Plan Review Details - Permit 04120363
Plan Review Stops For Permit 04120363
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-31 Cont ID  
Sent By jgomez Date 2005-03-31 Time 10:49 Rev Time 0.33
Received By jgomez Date 2005-03-31 Time 10:48 Sent To PC
Notes
2005-03-31 00:00:00PROVISO ITEMS SUBMITTED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-09 Cont ID  
Sent By jgomez Date 2005-02-09 Time 16:54 Rev Time 2.00
Received By jgomez Date 2005-02-09 Time 16:54 Sent To  
Notes
2005-02-09 00:00:00BUILDING REVIEW PROVISO (PROVIDE THE
 FOLLOWING INFORMATION PRIOR TO
 CONSTRUCTION TO AVOID
 DELAYS/CONFLICTS):
 1-REVISE GARAGE BAY WINDOW DETAIL AND
 ROOF FRAMING PLAN TO MATCH:
 A)BEAM TYPE. WOOD OR MASONRY.
 B)CONNECTORS REQUIRED. WOOD TO WOOD OR
 WOOD TO MASONRY AS REQUIRED.
 C)SPECIFY ALL DIMENSIONS.
 D)SPECIFY ALL FASTENERS.
 E)ROOF FRAMING PLAN TO MATCH TRUSSES
 LAYOUT AS SHOWN ON DETAIL.
 F)SPECIFY STUCCO THICKNESS & SUPPORTS.
 SEE ASTM C926 & C1063. SEC. 2504.2
 FBC 2001.
  
 2-SHOW CHIMNEY HEIGHT WITH MIN. HEIGHT
 REQUIRED TO COMPLY WITH SECTION
 2804.2.4 FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-20 Cont ID  
Sent By jgomez Date 2004-12-20 Time 16:09 Rev Time 2.50
Received By jgomez Date 2004-12-20 Time 15:10 Sent To  
Notes
2004-12-20 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2-PROVIDE COMPLETE WALL SECTION THRU
 GARAGE BAY WINDOW. SPECIFY ALL
 FASTENERS. SECTION 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
  
 3-REVISE ROOF SHEATHING NOTE ON SHEET
 A3. ROOF ZONE 3 IS NOT ONLY AT 4
 CORNERS
 BUT AT ALL ROOF CORNERS. SEE FIGURE
 1606.2(C) FBC 2001.
  
 4-REVISE ATTIC LIVE LOAD SPECIFIED ON
 ROOF LOADS TABLE ON SHEET A3. SEE TABLE
 1604.1 FBC 2001.
  
 5-PROVIDE ONLY THE DETAILS THAT APPLY
 TO
 THIS JOB TO EXPEDITE REVIEW PROCESS.
  
 6-ROOF FRAMING PLAN AND ELEVATIONS
 DON'T
 SHOW THE CHIMNEY. REVISE AS REQUIRED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 7-VERIFY THAT CHIMNEY UL LISTING AND
 SPECS ALLOW FLUE CAP TO HAVE ROOF ABOVE
 FOR PROPER FIREPLACE VENTILATION. THEN,
 REVISE DETAIL AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 8-PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL
 FOR (2 COPIES):
 A) ENTRY DOORS AS SHOWN ON PLANS.
 B) COMPLETE UL LISTING AND SPECS FOR
 FIREPLACE.
  
 9-AREA CALCULATIONS ON SHEET A1 DON'T
 ADD UP. REVISE AS REQUIRED. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 10-OWES #2032.65 FOR LOW VALUATION AND
 RADON FEES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-09 Cont ID  
Sent By btrobaug Date 2005-11-09 Time 06:20 Rev Time 0.50
Received By btrobaug Date 2005-11-09 Time 06:20 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-02-10 Cont ID  
Sent By btrobaug Date 2005-02-10 Time 09:50 Rev Time 0.00
Received By btrobaug Date 2005-11-09 Time 06:08 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-12-15 Cont ID  
Sent By btrobaug Date 2004-12-15 Time 13:31 Rev Time 0.50
Received By btrobaug Date 2004-12-15 Time 10:45 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-08 Cont ID  
Sent By adarroug Date 2005-11-08 Time 08:51 Rev Time 0.00
Received By adarroug Date 2005-11-08 Time 08:51 Sent To E
Notes
2005-11-08 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 11:09 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 11:09 Sent To B
Notes
2005-03-10 00:00:00TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-07 Cont ID  
Sent By adarroug Date 2005-02-07 Time 09:31 Rev Time 0.00
Received By adarroug Date 2005-02-07 Time 09:31 Sent To B
Notes
2005-02-07 00:00:00TO IGOMEZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-15 Cont ID  
Sent By mjacobs Date 2004-12-15 Time 08:13 Rev Time 0.00
Received By mjacobs Date 2004-12-15 Time 08:13 Sent To  
Notes
2004-12-15 00:00:00SENT TO "SF RACK"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-07 Cont ID  
Sent By mjacobs Date 2004-12-07 Time 16:08 Rev Time 0.00
Received By mjacobs Date 2004-12-07 Time 16:08 Sent To Z
Notes
2004-12-07 00:00:00SENT TO "Z" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-12-16 Cont ID  
Sent By pkrauss Date 2004-12-16 Time 06:55 Rev Time 0.35
Received By pkrauss Date 2004-12-16 Time 06:43 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-12-18 Cont ID  
Sent By jleech Date 2004-12-18 Time 10:37 Rev Time 33.00
Received By jleech Date 2004-12-18 Time 10:37 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-12-14 Cont ID  
Sent By mmclean Date 2004-12-14 Time 17:17 Rev Time 0.00
Received By mmclean Date 2004-12-14 Time 17:17 Sent To I
Notes
2004-12-14 00:00:00MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK/SCREEN ENCLOSURE.