Plan Review Details - Permit 04120528
Plan Review Stops For Permit 04120528
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-16 Cont ID  
Sent By jwitmer Date 2005-02-16 Time 14:57 Rev Time 1.11
Received By jwitmer Date 2005-02-16 Time 14:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-10 Cont ID  
Sent By jwitmer Date 2005-01-10 Time 15:47 Rev Time 2.00
Received By jwitmer Date 2005-01-10 Time 15:47 Sent To  
Notes
2005-01-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04120528
 ADD: 1655 PALM BCH LAKES# 203
 CONT: MJS CONSTRUCTION
 TEL: (561)772-1276
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COVER SHEET PROJECT DATA CORRECT
 TYPE OF CONSTRUCTION, BUILDING IS
 "HIGH-RISE".
  
 3) CONFERENCE ROOM IS 760 SQ FT, TABLE
 1003.1 FOR CONFERENCE ROOMS AREA PER
 OCCUPANT 15 NET = OCCUPANT LOAD TO BE
 51. 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS FOR THE FOLLOWING:
 (1) WHEN SERVING AN OCCUPANT LOAD OF 50
 OR MORE.
  
 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5)PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 MISSING INFORMATION ON THE TITLE BLOCK
 FOR ARCH'S FIRM FAC61G1-16.004,
 FL S. S. 481.219.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-04-26 Cont ID  
Sent By dpalmer Date 2005-04-26 Time 15:24 Rev Time 0.30
Received By dpalmer Date 2005-04-26 Time 15:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-14 Cont ID  
Sent By dpalmer Date 2005-02-14 Time 17:23 Rev Time 0.25
Received By dpalmer Date 2005-02-14 Time 17:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-02-11 Cont ID  
Sent By dpalmer Date 2005-01-24 Time 17:15 Rev Time 0.25
Received By dpalmer Date 2005-01-24 Time 17:15 Sent To  
Notes
2005-02-11 00:00:00************ UNSAT 3RD REVIEW *******
  
 1)NOTE: PLEASE SEE TITLE BLOCK HAS BEEN
 CORRECTED ON PART OFPLANS, HOWEVER,
 PLEASE SEE LOWER RIGHT TITLE BLOCK
 BELOW
 ENGINEER'S AND ALSO ALL OTHER SHEETS
 STILL REFERENCE FIRM.
 FS 481.219, FAC 61G1-16.004
 THIS IS FOR ALL SHEETS AND FOR ALL
 TRADES.
  
 ELEC SHEETS HAVE BEEN VOIDED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-27 Cont ID  
Sent By dpalmer Date 2004-12-27 Time 16:58 Rev Time 0.33
Received By dpalmer Date 2004-12-27 Time 16:58 Sent To  
Notes
2004-12-27 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.
 230.42,215.3, TEC
  
 2)NOTE: PLEASE CLARIFY NEW OR EXISTING
 GRND FOR TRANSFORMER. 250.30
  
 3)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCK FOR ARCH'S FIRM.
 FAC 61G1-16.004, FS 481.219
 PLEASE SEE THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLYINSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-04-27 Cont ID  
Sent By mwennerg Date 2005-04-27 Time 14:10 Rev Time 0.00
Received By mwennerg Date 2005-04-27 Time 14:10 Sent To  
Notes
2005-04-27 00:00:001) REVISION DATED 4/19/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-12-27 Cont ID  
Sent By nmccray Date 2004-12-27 Time 13:02 Rev Time 0.00
Received By nmccray Date 2004-12-27 Time 13:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-25 Cont ID  
Sent By adarroug Date 2005-04-25 Time 08:46 Rev Time 0.00
Received By adarroug Date 2005-04-25 Time 08:46 Sent To  
Notes
2005-04-25 00:00:00TO "COMM" BD#44

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-21 Cont ID  
Sent By mjacobs Date 2005-01-21 Time 14:25 Rev Time 0.00
Received By mjacobs Date 2005-01-21 Time 14:25 Sent To  
Notes
2005-01-21 00:00:00TO "COMM BD#1/RESUB."

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-21 Cont ID  
Sent By mjacobs Date 2005-01-10 Time 14:25 Rev Time 0.00
Received By mjacobs Date 2004-12-10 Time 08:14 Sent To  
Notes
2004-12-10 00:00:00SENT TO COMM BD#12

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-05-05 Cont ID  
Sent By pkrauss Date 2005-05-05 Time 07:23 Rev Time 0.30
Received By pkrauss Date 2005-05-05 Time 07:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-02-17 Cont ID  
Sent By pkrauss Date 2005-02-17 Time 14:03 Rev Time 0.30
Received By pkrauss Date 2005-02-17 Time 14:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-02-04 Cont ID  
Sent By pkrauss Date 2005-02-04 Time 10:28 Rev Time 0.35
Received By pkrauss Date 2005-02-04 Time 09:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-05 Cont ID  
Sent By pkrauss Date 2005-01-05 Time 07:46 Rev Time 0.40
Received By pkrauss Date 2005-01-05 Time 07:36 Sent To  
Notes
2005-01-05 00:00:00DENIED:
 SEE COMMENT BY DEWEY PALMER ELECTRICAL
 PLAN REVIEW IN REGARDS TO REQUIREMENT BY
 THE FAC 61G-16.004 & FS 481.219.
  
 PLEASE NOTE, NO COMBUSTIBLES ALLOWED
 ABOVE THE CEILING IN THE RETURN AIR
 PLENUM.
  
 PLAN ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-16 Cont ID  
Sent By kstevens Date 2005-02-16 Time 13:11 Rev Time 0.58
Received By kstevens Date 2005-02-16 Time 13:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-07 Cont ID  
Sent By jleech Date 2005-01-07 Time 14:28 Rev Time 0.75
Received By jleech Date 2005-01-07 Time 14:28 Sent To B
Notes
2005-01-07 00:00:00DENIED;
 1. SEE ELECTRICAL PLAN REVIEW NOTE 3.
 2.BREAK SINK TO COMPLY WITH FBC CHAPTER
 11 SEC 11-4.24.1 THRU 11-4.7. SHOW
 DETAIL A-4.1. HEIGH 34" KNEE CLEARANCE
 DEPTH CLEAR FLOOR SPACE EXPOSED PIPES
 AND FAUCET.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695