Plan Review Details - Permit 04120353
Plan Review Stops For Permit 04120353
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-10-02 Cont ID  
Sent By lursu Date 2006-10-02 Time 12:44 Rev Time 0.00
Received By hmoser Date 2008-01-24 Time 18:10 Sent To  
Notes
2006-10-02 00:00:00ADDRESS MATCHES THE PCN

Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-03-29 Cont ID  
Sent By jhiggins Date 2006-03-29 Time 08:02 Rev Time 0.00
Received By   Date 2008-02-15 Time 09:39 Sent To  
Notes
2004-12-13 00:00:00PCN CORRECTED TO: 74434322140050010

Review Stop B BUILDING (STRUCTURAL)
Rev No 384 Status N Date 2008-08-07 Cont ID  
Sent By mjacobs Date 2008-08-01 Time 08:15 Rev Time 0.00
Received By mjacobs Date 2008-08-01 Time 08:15 Sent To FIRE
Notes
2008-08-07 08:17:49THE RESIDENT EMERGENCY PROCEDURE EVACUATION PLAN
 SUBMITTAL WAS SENT TO FIRE. MJ

Review Stop B BUILDING (STRUCTURAL)
Rev No 383 Status P Date 2008-05-30 Cont ID  
Sent By mjacobs Date 2008-05-30 Time 11:34 Rev Time 0.00
Received By mjacobs Date 2008-05-30 Time 10:40 Sent To PC
Notes
2008-05-30 13:35:07FBC 2001
 SUBMITAL #08810.06 DOOR AT STEAM ROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 382 Status P Date 2008-05-16 Cont ID  
Sent By mjacobs Date 2008-05-16 Time 10:40 Rev Time 0.00
Received By mjacobs Date 2008-05-16 Time 10:24 Sent To PC
Notes
2008-05-16 10:40:39SUBMITTAL #05500.07 GARAGE PIPE PROTECTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 381 Status N Date 2008-04-30 Cont ID  
Sent By mjacobs Date 2008-04-30 Time 11:08 Rev Time 0.00
Received By mjacobs Date 2008-04-30 Time 11:08 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 380 Status F Date 2008-02-15 Cont ID  
Sent By mjacobs Date 2008-02-15 Time 13:51 Rev Time 0.00
Received By mjacobs Date 2008-02-15 Time 09:40 Sent To PC
Notes
2008-02-15 13:51:54BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S. OLIVE AVE
 CONT: KAST CONST.
 TEL: (561)329-9396
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 2-15-08
 ACTION: DENIED
 FBC 2001 SUBMITTAL #05100.02 TRUSS DETAIL
 CONNECTIONS.
  
 1) THE REPORT SUBMITTED REFERS TO FBC 2004 WITH THE
 2006 SUPPLEMENT. THE WIND SPEED INDICATED ON THE
 SUBMITTAL IS 130MPH (ASCE 7-02 CLOSED). **NOTE** THIS
 PROJECT HAS A PERMIT WHICH WAS ISSUED UNDER THE FBC
 2001 EDITION. THE WIND SPEED PER FBC 2001 TABLE
 1606.1.6.1 IS 140MPH 3SEC GUST (ASCE 7-98) SEE SECTION
 1606.1.1 FOR THE INFORMATION RELATED TO WIND. ALL
 CALCULATION AND SPECIFICATIONS SHALL BE IN ACCORDANCE
 WITH THE FBC 2001.
  
 2)FAC 61G15-23.002A PROFESSIONAL ENGINEER MAY ONLY
 SEALAN ENGINEERING REPORT, PLAN, PRINT OR
 SPECIFICATION IF THAT PROFESSIONAL ENGINEER WAS IN
 RESPONSIBLE CHARGE OF THE PREPARATION AND PRODUCTION OF
 THE ENGINEERING DOCUMENT AND THE PROFESSIONAL ENGINEER
 HAS THE EXPERTISE IN THE ENGINEERING DISCIPLINE USED IN
 PRODUCTION THE ENGINEERING DOCUMENT IN QUESTION.THE
 TRUSS DESIGN ENGINEER IS SCOTT L. SCHURWAN, HIS LICENSE
 NUMBER IS 31867. THE ENGINEER WHO SEALS THE TRUSS
 REPORTS IS RAJAN SOWRI HIS LICENSE NUMBER IS 52083.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. IF PRACTICING THROUGH
 A DULY AUTHORIZE ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. A
 TITLE BLOCK SHALL APPEAR ON EACH SHEET CONTAINING THE
 PRINTED NAME, ADDRESS, AND LICENSE NUMBER OF THE
 ENGINEER.
  
 3)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 379 Status P Date 2008-02-13 Cont ID  
Sent By rbrown Date 2008-02-13 Time 19:22 Rev Time 0.00
Received By rbrown Date 2008-02-13 Time 19:22 Sent To  
Notes
2008-02-13 19:26:43SUBMITTAL ON 1/29/08 FOR KOLTER LETTER ON EIFS
 ATTACHMENT ADHESIVE SUPPORTED BY DOW CHEMICALS COMPANY
 ENGINEER'S LETTER COMPARING MAXIMUM USE TEMPERATURE
 RATING OF THE ADHESIVE AND THE EIFS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 378 Status F Date 2008-02-01 Cont ID  
Sent By mjacobs Date 2008-02-01 Time 16:09 Rev Time 0.00
Received By mjacobs Date 2008-02-01 Time 10:17 Sent To PC
Notes
2008-02-01 16:07:25REVIEW: FBC 2001SUBMITTAL #05100.01
 ACTION: DENIED 2-1-08
  
 1) 106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS THAT
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. SUBMIT PRODUCT
 APPROVAL FOR THE ?HARDISOFFIT?. IN THE PRODUCT APPROVAL
 PACKAGE CIRCLE ALL ITEMS AND TABLES APPLICABLE TO THE
 INSTALLATION OF THE PRODUCT.
  
 2) PROVIDE THE FASTENER SPACING WHICH WILL MEET THE
 DESIGN PRESSURES FOR THOSE AREAS WHERE THE
 ?HARDISOFFIT? WILL BE INSTALLED. ALL INFORMATION
 SUBMITTED FOR OUR RECORD RETENTION PROGRAM SHALL BE
 CLEAR, LEGIBLE AND NO ?WHITE-OUT? CHANGES ALLOWED. THE
 INFORMATION FOR THE ?HARDISOFFIT? IS ILLEGIBLE WPB
 AMENDMENTS 106.1.3.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 377 Status F Date 2008-02-01 Cont ID  
Sent By mjacobs Date 2008-02-01 Time 08:43 Rev Time 0.00
Received By mjacobs Date 2008-01-29 Time 11:13 Sent To PC
Notes
2008-01-29 13:00:02FBC 2001
 SUBMITTAL #02400.06 LIMEROCK BASE. THE INFORMATION
 SUBMITTED IS ILLEGIBLE AND WAS REJECTED BY CRAVEN,
 THOMPOSN & ASSOCIATES, ENGINEERS, PLANNERS & SURVEYORS
 INC. THE REPORT NEES THE APPROVAL OF THE ENGINEERING
 FIRM. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. FBC 106.1.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 376 Status P Date 2008-01-29 Cont ID  
Sent By mjacobs Date 2008-01-29 Time 11:06 Rev Time 0.00
Received By mjacobs Date 2008-01-29 Time 11:01 Sent To  
Notes
2008-01-29 11:03:54FBC 2001
 SHORING AND GC LETTER FOR THE RESORHING FOR LEVEL 20
 POUR B. SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 375 Status F Date 2008-01-04 Cont ID  
Sent By mjacobs Date 2008-01-04 Time 10:22 Rev Time 0.00
Received By mjacobs Date 2008-01-04 Time 10:22 Sent To PC
Notes
2008-01-04 10:22:11FBC 2001
 SUBMITTAL #05100.02.01
 BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S. OLIVE AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 1-4-08
  
 1)THE DRAWINGS SUBMITTED WITH THE SEAL AND SIGNATURE
 OF ENGINEER KENNETH J. PAGANO REQUIRES DETAILS AND
 INFORMATION FROM THE ENGINEER OF RECORD SPECIFIC TO THE
 OMITTED EMBEDDED PLATES. THE NEW CONNECTION INFORMATION
 SHALL CONTAIN THE ORIGINAL SIGNATURE OF THE ENGINEER OF
 RECORD, ALONG WITH HIS/HER SEAL AND DATED ON WHICH THE
 INFORMATION IS SIGNED. THE 8 X 11 SHEET SUBMITTED
 REQUIRES MORE INFORMATION TO SHOW WHAT WILL REPLACE THE
 DELETED AND OMITTED ITEMS SHOWN ON THAT SHEET. SUBMIT A
 NEW SHEET SHOWING THE ATTACHMENT DETAIL WITH THE SIZE
 AND TYPE OF STRAPS ALONG WITH THE SPACING AS STATED ON
 SHEET 2 OF 3. SHEET 2 ALSO REFERS TO DETAIL TS027-30-31
 AND 43; I CANNOT FIND THIS DETAIL IN THE SUBMITTED
 PACKAGES. PLEASE SHOW THIS DETAIL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 374 Status P Date 2007-12-15 Cont ID  
Sent By mjacobs Date 2007-12-15 Time 09:51 Rev Time 0.00
Received By mjacobs Date 2007-12-15 Time 08:43 Sent To PC
Notes
2007-12-15 09:01:37FBC 2001
 SUBMITTAL #03100.31- HIGH ROOF SHORING/ RE- SHORING

Review Stop B BUILDING (STRUCTURAL)
Rev No 373 Status P Date 2007-12-15 Cont ID  
Sent By mjacobs Date 2007-12-15 Time 08:41 Rev Time 0.00
Received By mjacobs Date 2007-12-15 Time 08:06 Sent To PC
Notes
2007-12-15 08:41:14FBC 2001
 SUBMITTA;L #10536.01 AWNINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 372 Status P Date 2007-12-01 Cont ID  
Sent By mjacobs Date 2007-12-01 Time 11:29 Rev Time 0.00
Received By mjacobs Date 2007-12-01 Time 11:06 Sent To PC
Notes
2007-12-01 11:14:46FBC 2001
 SUBMITTAL #03460.09 SECOND FLOORBALCONY STONE PANEL
 ATTATCHMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 371 Status P Date 2007-12-01 Cont ID  
Sent By mjacobs Date 2007-12-01 Time 11:03 Rev Time 0.00
Received By mjacobs Date 2007-12-01 Time 10:44 Sent To E
Notes
2007-12-01 10:50:43FBC 2001
 SUBMITTAL #13032.01 SAUNA AND STEAN ROOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 370 Status F Date 2007-11-16 Cont ID  
Sent By mjacobs Date 2007-11-16 Time 07:46 Rev Time 0.00
Received By mjacobs Date 2007-11-16 Time 06:07 Sent To PC
Notes
2007-11-16 07:35:35BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:1ST
 ACTION: DENIED
  
 1A) INDICATE ON THE DRAWINGS HOWTHE"STONE VENEER"
 WILLL MEET REQUIREMENTS OF FBC 1405.FL 61G1-23.015
 (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND
 REVIEWING ALL PROJECT DATA, REPORTS,SHOP DRAWINGS
 ETC...THE ARCHITECT OR ENGINEER SHALL "SIGN, SEAL AND
 DATE THE DRAWING.
  
 ANY HAND WRITTEN INFORMATION SHALL BE SIGN AND DATED
 BY THE ARCHITECT OR ENGINEER WHO IS MAKING THE CHANGES.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, FOR RECORD RETENTION PROGRAM. PROVIDE
 NEW DRAWINGS WITH OUT THE HAND WRITTEN CHANGES.
 106.1.3*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 369 Status P Date 2007-11-05 Cont ID  
Sent By mjacobs Date 2007-11-05 Time 10:48 Rev Time 0.00
Received By mjacobs Date 2007-11-05 Time 10:12 Sent To PC
Notes
2007-11-05 10:20:54FBC 2001
 SUBMITTAL #09100.07 ACOUSTICAL CEILING PLAN AND
 DETAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 368 Status P Date 2007-10-25 Cont ID  
Sent By mjacobs Date 2007-10-25 Time 13:59 Rev Time 0.00
Received By mjacobs Date 2007-10-25 Time 12:50 Sent To PC
Notes
2007-10-25 12:52:24FBC 2001
 SUBMITTAL #07551.02 HEAT
 WELDED (TORCH DOWN) MODIVIED BITEMEN ROOFING SYSTEM.
 CHANGE FROM HOT MOP TO TORCH DOWN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 367 Status P Date 2007-10-25 Cont ID  
Sent By mjacobs Date 2007-10-25 Time 12:49 Rev Time 0.00
Received By mjacobs Date 2007-10-25 Time 12:00 Sent To PC
Notes
2007-10-25 12:23:25FBC 2001
 SUBMITTAL #07551.01.01 ROOFING SUBMITTALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 366 Status P Date 2007-10-25 Cont ID  
Sent By mjacobs Date 2007-10-19 Time 18:01 Rev Time 0.00
Received By mjacobs Date 2007-10-19 Time 11:00 Sent To PC
Notes
2007-10-19 18:01:11FBC 2001
 SUBMITTAL #05520.07.02 / #05520.08.02 / #05520.09.02
 TWO OF THE PLANS HAVE THE SAME NUMBER HOWEVER THE
 INFORMATIOON SHEET INDICATES THAT EACH DRAWING SHALL
 HAVE A DIFFERENT NUMBER. CLARIFY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 365 Status P Date 2007-10-19 Cont ID  
Sent By mjacobs Date 2007-10-19 Time 09:16 Rev Time 0.00
Received By mjacobs Date 2007-10-19 Time 08:05 Sent To PC
Notes
2007-10-19 08:12:08FBC 2001
 SUBMITTA #15430.01 ACCESS DOORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 364 Status P Date 2007-10-19 Cont ID  
Sent By mjacobs Date 2007-10-19 Time 07:59 Rev Time 0.00
Received By mjacobs Date 2007-10-19 Time 07:47 Sent To PC
Notes
2007-10-19 07:58:58FBC 2001
 SUBMITTAL #03200.53HIGH ROOF POUR D AND E MACHINE
 ROOM AND BEANS,SLABS AND MISC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 363 Status F Date 2007-10-19 Cont ID  
Sent By mjacobs Date 2007-10-19 Time 07:43 Rev Time 0.00
Received By mjacobs Date 2007-10-19 Time 06:24 Sent To PC
Notes
2007-10-19 07:43:11BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S. OLIVE AVE
 CONT: KAST CONST.
 TEL: (561)329-9396
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST OF SUBMITTAL #05100.02
 ACTION: DENIED
  
 1)FLORIDA STATUTES 471.025. (1)ALL FINAL DRAWINGS,
 SPECIFICATIONS, PLANS OR DOCUMENTS PREPARED OR ISSUED
 BY THE LICENSEE AND BEING FILED FOR PUBLIC RECORD AND
 ALL FINAL DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE SHALL BE SIGNED BY THE LICENSEE,
 DATED, AND SEALED WITH SAID SEAL.SUCH SIGNATURE,
 DATE, DATE AND SEAL SHALL BE EVIDENCE OF THE
 AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED. THE
 SIGNATURE ON THE REPORS SHALL BE ORIGINAL, THE REPORTS
 SUBMITTED CONTAIN EITHER A RUBBER STAMP OR PHOTO-COPY
 SIGNATURE OF THE ENGINEER. THIS IS NOT ACCEPTABLE.
 REPORTS BEING FILED FOR PUBLIC RECORS SHALL BE
 ORIGINAL.
  
 2)FAC 61G15-23.002 (2)A COVER OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE ORIGINALY SIGNED, SEALED AND DATED BY THOSE
 PROFESSINOL ENGINEERS RESPONSIBLE FOR THE DOCUMENT. THE
 COVER OR INDEX SHEET SHALL REFERENCE EACH SHEET OF THE
 DOCUMENT.
  
 FBC 2001
 SUBMITTAL #05100.02DETAIL TRUSS CONNECTIONS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 362 Status P Date 2007-10-19 Cont ID  
Sent By mjacobs Date 2007-10-19 Time 06:24 Rev Time 0.00
Received By mjacobs Date 2007-10-19 Time 05:53 Sent To PC
Notes
2007-10-19 06:05:12FBC 2001
 SUBMITTAL #05100.04.01GAZEEBO AND SUPPLYAIR SHAFT
 STEEL TRUSSES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 361 Status P Date 2007-10-18 Cont ID  
Sent By mjacobs Date 2007-10-18 Time 14:07 Rev Time 0.00
Received By mjacobs Date 2007-10-18 Time 12:45 Sent To PC
Notes
2007-10-18 14:07:30FBC 2001
 SUBMITTAL #05100.05.01STEEL TRUSSES FOR EXHAUST
 SHAFT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 360 Status P Date 2007-10-18 Cont ID  
Sent By mjacobs Date 2007-10-18 Time 12:14 Rev Time 0.00
Received By mjacobs Date 2007-10-18 Time 11:29 Sent To PC
Notes
2007-10-18 12:14:35FBC 2001
 SUBMITTAL #05100.03.01 4TH FL MANSARD STEEL TRUSSEES
 CONNECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 359 Status P Date 2007-10-13 Cont ID  
Sent By mjacobs Date 2007-10-13 Time 09:28 Rev Time 0.00
Received By mjacobs Date 2007-10-13 Time 08:39 Sent To PC
Notes
2007-10-13 08:45:02FBC 2001
 SUBMITTAL #03100.30 POOL DECK SHORING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 358 Status P Date 2007-10-06 Cont ID  
Sent By mjacobs Date 2007-10-06 Time 07:00 Rev Time 0.00
Received By mjacobs Date 2007-10-06 Time 05:53 Sent To PC
Notes
2007-10-06 07:00:53FBC 2001
 SUBMITTAL #07212.04.01 THERMAX HEAVY DUTY INSULATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 357 Status P Date 2007-09-30 Cont ID  
Sent By rbrown Date 2007-09-30 Time 23:05 Rev Time 0.00
Received By rbrown Date 2007-09-30 Time 23:05 Sent To  
Notes
2007-09-30 23:05:31STRUCTURAL REVISION SUBMITTED 7/11/07

Review Stop B BUILDING (STRUCTURAL)
Rev No 356 Status P Date 2007-09-30 Cont ID  
Sent By rbrown Date 2007-09-30 Time 23:03 Rev Time 0.00
Received By rbrown Date 2007-09-30 Time 23:03 Sent To  
Notes
2007-09-30 23:04:43ARCHITECTURAL AND STRUCTURAL REVISION SUBMITTED 7/6/07

Review Stop B BUILDING (STRUCTURAL)
Rev No 355 Status P Date 2007-09-15 Cont ID  
Sent By mjacobs Date 2007-09-15 Time 11:56 Rev Time 0.00
Received By mjacobs Date 2007-09-15 Time 11:05 Sent To PC
Notes
2007-09-15 11:31:13FBC 2001
 SUBMITTAL #11011.03 WINDOW CLEANING & FACADE
 MAINTENANCE SAFETYSYSTEM LAYOUT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 354 Status P Date 2007-09-15 Cont ID  
Sent By mjacobs Date 2007-09-15 Time 10:55 Rev Time 0.00
Received By mjacobs Date 2007-09-15 Time 09:57 Sent To PC
Notes
2007-09-15 10:34:02FBC 2001
 SUBMITTAL #03460.04WEST ELEVATION "F1"SICKER BAND
 PRECAST.

Review Stop B BUILDING (STRUCTURAL)
Rev No 353 Status P Date 2007-09-15 Cont ID  
Sent By mjacobs Date 2007-09-15 Time 09:56 Rev Time 0.00
Received By mjacobs Date 2007-09-15 Time 09:41 Sent To PC
Notes
2007-09-15 09:56:48FBC 2001
 SUBMITTAL #03460.06WINDOW SILL AT LANI LEVEL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 352 Status P Date 2007-09-15 Cont ID  
Sent By mjacobs Date 2007-09-15 Time 09:41 Rev Time 0.00
Received By mjacobs Date 2007-09-15 Time 09:16 Sent To PC
Notes
2007-09-15 09:41:23FBC 2001
 SUBMITTAL #13152.07.02POOL & FOUNTAIN WATERPROOFING
 SPEC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 351 Status P Date 2007-09-15 Cont ID  
Sent By mjacobs Date 2007-09-15 Time 09:16 Rev Time 0.00
Received By mjacobs Date 2007-09-15 Time 08:08 Sent To PC
Notes
2007-09-15 09:15:59FBC 2001
 SUBMITTAL #03200.52HIGH ROOF BEAMS, ARCH BEAMS, SLABS
 AND MISC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 350 Status F Date 2007-09-15 Cont ID  
Sent By mjacobs Date 2007-09-15 Time 08:04 Rev Time 0.00
Received By mjacobs Date 2007-09-15 Time 07:32 Sent To PC
Notes
2007-09-15 08:04:27BUILDING PLAN REVIEW
 PERMIT:04120353
 ADD: 717 S.OLIVE AVE.
 CONT: KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW1ST
 ACTION: DENIED
  
 1)AWNINGS SHALL BE DESIGNED SO THAT FABRIC OR
 MEMBRANE COVER CAN BE QUICKLY AND EASILY REMOVED PER
 3105.4.2.1 TIGHTLY WRAPED OR WOVEN CORDS ARE
 ACCEPTABLE, WHEN 2 COPIES OF A DETAILED INSTRUCTION
 GUIDE FOR REMOVAL ARE INCLUDED IN THE SUBMITTAL (PHOTOS
 SHOWING THE DIFFERENT STEPS WITH INSTRUCTIONS CAN ALSO
 BE SUBMITTED). IN ADDITION 2 COPIES OF A NOTORIZED
 LETTER OF INTENT TO REMOVE AT 75 MPH ARE REQUIRED. SEE
 GENERAL NOTE #7 FROM ENGINEERING EXPRESS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 349 Status P Date 2007-09-21 Cont ID  
Sent By mjacobs Date 2007-09-21 Time 07:25 Rev Time 0.00
Received By mjacobs Date 2007-09-15 Time 07:03 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 348 Status P Date 2007-09-15 Cont ID  
Sent By mjacobs Date 2007-09-15 Time 07:02 Rev Time 0.00
Received By mjacobs Date 2007-09-15 Time 06:31 Sent To PC
Notes
2007-09-15 07:01:24FBC 2001
 SUBMITTAL #04220.09VERTICOAT REMEDIAL @ BLOCK WALLS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 347 Status P Date 2007-09-15 Cont ID  
Sent By mjacobs Date 2007-09-15 Time 06:31 Rev Time 0.00
Received By mjacobs Date 2007-09-15 Time 05:44 Sent To PC
Notes
2007-09-15 06:31:21FBC 2001
 SUBMITTAL #03200.42MAIN ROOF POUR B

Review Stop B BUILDING (STRUCTURAL)
Rev No 346 Status F Date 2007-09-11 Cont ID  
Sent By mjacobs Date 2007-09-11 Time 11:29 Rev Time 0.00
Received By mjacobs Date 2007-09-11 Time 11:24 Sent To PC
Notes
2007-09-11 11:27:55FBC 2001
 SUBMITTALS #03200.50 WALLS REBAR AMENITY DECK POUR D.
  
  
 BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S.OLIVE AVE
 CONT: KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)AT LEAST ONE OF THE DRAWINGS SHALL HAVE THE
 ORIGINAL STAMPS AND SIGNATURE OF APPROVAL OF THE
 ENGINEER OF RECORD. CONSTRUCTION DOCUMENTS BEING FILED
 FOR PUBLIC RECORD SHALL HAVE THE ORIGINAL SIGNATURE/
 DATE AND SEAL OF THE ARCHITECT OR ENGINEER WHO DESIGN
 THE PROJECT. FBC. 106.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 345 Status P Date 2007-09-11 Cont ID  
Sent By mjacobs Date 2007-09-11 Time 11:21 Rev Time 0.00
Received By mjacobs Date 2007-09-11 Time 10:55 Sent To PC
Notes
2007-09-11 11:03:56FBC 2001
 SUBMITTAL #03200.51 POUR E AMENITY DECK/WALLS AND
 REBAR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 344 Status F Date 2007-09-10 Cont ID  
Sent By mjacobs Date 2007-09-10 Time 10:36 Rev Time 0.00
Received By mjacobs Date 2007-09-10 Time 06:49 Sent To PC
Notes
2007-09-10 10:36:24FBC 2001
 SUBMITTALS #03200.47 REBAR AMENITY DECK POUR B.
  
  
 BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S.OLIVE AVE
 CONT: KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)AT LEAST ONE OF THE DRAWINGS SHALL HAVE THE
 ORIGINAL STAMPS AND SIGNATURE OF APPROVAL OFTHE
 ENGINEER OF RECORD. CONSTRUCTION DOCUMENTS BEING FILED
 FOR PUBLIC RECORD SHALL HAVE THE ORIGINAL SIGNATURE/
 DATE AND SEAL OF THE ARCHITECT OR ENGINEER WHO DESIGN
 THE PROJECT. FBC. 106.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 343 Status P Date 2007-09-10 Cont ID  
Sent By mjacobs Date 2007-09-10 Time 06:47 Rev Time 0.00
Received By mjacobs Date 2007-09-10 Time 06:01 Sent To PC
Notes
2007-09-10 06:47:06FBC 2001
 SUBMITTAL #03200.49 REBAR- AMENITY DECK AND WALLS POUR
 C.

Review Stop B BUILDING (STRUCTURAL)
Rev No 342 Status P Date 2007-09-04 Cont ID  
Sent By mjacobs Date 2007-09-04 Time 08:23 Rev Time 0.00
Received By mjacobs Date 2007-09-04 Time 07:46 Sent To PC
Notes
2007-09-04 07:53:05FBC 2001
 SUBMITTAL #07830.04MULTIPLE CONDUIT & METALLIC PIPE
 PENETRATIONS THRU CONCRETE WALL AND FLOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 341 Status P Date 2007-09-04 Cont ID  
Sent By mjacobs Date 2007-09-04 Time 07:42 Rev Time 0.00
Received By mjacobs Date 2007-09-04 Time 07:14 Sent To PC
Notes
2007-09-04 07:16:14FBC 2001
 SUBMITTAL #05520.11POWDER COAT PRODUCT DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 340 Status P Date 2007-09-04 Cont ID  
Sent By mjacobs Date 2007-09-04 Time 07:13 Rev Time 0.00
Received By mjacobs Date 2007-09-04 Time 06:01 Sent To PC
Notes
2007-09-04 06:09:55FBC 2001
 SUBMITTAL #05520.04.02TRELLIS DETAIL @ POOL DECK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 339 Status P Date 2007-08-25 Cont ID  
Sent By mjacobs Date 2007-08-25 Time 14:25 Rev Time 0.00
Received By mjacobs Date 2007-08-25 Time 14:07 Sent To PC
Notes
2007-08-25 14:25:39FBC 2001
 SUBMITTAL #03200.48POOL DECK SLAB POUR B

Review Stop B BUILDING (STRUCTURAL)
Rev No 338 Status P Date 2007-08-24 Cont ID  
Sent By mjacobs Date 2007-08-24 Time 07:31 Rev Time 0.00
Received By mjacobs Date 2007-08-24 Time 07:12 Sent To PC
Notes
2007-08-24 07:31:41FBC 2001
 SUBMITTAL #03200.45MAIN ROOF DECK REBAR POUR E.

Review Stop B BUILDING (STRUCTURAL)
Rev No 337 Status P Date 2007-08-24 Cont ID  
Sent By mjacobs Date 2007-08-24 Time 07:08 Rev Time 0.00
Received By mjacobs Date 2007-08-24 Time 06:44 Sent To PC
Notes
2007-08-24 07:08:53FBC 2001
 SUBMITTAL #03365.17.03 22ND FLOOR ROOF PRE-STRESS
 CALCS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 336 Status P Date 2007-08-24 Cont ID  
Sent By mjacobs Date 2007-08-24 Time 06:44 Rev Time 0.00
Received By mjacobs Date 2007-08-24 Time 05:59 Sent To PC
Notes
2007-08-24 06:05:52FBC 2001
 SUBMITTAL #03200.46 ABOVE ROOF WALLS COLUMNS AND POOL
 DECK SLAB.

Review Stop B BUILDING (STRUCTURAL)
Rev No 335 Status P Date 2007-08-23 Cont ID  
Sent By mjacobs Date 2007-08-23 Time 18:58 Rev Time 0.00
Received By mjacobs Date 2007-08-23 Time 18:44 Sent To PC
Notes
2007-08-23 18:47:08FBC 2001
 SUBMITTAL #03100.28 MAIN ROOF SHORING PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 334 Status P Date 2007-08-23 Cont ID  
Sent By mjacobs Date 2007-08-23 Time 18:43 Rev Time 0.00
Received By mjacobs Date 2007-08-23 Time 18:26 Sent To PC
Notes
2007-08-23 18:43:12FBC 2001
 SUBMITTAL #03100.29 METAL DECK PLANTER LOCATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 333 Status P Date 2007-08-23 Cont ID  
Sent By mjacobs Date 2007-08-23 Time 18:25 Rev Time 0.00
Received By mjacobs Date 2007-08-23 Time 18:08 Sent To PC
Notes
2007-08-23 18:25:52FBC: 2001
 SUBMITTAL #03200.43 MAIN ROOF POUR C

Review Stop B BUILDING (STRUCTURAL)
Rev No 332 Status P Date 2007-08-23 Cont ID  
Sent By mjacobs Date 2007-08-23 Time 18:08 Rev Time 0.00
Received By mjacobs Date 2007-08-23 Time 17:38 Sent To PC
Notes
2007-08-23 18:08:20FBC: 2001
 SUBMITTAL #0320.44 MAIN ROOF POUR D

Review Stop B BUILDING (STRUCTURAL)
Rev No 331 Status P Date 2007-08-23 Cont ID  
Sent By mjacobs Date 2007-08-23 Time 17:37 Rev Time 0.00
Received By mjacobs Date 2007-08-23 Time 17:05 Sent To PC
Notes
2007-08-23 17:08:41FBC: 2001
 SHORING AND GC LETTER FOR POUR #126, LEVEL 22 POUR E.
 SENT TO JERALD INBOX

Review Stop B BUILDING (STRUCTURAL)
Rev No 330 Status P Date 2007-08-23 Cont ID  
Sent By mjacobs Date 2007-08-23 Time 17:03 Rev Time 0.00
Received By mjacobs Date 2007-08-23 Time 16:50 Sent To PC
Notes
2007-08-23 16:55:00FBC:2001
 SHOORING AND GC LETTER FOR POUR #125. ROOF LEVEL 22
 POUR D. SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 329 Status P Date 2007-08-01 Cont ID  
Sent By mjacobs Date 2007-08-01 Time 17:20 Rev Time 0.00
Received By mjacobs Date 2007-08-01 Time 17:13 Sent To PC
Notes
2007-08-01 17:16:06FBC 2001
 SHORING AND GC LETTER #22 FOR ROOF LEVEL 22 POUR C.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 328 Status F Date 2007-08-01 Cont ID  
Sent By mjacobs Date 2007-08-01 Time 17:04 Rev Time 0.00
Received By mjacobs Date 2007-07-26 Time 08:21 Sent To  
Notes
2007-07-26 09:22:51BUILDING PLAN REVIEW
 PERMIT:04120353
 ADD: 717 S.OLIVE AVE
 CONT: KAST
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:1ST
 ACTION: DENIED
  
 1)FBC 2001 SUBMITTAL #03100.27MAIN ROOF RESHORING.
 ONE OF THE PAGES IN THE SET CONTAINS A PHOTO-COPY STAMP
 OF THE STRUCTURAL ENGINEER. ALL INFORMATION BEING
 STORED FOR PUBLIC RECORD SHALL HAVE THE ORIGINAL STAMP
 AND SIGNATURE OF THE PERSON TAKING RESPONSIBILITY. FAC
 61G15-23.002.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 327 Status P Date 2007-07-26 Cont ID  
Sent By mjacobs Date 2007-07-26 Time 08:17 Rev Time 0.00
Received By mjacobs Date 2007-07-26 Time 07:40 Sent To PC
Notes
2007-07-26 08:17:46FBC 2001
  
 SUBMITTAL #03200.41 ROOF DECK POUR 'A'

Review Stop B BUILDING (STRUCTURAL)
Rev No 326 Status P Date 2007-07-20 Cont ID  
Sent By mjacobs Date 2007-07-20 Time 07:09 Rev Time 0.00
Received By mjacobs Date 2007-07-20 Time 07:06 Sent To PC
Notes
2007-07-20 07:08:57FBC. 2001
  
 SHORING AND GC LETTER FOR POUR#122 LEVEL 22 POUR A.
 SENT JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 325 Status P Date 2007-07-12 Cont ID  
Sent By mjacobs Date 2007-07-12 Time 07:39 Rev Time 0.00
Received By mjacobs Date 2007-07-12 Time 07:30 Sent To PC
Notes
2007-07-12 07:35:43FBC 2001
 RECEIVE 7/06/07
  
 SUBMITTAL #03300.293000 PSI.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 324 Status P Date 2007-07-12 Cont ID  
Sent By mjacobs Date 2007-07-12 Time 07:30 Rev Time 0.00
Received By mjacobs Date 2007-07-12 Time 07:11 Sent To PC
Notes
2007-07-12 07:30:21FBC 2001
 RECEIVE 7/6/07
 SUBMITTAL #03100.25MAIN ROOF SHORING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 323 Status P Date 2007-07-12 Cont ID  
Sent By mjacobs Date 2007-07-12 Time 07:06 Rev Time 0.00
Received By mjacobs Date 2007-07-12 Time 06:56 Sent To PC
Notes
2007-07-12 07:05:52FBC 2001
 RECEIVE 7/2/07
 SHORING AND GC LETTER FOR POUR #121 LEVEL 21 POUR E.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 322 Status P Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 13:36 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 13:36 Sent To  
Notes
2007-07-01 13:41:24ARCHITECTURAL REVISION SUBMITTED 6/5/07 FOR SHEETS
 A4.32, A4.35, A3.36, A4.42, A4.53, A7.01, A7.05,
 A7.05A, A7.09, AND A7.12.THE SAME SHEETS WERE DENIED
 ON 4/26/07 BUT HAVE BEEN RE-SUBMITTED WITH A COMMENT
 RESPONSE FROM BC ARCHITECTS CLARIFYING THAT 3/4" STEP
 IN SLAB IS STRUCTURAL SLAB LEVEL ONLY, TO ACCOMMODATE
 DIFFERENCE IN THICKNESS OF FINISHES.FINISHED FLOOR
 WILL BE LEVEL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 321 Status F Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 13:29 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 12:30 Sent To PC
Notes
2007-06-30 13:29:40BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S.OLIVE AVE
 CONT: KAST CONST.
 TEL: (561)835-3852
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 FBC 2001
 IN 6/26/07
 SUBMITTAL #11011.02 WINDOW CLEANING & FACADE
 MAINTENANCE SAFETY SYSTEM LAYOUT.
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)ENGINEER HO SIK HOL HAS A DELIQUENT STATUS.THE
 STATE WEB-SITE SHOWS THAT HIS LICENSE EXPIRED ON
 02/28/07. THIS ISSUE SHALL BE RESOLVED BEFORE
 RESUBMITTING.
  
 3)FAC. 61G15-23.002ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 LICENSE NUMBER, AS WESS AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND AFFIX
 HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS, FINAL
 BID DOCUMENTS OR OTHER DOCUMENTS PREPARED OR ISSUED BY
 SAID REGISTRANT AND GEING FILED FOR PUBLIC RECORD.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 320 Status P Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 12:22 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 11:08 Sent To PC
Notes
2007-06-30 12:22:48FBC 2001
 IN 6/19/07
 SUBMITTAL #03200.41 SHEAR WALL #1-6 TOWER 21 TO MAIN
 ROOF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 319 Status P Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 11:06 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 10:39 Sent To PC
Notes
2007-06-30 11:06:52FBC 2001
 IN 6/21/0
 SUBMITTAL #03365.1621ST FL POST TENSIONING
 CALCULATIONS PAGES 1-90

Review Stop B BUILDING (STRUCTURAL)
Rev No 318 Status P Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 10:37 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 10:13 Sent To PC
Notes
2007-06-30 10:37:00FBC 2001
 IN 6/19/07
 SUBMITTAL #03200.40 TOWER COLUMN SCHEDULE LEVEL 20 TO
 MAIN ROOF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 317 Status P Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 10:11 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 09:21 Sent To PC
Notes
2007-06-30 10:11:25FBC 2001
 IN 6/19/07
 SUBMITTAL #03460.01 PRE-CAST SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 316 Status P Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 09:19 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 09:06 Sent To PC
Notes
2007-06-30 09:19:25FBC 2001
 IN 6/26/07
 SUBMITTAL #03100.24 TOWER LEVEL 17-21 SHORING AND SHOP
 DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 315 Status P Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 09:06 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 08:50 Sent To PC
Notes
2007-06-30 09:02:23FBC 2001
 IN 6/21/07
 SUBMITTAL #03300.293000 PSI PEARROCK PUMPMIX WITH
 HRWR AND FIBER

Review Stop B BUILDING (STRUCTURAL)
Rev No 314 Status P Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 08:49 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 08:45 Sent To PC
Notes
2007-06-30 08:47:34FBC 2001
 IN 6/28/07
 SHORING AND GC LETTER FOR POUR #120 LEVEL 21 POUR D.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 313 Status P Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 08:44 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 08:40 Sent To PC
Notes
2007-06-30 08:44:43FBC 2001
 IN 6/26/07
 SHORING AND GC LETTER FOR POUR #119 LEVEL 21 POU C.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 312 Status P Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 08:40 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 08:33 Sent To PC
Notes
2007-06-30 08:38:12FBC 2001
 IN 6/21/07
 SHORING AND GC LETTER FOR POUR #118 LEVEL 21 POUR B.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 311 Status P Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 08:33 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 08:29 Sent To PC
Notes
2007-06-30 08:32:00FBC 2001
 IN 6/19/07
 SHORING AND GC LETTER FOR POUR #117 LEVEL 21 POUR A.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 310 Status P Date 2007-06-30 Cont ID  
Sent By mjacobs Date 2007-06-30 Time 08:27 Rev Time 0.00
Received By mjacobs Date 2007-06-30 Time 08:18 Sent To PC
Notes
2007-06-30 08:26:15FBC 2001
 IN 6/15/07
 SHORING AND GC LETTER FOR POUR #116 LEVEL 20 POUR E.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 309 Status F Date 2007-06-24 Cont ID  
Sent By rbrown Date 2007-06-24 Time 16:30 Rev Time 0.00
Received By rbrown Date 2007-06-24 Time 16:30 Sent To  
Notes
2007-06-24 16:39:54BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 6/5/07 FOR ENGINEERING CALCS FOR
 ADDITIONAL FASTENERS, WITHOUT SHIMS, TO ADDRESS FIELD
 VARIATIONS ON WINDOW AND SGD HEAD AND JAMB GAPS.
  
 1)FBC 1606.1ALL FASTENER LOCATIONS SHALL
 INCORPORATE SHIMS TO REDUCE FASTENER ROTATION, AND
 REDUCE THE RISK OF FASTENERS BACKING OUT DUE TO CYCLIC
 WIND LOADING.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 308 Status P Date 2007-06-24 Cont ID  
Sent By rbrown Date 2007-06-24 Time 16:27 Rev Time 0.00
Received By rbrown Date 2007-06-24 Time 16:27 Sent To  
Notes
2007-06-24 16:30:06SUBMITTAL ON 5/30/07 FOR ENGINEERING CALCS FOR
 ADDITIONAL FASTENERS, WITH SHIMS, TO ADDRESS FIELD
 VARIATIONS ON WINDOW AND SGD HEAD AND JAMB GAPS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 307 Status P Date 2007-06-24 Cont ID  
Sent By rbrown Date 2007-06-24 Time 15:49 Rev Time 0.00
Received By rbrown Date 2007-06-24 Time 15:49 Sent To  
Notes
2007-06-24 15:52:41SUBMITTAL ON 6/19/07 FOR ARCITECT'S LETTER DATED
 6/18/07 EXPLAINING INTENT OF LIVE/WORK UNITS:
 -MEZZANINE LEVEL IS INTENDED FOR PRIVATE DWELLING
 PURPOSES AND IS NOT SUBJECT TO FLORIDA ACCESSIBILITY
 CODE REQUIREMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 306 Status P Date 2007-06-24 Cont ID  
Sent By rbrown Date 2007-06-24 Time 15:44 Rev Time 0.00
Received By rbrown Date 2007-06-24 Time 15:44 Sent To  
Notes
2007-06-24 15:46:00SUBMITTAL ON 6/1/07 FOR EXTERIOR SYNERGY
 NON-COMBUSTIBLE FOAM ARCHITECTURAL TRIM PACKAGE AND
 SIGNED AND SEALED COVER LETTER FORM ARCHITECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 305 Status F Date 2007-06-18 Cont ID  
Sent By mjacobs Date 2007-06-18 Time 09:47 Rev Time 0.00
Received By mjacobs Date 2007-06-18 Time 07:54 Sent To PC
Notes
2007-06-18 09:47:17FBC 2001
  
 SUBMITTAL #05100.02. ONLY SOME OF THE INFORMATION
 SUBMITTED WILL BE APPROVED. THOSE ITEMS WHICH ARE
 APPROVED WILL BE STAMPED. THE OTHER ITEMS WILL BE
 RETUNED. THE SUBMITTALS BY KENNETH J. PAGANO, PE #58131
 ARE OK.THE INFORMATION BY SCOTT L. SCHURWAN PE
 #31867, IS MISSING THE PRINTED NAME AND NUMBER/THE DATE
 AND THE SIGNATURE ON SOME OF THE SUBMITTALS WERE
 STAMPED WHICH IS NOT ACCEPTABLE. SEE F.A.C.
 61G15-23.002(1)A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS,
 REPORTS, FINAL BID DOCUMENTS BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED
 AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER.
  
 (2) A COVER OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL
 ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX SO THAT THE USER WILL BE AWARE OF EACH
 PORTION OF THE SPECIFICATION FOR WHICH EACH
 PROFESSIONAL ENGINEER IS RESPONSIBLE. SEE F.A.C.
 61G15-23.002
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 304 Status P Date 2007-06-18 Cont ID  
Sent By mjacobs Date 2007-06-18 Time 07:21 Rev Time 0.00
Received By mjacobs Date 2007-06-18 Time 07:20 Sent To PC
Notes
2007-06-18 07:21:33FBC 2001
  
 SHORING AND GC LETTER FOR POUR #114. FOR LEVEL 10 POUR
 D.

Review Stop B BUILDING (STRUCTURAL)
Rev No 303 Status P Date 2007-06-18 Cont ID  
Sent By mjacobs Date 2007-06-18 Time 07:15 Rev Time 0.00
Received By mjacobs Date 2007-06-18 Time 07:07 Sent To PC
Notes
2007-06-18 07:15:00FBC 2001
  
 SHORING AND GC LETTER FOR POUR #114 LEVEL 20 POUR C.

Review Stop B BUILDING (STRUCTURAL)
Rev No 302 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 12:52 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 11:42 Sent To PC
Notes
2007-06-09 12:17:49FBC: 2001
  
 SUBMITTAL #03200.39 21ST FLOOR STEEL SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 301 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 11:34 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 10:36 Sent To PC
Notes
2007-06-09 11:34:40FBC 2001
  
 SUBMITTAL #03200.38 TOWER: 17TH - 20TH FLRS - POUR A

Review Stop B BUILDING (STRUCTURAL)
Rev No 300 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 10:31 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 10:21 Sent To PC
Notes
2007-06-09 10:31:01FBC: 2001
  
 SHORING AND GC LETTER FOR POUR #112. LEVEL 20POUR A

Review Stop B BUILDING (STRUCTURAL)
Rev No 299 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 10:18 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 09:53 Sent To PC
Notes
2007-06-09 10:18:30FBC 2001
  
 SUBMITTAL #09250.05. MOLD TOUGH GYPSUM PRODUCT DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 298 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 09:53 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 09:36 Sent To PC
Notes
2007-06-09 09:53:33FBC 2001
  
 SUBMITTAL #09300.11 . LIQUID ANTI-FRACTURE &
 WATERPROOFING MEMBRANE PRODUCT DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 297 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 09:32 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 09:08 Sent To PC
Notes
2007-06-09 09:32:23FBC 2001
  
 SUBMITTAL #08820.01 UNIT MIRROR PRODUCT SPECS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 296 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 09:08 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 08:35 Sent To PC
Notes
2007-06-09 09:00:06FBC 2001
  
 SUBMITTAL #09300.14MARBLE & TILEGROUT SPECS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 295 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 08:25 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 08:06 Sent To PC
Notes
2007-06-09 08:10:22FBC 2001
  
 SHORING AND GC LETTER FOR POUR #111 LEVEL19 POUR E.
 SENT TO JERALD INBOX

Review Stop B BUILDING (STRUCTURAL)
Rev No 294 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 08:05 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 08:03 Sent To PC
Notes
2007-06-09 08:05:41FBC 2001
  
 SHORING AND GC LETTER FOR POUR #110 LEVEL #19 POUR D.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 293 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 08:02 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 07:56 Sent To PC
Notes
2007-06-09 08:02:31FBC 2001
  
 SHORING AND GC LETTER FOR POUR #109 LEVEL 19 POUR C.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 292 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 07:56 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 07:54 Sent To PC
Notes
2007-06-09 07:56:04FBC 2001
  
 SHORING AND GC LETTER FOR POUR #108 LEVEL 19 POUR B.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 291 Status P Date 2007-06-09 Cont ID  
Sent By mjacobs Date 2007-06-09 Time 07:53 Rev Time 0.00
Received By mjacobs Date 2007-06-09 Time 07:37 Sent To PC
Notes
2007-06-09 07:42:01FBC: 2001.
  
 SHORING AND GC LETTER FOR POUR #107. LEVEL 19 POUR A.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 290 Status P Date 2007-05-21 Cont ID  
Sent By mjacobs Date 2007-05-21 Time 09:35 Rev Time 0.00
Received By mjacobs Date 2007-05-21 Time 09:16 Sent To PC
Notes
2007-05-21 09:35:14FBC 2001
  
 SHORING AND GC LETTER FOR POUR 106-E LEVEL 18. SENT TO
 JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 289 Status P Date 2007-05-21 Cont ID  
Sent By mjacobs Date 2007-05-21 Time 09:07 Rev Time 0.00
Received By mjacobs Date 2007-05-21 Time 09:02 Sent To PC
Notes
2007-05-21 09:07:14FBC 2001
  
 SHORING AND GC LETTER FOR POUR 105-D LEVEL 18. SENT TO
 JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 288 Status P Date 2007-05-21 Cont ID  
Sent By mjacobs Date 2007-05-21 Time 08:59 Rev Time 0.00
Received By mjacobs Date 2007-05-21 Time 08:55 Sent To PC
Notes
2007-05-21 08:58:52FBC 2001
  
 SHORING AND GC LETTER FOR POUR 104-C, LEVEL 18. SENT TO
 JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 287 Status P Date 2007-05-21 Cont ID  
Sent By mjacobs Date 2007-05-21 Time 08:51 Rev Time 0.00
Received By mjacobs Date 2007-05-21 Time 08:43 Sent To PC
Notes
2007-05-21 08:50:55FBC 2001
  
 SHORING AND GC LETTERS FOR POUR 103-B, LEVEL 18. SENT
 TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 286 Status P Date 2007-05-21 Cont ID  
Sent By mjacobs Date 2007-05-21 Time 08:43 Rev Time 0.00
Received By mjacobs Date 2007-05-21 Time 08:10 Sent To PC
Notes
2007-05-21 08:43:02FBC 2001
  
 SHORING AND GC LETTER FOR POUR 102-A, LEVEL 18. SENT TO
 JERALD INBOX.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 285 Status P Date 2007-05-21 Cont ID  
Sent By mjacobs Date 2007-05-21 Time 08:05 Rev Time 0.00
Received By mjacobs Date 2007-05-21 Time 07:54 Sent To PC
Notes
2007-05-21 08:05:06FBC 2001
  
 SHORING AND GC LETTER FOR POUR 101-E, LEVEL 17. SENT TO
 JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 284 Status P Date 2007-05-21 Cont ID  
Sent By mjacobs Date 2007-05-21 Time 07:54 Rev Time 0.00
Received By mjacobs Date 2007-05-21 Time 07:49 Sent To PC
Notes
2007-05-21 07:54:10FBC 2001
  
 SHORING AND GC LETTER FOR POUR100-D, LEVEL 17. SENT TO
 JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 283 Status P Date 2007-05-21 Cont ID  
Sent By mjacobs Date 2007-05-21 Time 07:18 Rev Time 0.00
Received By mjacobs Date 2007-05-21 Time 06:52 Sent To PC
Notes
2007-05-21 06:56:30FBC 2001
  
 SHORING AND GC LETTER FOR POUR 99-C, LEVEL 17. SENT TO
 JERALD DESK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 282 Status F Date 2007-04-26 Cont ID  
Sent By rbrown Date 2007-04-26 Time 19:45 Rev Time 0.00
Received By rbrown Date 2007-04-26 Time 19:44 Sent To  
Notes
2007-05-01 19:57:18BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 ARCHITECTURAL REVISION # 9
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 ALL SHEETS REVIEWED AND STAMPED EXCEPT SHEETS A4.32,
 A4.35, A3.36, A4.42, A4.53, A7.01, A7.05, A7.05A,
 A7.09, AND A7.12 WHICH ARE ALL DENIED PER THE COMMENT
 BELOW:
  
 1) FBC 1012.1.3ELEVATION CHANGE AT ELEVATOR VESTIBULE
 DOORWAY.SHEETS A4.32, A4.35, A3.36, A4.42, A4.53,
 A7.01, A7.05, A7.05A, A7.09, AND A7.12 ALL SHOW A 3/4
 INCH CHANGE IN FLOOR ELEVATION AT THE ELEVATOR
 VESTIBULE DOORWAY.THE ELEVATION CHANGE OF THE FLOOR
 SURFACES ON BOTH SIDES OF A DOOR SHALL NOT VARY BY MORE
 THAN 1/2 INCH AND ANY FLOOR LEVEL CHANGE MORE THAN 1/4
 INCH AT DOORWAYS SHALL BE BEVELED WITH A SLOPE NOT
 STEEPER THAN 1:2.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 281 Status P Date 2007-04-25 Cont ID  
Sent By mjacobs Date 2007-04-25 Time 07:05 Rev Time 0.00
Received By mjacobs Date 2007-04-25 Time 06:54 Sent To PC
Notes
2007-04-25 07:05:14FBC:2001
  
 SHORING AND GC LETTER FOR POUR #98-B. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 280 Status P Date 2007-04-25 Cont ID  
Sent By mjacobs Date 2007-04-25 Time 06:53 Rev Time 0.00
Received By mjacobs Date 2007-04-25 Time 06:47 Sent To PC
Notes
2007-04-25 06:52:58FBC. 2001
  
 SHORING AND GC LETTER FOR POUR #97. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 279 Status P Date 2007-04-23 Cont ID  
Sent By mjacobs Date 2007-04-23 Time 08:47 Rev Time 0.00
Received By mjacobs Date 2007-04-21 Time 14:30 Sent To PC
Notes
2007-04-21 14:41:24FBC. 2001
 RECEIVED 4/16/07.
  
 SUBMITTAL #03200.3716TH FL/ POUR #95 & 96. REBAR AND
 SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 278 Status P Date 2007-04-18 Cont ID  
Sent By mjacobs Date 2007-04-18 Time 14:56 Rev Time 0.00
Received By mjacobs Date 2007-04-18 Time 14:51 Sent To PC
Notes
2007-04-18 14:55:53FBC
  
 SHORING AND GC LETTER FOR POUR #96

Review Stop B BUILDING (STRUCTURAL)
Rev No 277 Status F Date 2007-04-18 Cont ID  
Sent By mjacobs Date 2007-04-18 Time 13:02 Rev Time 0.00
Received By mjacobs Date 2007-04-18 Time 12:22 Sent To PC
Notes
2007-04-18 13:02:54BUILDING PLAN REVIEW
 PERMIT:04120353
 ADD: 717 S. OLIVE AVE.
 CONT: KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SUBMITTALS.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE DESIGN PRESSURES FOR THE SENERFLEX WALL STATED
 IN THE NOA #02-1022.17 ARE 65 PSF AND 90 PSF. THE
 DESIGN PRESSURES STATED ON THE STRUCTURAL DRAWINGS IS
 120 PSF. SEE SHEET S-6.2 OF THE STRUCTURAL DRAWINGS.
 THE ES REPORT FOR THE SENERFLEX WALL SYSTEM (ADHERED)
 SEC. 4.1 AND 4.1.5 HAVE PRESSURES OF 30 PSF AND 54 PSF
 WHICH DOES MEET THE 120 PSF STATED ON THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 276 Status P Date 2007-04-18 Cont ID  
Sent By mjacobs Date 2007-04-18 Time 12:21 Rev Time 0.00
Received By mjacobs Date 2007-04-18 Time 12:12 Sent To PC
Notes
2007-04-18 12:18:04FBC.2001
  
 SHORING AND GC LETTER FOR POUR #95

Review Stop B BUILDING (STRUCTURAL)
Rev No 275 Status P Date 2007-04-18 Cont ID  
Sent By mjacobs Date 2007-04-18 Time 12:11 Rev Time 0.00
Received By mjacobs Date 2007-04-18 Time 12:02 Sent To PC
Notes
2007-04-18 12:11:38FBC.2001
  
 SHORING AND GC LETTER FOR POUR #94.

Review Stop B BUILDING (STRUCTURAL)
Rev No 274 Status P Date 2007-04-12 Cont ID  
Sent By mjacobs Date 2007-04-12 Time 06:47 Rev Time 0.00
Received By mjacobs Date 2007-04-12 Time 06:17 Sent To PC
Notes
2007-04-12 06:19:20FBC2001
  
 SUBMITTAL #09300.10. SOUND CONTROL CORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 273 Status P Date 2007-04-11 Cont ID  
Sent By mjacobs Date 2007-04-11 Time 18:31 Rev Time 0.00
Received By mjacobs Date 2007-04-11 Time 18:23 Sent To PC
Notes
2007-04-11 18:31:22FBC2001
  
 SUBMITTAL #09200.07FOR EXTERIOR ACCESS PANEL DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 272 Status P Date 2007-04-11 Cont ID  
Sent By mjacobs Date 2007-04-11 Time 18:22 Rev Time 0.00
Received By mjacobs Date 2007-04-11 Time 18:17 Sent To PC
Notes
2007-04-11 18:19:12FBC2001
  
 SHORING AND GC LETTER FOR POUR #92. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 271 Status P Date 2007-04-11 Cont ID  
Sent By mjacobs Date 2007-04-11 Time 18:17 Rev Time 0.00
Received By mjacobs Date 2007-04-11 Time 18:08 Sent To PC
Notes
2007-04-11 18:17:25FBC 2001
  
 SHORING AND GC LETTER FOR POUR #92. SENT TO JERELD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 270 Status F Date 2007-04-05 Cont ID  
Sent By mjacobs Date 2007-04-05 Time 09:47 Rev Time 0.00
Received By mjacobs Date 2007-04-05 Time 07:09 Sent To PC
Notes
2007-04-05 07:21:24BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S.OLIVE AVE.
 CONT: KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 W/ 2003 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW SUBMITTAL #11011.01.01 WINDOW WASHING
 EQUIPMENT SHOPS
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE ENGINEER WHO IS RESPONSIBLE FOR THE DESIGN
 SHALL SIGN,SEAL AND DATE THE DRAWINGS. THE CHM
 STRUCTURAL ENGINEER SHALL ALSO SIGN THE 8.5" X 11"
 SHEETS. F.A.C. 61G15-23.002 AND 471.025.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 269 Status P Date 2007-04-05 Cont ID  
Sent By mjacobs Date 2007-04-05 Time 08:20 Rev Time 0.00
Received By mjacobs Date 2007-04-05 Time 06:21 Sent To PC
Notes
2007-04-05 07:08:42FBC2001
  
 SUBMITTAL #07212.03 - INSULATION#09100.06 - FRAMING
 #09250.04 - DRYWALL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 268 Status P Date 2007-04-05 Cont ID  
Sent By mjacobs Date 2007-04-05 Time 06:06 Rev Time 0.00
Received By mjacobs Date 2007-04-05 Time 05:55 Sent To PC
Notes
2007-04-05 06:06:34FBC2001
  
 SHORING AND GC LETTER FOR POUR #91. SENT TO JERALD
 INBOX

Review Stop B BUILDING (STRUCTURAL)
Rev No 267 Status F Date 2007-04-04 Cont ID  
Sent By mjacobs Date 2007-04-04 Time 18:06 Rev Time 0.00
Received By mjacobs Date 2007-04-04 Time 16:57 Sent To PC
Notes
2007-04-04 18:02:12BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S.OLIVE AVE
 CONT: KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW SUBMITTAL #05100.05 EXHAUST SHAFT TRUSS
 DRAWINGS.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE ENGINEER SHALL INDICATE THE BOTTOM CHORD LIVE
 LOADPER FBC TABLE 1607.1 ON THE TRUSS DRAWINGS. THE
 BREAK CONNECTION DETAIL DRAWINGS SHALL ALSO BE SIGNED
 AND SEALED BY THE PERSON TAKING RESPONSIBILITY FOR
 THOSE DRAWINGS.THE RUBBER SEAL ON THE DRAWINGS ARE
 NOTORIGINAL SEAL. SEE F.A.C. 61G15-23.002/ FL.
 STATUTES 471.025.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 266 Status P Date 2007-04-04 Cont ID  
Sent By mjacobs Date 2007-04-04 Time 16:55 Rev Time 0.00
Received By mjacobs Date 2007-04-04 Time 15:34 Sent To PC
Notes
2007-04-04 16:55:04FBC 2001
  
 SUBMITTAL #09350.01CULTURED MARBLE PROCUCT

Review Stop B BUILDING (STRUCTURAL)
Rev No 265 Status P Date 2007-04-04 Cont ID  
Sent By mjacobs Date 2007-04-04 Time 14:29 Rev Time 0.00
Received By mjacobs Date 2007-04-04 Time 13:59 Sent To PC
Notes
2007-04-04 15:38:20FBC. 2001
  
 SUBMITTAL #09200.05SEALANT # EXTERIOR EIFS
 (SONOLASTIC 150 VLM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 264 Status P Date 2007-04-04 Cont ID  
Sent By mjacobs Date 2007-04-04 Time 12:52 Rev Time 0.00
Received By mjacobs Date 2007-04-04 Time 12:22 Sent To PC
Notes
2007-04-04 12:52:37FBC 2001
  
 SHORING AND GC LETTER FOR POUT #90. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 263 Status P Date 2007-03-30 Cont ID  
Sent By mjacobs Date 2007-03-30 Time 08:52 Rev Time 0.00
Received By mjacobs Date 2007-03-30 Time 08:19 Sent To PC
Notes
2007-03-30 08:52:13FBC 2001
  
 SUBMITTAL #03900.01 THIN - TOP SUPREME. FOR FLOOR
 REPAIRS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 262 Status F Date 2007-03-30 Cont ID  
Sent By mjacobs Date 2007-03-30 Time 07:46 Rev Time 0.00
Received By mjacobs Date 2007-03-30 Time 07:39 Sent To PC
Notes
2007-03-30 07:46:44BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S. OLIVE AVE
 CONT: KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW SUBMITTALS #03365.15FLOORS 17-20PT CABLE
 CALCS
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)SUBMIT AN INDEX SHEET FOR THE CALCULATIONS
 REFERENCEING EACH PAGE IN THE REPORT. SEE F.A.C.
 61G15-23.002(2)A COVER OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL
 ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX SO THAT THE USER WILL BE AWARE OF EACH
 PORTION OF THE SPECIFICATIONS FOR WHICH EACH
 PROFESSIONAL ENGINEER IS RESPONSIBLE.
  
 3)THE DRAWINGS SUBMITTED WITH THE PHOTO-COPIES SEAL
 AND SIGNATURE OF THE ENGINEER IS NOT ACCEPTABLE. A
 PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND AFFIX HIS
 SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS BEING FILED
 FOR PUBLIC RECORD.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 261 Status F Date 2007-03-30 Cont ID  
Sent By mjacobs Date 2007-03-30 Time 07:29 Rev Time 0.00
Received By mjacobs Date 2007-03-30 Time 06:25 Sent To PC
Notes
2007-03-30 07:29:39BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S. OLIVE AVE
 CONT: KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW SUBMITTALS #03365.1621ST FLOOR PT CABLE
 CALCS
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)SUBMIT AN INDEX SHEET FOR THE CALCULATIONS
 REFERENCEING EACH PAGE IN THE REPORT. SEE F.A.C.
 61G15-23.002(2)A COVER OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL
 ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX SO THAT THE USER WILL BE AWARE OF EACH
 PORTION OF THE SPECIFICATIONS FOR WHICH EACH
 PROFESSIONAL ENGINEER IS RESPONSIBLE.
  
 3)THE DRAWINGS SUBMITTED WITH THE PHOTO-COPIES SEAL
 AND SIGNATURE OF THE ENGINEER IS NOT ACCEPTABLE. A
 PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND AFFIX HIS
 SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS BEING FILED
 FOR PUBLIC RECORD.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 260 Status P Date 2007-03-30 Cont ID  
Sent By mjacobs Date 2007-03-30 Time 06:25 Rev Time 0.00
Received By mjacobs Date 2007-03-30 Time 06:00 Sent To PC
Notes
2007-03-30 06:05:11FBC2001
  
 SHORING AND GC LETTER FOR POUR #89. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 259 Status P Date 2007-03-29 Cont ID  
Sent By mjacobs Date 2007-03-29 Time 18:15 Rev Time 0.00
Received By mjacobs Date 2007-03-29 Time 18:09 Sent To PC
Notes
2007-03-29 18:09:56FBC 2001
  
 SUBMITTAL # 03900.02VINYL CONCRETE PATCHER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 258 Status P Date 2007-03-29 Cont ID  
Sent By mjacobs Date 2007-03-29 Time 18:07 Rev Time 0.00
Received By mjacobs Date 2007-03-29 Time 18:06 Sent To PC
Notes
2007-03-29 18:07:24FBC 2001
  
 SUBMITTAL #03900.03 BONSAL POLY-MOD CPMCRETE REPAIR
 MORTAR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 257 Status P Date 2007-03-29 Cont ID  
Sent By mjacobs Date 2007-03-29 Time 17:53 Rev Time 0.00
Received By mjacobs Date 2007-03-29 Time 17:47 Sent To  
Notes
2007-03-29 17:48:53FBC2001
  
 SHORING AND GC LETTER FOR POUR #88. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 256 Status F Date 2007-03-29 Cont ID  
Sent By mjacobs Date 2007-03-29 Time 17:40 Rev Time 0.00
Received By mjacobs Date 2007-03-29 Time 17:38 Sent To PC
Notes
2007-03-29 17:40:27BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEWSUBMITTAL/ RFI #517 SECONDARY SLAB
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)SEE NOTES FROM PREVIOUS REVIEW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 255 Status P Date 2007-03-29 Cont ID  
Sent By mjacobs Date 2007-03-29 Time 17:10 Rev Time 0.00
Received By mjacobs Date 2007-03-29 Time 16:52 Sent To PC
Notes
2007-03-29 17:10:25FBC. 2001
  
 SUBMITTAL #03200.35SHAREWALL SHOP LEVEL 17-20.

Review Stop B BUILDING (STRUCTURAL)
Rev No 254 Status F Date 2007-03-29 Cont ID  
Sent By mjacobs Date 2007-03-29 Time 13:22 Rev Time 0.00
Received By mjacobs Date 2007-03-29 Time 11:32 Sent To PC
Notes
2007-03-29 13:57:38BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S. OLIVE AVE
 CONT: KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:SUBMITTALS #05100.02 TRUSS STEEL
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)F.A.C.61G15-23.002 (2)A COVER OR INDEX SHEET
 FOR ENGINEERING SPECIFICATIONS MAY BE USED AND THAT
 SHEET MUST BE SIGNED, SEALED AND DATED BY THOSE
 PROFESSIONAL ENGINEERS IN RESPONSIBLE CHARGE OF THE
 PRODUCTION AND PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX SO THAT THE USER WILL BE
 AWARE OF EACH PORTION OF THE SPECIFICATIONS FOR WHICH
 EACH PROFESSIONAL ENGINEER IS RESPONSIBLE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 253 Status F Date 2007-03-29 Cont ID  
Sent By mjacobs Date 2007-03-29 Time 10:52 Rev Time 0.00
Received By mjacobs Date 2007-03-29 Time 10:19 Sent To PC
Notes
2007-03-29 10:52:11BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S.OLIVE AVE.
 CONT: KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW. SUBMITTALS
 ACTION: DENIED
  
 1)THE LETTER SUBMITTED FROM CECO DOOR PRODUCTS FOR
 THE FIRE DOORS AND WINDOWS SHALL REFERENCE THE CODES
 STANDARDS UNDER WHICH THE PERMIT WAS ISSUED. SEE FBC.
 2001 CH.35. (35.10) NFPA 80-95.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 252 Status N Date 2007-03-27 Cont ID  
Sent By mjacobs Date 2007-03-27 Time 12:21 Rev Time 0.00
Received By mjacobs Date 2007-03-27 Time 11:52 Sent To PC
Notes
2007-03-27 12:21:29FBC 2001
  
 SUBMITTAL #03200.36FLOORS 16 - 20 COLUMN,REBAR
 SHOPS DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 251 Status F Date 2007-03-27 Cont ID  
Sent By mjacobs Date 2007-03-27 Time 11:28 Rev Time 0.00
Received By mjacobs Date 2007-03-27 Time 09:53 Sent To PC
Notes
2007-03-27 11:27:49BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S. OLIVE AVE
 CONT: KAST CONSTRUCTION
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 SUBMITTAL #09100.05
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) THESE DRAWINGS HAS BEEN ALTERED, THEREFORE,THIS IS A
 REVISION AND NOT A SUBMITTAL. WHEN RESUBMITTION, PLEASE
 CHECK THE REVISION BOX ON THE SHEET. ALSO INDICATE ALL
 THE DIMENTIONS ON THE DRAWINGS. SEE PAGE TWO
  
 3) F.A.C. 61G15-23.001(1)THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS HAS ELEMINATED THE WORD
 CERTIFICATE FOR THE SEAL EFFECTIVE FEBRUARY 5, 2004. ON
 JANUARY 1, 2006, EVERY PROFESSIONAL ENGINEER MUST BE
 USING A NEW SEAL WITH THE WORD "LICENSE". THE ENGINEER
 HAS TO UPDATE HIS SEAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 250 Status F Date 2007-03-27 Cont ID  
Sent By mjacobs Date 2007-03-27 Time 07:54 Rev Time 0.00
Received By mjacobs Date 2007-03-27 Time 06:46 Sent To PC
Notes
2007-03-27 07:53:57BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S.OLIVE AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 SUBMITTAL #03365.14
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE NAME OF THE PROJECT IS TWO CITY PLAZA. NOT "TOW
 CITY PLAZA".
  
 3)F.A.C 61G15-23.002 (2)ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINES, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND DERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET.
  
 4)STATE THE YEAR OF THE FLORIDA BUILDING CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 249 Status F Date 2007-03-27 Cont ID  
Sent By mjacobs Date 2007-03-27 Time 06:42 Rev Time 0.00
Received By mjacobs Date 2007-03-27 Time 06:00 Sent To PC
Notes
2007-03-27 06:42:52BUILDING PLAN REVIEW
 PERMIT: 04120353
 ADD: 717 S.OLIVE AVE
 CONT: KAST CONSTRUCTION
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 SUBMITTAL #03100.24
 1)THE DRAWINGS HAS TO BE SIGNED, DATED AND SEALED BY
 THE ENGINEER.
 SEE FAC. 61G15-23.002.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 248 Status P Date 2007-03-26 Cont ID  
Sent By mjacobs Date 2007-03-26 Time 15:07 Rev Time 0.00
Received By mjacobs Date 2007-03-26 Time 15:04 Sent To PC
Notes
2007-03-26 15:07:18FBC2001
  
 SUBMITTAL #07830.03COUPLING THRU WALL ASSEMBLY @ 45
 DEGREE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 247 Status P Date 2007-03-26 Cont ID  
Sent By mjacobs Date 2007-03-26 Time 15:02 Rev Time 0.00
Received By mjacobs Date 2007-03-26 Time 12:20 Sent To  
Notes
2007-03-26 12:22:18FBC 2001
  
 SHORING AND GC LETTER FOR POUR #87. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 246 Status P Date 2007-03-26 Cont ID  
Sent By mjacobs Date 2007-03-26 Time 12:19 Rev Time 0.00
Received By mjacobs Date 2007-03-26 Time 12:11 Sent To  
Notes
2007-03-26 12:13:27FBC 2001
  
 SHORING AND GC LETTER FOR POUR #86. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 245 Status P Date 2007-03-26 Cont ID  
Sent By mjacobs Date 2007-03-26 Time 12:11 Rev Time 0.00
Received By mjacobs Date 2007-03-26 Time 12:08 Sent To  
Notes
2007-03-26 12:09:05FBC 2001
  
 SHORING AND GC LETTER FOR POUR #85. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 244 Status P Date 2007-03-26 Cont ID  
Sent By mjacobs Date 2007-03-26 Time 11:09 Rev Time 0.00
Received By mjacobs Date 2007-03-26 Time 10:26 Sent To  
Notes
2007-03-26 11:09:01FBC 2001
  
 SHORING AND GC LETTER FOR POUR # 84. SENT TOJERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 243 Status P Date 2007-03-16 Cont ID  
Sent By mjacobs Date 2007-03-16 Time 06:32 Rev Time 0.00
Received By mjacobs Date 2007-03-16 Time 06:27 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 242 Status P Date 2007-03-16 Cont ID  
Sent By mjacobs Date 2007-03-16 Time 06:25 Rev Time 0.00
Received By mjacobs Date 2007-03-16 Time 06:20 Sent To PC
Notes
2007-03-16 06:21:27FBC 2001
  
 SHORING AND GC LETTER FOR POUR #82. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 241 Status P Date 2007-03-16 Cont ID  
Sent By mjacobs Date 2007-03-16 Time 06:20 Rev Time 0.00
Received By mjacobs Date 2007-03-16 Time 06:14 Sent To PC
Notes
2007-03-16 06:15:22FBC 2001
  
 SHORING AND GC LETTER FOR POUR #81. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 240 Status P Date 2007-03-16 Cont ID  
Sent By mjacobs Date 2007-03-16 Time 06:13 Rev Time 0.00
Received By mjacobs Date 2007-03-16 Time 06:02 Sent To PC
Notes
2007-03-16 06:09:20FBC. 2001
  
 SHORING AND GC LETTERFOR POUR #80. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 239 Status P Date 2007-03-03 Cont ID  
Sent By mjacobs Date 2007-03-03 Time 17:34 Rev Time 0.00
Received By mjacobs Date 2007-03-03 Time 17:31 Sent To  
Notes
2007-03-03 17:34:25FBC; 2001
  
 SHORING AND FORMWORK LETTER FOR POUR #79. SENT TO
 JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 238 Status P Date 2007-03-03 Cont ID  
Sent By mjacobs Date 2007-03-03 Time 11:24 Rev Time 0.00
Received By mjacobs Date 2007-03-03 Time 11:09 Sent To  
Notes
2007-03-03 11:24:18FBC 2001
  
 SUBMITTAL #07120.12TREMPROOF 201 / 222

Review Stop B BUILDING (STRUCTURAL)
Rev No 237 Status P Date 2007-03-03 Cont ID  
Sent By mjacobs Date 2007-03-03 Time 11:01 Rev Time 0.00
Received By mjacobs Date 2007-03-03 Time 10:47 Sent To  
Notes
2007-03-03 11:01:01FBC : 2001
  
 SUBMITTAL #09200.04SILICONE SEALANTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 236 Status F Date 2007-03-03 Cont ID  
Sent By mjacobs Date 2007-03-03 Time 10:32 Rev Time 0.00
Received By mjacobs Date 2007-03-03 Time 09:39 Sent To PC
Notes
2007-03-03 10:30:26BUILDING PLAN REVIEW
 PERMIT:04120353
 ADD: 717 S. OLIVE AVE
 CONT: KOLTER CONST CO.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEWSUBMITTALS
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3) F.S481.221 (8) FINAL CONSTRUCTION DOCUMENTS
 PREPARED BY A REGISTERED ARCHITECT SHALL BE OF A
 SUFFICIENTLY HIGH STANDARD TO CLEARLY AND ACCURATELY
 INDICATE OR ILLUSTRATE ALL ESSENTIAL PARTS OF THE WORK
 TO WHICH THEY REFER.
  
 4)THESE DRAWINGS SHALL ALSO BE APPROVED BY THE
 ENGINEER OR ARCHITECT OF RECORD. SHOW A CROSS SECTION
 OF THE SECONDARY SLAB INDICATING THE THICKNESS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 235 Status P Date 2007-03-03 Cont ID  
Sent By mjacobs Date 2007-03-03 Time 09:38 Rev Time 0.00
Received By mjacobs Date 2007-03-03 Time 09:36 Sent To  
Notes
2007-03-03 09:38:13FBC : 2001
  
 SHORING AND FORMWORK LETTER FOR POUR #78. SENT TO
 JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 234 Status P Date 2007-03-03 Cont ID  
Sent By mjacobs Date 2007-03-03 Time 09:35 Rev Time 0.00
Received By mjacobs Date 2007-03-03 Time 09:25 Sent To  
Notes
2007-03-03 09:35:46FBC : 2001
  
 SHORING AND FORMWORK LETTER FOR POUR #77. SENT TO
 JERALD INBOX

Review Stop B BUILDING (STRUCTURAL)
Rev No 233 Status P Date 2007-03-03 Cont ID  
Sent By mjacobs Date 2007-03-03 Time 09:20 Rev Time 0.00
Received By mjacobs Date 2007-03-03 Time 08:43 Sent To  
Notes
2007-03-03 09:20:47FBC: 2001
  
 SHORING AND FORMWORK LETTER FOR POUR #76. SENT TO
 JERALD INBOX

Review Stop B BUILDING (STRUCTURAL)
Rev No 232 Status P Date 2007-02-24 Cont ID  
Sent By mjacobs Date 2007-02-24 Time 08:11 Rev Time 0.00
Received By mjacobs Date 2007-02-24 Time 08:08 Sent To  
Notes
2007-02-24 08:08:51FBC: 2001
  
 SHORING AND FORMWORK LETTER FOR POUR#75. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 231 Status P Date 2007-02-24 Cont ID  
Sent By mjacobs Date 2007-02-24 Time 08:00 Rev Time 0.00
Received By mjacobs Date 2007-02-24 Time 07:53 Sent To  
Notes
2007-02-24 07:53:48FBC: 2001
  
 SHORING AND FORMWORK LETTER FOR POUR#74. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 230 Status P Date 2007-02-24 Cont ID  
Sent By mjacobs Date 2007-02-24 Time 07:53 Rev Time 0.00
Received By mjacobs Date 2007-02-24 Time 07:47 Sent To  
Notes
2007-02-24 07:49:18FBC: 2001
  
 SHORING AND FORMWORK LETTER FOR POUR#73. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 229 Status   Date 2007-02-24 Cont ID  
Sent By mjacobs Date 2007-02-24 Time 07:42 Rev Time 0.00
Received By mjacobs Date 2007-02-24 Time 07:35 Sent To  
Notes
2007-02-24 07:42:52FBC: 2001
  
 SHORING AND FORMWORK LETTER FOR POUR#72. SENT TO JERALD
 INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 228 Status P Date 2007-02-12 Cont ID  
Sent By mjacobs Date 2007-02-12 Time 18:38 Rev Time 0.00
Received By mjacobs Date 2007-02-12 Time 18:32 Sent To  
Notes
2007-02-12 18:38:20FBC 2001
  
 SUBMITTAL #07212.02THERMO CON.SOUND AND
 CONDENSATION CONTROL

Review Stop B BUILDING (STRUCTURAL)
Rev No 227 Status P Date 2007-02-12 Cont ID  
Sent By mjacobs Date 2007-02-12 Time 18:32 Rev Time 0.00
Received By mjacobs Date 2007-02-12 Time 18:22 Sent To  
Notes
2007-02-12 18:32:15FBC 2001
  
 SHORING AND LETTER FOR POUR #71. SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 226 Status P Date 2007-02-12 Cont ID  
Sent By mjacobs Date 2007-02-12 Time 18:19 Rev Time 0.00
Received By mjacobs Date 2007-02-12 Time 18:17 Sent To  
Notes
2007-02-12 18:19:47FBC 2001
  
 SHORING AND LETTER FOR POUR #70 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 225 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 22:58 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 22:58 Sent To  
Notes
2007-02-11 22:59:41STRUCTURAL REVISION SUBMITTED ON 1/11/07.GENERAL
 REVISION/UPDATE OF STRUCTURAL PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 224 Status P Date 2007-02-05 Cont ID  
Sent By mjacobs Date 2007-02-05 Time 07:57 Rev Time 0.00
Received By mjacobs Date 2007-02-05 Time 07:48 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 223 Status P Date 2007-02-03 Cont ID  
Sent By mjacobs Date 2007-02-03 Time 15:33 Rev Time 0.00
Received By mjacobs Date 2007-02-03 Time 14:53 Sent To  
Notes
2007-02-03 14:56:49FBC 2001
  
 SUBMITTAL #03200.29.01REBAR AND SHOP DRAWINGS FOR
 FLS 10-15.

Review Stop B BUILDING (STRUCTURAL)
Rev No 222 Status P Date 2007-02-12 Cont ID  
Sent By mjacobs Date 2007-02-03 Time 14:53 Rev Time 0.00
Received By mjacobs Date 2007-02-03 Time 14:26 Sent To  
Notes
2007-02-03 14:39:00FBC2001
  
 SUBMITTAL #08815.01SHOWER DOOR ENCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 221 Status P Date 2007-02-03 Cont ID  
Sent By mjacobs Date 2007-02-03 Time 14:24 Rev Time 0.00
Received By mjacobs Date 2007-02-03 Time 14:20 Sent To  
Notes
2007-02-03 14:23:59FBC 2001
  
 SHORING LETTER FOR POUR #66SEND TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 220 Status P Date 2007-02-03 Cont ID  
Sent By mjacobs Date 2007-02-03 Time 14:19 Rev Time 0.00
Received By mjacobs Date 2007-02-03 Time 13:43 Sent To  
Notes
2007-02-03 14:17:54FBC 2001
  
 SUBMITTAL #07830.01TREMCO FIRESTOPPING DEATAILS FOR
 WATER CLOSETS FA-2136 AND FS-534F
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 219 Status P Date 2007-02-03 Cont ID  
Sent By mjacobs Date 2007-02-03 Time 13:37 Rev Time 0.00
Received By mjacobs Date 2007-02-03 Time 13:21 Sent To  
Notes
2007-02-03 13:23:25FBC : 2001
  
 SUBMITTAL #09900.02AIR PLENUM CONCRETE SEALER

Review Stop B BUILDING (STRUCTURAL)
Rev No 218 Status P Date 2007-02-03 Cont ID  
Sent By mjacobs Date 2007-02-03 Time 12:15 Rev Time 0.00
Received By mjacobs Date 2007-02-03 Time 11:29 Sent To  
Notes
2007-02-03 12:53:18FBC : 2001
  
 SUBMITTAL #10800.01TOILET ACCESSORIES AND PARTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 217 Status P Date 2007-02-03 Cont ID  
Sent By mjacobs Date 2007-02-03 Time 11:28 Rev Time 0.00
Received By mjacobs Date 2007-02-03 Time 11:03 Sent To  
Notes
2007-02-03 11:28:50FBC : 2001
  
 SUBMITTAL #07212.01INSULATION SPECIFICATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 216 Status P Date 2007-02-03 Cont ID  
Sent By mjacobs Date 2007-02-03 Time 10:55 Rev Time 0.00
Received By mjacobs Date 2007-02-03 Time 10:51 Sent To  
Notes
2007-02-03 10:55:11FBC : 2001
  
 SHORING LETTER FOR POUR #69. SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 215 Status P Date 2007-02-03 Cont ID  
Sent By mjacobs Date 2007-02-03 Time 10:51 Rev Time 0.00
Received By mjacobs Date 2007-02-03 Time 10:46 Sent To  
Notes
2007-02-03 10:47:49FBC : 2001
  
 SHORING LETTER FOR POUR #67. SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 214 Status P Date 2007-02-03 Cont ID  
Sent By mjacobs Date 2007-02-03 Time 10:45 Rev Time 0.00
Received By mjacobs Date 2007-02-03 Time 10:32 Sent To  
Notes
2007-02-03 10:42:19FBC :2001
  
 SHOING LETTER FOR POUR #68. SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 213 Status P Date 2007-02-03 Cont ID  
Sent By mjacobs Date 2007-01-29 Time 14:45 Rev Time 0.00
Received By mjacobs Date 2007-01-29 Time 13:58 Sent To  
Notes
2007-01-29 14:40:39FBC : 2001
  
 SUBMITTAL #03200.34SHEARWALL #1 TOWER 12 TO 17

Review Stop B BUILDING (STRUCTURAL)
Rev No 212 Status P Date 2007-01-24 Cont ID  
Sent By mjacobs Date 2007-01-24 Time 18:43 Rev Time 0.00
Received By mjacobs Date 2007-01-24 Time 18:17 Sent To PC
Notes
2007-01-24 18:30:03FBC : 2001
  
 SUBMITTAL #03200.31POURS FOR LANAI LEVEL/ SECONDARY
 COURT YARD/ PIERS, WALLS

Review Stop B BUILDING (STRUCTURAL)
Rev No 211 Status P Date 2007-01-24 Cont ID  
Sent By mjacobs Date 2007-01-24 Time 18:17 Rev Time 0.00
Received By mjacobs Date 2007-01-24 Time 18:00 Sent To PC
Notes
2007-01-24 18:06:12FBC : 2001
  
 SUBMITTAL #03200.3TOWER COLUMNS FOR FLOORS 11-16

Review Stop B BUILDING (STRUCTURAL)
Rev No 210 Status P Date 2007-01-24 Cont ID  
Sent By mjacobs Date 2007-01-24 Time 17:58 Rev Time 0.00
Received By mjacobs Date 2007-01-24 Time 17:49 Sent To PC
Notes
2007-01-24 17:58:08FBC : 2001
  
 SUBMITTAL FOR FORMWORK AND SHORING LETTERS FOR POUR #64

Review Stop B BUILDING (STRUCTURAL)
Rev No 209 Status P Date 2007-01-24 Cont ID  
Sent By mjacobs Date 2007-01-24 Time 17:48 Rev Time 0.00
Received By mjacobs Date 2007-01-24 Time 17:40 Sent To  
Notes
2007-01-24 17:48:37FBC: 2001
  
 SUBMITTAL OF SHORING AND FORMWORK LETTERS FOR DECK POUR
 #65

Review Stop B BUILDING (STRUCTURAL)
Rev No 208 Status P Date 2007-01-20 Cont ID  
Sent By mjacobs Date 2007-01-20 Time 09:05 Rev Time 0.00
Received By mjacobs Date 2007-01-20 Time 09:00 Sent To  
Notes
2007-01-20 09:04:57FBC: 2001
  
 SUBMITTAL #03300.27.6000 DCI 9" SLUMP

Review Stop B BUILDING (STRUCTURAL)
Rev No 207 Status P Date 2007-01-20 Cont ID  
Sent By mjacobs Date 2007-01-20 Time 08:15 Rev Time 0.00
Received By mjacobs Date 2007-01-20 Time 07:28 Sent To  
Notes
2007-01-20 08:15:42FBC : 2001
  
 SUBMITTAL #0330021.01MIX DESIGN #1347563 FOR PT DECK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 206 Status P Date 2007-01-20 Cont ID  
Sent By mjacobs Date 2007-01-20 Time 07:25 Rev Time 0.00
Received By mjacobs Date 2007-01-20 Time 07:22 Sent To  
Notes
2007-01-20 07:25:01FBC :2001
  
 SHORING AND FORMWORK LETTERS FOR POUR#62

Review Stop B BUILDING (STRUCTURAL)
Rev No 205 Status P Date 2007-01-20 Cont ID  
Sent By mjacobs Date 2007-01-20 Time 07:21 Rev Time 0.00
Received By mjacobs Date 2007-01-20 Time 07:16 Sent To  
Notes
2007-01-20 07:19:12FBC:2001
  
 SHORING AND FORMWORK LETTERS FOR POUR#63

Review Stop B BUILDING (STRUCTURAL)
Rev No 204 Status F Date 2007-01-18 Cont ID  
Sent By mjacobs Date 2007-01-18 Time 08:23 Rev Time 0.00
Received By mjacobs Date 2007-01-18 Time 07:05 Sent To PC
Notes
2007-01-18 08:23:32FBC; 2001
  
 SUBMITTAL #07830.01
  
 THE SUBMITTAL FOR THE WATER CLOSET FLOOR ASSEMBLY HAS
 TO BE REVIEWED BY THE ARCHITECT OF RECORD.PROVIDE A
 COPY OF THE THE FA-2136 UL LISTING. I SEARCH THE UL
 BOOK AND CANNOT FIND THIS LISTING NUMBER.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 203 Status P Date 2007-01-18 Cont ID  
Sent By mjacobs Date 2007-01-18 Time 06:46 Rev Time 0.00
Received By mjacobs Date 2007-01-18 Time 06:29 Sent To  
Notes
2007-01-18 06:46:49FBC:2001
  
 SUBMITTAL #04220.05EPOXY PRODUCT DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 202 Status P Date 2007-01-18 Cont ID  
Sent By mjacobs Date 2007-01-18 Time 06:21 Rev Time 0.00
Received By mjacobs Date 2007-01-18 Time 06:16 Sent To  
Notes
2007-01-18 06:21:31FBC: 2001
  
 SUBMITTA: POUR #61 SHORING AND FORMWORK LETTER FOR
 ELEVATED DECK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 201 Status P Date 2007-01-18 Cont ID  
Sent By mjacobs Date 2007-01-18 Time 06:06 Rev Time 0.00
Received By mjacobs Date 2007-01-16 Time 17:52 Sent To PC
Notes
2007-01-18 06:14:52FBC; 2001
  
 SUBMITTAL #09200.02- LATH/ STUCCO AND EXTERIOR
 FRAMING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 200 Status P Date 2007-01-10 Cont ID  
Sent By mjacobs Date 2007-01-10 Time 13:39 Rev Time 0.00
Received By mjacobs Date 2007-01-10 Time 13:37 Sent To  
Notes
2007-01-10 13:39:15FBC: 2001
  
 SUBMITTAL :SHORING AND FORMWORK FOR ELEVATED DECK
 POUR #60. SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 199 Status P Date 2007-01-09 Cont ID  
Sent By mjacobs Date 2007-01-09 Time 10:54 Rev Time 0.00
Received By mjacobs Date 2007-01-09 Time 09:48 Sent To  
Notes
2007-01-09 09:48:01FBC : 2001
  
 SUBMITTAL #09900.01.PAINT SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 198 Status P Date 2007-01-09 Cont ID  
Sent By mjacobs Date 2007-01-09 Time 09:02 Rev Time 0.00
Received By mjacobs Date 2007-01-09 Time 08:04 Sent To  
Notes
2007-01-09 08:11:32FBC: 2001
  
 SUBMITTAL #15100.03.01.FP-1 GROUND LEVEL & PARKING
 LEVEL P1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 197 Status P Date 2007-01-09 Cont ID  
Sent By mjacobs Date 2007-01-09 Time 08:03 Rev Time 0.00
Received By mjacobs Date 2007-01-09 Time 07:37 Sent To  
Notes
2007-01-09 07:44:47FBC: 2001
  
 SUBMITTAL: SHORING FORMWORK & LETTERS FOR ELEVATED DECK
 POUR #57.

Review Stop B BUILDING (STRUCTURAL)
Rev No 196 Status P Date 2007-01-09 Cont ID  
Sent By mjacobs Date 2007-01-09 Time 07:36 Rev Time 0.00
Received By mjacobs Date 2007-01-09 Time 07:12 Sent To  
Notes
2007-01-09 07:33:56FBC: 2001
  
 SUBMITTAL #08110.07. FIRELITE SPEC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 195 Status P Date 2007-01-09 Cont ID  
Sent By mjacobs Date 2007-01-09 Time 07:12 Rev Time 0.00
Received By mjacobs Date 2007-01-09 Time 06:54 Sent To  
Notes
2007-01-09 07:07:10FBC : 2001
  
 SUBMITTAL #09100.05.DIETRICH ULTRA STEEL FRAMING

Review Stop B BUILDING (STRUCTURAL)
Rev No 194 Status P Date 2007-01-09 Cont ID  
Sent By mjacobs Date 2007-01-09 Time 06:53 Rev Time 0.00
Received By mjacobs Date 2007-01-09 Time 06:35 Sent To  
Notes
2007-01-09 06:38:07FBC : 2001
  
 SUBMITTAL #05500.06 WIRE MESH PARTITION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 193 Status P Date 2007-01-09 Cont ID  
Sent By mjacobs Date 2007-01-09 Time 06:35 Rev Time 0.00
Received By mjacobs Date 2007-01-08 Time 16:49 Sent To  
Notes
2007-01-09 06:07:14FBC: 2001
  
 SUBMITTAL #03365.13. POST TENSION SHOP DRAWINGS FOR
 FLOORS 8-15. REVISED REBAR SHEET (PTT082)

Review Stop B BUILDING (STRUCTURAL)
Rev No 192 Status P Date 2007-01-08 Cont ID  
Sent By mjacobs Date 2007-01-08 Time 16:47 Rev Time 0.00
Received By mjacobs Date 2007-01-08 Time 16:44 Sent To  
Notes
2007-01-08 16:47:03FBC. 2001
  
 SUBMITTAL - SHORING AND FORMWORK FOR ELEVATED DECK POUR
 #58. SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 191 Status P Date 2007-01-08 Cont ID  
Sent By mjacobs Date 2007-01-08 Time 16:29 Rev Time 0.00
Received By mjacobs Date 2007-01-08 Time 16:23 Sent To  
Notes
2007-01-08 16:29:20FBC: 2001
  
 SUBMITTAL-SHORING AND FORMWORK LETTERS FOR ELEVATED
 DECK POUR #59. SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 190 Status P Date 2006-12-22 Cont ID  
Sent By mjacobs Date 2006-12-22 Time 16:40 Rev Time 0.00
Received By mjacobs Date 2006-12-22 Time 16:36 Sent To  
Notes
2006-12-22 16:39:01FBC : 2001
  
 SHORING AND FORMWORK LETTERS FOR POUR #56. SENT TO
 JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 189 Status P Date 2006-12-22 Cont ID  
Sent By mjacobs Date 2006-12-22 Time 16:32 Rev Time 0.00
Received By mjacobs Date 2006-12-22 Time 15:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 188 Status P Date 2006-12-22 Cont ID  
Sent By mjacobs Date 2006-12-22 Time 13:24 Rev Time 0.00
Received By mjacobs Date 2006-12-22 Time 13:19 Sent To  
Notes
2006-12-22 13:23:59FBC: 2001
  
 SUBMITTAL #09200.02LATH, STUCCO AND EXTERIOR FRAMING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 187 Status F Date   Cont ID  
Sent By   Date 2006-12-22 Time   Rev Time 0.00
Received By mjacobs Date 2006-12-22 Time 07:09 Sent To  
Notes
2006-12-22 07:36:48BUILDING PLAN REVIEW
 PERMIT:04120353
 ADD: 717 S. OLIVE AVE.
 CONT:KAST CONST.
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
 FBC:2001
 SUBMITTAL #09200.02LATH, STUCCO AND EXTERIORFRAMING.
 SECTION #8 OF THE PACKAGE
  
 ?1404.1.1 ARCHITECTURAL TRIM ON BUILDINGS OF TYPE I, II
 AND IV
 CONSTRUCTION NOT MORE THAN THREE STORIES OR 40 FT
 (12.2 M) HIGH MAY BE OF
 TYPE VI CONSTRUCTION, AND MAY BE OF TYPE VI
 CONSTRUCTION ON ALL BUILDINGS
 OF TYPE III, V AND VI CONSTRUCTION.TRIM SHALL BE
 SECURED TO THE WALL
 WITH METAL OR OTHER APPROVED BRACKETS OR FASTENERS.
 WHEN ARCHITECTURAL
 TRIM IS LOCATED ALONG THE TOP OF EXTERIOR WALLS, IT
 SHALL BE COMPLETELY
 BACKED BY THE EXTERIOR WALL AND SHALL NOT EXTEND OVER
 THE TOP OF EXTERIOR
 WALLS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 186 Status P Date 2006-12-22 Cont ID  
Sent By mjacobs Date 2006-12-22 Time 06:28 Rev Time 0.00
Received By mjacobs Date 2006-12-22 Time 06:00 Sent To  
Notes
2006-12-22 06:27:56FBC : 2001
  
 SUBMITTAL #08810.05.SEALANT, PRIMER, GROOUT AND
 TAPCONS PRODUCT DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 185 Status P Date 2006-12-19 Cont ID  
Sent By mjacobs Date 2006-12-19 Time 18:00 Rev Time 0.00
Received By mjacobs Date 2006-12-19 Time 17:39 Sent To  
Notes
2006-12-19 18:00:08FBC:2001
  
 SUBMITTAL #09900.01 PAINT

Review Stop B BUILDING (STRUCTURAL)
Rev No 184 Status P Date 2006-12-19 Cont ID  
Sent By mjacobs Date 2006-12-19 Time 17:38 Rev Time 0.00
Received By mjacobs Date 2006-12-19 Time 17:28 Sent To  
Notes
2006-12-19 17:35:02FBC :2001
  
 SHORING AND FORMWORK LETTERS FOR POUR #55.

Review Stop B BUILDING (STRUCTURAL)
Rev No 183 Status P Date 2006-12-16 Cont ID  
Sent By mjacobs Date 2006-12-16 Time 14:36 Rev Time 0.00
Received By mjacobs Date 2006-12-16 Time 14:07 Sent To PC
Notes
2006-12-16 14:10:10FBC : 2001
  
 SUBMITTAL #03365.13.POST TENSION CABLE SHOP
 DRAWINGS. LEVEL 8 THRU 15. CALCULATIONS ARE ALSO
 INCLUDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 182 Status P Date 2006-12-16 Cont ID  
Sent By mjacobs Date 2006-12-16 Time 13:57 Rev Time 0.00
Received By mjacobs Date 2006-12-16 Time 13:17 Sent To PC
Notes
2006-12-16 13:57:46FBC: 2001
  
 SUBMITTAL #03365.12POST TENSION CABLE SHOP DRAWINGS.
 7TH LEVEL - TOWER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 181 Status P Date 2006-12-16 Cont ID  
Sent By mjacobs Date 2006-12-16 Time 11:04 Rev Time 0.00
Received By mjacobs Date 2006-12-16 Time 10:31 Sent To PC
Notes
2006-12-16 13:04:41FBC:2001
  
 SUBMITTAL #09250.03 GOLD BOND GYPSUM WALL BOARD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 180 Status P Date 2006-12-16 Cont ID  
Sent By mjacobs Date 2006-12-16 Time 10:31 Rev Time 0.00
Received By mjacobs Date 2006-12-16 Time 10:19 Sent To  
Notes
2006-12-16 10:24:00FBC:2001
  
 SUBMITTAL #09250.02SHEETROCK READY MIX COMPOUND.

Review Stop B BUILDING (STRUCTURAL)
Rev No 179 Status P Date 2006-12-16 Cont ID  
Sent By mjacobs Date 2006-12-16 Time 10:19 Rev Time 0.00
Received By mjacobs Date 2006-12-16 Time 09:59 Sent To  
Notes
2006-12-16 10:05:18FBC: 2001
  
 SUBMITTAL #09100.03 RAMSET FASTENING SYSTEMS. ALSO
 GRABBER PAN HEAD STREAKER, GRABBER COARSE THREAD BLACK
 PHOSPHATE AND STREAKER FINE THREAD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 178 Status P Date 2006-12-16 Cont ID  
Sent By mjacobs Date 2006-12-16 Time 09:58 Rev Time 0.00
Received By mjacobs Date 2006-12-16 Time 09:35 Sent To  
Notes
2006-12-16 09:58:34FBC: 2001
  
 SUBMITTAL #09100.02 DIETRICH METAL FRAMING

Review Stop B BUILDING (STRUCTURAL)
Rev No 177 Status P Date 2006-12-16 Cont ID  
Sent By mjacobs Date 2006-12-16 Time 09:11 Rev Time 0.00
Received By mjacobs Date 2006-12-16 Time 09:03 Sent To  
Notes
2006-12-16 09:11:21FBC: 2001
  
 SHORING AND FORMWORK LETTERS FOR ELEVATED DECK POUR
 #54. SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 176 Status F Date 2006-12-14 Cont ID  
Sent By mjacobs Date 2006-12-14 Time 08:06 Rev Time 0.00
Received By mjacobs Date 2006-12-14 Time 08:04 Sent To PC
Notes
2006-12-14 08:06:01BUILDING PLAN REVIEW
 PERMIT:04120353
 ADD:717 S. OLIVE AVE.
 CONT:KASTCONSTRUCTION
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2NDRFI - 396
 ACTION: DENIED
  
  
 1) FBC.2001 SEC. 2101.2.CONSTRUCTION DOCUMENTS.
 DRAWINGS AND DETAILS SHALL SHOW ALL THE ITEMS REQUIRED
 TO BE SHOWN ON THE DRAWINGS BY THIS CODE INCLUDINGTHE
 FOLLOWING:
 4. PROVISION FOR DIMENSIONAL CHANGES RESULTING
 FROM ELASTIC DEFORMATION, CREEP, SHRINKAGE, TEMPERATURE
 AND MOISTURE.NOTE: CEMENT GROUT IS NOT A MATERIAL
 WHICH WILL MEET THE ELASTICITY DEFORMATION IN THIS
 SITUATION.CHOSE A MATERIAL WHICH WILL MEET THE FIRE
 RESISTANCE RATING OF THE WALL AND ELASTIC DEFORMATION.
  
 2)FBC.2001 SEC. 1604.5INTERIOR WALL LOADS.
 INTERIOR WALLS, PERMANENT PARTITIONS AND TEMPORARY
 PARTITIONS SHALL BE DESIGNED TO RESIST ALOADS TO
 WHICH THEY ARE SUBJECTED BUT NOT LESS THAN 5 PSF
 APPLIED PERPENDICULAR TO THE WALLS, EXCEPT FOR
 DECORATIVE SCREEN WALLS.
 ALSO SEE SEC. 703.2. FOR FIRE RESISTANCE RATINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 175 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 11:14 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 11:00 Sent To  
Notes
2006-12-07 11:04:45FBC : 2001
  
 SUBMITTAL #03200.32SHEARWALL AND REBAR DRAWINGS FOR
 LEVEL 8 THRU 11.

Review Stop B BUILDING (STRUCTURAL)
Rev No 174 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 10:56 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 10:40 Sent To  
Notes
2006-12-07 10:44:20FBC : 2001
  
 SUBMITTAL #09100.01BALCONY FRAMING @ LEVELS 1 THRU 4
 AND WEST ELEVATION FRAMING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 173 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 10:36 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 10:33 Sent To  
Notes
2006-12-07 10:36:49FBC : 2001
  
 SHORING AND FORMWORK LETTERS FOR POUR #53

Review Stop B BUILDING (STRUCTURAL)
Rev No 172 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 09:01 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 08:32 Sent To  
Notes
2006-12-07 08:46:24FBC : 2001
  
 SUBMITTAL #07830.01FIRESTOP DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 171 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 08:13 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 07:59 Sent To  
Notes
2006-12-07 08:13:18FBC : 2001
  
 SUBMITTAL # 03200.308TH FLOOR THRU 11TH FLOOR COLOMN
 SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 170 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 07:53 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 07:49 Sent To  
Notes
2006-12-07 07:51:57FBC : 2001
  
 SHORING AND FORMWORK LETTERS FOR POUR #50.

Review Stop B BUILDING (STRUCTURAL)
Rev No 169 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 07:49 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 07:19 Sent To  
Notes
2006-12-07 07:49:19FBC : 2001
  
 SUBMITTAL #03300.26PERLITE LIGHTWEIGHT CONCRETE. USED
 AT HOLLOW METAL FRAMES IN CONCRETE WALLS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 168 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 07:19 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 07:14 Sent To  
Notes
2006-12-07 07:19:15FBC : 2001
  
 SHORINGAND FORMWORK LETTERS FOR POUR #51

Review Stop B BUILDING (STRUCTURAL)
Rev No 167 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 07:14 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 07:04 Sent To  
Notes
2006-12-07 07:14:28FBC : 2001
  
 SHORING AND FORMWORK LETTERS FOR POUR #48.

Review Stop B BUILDING (STRUCTURAL)
Rev No 166 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 07:03 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 06:37 Sent To  
Notes
2006-12-07 07:03:31FBC : 2001
  
 SUBMITTAL #03200.29 PARKING LEVEL 7 THRU 15 REBAR SHOP
 DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 165 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 06:36 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 06:27 Sent To  
Notes
2006-12-07 06:36:43FBC :2001
  
 SUBMITTAL #03400.01.04CRANE SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 164 Status P Date 2006-12-07 Cont ID  
Sent By mjacobs Date 2006-12-07 Time 06:26 Rev Time 0.00
Received By mjacobs Date 2006-12-07 Time 05:48 Sent To  
Notes
2006-12-07 06:26:33FBC: 2001
  
 SUBMITTAL #05520.09.01 CALCULATIONS FOR STEEL PLATE
 SPIRAL STAIRS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 163 Status P Date 2006-12-06 Cont ID  
Sent By mjacobs Date 2006-12-06 Time 18:56 Rev Time 0.00
Received By mjacobs Date 2006-12-06 Time 18:31 Sent To  
Notes
2006-12-06 18:56:17FBC: 2001
  
 SUBMITTAL #05520.08.01STRAIGHT STAIRS. UNITS 1 THRU
 18

Review Stop B BUILDING (STRUCTURAL)
Rev No 162 Status P Date 2006-12-06 Cont ID  
Sent By mjacobs Date 2006-12-06 Time 18:31 Rev Time 0.00
Received By mjacobs Date 2006-12-06 Time 18:00 Sent To  
Notes
2006-12-06 18:31:12FBC: 2001
  
 SUBMITTAL#05520.07.01 FOR SPIRAL STAIRS. UNIT #7 - UNIT
 #11- UNIT #19

Review Stop B BUILDING (STRUCTURAL)
Rev No 161 Status P Date 2006-12-06 Cont ID  
Sent By mjacobs Date 2006-12-06 Time 17:56 Rev Time 0.00
Received By mjacobs Date 2006-12-06 Time 17:51 Sent To  
Notes
2006-12-06 17:56:13FBC:2001
  
 SUBMITTAL OF SHORING AND RESHORING LETTERS FOR POUR#52.
 SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 160 Status P Date 2006-12-06 Cont ID  
Sent By mjacobs Date 2006-12-06 Time 17:27 Rev Time 0.00
Received By mjacobs Date 2006-12-06 Time 17:26 Sent To  
Notes
2006-12-06 17:22:34FBC: 2001
  
 SUBMITTAL FOR SHORING AND FORMWORK LETTERS FOR POUR
 #49.SENT TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 159 Status F Date 2006-12-03 Cont ID  
Sent By rbrown Date 2006-12-03 Time 14:41 Rev Time 0.00
Received By rbrown Date 2006-12-03 Time 14:41 Sent To  
Notes
2006-12-03 14:58:31BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 DOOR AND WINDOW CALCULATIONS, PRODUCT APPROVAL AND SHOP
 DRAWINGS.
  
 1)ALL OF THE SUBMITTED PRODUCT APPROVALS HAVE BEEN
 REVIEWED AND STAMPED EXCEPT THE FOLLOWING:
 (A)GAMMA SERIES # 55.3 WINDOW WALL, SMALL MISSILE
 IMPACT - NO LOCAL/SITE SPECIFIC PRODUCT APPROVAL FORM
 OR TEST REPORT WAS SUBMITTED.SUBMIT A THREE COPIES OF
 THE PRODUCT APPROVAL FORM, WITH THE ORIGINAL SIGNATURE
 OF THE AUTHORIZED GAMMA U.S.A. REPRESENTATIVE, AND
 THREE COPIES OF THE PRODUCT TEST REPORT.THE SUBMITTED
 PRODUCT APPROVAL PACKAGE SHOULD BE SIMILAR TO THOSE
 THAT WERE SUBMITTED FOR THE REST OF THE DOORS/WINDOWS.
 (B)GAMMA SERIES # 66 SINGLE HUNG WINDOW, SMALL
 MISSILE IMPACT - NO LOCAL/SITE SPECIFIC PRODUCT
 APPROVAL FORM WAS SUBMITTED.SUBMIT A THREE COPIES OF
 THE PRODUCT APPROVAL FORM, WITH THE ORIGINAL SIGNATURE
 OF THE AUTHORIZED GAMMA U.S.A. REPRESENTATIVE.
  
 2) PROCESSING OF THE SHOP DRAWINGS CANNOT BE COMPLETED
 UNTIL THE ABOVE ITEMS ARE SUBMITTED.ALL THREE COPIES
 OF THE PARTIALLY STAMPED SHOP DRAWINGS MUST BE RETURNED
 WHEN RESUBMITTING.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 158 Status P Date 2006-11-16 Cont ID  
Sent By mjacobs Date 2006-11-16 Time 08:32 Rev Time 0.00
Received By mjacobs Date 2006-11-16 Time 07:56 Sent To PC
Notes
2006-11-16 08:31:22FBC: 2001
  
 SUBMITTAL #03200.26PARKING LEVEL 9 THRUTOWER LEVEL
 8 PARKING ANDTOWER COLUMN, REBAR SHOPS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 157 Status P Date 2006-11-16 Cont ID  
Sent By mjacobs Date 2006-11-16 Time 07:53 Rev Time 0.00
Received By mjacobs Date 2006-11-16 Time 07:17 Sent To PC
Notes
2006-11-16 07:25:47FBC: 2001
  
 SUBMITTAL #05520.06.01LOUVERS & GRILLS

Review Stop B BUILDING (STRUCTURAL)
Rev No 156 Status P Date 2006-11-16 Cont ID  
Sent By mjacobs Date 2006-11-16 Time 07:03 Rev Time 0.00
Received By mjacobs Date 2006-11-16 Time 06:29 Sent To PC
Notes
2006-11-16 07:03:22FBC : 2001
  
 SUBMITTAL #03200.28.REBAR SHOP DRAWINGS FOR 6TH FL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 155 Status P Date 2006-11-16 Cont ID  
Sent By mjacobs Date 2006-11-16 Time 06:28 Rev Time 0.00
Received By mjacobs Date 2006-11-16 Time 06:18 Sent To  
Notes
2006-11-16 06:22:57FBC: 2001
  
 SUBMITTAL LITTER FOR POUR #42. SEND TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 154 Status P Date 2006-11-16 Cont ID  
Sent By mjacobs Date 2006-11-16 Time 06:13 Rev Time 0.00
Received By mjacobs Date 2006-11-16 Time 05:57 Sent To  
Notes
2006-11-16 06:05:51FBC:2001
  
 SHORING LETTERS FOR POUR #44. SEND TO JERALD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 153 Status P Date 2006-11-15 Cont ID  
Sent By mjacobs Date 2006-11-15 Time 18:14 Rev Time 0.00
Received By mjacobs Date 2006-11-15 Time 18:10 Sent To  
Notes
2006-11-15 18:12:28FBC: 2001
  
 SHORING LETTER FOR POUR #43 TO JERELD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 152 Status P Date 2006-11-15 Cont ID  
Sent By mjacobs Date 2006-11-15 Time 18:10 Rev Time 0.00
Received By mjacobs Date 2006-11-15 Time 18:03 Sent To  
Notes
2006-11-15 18:05:46FBC: 2001
  
 SHORINGLETTER FOR POUR #45 TO JERELD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 151 Status P Date 2006-11-15 Cont ID  
Sent By mjacobs Date 2006-11-15 Time 18:03 Rev Time 0.00
Received By mjacobs Date 2006-11-15 Time 17:49 Sent To PC
Notes
2006-11-15 17:57:52FBC:2001
  
 SUBMITTAL #02520.01 PAVER PRODUCT DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 150 Status P Date 2006-11-15 Cont ID  
Sent By mjacobs Date 2006-11-15 Time 17:48 Rev Time 0.00
Received By mjacobs Date 2006-11-15 Time 17:37 Sent To  
Notes
2006-11-15 17:39:15FBC: 2001
  
 SHORING LETTER FOR POUR #46.SENT TO JERELD INBOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 149 Status P Date 2006-11-14 Cont ID  
Sent By mjacobs Date 2006-11-14 Time 18:46 Rev Time 0.00
Received By mjacobs Date 2006-11-14 Time 18:31 Sent To PC
Notes
2006-11-14 18:35:10FBC: 2001
  
 SUBMITTAL #03100.22SHORING SHOP DRAWINGS FOR FLOORS
 6-16 AND LOAD CALCULATIONS #FMI-1303.

Review Stop B BUILDING (STRUCTURAL)
Rev No 148 Status P Date 2006-11-14 Cont ID  
Sent By mjacobs Date 2006-11-14 Time 18:22 Rev Time 0.00
Received By mjacobs Date 2006-11-14 Time 17:46 Sent To PC
Notes
2006-11-14 18:00:40FBC:2001
  
 SUBMITTAL #03365.10.01POST TENSION SHOP DRAWINGS AND
 PRESTRESS FRICTION CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 147 Status P Date 2006-11-14 Cont ID  
Sent By mjacobs Date 2006-11-14 Time 13:18 Rev Time 0.00
Received By mjacobs Date 2006-11-14 Time 12:57 Sent To  
Notes
2006-11-14 13:17:22FBC: 2001
  
 SHORING AND RESHORING LETTERS FOR ELEVATED DECK POUR
 #47
 TO JERELD IN BOX

Review Stop B BUILDING (STRUCTURAL)
Rev No 146 Status P Date 2006-11-14 Cont ID  
Sent By mjacobs Date 2006-11-14 Time 12:55 Rev Time 0.00
Received By mjacobs Date 2006-11-14 Time 11:00 Sent To PC
Notes
2006-11-14 12:55:13FBC:2001
  
 SUBMITTAL #03365.11
 STUD RAIL SHOP DRAWINGS FOR 6TH FL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 145 Status P Date 2006-11-14 Cont ID  
Sent By mjacobs Date 2006-11-14 Time 10:54 Rev Time 0.00
Received By mjacobs Date 2006-11-14 Time 10:43 Sent To PC
Notes
2006-11-14 10:54:09FBC:2001
  
 SUBMITTAL #03100.21
 ARCH BEAM SHORING & SHOPS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 144 Status P Date 2006-11-14 Cont ID  
Sent By mjacobs Date 2006-11-14 Time 09:50 Rev Time 0.00
Received By mjacobs Date 2006-11-14 Time 09:33 Sent To PC
Notes
2006-11-14 09:50:22FBC:2001
  
 SUBMITTAL #03100.20.01
 POST SHORES (BOOM PUMP SHORING SHOPS).

Review Stop B BUILDING (STRUCTURAL)
Rev No 143 Status   Date   Cont ID  
Sent By rbrown Date   Time 13:23 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 13:23 Sent To  
Notes
2006-11-12 13:34:47SUBMITTAL FOR GAMMA U.S.A. DOOR/WINDOW DESIGN AND
 PRODUCT APPROVAL PACKAGE.
  
 GAMMA U.S.A. PLAN SHEET 1.04 STATES THAT NO PRESSURES
 COULD BE FOUND, IN THE WIND LOAD STUDY REPORT, FOR THE
 "SOUTH COURTYARD ELEVATION", AND LOADS OF +90/-90 PSF
 WERE USED.FIGURE 7 AND FIGURE 12 OF THE RWDI REPORT
 DO SHOW THE LOADS FOR SOUTH COURTYARD ELEVATION,
 HOWEVER THEY ARE LESS THAN +90/-90 PSF, SO RE-DESIGN IS
 NOT NECESSARY.
  
 ******PLAN REVIEW IN PROGRESS******

Review Stop B BUILDING (STRUCTURAL)
Rev No 142 Status F Date 2006-10-26 Cont ID  
Sent By mjacobs Date 2006-10-26 Time 18:17 Rev Time 0.00
Received By mjacobs Date 2006-10-26 Time 17:04 Sent To PC
Notes
2006-10-26 18:15:28BUILDING PLAN REVIEW
 PERMIT:04120353
 ADD:717 S. OLIVE AVE.
 CONT:KASTCONSTRUCTION
 TEL: (561)835-3890
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW RFI - 396
 ACTION: DENIED
  
  
 1) FBC.2001 SEC. 2101.2.CONSTRUCTION DOCUMENTS.
 DRAWINGS AND DETAILS SHALL SHOW ALL THE ITEMS REQUIRED
 TO BE SHOWN ON THE DRAWINGS BY THIS CODE INCLUDINGTHE
 FOLLOWING:
 4. PROVISION FOR DIMENSIONAL CHANGES RESULTING
 FROM ELASTIC DEFORMATION, CREEP, SHRINKAGE, TEMPERATURE
 AND MOISTURE.NOTE: CEMENT GROUT IS NOT A MATERIAL
 WHICH WILL MEET THE ELASTICITY DEFORMATION IN THIS
 SITUATION.CHOSE A MATERIAL WHICH WILL MEET THE FIRE
 RESISTANCE RATING OF THE WALL AND ELASTIC DEFORMATION.
  
 2)FBC.2001 SEC. 1604.5INTERIOR WALL LOADS.
 INTERIOR WALLS, PERMANENT PARTITIONS AND TEMPORARY
 PARTITIONS SHALL BE DESIGNED TO RESIST ALOADS TO
 WHICH THEY ARE SUBJECTED BUT NOT LESS THAN 5 PSF
 APPLIED PERPENDICULAR TO THE WALLS, EXCEPT FOR
 DECORATIVE SCREEN WALLS.
 ALSO SEE SEC. 703.2. FOR FIRE RESISTANCE RATINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 141 Status F Date 2006-10-13 Cont ID  
Sent By mjacobs Date 2006-10-13 Time 07:25 Rev Time 0.00
Received By mjacobs Date 2006-10-13 Time 07:07 Sent To PC
Notes
2006-10-13 07:25:47 
  
 1) F.S.471.025 AND F.A.C.61G15-23.002
 THE REGISTERED PROFESSIONALSHALL AFFIX HIS OR HER
 OFFICIAL SEAL,SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA AS REQUIRED BY
 FLORIDA STATUTE. HOWEVER, AND INDEX PAGE REFERENCEING
 ALL PAGES CAN BE SUBMITTED.
 NOTE: THE INFORMATION SUBMITTED ARE ALL PHOTO-COPIES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 140 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 16:50 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 16:34 Sent To  
Notes
2006-10-11 16:46:23FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR
 #39

Review Stop B BUILDING (STRUCTURAL)
Rev No 139 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 16:34 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 16:10 Sent To  
Notes
2006-10-11 16:25:29FBC: 2001.
 SHORING AND FORMWORKLETTERS FOR ELEVATED DECK AND
 POUR #38.

Review Stop B BUILDING (STRUCTURAL)
Rev No 138 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 16:10 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 16:05 Sent To  
Notes
2006-10-11 16:06:29FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR
 #37.

Review Stop B BUILDING (STRUCTURAL)
Rev No 137 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 16:04 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 15:53 Sent To  
Notes
2006-10-11 15:54:52FBC:2001
 SHORING AND FORMWORK LETTERS FOR ELEVATED DECK AND POUR
 #36

Review Stop B BUILDING (STRUCTURAL)
Rev No 136 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 15:51 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 15:40 Sent To  
Notes
2006-10-11 15:44:23FBC:2001
 SHORING AND FORMWORK LETTERFOR ELEVATED DECK AND POUR
 #35

Review Stop B BUILDING (STRUCTURAL)
Rev No 135 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 15:40 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 15:32 Sent To  
Notes
2006-10-11 15:34:58FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR
 #34.

Review Stop B BUILDING (STRUCTURAL)
Rev No 134 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 15:03 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 14:52 Sent To  
Notes
2006-10-11 14:59:31FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR
 #33

Review Stop B BUILDING (STRUCTURAL)
Rev No 133 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 14:51 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 14:50 Sent To  
Notes
2006-10-11 14:51:50FBC:2001.
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR
 #32

Review Stop B BUILDING (STRUCTURAL)
Rev No 132 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 14:50 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 14:36 Sent To  
Notes
2006-10-11 14:38:35FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR
 #31.

Review Stop B BUILDING (STRUCTURAL)
Rev No 131 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 14:35 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 14:21 Sent To  
Notes
2006-10-11 14:24:42FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR
 #30.

Review Stop B BUILDING (STRUCTURAL)
Rev No 130 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 14:15 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 14:10 Sent To  
Notes
2006-10-11 14:15:13FBC:2001.
 SHORING AND FORMWORK LETTER FOR ELEVATED DECKAND POUR
 #28.

Review Stop B BUILDING (STRUCTURAL)
Rev No 129 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 14:06 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 14:04 Sent To  
Notes
2006-10-11 14:06:02FBC:2001
 SHORING AND FORMWORK LETTERFOR ELEVATED DECK POUR
 #27.

Review Stop B BUILDING (STRUCTURAL)
Rev No 128 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 14:03 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:50 Sent To  
Notes
2006-10-11 13:58:48FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK AT LEVEL
 TWO AND POUR #26.

Review Stop B BUILDING (STRUCTURAL)
Rev No 127 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:49 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:47 Sent To  
Notes
2006-10-11 13:49:48FBC: 2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK AT LEVEL
 TWO POUR #25.

Review Stop B BUILDING (STRUCTURAL)
Rev No 126 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:47 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:42 Sent To  
Notes
2006-10-11 13:43:41FBC:2001
 SHORING AND FORMWORK LETTERS FOR ELEVATED DECK AT LEVEL
 TWO POUR #24.

Review Stop B BUILDING (STRUCTURAL)
Rev No 125 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:37 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:36 Sent To  
Notes
2006-10-11 13:37:35FBC:2001.
 SHORING AND FORMWORK LETTERS FOR ELEVATED DECK LEVEL
 TWO AND POUR #23.

Review Stop B BUILDING (STRUCTURAL)
Rev No 124 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:29 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:28 Sent To  
Notes
2006-10-11 13:29:48FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK AT LEVEL
 TWO POUR #22.

Review Stop B BUILDING (STRUCTURAL)
Rev No 123 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:26 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:24 Sent To  
Notes
2006-10-11 13:26:13FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK AT LEVEL
 TWO POUR #21.

Review Stop B BUILDING (STRUCTURAL)
Rev No 122 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:24 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:20 Sent To  
Notes
2006-10-11 13:23:59FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO
 AND POUR #20.

Review Stop B BUILDING (STRUCTURAL)
Rev No 121 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:20 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:15 Sent To  
Notes
2006-10-11 13:20:04FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO
 POUR #19.

Review Stop B BUILDING (STRUCTURAL)
Rev No 120 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:14 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:12 Sent To  
Notes
2006-10-11 13:14:04FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO
 AND POUR #17.

Review Stop B BUILDING (STRUCTURAL)
Rev No 119 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:12 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:10 Sent To  
Notes
2006-10-11 13:12:04FBC:2001
 SHORING AND FORMWORK LETTERFOR ELEVATED DECK LEVEL
 TWO POUR #16

Review Stop B BUILDING (STRUCTURAL)
Rev No 118 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:06 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:05 Sent To  
Notes
2006-10-11 13:06:27FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO
 AND POUR #15

Review Stop B BUILDING (STRUCTURAL)
Rev No 117 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:03 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:02 Sent To  
Notes
2006-10-11 13:03:16FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO
 AND POUR #14

Review Stop B BUILDING (STRUCTURAL)
Rev No 116 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:02 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 13:01 Sent To  
Notes
2006-10-11 13:02:02FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO
 AND POUR #14.

Review Stop B BUILDING (STRUCTURAL)
Rev No 115 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 13:00 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 12:58 Sent To  
Notes
2006-10-11 13:00:30FBC:2001
 SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO
 POUR #13.

Review Stop B BUILDING (STRUCTURAL)
Rev No 114 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 12:57 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 12:56 Sent To  
Notes
2006-10-11 12:57:44FBC:2001
 SHORING AND FORMWORK LETTERS FOR ELEVATED DECK LEVEL
 TWO POUR #12

Review Stop B BUILDING (STRUCTURAL)
Rev No 113 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 12:52 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 12:45 Sent To  
Notes
2006-10-11 12:52:26FBC:2001
 SHORINGAND FORMWORK LETTER FOR ELEVATED DECK AT LEVEL
 TWO POUR #11.

Review Stop B BUILDING (STRUCTURAL)
Rev No 112 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 12:39 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 12:36 Sent To  
Notes
2006-10-11 12:39:31FBC:2001
 SHORING AND FORMWORK LETTERS FOR LEVEL TWOELEVATED
 DECK POUR #10.

Review Stop B BUILDING (STRUCTURAL)
Rev No 111 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 11:19 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 11:17 Sent To  
Notes
2006-10-11 11:19:10FBC:2001
 SHORING AND FORMWORK LETTER FOR LEVEL TWO ELEVATED DECK
 POUR #7.

Review Stop B BUILDING (STRUCTURAL)
Rev No 110 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 11:17 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 11:15 Sent To  
Notes
2006-10-11 11:17:30FBC:2001
 SHORING/FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO
 POUR #6B

Review Stop B BUILDING (STRUCTURAL)
Rev No 109 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 11:15 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 11:13 Sent To  
Notes
2006-10-11 11:15:38FBC:2001
 SHORING/FORMWORD LETTER FOR ELEVATED DECK LEVEL TWO
 POUR #6

Review Stop B BUILDING (STRUCTURAL)
Rev No 108 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 11:13 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 11:10 Sent To  
Notes
2006-10-11 11:13:12FBC:2001
 SHORING/FORMWORK LETTER FOR LEVEL TWO POUR #5

Review Stop B BUILDING (STRUCTURAL)
Rev No 107 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 11:10 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 11:07 Sent To  
Notes
2006-10-11 11:10:10FBC:2001
 SHORING LETTER FOR LEVEL TWO POUR #4

Review Stop B BUILDING (STRUCTURAL)
Rev No 106 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 08:35 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 08:22 Sent To  
Notes
2006-10-11 08:23:55FBC:2001
 SUBMITTAL #03100.06.01. MEZZANINE POUR 5 AND 6. SHORING
 AND SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 105 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 06:58 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 06:54 Sent To  
Notes
2006-10-11 06:58:26FBC:2001
 SUBMITTAL #05500.01.CORNER GUARDS/FPL SUMP PIT FRAME
 AND COVER.
 ELEVATOR SUMP PIT FRAME AND COVER. ELEVATOR SEPERATOR
 BEAMS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 104 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 06:53 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 06:46 Sent To  
Notes
2006-10-11 06:48:14FBC:2001
 SUBMITTAL #07120.02. THOROSEAL DATA. USED AT
 FOUNDATION WALLS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 103 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 06:46 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 06:25 Sent To  
Notes
2006-10-11 06:46:17FBC:2001
 SUBMITTAL #02400.05 ALUMINUM WEIR SHOP DRAWINGS FOR
 CONTROL STRUCTURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 102 Status P Date 2006-10-11 Cont ID  
Sent By mjacobs Date 2006-10-11 Time 06:25 Rev Time 0.00
Received By mjacobs Date 2006-10-11 Time 06:23 Sent To  
Notes
2006-10-11 06:25:34FBC:2001
 SUBMITTAL #05500.04 BOLLARD SYSTEM AT PARKING GARAGE

Review Stop B BUILDING (STRUCTURAL)
Rev No 101 Status P Date 2006-10-10 Cont ID  
Sent By mjacobs Date 2006-10-10 Time 13:44 Rev Time 0.00
Received By mjacobs Date 2006-10-10 Time 13:41 Sent To  
Notes
2006-10-10 13:44:02FBC:2001
 SUBMITTAL #03100.08. TYPICAL ELEVATOR BEAM FORMING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 100 Status P Date 2006-10-10 Cont ID  
Sent By mjacobs Date 2006-10-10 Time 13:01 Rev Time 0.00
Received By mjacobs Date 2006-10-10 Time 11:20 Sent To  
Notes
2006-10-10 13:01:50FBC:2001
 SUBMITTAL # 04220.01MORTA,MIX DESIGN FOR GROUT-3000
 PSI. PRE-CAST LIINTELS/DOVETAILS- 20 GAUGE (MIN)
 HORIXONTAL REINFORCEMENTS-9 GUAGE, CMU PRODUCT DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 99 Status P Date 2006-10-10 Cont ID  
Sent By mjacobs Date 2006-10-10 Time 08:45 Rev Time 0.00
Received By mjacobs Date 2006-10-10 Time 06:48 Sent To  
Notes
2006-10-10 07:10:51FBC:2001
 SUBMITTAL #14210.01 ELEVATORS SHOP DRAWINGS FOR FLOORS
 1 THRU 7.

Review Stop B BUILDING (STRUCTURAL)
Rev No 98 Status P Date 2006-10-09 Cont ID  
Sent By mjacobs Date 2006-10-09 Time 12:28 Rev Time 0.00
Received By mjacobs Date 2006-10-09 Time 12:18 Sent To  
Notes
2006-10-09 12:28:21FBC:2001
 SUBMITTAL #03200.25. FOR LANAI REBAR SHOP DRAWINGS
 INCLUDING ARCH BEAMS, MASONRY AND DECK STEEL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 97 Status P Date 2006-10-09 Cont ID  
Sent By mjacobs Date 2006-10-09 Time 12:17 Rev Time 0.00
Received By mjacobs Date 2006-10-09 Time 12:15 Sent To  
Notes
2006-10-09 12:17:15FBC:2001
 SUBMITTAL #03200.24 PARKING LEVEL #9 DECK REBAR AND
 SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 96 Status P Date 2006-10-09 Cont ID  
Sent By mjacobs Date 2006-10-09 Time 12:12 Rev Time 0.00
Received By mjacobs Date 2006-10-09 Time 12:07 Sent To  
Notes
2006-10-09 12:12:47FBC:2001
 SUBMITTAL #03200.22FOR TIE COLUMNS/TIE BEAM AND
 MASONRY REBAR DRAWINGS FOR FLOORS 3 AND 4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 95 Status P Date 2006-10-09 Cont ID  
Sent By mjacobs Date 2006-10-09 Time 12:04 Rev Time 0.00
Received By mjacobs Date 2006-10-09 Time 11:59 Sent To  
Notes
2006-10-09 12:04:21FBC:2001
 SUBMITTAL #03200.21 FOR PARKING LEVEL 8 TOWER LEVEL 4
 REBAR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 94 Status P Date 2006-10-09 Cont ID  
Sent By mjacobs Date 2006-10-09 Time 11:59 Rev Time 0.00
Received By mjacobs Date 2006-10-09 Time 11:57 Sent To  
Notes
2006-10-09 11:59:20FBC: 2001
 SUBMITTAL #03200.20 FOR PARKING LEVEL 7. DECK REBAR AND
 BEAMS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 93 Status P Date 2006-10-09 Cont ID  
Sent By mjacobs Date 2006-10-09 Time 11:55 Rev Time 0.00
Received By mjacobs Date 2006-10-09 Time 11:52 Sent To  
Notes
2006-10-09 11:55:50FBC:2001
 SUBMITTAL #03200.18 PARKING LEVEL 5 POUR 17.
 BEAMS/BOTTOM/MISC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 92 Status P Date 2006-10-09 Cont ID  
Sent By mjacobs Date 2006-10-09 Time 11:38 Rev Time 0.00
Received By mjacobs Date 2006-10-09 Time 11:26 Sent To  
Notes
2006-10-09 11:38:10FBC:2001
 SUBMITTAL #03200.23LEVEL 4 TIE COLUMNS-TIE BEAMS AND
 MASORNRY REBAR

Review Stop B BUILDING (STRUCTURAL)
Rev No 91 Status P Date 2006-10-09 Cont ID  
Sent By mjacobs Date 2006-10-09 Time 11:25 Rev Time 0.00
Received By mjacobs Date 2006-10-09 Time 11:20 Sent To  
Notes
2006-10-09 11:24:40FBC:2001
 SUBMITTAL #03200.17 SHEAR WALL REBAR. SHOP DRAWINGS
 POUR 8 TOWER LEVEL 9.

Review Stop B BUILDING (STRUCTURAL)
Rev No 90 Status P Date 2006-10-06 Cont ID  
Sent By mjacobs Date 2006-10-06 Time 16:34 Rev Time 0.00
Received By mjacobs Date 2006-10-06 Time 15:29 Sent To  
Notes
2006-10-06 00:00:00FBC:2001
 SUBMITTAL #03200.19 PARKING LEVEL P6 AND
 3RD FLOOR DECK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 89 Status P Date 2006-10-06 Cont ID  
Sent By mjacobs Date 2006-10-06 Time 15:28 Rev Time 0.00
Received By mjacobs Date 2006-10-06 Time 14:05 Sent To  
Notes
2006-10-06 00:00:00FBC:2001
 SUBMITTAL #03200.14 TIE COLOMNS TIE
 BEAMS AND MASONRY FILL CELLS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 88 Status P Date 2006-10-06 Cont ID  
Sent By mjacobs Date 2006-10-06 Time 11:31 Rev Time 0.00
Received By mjacobs Date 2006-10-06 Time 08:43 Sent To  
Notes
2006-10-06 00:00:00FBC:2001
 SUBMITTAL #03200.15 TOWER AND PK6
 COLUMNS P5 TO P9

Review Stop B BUILDING (STRUCTURAL)
Rev No 87 Status P Date 2006-10-05 Cont ID  
Sent By mjacobs Date 2006-10-05 Time 18:23 Rev Time 0.00
Received By mjacobs Date 2006-10-05 Time 17:00 Sent To  
Notes
2006-10-05 00:00:00FBC:2001
 SUBMITTAL #03200.11.01 FOR TIE COLOMNS/
 TIE BEAMS AND MASONRY FILL CELLS
 FDN-LEVEL 2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 86 Status P Date 2006-10-05 Cont ID  
Sent By mjacobs Date 2006-10-05 Time 09:46 Rev Time 0.00
Received By mjacobs Date 2006-10-05 Time 08:58 Sent To  
Notes
2006-10-05 00:00:00FBC:2001
 SUBMITTAL #08110.03 FOR COMMON AREA
 DOORS/FRAMES AND HARDWARE. FLOORS 5 THRU
 ROOF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 85 Status P Date 2006-10-05 Cont ID  
Sent By mjacobs Date 2006-10-05 Time 08:57 Rev Time 0.00
Received By mjacobs Date 2006-10-05 Time 08:27 Sent To  
Notes
2006-10-05 00:00:00FBC:2001
 SUBMITTAL #03300.25 FOR 6000 PSI IN 28
 DAYS PEAROCK PUMP MIX. MIX CODE 1176167

Review Stop B BUILDING (STRUCTURAL)
Rev No 84 Status P Date 2006-10-05 Cont ID  
Sent By mjacobs Date 2006-10-05 Time 08:27 Rev Time 0.00
Received By mjacobs Date 2006-10-05 Time 08:12 Sent To  
Notes
2006-10-05 00:00:00FBC:2001
 SUBMITTAL #02361.01.01. SOIL TREATMENT
 DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 83 Status P Date 2006-10-05 Cont ID  
Sent By mjacobs Date 2006-10-05 Time 08:02 Rev Time 0.00
Received By mjacobs Date 2006-10-05 Time 07:40 Sent To  
Notes
2006-10-05 00:00:00FBC:2001
 SUBMITTAL #01780.01 SPEFIC PURPOSE
 SURVEY. BUILDING TIE IN AS-BUILT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 82 Status P Date 2006-10-05 Cont ID  
Sent By mjacobs Date 2006-10-05 Time 07:26 Rev Time 0.00
Received By mjacobs Date 2006-10-05 Time 06:52 Sent To  
Notes
2006-10-05 00:00:00FBC:2001
 SUBMITTAL #03100.14. VAPOR BARRIER FOR
 SLAB ON GRADE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 81 Status P Date 2006-10-05 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 18:56 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 18:51 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #09300.02 FOR MATERIAL SPECS
 AND MSDS SHEETS FOR CERAMIC TILE AND
 STONE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 80 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 18:50 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 18:17 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #05500.05. FOR HOIST BEAM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 79 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 18:16 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 18:07 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #03100.17. FOR HARE-ROK
 CEMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 78 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 18:07 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 17:58 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #03100.18. FOR SONOGROUT 10K.

Review Stop B BUILDING (STRUCTURAL)
Rev No 77 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 17:58 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 16:55 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #11170.01.02. FOR CHUTE FED
 COMPACTORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 76 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 16:38 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 16:30 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #15500.01M. MECHANICAL ACCESS
 PANELS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 75 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 13:02 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 11:52 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #07140.01 IRON WATERPELLER

Review Stop B BUILDING (STRUCTURAL)
Rev No 74 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 11:52 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 11:40 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #07120.09 ROOT BARRIER LOCATED
 AT PLANTER AREAS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 73 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 11:39 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 11:21 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #07120.08 TREMDRAIN 1000.
 DRAIN MAT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 72 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 11:11 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 11:09 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #07120.05 SIKAFLEX -2C NS/SL

Review Stop B BUILDING (STRUCTURAL)
Rev No 71 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 11:06 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 10:26 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #07120.06 VULKEM 350/345/346
 ELASTOMERIC,WATERPROOF TRAFFIC BEARING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 70 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 10:24 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 09:49 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL SHORING,FORMWORK AND GC
 LETTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 69 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 09:48 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 07:38 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #07120.04 CHEM-TRETE BSM 40
 VOC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 68 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 07:29 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 07:10 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #07120.03 VULKEN 450. FLUID
 APPLIED WATERPROOFING MEMBRANE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 67 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 07:09 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 07:00 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #08110.01.02 DOOR SCHEDULE &
 HARDWARE SCHEDULE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 66 Status P Date 2006-10-04 Cont ID  
Sent By mjacobs Date 2006-10-04 Time 06:47 Rev Time 0.00
Received By mjacobs Date 2006-10-04 Time 06:21 Sent To  
Notes
2006-10-04 00:00:00FBC:2001
 SUBMITTAL #03200.16 OE SHINY GALV.

Review Stop B BUILDING (STRUCTURAL)
Rev No 65 Status P Date 2006-10-03 Cont ID  
Sent By mjacobs Date 2006-10-03 Time 13:44 Rev Time 0.00
Received By mjacobs Date 2006-10-03 Time 13:14 Sent To  
Notes
2006-10-03 00:00:00FBC:2001
 SUBMITTAL #07120.07. VULKEM 350/351.
 SLIP-RESISTANT PEDESTRIAN WATEPROOFING
 SYSTEM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 64 Status P Date 2006-10-03 Cont ID  
Sent By mjacobs Date 2006-10-03 Time 11:53 Rev Time 0.00
Received By mjacobs Date 2006-10-03 Time 11:10 Sent To  
Notes
2006-10-03 00:00:00FBC:2001
 SUBMITTAL #03100.12. EXPANSION JOINT
 MATERIAL PRODUCT DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 63 Status P Date 2006-10-03 Cont ID  
Sent By mjacobs Date 2006-10-03 Time 11:09 Rev Time 0.00
Received By mjacobs Date 2006-10-03 Time 10:54 Sent To  
Notes
2006-10-03 00:00:00FBC:2001
 SUBMITTAL #03100.10. HILTI DATA SHEETS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 62 Status P Date 2006-10-03 Cont ID  
Sent By mjacobs Date 2006-10-03 Time 10:43 Rev Time 0.00
Received By mjacobs Date 2006-10-03 Time 10:27 Sent To  
Notes
2006-10-03 00:00:00FBC:2001
 SUBMITTAL #03300.24. VERTICAL/OVERHEAD
 CONCRETE REPAIR SYSTEM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 61 Status P Date 2006-10-03 Cont ID  
Sent By mjacobs Date 2006-10-03 Time 10:27 Rev Time 0.00
Received By mjacobs Date 2006-10-03 Time 09:33 Sent To  
Notes
2006-10-03 00:00:00FBC:2001
 SUBMITTAL #03100.11 FOAM DATA SHEETS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 60 Status P Date 2006-10-03 Cont ID  
Sent By mjacobs Date 2006-10-03 Time 08:59 Rev Time 0.00
Received By mjacobs Date 2006-10-03 Time 08:54 Sent To  
Notes
2006-10-03 00:00:00FBC:2001
 SUBMITTAL SHORING AND FORMWORK FOR
 ELEVATED DECK POUR #9. LEVEL #2.
 INSPECTION LETTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 59 Status P Date 2006-10-03 Cont ID  
Sent By mjacobs Date 2006-10-03 Time 08:53 Rev Time 0.00
Received By mjacobs Date 2006-10-03 Time 08:34 Sent To  
Notes
2006-10-03 00:00:00FBC:2001
 SUBMITTAL #03100.13. DOVETAIL SLOTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 58 Status P Date 2006-10-03 Cont ID  
Sent By mjacobs Date 2006-10-03 Time 08:34 Rev Time 0.00
Received By mjacobs Date 2006-10-03 Time 07:44 Sent To  
Notes
2006-10-03 00:00:00FBC:2001
 SUBMITTAL #03200.23. CONCRETE MIX CODE
 #1163512. 6000 PSI IN 28 DAYS. PARKING
 TOWER ELEVATED DECKS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 57 Status P Date 2006-10-03 Cont ID  
Sent By mjacobs Date 2006-10-03 Time 07:43 Rev Time 0.00
Received By mjacobs Date 2006-10-03 Time 07:10 Sent To  
Notes
2006-10-03 00:00:00FBC:2001
 SUBMITTAL #03365.04. TYPICAL LEVEL
 4TH,6TH AND 8TH PARKING SHOP DRAWINGS
 AND CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 56 Status P Date 2006-10-03 Cont ID  
Sent By mjacobs Date 2006-10-03 Time 07:10 Rev Time 0.00
Received By mjacobs Date 2006-10-03 Time 06:15 Sent To  
Notes
2006-10-03 00:00:00FBC:2001
 SUBMITTAL #03365.05. PARKING LEVEL 5TH
 AND 7TH PRESTRESS FRICTION CALCULATIONS
 AND DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 55 Status P Date 2006-10-02 Cont ID  
Sent By mjacobs Date 2006-10-02 Time 18:49 Rev Time 0.00
Received By mjacobs Date 2006-10-02 Time 18:22 Sent To  
Notes
2006-10-02 00:00:00FBC:2001
 SUBMITTAL #03365.07. PARKING LEVEL #9
 POST TENSION CABLE CALCULATIONS AND SHOP
 DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 54 Status P Date 2006-10-02 Cont ID  
Sent By mjacobs Date 2006-10-02 Time 18:07 Rev Time 0.00
Received By mjacobs Date 2006-10-02 Time 17:39 Sent To  
Notes
2006-10-02 00:00:00FBC:2001
 SUBMITTAL #03365.09 LANAI LEVEL
 PRESTRESS FRICTION CALCULATIONS AND
 POSTTENTION SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 53 Status P Date 2006-10-02 Cont ID  
Sent By mjacobs Date 2006-10-02 Time 09:48 Rev Time 0.00
Received By mjacobs Date 2006-10-02 Time 08:21 Sent To  
Notes
2006-10-02 00:00:00FBC:2001
 SUBMITTAL #03365.03 3RD LEVEL PARKING
 PRESTRESS FRICTION CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 52 Status P Date 2006-10-02 Cont ID  
Sent By mjacobs Date 2006-10-02 Time 08:21 Rev Time 0.00
Received By mjacobs Date 2006-10-02 Time 07:43 Sent To  
Notes
2006-10-02 00:00:00FBC:2001
 SUBMITTAL #03100.03 SPEED DOWELS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 51 Status P Date 2006-10-02 Cont ID  
Sent By mjacobs Date 2006-10-02 Time 07:43 Rev Time 0.00
Received By mjacobs Date 2006-10-02 Time 07:15 Sent To  
Notes
2006-10-02 00:00:00FBC:2001
 SUBMITTAL #03300.05 DESIGN MIX 1160713
 3000 PSI IN 28 DAYS. PEAROCK PUMPMIX
 WITH FIBER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 50 Status P Date 2006-10-02 Cont ID  
Sent By mjacobs Date 2006-10-02 Time 07:15 Rev Time 0.00
Received By mjacobs Date 2006-10-02 Time 06:56 Sent To  
Notes
2006-10-02 00:00:00FBC:2001
 SUBMITTAL #03300.04. DESIGN MIX 1179568
 3000 PSI IN 28 DAYS. SIDEWINDER WITH
 HRWR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 49 Status P Date 2006-10-02 Cont ID  
Sent By mjacobs Date 2006-10-02 Time 06:55 Rev Time 0.00
Received By mjacobs Date 2006-10-02 Time 06:33 Sent To  
Notes
2006-10-02 00:00:00FBC:2001
 SUBMITTAL #03300.03. DESIGN MIX 1313469
 3000 PSI IN 28 DAYS. FINE MASONRY GROUT
 WITH HRWR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 48 Status P Date 2006-10-02 Cont ID  
Sent By mjacobs Date 2006-10-02 Time 06:30 Rev Time 0.00
Received By mjacobs Date 2006-10-02 Time 06:16 Sent To  
Notes
2006-10-02 00:00:00FBC:2001
 SUBMITTAL #04220.02. NON- SHRINK GROUT
 FOR REPAIRS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 47 Status P Date 2006-09-30 Cont ID  
Sent By mjacobs Date 2006-09-30 Time 15:20 Rev Time 0.00
Received By mjacobs Date 2006-09-30 Time 15:00 Sent To  
Notes
2006-09-30 00:00:00FBC:2001
 SUBMITTAL #03300.23. CURING COMPOUND.

Review Stop B BUILDING (STRUCTURAL)
Rev No 46 Status P Date 2006-09-30 Cont ID  
Sent By mjacobs Date 2006-09-30 Time 14:51 Rev Time 0.00
Received By mjacobs Date 2006-09-30 Time 14:23 Sent To  
Notes
2006-09-30 00:00:00FBC:2001
 SUBMITTAL #03300.02. DESIGN MIX 1150401
 10000 PSI IN 56 DAYS. PEAROCK WITH
 HRWR,MODULUS OF ELASTICITY=4200 KSI.
 VERTICAL COLUMNS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status P Date 2006-09-30 Cont ID  
Sent By mjacobs Date 2006-09-30 Time 14:22 Rev Time 0.00
Received By mjacobs Date 2006-09-30 Time 14:14 Sent To  
Notes
2006-09-30 00:00:00FBC:2001
 SUBMITTAL #07120.01.01. FLUID APPLIED
 WATERPROOFING SYSTEM PRODUCT DATA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status P Date 2006-09-30 Cont ID  
Sent By mjacobs Date 2006-09-30 Time 14:14 Rev Time 0.00
Received By mjacobs Date 2006-09-30 Time 14:01 Sent To  
Notes
2006-09-30 00:00:00FBC:2001
 SUBMITTAL #03300.16. DESIGN MIX 1177204
 3000 PSI IN 28 DAYS. ASTM C-476.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status P Date 2006-09-30 Cont ID  
Sent By mjacobs Date 2006-09-30 Time 14:01 Rev Time 0.00
Received By mjacobs Date 2006-09-30 Time 13:48 Sent To  
Notes
2006-09-30 00:00:00FBC:2001
 SUBMITTAL #03100.01. NON-SHRINK GROUT
 FOR REPAIRS- EPOXY ANCHORING SYSTEM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status P Date 2006-09-30 Cont ID  
Sent By mjacobs Date 2006-09-30 Time 13:48 Rev Time 0.00
Received By mjacobs Date 2006-09-30 Time 13:38 Sent To  
Notes
2006-09-30 00:00:00FBC:2001
 SUBMITTAL #03300.01. DESIGN MIX 1189615
 5000 PSI IN 28 DAYS REGULAR WITH HRWR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status P Date 2006-09-30 Cont ID  
Sent By mjacobs Date 2006-09-30 Time 13:38 Rev Time 0.00
Received By mjacobs Date 2006-09-30 Time 13:25 Sent To  
Notes
2006-09-30 00:00:00FBC:2001
 SUBMITTAL #03300.13 DESIGN MIX 116537.
 4000 PSI IN 28 DAYS REGULAR. SLAB ON
 GRADE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status P Date 2006-09-30 Cont ID  
Sent By mjacobs Date 2006-09-30 Time 11:36 Rev Time 0.00
Received By mjacobs Date 2006-09-30 Time 11:06 Sent To  
Notes
2006-09-30 00:00:00FBC:2001
 SUBMITTALS #03300.22. 4000 PSI PEAROCK,
 PUMP MIX WITH HRWR. CRASH WALLS AND TIE
 COLOMNS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 18:49 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 18:47 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTAL #03100.04.01 NEOPRENE PPAD @
 DETAILS#5/S5.0

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 18:41 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 18:26 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTALS #03200.04 REVISED 17-PC AND
 40-PC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 18:25 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 17:53 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTAL #03300.21. 6000 PSI IN 72
 HOURS - REGULAR WITH HRWR

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 17:53 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 17:39 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUUBMITTAL #03300.15. DESIGN MIX
 1161529. 5000/6000 PSI IN 28 DAYS-
 REGULAR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 17:37 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 16:43 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTAL #03300.14
 DESIGN MIX 1163539. 5000 PSI IN 28
 DAYS-REGULAR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 17:05 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 16:27 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTAL: #033300.12
 DESIGN MIX 1161404. 3000 PSI IN 28 DAYS-
 REGULAR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 16:14 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 16:02 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTALS: #03300.07
 DESIGN MIX 1177399. 6000 PSI IN 28 DAYS
 PEAROCK WITH HRWR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 15:44 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 15:25 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTAL: # 03300.18
 DESIG MIX 1177563. 3000 PSI IN 40
 HOURS/6000 PSI IN 28 DAYS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 15:24 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 14:50 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTAL: #03300.19.
 MIX CODE 1227928. 300PSI IN
 24HOURS/6000PSI IN 28 DAYS-REGULAR

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 14:44 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 14:40 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTAL: #03300.10.
 DESIGN MIX 1353717. 8000 PSI IN 56 DAYS.
 PEAROCK WITH HRWR MODULOS OF
 ELASTICITY=4200KSI.

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 14:31 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 14:22 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTAL: #03300.11. DESIGN MIX
 1353718.9000 PSI IN 56 DAYS. PEAROCK
 WITH HRWR, MODULUS OF ELASTICITY=4200KSI

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 14:00 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 13:49 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTAL: #03300.08. DESIGN MIX CODE
 1149386. 6000 PSI IN 28 DAYS-REGULAR
 WITH CORROSION INHIBTORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 13:35 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 13:22 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTAL #03300.20. 4000 PSI SIDEWINDER
 WITH /HRWR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 13:22 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 11:14 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTAL #03200.12 SECONDARY SLAB AND
 REBAR SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2006-09-29 Cont ID  
Sent By mjacobs Date 2006-09-29 Time 09:00 Rev Time 0.00
Received By mjacobs Date 2006-09-29 Time 07:49 Sent To  
Notes
2006-09-29 00:00:00FBC:2001
 SUBMITTALS.#03365.01. STUD RAIL SHOP
 DRAWINGS. FLOORS P2 THRU LANAI.

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2006-09-28 Cont ID  
Sent By mjacobs Date 2006-09-28 Time 18:44 Rev Time 0.00
Received By mjacobs Date 2006-09-28 Time 18:28 Sent To  
Notes
2006-09-28 00:00:00FBC:2001
 SUBMITTAL #03200.07. STUB TIE/ COLUMNS
 TO ELEVATION OF FOUNDAATION WALLS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2006-09-28 Cont ID  
Sent By mjacobs Date 2006-09-28 Time 18:20 Rev Time 0.00
Received By mjacobs Date 2006-09-28 Time 18:04 Sent To  
Notes
2006-09-28 00:00:00FBC: 2001
 SUBMITTAL #03200.08 BOOM PUMP
 FOUNDATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2006-09-28 Cont ID  
Sent By mjacobs Date 2006-09-28 Time 18:00 Rev Time 0.00
Received By mjacobs Date 2006-09-28 Time 17:27 Sent To  
Notes
2006-09-28 00:00:00FBC:2001
 SUBMITTAL #03200.09. PARKING LEVEL
 DECK #2 POUR 1-4

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2006-09-28 Cont ID  
Sent By mjacobs Date 2006-09-28 Time 17:27 Rev Time 0.00
Received By mjacobs Date 2006-09-28 Time 17:00 Sent To  
Notes
2006-09-28 00:00:00FBC:2001
 SUBMITTAL #03200.05. GRADE BEAMS & STRAP
 BEAMS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2006-09-28 Cont ID  
Sent By mjacobs Date 2006-09-28 Time 16:49 Rev Time 0.00
Received By mjacobs Date 2006-09-28 Time 16:04 Sent To  
Notes
2006-09-28 00:00:00FBC:2001
 SUBMITTAL #03200.03 PARKING TOWER
 COLUMNS-PILE CAPS TO PARKING #5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2006-09-28 Cont ID  
Sent By mjacobs Date 2006-09-28 Time 07:56 Rev Time 0.00
Received By mjacobs Date 2006-09-28 Time 07:07 Sent To  
Notes
2006-09-28 00:00:00SUBMITTAL #03100.19.01 LANAI SHORING AND
 CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2006-09-28 Cont ID  
Sent By mjacobs Date 2006-09-28 Time 06:59 Rev Time 0.00
Received By mjacobs Date 2006-09-28 Time 06:07 Sent To  
Notes
2006-09-28 00:00:00SUBMITTAL #05500.02.02. STRUCTURAL STEEL
 STAIRS AND CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2006-09-27 Cont ID  
Sent By mjacobs Date 2006-09-27 Time 18:35 Rev Time 0.00
Received By mjacobs Date 2006-09-27 Time 18:14 Sent To  
Notes
2006-09-27 00:00:00 
 STRUCTURAL SUBMITTAL #05520.01.01 FOR
 ALUMINUM RAILING @ BALCONIES

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2006-09-27 Cont ID  
Sent By mjacobs Date 2006-09-27 Time 17:46 Rev Time 0.00
Received By mjacobs Date 2006-09-27 Time 17:09 Sent To  
Notes
2006-09-27 00:00:00SUBMITTAL #03100.16 PARKING LEVEL#4 THRU
 9. TOWER LEVEL 2 THRU 4. SHORING
 CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2006-09-27 Cont ID  
Sent By mjacobs Date 2006-09-27 Time 16:31 Rev Time 0.00
Received By mjacobs Date 2006-09-27 Time 16:31 Sent To  
Notes
2006-09-27 00:00:00SUBMITTAL SHORING. #03100.15 PARKING
 LEVEL 3 SHORING AND CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2006-09-27 Cont ID  
Sent By mjacobs Date 2006-09-27 Time 13:21 Rev Time 0.00
Received By mjacobs Date 2006-09-27 Time 11:06 Sent To  
Notes
2006-09-27 00:00:00SUBMITTAL #03100.09STAIR FORMING DETAILS

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2006-09-27 Cont ID  
Sent By mjacobs Date 2006-09-27 Time 11:00 Rev Time 0.00
Received By mjacobs Date 2006-09-27 Time 10:59 Sent To  
Notes
2006-09-26 00:00:00SUBMITTAL # 03400.01.02TOWER CRANE
 SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2006-09-26 Cont ID  
Sent By mjacobs Date 2006-09-26 Time 11:16 Rev Time 0.00
Received By mjacobs Date 2006-09-26 Time 11:00 Sent To  
Notes
2006-09-26 00:00:00SUBMITTAL #03365.02 PARKING LEVEL #2
 POST TENSION CABLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2006-09-26 Cont ID  
Sent By mjacobs Date 2006-09-26 Time 10:10 Rev Time 0.00
Received By mjacobs Date 2006-09-26 Time 09:44 Sent To  
Notes
2006-09-26 00:00:00SUBMITTAL #03200.06 SHEAR WALLS 1-9 AND
 PILE CAPS TO PARKING #8.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2006-09-26 Cont ID  
Sent By mjacobs Date 2006-09-26 Time 09:34 Rev Time 0.00
Received By mjacobs Date 2006-09-26 Time 08:47 Sent To  
Notes
2006-09-26 00:00:00SUBMITTAL #03100.05 PARKING LEVEL #2.
 POUR 1-3. SHORING AND CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2006-09-25 Cont ID  
Sent By mjacobs Date 2006-09-25 Time 18:57 Rev Time 0.00
Received By mjacobs Date 2006-09-25 Time 18:36 Sent To  
Notes
2006-09-25 00:00:00SUBMITTAL #03200.10 MEZZANINE AND
 PARKING LEVEL #3. POUR #5-#10.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-09-25 Cont ID  
Sent By mjacobs Date 2006-09-25 Time 18:06 Rev Time 0.00
Received By mjacobs Date 2006-09-25 Time 18:06 Sent To  
Notes
2006-09-25 00:00:00 
  
 SUBMITTAL ON 4/3/06#03200.13 PARKING
 LEVEL #4. POUR 11-16.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-09-03 Cont ID  
Sent By rbrown Date 2006-09-03 Time 19:08 Rev Time 0.00
Received By rbrown Date 2006-09-03 Time 19:08 Sent To  
Notes
2006-09-03 00:00:00ARCHITECTURAL AND STRUCTURAL REVISION
 SUBMITTED ON 6/22/06.ONE COPY OF THE
 REVIEWED PLANS HAS BEEN RETAINED AS FILE
 COPY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-09-03 Cont ID  
Sent By rbrown Date 2006-09-03 Time 19:06 Rev Time 0.00
Received By rbrown Date 2006-09-03 Time 19:06 Sent To  
Notes
2006-09-03 00:00:00STRUCTURAL REVISION SUBMITTED 5/9/06

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-03-29 Cont ID  
Sent By rbrown Date 2006-03-29 Time 08:02 Rev Time 0.00
Received By rbrown Date 2006-03-29 Time 08:02 Sent To  
Notes
2006-03-29 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
  
 PRODUCT APPROVAL PROVISOS:
  
  
 -PROVISO-
 STAIRWELL DOORS S1, R1 AND R15. SHEET
 A9.11, DOOR SCHEDULE, SHOWS THESE DOORS
 AS TYPE I, WHICH HAS A 10"X 10" VISION
 PANEL.THE SUBMITTED STATEWIDE PRODUCT
 APPROVAL FL2167 GIVES DESIGN WIND
 PRESSURES OF +65 PSF AND -65 PSF WITH
 THE RIM EXIT DEVICE (SEE DRAWING SHEET 3
 OF THE PRODUCT APPROVAL NOA# 02-0523.06
 THAT WAS SUBMITTED WITH THE STATEWIDE
 APPROVAL).THOSE PRESSURES ARE EXCEEDED
 BY THE WIND PRESSURES ON THE BUILDING AT
 THESE LOCATIONS.SUBMIT A PRODUCT
 APPROVAL FOR DOORS WITH ADEQUATE DESIGN
 WIND PRESSURES.
  
 -PROVISO-
 LOUVERS, SHEET A8.44.GRILLE/LOUVER
 TYPE N IS SHOWN AS 10'-3" HIGH ON THE
 LOUVER AND GRILLE SCHEDULE.THAT
 HEIGHT EXCEEDS THE MAXIMUM ALLOWED IN
 BOTH OF THE TWO SUBMITTED PRODUCT
 APPROVALS (FL4352 AND FL5160).AMEND
 THE SIZE OR SUBMIT AN APPROPRIATE
 PRODUCT APPROVALS.
  
 -PROVISO-
 AUTOMATIC SLIDING MAIN ENTRY DOOR.ON
 SHEET A8.41 THE UNIT HEIGHT IS SHOWN AS
 8'-0" WHICH EXCEEDS THE 7'-8" HEIGHT
 SHOWN IN THE SUBMITTED STANLEY ACCESS
 TECHNOLOGIES STATEWIDE PRODUCT APPROVAL
 FL6249 (SEE DRAWING SHEET 1 OF NOA#
 04-1026.02, SUBMITTED WITH THE STATEWIDE
 PRODUCT APPROVAL).EITHER AMEND THE
 HEIGHT SHOWN ON THE PLANS OR SUBMIT A
 PRODUCT APPROVAL SHOWING A DOOR HEIGHT
 NO LESS THAN THAT STATED ON THE PLANS.
  
 -PROVISO-
 SINGLE HUNG WINDOW, SHEET A8.41 SHOWS
 WINDOW TYPES W-2 AND W-2A AS 10'-1" TALL
 FROM FLOOR TO HORIZONTAL MULLION.THIS
 EXCEEDS THE MAXIMUM 9'-2" SHOWN IN THE
 SUBMITTED RC ALUMINUM STATEWIDE PRODUCT
 APPROVAL FL3398 (SEE DRAWING SHEET 1 OF
 NOA# 03-1216.06, SMALL MISSILE IMPACT
 AND NOA# 03.1216.04, LARGE MISSILE
 IMPACT).SUBMIT ALTERNATIVE OR
 ADDITIONAL PRODUCT APPROVALS TO COVER
 THE PROPOSED MAXIMUM WINDOW HEIGHT.
  
 -PROVISO-
 FIXED WINDOW, SHEET A8.41.DUE TO THEIR
 LOCATION ON THE BUILDING, WINDOW TYPES
 W-3 AND W-3.2 WILL BE SUBJECT TO 140 PSF
 NEGATIVE WIND PRESSURE.THE MAXIMUM
 NEGATIVE PRESSURE ALLOWED BY THE
 SUBMITTED EFCO STATEWIDE PRODUCT
 APPROVAL FL1520 IS 130 PSF (SEE DRAWING
 SHEET 1 OF NOA# 02-0410.04 SUBMITTED
 WITH THE STATEWIDE PRODUCT APPROVAL).
 SUBMIT AN ADDITIONAL OR ALTERNATE
 PRODUCT APPROVAL TO COVER THE WIND
 PRESSURES THAT THE WINDOWS WILL BE
 SUBJECTED TO.
  
 -PROVISO-
 STOREFRONT, SHEET A8.41.ALL THREE OF
 THE SUBMITTEDTHE SUBMITTED GAMMA
 U.S.A. WINDOW WALLPRODUCT APPROVALS
 ARE FOR SMALL MISSILE IMPACT LOCATIONS.
 NO APPROPRIATE PRODUCT APPROVAL HAS BEEN
 SUBMITTED FOR THE STOREFRONT WINDOWS
 (AND DOORS) ON THE FIRST FLOOR WHICH ARE
 IN THE LARGE MISSILE IMPACT ZONE. SUBMIT
 PRODUCT APPROVAL(S) FOR LARGE MISSILE
 IMPACT STOREFRONT WINDOWS (AND DOORS).

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-02-26 Cont ID  
Sent By rbrown Date 2006-02-26 Time 22:11 Rev Time 0.00
Received By rbrown Date 2006-02-23 Time 19:02 Sent To  
Notes
2006-02-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 11/11/05:
  
 4) NOTE THAT THE NOTICE OF COMMENCEMENT,
 IMPACT FEE RECEIPT AND SPECIAL INSPECTOR
 AGREEMENT WILL BE REQUIRED BEFORE A
 PERMIT CAN BE ISSUED:
 (A) THE SUBMITTED NOTICE OF
 COMMENCEMENTSTATES "...LIMITED TO
 CONCRETE FOUNDATION PILES ONLY".A NEW
 ONE MUST BE RECORDED
 (B) THE IMPACT FEE PAYMENT RECEIPT MUST
 BE SUBMITTED.THE IMPACT FEE STAMP IS
 CURRENTLY ON THE VOIDED COPY OF SHEET
 A0.00 AND HAS BEEN MARKED "KEEP FOR
 IMPACT FEE STAMP".THAT SHEET SHOULD BE
 ATTACHED TO ONE OF THE THREE PERMIT PLAN
 SETS.
 (C) THE SPECIAL INSPECTOR AGREEMENT WAS
 SUBMITTED ON A 1994 VERSION OF THE FORM
 WHICH IS NO LONGER IN USE.THIS WILL BE
 DISCUSSED WITH WITH THE THRESHOLD
 INSPECTOR PROGRAM MANAGER, HAROLD
 PISKURA, TO DETERMINE IF IT ACCEPTABLE.
 ALTERNATIVELY, PLEASE COLLECT A CURRENT
 FORM (JULY 1, 2004 VERSION) FROM THIS
 OFFICE, HAVE IT COMPLETED WITH ORIGINAL
 SIGNATURES (NOTARIZED OR SEALED AS
 APPROPRIATE) AND THEN SUBMIT IT.
  
 10) PRODUCT APPROVALS:
 (A) NONE OF THE SUBMITTED PRODUCT
 APPROVALS INCLUDE THE STATEWIDE PRODUCT
 APPROVAL OR LOCAL PRODUCT APPROVAL COVER
 SHEET REQUIRED TO DEMONSTRATE COMPLIANCE
 WITH FLORIDA ADMINISTRATIVE CODE RULE
 9B-72.FOR MORE DETAILS, SEE THE NOTE
 AT THE END OF THE PRODUCT APPROVAL
 COMMENTS.
 (B) ROOF TILE. THE WIND UPLIFT
 PRESSURES SHOWN ON ARCHITECTURAL PLAN,
 SHEET A1.02, FOR THE TILED ROOF AREAS,
 ARE UP TO 150 PSF (UPLIFT).SHEET 2 OF
 THE SUBMITTED MONIER LIFETILE SPANISH
 'S' CONCRETE ROOF TILE PRODUCT APPROVAL
 NOA# 02-1205.07 STATES THAT THE PRODUCT
 IS FOR USE IN LOCATIONS WERE THE DESIGN
 PRESSURES DO NOT EXCEED THOSE OBTAINED
 BY CALCULATIONS IN COMPLIANCE WITH RAS
 127.SUBMIT CALCULATIONS (SEE RAS 127)
 TO SHOW THAT THE PROPOSED ROOF TILE IS
 SUITABLE FOR THE UPLIFT PRESSURES OF
 THIS APPLICATION.
 ALSO, SHEET A8.23. DETAILS 3, 4, AND 5
 REFER TO THE STRUCTURAL PLANS FOR
 THICKNESS OF DENSE DECK AND ATTACHMENT
 OF TILES.THIS INFORMATION COULD NOT BE
 FOUND ON THE STRUCTURAL PLANS.SUBMIT
 DETAILS. THE NOTES ON SHEET S-1.25 REFER
 TO THE USE OF FIRE-RETARDANT TREATED
 PLYWOOD WHICH IS IN CONFLICT WITH THE
 ARCHITECTURAL PLANS AND IS NOT A
 PERMITTED MATERIAL FOR USE IN
 CONSTRUCTION TYPE I.AMEND THE
 STRUCTURAL PLANS.
 EITHER A STATEWIDE PRODUCT APPROVAL, OR
 LOCAL PRODUCT APPROVAL, COVER SHEET
 SHALL BE SUBMITTED WITH EACH COPY, SEE
 COMMENT (A) ABOVE.
 (C) MODIFIED BITUMEN ROOFING SYSTEM.
 EITHER A STATEWIDE PRODUCT APPROVAL, OR
 LOCAL PRODUCT APPROVAL, COVER SHEET
 SHALL BE INCLUDED WITH EACH COPY OF THE
 SUBMITTED JOHNS MANVILLE CORP. MODIFIED
 BITUMEN ROOFING SYSTEM PRODUCT APPROVAL
 NOA# 04-0401.04, SEE COMMENT (A) ABOVE.
 (D) LOADING AREA SECTIONAL DOOR S28.
 NO PRODUCT APPROVAL WAS SUBMITTED FOR
 THIS DOOR.SUBMIT A PRODUCT APPROVAL
 FOR THIS 14'-0" X 16'-0" SECTIONAL DOOR.
 (E) TRASH TERMINATION/HOLDING/WASTE
 CONTAINER ROOM DOORS.THESE DOORS ARE
 ON THE PARKING GARAGE VEHICLE ENTRY
 DRIVEWAY AND SO WILL BE SUBJECT TO WIND
 PRESSURES.SHEET A9.11, DOOR SCHEDULE,
 SHOWS EACH OF THESE DOORS AS A PAIR OF
 6' WIDE DOORS.NO PRODUCT APPROVAL WAS
 SUBMITTED FOR A DOOR OF THIS WIDTH.
 AMEND THE DOOR SCHEDULE OR SUBMIT AN
 APPROPRIATE PRODUCT APPROVAL.
 (F) STAIRWELL DOORS S1, R1 AND R15.
 SHEET A9.11, DOOR SCHEDULE, SHOWS THESE
 DOORS AS TYPE I, WHICH HAS A 10"X 10"
 VISION PANEL.NO PRODUCT APPROVAL HAS
 BEEN SUBMITTED FOR A HOLLOW METAL DOOR
 WITH VISION PANEL.SUBMIT A PRODUCT
 APPROVAL.
 (G) STEAM ROOM DOOR.THIS DOOR IS
 REFERENCED R14 ON SHEET A9.11 (DOOR
 SCHEDULE).IS IT THE SAME DOOR THAT IS
 CALLED UP AS DOOR R4 ON SHEET 4.72?THE
 DOOR SCHEDULE SHOWS DOOR R14 AS TYPE R,
 WHICH IS SHOWN AS "SUN-DOR-CO #SD-502".
 THAT MANUFACTURER AND REFERENCE DOES NOT
 CORRELATE WITH THE SUBMITTED ARCH
 ALUMINUM MEDIUM STILE ALUMINUM DOOR
 PRODUCT APPROVAL NOA# 01-1102.01.
 CLARIFY THE DOOR REFERENCE NUMBER ON
 SHEET A9.1 OR A4.72 AND REMOVE THE
 INCORRECT DOOR MANUFACTURER REFERENCE
 FOR DOOR R14.
 (H) LOBBY GARAGE ENTRY DOOR P8.SHEET
 A9.11, DOOR SCHEDULE, SHOWS THIS DOOR AS
 TYPE S (SOLID CORE WOOD DOOR).SHEET
 A4.14 SHOWS THE DOOR LEADING FROM THE
 GARAGE INTO THE CONDITIONED SPACE.THE
 GARAGE IS OPEN AT THE VEHICLE ENTRY
 DRIVEWAYS, SO DOOR P8 WILL BE SUBJECT TO
 WIND PRESSURES. SUBMIT A PRODUCT
 APPROVAL FOR THIS DOOR TYPE OR REVISE
 THE SHEET A4.14 AND THE DOOR SCHEDULE
 (SHEET A9.11).NOTE THAT THIS DOOR IS
 ALSO REQUIED TO BE 1-1/2 HOUR FIRE
 RATED.
 (I) LOUVERS, SHEET A8.44.NO PRODUCT
 APPROVALS WERE SUBMITTED FOR THE
 LOUVERS.SUBMIT APPROPRIATE PRODUCT
 APPROVALS.
 (J) WINDOW, STORE FRONT AND SLIDING
 GLASS DOOR PRODUCT APPROVALS.IN
 ADDITION TO THE COMMENTS BELOW, PLEASE
 NOTE THAT, ACCORDING TO THE WIND
 PRESSURES STATED ON ARCHITECTURAL PLAN
 SHEET A1.02, SOME OF THESE PRODUCTS WILL
 BEREQUIRED TO HAVE A DESIGN PRESSURE
 RATING OF UP TO +100 PSF (POSITIVE) AND
 -140 PSF (NEGATIVE).IT WOULD APPEAR
 THAT THE SUBMITTED PRODUCT APPROVALS
 WERE NOT CHECKED, PRIOR TO SUBMITTAL, TO
 ENSURE THAT THE PROPOSED PRODUCTS CAN
 WITHSTAND THE STATED WIND PRESSURES FOR
 THIS BUILDING.PLEASE CHECK THE DESIGN
 PRESSURE RATING OF ALL PRODUCT
 APPROVALS, PRIOR TO SUBMITTAL.
 (K) WINDOW WALL.THE SUBMITTED GAMMA
 U.S.A. SERIES 50.2 SMALL MISSILE IMPACT
 WINDOW WALL PRODUCT APPROVAL NO. 03-0345
 AND SERIES 61 LARGE MISSILE IMPACT
 WINDOW WALL PRODUCT APPROVAL NO. 03-0348
 BOTH STATE, ON THEIR RESPECTIVE COVER
 SHEETS, THAT THEY ARE "ONE-TIME PRODUCT
 APPROVAL" APPLICATIONS FOR A PROJECT
 CALLED "JADE RESIDENCE" 1331 BRICKELL
 BAY DR, MIAMI, FL.THESE PRODUCT
 APPROVALS ARE NOT VALID FOR OTHER
 PROJECTS.SUBMIT VALID PRODUCT
 APPROVALS.
 (L) WINDOW WALL.THE DRAWING SHEETS 1
 TO 8 SUBMITTED AS PART OF THE GAMMA
 U.S.A. SERIES 50.4A SMALL MISSILE IMPACT
 WINDOW WALL PRODUCT APPROVAL NOA#
 04-1006.01 ARE NOT COPIES OF THE ONES
 REVIEWED BY MIAMI-DADE CODE
 COMPLIANCE OFFICE (BCCO).UNLIKE THE
 DRAWINGS INCLUDED WITH THIS PRODUCT
 APPROVAL ON THE MIAMI-DADE BCCO WEBSITE,
 THEY DO NOT HAVE THE MIAMI-DADE BCCO
 APPROVAL STAMP.SUBMIT PRODUCT
 APPROVALS WITH DRAWINGS THAT INCLUDE THE
 PRODUCT CERTIFICATION AGENCY STAMP OF
 APPROVAL.ALSO, SEE COMMENT (J) ABOVE
 AND COMMENT (A) ABOVE.
 (M) WINDOW WALL WITH TILT WINDOW.
 SUBMITTAL OF FENESTRATION TESTING
 LABORATORY (FTL) REPORT 02-0729.01, FOR
 GAMMA U.S.A SERIES 55.2 WINDOW WALL WITH
 TILT WINDOW, IS NOTED BUT THIS IS NOT A
 PRODUCT APPROVAL. SUBMIT A PRODUCT
 APPROVAL FROM AN APPROVED PRODUCT
 CERTIFICATION AGENCY, SEE COMMENT (A)
 ABOVE.
 (N) GAMMA U.S.A SERIES 73 SLIDING GLASS
 DOOR. SUBMITTAL OF FENESTRATION TESTING
 LABORATORY (FTL) REPORT 03-0821.01, IS
 NOTED BUT THIS IS NOT A PRODUCT
 APPROVAL. SUBMIT A PRODUCT APPROVAL FROM
 AN APPROVED PRODUCT CERTIFICATION
 AGENCY, SEE COMMENT (A) ABOVE.
 (O) GAMMA U.S.A SERIES 76 ALDORA
 ALUMINUM SLIDING GLASS DOOR.THE
 DRAWING SHEETS 1 TO 8 SUBMITTED AS PART
 OF THE PRODUCT APPROVAL NOA#
 04-1006.03 ARE NOT COPIES OF THE ONES
 REVIEWED BY MIAMI-DADE CODE COMPLIANCE
 OFFICE (BCCO).UNLIKE THE DRAWINGS
 INCLUDED WITH THIS PRODUCT APPROVAL ON
 THE MIAMI-DADE BCCO WEBSITE, THEY DO NOT
 HAVE THE MIAMI-DADE BCCO APPROVAL STAMP.
 SUBMIT PRODUCT APPROVALS WITH DRAWINGS
 THAT INCLUDE THE PRODUCT CERTIFICATION
 AGENCY STAMP OF APPROVAL.ALSO, SEE
 COMMENT (J) ABOVE AND COMMENT (A) ABOVE.
  
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE WWW.
 FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
 FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE
 PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL
 CAN BE ACHIEVED IF THERE IS A QUALITY
 ASSURANCE PROGRAM IN PLACE WITH A STATE
 APPROVED QUALITY ASSURANCE ENTITY.
 LOCAL PRODUCT APPROVAL WILL ALLOW A
 PRODUCT TO BE USED, IN ACCORDANCE WITH
 THE TEST CRITERIA, THROUGHOUT THE
 JURISDICTION OF WEST PALM BEACH.
 LOCAL AND SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION FORMS ARE AVAILABLE FROM
 THIS OFFICE.APPROVED QUALITY ASSURANCE
 ENTITIES ARE LISTED ON THE DCA WEBSITE:
 FLORIDABUILDING.ORG/PR/PR_ORG_SRCH.ASPX
  
 25) NFPA 823-2.4.3.1REFUSE CHUTE.
 THIS COMMENT HAS NOT BEEN ADDESSED. THE
 COMMENT RESPONSE REFERING TO APPROVAL BY
 THE CONSTRUCTION BOARD OF ADJUSTMENTS
 AND APPEALS (CBAA) IS NOTED.PLEASE
 SUBMIT A COPY OF THE CBAA FINAL
 DECISION, FOR THE PERMIT FILE,SO THAT
 IT MAY BE DEEMED UNNECESSARY, FOR THIS
 PROJECT ONLY, TO PROVIDE A MINIMUM 6"
 CLEARANCE BETWEEN THE OPEN CHUTE LOADING
 DOOR AND CLOSED SERVICE OPENING ROOM
 DOOR.
  
 43) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-11-11 Cont ID  
Sent By rbrown Date 2005-11-11 Time 13:17 Rev Time 0.00
Received By rbrown Date 2005-10-21 Time 21:14 Sent To  
Notes
2005-11-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 5/19/05:
  
 4) INFORMATIVE. NOTE THAT THE NOTICE OF
 COMMENCEMENT, IMPACT FEE RECEIPT AND
 SPECIAL INSPECTOR AGREEMENT WILL BE
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
  
 5) FBC* 104.2.4SITE SURVEY. THIS
 COMMENT HAS NOT BEEN PROPERLY ADDRESSED.
 THIS TIME NO SURVEY DRAWING WAS
 SUBMITTED.A SIGNED AND SEALED SURVEY
 DRAWING PREPARED BY A LICENSED
 SURVEYOR/MAPPER IS REQUIRED.
 (REF: 472.025(1) FL. STATUTES).
  
 8) FBC* 1804.2.2SHEET S-0, GENERAL
 NOTES - FOUNDATIONS.THIS COMMENT HAS
 NOT BEEN ADDRESSED.SUBMIT THREE
 COPIES OF ARDAMAN & ASSOCIATES SOIL
 REPORT DATED 7/28/04 AS REFERENCED
 UNDER THE 'FOUNDATION' NOTE.
  
 9) FBC 13-103.1.2THIS COMMENT HAS NOT
 BEEN ADDRESSED.SHEET 2 OF THE
 SUBMITTED ENERGY CODE COMPLIANCE FORMS
 MUST BE SIGNED BY THE BUILDING OWNER,
 THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY
 THE OWNER.ALSO THE ARCHITECT'S LICENSE
 NUMBER MUST BE ADDED IN THE SPACE
 PROVIDED ON SHEET 2 AND ALL OF THE
 PROJECT INFORMATION ITEMS ON SHEET 1
 SHALL BE ENTERED.
  
 10) PRODUCT APPROVALS.THIS COMMENT HAS
 NOT BEEN ADDRESSED. SUBMIT PRODUCT
 APPROVALS FOR THE WINDOWS, STOREFRONTS,
 EXTERIOR DOORS AND ROOFING PRODUCTS.
  
 25) NFPA 823-2.4.3.1THE COMMENT
 RESPONSE REFERING TO APPROVAL BY THE
 CONSTRUCTION BOARD OF ADJUSTMENTS AND
 APPEALS (CBAA) IS NOTED.PLEASE SUBMIT
 A COPY OF THE CBAA FINAL DECISION, FOR
 THE PERMIT FILE,SO THAT IT MAY BE
 DEEMED UNNECESSARY, FOR THIS PROJECT
 ONLY, TO PROVIDE A MINIMUM 6" CLEARANCE
 BETWEEN THE OPEN CHUTE LOADING DOOR AND
 CLOSED SERVICE OPENING ROOM DOOR.
  
 37) FBC 1601.1SHEET A8.24,
 ARCHITECTURAL TRIM.SUBMITTAL OF
 DETAILS FOR ATTACHMENT OF MOULDINGS,
 ORNAMENTAL PANELS AND BANDS, AND OTHER
 ARCHITECTURAL TRIM IS NOTED BUT THE
 DETAILS DO NOT STATE THE HORIZONTAL
 SPACING OF THE 'TAPCONS'.AMEND THE
 DETAILS TO SHOW THE FASTENER SPACING.
  
 42) FBC 11.4.6.3SHEETS A2.04 THROUGH
 A2.09.ALL ACCESSIBLE PARKING SPACES
 SHALL BE MIN. 12'-0" WIDE.THE PLANS
 ONLY SHOW THE VAN ACCESSIBLE SPACES TO
 COMPLY WITH THIS REQUIREMENT.ALL OF
 THE REMAINING ACCESSIBLE SPACES ARE
 SHOWN AS ONLY 8'-6" WIDE.AMEND THE
 PLANS.
  
 43) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
2005-10-21 00:00:00****PLAN REVIEW IN PROGRESS****

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-19 Cont ID  
Sent By rbrown Date 2005-05-19 Time 08:05 Rev Time 0.00
Received By rbrown Date 2005-05-06 Time 08:09 Sent To  
Notes
2005-05-17 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/20/05:
  
 2) 61G1-16.004FL. ADMIN. CODE.IT IS
 NOTED THAT THE PLANS ARE NOW SIGNED AND
 SEALED BUT THE ARCHITECTURAL SHEETS DO
 NOT INCLUDE THE PRINTED NAME OF THE
 ARCHITECT OF RECORD. PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A
 TITLE BLOCK WHICH MUST INCLUDE THE
 PRINTED NAME OF THE ARCHITECT SEALING
 THE PLANS.
  
 4) INFORMATIVE. NOTE THAT THE NOTICE OF
 COMMENCEMENT, IMPACT FEE RECEIPT AND
 SPECIAL INSPECTOR AGREEMENT WILL BE
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
  
 5) FBC* 104.2.4SITE SURVEY.THE
 SUBMITTED SURVEY DRAWING IS NOT SIGNED
 AND SEALED AND INCLUDES A NOTE "...NOT
 VALID WITHOUT THE SIGNATURE AND THE
 ORIGINAL RAISED SEAL OF..."A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 LICENSED SURVEYOR/MAPPER IS REQUIRED.
 (REF: 472.025(1) FL. STATUTES).
  
 6) A SEPARATE PERMIT APPLICATION WILL
 BE REQUIRED FOR THE SWIMMING POOL AND
 SPA.ADD NOTES ON THE PLANS TO STATE
 'UNDER SEPARATE PERMIT'.
  
 7) FBC* 105.13.1SPECIAL INSPECTOR
 AGREEMENT.BEFORE A PERMIT CAN BE
 ISSUED IT WILL BE NECESSARY TO ARRANGE A
 MEETING, WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL: 561 805 6711),
 INVOLVING THE OWNER, THRESHOLD
 INSPECTOR, JOB INSPECTOR, CONTRACTOR
 AND ENGINEER.
  
 8) FBC* 1804.2.2SHEET S-0, GENERAL
 NOTES - FOUNDATIONS.THIS COMMENT HAS
 NOT BEEN ADDRESSED.SUBMIT THREE
 COPIES OF ARDAMAN & ASSOCIATES SOIL
 REPORT DATED 7/28/04 AS REFERENCED
 UNDER THE 'FOUNDATION' NOTE.
  
 9) FBC 13-103.1.2SUBMITTAL OF ENERGY
 CODE COMPLIANCE FORMS IS NOTED BUT SHEET
 2 MUST BE SIGNED BY THE BUILDING OWNER,
 THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY
 THE OWNER.ALSO THE ARCHITECT'S LICENSE
 NUMBER MUST BE ADDED IN THE SPACE
 PROVIDED ON SHEET 2 AND ALL OF THE
 PROJECT INFORMATION ITEMS ON SHEET 1
 SHALL BE ENTERED.
  
 10) PRODUCT APPROVALS.THIS COMMENT HAS
 NOT BEEN ADDRESSED. SUBMIT PRODUCT
 APPROVALS FOR THE WINDOWS, STOREFRONTS,
 EXTERIOR DOORS AND ROOFING PRODUCTS.
  
 11) FBC 1003.1.1SHEET LS0.01, BUILDING
 CODE INFORMATION, ITEM 5.10.THE
 COMBINED POOL DECK AND ROOF TERRACE
 OCCUPIABLE AREA IS STATED AS JUST
 12,849 SQFT.PLEASE CONFIRM THAT THE
 SQUARE FOOTAGE OF THE RELEVANT SPACES
 (INCLUDING THE MOONLIGHT THEATRE) MINUS
 THE POOL WATER SURFACE IS IN FACT
 12,849 SQFT.WHAT WILL THE MOONLIGHT
 THEATRE BE USED FOR AND WHAT IS THE
 OCCUPANCY RATE (IN SQFT PER PERSON)?
  
 21) PENDING BUILDING OFFICIAL REVIEW OF
 PROPOSAL FOR APPROVAL UNDER ALTERNATE
 MATERIALS AND METHODS:
 FBC* F102.2.7SHEETS A3.01 TO
 A3.06 ELEVATIONS.SEE ALSO COMMENT 34.
 THE KEY NOTES REFER TO 'F11'-FOAM COLUMN
 AND 'A'-MOULDING TYPES SEE SHEETS A??.
 ARCHITECTURAL TRIM, ON BUILDINGS LOCATED
 IN THE FIRE DISTRICT, SHALL BE
 CONSTRUCTED OF APPROVED NON-COMBUSTIBLE
 MATERIALS OR FIRE RETARDANT TREATED
 WOOD.ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE. RESPONSE NOTED.
  
 25) NFPA 823-2.4.3.1COMMENT RESPONSE
 IS NOTED BUT 2001 FBC 3502 CITES NFPA
 82-99 NOT NFPA 82-04.SHEET A7.14,
 TRASH CHUTE SERVICE OPENING ROOM.
 THERE SHALL BE MINIMUM 6" CLEARANCE
 BETWEEN THE OPEN CHUTE LOADING DOOR AND
 CLOSED SERVICE OPENING ROOM DOOR.
 AMEND THE PLANS.
  
 27) FBC 11-4.13.6SHEET A4.42 (AND
 SHEET A4.02), MANEUVERING CLEARANCES AT
 DOORS.THE ADDED DIMENSION OF 1'-4"
 BETWEEN THE WALL AND THE OUTSIDE EDGE OF
 THE DOOR IS NOTED BUT ADDITIONAL
 DIMENSIONING IS REQUIRED TO SHOW THAT
 THERE IS A MIN. 18" CLEARANCE BETWEEN
 THE STRIKE EDGE OF THE DOOR AND THE
 ADJACENT PERPENDICULAR WALL.
 AMEND/ANNOTATE THE PLANS WITH DIMENSIONS
 TO DEMONSTRATE COMPLIANCE.THE SAME
 ALSO APPLIES TO DOOR REFERENCE S14,
 SHOWN ON SHEET A4.02.
  
 28) FBC 411.2.3 AND FBC 1608.2.3SHEETS
 S-1.02, S-1.04, S-1.06 AND S-1.08.THE
 PARKING GARAGE WEST WALL BETWEEN COLUMNS
 P25 AND P28 (OR P27 WHERE APPLICABLE)
 AND THE CENTRAL WALL BETWEEN COLUMNS P33
 AND P69 SHOULD BE ANNOTATED AS IMPACT
 WALL PW-1 OR PW-2 PER SHEET S-4.3,
 PARKING GARAGE WALL SCHEDULE.THE SAME
 APPLIES TO SHEET S-1.02 (PARKING LEVEL
 2) FOR ALMOST THE WHOLE PERIMETER OF THE
 PARKING GARAGE AND SHEETS S-1.06 AND
 S-1.08 FOR THE NORTH WALL OF THE PERKING
 GARAGE.
  
 29) FBC 1608.2.2GUARDRAIL STRENGTH.
 THE COMMENT RESPONSE REFERING TO THE
 SPECIFICATIONS MANUAL SECTION 05520 IS
 NOTED.
  
 30) FBC* 104.2.1CONTRARY TO THE
 COMMENT RESPONSE, THE REQUIRED PLANS
 WERE NOT SUBMITTED SO THIS COMMENT HAS
 NOT BEEN ADDRESSED.THE SUBMITTED
 STRUCTURAL PLAN SET DOES NOT INCLUDE A
 GROUND FLOOR/PARKING LEVEL 1 REINFORCING
 PLAN AND THE HIGH ROOF REINFORCING PLAN
 IS NOT COMPLETE. SUBMIT COMPLETE PLANS
 FOR REVIEW.
  
 34) FBC* 103.7.1ALTERNATIVE MATERIALS
 AND METHODS.SHEET LS0.01 INCLUDES
 THREE ITEMS UNDER THE HEADING
 'EQUIVALENCIES AND ALTERNATIVES'.THESE
 ITEMS WILL NEED TO BE REMOVED FROM THE
 PERMIT PLAN SET IF THEY ARE NOT APPROVED
 BY THE BUILDING OFFICIAL.THE
 ITEMS SHOULD BE SUBMITTED TO THE
 BUILDING OFFICIAL IN LETTER FORM UNDER
 FBC 103.7.1 ALTERNATIVE MATERIALS AND
 METHODS.THE LETTER SHALL CITE THE
 CODE SECTIONS GIVEN IN THIS PLAN REVIEW
 COMMENT LIST.ITEM #3, ARCHITECTURAL
 TRIM IN THE FIRE DISTRICT, IS COVERED BY
 COMMENT 21 OF THIS PLAN REVIEW COMMENT
 LIST.ITEM #2, MASONRY WALL WATER STOP,
 IS ADDRESSED BY COMMENT 35 OF THIS PLAN
 REVIEW COMMENT LIST.ITEM #1, TEMPORARY
 WATERPROOFING OF MASONRY WALLS, IS NOT A
 PLAN REVIEW ISSUE.IT IS AN INSPECTION
 ISSUE THAT COULD POSSIBLY BE COVERED BY
 FBC* 105.6 UNDER THE DRY-IN PLAN.
 PLEASE CONTACT HAROLD PISKURA (ISPECTION
 SERVICES MANAGER) ON 561-805 6711 TO
 DISCUSS THIS ITEM.
  
 35)PENDING BUILDING OFFICIAL REVIEW OF
 PROPOSAL FOR APPROVAL UNDER ALTERNATE
 MATERIALS AND METHODS:
 FBC* 2111.1.9SHEET S-5.1,WATER
 STOP AT CONCRETE SLAB RECESS. SECTION
 DETAILS 11 TO 15 DO NOT SHOW THE
 REQUIRED 1.5" RECESS WHERE THE WALL
 MASONRY UNITS WILL BEAR ON THE CONCRETE
 SLAB.STATUS IS PENDING THE BUILDING
 OFFICIAL'S REVIEW OF THE PROPOSAL FOR
 APPROVAL UNDER FBC* 103.7.1 - ALTERNATE
 MATERIALS AND METHODS (SEE COMMENT #34).
  
 36) FBC 1606.1.4SHEET A8.41A, GLAZING
 DETAILS.UNDER THE HEADING 'NOTES' IS
 THE STATEMENT " 5/8" IMPACT GLASS FIRST
 30'-0" ABOVE GROUND".TO COMPLY WITH
 THE CODE, LARGE MISSILE IMPACT RESISTANT
 GLAZING IS REQUIRED UPTO 30 FEET AND
 SMALL MISSILE IMPACT RESISTANT GLAZING
 IS REQUIRED BETWEEN 30 AND 60 FEET ABOVE
 GRADE.AMEND THE NOTE TO DEMONSTRATE
 COMPLIANCE.
  
 37) FBC 1601.1SHEET A8.24,
 ARCHITECTURAL TRIM.SUBMIT DETAILS FOR
 ATTACHMENT OF MOULDINGS, ORNAMENTAL
 PANELS AND BANDS, AND OTHER
 ARCHITECTURAL TRIM.
  
 38) FBC 11-4.1.3(8)SHEET A4.11 TO
 A4.15.THE 19 GROUND FLOOR LIVE/WORK
 UNITS ARE BUSINESS OCCUPANCY CLASS SO
 THEY ARE REQUIRED TO HAVE ACCESSIBLE
 ENTRANCE.AS NONE OF THE
 DETAILS/SECTIONS APPEAR TO ADDRESS THIS,
 THE PLANS SHOULD BE ANNOTATED TO
 DEMONSTRATE COMPLIANCE.
  
 39) FBC 11-4.16 AND 11-4.19SHEET A5.11
 THIS SHEET HAS INSUFFICIENT/INCORRECT
 DIMENSIONS TO DEMONSTRATE COMPLIANCE
 WITH ACCESSIBILTY REQUIREMENTS FOR THE
 LIVE/WORK UNIT BATHROOMS.THE SHEET
 SHOULD BE CORRECTED AND REFER TO SHEET
 A9.14 SO THAT:
 (A) THE SIDE GRAB BAR AT THE W.C. SHALL
 BE A MIN. 42" LONG (SHOWN AS 40" ON
 SHEET A5.11)
 (B) THE HEIGHT OF THE W.C. PAN RIM
 SHALL BE BETWEEN 17' AND 19" ABOVE FLOOR
 LEVEL (NO DIMENSION IS STATED ON SHEET
 A5.11)
 (C) THE KNEE AND TOE CLEARANCES UNDER
 THE LAVATORIES ARE NOT DIMENSIONED ON
 SHEET A5.11 AND SHOULD BE REFERENCED TO
 THE DETAIL ON SHEET A9.14 WHICH WAS
 EXTRACTED FROM FIG 31 OF FLORIDA
 ACCESSIBILITY CODE.
 NOTE: IT IS NOTED THAT GENERAL
 ACCESSIBILTY REQUIREMENTS ARE SHOWN ON
 SHEET A9.14 BUT SHEET A5.11 GIVES MORE
 SPECIFIC REFERENCE AND IS NOT CORRECT.
  
 40) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 41) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-01-28 Cont ID  
Sent By rbrown Date 2005-01-28 Time 14:47 Rev Time 0.00
Received By rbrown Date 2005-01-20 Time 09:13 Sent To  
Notes
2005-01-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) WORKING DRAWING REVIEW ONLY.NO
 PERMIT CAN BE ISSUED UNTIL THE PERMIT
 APPLICATION AND FEES ARE SUBMITTED.
  
 2) FBC* 104.2IT IS NOTED THAT THE
 PLANS ARE NOT COMPLETE AT THIS STAGE.
 WHEN THE PLANS ARE SUBMITTED FOR PERMIT
 THEY SHALL BE COMPLETE AND SIGNED AND
 SEALED BY THE DESIGNERS OF RECORD.
  
 3) IMPACT FEES. IT IS NOTED THAT THE
 PLANS HAVE BEEN SUBMITTED FOR WORKING
 DRAWING REVIEW ONLY.PLEASE NOTE THAT
 BECAUSE THE PERMIT APPLICATION WILL BE
 FILED AFTER DECEMBER 30, 2004, THE FEE
 WILL BE BASED ON THE NEW (HIGHER)
 IMPACT FEE RATES.FOR MORE INFORMATION
 ON PALM BEACH COUNTY IMPACT FEES GO TO:
  
 HTTP://WWW.CO.PALM-BEACH.FL.US/PZB/
 IMPACTFEES/IMPACTFEES.HTM
  
 BEFORE A PERMIT CAN BE ISSUED, THE
 PLANS SHALL BE TAKEN TO PALM BEACH
 COUNTY BUILDING DEPARTMENT FOR IMPACT
 FEE ASSESSMENT. THEY SHALL BE STAMPED
 AT
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT SUBMITTED TO THE CITY OF WEST
 PALM BEACH DEPT OF CONSTRUCTION
 SERVICES
  
 4) NOTE THAT THE NOTICE OF
 COMMENCEMENT, IMPACT FEE RECEIPT AND
 SPECIAL INSPECTOR AGREEMENT WILL BE
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
 ALSO A DECLARATION OF CONDOMINIUM WILL
 BE REQUIRED BEFORE CERTIFICATE OF
 OCCUPANCY.
  
 5) FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 LICENSED SURVEYOR/MAPPER IS REQUIRED.
 (REF: 472.025(1) FL. STATUTES).UNITY
 OF TITLE AND HORIZONTAL SEPARATION
 REQUIREMENTS CANNOT BE ASSESSED WITHOUT
 A SITE SURVEY.
  
 6) A SEPARATE PERMIT APPLICATION WILL
 BE REQUIRED FOR THE SWIMMING POOL AND
 SPA.
  
 7) FBC* 105.13.1SPECIAL INSPECTOR
 AGREEMENT.BEFORE A PERMIT CAN BE
 ISSUED IT WILL BE NECESSARY TO ARRANGE,
 WITH HAROLD PISKURA (INSPECTION
 SERVICES
 MANAGER - TEL: 561 805 6711), A MEETING
 INVOLVING THE OWNER, THRESHOLD
 INSPECTOR, JOB INSPECTOR, CONTRACTOR
 AND ENGINEER.
  
 8) FBC* 1804.2.2SHEET S-0, GENERAL
 NOTES - FOUNDATIONS.SUBMIT THREE
 COPIES OF ARDAMAN & ASSOCIATES SOIL
 REPORT DATED 7/28/04 AS REFERENCED
 UNDER THE 'FOUNDATION' NOTE.
  
 9) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 10) SUBMIT PRODUCT APPROVALS FOR THE
 WINDOWS, STOREFRONTS, EXTERIOR DOORS
 AND ROOFING PRODUCTS.
  
 11) FBC TABLE 600SHEET A1.01, FIRE
 RESISTANCE OF STRUCTURAL ELEMENTS.IT
 IS NOTED THAT THE INDEX OF DRAWINGS
 REFERS TO SHEETS LS0.00 - CODE DATA AND
 LS1.00 - SITE PLAN & LIFE SAFETY NOTES
 AND THESE SHEETS WERE NOT SUBMITTED.
 THE REQUIRED FIRE RESISTANCE RATINGS OF
 STRUCTURAL ELEMENTS (WALLS, COLUMNS,
 BEAMS, FLOORS ETC) FOR A TYPE I
 BUILDING ARE NOT STATED ON THE PLANS
 AND
 SHOULD BE ADDED TO ONE OF THE
 ARCHITECTURAL SHEETS OR STRUCTURAL
 NOTES
 SHEET S-0.0
  
 12) FBC TABLE 600SHEET LS1.01,
 HORIZONTAL SEPARATION.THE GENERAL
 NOTES AND THE BUILDING ELEVATION SHEETS
 A3.01 TO A3.04 DO NOT STATE WHETHER THE
 AREA OF WALL OPENINGS EXCEEDS 40% OF
 THE WALL AREA.ADD A TABLE OR NOTES TO
 SHOW THAT THE AREA OF WALL OPENINGS
 DOES
 NOT EXCEED THAT ALLOWED BY THE PROVIDED
 HORIZONTAL SEPARATION.SEE THE ABOVE
 COMMENT REQUIRING A SURVEY DRAWING.
  
 13) FBC 707.1 SHEET S A9.02 AND A9.12,
 COMBUSTIBLES IN CONCEALED SPACES.IN
 TYPE I CONSTRUCTION., ALL WOOD BUCKS,
 HEADERS, FURRING STRIPS ETC SHALL BE
 APPROVED FIRE RETARDANT TREATED LUMBER.
 NOTE 1 ON SHEETA9.13 REFERS TO WOOD
 BACKING, BLOCKING ETC FOR THE
 INSTALLATION OF FINISHES.
 AMEND/ANNOTATE SHEETS A9.02 AND A9.12
 TO DEMONSTRATE COMPLIANCE.
  
 14) FBC 704.2.4SHEET LS1.01, EXIT
 ACCESS CORRIDORS.THE CROSS-CORRIDOR
 WALL LINKING THE MAIL ROOM TO ELEVATOR
 VESTIBULE #3, AND THE MECHANICAL ROOM
 TO THE CONFERENCE ROOM, AND THE WALLS
 SEPERATING THE CORRIDOR FROM THE
 JANITOR?S, MECHANICAL AND CONFERENCE
 ROOM ARE NOT SHOWN AS FIRE-RATED.IT
 IS NOTED THAT THE DOORS IN THESE WALLS
 ARE ALREADY SPECIFIED AS FIRE-RATED ON
 SHEET A9.11, DOOR SCHEDULE.
  
 15) FBC 701.1.1SHEET LS1.01,
 EMERGENCY GENERATOR ROOM.NO FIRE
 SEPARATION IS CURRENTLY SHOWN BETWEEN
 THE GENERATOR ROOM AND THE ADJACENT
 ENTRY/EXIT. AMEND THE PLAN.
  
 16) FBC 701.1.1SHEET LS1.01,WASTE
 CONTAINER TOWING EQUIPMENT AREA.THE
 REQUIRED 2 HOUR FIRE SEPARATION IS NOT
 SHOWN BETWEEN THIS STORAGE ROOM AND THE
 PARKING GARAGE.AMEND THE PLAN.ALSO,
 SHEET A4.11 DOES NOT SHOW ANY DOOR
 SCHEDULE REFERENCE FOR THE DOOR IN
 ORDER TO VERIFY THE DOOR FIRE RATING.
  
 17) FBC 701.1.1SHEETS LS1.01 AND
 LS1.02,BUILDING STORAGE ROOM.THE
 REQUIRED 2 HOUR FIRE SEPARATION IS NOT
 SHOWN FOR THE WALL BETWEEN THE PARKING
 GARAGE AND THE BUILDING STORAGE ROOM AT
 THE WEST END OF THE PARKING GARAGE.
 AMEND THE PLAN
  
 18) FBC 704.1.3.2SHEETS LS1.04,
 LS1.05 AND LS1.06, TENANT STORAGE
 ROOMS.
 THESE ARE REQUIRED TO HAVE 2 HOUR FIRE
 SEPARATION FROM THE PARKING GARAGE.
 FBC 704.1.2.2 DOES NOT APPLY HERE AS
 THE
 STORAGE ROOMS ARE ACCESSORY TO THE
 RESIDENTIAL OCCUPANCY NOT THE PARKING
 GARAGE.
  
 19) FBC 704.2.4SHEET LS1.04, WALL
 BETWEEN TENANT STORAGE ROOM AND PUBLIC
 CORRIDOR.THE NOTE ON THE PLAN REFERS
 TO FBC 704.1.2.2 EXCEPTION NO.4 AS
 JUSTIFICATION FOR NOT FIRE-RATING THIS
 WALL.THAT SECTION IS NOT APPLICABLE
 IN THIS CASE BECAUSE THE CORRIDOR IS AN
 EXIT ACCESS CORRIDOR AND IS REQUIRED TO
 BE FIRE RATED.AMEND THE PLAN.
  
 20) FBC* 104.2.1SHEETS A2.02, A2.05,
 A2.07 AND A2.09.ADD NOTES TO THESE
 SHEETS TO CLARIFY THAT THE UNLABELLED
 SPACE AROUND THE PARKING GARAGE IS
 ACTUALLY OCCUPIED BY 'RESIDENTIAL UNIT
 BELOW' AND 'CORRIDOR BELOW'.THE NOTES
 SHOULD STATE THAT THE REQUIRED
 FIRE-RATING FOR THE WALLS IS STATED ON
 THE PLAN FOR THE FLOOR BELOW.
  
 21) FBC* F102.2.7SHEETS A3.01 TO
 A3.06 ELEVATIONS.THE KEY NOTES REFER
 TO 'F11'-FOAM COLUMN AND 'A'-MOULDING
 TYPES SEE SHEETS A??.ARCHITECTURAL
 TRIM, ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 22) FBC 1012.1.2SHEET A2.16, EXIT
 DOOR LEADING TO STAIR #2.THIS DOOR
 SHALL OPEN IN THE DIRECTION OF EGRESS.
 AMEND THE PLAN.
  
 23) FBC 1012.1.4SHEET A7.12,STAIR
 #6.DURING ITS SWING, THE EXIT DOOR AT
 LEVELS P2 TO P9 SHALL LEAVE AT LEAST
 HALF OF THE REQUIRED STAIR WIDTH
 UNOBSTRUCTED.AMEND/ANNOTATE THE PLAN
 WITH DIMENSIONS TO DEMONSTRATE
 COMPLIANCE.
  
 24) FBC 1015.3SHEET A9.21, DETAIL 10,
 TYPICAL BALCONY GUARDRAIL.THE
 ORNAMENTAL PATTERN SHALL BE SUCH THAT A
 4? DIAMETER SPHERE CANNOT PASS THROUGH
 ANY OPENING UP TO A HEIGHT OF 34?.A
 BOTTOM RAIL OR CURB SHALL BE PROVIDED
 TO REJECT THE PASSAGE OF A 2? DIAMETER
 SPHERE.AMEND THE PLANS TO DEMONSTRATE
 COMPLIANCE.THE NOTE ON SHEET A10.02,
 DETAIL 1 IS FOR A DIFFERENT
 SITUATION/LOCATION.
  
 25) NFPA 823-2.4.3.1SHEET A7.14,
 TRASH CHUTE SERVICE OPENING ROOM.
 THERE SHALL BE MINIMUM 6" CLEARANCE
 BETWEEN THE OPEN CHUTE LOADING DOOR AND
 CLOSED SERVICE OPENING ROOM DOOR.
 AMEND
 THE PLANS.
  
 26)FBC 11-4.9.4SHEETS A7.05 AND
 A7.05A, STAIR #2.THE REQUIRED
 HANDRAIL EXTENSION LENGTHS AT THE TOP
 AND BOTTOM OF EACH FLIGHT ARE
 TRANSPOSED
 (TOP=BOTTOM, BOTTOM=TOP) AT 6TH LEVEL,
 7-14TH LEVEL, 15TH LEVEL AND 16TH
 LEVEL.
 AMEND THE PLANS.
  
 27) FBC 11-4.13.6SHEET A4.42,
 MANEUVERING CLEARANCES AT DOORS.IT IS
 NOTED THAT THIS SHEET IS NOT COMPLETE.
 THE DOORS PENCILED IN AS DOORP24 (TO
 THERAPY ROOM) SHALL HAVE A MIN. 18?
 CLEARANCE BETWEEN THE STRIKE EDGE OF
 THE DOOR AND THE ADJACENT PERPENDICULAR
 WALL.AMEND/ANNOTATE THE PLANS WITH
 DIMENSIONS TO DEMONSTRATE COMPLIANCE.
 THE SAME ALSO APPLIES TO DOOR REFERENCE
 S14, SHOWN ON SHEET A4.02.
  
 28) FBC 411.2.3SHEET A2.02, A2.05,
 A2.07 AND A2.09, VEHICLE IMPACT
 WALLS/GUARDRAILS.AMEND THE PLANS TO
 SHOW THE REQUIRED IMPACT
 WALLS/GUARDRAILS AT THE PERIMETER WALLS
 OF THE PARKING GARAGE.THIS ALSO
 APPLIES TO THE WALL, SHOWN ON SHEET
 A2.02, BETWEEN THE PARKING GARAGE AND
 THE VOID ABOVE THE NORTH PARKING GARAGE
 ENTRY/EXIT, AND TO THE NORTH PORTION OF
 THE WEST WALL AT ALL PARKING GARAGE
 LEVELS ABOVE GROUND.IMPACT GUARDRAILS
 ARE ALSO REQUIRED IN FRONT OF THE
 GARAGE EXHAUST AIR SHAFT LOUVERS AT THE
 WEST END OF EACH PARKING GARAGE LEVEL
 ABOVE GROUND.AMEND THE PLANS.
  
 29) FBC 1608.2.2SHEET A8.21, DETAILS
 A AND A1 AND SHEET A9.21, DETAIL 10.
 THE GUARDRAIL SHALL BE DESIGNED
 AND CONSTRUCTED FOR A CONCENTRATED LOAD
 OF 200 LB APPLIED IN ANY DIRECTION AT
 THE TOP OF THE GUARDRAIL, A
 CONCENTRATED HORIZONTAL LOAD OF 200 LB
 APPLIED ON A 1 SQ FT AREA AT ANY POINT,
 AND A LINE LOAD OF 50 PLF APPLIED
 HORIZONTALLY AT THE REQUIRED GUARDRAIL
 HEIGHT WITH A SIMULTANEOUS LINE LOAD OF
 100 PLF APPLIED VERTICALLY DOWNWARD ON
 THE TOP OF THE GUARDRAIL. THESE LOADS
 SHALL NOT BE APPLIED SIMULTANEOUSLY
 (UNLESS NOTED ABOVE) BUT SHALL BE
 APPLIED INDIVIDUALLY TO PRODUCE MAXIMUM
 STRESS IN EACH OF THE COMPONENTS OR
 SUPPORTS.AMEND/ANNOTATE THE PLANS.
  
 30) FBC* 104.2.1THE SUBMITTED
 STRUCTURAL PLAN SET DOES INCLUDE A
 GROUND FLOOR REINFORCING PLAN AND THE
 HIGH ROOF REINFORCING PLAN IS NOT
 COMPLETE. SUBMIT COMPLETE PLANS FOR
 REVIEW.
  
 31) FBC 3502SHEET S-0.0, GENERAL
 NOTES THE PLANS REFERENCE ACI 530.1-99
 AND ACI 318-99 (TWICE) UNDER THE
 SUB-TITLES 'CODES' AND 'THRESHOLD
 BUILDING INSPECTION PLAN'.THE
 VERSIONS
 OF THESE STANDARDS REFERENCED BY
 FLORIDA
 BUILDING CODE ARE ACI 530.1-02 AND ACI
 318-02. AMEND THE GENERAL NOTES.
  
 32) FBC 3502SHEET S-0.0, GENERAL
 NOTES THE PLANS REFERENCE ASTM A 185-85
 AND ASTM A 615-84A (TWICE) UNDER THE
 SUB-TITLES 'WELDED WIRE FABRIC' AND
 'REINFORCING STEEL'.THE VERSIONS OF
 THESE STANDARDS REFERENCED BY FLORIDA
 BUILDING CODE ARE ASTM A 185-97 AND
 ASTM A 615-94.AMEND THE GENERAL
 NOTES.
  
 33) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE
 RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL
 INFO
 TELEPHONE: (561) 805 6716ROBERT
 BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 35 Status F Date 2008-09-11 Cont ID  
Sent By dpalmer Date 2008-09-11 Time 09:23 Rev Time 0.00
Received By dpalmer Date 2008-09-11 Time 09:23 Sent To PC
Notes
2008-09-11 09:23:31 
  
  
  
 ** DENIED REVIEW OF REVISION**
  
  
  
 1) NOTE: ALL SITE LIGHTING IN RIGHT OF WAY AREAS SHALL
 NOT BE PERMITTED AS PART OF THE BASE BUILDING. ANY
 RIGHT OF WAY LIGHTING MAY NOT BE FED FROM BASE BUILDING
 ELECTRICAL SERVICE.
  
 2) NOTE: ANY ELECTRICAL PART OF THE BASE BUILDING NEEDS
 TO BE REVISED ON ELECTRICAL PLANS AND TO BE REVISED BY
 THE BASE BUILDING ELECTRICAL ENGINEER OF RECORD.
 FS 471
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 34 Status N Date 2008-03-21 Cont ID  
Sent By dpalmer Date 2008-03-21 Time 10:00 Rev Time 0.00
Received By dpalmer Date 2008-03-21 Time 10:00 Sent To PC
Notes
2008-03-21 10:01:03SUBMITTAL FOR AIR FILTERS, NA FOR ELEC

Review Stop E ELECTRICAL
Rev No 33 Status N Date 2008-03-21 Cont ID  
Sent By dpalmer Date 2008-03-21 Time 09:58 Rev Time 0.00
Received By dpalmer Date 2008-03-21 Time 09:58 Sent To PC
Notes
2008-03-21 09:58:47SUBMITTAL FOR PRESSURE SENSORS, NOT FOR ELEC, AND NOT
 NEEDED.

Review Stop E ELECTRICAL
Rev No 32 Status F Date 2008-03-15 Cont ID  
Sent By jleahy Date 2008-03-15 Time 21:05 Rev Time 3.50
Received By jleahy Date 2008-03-15 Time 20:24 Sent To  
Notes
2008-03-15 21:01:21PG. E2.02THE TWO A/CS IN P1 SHOW OCP THAT
 VIOLATES THE NAMEPLATE OF THE UNITS PLEASE CORRECT OCP
 FOR UNITS
  
 PG. E2.02SHOWS TWO SWITCHES TO FIXTURES ABOVE,
 ARE THESE FIXTURES IN THE SAME ROOM? PLAN IS
 CONFUSING.
  
 PG. E4.01 COMMUNICATION ROOM SHOW TAILS TO
 EQUIPMENT, HOW DO YOU KNOW TAILS WILL BE LARGE ENOUGH
 (AMPEREAGE)?
 YOU WILL NEED TO SUPPLY
 EQUIPMENT DETAILS FOR SIZING BRANCH CIRCUITS.ALSOL
 NEED TO SHOW EQUIPMENT ON PLANS.
  
 PG. E6.01LOOKING AT REV1 FOR THE GENERATOR SHOWS
 TWO BREAKERS BUILTIN, ON JOB ONE WAS ADDED TO
 GENERATOR, PLEASE HAVE GENERATOR RELISTED TO SHOW ONE
 INTERNAL
 AND ONE EXTERNAL.
  
 PG. E6.08, E6.09SHOWS TWO 4" CONDUITS STUBBING INTO
 THE CORIDOOR CEILING, DO YOU WANT ACCESS PANELS IN THE
 CORIDOOR CEILING TO BE ABLE TO ACCESS PIPES?
 SHOWS A 20 DEDICATED
 CIRCUIT TO COMMUNICATIONS PANEL IN BEDROOM CLOSET. THIS
 NEEDS TO BE AFCI PROTECTED.210.12
 SHOWS A CADWELL PLATE FOR
 GROUNDING, IS THIS JUST A TYPE OR ARE THE WIRES TO BE
 CADWELDED TO THIS BAR?
  
 PG. E7.14TRANSFORMER THAT FEEDS LGHE IS PROTECTED ON
 PRIMARY BY 3 POLE 25A BREAKER, AND SECONDARY HAS 100A.
 THERE IS NOT A 100A AVAILABLE ON THE SECONDARY SIDE
 PRIMARY HAS ROOM FOR 2.7 AMPERES. I WILL LOOK INTO THIS
 FURTHER AND GET BACK TO YOU BUT I DON'T FEEL THAT THE
 SECONDARY SHOULD BE PROTECTED BY 100A MAIN
 WHEN THERE IS NO ROOM FOR FUTURE
 EXPANSION.IF LOAD GOES TO 100% THE 25AMP MAIN SHOULD
 TRIP.

Review Stop E ELECTRICAL
Rev No 31 Status P Date 2008-03-10 Cont ID  
Sent By jleahy Date 2008-03-10 Time 10:02 Rev Time 2.00
Received By jleahy Date 2008-03-10 Time 10:01 Sent To  
Notes
2008-03-10 10:02:04THIS IS REV #22JL

Review Stop E ELECTRICAL
Rev No 30 Status F Date 2008-03-10 Cont ID  
Sent By jleahy Date 2008-03-10 Time 07:27 Rev Time 2.00
Received By jleahy Date 2008-03-10 Time 07:19 Sent To  
Notes
2008-03-10 07:23:52ONE SET NOT SEALED ONLY A COPY OF SIGNATURE, AND THREE
 SETS ARE NEEDED FOR THIS JOB.
  
 SETS ARE OTHERWISE OK.
  
 JAKE LEAHY 644-7291

Review Stop E ELECTRICAL
Rev No 29 Status F Date 2008-01-24 Cont ID  
Sent By dpalmer Date 2008-01-24 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2008-01-24 Time 12:55 Sent To FIRE
Notes
2008-01-24 12:55:27** DENIEDREVIEW OF REVISIONS. **
  
 THIS REVIEW STOP WILL REMAIN IN FAIL STATUS EVEN AS
 SOME SHEETS WERE OK.
  
 ** PLEASE KNOW THE FOLLOWING SHEETS SUBMITTED UNDER
 REVISION 19 ARE OK.
 SHEETS, 3.11, 7.13 AND 7.16 ARE OK AND STAMPED.
 RETAINED ONE FOR FILE SET.
  
  
 1) NOTE: PLEASE SEE SHEETS 1.03A AND 1.04 A ARE NOT
 PART OF THE BASE BUILDING AND WILL REQUIRE THIS LOW
 VOLTAGE WORK FOR SOUND SYSTEM TO BE SUBMITTED UNDER
 SEPARATE PERMIT.
  
 2) NOTE: PLEASE SEE SHEET 3.06 CAN NOT BE STAMPED BASED
 ON ITEMS FROM FIRE REVIEW COMMENTS ON 1/23/08.
 THIS SHEET IS OK WITH ELECTRICAL HOWEVER WILL HAVE
 COMMENTS FROM FIRE REVIEW.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 28 Status F Date 2008-01-23 Cont ID  
Sent By dpalmer Date 2008-01-23 Time 15:46 Rev Time 0.00
Received By dpalmer Date 2008-01-23 Time 15:46 Sent To PC
Notes
2008-01-23 15:47:33ELECTRICAL SHEETS WHICH WERE PASSED AND STAMPED HAVE
 NOW BEEN VOIDED BASED ON FIRE PLAN REVIEW COMMENTS BY
 FIRE MARSHAL.
 ELECTRICAL SHEETS FOR PANEL SCHEDULE ARE STILL OK AND
 ONLY VOIDED UNIT PLANS AND LAYOUTS.

Review Stop E ELECTRICAL
Rev No 27 Status N Date 2008-01-15 Cont ID  
Sent By dpalmer Date 2008-01-15 Time 16:21 Rev Time 0.00
Received By dpalmer Date 2008-01-15 Time 16:21 Sent To M
Notes
2008-01-15 16:22:48GENRATOR SILENCER SUBMITTAL. N/A.
 HS BILL 7121 STILL APPLIES FROM PREVIOUS REVIEWS.

Review Stop E ELECTRICAL
Rev No 26 Status P Date 2007-12-25 Cont ID  
Sent By dpalmer Date 2007-12-25 Time 11:14 Rev Time 0.00
Received By dpalmer Date 2007-12-25 Time 11:14 Sent To  
Notes
2007-12-25 11:15:06** PROVISO **
  
  
 1) NOTE: PLEASE SEE NOTES FROM REVIEW ON 8/26 WITH
 RESPECT TO HOUSE BILL 7121 AND BACK UP FULE REQUIRED.
 THIS IS BEING NOTED ONCE AGAIN FOR INFORMATION.
  
 ** REVISED ELECTRICAL SHEETS STAMPED PENDING FIRE
 REVIEW. IF FIRE REVIEW IS OK, ONE SET WILL BE RETAINED
 FOR FILE.
 SHEETS INCLUDE
 3.06,3.14,3.23,3.25,3.31,3.32,3.34,7.12,7.15,1705-1.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 25 Status P Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 18:36 Sent To  
Notes
2007-12-03 18:36:57REV'S ON 8 1/2 BY 11'S OK, WILL STILL NEED TO RIVISE ON
 LARGE FULL SIZED SHEETS FOR FINAL.

Review Stop E ELECTRICAL
Rev No 24 Status P Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 08:57 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 08:57 Sent To PC
Notes
2007-12-03 08:58:20STEAM UNITS ARE LISTED.

Review Stop E ELECTRICAL
Rev No 23 Status P Date 2007-08-26 Cont ID  
Sent By dpalmer Date 2007-08-26 Time 20:28 Rev Time 0.00
Received By dpalmer Date 2007-08-26 Time 17:10 Sent To  
Notes
2007-08-26 20:28:382007-08-26 20:28:38
  
 ** TWO CITY PLAZA **
 REVISIONS.
  
 **PLEASE SEE MANY OF THE SHEETS WERE OK AND WERE
 STAMPED. THESE ARE OK PENDING FIRE REVIEW.
  
 ** PLEASE SEE THE SUBMITTED ELECTRICAL NARRATIVE WAS
 NOT ACCURATE FOR ALL SHEETS BASED ON THE ELECTRICAL
 SHEETS SUBMITTED. THERE WERE SEVERAL SHEETS SUBMITTED
 WHICH WERE NOT ON THE NARRATIVE LIST.
 PLEASE SEE THE FOLLOWING COMMENTS:
  
  
 1) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES WITH
 RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS SIGNED
 INTO LAW JULY OF 07.
 PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE
 AFFECTED. PLEASE SEE THAT AN INDUSTRY BULLETIN IS BEING
 PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL
 INFORMATION.
 *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED,
 PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND
 DOCUMENTATION FOR REVIEW.
 PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE
 NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS
 ETC.
  
 2) NOTE: PLEASE SEE REVIEW NOTES DATED 3/10/07 HAVE NOT
 BEEN FULLY ADDRESSED AS OF YET.
 PLEASE SEE THE FOLLOWING WHICH WAS STATED ON THAT
 REVIEW.
 ****
 2) NOTE: PLEASE SEE NFPA-20, 1999 OR 2003. PLEASE KNOW
 THE AMOUNT OF FUEL FOR THE FIRE PUMP SHALL BE REVISED
 FOR THE ON-SITE POWER OF THE GENERATOR TO INDICATE THE
 MINIMUM FUEL AS STATED. PLEASE KNOW THAT THE ACTUAL
 LOAD ON THE GENERATOR WITH ALL ASSOCIATED OTHER LOADS
 SHALL BE CONSIDERED THE BASIS FOR THE FUEL CONSUMPTION
 PER HOUR. THE PLANS INDICATE 92.1 GALS PER HOUR AT THIS
 TIME.
 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT TO
 PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100 PERCENT
 OF THE RATED PUMP CAPACITY IN ADDITION TO THE SUPPLY
 REQUIRED FOR OTHER DEMANDS.
  
 3) NOTE: PLEASE SEE SHEET E3.32 WAS REPEATED IN TWO
 SETS.
  
 4) NOTE: PLEASE SEE SHEET E-1705.1 IS NOT TO THE
 MINIMUM SCALE AS REQUIRED UNDER THE FBC ADMIN SECTION.
 104.1.2 OR THE CURRENT CODE ADMIN SECTION WHICH STATES
 THE SAME AS THE ADMIN CODE IN EFFECT AT THE TIME OF
 PERMIT.106.1.3
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 22 Status P Date 2007-08-26 Cont ID  
Sent By dpalmer Date 2007-08-26 Time 18:26 Rev Time 0.00
Received By dpalmer Date 2007-08-26 Time 17:11 Sent To PC
Notes
2007-08-26 18:26:51LT SUBMITTAL FROM 8/13
 ONE FIXTURE

Review Stop E ELECTRICAL
Rev No 21 Status P Date 2007-08-03 Cont ID  
Sent By dpalmer Date 2007-08-03 Time 10:24 Rev Time 0.00
Received By dpalmer Date 2007-08-03 Time 10:24 Sent To PC
Notes
2007-08-03 10:24:39I LIGHTING SUBMITTAL CHANGE.

Review Stop E ELECTRICAL
Rev No 20 Status N Date 2007-08-03 Cont ID  
Sent By dpalmer Date 2007-08-03 Time 10:23 Rev Time 0.00
Received By dpalmer Date 2007-08-03 Time 10:23 Sent To PC
Notes
2007-08-03 10:24:00TWO SETS OF SUBMITTALS NOT NEEDED.

Review Stop E ELECTRICAL
Rev No 19 Status N Date 2007-08-26 Cont ID  
Sent By dpalmer Date 2007-04-19 Time 18:31 Rev Time 0.00
Received By dpalmer Date 2007-04-19 Time 16:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 18 Status N Date 2007-08-26 Cont ID  
Sent By dpalmer Date 2007-04-19 Time 18:32 Rev Time 0.00
Received By dpalmer Date 2007-04-19 Time 16:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 17 Status F Date 2007-03-10 Cont ID  
Sent By dpalmer Date 2007-03-10 Time 13:03 Rev Time 0.00
Received By dpalmer Date 2007-03-10 Time 13:02 Sent To  
Notes
2007-03-10 13:03:55** UNSAT**
  
 1) NOTE: PLEASE SEE THE SITE LIGHTING SHEET WITH
 LIGHTING WHICH IS CONTAINED IN THE *RIGHT OF WAY* SHALL
 BE UNDER A SEPARATE PERMIT AND CAN NOT BE INCLUDED IN
 THE BASE BUILDING PLANS. THIS WILL GO THROUGH
 ENGINEERING, BUILDING AND ELECTRICAL REVIEW ONCE
 SUBMITTED.
 * THIS SHEET WAS NOT STAMPED IN SETS AND VOIDED.
  
 2) NOTE: PLEASE SEE NFPA-20, 1999 OR 2003. PLEASE KNOW
 THE AMOUNT OF FUEL FOR THE FIRE PUMP SHALL BE REVISED
 FOR THE ON-SITE POWER OF THE GENERATOR TO INDICATE THE
 MINIMUM FUEL AS STATED. PLEASE KNOW THAT THE ACTUAL
 LOAD ON THE GENERATOR WITH ALL ASSOCIATED OTHER LOADS
 SHALL BE CONSIDERED THE BASIS FOR THE FUEL CONSUMPTION
 PER HOUR. THE PLANS INDICATE 92.1 GALS PER HOUR AT THIS
 TIME.
 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT TO
 PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100 PERCENT
 OF THE RATED PUMP CAPACITY IN ADDITION TO THE SUPPLY
 REQUIRED FOR OTHER DEMANDS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2007-03-10 Cont ID  
Sent By dpalmer Date 2007-03-10 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2007-03-06 Time 20:11 Sent To  
Notes
2007-03-10 13:03:21MOST ELECTRICAL SHEETS OK, PLEASE SEE NOTES ADDED ON
 3/10/07 FOR SHEETS E1.02 AND SHEET 6.01.
 STAMPED OTHER SHEETS IN SETS AND VOIDED THE ABOVE
 SHEETS AS NOT TO BE PART OF THIS REVISION.
2007-03-10 11:35:24IN PROGRESS
2007-03-06 20:10:252007-03-06 20:10:25
 IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 15 Status N Date 2007-02-08 Cont ID  
Sent By dpalmer Date 2007-02-08 Time 11:45 Rev Time 0.00
Received By dpalmer Date 2007-02-08 Time 11:45 Sent To M
Notes
2007-02-08 11:46:00SUBMITTALS FOR CO SENSORS NOT NEEDED FOR ELECTRICAL
 REVIEW.

Review Stop E ELECTRICAL
Rev No 14 Status P Date 2006-11-06 Cont ID  
Sent By pkrauss Date 2006-12-29 Time 10:18 Rev Time 1.00
Received By jleahy Date 2006-11-06 Time 07:17 Sent To  
Notes
2006-11-06 07:20:18NO CIRCUITS SHOWN ON DRAWINGS
  
 THE FOLLOWING ARE NOT SHOWN AS A LISTED PRODUCT(S)
  
 TYPE SE, SH, SJ, SK

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2006-11-06 Cont ID  
Sent By jleahy Date 2006-11-06 Time 07:14 Rev Time 1.30
Received By jleahy Date 2006-11-06 Time 07:04 Sent To  
Notes
2006-11-06 07:12:45SUBMITTALS APPROVED ACCEPT AS NOTED
  
 FIXTURE TYPE WBT- 232-B11-UNV-LA, TYPE C5 NO OPTION FOR
 BATTERY BACKUP SHOWN???
  
 NO BATH FIXTURES FOR FLOORS 16-21 SHOWN
  
 THE FOLLOWING ARE NOT SHOWN AS A LISTED PRODUCT(S).
  
 TYPE AC, AU, TRIMS LA, LB, LE, LF
  
  

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2006-10-12 Cont ID  
Sent By dpalmer Date 2006-10-12 Time 18:01 Rev Time 0.00
Received By dpalmer Date 2006-10-12 Time 18:00 Sent To B
Notes
2006-10-12 18:08:21** UNSAT *****
  
  
  
 1) NOTE:PLEASE SEE WIND LOAD CALCULATIONS FOR ANY
 POLE LTS WILL BE REQUIRED TO CONTAIN THE TITLE BLOCK,
 SIGNED, DATED AND SEALED BYTHE DESIGN PROFESSIONAL .
 FS 471.025. FAC 61G15-23.002
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANREVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2006-10-12 Cont ID  
Sent By dpalmer Date 2006-10-12 Time 15:30 Rev Time 0.00
Received By dpalmer Date 2006-10-12 Time 15:30 Sent To FIRE
Notes
2006-10-12 15:32:03FIRE PUMP SUBMITTIALS OK.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2006-10-12 Cont ID  
Sent By dpalmer Date 2006-10-12 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2006-10-12 Time 15:05 Sent To PC
Notes
2006-10-12 15:24:53**** UNSAT ****
  
 1) NOTE: PLEASE SEE THAT THE "LIGHTING PROTECTION"
 PLANS MUST BE SUBMITTED UNDER A SEPARATE PERMIT WITH
 PLANS SIGNED , DATED AND SEALED BY A PE.
 PLEASE ALSO KNOW, SEPARATE PLANS (3-SETS) AND FEES WILL
 BE DUE BASED ON VALUEFOR THIS SCOPE OF WORK.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status N Date 2006-10-12 Cont ID  
Sent By dpalmer Date 2006-10-12 Time 15:02 Rev Time 0.00
Received By dpalmer Date 2006-10-12 Time 15:02 Sent To PC
Notes
2006-10-12 15:03:59SUBMITTIALS FOR DEVICES/RECEPTS/LTS, NOT NEEDED.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2006-09-22 Cont ID  
Sent By dpalmer Date 2006-09-22 Time 17:20 Rev Time 0.00
Received By dpalmer Date 2006-09-22 Time 17:20 Sent To PC
Notes
2006-09-22 00:00:00** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT IF ALL THE LV/
 AV SYSTEMS ARE BEING DONE BY A SUB
 CONTRACTOR, ALL MUST BE SUBMNITTED UNDER
 A SEPARATE LV ELECTRICAL PERMIT.
 PLEASE KNOW, THESE SYSTEMS WERE NOT ON
 ORIGINAL PLANS AND NOT PART OF THE BASE
 BUILDING PLANS.
  
  
 2) NOTE: PLEASE KNOW ANY LV SECURITY
 MUST ALSO BE UNDER A LV SECURITY PERMIT.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-08-17 Cont ID  
Sent By dpalmer Date 2006-08-17 Time 17:50 Rev Time 0.00
Received By dpalmer Date 2006-08-17 Time 09:41 Sent To  
Notes
2006-08-17 00:00:00REV'S FROM 6, 6A IN ELEC FOR REVIEW.
 REV'S 6 AND 6A OK,
 REDLINED , 3/4" CONDUIT TO FEED FOR POOL
 LTS TOO SMALL FOR A TOTAL OF 4-#8'S
 REDLINED ALUM CONDUCTORS FOR FEEDERS ARE
 NOT PERMITTED SMALLER THAN #3.
 NO ALUM EQUIPMENT GROUNDING CONDUCTORS.

Review Stop E ELECTRICAL
Rev No 6 Status P Date   Cont ID  
Sent By   Date 2006-07-03 Time   Rev Time 0.00
Received By dpalmer Date 2006-07-02 Time 15:29 Sent To  
Notes
2006-07-02 00:00:00IN ELECTRICAL FOR REVIEW, REVIEW ALMOST
 COMPLETE.
 PROVISOADDRESSED, HOWEVER
 NEED TO VERIFY THE SEPARATELY DERIVED
 GEN SYSTEM.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-01-05 Cont ID  
Sent By dpalmer Date 2006-01-05 Time 08:56 Rev Time 0.00
Received By dpalmer Date 2006-01-05 Time 08:56 Sent To  
Notes
2006-01-05 00:00:00****************************************
 PLEASE SEE THE FOLLOWING WILL BE SET UP
 AS A "PROVISO" WHICH WILL REQUIRE SOME
 SHEETS TO BE REVISED "BEFORE ANY ROUGH
 ELECTRICAL INSPECTION" OR 6 MONTHS WHICH
 EVER COMES FIRST.
 THESE ITEMS HAVE ALSO BEEN REDLINED ON
 PLANS.
 ITEMS FROM PREVIOUS REVIEWS AND
 INFORMATION TO BE FORTH COMING.
  
  
 ********** PROVISO/REVISION ***********
  
 1)NOTE: PLEASE SEE MISSING RECEPTS IN
 UNITS
 "A", "G","D","HD". 210.52
 REDLINED
  
 2)NOTE:PLEASE SEE SOME AREAS LABLED AS
 "FOYER CONTAIN RECEPTS ON SMALL
 APPLIANCE CIRCUITS. SEE 210.52B1 UNIT
 G-1,E-1, VV1
 REDLINED.
  
 3)NOTE:PLEASE SEE THE FOLLOWING UNITS
 WHICH SMOKE DETECTORS ARE STILL SHOWN ON
 MORE THAN ONE CIRCUIT. SEE UNIT #4, C-1
 REDLINED.
  
 4)NOTE: PLEASE SEE UNIT "S" DINING RM
 DESIGNATION REMOVED.
 REDLINED
  
 5)NOTE: PLEASE SEE SHEET 7.09 DOES NOT
 CONTAIN THE FEEDER SCHEDULE FOR THE 225A
 PANEL "N", THIS WAS REVISED ON 7.08.
 REDLINED.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE FOR
 UNIT "D-2" WAS SUBMITTED, HOWEVER
 CIRCUIT #15 FOR SD'S DOES NOT INDICATE
 THE REQUIRED ARC FAULT PROTECTION NOTE.
 REDLINED ON PANEL SCHEDULE, UNIT.210.12
  
 7)NOTE:POOL AREA LIGHTING TO MEET MIN
 CLEARENCES PER 680.22 AND 411.4
 SOME FIXTURES SHOWN CLOSER THAN
 PERMITTED.
 REDLINED.
  
 8)NOTE:PLEASE SEE LS101 7.8.1.3 (1)
 WHICH REQUIRES A MIN OF 10FT
 CANDLES(108LUX) IN STAIR TOWERS. THIS
 LEVEL OF LIGHTING IS REQUIRED ON THE
 WALKING SURFACES DURING NOMRAL POWER
 CONDITIONS.(1FT CANDLE IN EMERGENCY
 CONDITIONS. PHOTO-METRICS WILL BE
 REQUIRED OF STAIR-
 TOWERS.
  
 PLEASE SEE LS101 7.9.2.2 WHICH MENTIONS
 IN THE EVENT OF THE TRIPPING OF ANY
 SINGLE MEANS OF OCP WSHOULD NOT LEAVE
 ANY EGRESS AREA IN TOTAL DARKNESS.
 PLEASE ALSO SEE A MIN OF SOME SORT OF
 BATTERY BACK UP FIXTURE FOR CORRIDOR'S
 AND PARKING GARAGE WILL BE REQUIRD TO
 PROVIDE MEANS OF EGRESS AT A LIGHTING
 LEVEL OF 1FT CANDLE.
  
 9)NOTE: PLEASE SEE 230.95,707.7D,700.26
 ETC.
 PLEASE SEE A 4-POLE ATS WILL BE
 REQUIRED.
 PLEASE KNOW, THE GFP IS NOT REQUIRED ON
 THE EMERGENCY/ GENERATOR SIDE OF THE EM
 DISTRIBUTION SYSTEM, HOWEVER PLEASE SEE
 THE ABOVE REFERENCES WHICH DO REQUIRE GF
 SENSING. PLEASE SEE THE FOLLOWING IS
 TAKEN DIRECTLY FROM ASCO DOCUMENTS
 FORWARD TO ME.
 "WHERE GROUND FAULTPROTECTION IS
 TRIGGERED BY THE CODE AND AN ALTERNATE
 POWER SUPPLY IS INCLUDED,SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY.THE
 SERVICE IS LARGER THAN 1,000 AMPS.
 CONSEQUENTLY, GROUNDFAULT PROTECTION
 IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF ITIS
 INSTALLED THERE AND THE GENERATOR
 NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL,
 A GROUND FAULT WHEN THE GENERATOR IS
 FEEDING THE LOAD WILL CAUSE THE MAIN
 SERVICE DISCONNECT TO OPEN. THIS WILL
 NOTDISCONNECT THE ARCING FAULT FROM
 THE GENERATOR. COORDINATION IS THUS
 LOST."
 PLEASE KNOW, IF THE MAIN IS IN THE
 OPENING POSITION WHEN POWERM COMES BACK
 ON, THE SENSING OF THE FPL WOULD CAUSE
 THE ATS TO SWITCH BACK, HOWEVER THERE
 WOULD NOT BE ANY POWER THROUGH THE
 ELECTRICAL SYSTEM AS THE MAIN FOR THE EM
 SYSTEM WOULD HAVE TRIPPED/OPENED.
 PLEASE REVISE RISER AND REVISE NOTES TO
 REFERENCE A 4-POLE TRANSFER SWITCH AND
 INDICATING THE SEPARATELY DERIVED
 SYSTEM.
  
  
 **PLEASE SEE THE ABOVE REDLINES/PROVISO
 ITEMS WILL NEED TO BE ADDRESSED BEFORE
 ANY ROUGH ELECTRICAL INSPECTION IS
 SCHEDULED.
 ** PLEASE KNOW, ELECTRICAL PERMIT MAY BE
 PLACED IN A "HOLD" STATUS UPON 6 MONTHS
 TIME TABLE AND "PROVISO" HAS NOT BEEN
 SUBMITTED.
  
 ** PLEASE KNOW, ANY OTHER
 REVISIONS/DESIGN CHANGES MAY ALSO BE
 SUBMITTED AT THAT TIME.
  
  
 ** PLEASE CALL TO GO OVER SUCH ITEMS
 LISTED ABOVE TO HELP IN EXPEDITING THIS
 PROJECT TO A "P" STATUS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-12-31 Cont ID  
Sent By dpalmer Date 2005-12-31 Time 12:17 Rev Time 11.00
Received By dpalmer Date 2005-12-30 Time 16:36 Sent To  
Notes
2005-12-31 00:00:00REVIEW STARTED, IN PROGRESS
 ** SEE ALL NOTES BELOW FOR CONDITIONS **
  
  
 ** PLANS TO REMAIN IN "F" STATUS UNTILL
 THE FOLLOWING NOTES ARE ADDRESSED TO
 CHANGE PROJECT TO "P" (PASSED) STATUS.
  
 1)NOTE: PLEASE SEE ONE SET IS MISSING
 SHEET E1.05
  
 2)NOTE: PLEASE SEE ALL THREE SETS ARE
 MISSING SHEETS E8.06-8.14 AS INDICATED
 ON COVER SHEET.?? THESE WERE IN PREVIOUS
 SETS? SEE PROVISO ALSO.
  
 2)NOTE: PLEASE SEE PREVIOUS REVIEWS
 WHICH REQUESTED ALL SUBMITTALS FOR ALL
 EQUIPMENT SPECS:
 PLEASE SEE THE FIRE PUMP AND FIRE PUMP
 CONTROLLER SPECS WERE SUBMITTED, HOWEVER
 THERE APPEARS TO BE ONLY ONE SET AND
 THEY ARE LOCATED IN THE REPSONSE PACKAGE
 BY THE ENGINEER. PLEASE SEE THE
 "EQUIPMENT SPEC BOOKS" SHOULD CONTAIN
 THREE SETS OF SAID SPECS FOR FP AND FPC.
  
 3)NOTE: PLEASE ALSO SEE NOTES PERTAINING
 TO "COLOR CODING SPEC SHEET" AND
 BUS-DUCT SPEC SHEET" WHICH WERE TO BE
 REVISED IN " JOBSITE SPEC BOOKS". THESE
 SHEETS WERE REVISED, HOWEVER THE ONE
 COPY OF THESE (BUS-DUCT) WAS SUBMITTED
 IN THE SAME PACKAGE WITH THE ENGINEER'S
 RESPONSES AND THE OTHER REVISED COPIES
 OF COLOR CODING WERE SUBMITTED IN EQUIP
 SPEC BKS..
 PLEASE SEE THREE COPIES OF THE REVISED
 16120-2 WERE PLACED IN EQIP SPEC BK
 INSTEAD IF JOBSITE SPEC BOOK.
  
 ** PLEASE BRING IN SHEETSNEEDED TO
 COMPLETE ALL THREE "JOBSITE SPEC BOOKS"
 AND THE THREE COPIES OF "EQUIPMENT SPEC
 BOOKS".
 THESE BOOKS WILL BE STAMPED AT THAT
 TIME.
  
 ****************************************
 PLEASE SEE THE FOLLOWING WILL BE SET UP
 AS A "PROVISO" WHICH WILL REQUIRE SOME
 SHEETS TO BE REVISED "BEFORE ANY ROUGH
 ELECTRICAL INSPECTION" OR 6 MONTHS WHICH
 EVER COMES FIRST.
 THESE ITEMS HAVE ALSO BEEN REDLINED ON
 PLANS.
 ITEMS FROM PREVIOUS REVIEWS AND
 INFORMATION TO BE FORTH COMING.
  
  
 ********** PROVISO/REVISION ***********
  
 1)NOTE: PLEASE SEE MISSING RECEPTS IN
 UNITS
 "A", "G","D","HD". 210.52
 REDLINED
  
 2)NOTE:PLEASE SEE SOME AREAS LABLED AS
 "FOYER CONTAIN RECEPTS ON SMALL
 APPLIANCE CIRCUITS. SEE 210.52B1 UNIT
 G-1,E-1, VV1
 REDLINED.
  
 3)NOTE:PLEASE SEE THE FOLLOWING UNITS
 WHICH SMOKE DETECTORS ARE STILL SHOWN ON
 MORE THAN ONE CIRCUIT. SEE UNIT #4, C-1
 REDLINED.
  
 4)NOTE: PLEASE SEE UNIT "S" DINING RM
 DESIGNATION REMOVED.
 REDLINED
  
 5)NOTE: PLEASE SEE SHEET 7.09 DOES NOT
 CONTAIN THE FEEDER SCHEDULE FOR THE 225A
 PANEL "N", THIS WAS REVISED ON 7.08.
 REDLINED.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE FOR
 UNIT "D-2" WAS SUBMITTED, HOWEVER
 CIRCUIT #15 FOR SD'S DOES NOT INDICATE
 THE REQUIRED ARC FAULT PROTECTION NOTE.
 REDLINED ON PANEL SCHEDULE, UNIT.210.12
  
 7)NOTE:POOL AREA LIGHTING TO MEET MIN
 CLEARENCES PER 680.22 AND 411.4
 SOME FIXTURES SHOWN CLOSER THAN
 PERMITTED.
 REDLINED.
  
 8)NOTE:PLEASE SEE LS101 7.8.1.3 (1)
 WHICH REQUIRES A MIN OF 10FT
 CANDLES(108LUX) IN STAIR TOWERS. THIS
 LEVEL OF LIGHTING IS REQUIRED ON THE
 WALKING SURFACES DURING NOMRAL POWER
 CONDITIONS.(1FT CANDLE IN EMERGENCY
 CONDITIONS. PHOTO-METRICS WILL BE
 REQUIRED OF STAIR-
 TOWERS.
  
 PLEASE SEE LS101 7.9.2.2 WHICH MENTIONS
 IN THE EVENT OF THE TRIPPING OF ANY
 SINGLE MEANS OF OCP WSHOULD NOT LEAVE
 ANY EGRESS AREA IN TOTAL DARKNESS.
 PLEASE ALSO SEE A MIN OF SOME SORT OF
 BATTERY BACK UP FIXTURE FOR CORRIDOR'S
 AND PARKING GARAGE WILL BE REQUIRD TO
 PROVIDE MEANS OF EGRESS AT A LIGHTING
 LEVEL OF 1FT CANDLE.
  
 9)NOTE: PLEASE SEE 230.95,707.7D,700.26
 ETC.
 PLEASE SEE A 4-POLE ATS WILL BE
 REQUIRED.
 PLEASE KNOW, THE GFP IS NOT REQUIRED ON
 THE EMERGENCY/ GENERATOR SIDE OF THE EM
 DISTRIBUTION SYSTEM, HOWEVER PLEASE SEE
 THE ABOVE REFERENCES WHICH DO REQUIRE GF
 SENSING. PLEASE SEE THE FOLLOWING IS
 TAKEN DIRECTLY FROM ASCO DOCUMENTS
 FORWARD TO ME.
 "WHERE GROUND FAULTPROTECTION IS
 TRIGGERED BY THE CODE AND AN ALTERNATE
 POWER SUPPLY IS INCLUDED,SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY.THE
 SERVICE IS LARGER THAN 1,000 AMPS.
 CONSEQUENTLY, GROUNDFAULT PROTECTION
 IS REQUIRED AT THE MAIN SERVICE
 DISCONNECT AT A MINIMUM. IF ITIS
 INSTALLED THERE AND THE GENERATOR
 NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL,
 A GROUND FAULT WHEN THE GENERATOR IS
 FEEDING THE LOAD WILL CAUSE THE MAIN
 SERVICE DISCONNECT TO OPEN. THIS WILL
 NOTDISCONNECT THE ARCING FAULT FROM
 THE GENERATOR. COORDINATION IS THUS
 LOST."
 PLEASE KNOW, IF THE MAIN IS IN THE
 OPENING POSITION WHEN POWERM COMES BACK
 ON, THE SENSING OF THE FPL WOULD CAUSE
 THE ATS TO SWITCH BACK, HOWEVER THERE
 WOULD NOT BE ANY POWER THROUGH THE
 ELECTRICAL SYSTEM AS THE MAIN FOR THE EM
 SYSTEM WOULD HAVE TRIPPED/OPENED.
 PLEASE REVISE RISER AND REVISE NOTES TO
 REFERENCE A 4-POLE TRANSFER SWITCH AND
 INDICATING THE SEPARATELY DERIVED
 SYSTEM.
  
  
 **PLEASE SEE THE ABOVE REDLINES/PROVISO
 ITEMS WILL NEED TO BE ADDRESSED BEFORE
 ANY ROUGH ELECTRICAL INSPECTION IS
 SCHEDULED.
 ** PLEASE KNOW, ELECTRICAL PERMIT MAY BE
 PLACED IN A "HOLD" STATUS UPON 6 MONTHS
 TIME TABLE AND "PROVISO" HAS NOT BEEN
 SUBMITTED.
  
 ** PLEASE KNOW, ANY OTHER
 REVISIONS/DESIGN CHANGES MAY ALSO BE
 SUBMITTED AT THAT TIME.
  
  
 ** PLEASE CALL TO GO OVER SUCH ITEMS
 LISTED ABOVE TO HELP IN EXPEDITING THIS
 PROJECT TO A "P" STATUS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ?
2005-12-30 00:00:00REVIEW IN PROGRESS, FINISH FOR 12/30
 WILL CONTINUE ON 12/31
2005-12-25 00:00:00IN ELECTRIC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-09-07 Cont ID  
Sent By dpalmer Date 2005-09-07 Time 07:29 Rev Time 20.00
Received By dpalmer Date 2005-09-04 Time 19:26 Sent To  
Notes
2005-09-07 00:00:00************ UNSAT 3ND REVIEW *********
  
 PLEASE SEENOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 PLEASE ALSO SEESOME NEW NOTES.
  
 ***************************************
 PLEASE SEE FIRST AND SECOND PART OF
 NOTES IS DIRECTLY TAKEN FROM FIRST TWO
 REVIEW. PART 3 WILL BE NEW NOTES.
 ***************************************
  
 1)NOTE: NOTE #1, OK, HOWEVER PLEASE SEE
 NOTE #19FROM SECOND REVIEW WHICH STILL
 HAS ONE COMMENT.
  
 2)NOTE: NOTE #2 OK
  
 3)NOTE: NOTE #3 OK
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK ON PREVIOUS REVIEW,
 HOWEVER PLEASE NOW SEE 2.04 WHICH SHOWS
 BOTH FPL VAULT AND MAIN ELECTRICAL RM
 BEING THE SAME ROOM?
  
 6)NOTE: NOTE #6 OK, NO, PLEASE SEE
 RESPONSE LTR FROM ENGINEER STATES
 SIGNAGE AND LOCATIONS, HOWEVER PLEASE
 SEE NOTES ADDED TO PLANS SEEMS TO HAV
 MISSED /OR HAVE FIRE COMMAND ROOM
 REMOVED FROM NOTE. PLEASE SEE NOTE FOR
 "ARC FLASH" COULD NOT BE LOCATED.
  
 7)NOTE: NOTE #7,OK
  
 8)NOTE: NOTE #8 OK. CORRECT, ADDED
 CIRCUITS.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 OK,
 PLEASE SEE NEW NOTES PERTAINING TO FIRE
 ALAEM SHEETS AND CODES REFEERNCED.
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE: NOTE #12 OK, ARCHITECTURUAL
 RESPONSE MENTIONS FULL ACCESSIBILTY FROM
 GARAGE TO UNITS BY WAY OF RAMPS FOR THE
 ENTIRE LENGTH OF TRAVEL. THIS COMMENT
 NOW BECOMES A BUILDING COMMENT AS NEC
 DOES NOT APPLY. IF THERE ARE ANY CHANGES
 TO DESIGN, PLEASE CORRELATE WITH
 ELECTRICAL PLANS.
  
 13)NOTE: NOTE: OK
  
 14)NOTE: NOTE: OK.
  
 15)NOTE: NOTE #15 NO,PLEASE SEE NOTE #44
 FROM SECOND REVIEW. CIRCUITING FOR SD'S.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 OK, HOWEVER PLEASE SEE
 NOTE# 49 FROM 2ND REVIEW.
 PLEASE ALSO SEE NEW NOTES ABOUT CATV AND
 TELEPHONE CABINETS.
  
 19)NOTE: NOTE #19 NO, PLEASEUNIT "M"
 STILL INDICATES AN ADDITIONAL PANEL,
 SEEM S TO BE A MISPRINT/OVERLAY PROBLEM.
 PANEL IN "LT GRAY".
  
 20)NOTE: NOTE #20 OK, SEE PREVIOUS NOTE
 FOR PANEL IN UNIT "M".
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE: NOTE #22 NO, PLEASE SEE MANY
 UNITS HAVE BEEN REDLINED FOR AREAS IN
 QUESTION. PLEASE SEE 210.52C1-5 FOR
 REQUIRED LOCATIONS OF GFI RECEPTS ALONG
 KITCHEN COUNTERSPACES, INCLUDING
 PENINSULARS AND " SEPARATE SPACES".
 210.52C2,4
 PLEASE SEE MANY OF THESE WERE CORRECTED
 AND RECEPTS WERE ADDED, HOWEVER PLEASE
 SEE PLANS WHICH HAVE BEEN REDLINED FOR
 OTHER LOCATIONS.
 PLEASE SEE UNITS, V-1,E-1,A,J,H,P,P1,U,
 O, N.
  
 23)NOTE: NOTE #23 NO, COULD NOT LOCATE
 NOTE REQUESTED FOR SD PLACEMENT ON
 PLANS.
 PLEASE CLARIFY WHERE THIS IS.
 PLEASE SEE RESPONSE LTR MENTIONS NOTE
 ADDED TO FIRE ALARM SHEET.
 PLEASE SEE E0.01, WHICH DID HAVE A NOTE
 FOR 3' MIN CLEARENCE FROM AIR DIFFUSERS,
 HOWEVER, PLEASE LIST 3' MIN FROM BATH
 AND KITCHEN DOORS, 20' FROM COOKING
 APPLIANCES. PLEASE SEE THERE ARE SD'S
 SHOWN W/IN 3' OF BATHROOM DOORS.
 PLEASE SEE REFERENCE TO NFPA-72 WAS
 INCORRECT. PLEASE SEE PROJECT WAS
 SUBMITTED FOR PERMIT AFTER JAN 1ST 2005,
 WHICH BRINGS NFPA-72 TO THE 2002
 EDITION.PLEASE SEE CHAPTER 11.8.3.5
 INSTALLATION SPEACIFICS.
 WRONG CODE WAS REFERENCED DUE TO PLANS
 ONLY BEING SUBMITTED FOR "PLAN REVIEW"
 BEFORE THE CODE CHANGE. THE REQUIREMENTS
 HAVE NOT CHANGED FOR THIS, ONLY THE
 CHAPTER NUMBER.
 PLEASE SEE NEW COMMENTS PERTAINING TO
 2003 NFPA-101
  
 24)NOTE: NOTE #24 OK.
  
 25)NOTE: NOTE #25 OK, NO JACUZZI TUBS AT
 THIS TIME PER ENGINNER.
  
 26)NOTE: NOTE #26NO. PLEASE SEE NOTE
 WAS ADDED FOR FIRE PUMP AND LOCKED
 ROTOR, HOWEVER PLEASE SEE NO SPECS WERE
 SUBMITTED FOR FIRE PUMP OR FIRE PUMP
 CPNTROLLER. PLEASE ALSO SEE OTHER
 COMMENTS FROMFIRST AND SECOND REVIEW
 AND THIS REVIEW WHICH REQUESTED THIS
 WILL BE THE THIRD REVIEW REQUESTING
 THESE TO BE SUBMITTED IN TO REVIEW THESE
 DEVICES FOR CODE COMPLIANCE.
 ********SEE NEW NOTES FOR THIS****
  
 27)NOTE: NOTE #27 NO, PLEASE SEE ABOVE
 NOTE. PLEASE SEE NO SPECS FOR GENERATOR,
 SUB BASE FUEL TANK ATS WERE SUBMITTED.
 PLEASE SEE ABOVE NOTE AND NEW NOTES FOR
 3RD REVIEW.
 PLEASE SEE NEW NOTES FOLLOWING.
  
 28)NOTE: NOTE #28 OK.
  
  
 29)NOTE: NOTE #29 OK.
  
 30)NOTE: NOTE #30 OK.
 PLEASE SEE NEW NOTES:
  
 31)NOTE: NO, PLEASE SEE RESPONSE LTR
 MENTIONS "WILL COMPLY" HOWEVER PLEASE
 SEE NEW NOTES PERTAINING TO NOTES ON
 PLANS AND SPECS.
 NO SEE NEW NOTES FROM SECOND REVIEW AND
 NEW FROM THIRD REVIEW.
  
 32)NOTE: NOTE #32 OK, (NO)NOTE ADDED ,
 GENERATOR WILL NOT BE SEPARATELY
 DERIVED. THIS WILL BE VERIFIED ONCE
 MANUFACTURE SPECS ARE SUBMITTED.
 SEE NEW NOTES AND PREVIOUS NOTES WITH
 RESPECT TO SHEETS FOR ALL REQUESTED
 EQUIPMENT AND CORRELATING WITH PLANS AND
 CODE COMPLIANCE.
  
 33)NOTE: NOTE #33 OK.
  
 34)NOTE: NOTE #34 NO, PLEASE SEE RISER
 DIAGRAM STILLDOES NOT INCLUDE A
 REDUCED "KEYED NOTES" OR RECDUCED
 "FEEDER SCHEDULE FOR REFERENCE WITHOUT
 HAVING TO TURN BACK AND FORTH FROM RISER
 DIAGRAM PAGE TO E-6.13.
 PLEASE SEE ONLY "KEYED NOTES ARE ON
 RISER SHEETS. PLEASE SEE REDLINED SET OF
 PLANS IN-WHICH A COPY OF THE FEEDER
 SCHEDULE WAS REDUCED AND PLACED ON RISER
 SHEETS 6.13.
 PLEASE MAKE CHANGES TO THIS , PLEASE SEE
 NEW COMMENTS PERTAINING TO "F" SCHEDULE
 AND CORRELATION WITH RISER AND PANEL
 SCHEDULES.
 2ND PART TO NOTE#34, NO. PLEASE SEE
 NEW COMMENTS AS RISERS, BUS DUCT ETC
 STILL DO NOT CORRELATE.
  
 35)NOTE: NOTE #35 OK.
  
 36)NOTE: NOTE # 36 OK.
  
 37)NOTE: NOTE #37 OK, PLEASE SEE
 FOLLOWING COMMENT WHICH STILL NEEDS TO
 BE ADDRESSED.
  
 38)NOTE: NOTE #38 NO, PLEASE SEE
 PANELS STILL SHOWN AS 200A WITH 225A OCP
 FEEDING PANEL(S).
 PLEASE SEE PANEL FOR UNIT "M".
  
 39)NOTE: NOTE #39 NO, PLEASE SEE WATER
 HEATERS SHOWN WITH 2P50A OCP FOR 4500VA
 UNITS ON #10 AWG.PLEASE SEE PANEL
 SCHEDULES, PANEL SCHEDULE "S" STILL
 SHOWS 50A OCP FOR 4.5KW WATER HEATER.
 PLEASE SEE NEW COMMENTS PERTAINING TO
 PANEL FOR UNIT "N".
 PLEASE SEE 422.13,422.11,240.4, 310.16
 ETC.
  
 ***************************************
 NEW NOTES FOR REVIEW ** (2ND REVIEW) **.
  
 40)NOTE: OK.
  
 41)NOTE: OK, PLEASE SEE AN EMERGENCY
 BATTERY BACK UP TYPE OF FIXTURE WILL BE
 REQUIRED FOR FIRE COMMAND ROMM. SEE THIS
 AS NEW NOTE.
  
 42)NOTE: NO, PLEASE SEE SOME UNITS FOR
 2' OF WALL SPACE REDLINED AT LOCATIONS.
 (KITCHENS WALL SPACE 2' OR MORE. MOST
 BEDRM WERE DONE, PLEASE SEE ANY POSSIBLE
 LOCATIONS REDLINED FOR THESE.
 PLEASE SEE P, P1, P2.
  
 43)NOTE: OK, NO FAN FOR DRYER TO BE
 ADDED PER ENGINEER.
  
 44)NOTE: NO,PLEASE SEE MANY UNITS WHERE
 CIRCUITING WAS UPDATED DUE TO PREVIOUS
 COMMENTS FOR ARC FAULT PROTECTION,
 HOWEVER PLEASE SEE NOW MANY SMOKE
 DETECTORS ARE BEINGSHOWN TWO DIFFERENT
 CIRCUITS IN THE SAME UNITS. PLEASE SEE
 NFPA-72 11.5.1.1 WHICH REQUIRES SD'S TO
 BE WIRED "IN-LINE". MUTIPLE CIRCUITS FOR
 SD'S CAN NOT BE DONE.
 2002 NEC 210.12 PLEASE BE SURE ARC FAULT
 CIRCUITS STILL CORRELATE AFTE UPDATING
 ANY CIRCUITING.
 PLEASE SEE ALL "OUTLETS" INCLUDING SD'S,
 LTS, FANS AND RECEPTS REQUIRED THIS.
 PLEASE SEE MANY OF THESE CIRCUIT #'S
 HAVE BEEN REDLINED ON PLANS, BUT NOT
 ALL. SEE UNITS, 15,V, V1, L, K, G,
 M,J,,,
  
 45)NOTE: OK. FIXTURES REMOVED.
  
 46)NOTE: OK, FIXTURE TYPE NOTED.
  
 47)NOTE: OK.
  
 48)NOTE: OK.
  
 49)NOTE:OK.
  
 49)NOTE:YE/ NO,PLEASE SEE MOST UNITS
 HAVE BEEN REVISED TO RE-LOCATE THESE
 PANELS, HOWEVER PLEASE SEE UNIT "Q"
 WHICH SHOWS THESE INWHAT APPEARS TO BE
 THE LINEN CLOSET.
 PLEASE SEE MANY CLOTHES CLOSETS
 CONTAINING COMBUSTIBLES ARE SHOWN WITH
 CATV AND TELEPHONE CABINETS. PLEASE SEE
 IF THESE UNITS WILL REQUIRE ANY "LV
 PLUG-IN" TYOE TRANSFORMERS THEN THESE
 RECEPTS WHICH ARE NOT SHOWN AT THIS TIME
 WOULD ONLY BE ALLOWED DIRECTLY OVER
 DOORS.
  
 50)NOTE:NO, PLEASE SEE2002 210.8B3
 FOR KITCHENS IN OTHER THAN DWELLING
 UNITS WHICH REQUIRES ALL 15- AND
 20-AMPERE, 125-VOLT RECEPTACLES IN
 NON-DWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
 THIS WOULD BE FOR "HOUSE KITCHEN".
  
 51)NOTE: OK, PLEASE SEE NOTES PERTAING
 TO 210.52, 210.52C1-5
  
 52)NOTE: OK.
 SEE NOTE WHICH WILL REQUIRE THE BATTERY
 BACK UP FIXTURE.
  
 53)NOTE: OK, HOWEVER NOTES WITH RESPECT
 TO SPECS,/MANUFACTURE CUT SHEETS. PLEASE
 ALSO NEW NOTES WITH RESPECT TO DPHE.
  
 54)NOTE: OK.
  
 55)NOTE: OK, DETAIL SUBMITTED WHICH
 NOTES NEW GROUNDING TO BLDG GROUNDING
 ELECTRODE SYSTEM.
  
 56)NOTE: OK, PLEASE KNOW, INFORMATION
 FOR ALL THIS ELEVATOR
 EQUIPMENT.DISCONNECTS ETC WILL BE
 REQUIRED TO BE REVISED BEFORE
 INSPECTIONS. NO CORRECTIONS NEEDED AT
 THIS TIME.
  
 57)NOTE: OK.
  
 58)NOTE: OK, HOWEVER SEE NEW NOTES TO
 FIRE PUMP FEEDERS NOW INDICATED.
  
 59)NOTE: NO, PLEASE SEE BUST DUCTKEY
 NOTES ON 6.02 AND 6.03. PLEASE SEE K-3
 WHICH MENTIONS CORRECTION, HOWEVER
 PLEASE SEE "K-7" WHICH SHOWS OLD. PLEASE
 SEE "SPEC BOOK", 16465
 2.2C WHICH MENTIONS ALUM BUS-DUCT WAS
 NOT REVISED.
 PLEASE SEE PREVIOUS NOTES IN REFERENCE
 TO EQUIPMENT GROUNDING METHOD OF
 BUS-DUCT. DOES THIS BUS-DUCT CONTAIN A
 SEPARATE ALUM BUS FOR GROUNDING? OR IS
 THE EQUIPMENT GROUNDING THAT IS GOING TO
 BE USED "PART" OF THE BUS-DUCT.
 ***************************************
 PLEASE SEE 2ND PART OF THIS NOTE COULD
 NOT BE LOCATED ON PLANS?
 ***************************************
 PLEASE ALSO PLACE NOTE ON PLANS FOR
 REQUIRED CURBS FOR FLOOR PENATRATIONS.
 PER 368.6BFLOOR PENETRATIONS SHALL
 COMPLY WITH (1) AND (2):
 BUSWAYS SHALL BE PERMITTED TO BE
 EXTENDED VERTICALLY THROUGH DRY FLOORS
 IF TOTALLY ENCLOSED (UNVENTILATED) WHERE
 PASSING THROUGH AND FOR A MINIMUM
 DISTANCE OF 1.8 M (6 FT) ABOVE THE FLOOR
 TO PROVIDE ADEQUATE PROTECTION FROM
 PHYSICAL DAMAGE.
 IN OTHER THAN INDUSTRIAL ESTABLISHMENTS,
 WHERE A VERTICAL RISER PENETRATES TWO OR
 MORE DRY FLOORS, A MINIMUM 100 MM (4
 IN.) HIGH CURB SHALL BE INSTALLED AROUND
 ALL FLOOR OPENINGS FOR RISER BUSWAYS TO
 PREVENT LIQUIDS FROM ENTERING THE
 OPENING. THE CURB SHALL BE INSTALLED
 WITHIN 300 MM (12 IN.) OF THE FLOOR
 OPENING. ELECTRICAL EQUIPMENT SHALL BE
 LOCATED SO THAT IT WILL NOT BE DAMAGED
 BY LIQUIDS THAT ARE RETAINED BY THE
 CURB.
  
 60)NOTE: NO, THIS WAS NOT CORRECT.
 PLEASE SEE "SPEC BOOK" 16120
 2.3A5, PLEASE SEE COLOR CODING FOR
 277/480V SHALL BE BROWN, PURPLE, YELLOW.
 215.8 LOCAL AMENDMENTS.
  
 61)NOTE:OK.
  
 62)NOTE: OK.
 HOWEVER PLEASE SEE NEW NOTES.
  
 63)NOTE: OK.
 HOWEVER SEE NEW NOTES.
  
 64)NOTE:OK.
  
 65)NOTE: OK.
 SEE NEW NOTES FOR OTHER "F" FEEDER
 SCHEDULE AND CORRELATION WITH PANE
 SCHEDULES.L
  
 66)NOTE: OK.
  
 67)NOTE: OK, HOWEVER GEN INFORMATION,
 FUEL SUB-BASE TANK STILL NOT SUBMITTED.
  
  
 68)NOTE:NO, SPECS FOR FIRE PUMP
 CONTROLLER ETCRATING S STILL TO BE
 VERIFIED.PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS SHOULD BE NOTED ON ALL
 EQUIPMENT.
  
 69)NOTE:OK, ENGINEER'S RESPONSE LETTER
 MENTIONS, "LIGHTNING PROTECTION SYSTEM"
 WILL BE UNDER SEPARATE PERMITS.
 PLEASE SEE ALL INFORMATION FOR
  
 70)NOTE: NO, INFORMATION NEEDS TO BE
 SUBMITTED FOR VERIFICATION OF CODE
 COMPLIANCE WITH SAID SYSTEMS.PLEASE ALSO
 SEEIF ALL INFORMATION FOR FIRE PUMP,
 FIRE PUMP CONTROLLER,GENERATOR, ATS,
 ETC WAS NOT SUBMITTED FOR REVIEW WITH
 BASE BLDG.
 PLEASE SEE FIRE REVIEW COMMENTS.
  
 71)NOTE: OK, NO RESPONSE NEEDED.
  
 72)NOTE:OK. NO RESPONSE NEEDED.
  
 73)NOTE: PLEASE KNOW, AS NOTED IN SOME
 NOTES, DUE TO SOME INFORMATION MISSING
 ON PLANS AND WITH PLANS, SOME COMMENTS
 ARE NEW AND SOME ARE REPEAT.
 ***************************************
  
 3RD REVIEW
 NEW COMMENTS/AND REPEAT COMMENTS WITH
 FURTHER EXPLANATION IN ORDER FOR
 COMMENTS TO BE ADDRESSED FOR A FINAL
 REVIEW.
  
  
 74) NOTE: PLEASE SEE PREVOUS NOTES
 PERTAINING TO BUS DUCT.
 PLEASE CORRELATE BUS-DUCT SIZES ON RISER
 DIAGRAM AND BLDG RISER UP THROUGH THE
 BLDG.
 A) PLEASE SEE MAIN RISER NOW HAS BEEN
 REVISED FOR BUS-STABS INTO FPL VAULT FOR
 MAINS, HOWEVER PLEASE NOW SEE 1SMCN AND
 2SMCN WHICH SHOWS 4000A BUS-DUCT INTO
 BOTH 3000A MAINS. (SEE KEY NOTE K-4)
 THIS OK, HOWEVER PLEASE CORRECT OF
 INDEED ONLY 3000A BUS IS GOING TO BE
 USED.
 B) PLEASE SEE 6.02, AND 6.03 FOR "KEY
 NOTES". PLEASE SEE 6.02 HAS NOW BEEN
 REVISED FOR 1SMCN RISER WHICH CONTAINS
 REVISION "K-3", PLEASE SEE THIS WAS
 CHANGED TO 4000A ON A 3000A MAIN, THIS
 IS OK, HOWEVER PLEASE SEE 6.03 "KEY
 NOTE" FOR SAME BUS DUCT RISER. PLEASE
 SEE KEY NOTES REF K-7 FOR THE SAME RISER
 WHICH IS SHOWN AS 3000A'S??
 PLEASE VERIFY SIZING OF BUST DUCT 3OR 4K
 AND IF THERE ARE TWO DIFFERENT SIZES
 BEING INSTALLED FOR THIS 3K MAIN.?
 PLEASE SEEFEEDERS AS NOTED ARE FOR
 3000A'S.
  
 75)NOTE: PLEASE SEE PREVIOUS NOTED A
 REQUEST TO PROVIDE "FEEDER SCHEDULE" ON
 RISER DIAGRAM AND TO NOTES TO CORRELATE
 FEEDERS.
 PLEASE SEE THE FOLLOWING:
  
 A) DPHREL, SHOWS F-9 ON RISER, F-10 ON
 PANEL SCHEDULE AND F-10 ON SHE. REDLINED
 LOCATION.
  
 B)DPHRE, SHOWS F-11 ON RISER, F-13 ON
 PANEL SCHEDULE. REDLINED LOCATION.
  
 C)DPHRN, SHOWS F-4 ON RISER, F-5 ON SHN,
 REDLINED LOCATION. PLEASE NOTE F-4 IS
 FOR 2500A'S?
  
 D)HRHN, SHOWS F-15 ON RISER, F-19 ON
 SHN, REDLINED LOCATION.
  
 E)HGME, SHOWS BLANK ON RISER, SHOWS F-12
 ON PANEL SCHEDULE DPHE.
  
 F)H5ME, SHOWS F-18 ON RISER, SHOWS F-20
 ON DPHE, REDLINED LOCATION.
  
 G)FIRE PUMP FEEDERS, F-10 INDICATE AN
 "EQUIPMENT GROUNDING CONDUCTOR" FROM
 FPL. PLEASE SEE 250.6 AND EQUIPMENT
 GROUNDING CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISC.
 (IT IS NOTED, FEEDERS NOT TO HAVE EQP
 GRND).
 PLEASE SEE FEEDERS LISTED AS K-24 WHICH
 INDICATES 6-SETS OF 3-3/0'S AND 3/0 GRND
 FOR FEEDERS TO FIRE PUMP FROM FIRE PUMP
 CONTROLLER?? PLEASE VERIFY THE SIZES AND
 NUMBER OF PARALLEL RUNS.
  
 H)SHN AND SHE ON RISER DIAGRAM INDICATES
 A "BUS-STAB" INOT FPL VAULT, HOWEVER,
 PANEL SCHEDULES FOR EACH OF THESE ON
 7.12 INDICATES "FEEDERS" AS F-3 AND F-6.
 PLEASE CORRELATE, LOCATION REDLINED.
  
 76)NOTE: PLEASE SEE SPECS FOR ATS NOT
 SUBMITTED TO VERIFY MEANS OF DISCONNECT,
 MANUAL, LOCATED ON OUTSIDE OF EQUIPMENT
 ETC.
 PLEASE SEE DPHE WILL BE REQUIRED TO HAVE
 A MAIN CIRCUIT BREAKER FOR SERVICE
 DISCONNECT FROM FPL AND GENERATOR.
 THIS WAS REDLINED ON SETS FROM PREVIOUS
 REVIEW, BUT UNABLE TO VERIFY MEANS OF
 DISCONNECT FROM OTHER REVIEWS DUE TO NO
 SPECS ETC SUBMITTED FOR ATS.
 NO OCP COULD BE LOCATED FOR SEC'S COMING
 INOT BLDG FROM FPL ON THIS.
 230.70,230.76,230.79,230.72,240.4.
  
 77)NOTE: PLEASE KNOW, PLANS WERE
 SUBMITTED ONLY FOR "PLAN REVIEW" BEFORE
 JAN 1ST, 2005 AND NOT FOR PERMIT
 APPLICATION.. PLEASE SEE NFPA-72 AND 101
 AND FIRE CODES CHANGE AT THAT TIME.
 PLEASE SEE NFPA 101 REFERENCES A 1999
 EDITION. EVEN IF UNDER THE OLD CODE,
 THIS WOULD BE 2000 EDITION OF 101,
 HOWEVER PERMIT APPLICATIONS AFTER JAN
 1ST , WOULD PLACE THIS PROJECT UNDER THE
 2002 NFPA-72 AND 2003 NFPA-101.
  
 78)NOTE: PLEASE SEE CHANGES TO PREVIOUS
 NOTES FOR WATER HEATERS SHOWING OCP AT
 50A'S FOR A 4.5KW UNIT. PLEASE SEEUNIT
 "N" WHICH NOW SHOWS SECOND WATER HEATER
 AS A "BLANK" FOR OCP ETC.
 PLEASE SEE LOAD CALCULATIONS AND PLANS
 STILL INDICATE TWO UNITS.
 PLEASE ADJUST AND CORRELATE.
  
 79)NOTE: PLEASE SEE PANEL SCHEDULE FOR
 UNIT D-2 COULD NOT BE LOCATED.
 PLEASE CLARIFY IF THIS IS A DIFFERENT
 PANEL. UNITS "D" AND D-1 ARE SUBMITTED.
  
 80)NOTE: PLEASE SEELAUNDRY RMS IN SOME
 UNITS INDICATE THE CIRCUIT PROVIDED FOR
 WASHER ALSO FEEDING THE ADDITIONAL GFI
 IN THE SAME RM? PLEASE SEE LOADING FOR
 CIRCUITING AS A DEDICATED CIRUIT AND NO
 OTHER RECEPTS ON THAT CIRCUIT SHOULD BE
 VERIFIED.
 LOAD FOR WASHER UNIT CAN NOT BE
 VERIFIED.
 PLEASE SEE 210.11C2
  
 81)NOTE: PLEASE SEENFPA-101 7-9 UNDER
 THE 2003. WHICH WOULD REQUIRE MUTIPLE
 CIRCUITS FEEDING EM LTS IN STAIR TOWERS.
 PLEASE KNOW THE AHJ/ FIRE MARSHAL'S
 OFFICE HAS DETERMIND EITHER EVERY OTHER
 EM LT TO ALTERNATE CIRUITS OR A BATTERY
 BACK UP FIXTURE AT EVERY OTHER LEVEL
 WOULD BE REQUIRED FOR EGRESS IN STAIR
 TOWER. PLEASE KNOW, IF BLDG IS UNDER
 GENERATOR/ EM POWER AND A TRIPPING OF A
 SINGLE BRKR , EITHER BRANCH CIRCUIT OR
 MAIN, THIS WOULD PLACE STAIR TOWER(S) IN
 TOTAL DARKNESS. TO ALLEAVIATE ANY OF
 ALTERNATING CIRCUITS, OR TRIPPING OF ANY
 OVERCURRENT PROTECTION DEVICE, A BATTERY
 BACK-UP TYPE OF FIXTURE WOULD BE
 REQUIRED TO PROVIDE A MIN OF .1 FT
 CANDLE AS LISTED UNDER 7.9.2.1,
 7.9.2.2, 7.8.1.2.
 THIS COMMENT CAN BE SET UP AS A
 "PROVISO"TO REVISE BEFORE ROUGH OR CAN
 BE ADDRESSED AT THIS TIME. PLEASE CALL
 TO GO OVER.
  
 82)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B) IS GIVEN ASNOTICE ONLY.
  
 PLEASE BE SURE TO SEE ANY COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE BE SURE TO REMOVED ALL OLD/
 VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 ONE COMPLETE SET OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT ALL OF THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SEE ANY COMMENTS FROM O
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2005-09-06 00:00:00PLANS WILL GO INTO A "F" STATUS.
  
 PLAN REVIEW NOTES TO FOLLOW, PLAN REVIEW
 AND NOTES IN PROGRESS.
2005-09-04 00:00:00ELECTRICAL PLANSONLY ARE AT DP'S DESK
 FOR REVIEW.
 REVIEW TO CONTINUE,,,, STOPPED FOR 9/4
2005-08-24 00:00:00REVISION TO THE TEMPORARY POWERJL

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-04-08 Time 09:03 Rev Time 22.00
Received By dpalmer Date 2005-04-08 Time 13:40 Sent To  
Notes
2005-04-08 00:00:00************ UNSAT 2ND REVIEW *********
  
 PLEASE SEE MANY NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 PLEASE ALSO SEE NEW NOTES DUE TO PLANS
 CONTAINING MORE INFORMATION THAN
 SUBMITTED ON PREVIOUS REVIEW.
  
 ***************************************
 PLEASE SEE FIRST PART OF REVIEW IS A
 DIRECT OVERVIEW OF PREVIOUS NOTES, NEW
 NOTES WILL BE FOLLOWING.
 ***************************************
  
 1)NOTE: NOTE #1, OK, HOWEVER PLEASE SEE
 NOTE #19 IN THIS AND PREVIOUS REVIEW.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE REQUIRED
 WIND LOADING INFORMATION IS NOT NOTED ON
 ELECTRICAL PLANS FOR POLES. IF THIS
 INFORMATION IS PROVIDED ON ADDITIONAL
 SHEETS FOR BLDG REVIEW, THIS IS FINE AND
 REQUIRED, HOWEVER THIS INFORMATION WILL
 NEED TO BE ELECTRICAL SHEET FOR
 ELECTRICAL CONTRACTOR ETC.
 WINB LOADING NOTE(S) SHOULD REFERENCE
 FBC 140 MPH.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE SHEET
 ATTACHED WHICH IS A PRINT OUT FROM
 DBPR'S WEBSITE. PLEASE SEE LICENSE
 INFORMATION PROVIDED ON TITLE BLOCKS FOR
 ARCHITECTUAL FIRM DOES NOT APPEAR TO BE
 ACCURATE. PLEASE SEE ATTACHED SHEET
 WHICH SHOWS BC ARCHITECTS INC. WITH AN
 ARCHITECTUAL BUS/FIRM LICENSE NUMBER OF
 AA#0003360. PLEASE SEE TITLE BLOCKS FOR
 ALL SHEETS AND FOR ALL TRADES APPEARS TO
 INDICATE THIS FIRM LICENSE NUMBER AS
 0008129???.
 PLEASE SEE FAC 61G1-16.004, FS 481.219.
 PLEASE SEE THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
 PLEASE SEE ENGINEERING FIRM'S TITLE
 BLOCK HAS BEEN CORRECTED.
  
 4)NOTE: NOTE #4, OK. NOTE ADDED FOR "NO
 SWIMMING" AFTER DUSK.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 OK, FIRE RATING VERIFIED
 FOR DIRECT ACCESS TO MAIN ELECTRICAL
 ROOM. HOWEVER, NOTES FOR SIGNAGE, MAPS
 AND/OR DIRECTORY COULD NOT BE LOCATED ON
 PLANS.
 230.2E 700.8A,701.9,702.8 ETC.
 A SIGN SHALL BE PLACED AT THE SERVICE
 ENTRANCE EQUIPMENT INDICATING TYPE AND
 LOCATION OF ON-SITE EMERGENCY POWER
 SOURCES.
 PLEASE SEE ALL SIGNAGE REQUIRED TO BE 1"
 MIN WITH CONTRASTING BACKGROUND.
 SIGNAGE/MAPPINGALSO REQUIRED AT FIRE
 COMMAND RM AND AT ACCESS DOOR CLOSEST TO
 MAIN ELECTRICAL ROOM.
 SIGNAGE FOR ALL ELECTRICAL ROOMS.
 PLEASE ALSO SEE 110.16
 110.16 FLASH PROTECTION.
 SWITCHBOARDS, PANELBOARDS, INDUSTRIAL
 CONTROL PANELS, AND MOTOR CONTROL
 CENTERS THAT ARE IN OTHER THAN DWELLING
 OCCUPANCIES AND ARE LIKELY TO REQUIRE
 EXAMINATION, ADJUSTMENT, SERVICING, OR
 MAINTENANCE WHILE ENERGIZED SHALL BE
 FIELD MARKED TO WARN QUALIFIED PERSONS
 OF POTENTIAL ELECTRIC ARC FLASH HAZARDS.
 THE MARKING SHALL BE LOCATED SO AS TO BE
 CLEARLY VISIBLE TO QUALIFIED PERSONS
 BEFORE EXAMINATION, ADJUSTMENT,
 SERVICING, OR MAINTENANCE OF THE
 EQUIPMENT.
 SEE FIRE COMMENTS FOR "KNOW BOX"
 LOCATIONS.
  
 7)NOTE: NOTE #7,OK HOWEVER PLEASE SEE
 SHEETS E 2.11,2.12, MANY ELECTRICAL
 DEVICES/FIXTURES APPEAR TO BE SHOWN WITH
 OUT CIRCUITS. ARE THESE MISPRINTED AND
 REPEATED ON OTHER SHEETS.
  
 8)NOTE: NOTE #8 NO, PLEASE SEE 620.23.24
 ETC.
 PLEASE SEE ELEVATOR EQUIPMENT RMS.
 A SEPARATE BRANCH CIRCUIT SHALL SUPPLY
 THE MACHINE ROOM OR CONTROL
 ROOM/MACHINERY SPACE OR CONTROL SPACE
 LIGHTING AND RECEPTACLE(S).
 A SEPARATE BRANCH CIRCUIT SHALL SUPPLY
 THE HOISTWAY PIT LIGHTING AND
 RECEPTACLE(S).
  
 9)NOTE: NOTE #9 NO, PLEASE SEE RECETPS
 WERE ADDED HOWEVER, ID SCALE IS CLOSE AS
 INDICATED, SOME RECEPTS APPEAR TO BE
 WITHIN THE RESTRICATED 10' AREA.
 PLEASE SEE 620.22A3
 PLEASE ALSO SEE NEW NOTE FOR LIGHTING
 AROUND POOLS.
  
 10)NOTE: NOTE #10 OK, REFERENCES
 CHANGED.
  
 11)NOTE: NOTE #11 OK, HOWEVER PLEASE SEE
 NEW NOTES FOR BATH/TUB/JACUZZI FIX.
  
 12)NOTE: NOTE #12 NO, PLEASE SEE UNITS
 ARE STILL SHOWN WITHOUT ACCESS TO
 GARAGE.
 AS PER CONVERSATION WITH MR. RAPL BAEZA,
 NO ACCESS WAS GOING TO BE INSTALLED FROM
 GARAGE IN DESIGN.
 PLEASE SEE BLDG REVIEW COMMENTS BY MR.
 ROBERT BROWN, ACCESSIBILTY FROM GARAGE
 MAY BE REQUIRED.
 IF SO, PLEASE SEE 210.70 AND LS101 5-8.
  
 13)NOTE: NOTE #13 NO, PLEASE SEE GRADE
 LEVEL ACCESS REQUIRES MEANS OF EGRESS
 LIGHTING/CONTROL. PLEASE ALSO SEE
 EXCEPTIONS.
  
 14)NOTE: NOTE #14, OK, HOWEVER PLEASE
 SEE NOTE #7.
  
 15)NOTE: NOTE #15 OK FOR SD'S HOWEVER
 PLEASE SEE NEW COMMENTS FOR CIRCUITING
 AND ARC FAULT PROTECTION.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 NO, PLEASE SEE 210.52D
 FOR GFI REQUIRED WITHIN 3' OF SINK/LAV
 EDGE.
 PLEASE SEE PLANS AHVE SOME REDLINED AT
 LOCATION(S) MISSING.
  
 18)NOTE: NOTE #18 NO, PLEASE SEE
 ELECTRICLA PANELS NOT PERMITTED ON
 CLOSETS. PLEASE SEE 110.26,408.7,240.24
 ETC.
 PLEASE SEE 240.24OVER CURRENT
 PROTECTION IS NOT TO BE LOCATED IN THE
 VICINITY OF EASILY IGNITIBLE MATERIAL. ,
 SUCH AS IN CLOTHES CLOSETS.
 PLEASE ALSO SEE NEW NOTES BAOUT CATV AND
 TELEPHONE CABINETS.
  
 19)NOTE: NOTE #19 NO, PLEASE SEE SOME
 UNITS STILL SHOW A COUPLE OF ELECTRICAL
 PANELS IN "LT GRAY". THIS APPEARS TO BE
 MISPRINTS . PLEASE SEE UNIT HD FOR ONE.
  
 20)NOTE: NOTE #20 OK, HOWEVER PLEASE SEE
 NOTE #28 FOR 110.26
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE: NOTE #22 NO, PLEASE SEE MANY
 UNITS HAVE BEEN REDLINED FOR AREAS IN
 QUESTION. PLEASE SEE 210.52C1-5 FOR
 REQUIRED LOCATIONS OF GFI RECEPTS ALONG
 KITCHEN COUNTERSPACES, INCLUDING
 PENINSULARS AND " SEPARATE SPACES".
 210.52C2,4
  
 23)NOTE: NOTE #23 NO, CPULD NOT LOCATE
 NOTE REQUESTED FOR SD PLACEMENT ON
 PLANS.
 PLEASE CLARIFY WHERE THIS IS.
 PLEASE SEE NFPA-72 8-1.4.2 FOR THESE
 LOCATIONS.
  
 24)NOTE: NOTE #24 NO, PLEASE SEE GFI
 RECEPTS WERE ADDED TOLOWER TERRACE
 LEVELS BUT NONE TO UPPER TERRACES.
 PLEASE SEE UPPER TERRACE ON ELECTRICAL
 PLANS APPEAR TO BE SHOWN MUCH LARGER
 THAN TERRACES SHOWN ON ARCH SHEETS.
 THIS IS ONLY A NOTE AND LIGHTING OR GFI
 RECEPTS ARE NOT REQUIRED ON THE SMALLER
 OR LARGE TERRACES, HOWEVER OF THEY ARE
 GOING TO BE INSTALLED, PLEASE SHOW ON
 PLANS AT THIS TIME OR PLANS WILL BE
 REQUIRED TO BE REVISED AT A LATER DATE.
  
 25)NOTE: NOTE #25 YES/NO , GFI BRKR
 NOTED AT PANEL SCHEDULES,HOWEVER A
 POWER/RECEPT COULD NOT BE LOCATED ON
 PLANS AT THESE UNITS.
 PLEASE SHOW.
  
 26)NOTE: NOTE #26NO. PLEASE SEE NO
 INFORMATION EXCEPT THAT FIRE PUMP IS
 GOING TO BE 250 HP. PLEASE SEE KEYNOTES
 K-23 DOES NOT PROVIDE ENOUGH
 INFORMATION.
 PLEASE ALSO SEE NEW NOTES PERTAINING TO
 FIRE PUMP/CONTROLLER ETC.
 PLEASE SEE PREVIOUS REQUEST WAS TO HAVE
 ALL MANUFACTURE SPEC SHEETS SUBMITTED
 FOR FIRE PUMP, FIRE PUMP CONTROLLER, ETC
 NONE COULD BE LOCATED IN SPECS,
 SUBMITTALS???
 SEE NEW NOTES:
  
 27)NOTE: NOTE #27 NO, PLEASE SEE ABOVE
 NOTE. PLEASE SE NO SPECS FOR GENERATOR,
 SUB BASE FUEL TANK ATS WERE SUBMITTED.
 215.5
 PLEASE SEE NEW NOTES FOLLOWING.
  
 28)NOTE: NOTE #28 NO, PLEASE SEE NOTE
 WAS ADDED TO ONE SHEET ONLY. PLEASE SEE
 SPECIFICS NOTES FOR 110.26 WILL BE
 REQUIRED ON ALL SHEETS SHOWING
 ELECTRICAL ROOMS AND ELECTRICAL CLOSETS.
  
 PLEASE SEE THIS NOTE SHOULD REFLECT "ALL
 ELECTRICAL ROOMSAND ELECTRICAL CLOSETS
 SHALL MEETS ALL THE REQUIREMENTS OF
 110.26 AND ALL OTHER REQUIREMENT OF
 2002 NEC" PLEASE SEE WE ARE HAVING MANY
 ISSUES WHERE WIDTHS ARE BEING MET,
 HOWEVER HEIGHT REQUIREMENTS ARE NOT.
 SEE NEW NOTES ALSO.
  
 29)NOTE: NOTE #29 OK.
  
 30)NOTE: NOTE #30 NO, PLEASE SEE MORE
 THAN ONE "K" NOTE LOCATED ON KEYNOTES DO
 NOT CORRELATE OR SHOWN "BLANK" OR NOTED
 AS NOT BEING USED, HOWEVER PLANS DO NOT
 MATCH THESE.
 PLEASE SEE K26,K35, ETC.
 PLEASE SEE NEW NOTES FOR F AND K NOTES
 WHICH DO NOT CORRELATE WITH PLANS.
 PLEASE SEE NEW NOTES:
  
 31)NOTE: NO, PLEASE SEE RESPONSE LTR
 MENTIONS "WILL COMPLY" HOWEVER PLEASE
 SEE NEW NOTES PERTAINING TO NOTES ON
 PLANS AND SPECS.
  
 32)NOTE: NOTE #32 OK, NOTE ADDED , GEN
 WILL NOT BE SEPARATELY DEREVED. THIS
 WILL BE VERIFIED ONCE MANUFACTURE SPECS
 ARE SUBMITTED.
 SEE NEW NOTES ALSO;
  
 33)NOTE: NOTE #33 OK, HOWEVER PLEASE SEE
 NEW NOTES PERTAINING TO FEEDER SIZES.
  
 34)NOTE: NOTE #34 NO, PLEASE SEE RISER
 DIAGRAM STILLDOES NOT INCLUDE A
 REDUCED "KEYED NOTES" OR RECDUCED
 "FEEDER SCHEDULE FOR REFERENCE WITHOUT
 HAVING TO TURN BACK AND FORTH FROM RISER
 DIAGRAM PAGE TO E-6.13.
 215.5.
 PLEASE SEE NEW NOTES FOR250.30
 PLEASE SEE RISER INDICATES 3000A
 BUS-STAB INTO FPL VAULT FEEDING 4000A
 MAINS?? PLEASE CORRELATE.
 PLEASE SEE RISER SHOWS 3000A MAIN
 FEEDING 4000A BUS-DUCT THEN CHANGES BACK
 TO 3000A BUS DUCT??
  
 35)NOTE: NOTE #35 OK, HOWEVER SEE NEW
 NOTES FOR CORRELATIONOF METER CENTERS
 AND LOAD CALCULATIONS/ EQUIPMENT.
  
 36)NOTE: NOTE # 36 OK, OVEN ADDED,
 RANGES CHANGED.
  
 37)NOTE: NOTE #37 PLEASE SEE "FEEDER
 HOME RUN SCHEDULE" WAS ADDED TO MOST
 SHEETS CONTAINING PANEL SCHEDULE, BUT
 SEE PLANS FOR MISSING DETAIL. PLEASE
 ALSO SEE NEW NOTES PERTAINING TO PANELS
 SIZES.
  
 38)NOTE: NOTE #38 NO, PLEASE SEE
 PANELS STILL SHOWN AS 200A WITH 225A OCP
 FEEDING PANEL(S). PLEASE SEE THE 250A
 OCP WAS REMOVED.
  
 39)NOTE: NOTE #39 NO, PLEASE SEE WATER
 HEATERS SHOWN WITH 2P50A OCP FOR 4500VA
 UNITS ON #10 AWG.
 PLEASE ALSO SEE 6KW WITH 30A OCP.
 PLEASE SEE MIN OCP IS 125% AND MAX OCP
 IS 150%.
 PLEASE SEE 422.13,422.11,240.4, 310.16
 ETC.
  
 ***************************************
 NEW NOTES FOR REVIEW.
  
 40)NOTE: PLEASE SEE MIN REQUIREMENTS FOR
 ELECTRICAL LIGHT FIXTURES FORM SWIMMING
 POOL. IF SCALE IS USED AS INDICATED ON
 PLANS, SOME FIXTURES SHOWN AS CLOSE AS
 3' FROM WATER'S EDGE.
 PLEASE SEE 680.22 AND PREVIOUS NOTES FOR
 RECEPT PLACEMENT.
  
 41)NOTE: PLEASE CLARIFY MANY
 ELECTRICAL/GENERATOR RMS CONTAIN EM LT
 FIXTURES ON EM CIRCUIT BUT YET THESE ARE
 ALSO BATTERY BACK UP? PLEASE SEE THEN
 ARE MANY ELECTRICAL RMS WHICH DO NOT
 CONTAIN BATTERY BACK UP?
 THIS IS ONLY A NOTE.
  
 42)NOTE: PLEASE SEE MANY UNITS, 5,6,8
 ETC FOR REQUIRED RECEPTS PER 210.52.
 PLEASE SEE 2' OF WALL SPACES INT
 KITCHENS, BEDROOMS(EVEN IF BEHIND
 DOORS).
 PLEASE SEE MANY REDLINED AT LOCATIONS ON
 PLANS.
  
 43)NOTE: PLEASE SEE MOST DRYER LOCATIONS
 INDICATE A MANUAL SWITCH FOR DRYER
 "BOOST FAN" YET MANY DO NOT CONTAIN THIS
 SAME SW?
 HOWEVER, PLEASE SEE NOTES LOCATED ON
 EACH SHEET WHICH MENTIONS THAT THESE
 WILL BE AUTOMATICALLY INTERCONNECTED?
 PLEASE SEE MECHANICAL NOTES FOR THIS
 SAME ITEM. IT APPEARS INTERCONNECTING
 ANY DEVICES IN THESE FANS/ DRYERS MAY
 VOIDED WARRANTIES AND/OR VOIDED LISTINGS
 FROM MANUFACTURE.
  
 44)NOTE: PLEASE SEE AS MENTIONED ON
 ORIGINAL NOTES, ARC FAULT PROTECTION
 REQUIRED PER 2002 NEC 210.12, HOWEVER
 THERE ARE NUMEROUS AREAS IN MOST UNITS
 IN WHICH CIRCUITING FOR LIGHTING ETC
 DOES NOT HAVE THE "* " ON THE CIRCUIT
 #'S ON PANEL SCHEDULE FOR THE
 PROTECTION.
 PLEASE SEE ALL "OUTLETS" INCLUDING SD'S,
 LTS, FANS AND RECEPTS REQUIRED THIS.
 PLEASE SEE MANY OF THESE CIRCUIT #'S
 HAVE BEEN REDLINED ON PLANS, BUT NOT
 ALL.
  
 45)NOTE: PLEASE SEE SOME UNITS ARE
 SHOWING FIXTURES IN SOME UTILITY/CLOTHES
 CLOSETS WHICH DO NOT APPEAR TO MEET
 410.8 FOR MIN CLEARENCE. PLEASE VERIFY.
  
 46)NOTE:PLEASE VERIFY FIXTURE
 CLEARENCE OVER TUBS/HYDRO ETC. AN
 ELEVATION IS NOT SHOWN FOR MIN CLEARENCE
 AND WE HAVE ENCOUNTERED MANY WHICH FALL
 BELOW MIN CLEARENCE EVEN FOR A RECESSED
 LT WITH AN ENCLOSED COVER.
 THIS IS ONLY A NOTE:
  
 47)NOTE: SEE PREVIOUS/UPPER NOTES, UNIT
 # H-7 FOR MISSING GFI W/IN 3' OF SINK.
 210.52
  
 48)NOTE: PLEASE SEE UNIT A-1 WHICH
 INDICATES A THIRD SMALL APPL CIRCUIT ,
 HOWEVER THIS COULD NOT BE LOCATED ON
 PLANS?
  
 49)NOTE: PLEASE SEE UNIT V-1 THIS
 APPEARS TO HAVE "ALL" DEVICES SHIFTED
 AND REVIEW FOR PLACEMENT FOR THESE
 DEVICES CAN NOT BE DONE AT THIS TIME.
  
 49)NOTE: PLEASE SEE MANY CLOTHES CLOSETS
 CONTAINING COMBUSTIBLES ARE SHOWN WITH
 CATV AND TELEPHONE CABINETS. PLEASE SEE
 IF THESE UNITS WILL REQUIRE ANY "LV
 PLUG-IN" TYOE TRANSFORMERS THEN THESE
 RECEPTS WHICH ARE NOT SHOWN AT THIS TIME
 WOULD ONLY BE ALLOWED DIRECTLY OVER
 DOORS.
 PLEASE SEE PLANS DO NOT INDICATE ANY LV
 ALARM PANELS AT THIS TIME AND SAME WOULD
 BE REQUIED IF LOCATED IN A CLOTHES
 CLOSET. THIS IS ONLY A NOTE:
  
 50)NOTE: PLEASE SEE 2002 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS.
 THIS WOULD BE FOR "HOUSE KITCHEN".
  
 51)NOTE: PLEASE SEE SOME UNITS WHICH DO
 NOT SHOW DEVICES, MENTIONS TO SEE OTHER
 SIMILAR UNITS, HOWEVER PLEASE SSE SOME
 ARE MSSING OR DO NOT CORRELATE.
 PLEASE SEE "B" UNIT, 3.23, "D-1"AND
 "D" UNIT ON 3.25.
  
 52)NOTE: PLEASE SEE FIRE COMMAND ROOM
 LAYOUT DO NOT NOT CORRLETATE FOR LAYOUT
 AND EQUIPMENT IN ROOMS AS NOTED.
 8.05,4.01
  
 53)NOTE: PLEASE SEE RISER AND PLANS DO
 NOT INDICATE ANY INFORMATION FOR
 DISC/BRKRS/OCP LOCATED ON GENERATOR FOR
 FEED/FEEDS TO GUTTER AND ON TO
 DISCONNECTS LOCATE DIN GEN RM.
 215.5 COMPLIANCE CAN NOT BE VERIFIED AT
 THIS TIME.
  
 54)NOTE: PLEASE SEE GROUND FUALT
 PROTECTION FOR SHN CAN NOT BE VERIFIED.
 CAN NOT LOCATE ON PLANS, RISER OR PANEL
 DETAIL/SCHEDULE.
 PLEASE SEE 240, GROUND-FAULT PROTECTION
 OF EQUIPMENT SHALL BE PROVIDED IN
 ACCORDANCE WITH THE PROVISIONS OF 230.95
 FOR SOLIDLY GROUNDED WYE ELECTRICAL
 SYSTEMS OF MORE THAN 150 VOLTS TO GROUND
 BUT NOT EXCEEDING 600 VOLTS
 PHASE-TO-PHASE FOR EACH INDIVIDUAL
 DEVICE USED AS A BUILDING OR STRUCTURE
 MAIN DISCONNECTING MEANS RATED 1000
 AMPERES OR MORE.
  
 55)NOTE: PLEASE SEE K-27 MENTIONS TO SEE
 TRANSFORMER GROUNDING DETAIL, HOWEVER
 THIS COULD NOT BE LCOATED ON PLANS.?
 PLEASE SHOW EITHER A TYPICAL DETAIL OR
 SHOW EACH. 250.30,215.5
  
 56)NOTE:PLEASE SEE KEYNOTE K-31,
 MENTIONS PER NAMEPLATE, HOWEVER
 DISCONNETC SIZES ETC, ARE REQUIRED AT
 THIS TIME A S MIN. 215.5
 PLEASE ALSO SEE K-NOTE FOR ELEVATOR
 CONTROLLER.
  
 57)NOTE: PLEASE SEE GUTTER SHOWN AT
 GENERATOR ROOM REFERENCES TO MEET 366.
 PLEASE SEE FBC 104.2.1, CODES FOR
 SPECIFIC DESIGNS ARE NOT TO BE REFERNECD
 IN WHOLE OR IN-PART. PLEASE SHOWN MIN
 GUTTER SIZE.
 PLEASE ALSO SEE NO CONDUCTORS SIZES ARE
 SHOWN, NO CONDUIT SIZES AND NO OCP
 (PREVIOUS NOTE) ARE SHOWN TO VERIFY
 COMPLIANCE. 310.16,215.5 240.4 ETC.
  
 58)NOTE: PLEASE SEE K-24, K25, NO SIZE
 FOR CONDUIT, FEEDER ETC FROM FIRE PUMP
 CONTROLLER TO FIRE PUMP. PLEASE SEE
 PLANS INDUCATE A "MAGNETIC TYPE" BRKR,
 HOWEVER NO SIZE IS GIVEN?
 215.5,310.16 ETC.
 PLEASE SEE PREVIOUS NOTES.
  
 59)NOTE: PLEASE SEE "SPEC BOOK", 16465
 2.2C WHICH MENTIONS ALUM BUS-DUCT.
 PLEASE SEE PREVIOUS NOTES IN REFERENCE
 TO EQUIPMENT GROUNDING METHOD OF
 BUS-DUCT. DOES THIS BUS-DUCT CONTAIN A
 SEPARATE ALUM BUS FOR GROUNDING? OR IS
 THE EQUIPMENT GROUNDING THAT IS GOING TO
 BE USED "PART" OF THE BUS-DUCT.
 PLEASE ALSO PLACE NOTE ON PLANS FOR
 REQUIRED CURBS FOR FLOOR PENATRATIONS.
 PER 368.6BFLOOR PENETRATIONS SHALL
 COMPLY WITH (1) AND (2):
 BUSWAYS SHALL BE PERMITTED TO BE
 EXTENDED VERTICALLY THROUGH DRY FLOORS
 IF TOTALLY ENCLOSED (UNVENTILATED) WHERE
 PASSING THROUGH AND FOR A MINIMUM
 DISTANCE OF 1.8 M (6 FT) ABOVE THE FLOOR
 TO PROVIDE ADEQUATE PROTECTION FROM
 PHYSICAL DAMAGE.
 IN OTHER THAN INDUSTRIAL ESTABLISHMENTS,
 WHERE A VERTICAL RISER PENETRATES TWO OR
 MORE DRY FLOORS, A MINIMUM 100 MM (4
 IN.) HIGH CURB SHALL BE INSTALLED AROUND
 ALL FLOOR OPENINGS FOR RISER BUSWAYS TO
 PREVENT LIQUIDS FROM ENTERING THE
 OPENING. THE CURB SHALL BE INSTALLED
 WITHIN 300 MM (12 IN.) OF THE FLOOR
 OPENING. ELECTRICAL EQUIPMENT SHALL BE
 LOCATED SO THAT IT WILL NOT BE DAMAGED
 BY LIQUIDS THAT ARE RETAINED BY THE
 CURB.
  
 60)NOTE: PLEASE SEE "SPEC BOOK" 16120
 2.3A5, PLEASE SEE COLOR CODING FOR
 277/480V SHALL BE BROWN, PURPLE, YELLOW.
 215.8 LOCAL AMENDMENTS.
  
 61)NOTE: THIS IS ONLY A NOTE: PLEASE SEE
 LOAD ON HGMN SHOWN AT 197A'S WITH 200A
 BRKR FEEDING THIS.
  
 62)NOTE: PLEASE SEE PLANS INDICATE "SHN"
 FEEDING"H5MN" WITH 125A BRKR, YET H5MN
 IS ONLY 100A'S.?
 PLEASE ALSO SEE RISER , APPEARS TO SHOW
 THIS AS "H5MH"?
  
 63)NOTE: PLEASE SEE DPHRN 150A BRKR TO
 100A FEEDERS (F-19).
  
 64)NOTE: PLEASE CORRELATE LOADS SHOWN ON
 "HRHN" AND TWO OTHER LOADS SHOWN ON
 "LRHN"
 215.5
  
 65)NOTE: PLEASE CORRELATE F-7, F-9 TO
 DPHE ON PANEL AND RISER.
 PLEASE SEE NO FEEDER SHOWN K? FOR HGMN
 ON RISER.
  
 66)NOTE: PLEASE CORRELATE "P-4" METER
 CENTER LOAD ANALYSIS AND NOT SHOWN ON
 ANY "SWITCH BOARD"?
 PLEASE ALSO SEE 2-W NEEDS TO CORRELATE
 WITH "SMCW". PLEASE ALSO SEE "MW" NOT
 SHOWN??
 215.5
  
 67)NOTE: PLEASE SEE "FUEL NOTE" MENTIONS
 277 GALS OF FUEL PER HR??? RUNNING A MIN
 OF 2.? HRS.
 PLEASE CLARIFY THIS NOTE: PLEASE SEE
 SIZING, CONSUMPTION OF GEN ETC CAN NOT
 BE VERIFIED. PLEASE SEE PREVIOUS NOTES
 PERTAINNG TO INFORMATION REQUIRED FOR
 GENERATOR ETC.
  
 68)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS SHOULD BE NOTED ON ALL
 EQUIPMENT.
  
 69)NOTE: PLEASE SEE ALL INFORMATION FOR
 AS SHOWN ON PLANS FOR LIGHTNING
 PROTECTION SYSTEMCAN BE INCLUDED UNDER
 BASE BLDG'S ELECTRICAL PERMIT. HOWEVER
 ANY CHANGES IN SYSTEM WOULD NEED
 REVISION. THIS SYSTEM WILL BE THE
 RESPONSIBILITY OF THE ELECTRICAL
 CONTRACTOR. IF THIS WORK IS "SUBBED'
 OUT, A SEPARATE PERMIT MUST BE PULLED BY
 LIGHTNING PROTECTION CONTRACTOR. SINCE
 THESE PLANS CONTAIN INFORMATION FOR
 SYSTEM, SUB CONTRACTOR MAY REFERENCE
 THESE PLANS AND A MIN $50 PERMIT FEE
 WILL BE DUE.
  
 70)NOTE: PLEASE ALSO SEEIF ALL
 INFORMATION FOR FIRE PUMP, FIRE PUMP
 CONTROLLER,GENERATOR, ATS, ETC IS NOT
 SUBMITTED FOR REVIEW WITH BASE BLDG
 PLANS, ALL OF THESE ITEMS WILL BE
 REQUIRED TO BE UNDER SEPARATE PERMIT
 ALONG WITH ALL FEES BASED ON VALUE OF
 ALL OF THOSE ITEMS.
 PLEASE SEE FIRE REVIEW COMMENTS.
  
 71)NOTE: PLEASE SEE MANY OF THE ABOVE
 ITEMS ARE REDLINED ON PLANS FOR AREAS OF
 NOTES. NOT "ALL" ITEMS ARE REDLINED.
  
 72)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SEE "ONE" SET OF ALL OLD/VOIDED
 REMOVED SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE ONLY.
  
 73)NOTE: PLEASE KNOW, AS NOTED IN SOME
 NOTES, DUE TO SOME INFORMATION MISSING
 ON PLANS AND WITH PLANS, A COMPLETE
 REVIEW FOR CODE COMPLIANCE CAN NOT BE
 DONE AT THIS TIME.
 PLEASE BE SURE TO INCLUDE ALL
 INFORMATION AS REQUESTED/NEEDED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER @WPB.ORG

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-01-06 Cont ID  
Sent By dpalmer Date 2005-01-06 Time 13:43 Rev Time 18.00
Received By dpalmer Date 2005-01-03 Time 15:09 Sent To  
Notes
2005-01-06 00:00:00*************** UNSAT *****************
  
 PLAN REVIEW ONLY FOR "TWO CITY PLAZA"
 PLANS NOT SUBMITTED FOR PERMIT AT THIS
 TIME, ONLY IN FOR "PLAN REVIEW".
  
  
 ****************************************
 ***************************************
  
 PLEASE SEE THAT DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, A FULL REVIEW
 FOR 2002 NEC CODE COMPLIANCE CAN NOT BE
 DONE.
 ****************************************
 ***************************************
  
 THE FOLLOWING NOTES ARE ONLY BASED ON
 WHAT INFORMATION IS AVAIBLAE AT THIS
 TIME.
 ****************************************
 ***************************************
  
 1)NOTE: PLEASE SEE SOME SHEETS HAVE THE
 ELECTRICAL PRINTED WITH DARKEN LINES
 AND MANY OF THE SHEETS ARE LT GRAY FOR
 ELECTRICAL. PLEASE DARKEN FOR EASE OF
 REVIEW PROCESS.
  
 2)NOTE: PLEASE SUBMIT WIND-LOADING FOR
 SITE/POLE LIGHTING AT THIS TIME. THIS
 IS REQUIRED FOR REVIEW AT THIS TIME.
 WIND LOADS 140MPH PER FBC.
  
 3)NOTE: PLEASE SEE FAC 61G15-23.002,
 61G1-16.004 FOR MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS FOR BOTH
 ENGIEERING FIRM AND ARCH FIRM.
 FS 471.023,481.219
 PLEASE ALSO SEE PLANS ARE REQUIRED TO
 BE SIGNED, DATED AND SEALED BY ENGINEER
 WHEN SUBMITTING FOR PERMIT.
  
 4)NOTE: PLEASE PROVIDE NOTE ON POOL
 PLANS: POOL TO BE UNDER SEPARATE:
 PLEASE PROVIDE NOTE FOR HOURS OF
 SWIMMING. IF AFTER DUSK SWIMMING IS TO
 TAKE PLACE AND COMPLETE PHOTOMETRICS
 WILL NEED TO BE SUBMITTED FOR REVIEW
 AND STAMPING BY THE PALM BEACH COUNTY
 HEALT DEPT. AND WILL BE REQUIRED TO BE
 IN THIS PLAN REVIEW.
  
 5)NOTE: PLEASE SEE FPL VAULT ROOM IS
 ALSO NOTED AS BEING ELECTRICAL ROOM FOR
 GARAGE. PLEASE SEE FPL VAULT
 REQUIREMENTS SET FORTH BY FPL AND
 PERMITTING NO OTHER ELECTRICAL
 EQUIPMENT
 IN THEIR VAULT.
  
 6)NOTE: ELECTRICAL PLANS DO NOT CLEARLY
 SHOW A DIRECT FIRE RATE ACCESS TO MAIN
 ELECTRICAL RM WHICH APPEARS TO BE
 LOCATED ABOVE GRADE LEVEL. PLEASE
 PROVIDE INFORMATION/DIRECTIONAL FOR
 ACCESS FOR FIRE DEPT PERSONNEL FOR
 SHUTTING DOWN OF MAINS. PLEASE ALSO
 PROVIDE NOTE ON PLANS FOR REQUIRED
 "KNOX BOX" FOR FIRE DEPT. PLEASE SEE
 FIRE REVIEW NOTES FOR THIS.
  
 7)NOTE: PLEASE SEE MANY AREAS OF PLANS
 FOR COMMON AREAS/COMMON HALLWAYS ETC DO
 NOT INDICATE ANY ELECTRICAL FOR
 LIGHTING, RECEPTS, FIRE DEVICES ETC.
 PLEASE SUBMIT COMPLETED COMMON AREAS.
  
 8)NOTE: PLEASE SEE 620.23,620.24 FOR
 REQUIREMENTS IN ELEV RMS/ PITS ETC.
  
 9)NOTE: PLEASE CLARIFY RECEPTS W/IN 20'
 OF POOL ON ROOF.620.22A3 WHERE A
 PERMANENTLY INSTALLED POOL IS INSTALLED
 AT A DWELLING UNIT(S), NO FEWER THAN
 ONE 125-VOLT 15- OR 20-AMPERE RECEPTACLE
 ON A GENERAL-PURPOSE BRANCH CIRCUIT
 SHALL BE LOCATED NOT LESS THAN 3.0 M (10
 FT)FROM AND NOT MORE THAN 6.0 M (20 FT)
 FROM THE INSIDE WALL OF THE POOL.
  
 10)NOTE: PLEASE SEE GENERAL NOTES ON
 UNIT ELECTRICLA PLANS REFERENCE 1999
 NEC. PLEASE SEE AS OF JULY 1ST, 2003,
 WE ARE UNDER THE 2002 NEC. PLEASE
 ADJUST
 NOTES AND PLEASE ALSO ADJUST ALL OTHER
 SHEETS WHERE CODES ARE REFERENCED.
  
 11)NOTE: PLEASE PROVIDE A COMPLETE
 FIXTURE SCHEDULE. PLEASE ALSO CORRELATE
 WITH PLANS.
  
 12)NOTE: PLEASE CLARIFY UNITS,
 1,2,3,AND 4. IT APPEARS THERE IS NO
 ACCESS TO UNITS FROM GARAGE?
  
 13)NOTE: PLEASE SEE 210.70 FOR CONTROL
 OF EGRESS LIGHTING FOR UNITS W/ ACCESS
 FROM OUTSIDE WITH WHAT APPEARS TO HAVE
 NO CONTROL/SWICTHING OF LIGHTING WHEN
 ENTERING THE UNITS.
 PLEASE ALSO SEE ANY OTHER GRADE LEVEL
 ACCESS UNITS WHICH 3-WAY SWITCHING MAY
 BE REQUIRED. LS-101 5-8
  
 14)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE UNITS #6, 17
  
 15)NOTE: PLEASE SEE SD'S APPEAR TO BE
 SHOWN ON LITCHEN/BATH LIGHTING
 CIRCUITS.
 THIS IS FINE, HOWEVER ARC FAULT
 PROTECTION WOULD ALSO BE REQUIRED FOR
 THISE CIRCUITS AND NEED TO BE NOTED ON
 PANEL SCHEDULES. (NOTE 6) ON PANEL
 SCHEDULES.
 PLEASE SEE 2002 NEC 210.12
  
 16)NOTE: PLEASE SEE SOME UNITS, IN SOME
 BEDRMS, SD'S ARE MISSING. ( #11)
 NFPA-72 8-1.4.1.6.2
  
 17)NOTE: PLEASE SEE 210.52D FOR GFI
 RECEPTS REQUIRED WITHIN 3' OF THE EDGE
 OF LAVS. PLEASE SEE AREAS WITH TWO
 SINKS. GFI MAY BE MOVED TO CENTER OF
 SINKS OR MAYHAVE AN ADDITIONAL GFI
 ADDED.
  
 18)NOTE:PLEASE SEE PANEL NOT PERMITTED
 IN STORAGE/CLOTHES CLOSET. 240.24
 OVERCURRENT DEVICES SHALL NOT BE
 LOCATED IN THE VICINITY OF EASILY
 IGNITIBLE MATERIAL, SUCH AS IN CLOTHES
 CLOSETS.
 PLEASE ALSO SEE 408.7
  
 19)NOTE:PLEASE SEE SOME UNITS APPEAR TO
 BE SHOWING TWO PANELS. UNIT VV.
  
 20)NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARENCE REQUIREMENTS FOR PANELS SHOWN
 IN SOME UNITS. ONE SHOWN FACING
 COUNTERSPACE/ DISHWASHER. UNIT M.
  
 21)NOTE: PLEASE SEE 210.70 FOR LT
 REQUIRED FOR AHU'S IN HALL CLOSETS,
 PLEASE ALSO SEE 210.63
  
 22)NOTE: PLEASE SEE 210.52C1-4
 PENINSULAR COUNTER SPACES. AT LEAST ONE
 RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH PENINSULAR COUNTER SPACE WITH A
 LONG DIMENSION OF 600 MM (24 IN.) OR
 GREATER AND A SHORT DIMENSION OF 300 MM
 (12 IN.) OR GREATER. A PENINSULAR
 COUNTERTOP IS MEASURED FROM THE
 CONNECTING EDGE.COUNTERTOP SPACES
 SEPARATED BY RANGE TOPS, REFRIGERATORS,
 OR SINKS SHALL BE CONSIDERED AS
 SEPARATE COUNTERTOP SPACES IN APPLYING
 THE REQUIREMENTS OF 210.52(C)(1), (2),
 AND (3). UNITS D, G, A ETC.
  
 23)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 SD LOCATION REQUIREMENTS PER NFPA-72
 8-1.4.2
  
 24)NOTE: PLEASE VERIFY IF THERE ARE
 GOING TO BE ANY TERRACE LTS/GFI'S?
 PLEASE SEE ARCH SHEETS, ELEVATION PLANS
 SHOWS LTS. PLEASE CORRLELATE.
 PLEASE ALSO CORRELATE LAYOUT OF TERRACE
 ON ELECTRICAL PLANS WITH LAYOUT AS
 SHOWN ON FLR PLANS ON ARCH.
  
 25)NOTE:PLEASE VERIFY IF UNITS WITH
 JACUZZI/SPA UNITS. PANEL SCHEDULES
 INDICATE SOME AS FUTURE AND SOME APPEAR
 TO BE INSTALLED AT THIS TIME, HOWEVER
 THE FLR LAYOUTS DO NOT INDICATE THIS OR
 GFI RECEPTS OR GFI BRKRS.680.62A THE
 OUTLET(S) THAT SUPPLIES A
 SELF-CONTAINED THERAPEUTIC TUB OR
 HYDROTHERAPEUTIC TANK, A PACKAGED
 THERAPEUTIC TUB OR HYDROTHERAPEUTIC
 TANK, OR A FIELD-ASSEMBLED THERAPEUTIC
 TUB OR HYDROTHERAPEUTIC TANK SHALL BE
 PROTECTED BY A GROUND-FAULT CIRCUIT
 INTERRUPTER.
  
 26)NOTE: PLEASE SEE OCP FOR FIRE PUMP
 IS TO BE PER LOCKED ROTOR AS NOTED ON
 RISER. PLEASE SUBMIT ALL INFORMATION
 FOR FIRE PUMP, FIRE PUMP CONTROLLER.
 ETC
 SUBMIT ALL MANUFACT SPECS.
 PLEASE SPECIFY CODE LTR FOR PUMP.
  
  
 27)NOTE: PLEASE ALSO SUBMIT ALL
 MANUFACTURER SPECS FOR GENERATOR, ALL
 TRANSFER SWITCHES AND FUEL TANK, SHOWING
 ALL LISTINGS BY THE NRTL.
  
 28)NOTE: PLEASE SEE 110.26 FOR ALL
 CLEARENCE REQUIREMENTS FOR ELECTRICAL
 RMS AND CLOSETS. MANY OF THE LAYOUTS
 SHOWN DO NOT MEET 110.26 FOR CLEARENCE
 OF EQUIPMENT.
 PLEASE ALSO SEE 110.26 FOR DOOR SWING,
 AND REQUIREMENTS FOR PANIC HARDWARE ON
 DOORS. A NOTE NEEDS TO BE PLACED ON
 PLANS FOR THIS REQUIREMT.
  
 29)NOTE:PLEASE CORRELATE ELECTRICAL
 RISER WITH ELECTRICAL EQUIPMENT SHOWN
 IN
 ELECTRICAL RMS. PLEASE SEE MISSING
 "SHE".
  
 30)NOTE: PLEASE CORRELATE "K" NOTES ON
 RISER WITH THE ACTUAL SCHEDULE OF KEYED
 NOTES ON PLANS. K-10 ETC.
  
 31)NOTE: PLEASE VERIFY COPPER EQUIPMENT
 GROUNDING IN BUS-DUCT. PLEASE SEE LOAL
 AMENDMENTS WHICH DOES NOT PERMIT ALUM
 FOR GROUNDING OR BONDING.310.2,250.62
  
 32)NOTE: PLEASE PROVIDE NOTE WHEATHER
 OR NOT GENERATOR WILL BE SEPARATELY
 DERIVED OR NOT. IF YES, PLEASE SEE ATS,
 TO 4-POLE.
  
 33)NOTE: PLEASE SEE RISER FOR ATS SIZES
 AND OCP FEEDING ATS SWITCHES. PLEASE
 SEE 900A OCP FEEDING 800A ATS.
  
 34)NOTE: PLEASE COMPLETE RISER DIAGRAM
 WITH SIZE OF EQUIPMENT SHOWN ON RISER.
 PLEASE PROVIDE SIZES OF ALL EQUIPMENT ,
 TRANSFORMERS, GROUNDING FOR
 TRANSFORMERS, KEYED NOTES ON RISER ETC.
 215.5,250.30, ETC.
 PLEASE SUBMIT PANEL SCHEDULES FOR ALL
 EQUIPMENT SHOWN ON SERVICE RISER.
 PLEASE SEE RISER/NOTES APPEAR TO HAVE
 4000A MAINS/OCP FEEDING 3000A BUS-DUCT.
 MANY OF THESE ITEMS CAN NOT BE VERIFIED
 AT THIS TIME, DUE TO NONE OFTHIS
 INFORMATION SUBMITTED.
  
 35)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR BUILDING. THE ONLY
 LOAD CALCS SUBMITTED WERE FOR
 INDIVIDUAL
 UNITS AND METER CNTRS.
 215.5,220
  
 36)NOTE: PLEASE VERIFY MANY UNITS ONLY
 SHOWING A "COOKTOP". ARE THESE RANGES,
 CONTAINING AN OVEN ALSO?
 SOME UNITS SHOW SEPARATE COOKTOPS AND
 OVENS, BUT IT APPEARS UNITS ONLY WITH
 "COOKTOP" WILL HAVE NO OVENS??
  
 37)NOTE: PLEASE SEE FEEDERS SCHEDULE
 SET UP FOR UNITS SHOWN FOR 125A,150A
 AND
 175A ONLY. PLEASE SEE LOADS CALCS/MTR
 CNTRS SHOW SOME UNITS FED WITH 200A OCP
 AND 250A OCP. PLEASE SEE MIN CONDUCTORS
 FOR 250A PER 310.16
  
 38)NOTE: PLEASE VERIFY SIZE OF PANELS.
 PANELS ARE SHOWN AS 200A , HOWEVER SOME
 SHOWN W/ 250A OCP FROM METER CNTRS.
  
 39)NOTE: PLEASE VERIFY OCP FOR SOME
 WATER HEATERS ( 6KW) MAX OCP 150%, PER
 422.11, MIN 125% 422.13.A BRANCH
 CIRCUIT
 SUPPLYING A FIXED STORAGE-TYPE WATER
 HEATER THAT HAS A CAPACITY OF 450 L
 (120GAL) OR LESS SHALL HAVE A RATING
 NOT
 LESS THAN 125 PERCENT OF THE NAMEPLATE
 RATING OF THE WATER HEATER.
  
 PLEASE SEE MANY OF THESE NOTES ARE
 REDLINED ON ONE SET OF REVIEWED PLANS
 FOR AREAS OF CONCERN.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 SUBMIT COMPLETED SETS FOR REVIEW.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE ANY
 AFFECT ON ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2005-01-03 00:00:00IN ELECTRICAL FOR REVIEW.
 NOTES TO FOLLOW.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-04-10 Cont ID  
Sent By rchokshi Date 2008-04-10 Time 11:39 Rev Time 0.00
Received By rchokshi Date 2008-04-10 Time 11:38 Sent To Z
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-04-15 Cont ID  
Sent By mamini Date 2005-04-15 Time 11:41 Rev Time 1.00
Received By mamini Date 2005-04-15 Time 11:41 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-12-10 Cont ID  
Sent By mamini Date 2004-12-10 Time 08:37 Rev Time 0.50
Received By mamini Date 2004-12-10 Time 08:37 Sent To  
Notes
2004-12-10 00:00:00FAILED:
  
 1. NO CIVIL PLANS WITH THIS SUBMITTAL
 PACKAGE. PLEASE SUBMIT CIVIL PLANS FOR
 OUR REVIEW AND APPROVAL UPON COMPLETION.
  
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 20 Status P Date 2008-08-11 Cont ID  
Sent By mawillia Date 2008-08-11 Time 17:05 Rev Time 0.00
Received By mawillia Date 2008-08-11 Time 16:23 Sent To  
Notes
2008-08-11 16:25:45*****SUBMITTAL*****
  
  
 RESIDENT EMERGENCY PROCEDURES & EVACUATION PLAN.THREE
 SETS WERE SUBMITTED -(1) TO BE FILED AT CONSTRUCTION
 SERVICES DEPARTMENT,(1) TO BE FILED AT THE FIRE
 PREVENTION BUREAU,AND (10 TO BE RETURNED TO THE
 CONTRACTOR.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 19 Status P Date 2008-03-14 Cont ID  
Sent By mwennerg Date 2008-03-14 Time 13:12 Rev Time 0.00
Received By mwennerg Date 2008-03-14 Time 13:12 Sent To  
Notes
2008-03-14 13:13:32SMOKE MANAGEMENT PANEL SUBMITTAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 18 Status F Date 2008-02-06 Cont ID  
Sent By mawillia Date 2008-02-06 Time 14:30 Rev Time 0.00
Received By mawillia Date 2008-02-06 Time 14:19 Sent To  
Notes
2008-02-06 14:23:49*****UNSAT*****
  
  
 AS PER WEST PALM BEACH FIRE PREVENTION, DUCT SMOKE
 DETECTORS SHALL INITIATE GENERAL FIRE ALARM.AMEND
 SHEET E3.06 TO REFLECT AS SUCH
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 17 Status F Date 2008-01-23 Cont ID  
Sent By mawillia Date 2008-01-23 Time 12:08 Rev Time 0.00
Received By mawillia Date 2008-01-23 Time 11:30 Sent To  
Notes
2008-01-23 12:04:20*****REVISION 18, DATED 12/19/07 , UNSAT*****
  
  
  
 PLEASE BE ADVISED THAT DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.AMEND THE APPROPIATE
 ELECTRICAL SHEETS TO REFLECT THIS AS PER LOCAL
 REQUIREMENTS
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 16 Status P Date 2007-12-28 Cont ID  
Sent By mawillia Date 2007-12-28 Time 11:43 Rev Time 0.00
Received By mawillia Date 2007-12-28 Time 11:21 Sent To  
Notes
2007-12-28 11:42:20*****REVISION APPROVED*****
  
  
 REVIEWED VARIOUS REVISED ELECTRICAL PARTIAL SHEETS;NO
 FIRE-STAMPING NEEDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 15 Status P Date 2007-09-14 Cont ID  
Sent By mwennerg Date 2007-09-14 Time 15:21 Rev Time 0.00
Received By mwennerg Date 2007-09-14 Time 15:21 Sent To  
Notes
2007-09-14 15:23:19REVISION ILLUSTRATING FIRE EXTINGUISHER LOCATIONS.
 ADDITIONAL EXTINGUISHERS REQUIRED AT POOL LEVEL. LIFE
 SAFETY SHEETS STAMPED. (2 ROLLS)

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status F Date 2007-07-25 Cont ID  
Sent By mwennerg Date 2007-07-25 Time 15:37 Rev Time 0.00
Received By mwennerg Date 2007-07-25 Time 15:37 Sent To  
Notes
2007-07-25 15:38:41FIRE ALARM EQUIPMENT SUBMITTAL TO BE SUBMITTED UNDER
 FIRE ALARM PERMIT

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status P Date 2007-05-15 Cont ID  
Sent By mwennerg Date 2007-05-15 Time 09:47 Rev Time 0.00
Received By mwennerg Date 2007-05-15 Time 09:47 Sent To  
Notes
2007-05-15 09:50:18FIRE PROTECTION REVISIONS SHALL BE SUBMITTED UNDER THE
 FIRE SPRINKLER PERMIT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2007-05-15 Cont ID  
Sent By mwennerg Date 2007-05-15 Time 09:28 Rev Time 0.00
Received By mwennerg Date 2007-05-15 Time 09:28 Sent To  
Notes
2007-05-15 09:29:00FIRE VALVE CABINET SUBMITTAL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status N Date 2007-03-20 Cont ID  
Sent By mwennerg Date 2007-03-20 Time 15:08 Rev Time 0.00
Received By mwennerg Date 2007-03-20 Time 15:08 Sent To  
Notes
2007-03-20 15:09:45FIRE PROTECTION REVISIONS INDICATED BUT NO FIRE
 PROTECTION SHEETS SUBMITTED. REVISIONS FOR SEPARATE
 PERMITTED WORK TO BE SUBMITTED UNDER APPLICABLE PERMIT.
 NO REVISED LIFE SAFETY SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status P Date 2007-01-19 Cont ID  
Sent By mawillia Date 2007-01-19 Time 17:02 Rev Time 0.00
Received By mawillia Date 2007-01-19 Time 17:02 Sent To  
Notes
2007-01-19 17:08:47*****APPROVED*****
  
  
 DATE STAMPED:HYDRAULIC CALCULATIONS AND SUBMITTAL
 PACKAGES FROM SUMMERS FIRE SPRINKLERS,INC.

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2006-12-29 Cont ID  
Sent By mawillia Date 2006-12-29 Time 11:13 Rev Time 0.00
Received By mawillia Date 2006-12-29 Time 11:13 Sent To  
Notes
2006-12-29 11:17:02*****APPROVED*****
  
  
  
 OK'DTHE LOCATION OF FIRE SPRINKLERS (EVERY OTHER
 FLOOR) FOR THE NEWLY INSTALLED TRASH CHUTE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2006-10-17 Cont ID  
Sent By mwennerg Date 2006-10-17 Time 16:00 Rev Time 0.00
Received By mwennerg Date 2006-10-17 Time 16:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2006-07-21 Cont ID  
Sent By mwennerg Date 2006-07-21 Time 08:41 Rev Time 0.00
Received By mwennerg Date 2006-07-21 Time 08:41 Sent To  
Notes
2006-07-21 00:00:00REVISION DATED 4/6/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2006-07-20 Cont ID  
Sent By mwennerg Date 2006-04-13 Time 14:58 Rev Time 0.00
Received By mwennerg Date 2006-04-13 Time 14:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-02-16 Cont ID  
Sent By mcarsill Date 2006-02-16 Time 11:56 Rev Time 0.00
Received By mcarsill Date 2006-02-16 Time 11:56 Sent To  
Notes
2006-02-16 00:00:001. REVISIONS FOR COMMENTS COMPLETED ON
 1/6/06 ARE TO BE SUBMITTED WITHIN 30
 DAYS OF FEBRUARY 16, 2006.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709
 PLANS ARE APPROVED PROVISO THAT ALL
 PREVIOUS COMMENTS ARE ADDRESSED WITH
 REVISED PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2006-01-06 Cont ID  
Sent By mcarsill Date 2006-01-06 Time 14:48 Rev Time 0.00
Received By mcarsill Date 2006-01-06 Time 12:20 Sent To  
Notes
2006-01-23 00:00:0019. PLEASE EXPLAIN "OR THROUGH THE
 ANNUNCIATION OF AT LEAST THREE (3) AREA
 WIDE SMOKE DETECTORS SERVING A SMOKE
 CONTROL ZONE". (SMOKE CONTROL OPERATION
 PAGE M7.01.) WHY WILL IT TAKE THREE
 SMOKE DETECTORS TO OPERATE.
  
 20. PLEASE INCLUDE NOTE TO PAGE M7.01
 "ANTICPATED STACK EFFECT" REGARDING
 STAIR PRESSURIZATION.
  
 21. FIRE SPRINKLER PROTECTION REQUIRED
 BELOW DUCTWORK THAT IS GREATER THAN 48"
 WIDE.
  
 22. THE EMERGENCY GENERATOR TERMINATION
 EXHAUST DUCT POINT SHALL BE LOCATED WITH
 RESPECT TO WINDOWS, DOORS OR SUPPLY AIR
 OPENING. ALSO ARCHITECTURAL FEATURES CAN
 CAUSE A BACKFEED CONDITION.
  
 23. ALL FIRE DAMPERS ARE TO BE DROP
 TESTED AND CERTIFIED AFTER INSTALLATION.
  
 24. COOLING TOWERS TO COMPLY WITH NFPA
 214.
  
 25. TWO DAMPERS APPEAR TO BE SHOWN ON
 DRAWING BUT ARE NOT CALLED OUT ON PAGE
 M2.09.
  
 26. A DAMPER IS SHOWN ON PAGE M2.03 DOES
 NOT APPEAR TO BE CALLED OUT.
  
 27. WILL THE HORIZONTAL MEMBERS OF THE
 TRELLIS HAVE AN EFFECT ON SEF-1, SHOWN
 ON THE SECTION 1, PAGE M1.13.
  
 28. THE SMOKE SYSTEM AND STAIRWELL
 PRESSURIZATION SYSTEMS SHALL BE TESTED
 PRIOR TO REQUESTING A TCO OR CO AND BOTH
 SYSTEMS MUST BE APPROVED BY CITY
 OFFICIALS.
2006-01-06 00:00:001. ALL EXIT ACCESS AREAS AND EXIT DOORS
 SHALL BE PROVIDED WITH EXIT SIGNS. SOME
 ELECTRICAL SHEETS APPEAR TO BE MISSING
 EXIT SIGNS.
  
 2. NO EXIT SIGNS SHOWN ON MAIN ROOF
 LEVEL WEST. E2.19. THE SAME CONDITION
 MAIN ROOF LEVEL EAST.
  
 3. THERE APPEARS TO BE A DISCREPANCY
 BETWEEN SOME DRAWING SHEETS. ON ONE
 SHEET THE SMOKE MANAGEMENT PANEL IS
 MISSING FROM THE FIRE COMMAND ROOM AND
 ANOTHER PAGE IT IS SHOWN.
  
 4. THE REQUIRED FIRE ALARM SYSTEM SHALL
 BE MONITORED BY A UL LISTED CENTRAL
 STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 5. FIRE SPRINKLER HEADS SHALL BE QUICK
 RESPONSE OR BE RESIDENTIAL TYPES.
  
 6. STANDPIPES SHALL PROVIDE COVERAGE TO
 ALL ARES OF THE BUILDING. ALL REQUIRED
 STAIRWELLS ARE REQUIRED TO HAVE
 STANDPIPES.
  
 7. ALL ELEVATORS THAT CAN BE USED FOR
 STRETCHERS SHALL BE IDENTIFIED.
  
 8. DOOR MISSING FROM EXIT PATH FROM
 ELEVATOR VESTIBULE # 3 UP THE STAIRS AND
 APPEARS TO TRAVEL BEHIND PARKING SPACE.
 PLEASE SEE PAGE LS1.03.
  
 9. PLEASE VERIFY DOOR SWINGS IN
 HORIZONTAL EXITS SHOWN ON PAGE LS1.03.
  
 10. EXIT SIGNS ON POOL DECK SHALL NOT
 EXCEED 100 FEET. PLEASE SEE LS1.10.
  
 11. PLEASE PROVIDE FLAMESPREAD DATA ON
 "THERMOCON SPRAY -ON INSULATION SHOWN ON
 PAGE A4.02.
  
 12. THE "3-0 WIDE PEDESTRIAN PASS GATE
 MUST BE LABELED AS AN EXIT. WHEN THE
 VEHICULAR SECTIONAL GATE IS DOWN ONLY
 ONE EXIT APPEAR VISIBLES FROM THE THAT
 SPECIFIC PARKING AREA. PLEASE SEE A4.11.
  
 13. PLEASE EXPLAIN CARD READERS SHOWN ON
 PAGE A4.14. WILL THEY POSE ANY PROBLEMS
 WITH REGARDS TO EXITING.
  
 14. CARD READERS NOTED IN SEVERAL PLACES
 ON DOOR SCHEDULE. PLEASE NOTE ON THE
 PLANS HOW THESE DEVICES WILL NOT
 INTERFERE WITH EXITING REQUIREMENTS.
  
 15. MECHANICAL ACCESS SPACES SHOWN ON
 SEVERAL A PAGES. PLEASE PROVIDE DETAILS.
  
 16. POOL DECK FLOOR HAS A DOOR THAT
 OPPOSES ONE OF THE POOL PUMP ROOM DOOR.
 PLEASE SEE PAGE A7.05A
  
 17. MORE DETAILS NEEDED ON NON-RATED
 METAL MESH PARTITION SHOWN ON PAGE
 A7.03.
  
 18. ON SOME OF THE REFLECTED CEILING
 PLANS, SMOKE DETECTORS APPEAR TO BE
 DIRECTLY NEXT TO HVAC DIFFUSERS. THE
 MINIMUM THREE FOOT RULE IS TO APPLY.
  
 NOTE: MECHANICAL DRAWINGS WILL BE NEXT
 SET OF DRAWINGS TO BE REVIEWED BY THIS
 OFFICE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-09-30 Cont ID  
Sent By mwennerg Date 2005-09-30 Time 09:28 Rev Time 0.00
Received By mwennerg Date 2005-09-30 Time 09:28 Sent To  
Notes
2005-09-30 00:00:00******DENIED******
  
 1) EXIT SIGN STILL APPEARS TO LEAD
 PERSONS INTO THE LOADING AREA. SHT
 E-2.01. PLEASE CLARIFY ARCHITECT'S
 RESPONSE.
  
 2) FIRE PROTECTION PLANS HAVE BEEN
 SUBMITTED WITH THIS PERMIT. SEPARATE
 SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS.
  
 3) A COPY OF THE FIRST REVIEW HAS BEEN
 INCLUDED. PLEASE SUBMIT YOU RESPONSE
 LETTER TO THAT REVIEW THAT WAS COMPLETED
 ON 1/21/05. A RESPONSE LETTER COULD NOT
 BE FOUND WITH THIS SUBMITTAL.
  
 4) ELECTRONIC SWITCHES, CHAIN AND LOCK
 REQUIRED ON DOUBLE CHECK DETECTOR
 ASSEMBLY.
  
 5) SIGNS ARE REQUIRED IN STAIRWELLS THAT
 INDICATE TOP, FLOOR# AND ROOF ACCESS.
  
 6) TACTILE SIGNAGE IS REQUIRED FOR EXIT
 DOORS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-04-28 Cont ID  
Sent By mwennerg Date 2005-04-28 Time 09:56 Rev Time 0.00
Received By mwennerg Date 2005-04-28 Time 09:55 Sent To  
Notes
2005-04-28 00:00:001) NOTE #1- EXIT PATH MAY REQUIRE
 STRIPING OR SOME OTHER APPROVED METHOD
 OF MARKING TO MAINTAIN A CLEAR AND
 UNOBSTRUCTED PATH OF TRAVEL.
  
 2) NOTE #24- DOOR SWINGS ON STAIRS #7&8
 APPEAR TO BE SWINGING IN THE WRONG
 DIRECTION.
  
 3) NOTE #26- NO RESPONSE CAN BE FOUND
 REGARDING TWO FIRE DEPARTMENT
 CONNECTIONS.
  
 4) NOTE #37- NO RESPONSE FOUND REGARDING
 SMOKE DETECTOR IN FIRE COMMAND ROOM.
  
 5) NOTE #57- NO RESPONSE FOUND REGARDING
 SMOKE MANAGEMENT REQUIREMENTS.
  
 6) NOTE #59- HOW WAS THE COMMENT
 REGARDING DIRECTION OF EGRESS ADDRESSED?
  
  
 7) NOTE #58- NO RESPONSE FOUND
  
 8) NOTES #60-64- NO RESPONSES FOUND.
  
 NOTE: WHEN RESPONDING TO REVIEW NOTES,
 PLEASE IDENTIFY THE SHEET NUMBER WITH
 REVISION CLOUDS TO HELP EXPEDITE THIS
 PROCESS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-01-21 Cont ID  
Sent By mcarsill Date 2005-01-21 Time 09:41 Rev Time 0.00
Received By mcarsill Date 2005-01-21 Time 09:41 Sent To  
Notes
2005-01-21 00:00:001. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE
 STORIES OR 30 FEET IN HEIGHT.
  
 3. SINCE THE BUILDING WILL BE
 CONSIDERED HIGH-RISE IT MUST
 COMPLY WITH APPLICABLE BUILDING AND
 FIRE CODE REQUIREMENTS FOR HIGH-RISE
 BUILDINGS.
  
 4. PLEASE EXPLAIN CONTROLLED ENTRY
 AND EXIT NOTES ON PAGE LS1.01.
  
 5. PLEASE INDICATE WHAT ELEVATORS
 ARE STRETCHER ACCESSIBLE.
  
 6. EXIT SIGN PLACEMENT SHALL NOT
 EXCEED 100 FEET.
  
 7. PLEASE ILLUSTRATE ALL EXIT
 DISCHARGE LOCATIONS FROM THE
 BUILDING. EXIT DISCHARGE LOCATIONS
 SHALL COMPLY WITH APPLICABLE FIRE
 CODE REQUIREMENTS.
  
 8. KNOX-BOXES WILL BE REQUIRED FOR
 THE BUILDING.
  
 9. ON PAGE LS1.03 PLANS MAKE REFERENCE
 TO HORIZONTAL EXITS. PLEASE EXPLAIN
 HOW THE CODE REQUIREMENTS FOR
 HORIZONTAL EXITS ARE BEING MET.
  
 10. ON PAGE LS1.03 EXITING IS SHOWN
 THRU TENANT STORAGE ROOM B. PLEASE
 EXPLAIN WHAT CODE ALLOWS THIS TO
 OCCUR.
  
 11. EXIT PATH ON LS1.05 IS GOING
 BETWEEN TWO HANDICAP VEHICLES. PLEASE
 EXPLAIN.
  
 12. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND
 CEILINGS.
  
 13. PLEASE INDICATE OCCUPANT LOAD
 FOR THE 5TH FLOOR LANAI SHOWN
 ON PAGE LS1.07.
  
 14. PLEASE VERIFY OCCUPANT LOADS
 FOR THE HEALTH CLUB AND MULTI-PURPOSE
 ROOMS TO DETERMINE IF EXIT DOORS
 SWINGS ARE PROPER. LS1.07.
  
 15. WHAT CODE REQUIREMENTS ARE BEING
 MET
 TO EXIT FROM THE DECK OF THE LANAI
 AREA.
  
 16. IS THE AREA CALLED OUT ON PAGE
 LS1.10 "EXIT PATH OF TRAVEL-LIGHTED
 AND PAINTED LINES OF DEMARKATION"
 ALSO SLIP RESISTANT.
  
 17. NO STORAGE OF ANY KIND WILL BE
 ALLOWED IN LOCATIONS NOTED FOR
 INSPECTION AND SERVICE ONLY.
  
 18. THE FIRE PROTECTION FOR THE
 COOLING TOWERS SHALL COMPLY WITH
 NFPA 214.
  
 19. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL
 HANDRAILS AND GUARDRAILS.
  
 20. SOME DOOR SWINGS ON THE MEZZANINE
 LEVEL AND PARKING LEVEL P3 ON
 PAGE A2.03 MAY NOT SWING IN THE
 PROPER DIRECTION.
  
 21. PARKING AREA TO COMPLY WITH
 NFPA 88A.
  
 22. NO NOTE INDICATING THAT STAIR #6
 IS PRESSURIZED.
  
 23. PLANS ILLUSTRATE A 21ST FLOOR
 BUT IT IS BELIEVED THAT THE PERMIT
 APPLICATION INDICATES A 20 STORY
 BUILDING.
  
 24. DOOR SWINGS ON STAIR # 2,7,AND 8
 ARE SWINGING IN THE WRONG DIRECTION
 ON PAGE A2.16.
  
 25. WRONG ADDRESS NOTED ON F10 NOTE
 ON PAGE A3.01. SAME CONDITION EXISTS
 ON A3.03.
  
 26. TWO FIRE DEPARTMENT CONNECTIONS
 WILL BE REQUIRED SINCE IT IS A
 HIGH-RISE BUILDING.
  
 27. NEW FIRE ALARM SYSTEM SHALL BE
 MONITORED UL LISTED CENTRAL STATION
 APPROVED FOR CENTRAL STATION SERVICE.
  
 28. IS ANY ACCESS PROVIDED FOR
 MECHANICAL SPACES SHOWN ON PAGE A3.21.
  
 29. A DOOR IS NOTED WITHIN THE EXIT
 ENCLOSURE FOR STAIR # 2 NEAR
 ELEVATOR # 3. PLEASE EXPLAIN CODE
 PROVISIONS THAT YOU MEET THAT
 ALLOWS FOR THIS.
  
 30. PLEASE INDICATE SIZE OF PEDESTRIAN
 PASS DOOR ON PAGE A4.11.
  
 31. KNOX-BOX LOCKING CAPS WILL BE
 REQUIRED ON FIRE DEPARTMENT
 CONNECTIONS.
  
 32. ALL SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF THREE FEET
 FROM AC DIFFUSERS.
  
 33. WHAT IS THE ELEVATION OF THE
 TERRACE SHOWN ON PAGE A4.41.
  
 34. HAND WRITTEN NOTES APPEAR ON
 SEVERAL PAGES OF THE PLAN.
  
 35. EXIT STAIRS ARE TO BE KEPT UP
 WITH CONSTRUCTION.
  
 36. NO COMBUSTIBLES ALLOWED IN ANY
 RETURN AIR PLENUM. NOTES LOCATED IN
 PLANS.
  
 37. NO SMOKE DETECTOR SHOWN IN FIRE
 COMMAND ROOM.
  
 38. ELEVATOR WARNING SIGNS REQUIRED
 AT ELEVATOR LOBBIES.
  
 39. PLEASE INDICATE LOCATIONS OF
 SPEAKER STROBES FOR APARTMENTS
 PROVIDED FOR THE HANDICAPPED.
  
 40. ANY SOFFITS THAT ARE PLANNED SHALL
 NOT INTERFERE WITH ANY FIRE PROTECTION
 EQUIPMENT OR DEVICES.
  
 41. PLEASE PROVIDE FLAMESPREAD DETAILS
 ON HIGH-DENSITY STYROFOAM BLOCK
 SHOWN ON A7.02. PLEASE EXPLAIN
 PURPOSE OF MATERIAL.
  
 42. STAIR PRESSURIZZATION DUCT SHOWN
 ON PAGE A7.11 MUST BE A MINIMUM 2
 HOUR RATED SHAFT.
  
 43. WHAT ACTIVITIES OCCUR IN OPEN
 AIR COVERED STRUCTURE SHOWN ON PAGE
 A8.11.
  
 44. BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. CERTAIN RESTRICTIONS
 WILL APPLY SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 45. PLEASE EXPLAIN USE OF CARD READERS
 FOR THE BUILDING. WHAT ISSUES DO
 THEY RAISE IF ANY TO EXITING.
  
 46. ALL FIRE DOORS AND WINDOWS TO
 COMPLY WITH NFPA 80, FIRE DOORS AND
 WINDOWS. PLEASE ADD NOTE TO
 DRAWINGS.
  
 47. NO CUTTING OR WELDING OPERATIONS
 TO OCCUR WITHOUT APPROVAL OF THE
 FIRE PREVENTION BUREAU AND COMPLIANCE
 WITH NFPA 51B.
  
 48. ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY WITH 6" HIGH
 LETTERS.
  
 49. ALL ARCHITECURAL TRIM LOCATED
 IN THE FIRE LIMITS SHALL BE
 NON-COMBUSTIBLE.
  
 50. PAGE E0.01 INSERTED UPSIDE DOWN
 IN SET.
  
 51. A SITE PLAN DETAILING ALL EXISTING
 OR NEW FIRE HYDRANTS AND WATER MAINS
 SHALL BE PROVIDED.
  
 52. PLEASE INDICATE EMERGENCY LIGHTING
 FOR LANAI DECK, PAGE E1.03.
  
 53. CLASS B FIRE ALARM CIRCUITS SHOWN
 ON PAGE E8.04. ONLY CLASS A, STYLE D
 OR FULLY ADDRESSABLE FIRE ALARM
 CIRCUITS
 SHALL BE PERMITTED.
  
 54. FIRE ALARM SYSTEM SHALL MEET THE
 SURVIVABILITY REQUIREMENTS OF NFPA 72.
  
 55. NOTE # 40 ON PAGE E8.04 IS
 INCORRECT. LIFE SAFETY CODE 2003
 EDITION SHOULD BE REFERENCED.
  
 56. BUILDING IS TO COMPLY WITH
 SECTON 11-8, LIFE SAFETY CODE, 2003
 EDITION.
  
 57. THE FIREFIGHTER SMOKE MANAGEMENT
 PANEL SHALL PROVIDE A GRAPHIC
 REPRESENTATION OF THE BUILDING. HOA
 SWITCHES WITH NO OVERLAY OF THE
 BUILDING WILL NOT BE ACCEPTABLE.
  
 58. MORE DETAILS REQUIRED ON PROPOSED
 DRYER BOOSTER FANS. SHOWN ON
 ELECTRICAL PAGES.
  
 59. EXIT SIGN SHOWN ON PAGE E2.01
 DIRECTING PERSONS INTO LOADING
 AREA. PLEASE EXPLAIN.
  
 60. EXIT SIGNS APPEAR TO BE MISSING
 ON SOME OF THE ELECTRICAL DRAWINGS.
  
 61. MORE EXIT SIGNS APPEAR TO BE
 NEEDED ON PAGE E2.02.
  
 62. MORE EXIT SIGNS APPEAR TO BE
 NEEDED ON PAGE E2.08.
  
 63. ONLY TWO EXIT SIGNS SHOWN ON
 PAGE E2.11.
  
 64. THE ANTICPATED STACK EFFECT NOTE
 WORDING SHALL BE ADDED TO THE
 MECHANICAL PLANS.
  
 65. FIRE DAMPERS TO COMPLY WITH
 UL 555.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 261 Status N Date 2008-07-28 Cont ID  
Sent By adarroug Date 2008-07-28 Time 12:18 Rev Time 0.00
Received By adarroug Date 2008-07-28 Time 12:18 Sent To Z
Notes
2008-07-28 12:19:18TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 260 Status N Date 2008-07-28 Cont ID  
Sent By adarroug Date 2008-07-28 Time 12:15 Rev Time 0.00
Received By adarroug Date 2008-07-28 Time 12:15 Sent To B
Notes
2008-07-28 12:15:30TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 259 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 13:15 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 13:15 Sent To M
Notes
2008-07-17 13:15:16TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 258 Status N Date 2008-07-16 Cont ID  
Sent By adarroug Date 2008-07-16 Time 15:11 Rev Time 0.00
Received By adarroug Date 2008-07-16 Time 15:11 Sent To M
Notes
2008-07-16 15:11:43TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 257 Status N Date 2008-07-03 Cont ID  
Sent By shill Date 2008-07-03 Time 17:10 Rev Time 0.00
Received By shill Date 2008-07-03 Time 17:10 Sent To E
Notes
2008-07-03 17:11:10TO "DPALMER' DESK/ PER MASTER

Review Stop I INCOMING/PROCESSING
Rev No 256 Status N Date 2008-06-25 Cont ID  
Sent By adarroug Date 2008-06-25 Time 15:51 Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 15:51 Sent To M
Notes
2008-06-25 15:51:44TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 255 Status N Date 2008-06-25 Cont ID  
Sent By adarroug Date 2008-06-25 Time 14:39 Rev Time 0.00
Received By adarroug Date 2008-06-25 Time 14:39 Sent To M
Notes
2008-06-25 14:39:41TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 254 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 15:54 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 15:54 Sent To B
Notes
2008-05-16 15:54:46TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 253 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 15:52 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 15:52 Sent To P
Notes
2008-05-16 15:52:46TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 252 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 14:17 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 14:17 Sent To E
Notes
2008-05-12 14:17:58TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 251 Status N Date 2008-05-06 Cont ID  
Sent By adarroug Date 2008-05-06 Time 14:46 Rev Time 0.00
Received By adarroug Date 2008-05-06 Time 14:18 Sent To M
Notes
2008-05-06 14:47:10TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 250 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 16:40 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 16:40 Sent To M
Notes
2008-05-02 16:41:29TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 249 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 12:52 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 12:52 Sent To B
Notes
2008-05-02 12:52:31TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 248 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 14:35 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 14:35 Sent To ENG
Notes
2008-04-04 14:36:10TO "ENG" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 247 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 14:31 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 14:31 Sent To P
Notes
2008-04-04 14:31:55TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 246 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 15:27 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 15:27 Sent To M
Notes
2008-03-13 15:28:15TO "M" BOX/2 SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 245 Status N Date 2008-03-12 Cont ID  
Sent By adarroug Date 2008-03-12 Time 09:16 Rev Time 0.00
Received By adarroug Date 2008-03-12 Time 09:16 Sent To M
Notes
2008-03-12 09:17:07TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 244 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 08:25 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 08:25 Sent To FIRE
Notes
2008-03-06 08:25:26TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 243 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 12:45 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 12:45 Sent To E
Notes
2008-02-19 12:46:15TO "E" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 242 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 12:45 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 12:45 Sent To B
Notes
2008-02-19 12:45:27TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 241 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 11:21 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 11:21 Sent To M
Notes
2008-02-19 11:21:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 240 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 11:11 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 11:11 Sent To E
Notes
2008-02-19 11:11:53TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 239 Status N Date 2008-02-05 Cont ID  
Sent By shill Date 2008-02-05 Time 10:10 Rev Time 0.00
Received By shill Date 2008-02-05 Time 10:10 Sent To B
Notes
2008-02-05 10:10:41TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 238 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 15:31 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 15:31 Sent To B
Notes
2008-01-29 15:32:01TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 237 Status N Date 2008-01-22 Cont ID  
Sent By adarroug Date 2008-01-22 Time 14:06 Rev Time 0.00
Received By adarroug Date 2008-01-22 Time 14:06 Sent To B
Notes
2008-01-22 14:07:19TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 236 Status N Date 2008-01-22 Cont ID  
Sent By adarroug Date 2008-01-22 Time 10:20 Rev Time 0.00
Received By adarroug Date 2008-01-22 Time 10:20 Sent To M
Notes
2008-01-22 10:20:43TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 235 Status N Date 2008-01-18 Cont ID  
Sent By adarroug Date 2008-01-18 Time 10:49 Rev Time 0.00
Received By adarroug Date 2008-01-18 Time 10:49 Sent To E
Notes
2008-01-18 10:50:13TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 234 Status N Date 2008-01-14 Cont ID  
Sent By adarroug Date 2008-01-14 Time 08:52 Rev Time 0.00
Received By adarroug Date 2008-01-14 Time 08:52 Sent To B
Notes
2008-01-14 08:53:03TO "MJACOBS" DESK/SUBMITAL

Review Stop I INCOMING/PROCESSING
Rev No 233 Status N Date 2008-01-14 Cont ID  
Sent By adarroug Date 2008-01-14 Time 08:44 Rev Time 0.00
Received By adarroug Date 2008-01-14 Time 08:44 Sent To E
Notes
2008-01-14 08:47:03TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 232 Status N Date 2007-12-21 Cont ID  
Sent By mmiller Date 2007-12-21 Time 16:50 Rev Time 0.00
Received By mmiller Date 2007-12-21 Time 16:50 Sent To  
Notes
2007-12-21 16:51:10SENT TO COMMERICAL BOARD #32 MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 231 Status N Date 2007-12-19 Cont ID  
Sent By adarroug Date 2007-12-19 Time 13:16 Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 13:16 Sent To B
Notes
2007-12-19 13:16:32TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 230 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 09:59 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 09:59 Sent To B
Notes
2007-12-10 09:59:36TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 229 Status N Date 2007-12-03 Cont ID  
Sent By adarroug Date 2007-12-03 Time 13:15 Rev Time 0.00
Received By adarroug Date 2007-12-03 Time 13:15 Sent To B
Notes
2007-12-03 13:15:49TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 228 Status N Date 2007-11-30 Cont ID  
Sent By adarroug Date 2007-11-30 Time 16:29 Rev Time 0.00
Received By adarroug Date 2007-11-30 Time 16:29 Sent To  
Notes
2007-11-30 16:29:33WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 227 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 11:16 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 11:16 Sent To  
Notes
2007-11-28 11:17:04WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 226 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 09:37 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 09:37 Sent To M
Notes
2007-11-16 09:38:45TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 225 Status N Date 2007-11-16 Cont ID  
Sent By adarroug Date 2007-11-16 Time 09:34 Rev Time 0.00
Received By adarroug Date 2007-11-16 Time 09:34 Sent To B
Notes
2007-11-16 09:35:37TO "BTROBAUG" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 224 Status N Date 2007-11-13 Cont ID  
Sent By adarroug Date 2007-11-13 Time 10:54 Rev Time 0.00
Received By adarroug Date 2007-11-13 Time 10:54 Sent To B
Notes
2007-11-13 10:54:54TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 223 Status N Date 2007-11-05 Cont ID  
Sent By adarroug Date 2007-11-05 Time 16:03 Rev Time 0.00
Received By adarroug Date 2007-11-05 Time 16:03 Sent To M
Notes
2007-11-05 16:03:37TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 222 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 11:40 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 11:40 Sent To B
Notes
2007-10-30 11:40:36TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 221 Status N Date 2007-10-29 Cont ID  
Sent By adarroug Date 2007-10-29 Time 16:46 Rev Time 0.00
Received By adarroug Date 2007-10-29 Time 16:46 Sent To B
Notes
2007-10-29 16:46:38TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 220 Status N Date 2007-10-18 Cont ID  
Sent By adarroug Date 2007-10-18 Time 16:39 Rev Time 0.00
Received By adarroug Date 2007-10-18 Time 16:39 Sent To B
Notes
2007-10-18 16:39:48TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 219 Status N Date 2007-10-18 Cont ID  
Sent By adarroug Date 2007-10-18 Time 10:33 Rev Time 0.00
Received By adarroug Date 2007-10-18 Time 10:33 Sent To M
Notes
2007-10-18 10:33:28TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 218 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 16:20 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 16:20 Sent To B
Notes
2007-10-15 16:21:08TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 217 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 14:56 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 14:56 Sent To B
Notes
2007-10-15 14:57:13TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 216 Status N Date 2007-10-09 Cont ID  
Sent By adarroug Date 2007-10-09 Time 11:20 Rev Time 0.00
Received By adarroug Date 2007-10-09 Time 11:20 Sent To M
Notes
2007-10-09 11:21:14TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 215 Status N Date 2007-10-09 Cont ID  
Sent By adarroug Date 2007-10-09 Time 09:36 Rev Time 0.00
Received By adarroug Date 2007-10-09 Time 09:36 Sent To B
Notes
2007-10-09 09:37:22TO "MJACOBS" DESK/ 2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 214 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 08:58 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 08:58 Sent To B
Notes
2007-10-03 08:59:14TO "MJACOBS" DESK/5 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 213 Status N Date 2007-09-25 Cont ID  
Sent By adarroug Date 2007-09-25 Time 09:35 Rev Time 0.00
Received By adarroug Date 2007-09-25 Time 09:35 Sent To B
Notes
2007-09-25 09:35:36TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 212 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 17:00 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 17:00 Sent To M
Notes
2007-09-18 17:01:01TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 211 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 09:59 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 09:59 Sent To B
Notes
2007-09-18 10:00:08TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 210 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 08:46 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 08:46 Sent To B
Notes
2007-09-07 08:47:14TO "MJACOBS" DESK/6 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 209 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 16:18 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 16:18 Sent To B
Notes
2007-09-06 16:19:13TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 208 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 09:26 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 09:26 Sent To B
Notes
2007-08-29 09:26:34TO "MJACOBS" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 207 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 08:10 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 08:10 Sent To B
Notes
2007-08-28 08:10:33TO "MJACOBS" DESK/6 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 206 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 15:28 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 15:28 Sent To M
Notes
2007-08-27 15:28:44TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 205 Status N Date 2007-08-15 Cont ID  
Sent By adarroug Date 2007-08-15 Time 13:54 Rev Time 0.00
Received By adarroug Date 2007-08-15 Time 13:54 Sent To B
Notes
2007-08-15 13:54:25TO "MJACOBS' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 204 Status N Date 2007-08-15 Cont ID  
Sent By adarroug Date 2007-08-15 Time 13:51 Rev Time 0.00
Received By adarroug Date 2007-08-15 Time 13:51 Sent To M
Notes
2007-08-15 13:51:49TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 203 Status N Date 2007-08-13 Cont ID  
Sent By adarroug Date 2007-08-13 Time 14:05 Rev Time 0.00
Received By adarroug Date 2007-08-13 Time 14:05 Sent To B
Notes
2007-08-13 14:06:05TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 202 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 08:18 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 08:17 Sent To B
Notes
2007-08-10 08:18:17TO MJ'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 201 Status N Date 2007-08-09 Cont ID  
Sent By dpalmer Date 2007-08-09 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2007-08-09 Time 12:46 Sent To B
Notes
2007-08-09 12:46:324-BLDG SUBMITTALS TO MJ'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 200 Status N Date 2007-08-07 Cont ID  
Sent By dpalmer Date 2007-08-07 Time 20:10 Rev Time 0.00
Received By dpalmer Date 2007-08-07 Time 20:10 Sent To M
Notes
2007-08-07 20:11:22MECH REVISIONS TO RON R DESK.

Review Stop I INCOMING/PROCESSING
Rev No 199 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 16:24 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 16:24 Sent To B
Notes
2007-08-03 16:25:30TO "MJACOBS" DESK/4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 198 Status N Date 2007-07-28 Cont ID  
Sent By adarroug Date 2007-07-28 Time 12:39 Rev Time 0.00
Received By adarroug Date 2007-07-28 Time 12:39 Sent To B
Notes
2007-07-28 12:39:53TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 197 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 14:44 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 14:44 Sent To M
Notes
2007-07-27 14:44:44TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 196 Status N Date 2007-07-23 Cont ID  
Sent By adarroug Date 2007-07-23 Time 10:31 Rev Time 0.00
Received By adarroug Date 2007-07-23 Time 10:31 Sent To B
Notes
2007-07-23 10:31:42TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 195 Status N Date 2007-07-16 Cont ID  
Sent By adarroug Date 2007-07-16 Time 11:24 Rev Time 0.00
Received By adarroug Date 2007-07-16 Time 11:24 Sent To M
Notes
2007-07-16 11:25:06TO "RREGEIRO" DESK

Review Stop I INCOMING/PROCESSING
Rev No 194 Status N Date 2007-07-13 Cont ID  
Sent By adarroug Date 2007-07-13 Time 16:42 Rev Time 0.00
Received By adarroug Date 2007-07-13 Time 16:42 Sent To B
Notes
2007-07-13 16:42:51TO "MJACOBS' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 193 Status N Date 2007-07-13 Cont ID  
Sent By adarroug Date 2007-07-13 Time 11:38 Rev Time 0.00
Received By adarroug Date 2007-07-13 Time 11:38 Sent To  
Notes
2007-07-27 11:43:46TO "COMM" BD#14
2007-07-13 11:38:23WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 192 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 16:57 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 16:57 Sent To  
Notes
2007-07-24 08:45:38TO "COMM" BD#6/PLANS ON RACK--6 ROLLS
2007-07-06 16:57:49WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 191 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 16:32 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 16:32 Sent To B
Notes
2007-07-06 16:32:57TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 190 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 16:26 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 16:26 Sent To FIRE
Notes
2007-07-06 16:27:19TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 189 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 15:47 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 15:47 Sent To B
Notes
2007-07-03 15:48:15TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 188 Status N Date 2007-06-29 Cont ID  
Sent By adarroug Date 2007-06-29 Time 09:28 Rev Time 0.00
Received By adarroug Date 2007-06-29 Time 09:28 Sent To B
Notes
2007-06-29 09:28:51TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 187 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-28 Time 15:45 Rev Time 0.00
Received By adarroug Date 2007-06-28 Time 15:45 Sent To M
Notes
2007-06-28 15:46:09TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 186 Status N Date 2007-06-27 Cont ID  
Sent By adarroug Date 2007-06-27 Time 13:17 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 13:17 Sent To B
Notes
2007-06-27 13:18:35TO "MJACOBS" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 185 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 17:39 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 17:39 Sent To B
Notes
2007-06-24 17:39:52TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 184 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 14:48 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 14:48 Sent To B
Notes
2007-06-24 14:48:33TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 183 Status N Date 2007-06-22 Cont ID  
Sent By adarroug Date 2007-06-22 Time 09:34 Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 09:34 Sent To B
Notes
2007-06-22 09:35:15TO "MJACOBS" DESK/3 SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 182 Status N Date 2007-06-21 Cont ID  
Sent By adarroug Date 2007-06-21 Time 15:30 Rev Time 0.00
Received By adarroug Date 2007-06-21 Time 15:30 Sent To M
Notes
2007-06-21 15:31:04TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 181 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 14:38 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 14:38 Sent To B
Notes
2007-06-19 14:38:25TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 180 Status N Date 2007-06-15 Cont ID  
Sent By adarroug Date 2007-06-15 Time 16:36 Rev Time 0.00
Received By adarroug Date 2007-06-15 Time 16:36 Sent To B
Notes
2007-06-15 16:37:19TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 179 Status N Date 2007-06-13 Cont ID  
Sent By adarroug Date 2007-06-13 Time 16:41 Rev Time 0.00
Received By adarroug Date 2007-06-13 Time 16:41 Sent To B
Notes
2007-06-13 16:41:28TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 178 Status N Date 2007-06-13 Cont ID  
Sent By adarroug Date 2007-06-13 Time 16:40 Rev Time 0.00
Received By adarroug Date 2007-06-13 Time 16:40 Sent To M
Notes
2007-06-13 16:40:56TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 177 Status N Date 2007-06-12 Cont ID  
Sent By adarroug Date 2007-06-12 Time 08:55 Rev Time 0.00
Received By adarroug Date 2007-06-12 Time 08:55 Sent To M
Notes
2007-06-12 08:55:55TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 176 Status N Date 2007-06-08 Cont ID  
Sent By adarroug Date 2007-06-08 Time 16:35 Rev Time 0.00
Received By adarroug Date 2007-06-08 Time 16:35 Sent To B
Notes
2007-06-08 16:35:39TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 175 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 16:44 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 16:44 Sent To B
Notes
2007-06-07 16:45:01TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 174 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 10:10 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 10:10 Sent To E
Notes
2007-06-07 10:10:24TO "DPALMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 173 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 10:09 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 10:09 Sent To B
Notes
2007-06-07 10:09:35TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 172 Status N Date 2007-06-06 Cont ID  
Sent By adarroug Date 2007-06-06 Time 08:21 Rev Time 0.00
Received By adarroug Date 2007-06-06 Time 08:21 Sent To B
Notes
2007-06-06 08:21:38TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 171 Status N Date 2007-06-04 Cont ID  
Sent By adarroug Date 2007-06-04 Time 13:08 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 13:08 Sent To B
Notes
2007-06-04 13:10:01TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 170 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 15:03 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 15:03 Sent To B
Notes
2007-06-01 15:03:48TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 169 Status N Date 2007-05-30 Cont ID  
Sent By adarroug Date 2007-05-30 Time 10:01 Rev Time 0.00
Received By adarroug Date 2007-05-30 Time 10:01 Sent To B
Notes
2007-05-30 10:01:33TO "MJACOBS" DESK/4 SUBMATTALS

Review Stop I INCOMING/PROCESSING
Rev No 168 Status N Date 2007-05-25 Cont ID  
Sent By adarroug Date 2007-05-25 Time 09:07 Rev Time 0.00
Received By adarroug Date 2007-05-25 Time 09:07 Sent To B
Notes
2007-05-25 09:07:41TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 167 Status N Date 2007-05-24 Cont ID  
Sent By adarroug Date 2007-05-24 Time 11:16 Rev Time 0.00
Received By adarroug Date 2007-05-24 Time 11:16 Sent To B
Notes
2007-05-24 11:17:00TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 166 Status N Date 2007-05-24 Cont ID  
Sent By adarroug Date 2007-05-24 Time 10:08 Rev Time 0.00
Received By adarroug Date 2007-05-24 Time 10:08 Sent To B
Notes
2007-05-24 10:09:02TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 165 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 09:12 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 09:12 Sent To B
Notes
2007-05-18 09:12:35TO "MJACOB" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 164 Status N Date 2007-05-16 Cont ID  
Sent By adarroug Date 2007-05-16 Time 11:43 Rev Time 0.00
Received By adarroug Date 2007-05-16 Time 11:43 Sent To B
Notes
2007-05-16 11:43:46TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 163 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 14:24 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 14:24 Sent To B
Notes
2007-05-15 14:24:40TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 162 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 13:57 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 13:57 Sent To B
Notes
2007-05-10 13:57:51TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 161 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 09:21 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 09:21 Sent To B
Notes
2007-05-08 09:21:41TO "MJACOBS" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 160 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 11:45 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 11:45 Sent To M
Notes
2007-05-04 11:46:12TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 159 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 11:44 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 11:44 Sent To B
Notes
2007-05-04 11:44:59TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 158 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 13:10 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 13:10 Sent To B
Notes
2007-05-02 13:11:15TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 157 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 13:09 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 13:09 Sent To FIRE
Notes
2007-05-02 13:09:40TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 156 Status N Date 2007-05-01 Cont ID  
Sent By adarroug Date 2007-05-01 Time 16:38 Rev Time 0.00
Received By adarroug Date 2007-05-01 Time 16:38 Sent To B
Notes
2007-05-01 16:38:57TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 155 Status N Date 2007-04-24 Cont ID  
Sent By adarroug Date 2007-04-24 Time 15:09 Rev Time 0.00
Received By adarroug Date 2007-04-24 Time 15:09 Sent To B
Notes
2007-04-24 15:09:35TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 154 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 14:12 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 14:12 Sent To P
Notes
2007-04-23 14:12:58TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 153 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 14:11 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 14:11 Sent To B
Notes
2007-04-23 14:12:02TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 152 Status N Date 2007-04-17 Cont ID  
Sent By adarroug Date 2007-04-17 Time 14:16 Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 14:15 Sent To E
Notes
2007-04-17 14:16:35TO "DPALMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 151 Status N Date 2007-04-17 Cont ID  
Sent By adarroug Date 2007-04-17 Time 14:13 Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 14:13 Sent To B
Notes
2007-04-17 14:13:44TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 150 Status N Date 2007-04-17 Cont ID  
Sent By adarroug Date 2007-04-17 Time 14:11 Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 14:11 Sent To FIRE
Notes
2007-04-17 14:11:34TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 149 Status N Date 2007-04-13 Cont ID  
Sent By adarroug Date 2007-04-13 Time 15:00 Rev Time 0.00
Received By adarroug Date 2007-04-13 Time 15:00 Sent To B
Notes
2007-04-13 15:01:19TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 148 Status N Date 2007-04-10 Cont ID  
Sent By adarroug Date 2007-04-10 Time 16:42 Rev Time 0.00
Received By adarroug Date 2007-04-10 Time 16:42 Sent To M
Notes
2007-04-10 16:43:05TO "M" BOX/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 147 Status N Date 2007-04-10 Cont ID  
Sent By adarroug Date 2007-04-10 Time 16:32 Rev Time 0.00
Received By adarroug Date 2007-04-10 Time 16:32 Sent To B
Notes
2007-04-10 16:33:19TO "MJACOBS" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 146 Status N Date 2007-04-04 Cont ID  
Sent By spalmer Date 2007-04-04 Time 17:22 Rev Time 0.00
Received By spalmer Date 2007-04-04 Time 17:22 Sent To B
Notes
2007-04-04 17:22:56TO MYRON JACOBS

Review Stop I INCOMING/PROCESSING
Rev No 145 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 18:08 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 18:08 Sent To B
Notes
2007-04-02 18:08:54SIX SUBMITTALS TO MYRON JACOBS DESK

Review Stop I INCOMING/PROCESSING
Rev No 144 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 20:04 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 20:04 Sent To B
Notes
2007-03-29 20:04:21SUBMITTAL TO MJ'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 143 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 20:04 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 20:04 Sent To B
Notes
2007-03-29 20:04:48SUBMITTAL TO MJ'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 142 Status N Date 2007-03-27 Cont ID  
Sent By spalmer Date 2007-03-27 Time 17:45 Rev Time 0.00
Received By spalmer Date 2007-03-27 Time 17:45 Sent To B
Notes
2007-03-27 17:46:09SIX SUBMITTALS TO MYRON JACOBS

Review Stop I INCOMING/PROCESSING
Rev No 141 Status N Date 2007-03-25 Cont ID  
Sent By adarroug Date 2007-03-25 Time 12:38 Rev Time 0.00
Received By adarroug Date 2007-03-25 Time 12:38 Sent To B
Notes
2007-03-25 12:38:44TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 140 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 16:28 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 16:28 Sent To B
Notes
2007-03-23 16:29:27TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 139 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 16:27 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 16:27 Sent To B
Notes
2007-03-23 16:27:44TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 138 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 16:21 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 16:21 Sent To B
Notes
2007-03-23 16:23:48TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 137 Status N Date 2007-03-21 Cont ID  
Sent By adarroug Date 2007-03-21 Time 11:54 Rev Time 0.00
Received By adarroug Date 2007-03-21 Time 11:54 Sent To B
Notes
2007-03-21 11:55:20TO "MJACOBS" DESK/4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 136 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 14:42 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 14:42 Sent To P
Notes
2007-03-16 14:42:52TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 135 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 08:50 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 08:50 Sent To B
Notes
2007-03-16 08:50:35TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 134 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 08:24 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 08:23 Sent To B
Notes
2007-03-16 08:25:01TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 133 Status N Date 2007-03-15 Cont ID  
Sent By adarroug Date 2007-03-15 Time 15:59 Rev Time 0.00
Received By adarroug Date 2007-03-15 Time 15:59 Sent To B
Notes
2007-03-15 15:59:59TO "MJACOBS' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 132 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 15:21 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 15:20 Sent To B
Notes
2007-03-14 15:21:22TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 131 Status N Date 2007-03-12 Cont ID  
Sent By adarroug Date 2007-03-12 Time 08:21 Rev Time 0.00
Received By adarroug Date 2007-03-12 Time 08:21 Sent To B
Notes
2007-03-12 08:21:43TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 130 Status N Date 2007-03-08 Cont ID  
Sent By adarroug Date 2007-03-08 Time 15:09 Rev Time 0.00
Received By adarroug Date 2007-03-08 Time 15:09 Sent To B
Notes
2007-03-08 15:10:09TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 129 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 14:32 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 14:32 Sent To B
Notes
2007-03-06 14:33:07TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 128 Status N Date 2007-03-03 Cont ID  
Sent By adarroug Date 2007-03-03 Time 16:08 Rev Time 0.00
Received By adarroug Date 2007-03-03 Time 16:08 Sent To B
Notes
2007-03-03 16:08:22TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 127 Status N Date 2007-02-28 Cont ID  
Sent By adarroug Date 2007-02-28 Time 15:53 Rev Time 0.00
Received By adarroug Date 2007-02-28 Time 15:53 Sent To B
Notes
2007-02-28 15:53:26TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 126 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 17:19 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 17:19 Sent To B
Notes
2007-02-27 17:19:54TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 125 Status N Date 2007-02-26 Cont ID  
Sent By adarroug Date 2007-02-26 Time 09:35 Rev Time 0.00
Received By adarroug Date 2007-02-26 Time 09:35 Sent To B
Notes
2007-02-26 09:36:14TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 124 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 11:39 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 11:39 Sent To B
Notes
2007-02-22 11:39:54TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 123 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 13:34 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 13:34 Sent To P
Notes
2007-02-15 13:34:49TO "P" BOX/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 122 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 13:33 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 13:33 Sent To B
Notes
2007-02-15 13:33:44TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 121 Status N Date 2007-02-13 Cont ID  
Sent By adarroug Date 2007-02-13 Time 09:07 Rev Time 0.00
Received By adarroug Date 2007-02-13 Time 09:07 Sent To B
Notes
2007-02-13 09:09:16TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 120 Status N Date 2007-02-09 Cont ID  
Sent By adarroug Date 2007-02-09 Time 09:53 Rev Time 0.00
Received By adarroug Date 2007-02-09 Time 09:53 Sent To B
Notes
2007-02-09 09:53:28TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 119 Status N Date 2007-02-06 Cont ID  
Sent By adarroug Date 2007-02-06 Time 15:59 Rev Time 0.00
Received By adarroug Date 2007-02-06 Time 15:58 Sent To B
Notes
2007-02-06 15:59:29TO "MJACOBS" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 118 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 15:08 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 15:08 Sent To E
Notes
2007-02-02 15:09:20TO "DPALMER" DESK/SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 117 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 15:07 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 15:07 Sent To P
Notes
2007-02-02 15:07:39TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 116 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 15:03 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 15:03 Sent To B
Notes
2007-02-02 15:03:40TO "MJACOBS" DESK/2 SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 115 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 13:46 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 13:46 Sent To B
Notes
2007-01-31 13:47:16TO "MJACOBS" DESK/ 3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 114 Status N Date 2007-01-29 Cont ID  
Sent By adarroug Date 2007-01-29 Time 16:27 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 16:27 Sent To B
Notes
2007-01-29 16:27:40TO "MJACOBS" DESK/ 3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 113 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 13:16 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 13:16 Sent To M
Notes
2007-01-24 13:16:42TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 112 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 13:13 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 13:13 Sent To P
Notes
2007-01-24 13:14:12TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 111 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 11:06 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 11:06 Sent To B
Notes
2007-01-24 11:06:41TO "MJACOBS" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 110 Status N Date 2007-01-23 Cont ID  
Sent By adarroug Date 2007-01-23 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-01-23 Time 10:11 Sent To B
Notes
2007-01-23 10:11:31TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 109 Status N Date 2007-01-19 Cont ID  
Sent By adarroug Date 2007-01-19 Time 08:52 Rev Time 0.00
Received By adarroug Date 2007-01-19 Time 08:51 Sent To B
Notes
2007-01-19 08:52:26TO "MJACOBS" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 108 Status N Date 2007-01-18 Cont ID  
Sent By adarroug Date 2007-01-18 Time 12:42 Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 12:42 Sent To B
Notes
2007-01-18 12:43:09TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 107 Status N Date 2007-01-16 Cont ID  
Sent By adarroug Date 2007-01-16 Time 15:04 Rev Time 0.00
Received By adarroug Date 2007-01-16 Time 15:04 Sent To B
Notes
2007-01-16 15:05:04TO "MJACOBS.COM/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 106 Status N Date 2007-01-11 Cont ID  
Sent By adarroug Date 2007-01-11 Time 13:37 Rev Time 0.00
Received By adarroug Date 2007-01-11 Time 13:37 Sent To  
Notes
2007-01-24 09:00:41TO "COMM" BD#23/PLANS ON RACK--7 ROLLS
2007-01-11 13:38:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 105 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 14:37 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 14:37 Sent To B
Notes
2007-01-09 14:38:01TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 104 Status N Date 2007-01-05 Cont ID  
Sent By adarroug Date 2007-01-05 Time 11:20 Rev Time 0.00
Received By adarroug Date 2007-01-05 Time 11:20 Sent To B
Notes
2007-01-05 11:20:58TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 103 Status N Date 2007-01-03 Cont ID  
Sent By adarroug Date 2007-01-03 Time 11:26 Rev Time 0.00
Received By adarroug Date 2007-01-03 Time 11:26 Sent To B
Notes
2007-01-03 11:26:33TO "MJACOBS" DESK/5 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 102 Status N Date 2007-01-03 Cont ID  
Sent By adarroug Date 2007-01-03 Time 11:23 Rev Time 0.00
Received By adarroug Date 2007-01-03 Time 11:23 Sent To FIRE
Notes
2007-01-03 11:24:30TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 101 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 15:43 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 15:43 Sent To B
Notes
2006-12-27 15:44:14TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 100 Status N Date 2006-12-22 Cont ID  
Sent By adarroug Date 2006-12-22 Time 09:05 Rev Time 0.00
Received By adarroug Date 2006-12-22 Time 09:05 Sent To B
Notes
2006-12-22 09:06:01TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 99 Status N Date 2006-12-16 Cont ID  
Sent By adarroug Date 2006-12-16 Time 16:52 Rev Time 0.00
Received By adarroug Date 2006-12-16 Time 16:52 Sent To B
Notes
2006-12-16 16:53:07TO "MJACOBS" DESK/4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 98 Status N Date 2006-12-16 Cont ID  
Sent By adarroug Date 2006-12-16 Time 16:37 Rev Time 0.00
Received By adarroug Date 2006-12-16 Time 16:37 Sent To B
Notes
2006-12-16 16:37:35TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 97 Status N Date 2006-12-15 Cont ID  
Sent By adarroug Date 2006-12-15 Time 15:17 Rev Time 0.00
Received By adarroug Date 2006-12-15 Time 15:16 Sent To B
Notes
2006-12-15 15:17:21TO "MJACOBS" DESK/7 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 96 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 13:15 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 13:15 Sent To B
Notes
2006-12-04 13:16:02TO "MJACOBS" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 95 Status   Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 18:55 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 18:55 Sent To B
Notes
2006-11-29 18:56:07SENT TO MYRON JACOB'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 94 Status N Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 17:49 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 17:49 Sent To B
Notes
2006-11-29 17:50:21SENT TO MYRON JACOB'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 93 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 15:20 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 15:20 Sent To P
Notes
2006-11-21 15:20:28TO "P" BOX/4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 92 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 15:19 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 15:19 Sent To M
Notes
2006-11-21 15:19:55TO"M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 91 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 15:18 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 15:18 Sent To B
Notes
2006-11-21 15:19:21TO "LMARTINEZ"DESK/7 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 90 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 14:53 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 14:53 Sent To B
Notes
2006-11-21 14:53:54TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 89 Status N Date 2006-11-13 Cont ID  
Sent By adarroug Date 2006-11-13 Time 15:54 Rev Time 0.00
Received By adarroug Date 2006-11-13 Time 15:54 Sent To B
Notes
2006-11-13 15:54:46TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 88 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 16:33 Sent To M
Notes
2006-11-07 16:34:12TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 87 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 09:35 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 09:35 Sent To B
Notes
2006-11-07 09:35:23TO "LMARTINEZ" DESK/6 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 86 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 09:30 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 09:30 Sent To M
Notes
2006-11-07 09:30:49TO "M" BOX/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 85 Status N Date 2006-11-03 Cont ID  
Sent By adarroug Date 2006-11-03 Time 11:01 Rev Time 0.00
Received By adarroug Date 2006-11-03 Time 11:01 Sent To  
Notes
2006-11-03 11:01:52TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 84 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 08:53 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 08:53 Sent To B
Notes
2006-10-27 08:53:49TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 83 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 08:34 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 08:34 Sent To M
Notes
2006-10-27 08:35:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 82 Status N Date 2006-10-26 Cont ID  
Sent By adarroug Date 2006-10-26 Time 14:47 Rev Time 0.00
Received By adarroug Date 2006-10-26 Time 14:47 Sent To B
Notes
2006-10-26 14:48:12TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 81 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 14:17 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 14:17 Sent To B
Notes
2006-10-24 14:18:13TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 80 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 14:17 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 14:17 Sent To  
Notes
2006-10-24 14:17:34TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 79 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 10:00 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 10:00 Sent To B
Notes
2006-10-24 10:00:46TO JERALD SMITH'S DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 78 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 08:39 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 08:39 Sent To B
Notes
2006-10-23 08:40:10TO "LMARTINEZ" DESK/SUBMITTAL--(SHORING FORMWORK AND GC
 LETTER POUR#44)

Review Stop I INCOMING/PROCESSING
Rev No 77 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 16:16 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 16:16 Sent To P
Notes
2006-10-14 16:17:09TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 16:13 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 16:13 Sent To B
Notes
2006-10-14 16:13:35TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 15:10 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 15:10 Sent To M
Notes
2006-10-14 15:10:44TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 74 Status N Date 2006-10-13 Cont ID  
Sent By adarroug Date 2006-10-13 Time 16:23 Rev Time 0.00
Received By adarroug Date 2006-10-13 Time 16:23 Sent To M
Notes
2006-10-13 16:24:37TO "M" BOX/ 4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 73 Status N Date 2006-10-13 Cont ID  
Sent By adarroug Date 2006-10-13 Time 15:25 Rev Time 0.00
Received By adarroug Date 2006-10-13 Time 15:25 Sent To FIRE
Notes
2006-10-13 15:25:45TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2006-10-06 Cont ID  
Sent By adarroug Date 2006-10-06 Time 11:48 Rev Time 0.00
Received By adarroug Date 2006-10-06 Time 11:48 Sent To B
Notes
2006-10-06 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-10-02 Time 10:20 Rev Time 0.00
Received By adarroug Date 2006-10-02 Time 10:20 Sent To E
Notes
2006-10-02 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-10-02 Time 10:19 Rev Time 0.00
Received By adarroug Date 2006-10-02 Time 10:19 Sent To M
Notes
2006-10-02 00:00:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-10-02 Time 10:13 Rev Time 0.00
Received By adarroug Date 2006-10-02 Time 10:13 Sent To P
Notes
2006-10-02 00:00:00TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 68 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-10-02 Time 10:06 Rev Time 0.00
Received By adarroug Date 2006-10-02 Time 10:06 Sent To B
Notes
2006-10-02 00:00:00TO "LMARTINEZ" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2006-09-19 Cont ID  
Sent By adarroug Date 2006-09-19 Time 09:25 Rev Time 0.00
Received By adarroug Date 2006-09-19 Time 09:25 Sent To B
Notes
2006-09-19 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 10:56 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 10:56 Sent To P
Notes
2006-09-12 00:00:00TO "KSTEVENS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 10:53 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 10:53 Sent To P
Notes
2006-09-12 00:00:00TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 10:52 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 10:52 Sent To B
Notes
2006-09-12 00:00:00TO "LMARTINEZ" DESK/4 BLDG SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 15:43 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 15:43 Sent To B
Notes
2006-09-06 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 09:30 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 09:30 Sent To B
Notes
2006-09-06 00:00:00TO "LMARTINEZ" DESK/3 BLDG SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 09:27 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 09:27 Sent To P
Notes
2006-09-06 00:00:00TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 09:24 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 09:24 Sent To M
Notes
2006-09-06 00:00:00TO "M" BOX/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2006-08-26 Cont ID  
Sent By adarroug Date 2006-08-26 Time 16:43 Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 16:43 Sent To B
Notes
2006-08-26 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2006-08-23 Cont ID  
Sent By adarroug Date 2006-08-23 Time 09:00 Rev Time 0.00
Received By adarroug Date 2006-08-23 Time 09:00 Sent To B
Notes
2006-08-23 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 11:39 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 11:39 Sent To B
Notes
2006-08-18 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2006-08-17 Cont ID  
Sent By adarroug Date 2006-08-17 Time 17:14 Rev Time 0.00
Received By adarroug Date 2006-08-17 Time 17:14 Sent To B
Notes
2006-08-17 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 18:12 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 18:12 Sent To B
Notes
2006-08-11 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 10:20 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 10:20 Sent To  
Notes
2006-08-08 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2006-08-04 Cont ID  
Sent By mmiller Date 2006-08-04 Time 14:06 Rev Time 0.00
Received By mmiller Date 2006-08-07 Time 08:19 Sent To B
Notes
2006-08-04 00:00:00SENT TO "LMARTINEZ" DESK

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 15:11 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 15:11 Sent To B
Notes
2006-08-02 00:00:00TO "LMARTINEZ" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 09:43 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 09:43 Sent To B
Notes
2006-08-01 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 13:16 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 13:16 Sent To B
Notes
2006-07-31 00:00:00TO "LMARTINEZ" DESK/6 BLDG SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 13:13 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 13:13 Sent To P
Notes
2006-07-31 00:00:00TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 13:35 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 13:35 Sent To B
Notes
2006-07-27 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2006-07-22 Cont ID  
Sent By adarroug Date 2006-07-22 Time 13:44 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 13:44 Sent To B
Notes
2006-07-22 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 14:42 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 14:42 Sent To B
Notes
2006-07-18 00:00:00TO "LMARTINEZ' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 14:07 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 14:07 Sent To P
Notes
2006-07-14 00:00:00TO "P" BOX/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 13:57 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 13:57 Sent To E
Notes
2006-07-14 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 13:56 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 13:56 Sent To B
Notes
2006-07-14 00:00:00TO "LMARTINEZ" DESK/3 BLDG SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2006-07-06 Cont ID  
Sent By adarroug Date 2006-07-06 Time 15:20 Rev Time 0.00
Received By adarroug Date 2006-07-06 Time 15:20 Sent To B
Notes
2006-07-06 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 14:45 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 14:45 Sent To M
Notes
2006-06-29 00:00:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 14:45 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 14:45 Sent To B
Notes
2006-06-29 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 14:44 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 14:44 Sent To P
Notes
2006-06-29 00:00:00TO "P" BOX/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 13:40 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 13:40 Sent To B
Notes
2006-07-06 00:00:006/23/06-REV TO "COMM" BD#29/PLANS ON
 RACK
2006-06-23 00:00:00 
  
  
  
  
 TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 11:52 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 11:52 Sent To B
Notes
2006-06-22 00:00:00TO "LMARTINEZ" DESK/4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 16:42 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 16:42 Sent To B
Notes
2006-06-21 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 13:45 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 13:45 Sent To E
Notes
2006-06-19 00:00:00TO "DPALMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 13:31 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 13:31 Sent To B
Notes
2006-06-19 00:00:00TO "LMARTINEZ" DESK/7 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 13:29 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 13:29 Sent To M
Notes
2006-06-19 00:00:00TO "M" BOX/5 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 13:26 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 13:26 Sent To P
Notes
2006-06-19 00:00:00TO "P" BOX/12 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 13:21 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 13:21 Sent To B
Notes
2006-06-14 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 14:20 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 14:20 Sent To P
Notes
2006-06-09 00:00:00TO "P" BOX/7 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2006-06-09 Cont ID  
Sent By adarroug Date 2006-06-09 Time 14:02 Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 14:02 Sent To B
Notes
2006-06-09 00:00:00TO "LMARTINEZ' DESK/8 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 18:00 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 18:00 Sent To B
Notes
2006-06-07 00:00:00TO "LMARTINEZ' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2006-06-02 Cont ID  
Sent By adarroug Date 2006-06-02 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-06-02 Time 16:39 Sent To B
Notes
2006-06-02 00:00:00TO "LMARTINEZ' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2006-05-27 Cont ID  
Sent By adarroug Date 2006-05-27 Time 13:15 Rev Time 0.00
Received By adarroug Date 2006-05-27 Time 13:15 Sent To B
Notes
2006-05-27 00:00:00TO "LMARTINEZ' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2006-05-23 Cont ID  
Sent By adarroug Date 2006-05-23 Time 15:34 Rev Time 0.00
Received By adarroug Date 2006-05-23 Time 15:34 Sent To B
Notes
2006-05-23 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2006-05-19 Cont ID  
Sent By adarroug Date 2006-05-19 Time 11:06 Rev Time 0.00
Received By adarroug Date 2006-05-19 Time 11:06 Sent To B
Notes
2006-05-19 00:00:00TO "LMARTINEZ' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2006-05-19 Cont ID  
Sent By adarroug Date 2006-05-19 Time 10:25 Rev Time 0.00
Received By adarroug Date 2006-05-19 Time 10:25 Sent To M
Notes
2006-05-19 00:00:00TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2006-05-19 Cont ID  
Sent By adarroug Date 2006-05-19 Time 10:23 Rev Time 0.00
Received By adarroug Date 2006-05-19 Time 10:23 Sent To B
Notes
2006-05-19 00:00:00TO "LMARTINEZ' DESK/6 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2006-05-15 Cont ID  
Sent By adarroug Date 2006-05-15 Time 11:34 Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 11:34 Sent To B
Notes
2006-05-15 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2006-05-12 Cont ID  
Sent By adarroug Date 2006-05-12 Time 08:46 Rev Time 0.00
Received By adarroug Date 2006-05-12 Time 08:46 Sent To B
Notes
2006-05-12 00:00:00TO "LMARTINEZ" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2006-05-12 Cont ID  
Sent By adarroug Date 2006-05-12 Time 08:39 Rev Time 0.00
Received By adarroug Date 2006-05-12 Time 08:39 Sent To B
Notes
2006-05-12 00:00:00TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 13:19 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 13:19 Sent To P
Notes
2006-05-11 00:00:00TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 13:16 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 13:16 Sent To B
Notes
2006-05-11 00:00:00TO "LMARTINEZ" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-05-03 Cont ID  
Sent By adarroug Date 2006-05-03 Time 12:03 Rev Time 0.00
Received By adarroug Date 2006-05-03 Time 12:03 Sent To B
Notes
2006-05-03 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 15:27 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 15:27 Sent To B
Notes
2006-05-01 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-05-01 Cont ID  
Sent By adarroug Date 2006-05-01 Time 09:30 Rev Time 0.00
Received By adarroug Date 2006-05-01 Time 09:30 Sent To B
Notes
2006-05-01 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-04-29 Cont ID  
Sent By adarroug Date 2006-04-29 Time 13:47 Rev Time 0.00
Received By adarroug Date 2006-04-29 Time 13:47 Sent To B
Notes
2006-06-06 00:00:00TO "COMM" BD#32/PLANS ON RACK
2006-05-31 00:00:00WAITING FOR "COMM" BD-REV--ROLLS IN
 INCOMING
2006-04-29 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-04-19 Cont ID  
Sent By adarroug Date 2006-04-19 Time 14:15 Rev Time 0.00
Received By adarroug Date 2006-04-19 Time 14:15 Sent To B
Notes
2006-04-19 00:00:00TO "LMARTINEZ" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-04-17 Cont ID  
Sent By adarroug Date 2006-04-17 Time 12:48 Rev Time 0.00
Received By adarroug Date 2006-04-17 Time 12:48 Sent To B
Notes
2006-04-17 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-04-14 Cont ID  
Sent By adarroug Date 2006-04-14 Time 11:24 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 11:24 Sent To B
Notes
2006-04-14 00:00:00TO "LMARTINEZ" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-04-06 Cont ID  
Sent By adarroug Date 2006-04-06 Time 15:39 Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 15:39 Sent To B
Notes
2006-04-06 00:00:00TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-03 Cont ID  
Sent By adarroug Date 2006-04-03 Time 14:57 Rev Time 0.00
Received By adarroug Date 2006-04-03 Time 14:57 Sent To B
Notes
2006-04-03 00:00:00TO "LMARTINEZ" DESK/40 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-01-31 Cont ID  
Sent By adarroug Date 2006-01-31 Time 14:32 Rev Time 0.00
Received By adarroug Date 2006-01-31 Time 14:32 Sent To  
Notes
2006-01-31 00:00:00TO "COMM" BD #7 WITH PLANS IN REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-11-28 Cont ID  
Sent By adarroug Date 2005-11-28 Time 10:01 Rev Time 0.00
Received By adarroug Date 2005-11-28 Time 10:01 Sent To  
Notes
2005-12-27 00:00:00TO "COMM" BD#7
2005-11-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 10:03 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 10:03 Sent To Z
Notes
2005-10-19 00:00:00TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 15:16 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 15:16 Sent To  
Notes
2005-08-08 00:00:00TO "COMM" BD#38/PLANS ON RACK
2005-08-03 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-11 Cont ID  
Sent By adarroug Date 2005-03-11 Time 15:20 Rev Time 0.00
Received By adarroug Date 2005-03-11 Time 15:20 Sent To  
Notes
2005-03-11 00:00:00TO "COMM" BD#40/"COMM" RACK, 12 ROLLS
 "SEE FRONT SCREEN NOTES"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-02-24 Cont ID  
Sent By adarroug Date 2005-02-24 Time 08:55 Rev Time 0.00
Received By adarroug Date 2005-02-24 Time 08:22 Sent To  
Notes
2005-02-24 00:00:00TO "COMM" BD#18/
 "COMM" RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-28 Cont ID  
Sent By mjacobs Date 2005-01-28 Time 15:00 Rev Time 0.00
Received By rbrown Date 2004-12-07 Time 13:32 Sent To  
Notes
2004-12-07 00:00:00SENT TO COMM BD#27 :PLANS ON RACK.

