Plan Review Details - Permit 04120431
Plan Review Stops For Permit 04120431
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-10-04 Cont ID  
Sent By jwitmer Date 2005-10-04 Time 15:19 Rev Time 0.00
Received By astelly Date 2005-10-04 Time 14:48 Sent To PC
Notes
2006-06-12 00:00:00JIM WHITMER REVIEWED ON 10/04/2005

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-28 Cont ID  
Sent By jwitmer Date 2005-09-28 Time 11:18 Rev Time 0.00
Received By jwitmer Date 2005-09-28 Time 11:18 Sent To  
Notes
2005-09-28 00:00:00PERMIT:04120431
 ADD: 333 EVERNIA
 CONT: SCHNELL CONSTRUCTION
 TEL: (941)321-1915
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
  
 1) QUESTION # 1 FROM THE PREVIOUS REVIEW
 ASK FOR THE MINIMUM BUILDING TYPE?
  
 3401.7.2.3 NON-STRUCTURAL REPAIRS AND
 ALTERATIONS EXCLUSIVE OF FIXTURES AND
 FURNITURE, THE COST OF WHICH DOES NOT
 EXCEED 25 PERCENT OF THE VALUE OF THE
 EXISTING BUILDING OR STRUCTURE AND WHICH
 DO NOT AFFECT EGRESS OR FIRE
 RESISTIVITY, MAY BE MADE OF THE SAME
 MATERIAL OF WHICH THE BUILDING OR
 STRUCTURE IS CONSTRUCTED.
 THE KEY WORDS "FIRE RESISTANCY" ARE
 THE FACTORS WE ARE CONCERNED WITH.THIS
 BUILDING IS A TYPE IV BUILDING DESIGNED
 UNDER THE SBC AT 110 MPH (FASTEST MILE).
 THE FIRE RESISTANCY WE SPEAK OF HAS BEEN
 IN CHAPTER 26 SINCE AT LEAST 1982.EFIS
 SYSTEMS ARE A COMBUSSTIBLE AND ARETO BE
 TESTED TO ASTM E 119. THEY ALSO NEED TO
 BE TESTED FOR COMPLIANCE FOR WIND. UNDER
 THE SBC YEAR 1982 TABLE 1205.1 FASTEST
 MILE PRESSURE WOULD BE - 40 FOR
 BUILDINGS 50-100'. THIS WOULD TRANSLATE
 TO THE CURRENT CODE 140 MILES PER HR AND
 THE -36.7 FOR 100" EFFECTIVE WIND AREA.
  
 EITHER UNDER THE CODE THE BUILDING WAS
 DESIGNED OR CURRENT CODE, PRODUCT
 APPROVALS FOR FIRE RESISTANCY AS WELL AS
 WIND TABLE 1205.1 82 CODE OR 1606.2 B
 UNDER THE CURRENT 2001 FL B CODE WILL
 REQUIRE PRODUCT APPROVALS.
  
 THE FL COVERSHEET FOR THE STO EFIS
 SYSTEM IS REQUIRED BUT THE CONTRACTOR
 STILL HAS NOT SUBMITTED THE BACKUP
 REPORT. THE ARCHITECT EVEN SPECIFIES
 THAT STO HI-CM EFIS SYSTEM IS TO BE
 USED.THE CONTRACTOR IS TO SUPPLY (2)
 COPIES OF THE MIAMI-DADE REPORT. THIS
 REPORT INDICATES WHAT PRESSURES IT IS
 DESIGNED FOR.
  
 2) COMMENT # 2 FROM THE PREVIOUS
 REVIEW. DEALS WITH THE PRE-MANUFACTURED
 ATTENDANT BOOTH, THIS STRUCTURE IS
 COVERED A MANUFACTURED BUILDING COVERED
 UNDER DEPARTMENT OF COMMUNITY AFFAIRS.
 THESE ARE STATE APPROVED PLANS, PROVIDE
 COPIES OF THESE PLANS INDICATING THAT IT
 COMPLIES WITH 140 MPH WIND ZONE.RULE
 9B-1 MANUFACTUREED BUILDINGS, FL S S 553
 PART (1).PROVIDE THE 14 SHEETS THAT ARE
 A PART OF THE STATE APPROVED PLANS.
 PAGE 8 WILL SHOW THE ATTACHMENT DETAILS
 TO THE FOUNDATION (SLAB).
  
 3)NOTE!!! THIS IS A COMMENT THAT DEALS
 WITH THE ATTENDANTS BOOTH, THE BOOTH
 DOES HAVE TO BE HANDICAPPED ACCESSIBLE
 PROVIDE DETAILS INDICATING ACCESSIBILITY
 INTO THE BOOTH.STATE PLANS SHOULD SHOW
 RAMPAGE TO BOOTH.ACCESSIBILE ROUTE TO
 ALTERED AREAS.
 HIGHLIGHT WHICH TYPE OF BOOTH TO BE
 USED, SIDE ENTRANCE OR REAR ENTRANCE FOR
  
 ACCESSIBILTY.
  
 11-4.1.6(2) DUTY TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO
 ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20 % OF
 THE COST OF THE ALTERA- TION TO THE
 PRIMARY FUNCTION AREA.(A)(I) AN
 ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-10 Cont ID  
Sent By jwitmer Date 2005-06-10 Time 13:41 Rev Time 1.11
Received By jwitmer Date 2005-06-10 Time 13:41 Sent To Z
Notes
2005-06-10 00:00:00BUILDING PLAN REVIEW
 PERMIT:04120431
 ADD: 333 EVERNIA
 CONT: SCHNELL CONSTRUCTION
 TEL: (941)321-1915
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
  
 1) QUESTION # 5 FROM THE PREVIOUS REVIEW
 ASK FOR THE MINIMUM BUILDING TYPE?
 YOUR ANSWER CITES 3401.8.2WHICH DEALS
 WITH REPAIRS TO BUILDINGS WITHIN THE
 HIGH VELOCITY HURRICANE ZONE. THIS CODE
 SECTION IS TO BE USED ONLY FOR DADE AND
 BROWARD COUNTY.
 THE CORRECT SECTION THAT YOU SHOULD
 HAVE CITED IS:
 3401.7.2.3 NON-STRUCTURAL REPAIRS AND
 ALTERATIONS EXCLUSIVE OF FIXTURES AND
 FURNITURE, THE COST OF WHICH DOES NOT
 EXCEED 25 PERCENT OF THE VALUE OF THE
 EXISTING BUILDING OR STRUCTURE AND WHICH
 DO NOT AFFECT EGRESS OR FIRE
 RESISTIVITY, MAY BE MADE OF THE SAME
 MATERIAL OF WHICH THE BUILDING OR
 STRUCTURE IS CONSTRUCTED.
 THE KEY WORDS "FIRE RESISTANCY" ARE
 THE FACTORS WE ARE CONCERNED WITH.THIS
 BUILDING IS A TYPE IV BUILDING DESIGNED
 UNDER THE SBC AT 110 MPH (FASTEST MILE).
 THE FIRE RESISTANCY WE SPEAK OF HAS BEEN
 IN CHAPTER 26 SINCE AT LEAST 1982.EFIS
 SYSTEMS ARE A COMBUSSTIBLE AND ARETO BE
 TESTED TO ASTM E 119. THEY ALSO NEED TO
 BE TESTED FOR COMPLIANCE FOR WIND. UNDER
 THE SBC YEAR 1982 TABLE 1205.1 FASTEST
 MILE PRESSURE WOULD BE - 40 FOR
 BUILDINGS 50-100'. THIS WOULD TRANSLATE
 TO THE CURRENT CODE 140 MILES PER HR AND
 THE -36.7 FOR 100" EFFECTIVE WIND AREA.
  
 EITHER UNDER THE CODE THE BUILDING WAS
 DESIGNED OR CURRENT CODE, PRODUCT
 APPROVALS FOR FIRE RESISTANCY AS WELL AS
 WIND TABLE 1205.1 82 CODE OR 1606.2 B
 UNDER THE CURRENT 2001 FL B CODE WILL
 REQUIRE PRODUCT APPROVALS.
  
