| Plan Review Stops For Permit 04120557 |
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2004-12-15 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2004-12-15 |
Time |
07:14 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2004-12-15 |
Time |
07:14 |
Sent To |
|
|
| Notes |
| 2004-12-11 00:00:00 | GAS PLAN REVIEW,DENIED FBC 2001 FUEL | | | GAS | | | CODE. | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | | | | 2. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE EXISTINGSYSTEM. | | | REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34) | | | 3. MANFACTURES CUT SHEET ON 2LB GAS | | | REGULATORS, SHOW LOCATION OF EACH GAS | | | REGULATOR. | | | END OF COMMENTS QUESTIONS 561-805-6692 |
|
|
|