| 2005-06-09 00:00:00 | ************* UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE MISSING LICENSE |
| | INFORMATION ON TITLE BLOCK FOR ARCH |
| | FIRM. PER FAC 61G1-16.004, FS 481.219. |
| | PLEASE ALSO SEE MISSING INFORMATION |
| | REQUIRED ON ELECTRICAL ENGINEERING TITLE |
| | BLOCK PER FAC 61G15-23.002, FS 471.023 |
| | PLEASE SEE THIS INFORMATION IS REQUIRED |
| | ON ALL SHEETS AND FOR ALL TRADES |
| | WHEATHER OR NOT COMMENTS IS MADE BY |
| | OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SEE PANEL EM IS REQUIRED |
| | TO HAVE A MCB AND SHALL BE LABELED WITH |
| | THE PROPER SIGNAGE AS REQUIRED UNDER |
| | 702.8 |
| | PLEASE SEE MCB REQUIRED PER |
| | 225.31-225.36. |
| | |
| | 3)NOTE: PLEASE PROVIDE ALL MANUFACTURE |
| | SPECS/CUT SHEETS FOR GENERATOR, AT, |
| | STATUS PANEL. |
| | PLEASE ALSO PROVIDE PRIME MOVER |
| | INFORMATION. IF ANY KIND OF FUEL TANK |
| | SYSTEM IS TO BE INSTALLED, THEN SPECS |
| | FOR FUELSTORAGE MUST ALSO BE SUBMITTED |
| | FOR REVIEW BY FIRE/MECH. |
| | PLEASE SEE ALL EQUIPMENT/DISC/ATS ETC |
| | MUST MEET 225.36 . |
| | |
| | 4)NOTE: PLEASE CALRIFY SIZE OF OCP , AWG |
| | FOR LIGHTING CIRCUIT INDICATED AS |
| | 1P-30A'S-1P40A BRKRS??? |
| | PLEASE SHOW CONDUCTOR SIZES. |
| | 240.4,310.16 ETC. |
| | |
| | 5)NOTE: PLEASE PROVIDE INFORMATION ON |
| | WHEATHER THERE IS NEW OR EXSITNG |
| | MEETING: |
| | *620.23 A SEPARATE BRANCH CIRCUIT SHALL |
| | SUPPLY THE MACHINE ROOM OR CONTROL |
| | ROOM/MACHINERY SPACE OR CONTROL SPACE |
| | LIGHTING AND RECEPTACLE(S). |
| | |
| | *620.24,A SEPARATE BRANCH CIRCUIT SHALL |
| | SUPPLY THE HOISTWAY PIT LIGHTING AND |
| | RECEPTACLE(S). |
| | REQUIRED LIGHTING SHALL NOT BE CONNECTED |
| | TO THE LOAD SIDE OF A GROUND-FAULT |
| | CIRCUIT INTERRUPTER.THE LIGHTING SWITCH |
| | SHALL BE LOCATED SO AS TO BE READILY |
| | ACCESSIBLE FROM THE PIT ACCESS DOOR. |
| | AT LEAST ONE 125-VOLT, SINGLE-PHASE, |
| | DUPLEX RECEPTACLE SHALL BE PROVIDED IN |
| | THE HOISTWAY PIT. |
| | |
| | *700.16, PLEASE PROVIDE INFORMATION ON |
| | FIXTURE TYPE.EMERGENCY ILLUMINATION |
| | SHALL INCLUDE ALL REQUIRED MEANS OF |
| | EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, |
| | AND ALL OTHER LIGHTS SPECIFIED AS |
| | NECESSARY TO PROVIDE REQUIRED |
| | ILLUMINATION. |
| | EMERGENCY LIGHTING SYSTEMS SHALL BE |
| | DESIGNED AND INSTALLED SO THAT THE |
| | FAILURE OF ANY INDIVIDUAL LIGHTING |
| | ELEMENT, SUCH AS THE BURNING OUT OF A |
| | LIGHT BULB, CANNOT LEAVE IN TOTAL |
| | DARKNESS ANY SPACE THAT REQUIRES |
| | EMERGENCY ILLUMINATION. |
| | WHERE HIGH-INTENSITY DISCHARGE LIGHTING |
| | SUCH AS HIGH- AND LOW-PRESSURE SODIUM, |
| | MERCURY VAPOR, AND METAL HALIDE IS USED |
| | AS THE SOLE SOURCE OF NORMAL |
| | ILLUMINATION, THE EMERGENCY LIGHTING |
| | SYSTEM SHALL BE REQUIRED TO OPERATE |
| | UNTIL NORMAL ILLUMINATION HAS BEEN |
| | RESTORED. |
| | * 700.12E THE BRANCH CIRCUIT FEEDING THE |
| | UNIT EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES.THE BRANCH CIRCUIT |
| | THAT FEEDS UNIT EQUIPMENT SHALL BE |
| | CLEARLY IDENTIFIED AT THE DISTRIBUTION |
| | PANEL. |
| | |
| | 6)NOTE:PLEASE PROVIDE GROUNDING |
| | ELECTRODE CONDUCTOR SIZES PER 250.66 |
| | NO SIZES ARE SHOWN. |
| | |
| | 7)NOTE: PLEASE SEE THERE ARE MANY NOTES |
| | ON "RISER DIAGRAM NOTES" WHICH MENTION |
| | TO SEE GROUNDING DETAIL, HOWEVER PLEASE |
| | SEE PREVIOUS COMMENT AND PLEASE SEE FBC |
| | 104.2.1, WHICH STATES THE CODE SHALL NOT |
| | BE QUOTED IN WHOLE OR IN-PART. |
| | PLEASE SEE NOTE #19 WHICH REFERENCES TO |
| | SEE GROUNDING ELECTRODE DETAIL ON SMAE |
| | SHEET, YET THIS CONNECTION IS NOT SHOWN. |
| | PLEASE VERIFY IF INDEED THIS CONNECTION |
| | IS BEING MADE. IS THIS SYSTEM A |
| | NON-SEPARATELY DERIVED SYSTEM? OR |
| | SEPARATELY DERIVED? 250.30 ETC. |
| | |
| | 8)NOTE: PLEASE SEE NOTE#8,PLEASE PROVIDE |
| | MORE INFORMATION ON SIZE OF TRANSFORMER |
| | IN ORDER TO VERIFY OCP PROVIDED. THIS |
| | SHALL MEET 125% MAX PER 450.3 |
| | |
| | 9)NOTE: PLEASE SEE NOTE #16, #17 |
| | MENTIONS TO PROVIDE NEW , HOWEVER RISER |
| | SHOWS EXISTING IN LT GRAY? |
| | |
| | 10)NOTE: PLEASE SEE TWO DIFFERENT |
| | VOLTAGES ON PLANS SHOWN. PANEL "C" IS |
| | SHOWN AS 120/208V AND "EM AS 120/240V? |
| | PLEASE SEE IT APPEARS EXISTING LIGHTING |
| | IS FED FROM A DIFFERENT VOLTAGE THEN IS |
| | PROPOSED. ?? |
| | |
| | 11)NOTE: PLEASE VERIFY MSB AS BEING A |
| | FUSED DP, WITH FUSES FOR EACH SUB PANEL |
| | FEED. |
| | |
| | 12)NOTE: PLEASE SEE SHEET E-1, WHICH |
| | NOTES FOR TOWER ELEVATOR RMS #1&2 TO SEE |
| | ENLARGED DEATIL ON SHEET E-2, HOWEVER NO |
| | SHEET E-2 WAS SUBMITTED FOR REVIEW? |
| | PLEASE CORRELATE THIS COMMENT WITH |
| | PREVIOUS NOTE #5. |
| | PLEASE ALSO SEE SHEET E-1 MENTIONS TO |
| | SEE TOLLBOOTH DETAIL ON E-2, YET NO E-2 |
| | PROVIDED. |
| | |
| | 13)NOTE: PLEASE SEE TRANSFORMER TO BE |
| | INSTALLED IN EXSITING ELECTRICAL ROOM IS |
| | NOTED AS TO MEET CLEARENCE PER NEC. |
| | HOWEVER, PLEASE SEE AS PER PLANS, |
| | CLEARENCE AMY NOT BE ABLE TO BE MET PER |
| | 110.26. IF TRANSFORMER IS TO |
| | CEILING/WALL MOUNTED, THEN PLEASE |
| | PROVIDE DETAIL FOR STRCUTUAL REVIEW. |
| | 215.5 |
| | |
| | 14)NOTE: PLEASE PROVIDE INFORMATION/ |
| | SIZE OF OCP AT GEN FOR FEED COMING INTO |
| | BLDG. PLEASE SEE DISC SHOWN MENTIONS NF. |
| | PLEASE SEE 310.16,240.4. |
| | IF GEN HAS BUILT IN BRKR/OCP, PLEASE |
| | PROVIDE THIS INFORMATION ON PLANS. THIS |
| | SHOULD ALSO BE ON SPECS.(PREVIOUS NOTE). |
| | |
| | PLEASE SEEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |