Plan Review Details - Permit 04120601
Plan Review Stops For Permit 04120601
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-11 Cont ID  
Sent By btrobaug Date 2005-02-11 Time 14:40 Rev Time 0.00
Received By btrobaug Date 2005-02-11 Time 14:40 Sent To  
Notes
2005-02-11 00:00:00 
  
 PROVISO
 ~~~~~~~
  
 PROVIDE SIGNAGE INDICATING GENERATOR
 DISCONNECT LOCATION WITH THE MAIN
 SERVICE EQUIPMENT.
  
 THE OUTPUT OF THE 25KW GENERATOR IS
 104AMPS. THE LOAD CALC SUBMITTED IS 116
 AMPS. INSTALL AN EMERGENCY PANEL AND
 SELECT LOADS TO CORRELATE WITH GENERATOR
 OUTPUT. RESUMBIT RISER DIAAGRAM SHOWING
 ALL EQUIPMENT AND HOW CONNECTED PRIOR TO
 SCHEDULING FINL ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-17 Cont ID  
Sent By btrobaug Date 2004-12-17 Time 15:57 Rev Time 0.50
Received By btrobaug Date 2004-12-17 Time 15:25 Sent To Z
Notes
2004-12-17 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE MANUFACTURER
 SPECIFICATIONS FOR THE GENERATOR.
  
 2} INDICATE THE PRIME MOVER FOR THE
 GENERATOR AND HOW STORED , IF
 APPLICABLE.(OTHER THAN NATURAL GAS).
  
 3)INDICATE GROUNDING METHOD.
  
 4} INDICATE RATING, TYPE AND LOCATION OF
 DISCONNECT PER 225.31 AND 230.70 CWPB.
  
 5} PROVIDE A LOAD CALCULATIION FOR THE
 CIRCUITS INTENDED TO BE SERVED BY THE
 GENERATOR AND A PANEL SCHEDULE OF SAME.
  
 6} PROVIDE INFORMATION REGARDING HOW
 LOADS ARE TO BE TRANSFERRED. ALSO SPECS
 ON TRANSFER SWITCH.
  
 7} GIVE THE SIZE OF ALL CONDUCTORS AND
 CONDUITS BEING INSTALLED.
  
 8} THE VALUATION ON THE APPLICATION MUST
 INCLUDE ALL COST FOR THIS PROJECT,
 INCLUDING THE COST OF THE GENERATOR,
 LABOR AND MATERIAL. PLEASE CHANGE
 VALUATION ON THE APPLICATION TO REFLECT
 SAME PER 104.6.5.FBC.AND CWPB.
  
 9} THE DESIGNER OF RECORD MUST PRINT AND
 SIGN NAME ON PLANS PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-03 Cont ID  
Sent By adarroug Date 2005-02-03 Time 10:36 Rev Time 0.00
Received By adarroug Date 2005-02-03 Time 10:36 Sent To E
Notes
2005-02-03 00:00:00TO BT DESK/RESUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-01-28 Time 16:13 Rev Time 0.00
Received By mjacobs Date 2005-01-28 Time 16:13 Sent To Z
Notes
2005-01-28 00:00:00TO "Z" BOX/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-13 Cont ID  
Sent By mjacobs Date 2004-12-13 Time 11:58 Rev Time 0.00
Received By mjacobs Date 2004-12-13 Time 11:58 Sent To E
Notes
2004-12-13 00:00:00SENT TO "E" BOX.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-02-02 Cont ID  
Sent By mmclean Date 2005-02-02 Time 12:26 Rev Time 0.00
Received By mmclean Date 2005-02-02 Time 12:26 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-17 Cont ID  
Sent By mmclean Date 2004-12-17 Time 16:03 Rev Time 0.00
Received By mmclean Date 2004-12-17 Time 16:03 Sent To E
Notes
2004-12-17 00:00:00DENIED, NEED TO PROVIDE TWO COPY OF
 SURVEY SHOWING THE LOCATION OF THE
 GENERATOR WITH SETBACKS.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved