW DRIVEWAY (LENGTH &
 WIDTH)
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 3. THE LOCATION OF THE CONCRETE IS NOT
 LOCATED AT THE SAME LOCATION AS
 ORIGINALLY APPROVED. ALSO, THEY IS AN
 ADDED SLAB.
 4. A-3 OF PLANS IS SHOWN IN THE ORINGAL
 APPROVED PLANS (8.15.95)
 5. THE FLOOR PLANS SHOWS A DIFFERENT
 LAYOUT OF WALKWALY.
 5. THE PLANS SUBMITTED SHOULD BE A
 REVISION.
 6. MUST PULL A SEPARATE PERMIT FOR
 WALL/FENCE/GATE WITH EASMENT APPROVAL
 FROM THE CITY OF WEST PALM BEACH UTILITY
 DEPT.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  
 PLANS ROUTED TO LUIS MARTINEZ, CHIEF
 BUILDING PLAN REVIEWER.

Review Stop Z ZONING
Rev No 4 Status F Date 2006-07-28 Cont ID  
Sent By mmclean Date 2006-07-28 Time 18:04 Rev Time 0.00
Received By mmclean Date 2006-07-28 Time 18:04 Sent To  
Notes
2006-07-28 00:00:00DENIED,
 1. SEPERATE PERMIT IS NEEDED FOR THE
 SITEWALL WITH EASEMENT APPROVAL FROM THE
 CITY OF WEST PALM BEACH UTILITY DEPT.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 3 Status P Date 2005-03-25 Cont ID  
Sent By mmclean Date 2005-03-25 Time 12:58 Rev Time 0.00
Received By mmclean Date 2005-03-25 Time 12:58 Sent To I
Notes
2005-03-25 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 POOL/DECK/SCREEN
 ENCLOSURE/SPA/FENCE/WALL (WITH CITY OF
 WEST PALM UTILITY DEPT APPROVAL).

Review Stop Z ZONING
Rev No 2 Status F Date 2005-03-04 Cont ID  
Sent By mmclean Date 2005-03-04 Time 16:32 Rev Time 0.00
Received By mmclean Date 2005-03-04 Time 16:28 Sent To I
Notes
2005-03-04 00:00:00DENIED,
 1. NEED TO CHANGE SITEPLAN TO SAY "GAME
 ROOM" INSTEAD OF GUEST SUITE (ZONED SF7)
 2. ACCESSORY STRUCTURE MUST BE 6FT FROM
 THE MAIN STRUCTURE, FROM ROOF LINE TO
 ROOF LINE. OR ACCESSORY STRUCTURE CAN BE
 ATTACHED TO MAIN STRUCTURE AND MEET THE
 10FT SETBACK IN REAR.
 3. GAME ROOM REFRIDGERATOR MUST SHOW U/C
 REF. AND APPLIANCE (ELEC) NEEDS TO BE
 CHANGE FROM 220 TO 110. (SEE ELEC NOTES)
 4. SEPERATE PERMIT MUST BE PULLED FOR
 THE POOL/SPA/DECK AND CBS WALL (WITH
 CITY OF WEST PALM BEACH UTILITY DEPT
 EASEMENT APPROVAL)
 5. PLANS WERE SWITCH WITH 04120901 AND
 ZONING NOTES DOES NOT MATCH THE
 SUBMITTED PLANS.LOT INFO ON
 APPLICATION DOES NOT MATCH SITEPLAN.
 6. ACCESSORY STRUCTURE CANNOT BE
 ATTACHED TO MAIN STRUCTURE WITH GATES.
 SEE NOTE #2.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SERVICEES
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-21 Cont ID  
Sent By mmclean Date 2004-12-21 Time 16:54 Rev Time 0.00
Received By mmclean Date 2004-12-21 Time 16:54 Sent To M
Notes
2005-04-05 00:00:00NOTES DOES NOT MATCH THIS PERMIT. DEAN R
 CHANGES PERMIT APPLICATION AND DID NOT
 CHANGE COMMENTS. SEE PERMIT 04120901
2004-12-21 00:00:00DENIED, THE 2ND STORY SITTING ROOM & 4TH
 BEDROOM MUST BE ACCESSIBLE FROM THE
 INSIDE OF MAIN STRUCTURE. ZONED SF7
 CANNOT HAVE A SEPERATE LIVING SPACE.
 CALLED & LEFT MSG ON VOICE MAIL.