Plan Review Details - Permit 04120901
Plan Review Stops For Permit 04120901
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rmcdouga Date 2006-02-01 Time 11:34 Sent To  
Notes
2006-02-01 00:00:00REVISE SHEETS A1,A2,A3,A4,S1,S4 AND S5
 ARE OK.
 SUBMITAL FOR ISOKERN FIREPLACE AND
 SPIRAL STAIRS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-01-27 Cont ID  
Sent By rmcdouga Date 2006-01-27 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2006-01-27 Time 16:06 Sent To  
Notes
2006-01-27 00:00:00REVISIONS DENIED
  
 1) SUBMIT MANUFACTURER'S SPECS. AND
 INSTALLATION INSTRUCTIONS FOR THE
 ISOKERN FIREPLACE AND CHIMNEY. SEE
 PREVIOUS REVIEWS.
  
 2) REVISED STRUCTURAL PLANS ARE REQUIRED
 TO BE SIGNED, SEALED AND DATED BY THE
 ENGINEER OF RECORD PER FS 471.
  
 3) THE REVISED ENERGY CALCULATIONS ARE
 REQUIRED TO BE SIGNED AND DATED BY THE
 OWNER/AGENT PER 2001 FBC CHAPTER 13.
  
 4) SUBMIT REVISED ELEVATION SHEETS FOR
 THE ELEVATIONS THAT ARE AFFECTED BY THE
 REVISED EXTERIOR STAIR AND WINDOW
 OPENINGS. SEE PREVIOUS REVIEWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-12-29 Cont ID  
Sent By rmcdouga Date 2005-12-28 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2005-12-28 Time 07:44 Sent To P
Notes
2005-12-29 00:00:00REVISIONS DENIED
  
 1) SUBMIT REVISED ENERGY CALCULATIONS
 FOR R-20 INSULATION.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE
 ICYNENE INSULATION.
  
 3) ICYENE INSULATION IS TYPICALLY USED
 FOR UNVENTED ATTICS AND IS INSTALLED ON
 THE TOP CORD OF THE TRUSSES. THE
 SECTIONS ON S-4 SPECIFY INSTALLATION ON
 THE BOTTOM CORD. IF APPLIED TO THE
 BOTTOM CORD THE ATTIC VENTILATION MUST
 BE MAINTAINED AND RECESSED LIGHTING WILL
 BE AFFECTED. PROVIDE MANUFACTURER'S
 INFORMATION WHICH ADDRESSES THESE ITEMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-11-10 Cont ID  
Sent By rmcdouga Date 2005-11-10 Time 14:47 Rev Time 0.00
Received By rmcdouga Date 2005-11-10 Time 14:47 Sent To  
Notes
2005-11-10 00:00:00REVISION DENIED
  
 1) SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS AND LISTING INFORMATION
 FOR THE ISOKERN FIREPLACE.
  
 2) THE REVISIONS SPECIFIED ON SHEETS A1
 AND A2 AFFECT THE STRUCTURAL PLANS AND
 ELEVATIONS. PLEASE REVISE ALL AFFECTED
 PLAN SHEET AND DETAILS.
  
 3) PROVIDE STRUCTURAL DRAWING K ON S5
 WHICH IS CALLED OUT ON THE REVISED PLANS
 BUT NOT SPECIFIED ON THE APPROVED PLANS.
  
 4) PROVIDE THE BEAM ATTACHMENT DETAILS
 FOR THE EXTENDED PORCH.
  
 5) PROVIDE DETAILS FOR THE SPIRAL
 STAIRS.
  
 6) THE REVISIONS ALSO AFFECT OTHER
 TRADES AND ZONING. PLEASE ADDRESS THEIR
 COMMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-28 Cont ID  
Sent By rmcdouga Date 2005-03-28 Time 8:58 Rev Time 0.00
Received By rmcdouga Date 2005-03-28 Time 07:29 Sent To  
Notes
2005-03-28 00:00:00BUILDING PROVISO
  
 1) STRUCTURE IS LOCATED IN AN "A5" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) SHOP DRAWINGS WILL BE REQUIRED FOR
 THE ALUMINUM GUARDRAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-28 Cont ID  
Sent By rmcdouga Date 2005-02-28 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2005-02-28 Time 16:14 Sent To  
Notes
2005-02-28 00:00:00DENIED
  
 1) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 2) SHOP DRAWINGS WILL BE REQUIRED TO BE
 SUBMITTED FOR THE ALUMNIUM GUARDRAILS.
  
