Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-20 Cont ID  
Sent By btrobaug Date 2004-12-20 Time 16:40 Rev Time 0.50
Received By btrobaug Date 2004-12-20 Time 16:24 Sent To  
Notes
2004-12-20 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE CONDUIT & WIRE SIZE & TYPE
 ON THE EXISTING SERVICE.
  
 2} PLEASE SUBMIT AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT BEING INSTALLED.
 MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9.
  
 3} THE CONDUCTORS FROM THE METER TO THE
 PANEL DO NOT COMPLY WITH 310.15(B)(6).
 ALSO INDICATE CONDUIT TYPE.
  
 4} THE GROUND RODS SHOWN DON'T APPEAR TO
 BE CONNECTED TO ANYTHING, PLEASE CLARIFY
 AND INDICATE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR.
  
 5} PLEASE PROVIDE A SITE DRAWING
 INDICATING WHERE ALL THE COMPONENTS OF
 THE SERNICE ARE LOCATED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-10 Cont ID  
Sent By mjacobs Date 2004-12-10 Time 14:25 Rev Time 0.00
Received By mjacobs Date 2004-12-10 Time 14:25 Sent To E
Notes
2004-12-10 00:00:00SENT TO "E" BOX.