| Plan Review Stops For Permit 04120528 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-02-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-02-16 |
Time |
14:57 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2005-02-16 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-01-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-01-10 |
Time |
15:47 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2005-01-10 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2005-01-10 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04120528 | | | ADD: 1655 PALM BCH LAKES# 203 | | | CONT: MJS CONSTRUCTION | | | TEL: (561)772-1276 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) COVER SHEET PROJECT DATA CORRECT | | | TYPE OF CONSTRUCTION, BUILDING IS | | | "HIGH-RISE". | | | | | | 3) CONFERENCE ROOM IS 760 SQ FT, TABLE | | | 1003.1 FOR CONFERENCE ROOMS AREA PER | | | OCCUPANT 15 NET = OCCUPANT LOAD TO BE | | | 51. 1012.1.2 EGRESS DOORS SHALL BE SIDE | | | SWINGING TYPE. DOORS SHALL SWING IN THE | | | DIRECTION OF EGRESS FOR THE FOLLOWING: | | | (1) WHEN SERVING AN OCCUPANT LOAD OF 50 | | | OR MORE. | | | | | | 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 5)PLANS, SPECIFICATIONS,REPORTS OR OTHER | | | DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | MISSING INFORMATION ON THE TITLE BLOCK | | | FOR ARCH'S FIRM FAC61G1-16.004, | | | FL S. S. 481.219. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-04-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-26 |
Time |
15:24 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-04-26 |
Time |
15:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-02-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-14 |
Time |
17:23 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-02-14 |
Time |
17:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-02-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-24 |
Time |
17:15 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-01-24 |
Time |
17:15 |
Sent To |
|
|
| Notes |
| 2005-02-11 00:00:00 | ************ UNSAT 3RD REVIEW ******* | | | | | | 1)NOTE: PLEASE SEE TITLE BLOCK HAS BEEN | | | CORRECTED ON PART OFPLANS, HOWEVER, | | | PLEASE SEE LOWER RIGHT TITLE BLOCK | | | BELOW | | | ENGINEER'S AND ALSO ALL OTHER SHEETS | | | STILL REFERENCE FIRM. | | | FS 481.219, FAC 61G1-16.004 | | | THIS IS FOR ALL SHEETS AND FOR ALL | | | TRADES. | | | | | | ELEC SHEETS HAVE BEEN VOIDED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-12-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-12-27 |
Time |
16:58 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-12-27 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2004-12-27 00:00:00 | *********** UNSAT ********** | | | | | | 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. | | | 230.42,215.3, TEC | | | | | | 2)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | GRND FOR TRANSFORMER. 250.30 | | | | | | 3)NOTE: PLEASE SEE MISSING INFORMATION | | | ON TITLE BLOCK FOR ARCH'S FIRM. | | | FAC 61G1-16.004, FS 481.219 | | | PLEASE SEE THIS IS REQUIRED ON ALL | | | SHEETS AND FOR ALL TRADES WHEATHER OR | | | NOT COMMENT IS MADE BY OTHER | | | REVIEWER(S). | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLYINSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-04-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-04-27 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-04-27 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2005-04-27 00:00:00 | 1) REVISION DATED 4/19/05 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2004-12-27 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-12-27 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-12-27 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-04-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-25 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-25 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2005-04-25 00:00:00 | TO "COMM" BD#44 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-01-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-21 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-21 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2005-01-21 00:00:00 | TO "COMM BD#1/RESUB." |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-01-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-10 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-10 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2004-12-10 00:00:00 | SENT TO COMM BD#12 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2005-05-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-05-05 |
Time |
07:23 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2005-05-05 |
Time |
07:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-02-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-02-17 |
Time |
14:03 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2005-02-17 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-02-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-02-04 |
Time |
10:28 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2005-02-04 |
Time |
09:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-01-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-01-05 |
Time |
07:46 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-01-05 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2005-01-05 00:00:00 | DENIED: | | | SEE COMMENT BY DEWEY PALMER ELECTRICAL | | | PLAN REVIEW IN REGARDS TO REQUIREMENT BY | | | THE FAC 61G-16.004 & FS 481.219. | | | | | | PLEASE NOTE, NO COMBUSTIBLES ALLOWED | | | ABOVE THE CEILING IN THE RETURN AIR | | | PLENUM. | | | | | | PLAN ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-02-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-02-16 |
Time |
13:11 |
Rev Time |
0.58 |
| Received By |
kstevens |
Date |
2005-02-16 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-01-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-01-07 |
Time |
14:28 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2005-01-07 |
Time |
14:28 |
Sent To |
B |
|
| Notes |
| 2005-01-07 00:00:00 | DENIED; | | | 1. SEE ELECTRICAL PLAN REVIEW NOTE 3. | | | 2.BREAK SINK TO COMPLY WITH FBC CHAPTER | | | 11 SEC 11-4.24.1 THRU 11-4.7. SHOW | | | DETAIL A-4.1. HEIGH 34" KNEE CLEARANCE | | | DEPTH CLEAR FLOOR SPACE EXPOSED PIPES | | | AND FAUCET. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|