 3)PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 A COVER SHEET WITH THE FL PRODUCT
 APPROVAL NUMBER IS REQUIRED TO BE
 ATTACHED TO THE MATCHING INSTALLATION
 INSTRUCTIONS (NOA, ICC EVALUATION
 REPORT, OR ENGINEERING) FOR ALL WINDOWS,
 DOORS AND OTHER STRUCTURAL COMPONENTS
 LISTED IN F.A.C. RULE 9B-72.
  
 4) SUBMIT FL PRODUCT APPROVAL COVER
 SHEETS FOR THE MULLIONS,SWD-101 FRENCH
 DOOR, FD-101 FRENCH DOOR WITH SIDELITE,
 SH-701 SINGLE HUNG WINDOWS AND METAL
 ROOF SYSTEM.
  
 5) A PRODUCT APPROVAL FOR NON-IMPACT
 CASEMENT WINDOWS WAS SUBMITTED. SUBMIT
 STORM PANEL PRODUCT APPROVALS, KEY PLAN
 AND INSTALLATION SCHEDULE FOR THESE
 WINDOWS. PLEASE REMOVE FROM SUBMITTALS
 IF THESE WINDOWS ARE NOT BEING
 INSTALLED.
  
 6) THE STATE PRODUCT APPROVAL COVER
 SHEET FOR FD-750 DOORS WERE SUBMITTED
 WITHOUT THE INSTALLATION INSTRUCTIONS,
 NOA OR OTHER EVALUATION. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-05 Cont ID  
Sent By rmcdouga Date 2005-01-05 Time 14:26 Rev Time 0.00
Received By rmcdouga Date 2005-01-05 Time 14:26 Sent To  
Notes
2005-01-05 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE STRUCTURES ARE LOCATED IN AN "A5"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED. THE MINIMUM ELEVATION
 IS 7.5', WHICH INCLUDES AN ADDITIONAL
 6" PER CITY OF WEST PALM BEACH
 ORDINANCE.
  
 4) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 5) SPECIFY THE INSULATION R-VALUE OF THE
 FLOOR OF THE GUEST HOUSE. SHEET S5
 SPECIFIES R-19.
  
 6) SPECIFY ON THE PLANS THAT THE
 INTERMEDIATE RAILS OF GUARDRAILS AT
 STAIRS AND BALCONIES ARE REQUIRED TO
 REJECT A 4" SPHERE AND THE BOTTOM RAIL
 SHALL REJECT A 2" SPHERE. SEE FBC
 1015.3
  
 7) SPECIFY FIREBLOCKING AT THE ENCLOSED
 SPACES BETWEEN STAIR STRINGERS AT THE
 TOP AND BOTTOM OF RUNS. SEE FBC
 2305.1.4
  
 8) ON S1 THE FTG.DETAILS D & I THE PAD
 FOOTER DEPTH IS INCORRECT.
  
 9) THE GARAGE WALL SECTION 1 ON S5 DOES
 NOT MATCH THE FTG. DETAIL B ON S1.
  
 10) ON S1 FTG DETAIL B IS INCORRECTLY
 SPECIFIED AT THE GARAGE DOOR OPENING.
  
 11) THE CITY OF WEST PALM BEACH
 AMENDMENTS TO FBC TABLE 2306.1 REQUIRES
 THE ROOF SHEATHING TO BE NAILED AT 4"OC
 AT EDGES AND 6" OC INTERMEDIATE IN ZONE
 3 WHICH INCLUDES THE OUTSIDE CORNERS OF
 HIP ROOFS.
  
 12) SHOP DRAWINGS WILL BE REQUIRED TO BE
 SUBMITTED FOR EXTERIOR IRON GUARDRAILS
 AT STAIRS AND BALCONY FOR APPROVAL PRIOR
 TO THEIR INSTALLATION.
  
 13) THE EXTERIOR EXITWAY STAIRS AND
 PORCHES,ETC. ARE REQUIRED TO BE LOCATED
 A MINIMUM OF 10' FROM ADJACENT PROPERTY
 LINES. BALCONIES, PORCHES , ETC. SHALL
 BE NOT LESS THAN 4.5' WIDE. SEE FBC
 1006.2.2
  
 14) FBC 1006.2.4 REQUIRES WINDOWS WITHIN
 10' OF EXTERIOR EXIT STAIRS TO HAVE
 OPENING PROTECTIVES. SEE FBC 1006.2.4
  
 15) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT TWO
 (2) LEGIBLE COPIES FOR EACH ITEM.
  
 16) SUBMIT (2) TWO CLEAN LEGIBLE COPIES
 OF ALL PRODUCT APPROVALS. - SUBMIT
 PRODUCT APPROVALS FOR THE FOLLOWING:
 - ARCHED TOP DOOR SPECIFIED ON THE PLANS
 FOR THE CABANA BATH.
 - THERMA-TRU FIBERGLASS DOOR
 - CASEMENT WINDOWS
 - ROOF COVERING FOR FLAT ROOFS
 - ROOFING MATERIAL AT SUN DECKS
 - OVERHEAD GARAGE DOOR
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-01-27 Cont ID  
Sent By dpalmer Date 2006-01-27 Time 19:33 Rev Time 0.00
Received By dpalmer Date 2006-01-27 Time 19:33 Sent To PC
Notes
2006-01-27 00:00:00REV OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 20:19 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 20:07 Sent To  
Notes
2006-01-20 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE CORRELATE RISER AND
 PLANS. PLEASE SEE RISER HAS NOW BEEN
 REVISED AND SHOWS AN ADDITIONAL RISER??
 PLEASE SEE RISER SHOWS CU'S BEING FED
 FROM THESE OUTDOOR PANELS, HOWEVER NO
 OCP, AWG, OR LOADS ARE SHOWN FOR THESE
 CU'S.?
 PLEASE SEE PLANS INDICATE 3-220V DISC'S
 NEXT TO METER, PLEASE SEE IT WAS ASSUMED
 THESE WERE THE DISC'S FOR POOL PUMP, AND
 CU'S HOWEVER THIS IS NOT CLEAR. PLEASE
 CORRELATE PLANS WITH SERVICE EQUIPMENT
 AND RISER DIAGRAM.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-12-15 Cont ID  
Sent By dpalmer Date 2005-12-15 Time 08:14 Rev Time 0.00
Received By dpalmer Date 2005-12-14 Time 17:00 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-11-10 Cont ID  
Sent By dpalmer Date 2005-11-10 Time 18:54 Rev Time 0.00
Received By dpalmer Date 2005-11-10 Time 18:37 Sent To  
Notes
2005-11-10 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE VERIFY DRYER(S) AND
 WASHER(S).
 PLEASE SEE PLANS INDICATE TWO DRYERS AND
 TWO WASHER RECEPTS SHOWN AT THIS SAME
 LOCATION, HOWEVER PANEL SCHEDULE AND
 LOAD CALCULATIONS ONLY INDICATE ONE
 WASHER?
 PLEASE ALSO CALRIFY IF THESE UNITS A
 STACKABLE UNITS AND PERHAPS THE 120V
 RECEPTS ARE ONLY PLACED FOR POSSIBLE
 FUTURE INDIVIDUAL UNITS.??
  
 2)NOTE: PLEASE VERIFY THE LOAD ON GDO'S
 AS 1/4 HP OR MORE REQUIRES DEDICATED
 CIRCUITS AND MAY NOT SHARE OTHER MOTOR
 LOADS.430.53, 430.148
  
 3)NOTE: PLEASE SEE REDLINED PLANS FOR
 POSSIBLE MISSING RECEPTS PER 210.52, 2'
 OF WALL SPACE.
 PLEASE SEE THAT RAIL AREA IN LOFT RM, IS
 CONSIDERED WALL SPACE AND WILL BE
 REQUIRED TO HAVE A RECEPT(FLOOR).
  