 2) COMMENT # 10 FROM THE PREVIOUS
 REVIEW. DEALS WITH THE PRE-MANUFACTURED
 ATTENDANT BOOTH, THIS STRUCTURE IS
 COVERED A MANUFACTURED BUILDING COVERED
 UNDER DEPARTMENT OF COMMUNITY AFFAIRS.
 THESE ARE STATE APPROVED PLANS, PROVIDE
 COPIES OF THESE PLANS INDICATING THAT IT
 COMPLIES WITH 140 MPH WIND ZONE.RULE
 9B-1 MANUFACTUREED BUILDINGS, FL S S 553
 PART (1).
  
 3)NOTE!!! THIS IS A COMMENT THAT DEALS
 WITH THE ATTENDANTS BOOTH, THE BOOTH
 DOES HAVE TO BE HANDICAPPED ACCESSIBLE
 PROVIDE DETAILS INDICATING ACCESSIBILITY
 INTO THE BOOTH.STATE PLANS SHOULD SHOW
 RAMPAGE TO BOOTH.ACCESSIBILE ROUTE TO
 ALTERED AREAS. 11-4.1.6(2) DUTY TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO
 ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20 % OF
 THE COST OF THE ALTERA- TION TO THE
 PRIMARY FUNCTION AREA.(A)(I) AN
 ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-13 Cont ID  
Sent By jwitmer Date 2004-12-13 Time 13:01 Rev Time 1.11
Received By jwitmer Date 2004-12-13 Time 13:00 Sent To  
Notes
2004-12-13 00:00:00BUILDING PLAN REVIEW
 PERMIT:04120431
 ADD: 333 EVERNIA
 CONT: SCHNELL CONSTRUCTION
 TEL: (941)321-1915
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 1)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 2)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 3) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CON- TAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4) FIRE DISTRICT THERE SHALL BE NO TYPE
 VI CONSTRUCTION IN THE FIRE DISTRICT.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE THE MINIMUM BLDG DESIGN?
  
 6) INDICATE CODE COMPLIANCE WITH 2603.6
 EFIS SYSTEMS?
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EFIS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8) PROVIDE POSITIVE & NEGATIVE
 PRESSURE ZONES FOR BUILDING, 1606.2B>
  
  
 9) FL. BLD CODE 1606.1.7 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 10) THE PRE-MANUFACTURED ATTENDANT BOOTH
 IS COSIDERED A MANUFACTURED BLDG,
 PROVIDE STATE APPROVED PLANS THROUGH THE
  
 DEPARTMENT OF COMMUNITY AFFAIRS LISTING
 THIS BLDG FOR 140 MPH WIND ZONE, 3
 SECOND GUST.
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-06-16 Cont ID  
Sent By dpalmer Date 2006-06-16 Time 07:28 Rev Time 0.00
Received By dpalmer Date 2006-06-16 Time 07:23 Sent To PC
Notes
2006-06-16 00:00:00********** UNSAT ***********
  
  
 1) NOTE: PLEASE ONLY SUBMIT PLANS WHICH
 ARE SIGNED, DATED AND SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD.
 PLEASE SEE PLANS SUBMITTED ARE INDEED
 PHOTO-COPIES OF ORIGINAL PLANS.
 PLEASE ALSO KNOW, GLUED OR TAPED ON
 SHEETS ON PLANS ARE ALSO NOT PERMITTED.
 PLEASE SEE FAC 61G15-23.002, FS 471.025
 FBC ADMIN SEC 106.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 11:25 Rev Time 0.30
Received By dpalmer Date 2005-09-10 Time 11:15 Sent To  
Notes
2005-09-10 00:00:00STAMPED 2ND AND 3RD SET OF SUBMITTIALS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 20:07 Rev Time 0.80
Received By dpalmer Date 2005-09-03 Time 19:15 Sent To  
Notes
2005-09-03 00:00:00****** NOTE****
  
 ONLY ONE SET OF GENERATOR AND ATS SPECS
 WERE SUBMITTED, CALLED CONTRACTOR FOR
 2ND SET.
  
