Plan Review Details - Permit 04120602
Plan Review Stops For Permit 04120602
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2005-03-31 Cont ID  
Sent By alange Date 2005-03-31 Time 15:54 Rev Time 0.25
Received By alange Date 2005-03-31 Time 15:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-10 Cont ID  
Sent By dpalmer Date 2005-03-10 Time 11:46 Rev Time 0.25
Received By dpalmer Date 2005-03-10 Time 11:46 Sent To  
Notes
2005-03-10 00:00:00SECOND SET OF SUBMITTALS SUBMITTED,OK.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-24 Cont ID  
Sent By dpalmer Date 2005-01-24 Time 11:37 Rev Time 0.50
Received By dpalmer Date 2005-01-24 Time 11:37 Sent To  
Notes
2005-01-24 00:00:00****************************************
 ***************************************
  
 PLEASE SEE A SECOND SET OF GENERATOR
 SUBMITTALS NEEDS TO BE SUBMITTED.
 ONLY ONE SET COULD BE LOCATED IN
 PACKAGE.
 ELECTRICAL PLANS STAMPED.
  
 NOTES REDLINED FOR ALL SIGNAGE PER
 700.8,702.8.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 11:15 Rev Time 0.50
Received By dpalmer Date 2004-12-23 Time 11:15 Sent To  
Notes
2004-12-23 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SUBMIT PLANS SIGNED,
 DATED AND SEALED BY ENGINEER.
 PLANS SUBMITTED ARE COPIES WITH CHANGES
 MADE TO ORIG PLANS.
 FS 471.025
  
 2)NOTE: PLEASE SHOW MEANS OF DISC FOR
 POWER COMING FROM GEN.
 PLEASE SEE 225.31,32,36 ETC.
  
 3)NOTE: PLEASE SUBMIT MANUFACT SPECS
 SHEETS FOR ALL NEW EQUIPMENT BEING
 INSTALLED.
  
 4)NOTE: PLEASE HAVE PLANS CLEARLY SHOW
 EXISTING AND NEW.
 215.5
  
 5)NOTE: PLEASE SEE 230.72 AND GROUPING
 OF DISC'S AND REQUIRED TO BE IN CLOSE
 PROXIMITY AS DETERMINED BY AHJ.
  
 6)NOTE: PLEASE SEE COMMENTS FROM OTHER
 REVIEWERS AS THEY WILL DIRECTLY AFFECT
 ELECTRICAL PLANS AND PROJECT.
  
 MUST PROVIDE SITE PLANS, WIND LOADING,
 GUARDING OF LIVE PARTS/ENCLOSURE FOR GEN
 ETC.
  
 PLEASE NOTE, DUE TO PLANS AND SUBMITTED
 PACKAGE NOT BEING COMPLETE AT THIS TIME,
 THERE MAY BE OTHER COMMENTS TO FOLLOW.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-02-17 Cont ID  
Sent By mcarsill Date 2005-02-17 Time 15:29 Rev Time 0.00
Received By mcarsill Date 2005-02-17 Time 15:29 Sent To  
Notes
2005-02-17 00:00:00ON 2/17/05 TEKTON ELECTRICAL SYSTEMS
 INC. REPRESENTATIVE CAME TO THE FIRE
 STATION AND PROVIDED MORE INFORMATION
 AND WE REVIEWED THE PLANS AND THE
 ORIGINAL PLANS ALONG WITH OTHER
 DRAWINGS. THE GENERATOR INSTALLATION
 IS NOW APPROVED AFTER THIS REVIEW.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-02-03 Cont ID  
Sent By mcarsill Date 2005-02-03 Time 08:33 Rev Time 0.00
Received By mcarsill Date 2005-02-03 Time 08:33 Sent To  
Notes
2005-02-03 00:00:001. PLEASE ILLUSTRATE ADJOINING PROPERTY
 LINES, ADJACENT STRUCTURES, IMPORTANT
 BUILDINGS.
  
 2. PLEASE INDICATE ANY EASEMENTS IN THE
 VICINITY.
  
 3. FUEL STORAGE TO COMPLY WITH
 NFPA 30.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-27 Cont ID  
Sent By mcarsill Date 2004-12-27 Time 13:57 Rev Time 0.00
Received By mcarsill Date 2004-12-27 Time 13:57 Sent To  
Notes
2004-12-27 00:00:001. PLEASE PROVIDE PRODUCT APPROVALS
 FOR GENERATOR.
  
 2. PLEASE PROVIDE SITE PLAN
 INDICATING WHERE THE GENERATOR
 IS TO BE INSTALLED.
  
 3. PLEASE INDICATE AMOUNT OF FUEL
 THAT IS PLANNED.
  
 4. WHAT IS THE GENERATOR GOING TO
 SUPPLY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 10:05 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 10:10 Sent To  
Notes
2005-03-10 00:00:00TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-14 Cont ID  
Sent By mjacobs Date 2005-01-14 Time 14:20 Rev Time 0.00
Received By mjacobs Date 2005-01-14 Time 14:20 Sent To  
Notes
2005-01-14 00:00:00TO "COMM BD#50"/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-13 Cont ID  
Sent By mjacobs Date 2004-12-13 Time 12:01 Rev Time 0.00
Received By mjacobs Date 2004-12-13 Time 12:01 Sent To E
Notes
2004-12-13 00:00:00SENT TO "COMM BD#10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-03-30 Cont ID  
Sent By pkrauss Date 2005-03-29 Time 14:42 Rev Time 0.45
Received By pkrauss Date 2005-03-29 Time 14:42 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-05 Cont ID  
Sent By pkrauss Date 2005-01-05 Time 16:38 Rev Time 0.55
Received By pkrauss Date 2005-01-05 Time 16:23 Sent To  
Notes
2005-01-06 00:00:00DENIED:
 1.PROVIDE A SITE PLAN SHOWING THE
 LOCATION OF THE GENERATOR IN RELATION TO
 THE PROPERTY LINES AND DISTANCES TO
 BUILDING STRUCTURE AND ANY EXTERIOR
 EQUIPMENT OR APPLICANCES (I.E. CONDESING
 UNITS, PUMPS, ETC).
  
 2.PROVIDE MANUFACTURER'S SUBMITTAL AND
 INSTALLATION INSTRUCTIONS FOR THE DEISEL
 GENERATOR.
  
 3.INDICATE LOCATION OF FUEL STORAGE.
 SHOULD A REMOTE TANK BE NECESSARY,
 PROVIDE SUBMITTAL FOR THE TANK.
 INDICATE ALSO ON THE PLAN LOCATION OF
 FUEL TANKS.
  
 4.ADDTIONAL PERMIT WILL BE REQUIRED
 FOR ALL FUEL PIPING & TANK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2005-03-29 Cont ID  
Sent By pkrauss Date 2005-03-30 Time 15:24 Rev Time 0.00
Received By jroach Date 2005-03-29 Time 15:36 Sent To  
Notes
2005-03-29 00:00:003/29/05 ***PASSED***
  
 NO MINOR PD AMENDMENT REQUIRED, LOCATION
 APPROVED AS PART OF PREVIOUS SITE PLAN
 APPROVAL.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN
 ROACH, PLANNER AT (561)822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-02-08 Cont ID  
Sent By jroach Date 2005-02-08 Time 14:20 Rev Time 0.00
Received By jroach Date 2005-02-08 Time 14:20 Sent To  
Notes
2005-02-08 00:00:002/8/05 ***FAILED***
  
 1) UPON REVIEWING SUBMITTED SITE PLAN,
 EXTERIOR GENERATOR REQUIRES MINOR PD
 AMENDMENT, PURSUANT TO SECTION
 94-207(E)(2) OF THE CITY OF WEST PALM
 BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS TO ADOPT AN AMENDED SITE
 PLAN AND LANDSCAPE PLAN.
  
 PLEASE CONTACT JOHN ROACH, PLANNER WITH
 REGARD TO THESE COMMENTS. (561) 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-29 Cont ID  
Sent By jroach Date 2004-12-29 Time 16:29 Rev Time 0.00
Received By jroach Date 2004-12-29 Time 16:28 Sent To  
Notes
2004-12-29 00:00:0012/29/04 ***FAILED***
  
 1) PLEASE PROVIDE A SITE PLAN INDICATING
 THE LOCATION OF THE GENERATOR AND ALL
 OTHER EXTERIOR ELEMENTS.
  
 PLEASE CALL JOHN ROACH, PLANNER FOR
 QUESTIONS/COMMENTS. (561) 822-1435