  
 4)NOTE: PLEASE SEE POSSIBLE
 KITCHEN/BUTLER COUNTERSPACE FOR MISSING
 GFI RECEPT(S) PER 210.52C1
 THESE LOCATIONS ARE REDLINED TO BE
 VERIFIED.
  
 5)NOTE: PLEASE SEE 210.8A2 WHICH
 REQUIRES ALL OUTDOOR RECEPT READILY
 ACCESSIBLE (6 1/2' ) OR LESS TO BE
 GFI/GFI PROTECTED.
 REDLINED.
  
 6)NOTE: PLEASE SEE PLANS INDICATE
 2-DISPOSAL'S, YET, PANEL SCHEDULES AND
 LOAD CALCULATIONS, ONLY INDICATE ONE?
 PLEASE CORRELATE AND ADJUST.
 215.5
  
 7)NOTE: PLEASE SEE LOAD CALCS INDICATE
 THREE SMALL APPLIANCE CIRCUITS, YET
 PANEL SCHEDULES ONLY SHOW TWO.
 PLEASE CORRELATE AND ADJUST AS NESS.
 215.5
  
 8)NOTE: PLEASE CORRLELATE THE NUMBER OF
 RECESSED LTS ON LOAD CALCULATIONS, WITH
 THE NUMBER OF FIXTURES SHOWN ON PLANS.
 PLEASE ADJUST LOAD CALCS AS NEEDED.
 215.5, 220.4
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-08 Cont ID  
Sent By dpalmer Date 2005-03-08 Time 12:40 Rev Time 0.30
Received By dpalmer Date 2005-03-08 Time 12:40 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-24 Cont ID  
Sent By dpalmer Date 2005-02-24 Time 06:07 Rev Time 0.30
Received By dpalmer Date 2005-02-23 Time 18:21 Sent To P
Notes
2005-02-24 00:00:00******* UNSAT *******
  
 PLEASE SEE PLANS ARE COMING BACK FOR
 ZONING COMMENTS.
 PLEASE CORRECT AT THIS TIME.
  
 1)NOTE: PLEASE SEE RISER HAS NOW
 INCREASED ORIG 100A PANEL TO 150A'S.
 PLEASE SEE CONDUCTORS WERE NOT INCREASED
 FOR 150A'S, PLEASE SEE 310.15B6 MIN,
 310.16.
 PLEASE CORRELATE PANEL , PLEASE SEE
 PANEL DETAILS LOCATED AT BOTTOM OF PANEL
 BOTH INDICATE 100A MAIN AND 150A.
 215.5
  
 2)NOTE: PLEASE SEE ELECTRICAL PLANS NOW
 INDICATE AN OPENING INTO SECOND FLR
 MEDIA RM, HOWEVER NO MEANS FOR SWITCHING
 OF EGRESS LIGHTINGIS SHOWN. PLANS
 REDLINED ON ONE SET. (3-WAY SWITCH)?.
  
 3)NOTE: PLEASE SEE 310.15B6,250.66, DUE
 TO INCREASE IN SIZE OF SERVICE, PLEASE
 SEE MIN GROUNDING ELECTRODE CONDUCTOR IS
 NOW 1/0. PLEASE ADJUST.
  
 4)NOTE: PLEASE SEE EACH SD HAS A RECEPT
 SHOWN NEXT TO IT? THIS SEEMS TO BE
 EITHER AT CEILING OR AT FLR? PLEASE
 VERIFY IF THIS RECEPT IS GOING BE
 INSTALLED AT EACH SD LOCATION?
 THIS IS ONLY A NOTE: PLANS ARE COMING
 BACK AND IF ANY CHANGES NEEDED TO MADE,
 THIS WOULD SAVE FROM HAVING TO REVISE
 PLANS AGAIN BEFORE ROUGH.
  