 REDLINED PLANS FOR 620.23,620.24 AS
 NOTED BY ENGINEER.
  
 REDLINED PLANS, THE MAIN ELECTRICAL RM
 WILL BE REQUIRED TO HAVE AN EMERGENCY LT
 W/ BATTERY BACK UP POWER.
 700.16,LS 101 7-9

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-09 Cont ID  
Sent By dpalmer Date 2005-06-09 Time 12:59 Rev Time 2.00
Received By dpalmer Date 2005-06-09 Time 12:59 Sent To FIRE
Notes
2005-06-09 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION ON TITLE BLOCK FOR ARCH
 FIRM. PER FAC 61G1-16.004, FS 481.219.
 PLEASE ALSO SEE MISSING INFORMATION
 REQUIRED ON ELECTRICAL ENGINEERING TITLE
 BLOCK PER FAC 61G15-23.002, FS 471.023
 PLEASE SEE THIS INFORMATION IS REQUIRED
 ON ALL SHEETS AND FOR ALL TRADES
 WHEATHER OR NOT COMMENTS IS MADE BY
 OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE PANEL EM IS REQUIRED
 TO HAVE A MCB AND SHALL BE LABELED WITH
 THE PROPER SIGNAGE AS REQUIRED UNDER
 702.8
 PLEASE SEE MCB REQUIRED PER
 225.31-225.36.
  
 3)NOTE: PLEASE PROVIDE ALL MANUFACTURE
 SPECS/CUT SHEETS FOR GENERATOR, AT,
 STATUS PANEL.
 PLEASE ALSO PROVIDE PRIME MOVER
 INFORMATION. IF ANY KIND OF FUEL TANK
 SYSTEM IS TO BE INSTALLED, THEN SPECS
 FOR FUELSTORAGE MUST ALSO BE SUBMITTED
 FOR REVIEW BY FIRE/MECH.
 PLEASE SEE ALL EQUIPMENT/DISC/ATS ETC
 MUST MEET 225.36 .
  
 4)NOTE: PLEASE CALRIFY SIZE OF OCP , AWG
 FOR LIGHTING CIRCUIT INDICATED AS
 1P-30A'S-1P40A BRKRS???
 PLEASE SHOW CONDUCTOR SIZES.
 240.4,310.16 ETC.
  
 5)NOTE: PLEASE PROVIDE INFORMATION ON
 WHEATHER THERE IS NEW OR EXSITNG
 MEETING:
 *620.23 A SEPARATE BRANCH CIRCUIT SHALL
 SUPPLY THE MACHINE ROOM OR CONTROL
 ROOM/MACHINERY SPACE OR CONTROL SPACE
 LIGHTING AND RECEPTACLE(S).
  
 *620.24,A SEPARATE BRANCH CIRCUIT SHALL
 SUPPLY THE HOISTWAY PIT LIGHTING AND
 RECEPTACLE(S).
 REQUIRED LIGHTING SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF A GROUND-FAULT
 CIRCUIT INTERRUPTER.THE LIGHTING SWITCH
 SHALL BE LOCATED SO AS TO BE READILY
 ACCESSIBLE FROM THE PIT ACCESS DOOR.
 AT LEAST ONE 125-VOLT, SINGLE-PHASE,
 DUPLEX RECEPTACLE SHALL BE PROVIDED IN
 THE HOISTWAY PIT.
  
 *700.16, PLEASE PROVIDE INFORMATION ON
 FIXTURE TYPE.EMERGENCY ILLUMINATION
 SHALL INCLUDE ALL REQUIRED MEANS OF
 EGRESS LIGHTING, ILLUMINATED EXIT SIGNS,
 AND ALL OTHER LIGHTS SPECIFIED AS
 NECESSARY TO PROVIDE REQUIRED
 ILLUMINATION.
 EMERGENCY LIGHTING SYSTEMS SHALL BE
 DESIGNED AND INSTALLED SO THAT THE
 FAILURE OF ANY INDIVIDUAL LIGHTING
 ELEMENT, SUCH AS THE BURNING OUT OF A
 LIGHT BULB, CANNOT LEAVE IN TOTAL
 DARKNESS ANY SPACE THAT REQUIRES
 EMERGENCY ILLUMINATION.
 WHERE HIGH-INTENSITY DISCHARGE LIGHTING
 SUCH AS HIGH- AND LOW-PRESSURE SODIUM,
 MERCURY VAPOR, AND METAL HALIDE IS USED
 AS THE SOLE SOURCE OF NORMAL
 ILLUMINATION, THE EMERGENCY LIGHTING
 SYSTEM SHALL BE REQUIRED TO OPERATE
 UNTIL NORMAL ILLUMINATION HAS BEEN
 RESTORED.
 * 700.12E THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.THE BRANCH CIRCUIT
 THAT FEEDS UNIT EQUIPMENT SHALL BE
 CLEARLY IDENTIFIED AT THE DISTRIBUTION
 PANEL.
  
 6)NOTE:PLEASE PROVIDE GROUNDING
 ELECTRODE CONDUCTOR SIZES PER 250.66
 NO SIZES ARE SHOWN.
  
 7)NOTE: PLEASE SEE THERE ARE MANY NOTES
 ON "RISER DIAGRAM NOTES" WHICH MENTION
 TO SEE GROUNDING DETAIL, HOWEVER PLEASE
 SEE PREVIOUS COMMENT AND PLEASE SEE FBC
 104.2.1, WHICH STATES THE CODE SHALL NOT
 BE QUOTED IN WHOLE OR IN-PART.
 PLEASE SEE NOTE #19 WHICH REFERENCES TO
 SEE GROUNDING ELECTRODE DETAIL ON SMAE
 SHEET, YET THIS CONNECTION IS NOT SHOWN.
 PLEASE VERIFY IF INDEED THIS CONNECTION
 IS BEING MADE. IS THIS SYSTEM A
 NON-SEPARATELY DERIVED SYSTEM? OR
 SEPARATELY DERIVED? 250.30 ETC.
  
 8)NOTE: PLEASE SEE NOTE#8,PLEASE PROVIDE
 MORE INFORMATION ON SIZE OF TRANSFORMER
 IN ORDER TO VERIFY OCP PROVIDED. THIS
 SHALL MEET 125% MAX PER 450.3
  
 9)NOTE: PLEASE SEE NOTE #16, #17
 MENTIONS TO PROVIDE NEW , HOWEVER RISER
 SHOWS EXISTING IN LT GRAY?
  
 10)NOTE: PLEASE SEE TWO DIFFERENT
 VOLTAGES ON PLANS SHOWN. PANEL "C" IS
 SHOWN AS 120/208V AND "EM AS 120/240V?
 PLEASE SEE IT APPEARS EXISTING LIGHTING
 IS FED FROM A DIFFERENT VOLTAGE THEN IS
 PROPOSED. ??
  
 11)NOTE: PLEASE VERIFY MSB AS BEING A
 FUSED DP, WITH FUSES FOR EACH SUB PANEL
 FEED.
  
 12)NOTE: PLEASE SEE SHEET E-1, WHICH
 NOTES FOR TOWER ELEVATOR RMS #1&2 TO SEE
 ENLARGED DEATIL ON SHEET E-2, HOWEVER NO
 SHEET E-2 WAS SUBMITTED FOR REVIEW?
 PLEASE CORRELATE THIS COMMENT WITH
 PREVIOUS NOTE #5.
 PLEASE ALSO SEE SHEET E-1 MENTIONS TO
 SEE TOLLBOOTH DETAIL ON E-2, YET NO E-2
 PROVIDED.
  