 PLEASE SEE ONE SET OF PLANS HAVE AREAS
 REDLINED AT LOCATIONS FOR NOTES.
  
 PLEASE REMOVE OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2005-02-23 00:00:00FROM ZONIING TO ELECTRIC REVIEW ON
 2/19/05

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 09:15 Rev Time 0.75
Received By dpalmer Date 2004-12-23 Time 09:15 Sent To M
Notes
2004-12-23 00:00:00********** UNSAT ****************
  
  
 1) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 2)NOTE: PLEASE SEE 210.52D FOR LOCATION
 OF GFI RECEPT SPACING TO WITHIN 3' OF
 SINK EDGE.
  
 3)NOTE: PLEASE SEE 210.63, 210.70 FOR
 GFI RECETP AND LT REQUIRED FOR AHU
 OUTSIDE MECH RM.
  
 4)NOTE: PLEASE VERIFY KW LOAD SHOWN FOR
 WATER HEATER AND OVENS. WH IS SHOWN AS
 80 GAL YET ONLY SHOWS 5KW HEAT?
 PLEASE ALSO SEE DOUBLE OVENS ARE SHOWN
 WITH 50A OCP YET TWO OVENS ARE ONLY
 SHOWN WITH 6KW LOAD??
 PLEASE VERIFY THE ABOVE AND ADJUST AS
 NEEDED.
  
 5)NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS
 ON PLANS.
  
 6)NOTE: PLEASE INDICATE GFI FOR
 JACUZZI/SPA TUB. PER 680
  
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY
 NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: PLEASE SEE ZONING COMMENTS FOR
 APT AREA SHOWN ABOVE GARAGE.
 THIS WILL AFFECT ELECTRICAL PLANS.
  
 9)NOTE: PLEASE SEE MAIN HOUSE PANEL IS
 SHOWN AT DETACHED BLDG.
 PLEASE SEE 225.31,32,36
 250.31
 MEANS SHALL BE PROVIDED FOR
 DISCONNECTING ALL UNGROUNDED CONDUCTORS
 THAT SUPPLY OR PASS THROUGH THE BUILDING
 OR STRUCTURE.
 THE DISCONNECTING MEANS SHALL BE
 INSTALLED EITHER INSIDE OR OUTSIDE OF
 THE BUILDING OR STRUCTURE SERVED OR
 WHERE THE CONDUCTORS PASS THROUGH THE
 BUILDING OR STRUCTURE. THE DISCONNECTING
 MEANS SHALL BE AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE
 OF THE CONDUCTORS. FOR THE PURPOSES OF
 THIS SECTION, THE REQUIREMENTS IN 230.6
 SHALL BE PERMITTED TO BE UTILIZED.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHOULD BE SUBMITTED FOR
 REFERENCE ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-01-11 Cont ID  
Sent By adarroug Date 2006-01-11 Time 11:36 Rev Time 0.00
Received By adarroug Date 2006-01-11 Time 11:36 Sent To P
Notes
2006-01-11 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-12-12 Cont ID  
Sent By adarroug Date 2005-12-12 Time 14:00 Rev Time 0.00
Received By adarroug Date 2005-12-12 Time 14:00 Sent To E
Notes
2005-12-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-10-20 Cont ID  
Sent By adarroug Date 2005-10-20 Time 09:07 Rev Time 0.00
Received By adarroug Date 2005-10-20 Time 09:07 Sent To B
Notes
2005-10-20 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-10-20 Cont ID  
Sent By adarroug Date 2005-10-20 Time 08:20 Rev Time 0.00
Received By adarroug Date 2005-10-20 Time 08:20 Sent To E
Notes
2005-10-20 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-09-15 Cont ID  
Sent By adarroug Date 2005-09-15 Time 16:07 Rev Time 0.00
Received By adarroug Date 2005-09-15 Time 16:07 Sent To P
Notes
2005-09-15 00:00:00TO "JLEECH" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-04-01 Cont ID  
Sent By adarroug Date 2005-04-01 Time 09:23 Rev Time 0.00
Received By adarroug Date 2005-04-01 Time 09:23 Sent To Z
Notes
2005-04-01 00:00:00TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-07 Cont ID  
Sent By adarroug Date 2005-03-07 Time 09:08 Rev Time 0.00
Received By adarroug Date 2005-03-07 Time 09:08 Sent To E
Notes
2005-03-07 00:00:00TO DPALMER DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-03 Cont ID  
Sent By adarroug Date 2005-03-03 Time 11:42 Rev Time 0.00
Received By adarroug Date 2005-03-03 Time 11:42 Sent To Z
Notes
2005-03-03 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 11:44 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 11:44 Sent To E
Notes
2005-02-22 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-07 Cont ID  
Sent By adarroug Date 2005-02-07 Time 14:21 Rev Time 0.00
Received By adarroug Date 2005-02-07 Time 14:21 Sent To Z
Notes
2005-02-07 00:00:00TO "Z"BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-22 Cont ID  
Sent By mjacobs Date 2004-12-22 Time 16:23 Rev Time 0.00
Received By mjacobs Date 2004-12-22 Time 16:23 Sent To  
Notes
2004-12-22 00:00:00SENT TO "SFR" RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-17 Cont ID  
Sent By mjacobs Date 2004-12-17 Time 08:43 Rev Time 0.00
Received By mjacobs Date 2004-12-17 Time 08:43 Sent To Z
Notes
2004-12-17 00:00:00SENT TO "Z" BOX./NEED ADDRESSING
 CORRECTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2005-04-05 Cont ID  
Sent By pkrauss Date 2005-04-05 Time 13:55 Rev Time 0.40
Received By pkrauss Date 2005-04-05 Time 13:55 Sent To  
Notes
2005-04-05 00:00:00MECHANICAL CONTRACTOR TO APPLY
 SEPARATELY AND TO SUBMIT PLANS AND
 MANUAL J CALCS AT THAT TIME (KYLE/ACTION
 AIR).PER CONVERSATION WITH ROGER
 THOMAS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2005-03-22 Time   Rev Time 0.00
Received By hmoser Date 2005-03-22 Time 18:38 Sent To B1
Notes
2005-03-22 00:00:00NO A/C PLANS OR MANUAL (J)
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-02-28 Cont ID  
Sent By prafter Date 2005-02-28 Time 08:17 Rev Time 0.50
Received By prafter Date 2005-02-28 Time 08:17 Sent To B
Notes
2005-02-28 00:00:00SECOND MECH. PLAN REVIEW.
  
 NO A/C PLAN OR EQUIPMENT INFORMATION
 .
  
 PAT RAFTER 561/805/6728.OR 805/6719.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-12-30 Cont ID  
Sent By hmoser Date 2004-12-30 Time   Rev Time  
Received By hmoser Date 2004-12-30 Time   Sent To B
Notes
2004-12-30 00:00:00NO MECHANICAL PLANS.

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-01-25 Cont ID  
Sent By jleech Date 2006-01-25 Time 13:44 Rev Time 0.50
Received By jleech Date 2006-01-25 Time 09:22 Sent To B
Notes
2006-01-25 00:00:00REVISED PLUMBING RISER DIAGRAM
 (SANITARY) MOVED W/M TO 2ND FLOOR