 13)NOTE: PLEASE SEE TRANSFORMER TO BE
 INSTALLED IN EXSITING ELECTRICAL ROOM IS
 NOTED AS TO MEET CLEARENCE PER NEC.
 HOWEVER, PLEASE SEE AS PER PLANS,
 CLEARENCE AMY NOT BE ABLE TO BE MET PER
 110.26. IF TRANSFORMER IS TO
 CEILING/WALL MOUNTED, THEN PLEASE
 PROVIDE DETAIL FOR STRCUTUAL REVIEW.
 215.5
  
 14)NOTE: PLEASE PROVIDE INFORMATION/
 SIZE OF OCP AT GEN FOR FEED COMING INTO
 BLDG. PLEASE SEE DISC SHOWN MENTIONS NF.
 PLEASE SEE 310.16,240.4.
 IF GEN HAS BUILT IN BRKR/OCP, PLEASE
 PROVIDE THIS INFORMATION ON PLANS. THIS
 SHOULD ALSO BE ON SPECS.(PREVIOUS NOTE).
  
 PLEASE SEEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-10 Cont ID  
Sent By jleahy Date 2004-12-10 Time 14:29 Rev Time 1.00
Received By jleahy Date 2004-12-10 Time 14:27 Sent To  
Notes
2004-12-10 00:00:00NEED A DISCONNECT OUT AT GENERATOR PER
 225.31 BEFORE IT PASSES THROUGH THE
 BUILDING.DISCONNECT TO BE READILY
 ACCESSIBLE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-09-12 Cont ID  
Sent By mcarsill Date 2005-09-12 Time 11:21 Rev Time 0.00
Received By mcarsill Date 2005-09-12 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-06-10 Cont ID  
Sent By mwennerg Date 2005-06-10 Time 09:26 Rev Time 0.00
Received By mwennerg Date 2005-06-10 Time 09:23 Sent To  
Notes
2005-06-10 00:00:00****DENIED****
  
 1) PLEASE NOTE THAT COMMENTS FROM THE
 PREVIOUS FIRE REVIEW HAVE NOT BEEN
 ADDRESSED. IN ADDITION TO THIS REVIEW,
 PLEASE INCLUDE YOUR RESPONSES FROM THE
 FIRST REVIEW.
  
 2) PLEASE SUBMIT FURTHER INFORMATION AND
 LOCATIONS OF ALL NEW OR EXISTING
 EMERGENCY LIGHT FACILITIES AND
 ILLUMINATED EXIT SIGNS.
  
 3) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 4) PLEASE SUBMIT CUT SHEETS AND
 PERTINENT INFORMATION IN REGARDS TO THE
 GENERATOR AND ASSOCIATED FUEL AND
 STORAGE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By mcarsill Date 2004-12-15 Time 08:04 Rev Time 0.00
Received By mcarsill Date 2004-12-15 Time 08:04 Sent To  
Notes
2004-12-15 00:00:001. EMERGENCY LIGHTING AND ILLUMINATED
 EXIT SIGNS SHALL COMPLY WITH
 CHAPTER SEVEN, MEANS OF EGRESS,
 LIFE SAFETY CODE, 2000 EDITION.
  
 2. NO PENETRATIONS ALLOWED WITHIN
 ANY EXIT STAIRS. TOWER # 2 PARTIAL
 GROUND LEVEL FLOOR PLAN.
  
 3. PARKING GARAGE TO COMPLY WITH
 NFPA 88A.
  
 4. REPAIRS FOR CRACKS NEAR STAIRTOWERS
 SHALL NOT INTERFERE WITH ANY ABILITY
 TO EXIT.
  
 5. NO PRODUCT INFORMATION REGARDING
 THE PROPOSED GENERATOR.
  
 6. ANY ROOMS OPENING DIRECTLY
 ONTO EXIT STAIRTOWERS ARE TO BE
 PROPERLY RATED.
  
 7. WILL THE EXISTING FIRE PUMP
 BE CONNECTED TO THE NEW PROPOSED
 GENERATOR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 09:15 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 09:11 Sent To E
Notes
2006-06-14 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 11:24 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 11:24 Sent To Z
Notes
2006-06-07 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 11:09 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 11:09 Sent To  
Notes
2005-09-02 00:00:00TO "COMM" BD#46