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-12-29 Cont ID  
Sent By jleech Date 2005-12-29 Time 09:29 Rev Time 0.50
Received By jleech Date 2005-12-29 Time 09:29 Sent To  
Notes
2005-12-29 00:00:00DENIED;
 1.FIRST FLOOR WASHING MACHINE SHOWN ON
 SAN. RISER DIAGRAM IS NOT SHOWN ON FLOOR
 PLAN.
 2.THE TWO W/M'S AND SERVICE SINK SHOWN
 ON PLANS ARE NOT SHOWN ON SAN. RISER
 DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-03-18 Cont ID  
Sent By kstevens Date 2005-03-18 Time 22:09 Rev Time 0.33
Received By kstevens Date 2005-03-18 Time 22:09 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-02-26 Cont ID  
Sent By jleech Date 2005-02-26 Time 10:06 Rev Time 0.75
Received By jleech Date 2005-02-26 Time 10:06 Sent To M
Notes
2005-02-26 00:00:00DENIED;
 1.LAUNDRY TUB REQUIRED TO DISCHARGE
 ABOVE WASHER.
 2.CLOTHS WASHER WASTE ARM AND TRAP TO BE
 TWO INCH.
 3.RISER DIAGRAM DOES NOT MATCH FLOOR
 PLAN.(LAUNDRY ROOM ON SAME WALL AS
 KITCHEN, LAUNDRY ROOM IS NEAR DINING
 ROOM KITCHEN IS NEAR GARAGE. 3' RISERS
 FOR 2ND FLOOR ARE OUTSIDE HOUSE)
 4.3" RISERS FOR 2ND FLOOR REQUIRE A 6"
 WALL PLEASE SHOW ON DRAWING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-12-27 Cont ID  
Sent By jleech Date 2004-12-27 Time 13:46 Rev Time 0.50
Received By jleech Date 2004-12-27 Time 13:46 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2005-04-05 Cont ID  
Sent By mmclean Date 2005-04-05 Time 11:30 Rev Time 0.00
Received By mmclean Date 2005-04-05 Time 11:30 Sent To M
Notes
2005-04-05 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE. ALSO,
 FOR FENCE/WALL/GATE WITH CITY OF WEST
 PALM UTILILTY DEPT, UTILITY EASEMENT
 APPROVAL.CANNOT PUT GATE/WALL IN 15FT
 UE.

Review Stop Z ZONING
Rev No 3 Status F Date 2005-03-04 Cont ID  
Sent By mmclean Date 2005-03-04 Time 16:53 Rev Time 0.00
Received By mmclean Date 2005-03-04 Time 16:53 Sent To I
Notes
2005-03-04 00:00:00DENIED,
 1. SITEPLAN & APPLICATION DOES NOT MATCH
 LOTS (SITEPLAN LOT 141 AND APPLCIATION
 1/2 LOF 135, 136, 137.NEED TO BE
 CORRECTED.
 2. CANNOT HAVE GUEST HOUSE IN SF7, MUST
 CHANGE APPLICATION AND COMPUTER SCREEN
 TO SAY "MEDIA ROOM"
  
 NOTE: SEPARATE PERMIT MUST BE PULLED FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE. ALL
 REFRIDGERATOR EXCEPT FOR KITCHEN SHOULD
 HAVE ON PLANS U/C REFRIDGERATOR.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SERVICES
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2005-02-18 Cont ID  
Sent By mmclean Date 2005-02-18 Time 09:21 Rev Time 0.00
Received By mmclean Date 2005-02-18 Time 09:21 Sent To I
Notes
2005-02-18 00:00:00DENIED,
 1. MUST HAVE A REGULAR DOOR OPENING ON
 THE 2ND FLOOR (MEDIA ROOM), IN ORDER TO
 HAVE EXTERIOR STAIRS.
 2. MUST REMOVE ON APPLICATION AND
 COMPUTER SCREEN GUEST HOUSE. ZONED SF7.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 CONSTRUCTION SERVICES
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-22 Cont ID  
Sent By mmclean Date 2004-12-22 Time 11:38 Rev Time 0.00
Received By mmclean Date 2004-12-22 Time 11:38 Sent To  
Notes
2005-04-05 00:00:00THE ABOVE NOTES DOES NOT MATCH COMMENTS
 TO THIS PERMIT.DEAN R CHANGED PLANS
 AND DID NOT MAKE CHANGES TO THE PLAN
 REVIEW COMMENTS.
2004-12-22 00:00:00DENIED, ZONED SF7, NO OTHER LIVING
 QUARTERS ALLOWED WITH MAIN STRUCTURE.
 CANNOT HAVE EXTERIOR STAIRS.ACCESSORY
 STUCTURE MUST BE A MIN OF 6FT FROM MAIN
 STRUCTURE AND ONLY A GAME ROOM ALLOWED.
 CALLED ROGER CONTRACTOR.