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-02 Cont ID  
Sent By adarroug Date 2005-06-02 Time 17:09 Rev Time 0.00
Received By adarroug Date 2005-06-02 Time 17:09 Sent To  
Notes
2005-06-08 00:00:00ROUTED TO K STEVENS DESK
  
  
  
2005-06-02 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-08 Cont ID  
Sent By rbrown Date 2004-12-15 Time 09:49 Rev Time 0.00
Received By rbrown Date 2004-12-09 Time 08:15 Sent To  
Notes
2004-12-09 00:00:00SENT TO COMM BD#14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-14 Cont ID  
Sent By pkrauss Date 2005-09-13 Time 16:19 Rev Time 0.55
Received By pkrauss Date 2005-09-13 Time 16:19 Sent To  
Notes
2005-09-13 00:00:00PROVISO:
 PLEASE NOTE, A PERMANENT MEANS OF ACCESS
 WILL BE REQUIRED FOR CU-1 & CU-2 SHOULD
 THE ACCESS BE GREATER THAN 16 FT ABOVE
 GRADE - 2001 FBC(M) 306.5
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2004-12-15 Time   Rev Time  
Received By   Date 2004-12-15 Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-10 Cont ID  
Sent By kstevens Date 2005-09-10 Time 11:02 Rev Time 0.51
Received By kstevens Date 2005-09-10 Time 11:02 Sent To  
Notes
2005-09-10 00:00:00IRRIGATION PERMIT REQUIRED
 GAS PERMIT/PLANS REQUIRED

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-08 Cont ID  
Sent By kstevens Date 2005-06-08 Time 16:54 Rev Time 0.33
Received By kstevens Date 2005-06-08 Time 16:54 Sent To B
Notes
2005-06-08 00:00:00IRRIGATION PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-11 Cont ID  
Sent By kstevens Date 2004-12-11 Time 17:04 Rev Time 0.50
Received By kstevens Date 2004-12-11 Time 17:04 Sent To  
Notes
2004-12-11 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE\
 FLORIDA STATUTES
  
  
 1) SHT P-1 ENGINEER SHALL SIGN HIS NAME
 PER FAC 61G15-23.002(1) & FS 471.025.
 PER FBPE'S RULING A MINIMUM FIRST AND
 LAST NAME SHALL BE AFFIXED TO THE SEAL.
 INITIALS ARE NOT ACCEPTABLE. SUBMIT
 PROOF OF LEGAL SIGNATURE, IN THE FORM OF
 A DRIVERS LICENSE, VOTERS REGISTRATION
 OR SIMILAR LEGAL ID FOR SIGNATURE
 VERIFICATION. A NOTORIZED, SIGNED,
 SEALED, LETTER SHOWING LEGAL SIGNATURE
 FOR OUR FILES.
 2) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME ON THE TITLE BLOCK. FAC
 61G15-23.002(2)
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2006-06-12 Cont ID  
Sent By astelly Date 2006-06-12 Time 14:45 Rev Time 0.00
Received By astelly Date 2006-06-12 Time 14:50 Sent To  
Notes
2006-06-12 00:00:00MECHANICAL EQUIPMENT MUST BE SCREENED.
  
 PLEASE PROVIDE STREET NAMES ON THE
 CURRENT PLAN OR PROVIDE A SITE PLAN
 SHOWING THE LOCATION OF THE EQUIPMENT.

Review Stop Z ZONING
Rev No 2 Status N Date 2005-09-21 Cont ID  
Sent By mmclean Date 2005-09-21 Time 14:37 Rev Time 0.00
Received By mmclean Date 2005-09-21 Time 14:37 Sent To  
Notes
2005-09-21 00:00:00REVIEWED BY MATTHEW FLIS, URBAN PLANNER
 822-1435

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-21 Cont ID  
Sent By aaponte Date 2005-06-21 Time 15:30 Rev Time 0.00
Received By aaponte Date 2005-06-21 Time 15:30 Sent To  
Notes
***NONE***