Review Stop M MECHANICAL (A/C)
Rev No 74 Status P Date 2008-08-05 Cont ID  
Sent By rregueir Date 2008-08-05 Time 08:19 Rev Time 0.00
Received By rregueir Date 2008-08-05 Time 08:18 Sent To P
Notes
2008-08-05 08:19:438X11 REVISION FOR DEEP TRAP/PRIMER IN GARAGE FOR WH
 OVERFLOW.

Review Stop M MECHANICAL (A/C)
Rev No 73 Status P Date 2008-08-04 Cont ID  
Sent By rregueir Date 2008-08-04 Time 16:13 Rev Time 0.00
Received By rregueir Date 2008-08-04 Time 15:26 Sent To PC
Notes
2008-08-04 16:12:58REVISION 27 PP: M1.01 THRU M1.09, M1.14, M2.33, M3.02,
 M5.03

Review Stop M MECHANICAL (A/C)
Rev No 72 Status P Date 2008-07-15 Cont ID  
Sent By rregueir Date 2008-07-15 Time 10:51 Rev Time 0.00
Received By rregueir Date 2008-07-15 Time 10:04 Sent To PC
Notes
2008-07-15 10:32:05REVISION #26 PAGES M1.13, M2.33, M3.02, M3.03, M6.01

Review Stop M MECHANICAL (A/C)
Rev No 71 Status P Date 2008-05-21 Cont ID  
Sent By rregueir Date 2008-05-21 Time 14:40 Rev Time 0.00
Received By rregueir Date 2008-05-21 Time 14:40 Sent To PC
Notes
2008-05-21 14:40:42SUBMITTAL # 15051.01.01 - STARTERS FOR HVAC PUMPS

Review Stop M MECHANICAL (A/C)
Rev No 70 Status P Date 2008-05-21 Cont ID  
Sent By rregueir Date 2008-05-21 Time 14:21 Rev Time 0.00
Received By rregueir Date 2008-05-21 Time 14:20 Sent To PC
Notes
2008-05-21 14:21:17REV.25 PAGES: M1.14, M2.12, M2.33, M2.35

Review Stop M MECHANICAL (A/C)
Rev No 69 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hmoser Date 2008-03-20 Time 18:58 Sent To E
Notes
2008-03-20 19:09:09SUBMITTAL 15930.01- STATIC PRESSURE SENSOR.

Review Stop M MECHANICAL (A/C)
Rev No 68 Status P Date 2008-03-20 Cont ID  
Sent By hmoser Date 2008-03-20 Time 18:56 Rev Time 0.00
Received By hmoser Date 2008-03-20 Time 18:56 Sent To  
Notes
2008-03-20 18:58:27SUBMITTAL 15762.02.05 TRANE HEAT PUMP UNITS-1,2,3

Review Stop M MECHANICAL (A/C)
Rev No 67 Status P Date 2008-03-20 Cont ID  
Sent By hmoser Date 2008-03-20 Time 18:41 Rev Time 0.00
Received By hmoser Date 2008-03-20 Time 18:40 Sent To  
Notes
2008-03-20 18:42:48SUBMITTAL 23 MECHANICAL SMOKE ZONE.

Review Stop M MECHANICAL (A/C)
Rev No 66 Status P Date 2008-03-04 Cont ID  
Sent By hmoser Date 2008-03-04 Time 14:48 Rev Time 0.00
Received By hmoser Date 2008-03-04 Time 14:48 Sent To  
Notes
2008-03-04 14:49:35SUBMITTAL # 15815.13.01 WALL CAPS

Review Stop M MECHANICAL (A/C)
Rev No 65 Status P Date 2008-03-04 Cont ID  
Sent By rregueir Date 2008-03-04 Time 07:52 Rev Time 0.00
Received By rregueir Date 2008-03-03 Time 18:00 Sent To PC
Notes
2008-03-04 07:52:29REV.22 PP: M2.01, M2.07, M2.18, M2.29, M2.30, M2.32C,
 M2.32D, M5.01, M6.03

Review Stop M MECHANICAL (A/C)
Rev No 64 Status P Date 2008-03-03 Cont ID  
Sent By rregueir Date 2008-03-03 Time 17:49 Rev Time 0.00
Received By rregueir Date 2008-02-26 Time 08:06 Sent To PC
Notes
2008-03-03 17:48:50REV 20 PP: M2.05, M2.18, M2.32, M2.32F, M3.04, M5.01

Review Stop M MECHANICAL (A/C)
Rev No 63 Status P Date 2008-02-25 Cont ID  
Sent By rregueir Date 2008-02-25 Time 17:48 Rev Time 0.00
Received By rregueir Date 2008-02-25 Time 15:04 Sent To PC
Notes
2008-02-25 17:48:04REV 20: M2.05, M2.18, M3.04, M5.01

Review Stop M MECHANICAL (A/C)
Rev No 62 Status P Date 2008-02-05 Cont ID  
Sent By hmoser Date 2008-02-05 Time 19:02 Rev Time 0.00
Received By hmoser Date 2008-02-05 Time 19:02 Sent To  
Notes
2008-02-05 19:04:13SUBMITTLE # 15614 COOLING TOWER WATER AND DRAIN
 CONNECTION

Review Stop M MECHANICAL (A/C)
Rev No 61 Status P Date 2008-02-05 Cont ID  
Sent By hmoser Date 2008-02-05 Time 18:37 Rev Time 0.00
Received By hmoser Date 2008-02-05 Time 18:36 Sent To  
Notes
2008-02-05 18:39:10SUBMITTLE # 15840.01 VARIABLE AIR VOLUME

Review Stop M MECHANICAL (A/C)
Rev No 60 Status F Date 2008-02-05 Cont ID  
Sent By hmoser Date 2008-02-05 Time 18:07 Rev Time 0.00
Received By hmoser Date 2008-02-05 Time 18:07 Sent To  
Notes
2008-02-05 18:13:27SUBMITTLE # 15080.01 DENIED ALUMAGUARD 60 IS A CLOSURE
 SYSTEM THAT IS NOT A UL 181 LISTED PRODUCT

Review Stop M MECHANICAL (A/C)
Rev No 59 Status P Date 2008-02-05 Cont ID  
Sent By hmoser Date 2008-02-05 Time 17:22 Rev Time 0.00
Received By hmoser Date 2008-02-05 Time 17:22 Sent To  
Notes
2008-02-05 17:23:56SUBMITTLE NUMBER 15815.03 LOVERS & GRILLS.

Review Stop M MECHANICAL (A/C)
Rev No 58 Status P Date 2008-02-05 Cont ID  
Sent By hmoser Date 2008-02-05 Time 16:52 Rev Time 0.00
Received By hmoser Date 2008-02-05 Time 16:52 Sent To  
Notes
2008-02-05 16:54:29SUBMITTLE # 15815.01 FLEX DUCT,EXHAUST WALL CAPS ,
 POWER VENTILATORS

Review Stop M MECHANICAL (A/C)
Rev No 57 Status P Date 2008-02-05 Cont ID  
Sent By hmoser Date 2008-02-05 Time 16:16 Rev Time 0.00
Received By hmoser Date 2008-02-05 Time 16:16 Sent To  
Notes
2008-02-05 16:20:07SUBMITTLE 15450.05 AQUASTAT.

Review Stop M MECHANICAL (A/C)
Rev No 56 Status P Date 2008-02-05 Cont ID  
Sent By hmoser Date 2008-02-05 Time 16:12 Rev Time 0.00
Received By hmoser Date 2008-02-05 Time 16:12 Sent To  
Notes
2008-02-05 16:14:18SUBMITTLE # 15815.14.01 GARAGE SUPPLY FANS

Review Stop M MECHANICAL (A/C)
Rev No 55 Status P Date 2008-01-30 Cont ID  
Sent By hmoser Date 2008-01-30 Time 18:49 Rev Time 0.00
Received By hmoser Date 2008-01-30 Time 18:49 Sent To  
Notes
2008-01-30 18:50:14SUBMITTLE # 15815.02 LOUVERS AND DAMPERS

Review Stop M MECHANICAL (A/C)
Rev No 54 Status P Date 2008-01-30 Cont ID  
Sent By hmoser Date 2008-01-30 Time 18:33 Rev Time 0.00
Received By hmoser Date 2008-01-30 Time 18:33 Sent To  
Notes
2008-01-30 18:36:23SUBMITTLE # 15075.01 IDENTIFICATION AND NAMEPLATES

Review Stop M MECHANICAL (A/C)
Rev No 53 Status P Date 2008-01-30 Cont ID  
Sent By hmoser Date 2008-01-30 Time 17:47 Rev Time 0.00
Received By hmoser Date 2008-01-30 Time 17:46 Sent To  
Notes
2008-01-30 17:48:21SUBMITTLE # 15181.03M DESEL ENGINE EXHAUST PIPING

Review Stop M MECHANICAL (A/C)
Rev No 52 Status P Date 2008-03-04 Cont ID  
Sent By hmoser Date 2008-03-04 Time 14:38 Rev Time 0.00
Received By hmoser Date 2008-03-04 Time 14:38 Sent To  
Notes
2008-01-30 17:04:53SUBMITTLE # 15181.02M SUCTION DIFFUSER FOR CWP.& TRIPLE
 DUTY VALVES.

Review Stop M MECHANICAL (A/C)
Rev No 51 Status P Date 2008-01-30 Cont ID  
Sent By hmoser Date 2008-01-30 Time 16:21 Rev Time 0.00
Received By hmoser Date 2008-01-30 Time 16:21 Sent To  
Notes
2008-01-30 16:24:5704120353 SUBMITLE 15122.02 READ OUT

Review Stop M MECHANICAL (A/C)
Rev No 50 Status P Date 2008-01-24 Cont ID  
Sent By hmoser Date 2008-01-24 Time 18:48 Rev Time 0.00
Received By hmoser Date 2008-01-24 Time 18:47 Sent To  
Notes
2008-01-24 18:49:51SUBMITTLE NUMBER 15122.01 THERMOMETERS,GAGES AND TEST
 PLUGS

Review Stop M MECHANICAL (A/C)
Rev No 49 Status P Date 2008-03-04 Cont ID  
Sent By hmoser Date 2008-03-04 Time 14:40 Rev Time 0.00
Received By hmoser Date 2008-01-24 Time 18:41 Sent To  
Notes
2008-01-24 18:42:28SUBMITTLE NUMBER 15641.01.02 COOLING TOWER DATA

Review Stop M MECHANICAL (A/C)
Rev No 48 Status P Date 2008-01-24 Cont ID  
Sent By hmoser Date 2008-01-24 Time 18:24 Rev Time 0.00
Received By hmoser Date 2008-01-24 Time 18:24 Sent To  
Notes
2008-01-24 18:26:32SUBMITTLE NUMBER 15110.01 BALL,BUTTERFLY AND CHECK
 VALVE

Review Stop M MECHANICAL (A/C)
Rev No 47 Status P Date 2008-01-24 Cont ID  
Sent By hmoser Date 2008-01-24 Time 18:17 Rev Time 0.00
Received By hmoser Date 2008-01-24 Time 18:16 Sent To  
Notes
2008-01-24 18:18:52SUBMITTLE NUMBER 15685.01.02 WATER TREATMENT &
 CHEMICALS

Review Stop M MECHANICAL (A/C)
Rev No 45 Status P Date 2008-01-24 Cont ID  
Sent By hmoser Date 2008-01-24 Time 17:37 Rev Time 0.00
Received By hmoser Date 2008-01-24 Time 17:37 Sent To B
Notes
2008-01-24 17:39:20SUBMITTLE NUMBER 15181.07M EXHAUST PHIMBLES.

Review Stop M MECHANICAL (A/C)
Rev No 44 Status P Date 2008-01-24 Cont ID  
Sent By hmoser Date 2008-01-24 Time 17:00 Rev Time 0.00
Received By hmoser Date 2008-01-24 Time 17:00 Sent To  
Notes
2008-01-24 17:05:32SUBMITTAL NUMBER 16100.10 CARBON MONOXIDE SENSORS

Review Stop M MECHANICAL (A/C)
Rev No 43 Status P Date 2008-01-22 Cont ID  
Sent By rregueir Date 2008-01-22 Time 11:44 Rev Time 0.00
Received By rregueir Date 2008-01-22 Time 11:43 Sent To PC
Notes
2008-01-22 11:44:02SUBMITTAL #15181.08 WELDED PIPE NIPPLES

Review Stop M MECHANICAL (A/C)
Rev No 42 Status P Date 2008-01-22 Cont ID  
Sent By rregueir Date 2008-01-22 Time 11:42 Rev Time 0.00
Received By rregueir Date 2008-01-22 Time 11:35 Sent To PC
Notes
2008-01-22 11:41:13SUBMITTAL #16000.16 SILENCER FOR EMERGENCY GENERATOR

Review Stop M MECHANICAL (A/C)
Rev No 41 Status P Date 2008-01-19 Cont ID  
Sent By rregueir Date 2008-01-19 Time 13:10 Rev Time 0.00
Received By rregueir Date 2008-01-19 Time 11:23 Sent To  
Notes
2008-01-19 12:13:22REV.18 PAGES M2.08, M2.20, M2.27, M2.29, M2.30, M2.32,
 M2.32A, M2.32B, M2.32C, M2.32D, M2.32F, M5.01
  
 1. M2.32C:THE FOLLOWING COMMENT FROM THE 10/25/07
 REVIEW OF REV 16 HAS NOT BEEN ADDRESSED "UNIT P1, 12X8
 RETURN TRANSFER FOR MASTER BEDROOM IS TOO SMALL TO MEET
 THE BALANCED RETURN EXCEPTIONS UNDER FBC,M 601.4. IF
 TRANSFERS ARE NOT DESIGNED TO MEET THESE EXCEPTIONS, A
 FIELD TEST WILL BE REQUIRED AT FNAL INSPECTION TO
 VERIFY PRESSURE DIFFERENTIALS ARE LESS THAN 0.01 INCHES
 W.C AS REQUIRED BY THIS SECTION." THE PAGE WILL PASS
 REVIEW AS IT IS THE ONLLY OUTSTANDING COMMENT. THERE
 WILL BE A STAMP ON PLANS CALLING FOR A FIELD TEST TO
 VERIFY BALANCED RETURN AT FINAL INSPECTION.
  
 2. M2.30 AND M2.32D: SAME COMMENT AS ABOVE APPLIES TO
 UNIT P ON THIS PAGE FOR 15X6 TRANSFER FROM MASTER
 BEDROOM.
  
 3. M2.32 AND M2.32F: SAME COMMENT AS ABOVE APPLIES TO
 UNIT N ON THIS PAGE FOR 10 INCH ROUND TRANSFER FROM
 BEDROOM 3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 40 Status P Date 2007-11-24 Cont ID  
Sent By rregueir Date 2007-11-24 Time 15:03 Rev Time 0.00
Received By rregueir Date 2007-11-24 Time 13:36 Sent To PC
Notes
2007-11-24 15:02:59REV 17 M2.27, M2.29, M2.30, M2.31, M2.32

Review Stop M MECHANICAL (A/C)
Rev No 39 Status P Date 2007-11-24 Cont ID  
Sent By rregueir Date 2007-11-24 Time 13:36 Rev Time 0.00
Received By rregueir Date 2007-11-24 Time 10:08 Sent To PC
Notes
2007-11-24 12:31:11REV 13 M2.21, M2.23, M2.24, M2.26

Review Stop M MECHANICAL (A/C)
Rev No 38 Status P Date 2007-10-25 Cont ID  
Sent By rregueir Date 2007-10-25 Time 18:29 Rev Time 0.00
Received By rregueir Date 2007-10-21 Time 18:21 Sent To PC
Notes
2007-10-25 18:28:12REVISION 16
  
 FBC 2001 CODES W/ 2003 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING PAGE(S) WERE REVIEWED FOR CODE COMPLIANCE
 AND PASSED:
 M6.03
  
 THE FOLLOWING PAGES WERE REVIEWED FOR CODE COMPLIANCE
 AND WERE DENIED WITH COMMENTS:
  
 M2.27: UNIT M, HER WALK-IN-CLOSET, THERE IS A RETURN
 GRILL SHOWN IN THE CEILING AT A LOCATION WHERE THERE IS
 NO PLENUM. WHAT IS THE PURPOSE OF THE GRILL? ALSO,
 PLEASE VERIFY THAT IT IS THE INTENDED DESIGN FOR THERE
 TO BE RETURNS IN CLOSETS AND LAUNDRY ROOM. BALANCED
 RETURN FROM THESE AREAS IS NOT REQUIRED. THIS CONDITION
 OCCURS ON OTHER PAGES AS WELL.
  
 M2.29: UNIT-S, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO
 BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3.
 HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING
 MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW
 HOW THIS IS TO BE ACCOMPLISHED.
 NOTE: UNIT-P1, HPU-1 AND HPU-6 REQUIRE FAN SHUT-DOWN BY
 SMOKE DETECTOR IN ACCORDANCE WITH FBC,M 606.2.2.
  
 M2.32A: NOTE ON PLAN STATES "SHADED AREA IS A RETURN
 AIR PLENUM (TYPICAL)." HOWEVER, THERE ARE NO SHADED
 PLENUM AREAS ON PLAN. PLEASE CORRECT. FBC,M 602.2
  
 M2.32C: UNIT P1, 12X8 RETURN TRANSFER FOR MASTER
 BEDROOM IS TOO SMALL TO MEET THE BALANCED RETURN
 EXCEPTIONS UNDER FBC,M 601.4. IF TRANSFERS ARE NOT
 DESIGNED TO MEET THESE EXCEPTIONS, A FIELD TEST WILL BE
 REQUIRED AT FNAL INSPECTION TO VERIFY PRESSURE
 DIFFERENTIALS ARE LESS THAN 0.01 INCHES W.C AS REQUIRED
 BY THIS SECTION.
  
 M2.32C: UNIT R1, BEDROOM 3/DEN HAS NO RETURN. SHOW
 BALANCED RETURN IN ACCORDANCE WITH FBC,M 601.4.
  
 M2.32C: UNIT S, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO
 BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3.
 HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING
 MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW
 HOW THIS IS TO BE ACCOMPLISHED. ALSO, THE BRANCH DUCT
 FEEDING BEDROOM 2 AND THE BATHROOM IS MISSING SIZE.
 PLEASE CORRECT. FBC,M 601.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 37 Status P Date 2007-10-25 Cont ID  
Sent By rregueir Date 2007-10-25 Time 18:10 Rev Time 0.00
Received By rregueir Date 2007-10-21 Time 18:30 Sent To PC
Notes
2007-10-25 18:10:05REVISION 15
  
 FBC 2001 CODES W/ 2003 SUPPLEMENTS
  
 THE FOLLOWING PAGES WERE NOT REVIEWED AS PART OF REV15
 BECAUSE THEY WERE SUPERCEDED PRIOR TO REVIEW:
 M2.27 SUPERCEDED BY REV16
 M2.29 SUPERCEDED BY REV16
 M2.32A SUPERCEDED BY REV16
 M2.32C SUPERCEDED BY REV16
 M6.03 SUPERCEDED BY REV16
  
 THE FOLLOWING PAGES WERE REVIEWED FOR CODE COMPLIANCE
 AND PASSED:
 M2.05
 M2.06
 M2.19
 M2.19B
 M2.20A
 M2.28
 M3.02
 M3.03
 M3.04
 M4.02
  
 THE FOLLOWING PAGE(S) WERE REVIEWED FOR CODE COMPLIANCE
 AND DENIED WITH COMMENTS:
  
 M2.18: TOILET AND DRYER EXHAUST IN UNIT V1 ARE
 TERMINATING AT "CUBE CORE" GRILLS. ARE THESE LISTED FOR
 USE ON DRYER EXHAUST? WHERE WILL THE BACKDRAFT DAMPER
 FOR THE DRYER EXHAUST BE LOCATED? WHY IS THERE AN
 INLINE BACKDRAFT DAMPER IN THE TOILET EXHAUST DUCT?
 THERE IS NO DETAIL FOR THIS TYPE OF TERMINATION AT
 DRYER AND TOILET EXHAUST. THIS IS THE SECOND TIME THIS
 INFORMATION IS BEING REQUESTED. SHOW COMPLIANCE WITH
 FBC,M 401.5 AND 504.4.
  
 M2.20: MECHANICAL CLOSET FOR HPU-5-3 IS SHOWN AS A
 PLENUM. DISCHARGE EXHAUST DUCT FOR EF-5-2 IS ROUTED
 THROUGH THIS PLENUM. EXHAUST DUCTS UNDER POSITIVE
 PRESSURE SHALL NOT BE LOCATED IN A PLENUM IN ACCORDANCE
 WITH FBC,M 601.3. SHOW HOW THIS DUCT IS TO BE ISOLATED
 FROM PLENUM.
  
 M2.30: UNIT-P, HPU-1 AND HPU-5 REQUIRE FAN SHUT DOWN BY
 SMOKE DETECTOR IN ACCORDANCE WITH FBC,M 606.2.2.
  
 M2.31: UNIT-T, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO
 BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3.
 HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING
 MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW
 HOW THIS IS TO BE ACCOMPLISHED.
  
 M2.32: UNIT-U, 12X6 RETURN DUCT IN BEDROOM 2 DOES NOT
 ATTACH TO PLENUM. HOW WILL RETURN AIR GET FROM BEDROOM
 TO PLENUM? SHOW COMPLIANCE WITH FBC,M 601.4. ALSO, WHY
 US THERE A RETURN IN THE LAUNDRY ROOM? BALANCED RETURN
 IS NOT REQUIRED FROM THIS AREA UNDER THIS SECTION.
  
 M2.32B: UNIT P2, SUPPLY FLEX IN BEDROOM 2 IS MISSING
 SIZE. PLEASE CORRECT. FBC,M 601.1
  
 M2.23D: UNIT P, RETURN TRANSFERS FROM MASTER BEDROOM
 AND BEDROOM 2 ARE TOO SMALL TO MEET THE BALANCED RETURN
 EXCEPTIONS UNDER FBC,M 601.4. IF TRANSFERS ARE NOT
 DESIGNED TO MEET THESE EXCEPTIONS, A FIELD TEST WILL BE
 REQUIRED AT FNAL INSPECTION TO VERIFY PRESSURE
 DIFFERENTIALS ARE LESS THAN 0.01 INCHES W.C AS REQUIRED
 BY THIS SECTION. ALSO, NOTE ON PLAN CALLS FOR EXHAUST
 DUCT TO BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M
 601.3. HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE
 CEILING MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM.
 PLEASE SHOW HOW THIS IS TO BE ACCOMPLISHED.
  
 M2.32D: UNIT R, RETURN TRANSFER FOR MASTER BEDROOM IS
 TOO SMALL TO MEET THE BALANCED RETURN EXCEPTIONS UNDER
 FBC,M 601.4. IF TRANSFERS ARE NOT DESIGNED TO MEET
 THESE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED AT FNAL
 INSPECTION TO VERIFY PRESSURE DIFFERENTIALS ARE LESS
 THAN 0.01 INCHES W.C AS REQUIRED BY THIS SECTION.
  
 M2.32D: UNIT S, THE RETURN TRANSFER FOR BEDROOM 2 IS
 GOING INTO THE BATHROOM, THEREFORE THE AIR IS NOT BEING
 RETURNED TO THE HPU. PLEASE CORRECT AND SHOW COMPLIANCE
 WITH FBC,M 601.3. ALSO, THE PLENUM AREA ABOVE THE
 CEILING IS NOT DEFINED ON THE FLOOR PLAN. PLEASE
 CORRECT. FBC,M 602.2
  
 M2.32E: UNIT T, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO
 BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3.
 HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING
 MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW
 HOW THIS IS TO BE ACCOMPLISHED.
  
 M2.32F: UNIT U, 12X6 RETURN DUCT IN BEDROOM 2 IS NOT
 ATTACHED TO PLENUM. PLEASE CORRECT AND SHOW COMPLIANCE
 WITH FBC,M 601.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 36 Status P Date 2007-10-25 Cont ID  
Sent By rregueir Date 2007-10-25 Time 16:59 Rev Time 0.00
Received By rregueir Date 2007-10-21 Time 18:07 Sent To PC
Notes
2007-10-25 16:29:37MECH REVISION 14
  
 FBC 2001 CODES W/ 2003 SUPPLEMENTS
  
 THE FOLLOWING PAGES WERE NOT REVIEWED BECUASE THEY WERE
 SUPERCEDED PRIOR TO REVIEW OF REV 14:
 M2.06 SUPERCEDED BY REV15
 M4.02 SUPERCEDED BY REV15
 M6.03 SUPERCEDED BY REV16
  
 THE FOLLOWING PAGES WERE REVIEWED FOR CODE COMPLIANCE
 AND PASSED:
 M2.01
 M2.02
 M2.03
 M2.04
 M2.07
 M2.09
 M2.10
 M2.11
 M2.12
 M2.13 REV.12
 M2.17 REV.12
 M2.26B
 M2.26D
 M2.26F
 M4.01
 M4.03
 M5.01
 M6.01
  
 THE FOLLOWING PAGE(S) WERE REVIEWED FOR CODE COMPLIANCE
 AND DENIED WITH COMMENTS:
  
 M2.08: 6X6 SUPPLY DUCT FROM HPU-P3-4 IS PASSING THROUGH
 A RATED WALL. NOTE ON PLAN CLAIMS AN EXCEPTION TO THE
 REQUIREMENT FOR A FIRE DAMPER PER FBC,M 607.1.3.
 HOWEVER, UNDER EXCEPTION #3 THE DUCT IS REQUIRED TO BE
 INSTALLED ABOVE A CEILING. THE STORAGE AREAS DO NOT
 HAVE A CEILING, THEREFORE A FIRE DAMPER IS REQUIRED AT
 THIS DUCT PENETRATION OF THE RATED WALL.
  
 M2.26A: UNIT C, RETURN TRANSFER (8IN. ROUND) IN BEDROOM
 2 IS TOO SMALL TO MEET THE BALANCED RETURN EXCEPTIONS
 UNDER FBC,M 601.4. IF TRANSFERS ARE NOT DESIGNED TO
 MEET THESE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED AT
 FNAL INSPECTION TO VERIFY PRESSURE DIFFERENTIALS ARE
 LESS THAN 0.01 INCHES W.C AS REQUIRED BY THIS SECTION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 35 Status P Date 2007-09-11 Cont ID  
Sent By rregueir Date 2007-09-11 Time 17:42 Rev Time 0.00
Received By rregueir Date 2007-09-11 Time 17:30 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 34 Status F Date 2007-08-17 Cont ID  
Sent By rregueir Date 2007-08-17 Time 11:51 Rev Time 0.00
Received By rregueir Date 2007-08-17 Time 11:49 Sent To  
Notes
2007-08-17 11:51:13REV 12R PG M2.05
 ACTION: DENIED
  
 THIS PAGE WAS PREVIOUSLY SUBMMITED AS A REVISION AND
 DENIED. PLEASE SEE MECHANICAL PLAN REVIEW COMMENTS
 DATED 7/23/07 RELATED TO PG M2.05. ADDRESS PREVIOUS
 COMMENTS AND RESUBMIT.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 33 Status F Date 2007-08-17 Cont ID  
Sent By rregueir Date 2007-08-17 Time 11:22 Rev Time 0.00
Received By rregueir Date 2007-08-16 Time 14:42 Sent To  
Notes
2007-08-17 11:21:58REV 13R
 THE FOLLOWING PAGES WERE REVIEWED AND PASSED:
 M2.12, M2.25, M2.26C, M2.26E
  
 THE FOLLOWING PAGES WERE DENIED WITH COMMENTS:
 M2.22, M2.26A, M2.26B, M2.26D, M2.26F
  
 ONE COPY OF PASSED PAGES WAS RETAINED FOR PERMIT
 RECORDS. ONE COPY OF DENIDE PAGES WAS RED-LINED TO
 ASSIST IN UNDERSTANDING THE LOCATION AND NATURE OF
 WRITTEN REVIEW COMMENTS.
  
 1. M2.22 UNIT D1: THERE IS NO RETURN GRILL IN THE
 PLENUM. PLEASE CORRECT.
  
 2. M2.26A-
 UNITS C AND L: MISSING RETURNS IN BEDROOM #2. FBC,M
 601.4
 UNITS B5 AND B6: PLAN SHOWS 14X14 R/A IN CEILING OF
 MASTER BEDROOM FOR WHAT PURPOSE? PLEASE CLARIFY.
  
 3. M2.26B-
 UNIT G1: CONTAINS NOTE FOR FLEX DUCT TO OFFSET DRYER
 EXHAUST. FLEX DUCT SHALL NOT BE USED IN CONCEALED
 SPACES. FBC,M 504.6. ALSO IN G1, 16X16 R/A GRILL IN
 MASTER BEDROOM HAS NO DUCT OR PLENUM OR OTHER WAY FOR
 AIR TO RETURN FROM ROOM.
 UNIT D1, THERE IS NO RETURN GRILL IN PLENUM CEILING.
 UNIT C2, 12X12 R/A FOR MASTER BEDROOM IS NOT LOCATED
 WITHIN THE CEILING PLENUM SPACE.
  
 4. M2.26D UNIT J: THERE IS NO DEFINED CEILING PLENUM
 AREA SHOWN ON PLAN. PLEASE CORRECT.
  
 5. M2.26F UNIT C1: NO FIRE RATING OR OPENING
 PROTECTIVES ARE SHOWN WHERE THE PLENUM EXTENDS INTO THE
 CORRIDOR. PLEASE CORRECT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 32 Status N Date 2007-08-02 Cont ID  
Sent By rregueir Date 2007-08-02 Time 08:31 Rev Time 0.00
Received By rregueir Date 2007-08-01 Time 18:59 Sent To  
Notes
2007-08-02 08:31:26THIS MECH REVISION WAS DONE UNDER SEPARATE SUBMITTAL
 REVIEWED 7/23/07

Review Stop M MECHANICAL (A/C)
Rev No 31 Status F Date 2007-07-23 Cont ID  
Sent By rregueir Date 2007-07-23 Time 10:13 Rev Time 0.00
Received By rregueir Date 2007-07-22 Time 11:45 Sent To  
Notes
2007-07-23 10:13:52THE FOLLOWING PAGES WERE REVIEWED AND STAMPED:
  
 M1.01 THROUGH M1.12, M2.14, M2.15, M2.16, M2.19A,
 M2.20B, M3.02, M3.03, M3.04
  
 THE FOLLOWING PAGES WERE DENIED WITH COMMENTS:
  
 1. M2.05: EF-A IN JANITOR'S CLOSET, DUCT PASSES THROUGH
 MECHANICAL ROOM WHICH IS A PLENUM. EXHAUST DUCTS UNDER
 POSITIVE PRESSURE SHALL NOT PASS THROUGH A PLENUM.
 FBC,M 601.3
  
 2. M2.05: EXHAUST DUCT PENETRATION AT MECHANICAL ROOM
 RATED WALL REQUIRES A FIRE DAMPER. IT DOES NOT MEET ALL
 CONDITIONS OF THE EXCEPTION UNDER FBC,M 607.1.3 UNLESS
 THE DUCT IS INTALLED ABOVE A CEILING. SEE ITEM (4) OF
 THIS SECTION.
  
 3. M2.13: UNIT VV, THERE IS NO DUCT SHOWN ON PLANS
 FEEDING THE 8X6 SUPPLY REGISTER IN THE MASTER BEDROOM.
 PLEASE CORRECT.
  
 4. M2.17: UNIT H4, PORTIONS OF SUPPLY TRUNK ARE MISSING
 FROM PLAN. PLEASE CORRECT.
  
 5. M2.18: UNIT V1, PLAN SHOWS INLINE BACKDRAFT DAMPER
 IN EXHAUST DUCT. IS THIS FOR BATH EXHAUST ONLY OR ALSO
 FOR DRYER? IS THE INLINE BACKDRAFT DAMPER LISTED FOR
 USE IN A DRYER EXHAUST DUCT? DRYER EXHAUST DUCT IS TO
 BE FREE OF OBSTRUCTIONS AND HAVE A SMOOTH INTERIOR
 SURFACE. SEE FBC,M 504.4 AND 504.6. ALSO, HAS THERE
 BEEN A SUBMITTAL FOR THE "CUBE CORE GRILL" FOR USE ON
 DRYER EXHAUST? THE GRILL FOR BATH EXHAUST REQUIRES A
 SCREEN (FBC,M 401.6) AND A SCREEN IS PROHIBITED ON
 DRYER EXHAUST OUTLETS (FBC,M 504.4).
  
 6. M2.19: MOTORIZED DAMPER 5-1-2 IS NO LONGER SHOWN IN
 DUCT, BUT THE DESIGNATION AND NOTE ARE STILL ON THE
 PLAN. IS THE SMOKE CONTROL SYSTEM BEING REVISED OR IS
 THE DAMPER MISTAKENLY OMITTED?
  
 7. M2.19: GRILL AND DUCT SIZE MISSING FROM TWO DROPS IN
 MULTI USE ROOM AND KITCHEN.
  
 8. M2.19B: UNIT C2, PROVIDE NOTE REGARDING EXHAUST
 DUCTS IN RETURN AIR PLENUM. WILL THE SYSTEM WHICH WAS
 SUBMITTED AS AN ALTERNATE MATERIAL/METHOD FOR EXHAUST
 IN A PLENUM WORK IN THIS CASE, WHERE THE EXHAUST FAN
 ITSELF IS LOCATED IN THE PLENUM? PLEASE PROVIDE DETAIL.
 FBC,M 601.3
  
 9. M2.20: COMMON AREAS ARE NOT SHOWN ON PLAN AS HAVING
 BEEN REVISED. HOWEVER, THE AREA CONTAINS SEVERAL
 CHANGES FROM PREVIOUS APPROVED PLANS. PLEASE INDICATE
 ALL AREAS WHICH ARE PART OF THIS REVISION.
  
 10. M:20A: SAME AS COMMENT #10. COMMON AREA DUCT
 SYSTEMS WHICH ARE SHOWN IN THEIR ENTIRETY ON PG M2.20
 MAY BE OMITTED FROM THIS PAGE, OR THE AREAS BEING
 REVISED MUST BE CLEARLY IDENTIFIED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 30 Status P Date 2007-07-02 Cont ID  
Sent By rregueir Date 2007-07-02 Time 15:11 Rev Time 0.00
Received By rregueir Date 2007-06-29 Time 16:39 Sent To  
Notes
2007-07-02 15:11:07FAN SHUT-DOWN VIA DUCT OR AREA SMOKE DETECTOR IS
 REQUIRED IN ALL UNITS WHICH HAVE HPU-4 AS SHOWN ON
 EQUIPMENT SCHEDULE (M5.01) WITH A SUPERVISORY SIGNAL AT
 A CONSTANTLY ATTENDED LOCATION.
 ALSO, PLEASE PROVIDE DOCUMENTATION SHOWING HPU-5 WITHIN
 RANGE OF CFM'S REQUIRED ON FLOOR PLAN BASED ON ACTUAL
 E.S.P. IN UNTS D AND D1.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 29 Status F Date 2007-06-23 Cont ID  
Sent By rregueir Date 2007-06-23 Time 14:19 Rev Time 0.00
Received By rregueir Date 2007-06-23 Time 13:51 Sent To  
Notes
2007-06-23 14:10:17-------------------DENIED-------------------------
  
 PAGES M2.21 THROUGH M2.26: THESE ARE THE SAME EXACT
 PAGES WHICH WERE DENIED 6/18/07. THERE ARE NO CHANGES
 FROM THAT SET AND NONE OF THE COMMENTS FROM PREVIOUS
 REVIEW HAVE BEEN ADDRESSED. PLEASE SEE ATTACHED
 PREVIOUS REVIEW COMMENTS. PLEASE RESPOND TO EACH ISSUE
 IN WRITING AND SHOW ON PLANS WHERE CORRECTIONS HAVE
 BEEN MADE. ALSO, SEE ATTACHED NOTICE REGARDING
 ADDITIONAL FEES FOR PLANS WHIC ARE REJECTED REPEATEDLY
 FOR THE SAME CODE ISSUES.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 28 Status F Date 2007-06-18 Cont ID  
Sent By rregueir Date 2007-06-18 Time 10:40 Rev Time 0.00
Received By rregueir Date 2007-06-16 Time 12:45 Sent To  
Notes
2007-06-18 10:40:26----------------DENIED-----------------
  
 NOTE: AREAS ADDRESSED IN THESE COMMENTS HAVE BEEN
 MARKED ON ONE SET OF THE SUBMITTED PLANS, WHERE
 PRACTICAL, FOR THE PURPOSE OF CLARITY.
  
 1. M2.21 UNIT L: FLOOR PLAN SHOWS 1445 CFM SUPPLY.
 HPU-4 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 2000 CFM.
 PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND
 EQUIPMENT SCHEDULE. WHICH IS CORRECT?
  
 2. M2.21 UNIT C: SQUARE 90 DEGREE ELBOW ON 12X10 SUPPLY
 DUCT REQUIRES TURNING VANES PER FBC,M 603.4, SMACNA OR
 NAIMA DUCT CONSTRUCTION STANDARDS.
  
 3. M2.21 UNIT C: PLEASE SHOW PROVISIONS FOR BALANCED
 RETURN PER FBC,M 601.4.
  
 4. M2.21 UNIT K: FLOOR PLAN SHOWS 1030 CFM SUPPLY.
 HPU-3 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 1250 CFM.
 PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND
 EQUIPMENT SCHEDULE. WHICH IS CORRECT?
  
 5. M2.21 UNIT K: TRANSFER DUCT FROM MASTER BEDROOM IS
 NOT DESIGNED TO MEET THE BALANCED RETURN EXCEPTIONS OF
 FBC,M 601.4. 10X8 SUPPLY X 1.5 = 120 SQ.IN. THIS IS THE
 MINIMUM SIZE TRANSFER DUCT PLUS 1" UNDERCUT DOOR. IF
 TRANSFERS ARE NOT DESIGNED TO THESE EXCEPTIONS, A FIELD
 TEST WILL BE REQUIRED TO VERIFY BALANCED RETURN
 PRESSURE DIFFERENTIAL OF 0.01" W.C. OR LESS PER 601.4.
  
 6. M2.21 UNIT B5: FLOOR PLAN SHOWS 1050 CFM SUPPLY.
 HPU-2 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 950 CFM.
 PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND
 EQUIPMENT SCHEDULE. WHICH IS CORRECT?
  
 7. M2.21 UNIT B5: TRANSFER DUCT IN MASTER BEDROOM. 12X8
 SUPPLY X 1.5 = 144 SQ.IN. THIS IS THE MINIMUM SIZE
 REQUIRED FOR TRANSFER DUCT PLUS 1" UNDERCUT DOOR. SEE
 COMMENT #5 FOR CONDITIONS.
  
 8. M2.21 AND M2.22: PLEASE SHOW ENTIRE DUCT
 LAYOUT/FLOOR PLAN FOR UNIT B6 ON ONE PAGE OR THE
 OTHER.
  
 9. M2.21 UNIT B6: SQUARE 90 DEGREE ELBOW REQUIRES
 TURNING VANES. SEE COMMENT #2. COMMENTS 6 AND 7 ALSO
 APPLY TO UNIT B6.
  
 10. M2.22 UNIT G1: THE DESIGN OF THE TRANSFER DUCT AND
 GRILLS FOR THE MASTER BEDROOM IS UNCLEAR DUE TO SOME
 COMPONENTS NOT BEING SHOWN ON PLAN. FBC 104.3.1.1
  
 11. M2.22 UNIT D1: PRIMARY RETURN GRILL IS MISSING FROM
 PLANS. PLEASE CORRECT.
  
 12. M2.22 UNIT D1: FLOOR PLAN SHOWS 845 CFM SUPPLY.
 HPU-5 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 650 CFM.
 PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND
 EQUIPMENT SCHEDULE. WHICH IS CORRECT?
  
 13. M2.22 UNIT E1: SQUARE 90 DEGREE ELBOW NEEDS TURNING
 VANES. SEE COMMENT #2.
  
 14. M2.22 UNIT E1: PLAN SHOWS 4" BATH EXHAUST PASSIGN
 THROUGH R/A PLENUM. EXHAUST DUCTS UNDER POSITIVE
 PRESSURE SHALL NOT EXTEND INTO OR PASS THROUGH DUCTS OR
 PLENUMS. FBC,M 601.3.
  
 15. M2.22 UNIT C2: PLEASE SHOW ON PLANS THE SIZE OF
 SUPPLY DUCT FROM A/C CLOSET TO THE TRANSITION AND SHOW
 THE DUCT LINE IN ITS ENTIRETY. PORTIONS OF THE DUCT ARE
 MISSING FROM PLAN.
  
 16. M2.22 UNIT C2: FLOOR PLAN SHOWS 1125 CFM SUPPLY.
 HPU-1 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 11350 CFM.
 PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND
 EQUIPMENT SCHEDULE. WHICH IS CORRECT?
  
 17. M2.23 UNIT A: FLOOR PLAN SHOWS 1540 CFM SUPPLY.
 HPU-4 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 2000 CFM.
 PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND
 EQUIPMENT SCHEDULE. WHICH IS CORRECT?
  
 18. M2.23 UNIT B3: SQUARE 90 DEGREE ELBOWS NEED TURNING
 VANES. SEE COMMENT #2.
  
 19: M2.23 UNIT B4: PLEASE SHOW LOCATION OF PLENUM
 CEILING AREA ON FLOOR PLAN.
  
 20. M2.23 UNIT B4: SQUARE 90 DEGREE ELBOWS REQUIRE
 TURNING VANES. SEE COMMENT #2.
  
 21. M2.23 UNIT G: FLOOR PLAN SHOWS 635 CFM SUPPLY.
 HPU-6 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 800 CFM.
 PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND
 EQUIPMENT SCHEDULE. WHICH IS CORRECT?
  
 22. M2.24 UNIT A: PLEASE SEE COMMENT #17
  
 23. M2.24 UNIT A: TWO 90 DEGREE ELBOWS REQUIRE TURNING
 VANES. PLEASE SEE COMMENT #2.
  
 24. M2.24 UNIT A: PLEASE SHOW LOCATION OF PLENUM
 CEILING AREA ON FLOOR PLAN.
  
 25. M2.25 UNIT D: FLOOR PLAN SHOWS 770 CFM SUPPLY.
 HPU-5IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 650 CFM.
 PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND
 EQUIPMENT SCHEDULE. WHICH IS CORRECT?
  
 26. M2.26 UNIT C1; FLOOR PLAN SHOWS AN EXTRA BRANCH
 DUCT AND REGISTER IN THE KITCHEN. PLEASE CLARIFY.
  
 27. M2.26 UNIT C1: FLOOR PLAN SHOWS 1260 CFM SUPPLY.
 HPU-1 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 1350 CFM.
 PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND
 EQUIPMENT SCHEDULE. WHICH IS CORRECT?
  
 NOTE: ALL APARTMENTS SHOWING HPU-4 AT 2000 CFM WILL
 REQUIRE DUCT SMOKE DETECTORS WITH FAN SHUT-DOWN AND
 SHALL BE INTERCONNECTED WITH THE BUILDING FIRE ALARM
 SYSTEM PER FBC,M 606.2.1 AND 606.4.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 27 Status F Date 2007-06-13 Cont ID  
Sent By hmoser Date 2007-06-13 Time 19:12 Rev Time 0.00
Received By hmoser Date 2007-06-13 Time 19:12 Sent To  
Notes
2007-06-13 19:16:42SHOP DROWINGS AND SEALD PLANS DO NOT MATCH
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 26 Status P Date 2007-06-04 Cont ID  
Sent By hmoser Date 2007-06-04 Time 18:27 Rev Time 0.00
Received By hmoser Date 2007-06-04 Time 18:27 Sent To  
Notes
2007-06-04 18:30:386/4/07
 PAGE M4.03 CAN NOT FIND CHANGES ON THE PLANS .
 PLAN REVIEWBY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 25 Status P Date 2007-05-09 Cont ID  
Sent By hmoser Date 2007-05-09 Time 08:29 Rev Time 0.00
Received By hmoser Date 2007-05-09 Time 08:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 24 Status P Date 2007-04-24 Cont ID  
Sent By hmoser Date 2007-04-24 Time 14:15 Rev Time 0.00
Received By hmoser Date 2007-04-24 Time 14:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 23 Status P Date 2007-02-28 Cont ID  
Sent By rregueir Date 2007-02-28 Time 15:10 Rev Time 0.00
Received By rregueir Date 2007-02-26 Time 11:11 Sent To  
Notes
2007-02-28 15:14:00REVISIONS SUBMITTED 1/11/07
  
 ONE PAGE DENIED:
  
 M2.19 - APT D2, EXHAUST DISCHARGE LOCATION IN CLOSE
 PROXIMITY TO FRESH AIR INTAKE. SHOW COMPLIANCE WITH
 FBC,M 401.5 AND 501.3.
  
 ALL OUTSTANDING PROVISOS HAVE BEEN ADDRESSED AND
 SATISFIED WITH THESE REVISIONS.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 22 Status P Date 2007-01-03 Cont ID  
Sent By pkrauss Date 2007-01-03 Time 06:45 Rev Time 0.00
Received By pkrauss Date 2007-01-03 Time 06:45 Sent To  
Notes
2007-01-03 07:21:16SUBMITTAL #15815.13 (BOX WALL CAPS)
 #15060.03 HEATER FRAMES

Review Stop M MECHANICAL (A/C)
Rev No 21 Status P Date 2006-12-29 Cont ID  
Sent By pkrauss Date 2006-12-29 Time 07:33 Rev Time 0.00
Received By pkrauss Date 2006-12-29 Time 07:32 Sent To FIRE
Notes
2006-12-29 07:32:59SUBMITTAL / TRASH CHUTES NORTH & SOUTH

Review Stop M MECHANICAL (A/C)
Rev No 20 Status N Date 2006-12-28 Cont ID  
Sent By pkrauss Date 2006-12-28 Time 10:36 Rev Time 0.00
Received By pkrauss Date 2006-12-28 Time 10:35 Sent To  
Notes
2006-12-28 10:49:16SUBMITTAL #15815.17 - 6TH TO 15TH FLOOR (DUCTWORK SHOP
 DRAWINGS).PER FS 481.221(1)(A) & 471.025(1), ALL
 PLANS, SPECIFICATIONS AND REPORTS THAT ARE PREPARED OR
 ISSUED BY A REGISTERED ARCHITECT/ENGINEER, SHALL BEAR
 THE SIGNATURE, DATE AND SEAL OF THE SAID
 ARCHITECT/ENGINEER OF RECORD AND FILED FOR PUBLIC
 RECORD.

Review Stop M MECHANICAL (A/C)
Rev No 19 Status F Date 2006-11-29 Cont ID  
Sent By hmoser Date 2006-11-29 Time 18:37 Rev Time 0.00
Received By hmoser Date 2006-11-29 Time 18:37 Sent To  
Notes
2006-11-29 18:40:09SUBMITTLE MUST BE SUBMITED AS A REVISON BY ENGINEER OF
 RECORD.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 18 Status F Date 2006-11-29 Cont ID  
Sent By hmoser Date 2006-11-29 Time 17:28 Rev Time 0.00
Received By hmoser Date 2006-11-29 Time 17:28 Sent To  
Notes
2006-11-29 17:31:07THIS SUBMITTAL MUST BE SUBMITED AS A REVISON.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 17 Status P Date 2006-11-15 Cont ID  
Sent By rregueir Date 2006-11-15 Time 19:51 Rev Time 0.00
Received By rregueir Date 2006-11-15 Time 19:51 Sent To  
Notes
2006-11-15 19:52:30SUBMITTAL #15815.18
  
 PARKING LEVEL 9 DUCTWORK SHOP DRAWINGS

Review Stop M MECHANICAL (A/C)
Rev No 16 Status P Date 2006-11-15 Cont ID  
Sent By rregueir Date 2006-11-15 Time 19:08 Rev Time 0.00
Received By rregueir Date 2006-11-15 Time 19:08 Sent To  
Notes
2006-11-15 19:09:45SUBMITTAL #15815.16
  
 PARKING LEVEL 7 DUCTWORK SHOP DRAWINGS

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date 2006-11-15 Cont ID  
Sent By rregueir Date 2006-11-15 Time 18:53 Rev Time 0.00
Received By rregueir Date 2006-11-15 Time 18:52 Sent To  
Notes
2006-11-15 18:53:58SUBMITTAL #15815.15
  
 PARKING LEVEL 5 DUCTWORK SHOP DRAWING

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2006-11-15 Cont ID  
Sent By rregueir Date 2006-11-15 Time 18:34 Rev Time 0.00
Received By rregueir Date 2006-11-15 Time 18:36 Sent To  
Notes
2006-11-15 18:35:10SUBMITTAL #15815.15
  
 PARKING LEVEL 2 DUCTWORK SHOP DRAWING.

Review Stop M MECHANICAL (A/C)
Rev No 13 Status F Date 2006-11-14 Cont ID  
Sent By rregueir Date 2006-11-14 Time 19:23 Rev Time 0.00
Received By rregueir Date 2006-11-14 Time 19:23 Sent To  
Notes
2006-11-14 19:35:09SUBMITTAL # 15815.4 REC'D 9/28/06
 SUPPLY AND EXHAUST FANS
  
 ERRORS ON SUBMITTAL DATA AS FOLLOWS:
  
 1. GEF-3 MODEL # ON SUBMITTAL DIFFERS FROM MODEL # ON
 PLAN.
 2. GSF-P1 THRU P9 MAXIMUM SOUND LEVEL ON SUBMITTAL
 EXCEEDS MAXIMUM SOUND LEVEL ON PLAN.
 3. SUBMITTALS ARE MISSING PAGES FOR SPF-5 AND SPF-6 4.
 EF-A AND EF-B SUBMITTAL DATA DOES NOT MATCH PLAN IN ANY
 CATEGORY.
 5. EF-R4 MAXIMUM SOUND LEVEL ON SUBMITTAL EXCEEDS
 MAXIMUM SOUND LEVEL ON PLAN.
 6. EF-P1-3,EF-P3-1,EF-5-1,EF-5-2 MODEL #S ON SUBMITTALS
 DO NOT MATCH PLAN.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 12 Status F Date 2006-11-13 Cont ID  
Sent By hmoser Date 2006-11-13 Time 16:26 Rev Time 0.00
Received By hmoser Date 2006-11-13 Time 16:26 Sent To  
Notes
2006-11-13 16:25:01PLEASE REFER TO SECTION 1203.1.1 2004 JOINTS BETWEEN
 DIFFERENT PIPING MATERIALS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 11 Status F Date 2006-10-04 Cont ID  
Sent By hmoser Date 2006-10-04 Time 15:10 Rev Time 0.00
Received By hmoser Date 2006-10-04 Time 15:10 Sent To  
Notes
2006-10-04 00:00:00PLAN DENIED
 PAGE M2.02 PLEASE REFER TO SECTION 601.3
 FBC(M) 2001 CONTAMINATION & PREVENTION .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2006-09-07 Cont ID  
Sent By pkrauss Date 2006-09-07 Time 13:03 Rev Time 0.00
Received By pkrauss Date 2006-09-06 Time 14:50 Sent To  
Notes
2006-09-07 00:00:00PROVISO:
  
 1.PLEASE REVISE CALCULATIONS FOR THE
 GARAGE VENTILATION.SHOW COMPLIANCE
 WITH 2001 FBC 411.4.2 & 2001 FMC 501.4.
  
 2.PLEASE INDICATE IF THE CO SENSORS
 WILL BE TIED TO THE EMERGENCY POWER.
  
 3.PLAN SHEET M2.04 - PLEASE VERIFY THE
 LENGTH OF THE DRYER EXHAUST, DUE TO THE
 RE-ROUTING OF THE DUCT.THIS COMMENT IS
 IN RESPONSE TO NARRATIVE NOTE #15.
  
 4.PLEASE NOTE, AIR HANDLER CLOSETS
 SERVE AS A PLENUM AND SHALL COMPLY WITH
 2001 FMC 602.2.1, MATERIALS EXPOSED
 WITHIN THE PLENUM SHALL BE
 NON-COMBUSTIBLE.THIS INCLUDES THE DOOR
 AND FRAME.
  
 5.DRYER EXHAUST SHALL NOT EXCEED THE
 MANUFACTURER'S SPECIFIED LENGTH OR
 COMPLY WITH 2001 FMC 504.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2006-06-02 Cont ID  
Sent By tgordon Date 2006-06-02 Time 12:08 Rev Time 0.15
Received By tgordon Date 2006-06-02 Time 12:08 Sent To  
Notes
2006-06-02 00:00:00SUBMITTAL #15685.02 COOLING TOWER
 FILTRATION SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2006-05-16 Cont ID  
Sent By pkrauss Date 2006-05-16 Time 14:56 Rev Time 0.00
Received By pkrauss Date 2006-05-16 Time 14:56 Sent To  
Notes
2006-05-16 00:00:00SUBMITTAL - UL APPROVED DRYER BOXES;
 RESIDENTIAL UNIT DRYERS

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-03-17 Cont ID  
Sent By pkrauss Date 2006-03-17 Time 07:14 Rev Time 0.00
Received By pkrauss Date 2006-03-17 Time 07:12 Sent To  
Notes
2006-03-17 00:00:00PROVISO:
 RESPONSE TO COMMENT #1 DATED 03/02/06:
 500 GALLON FUEL TANK WAS REMOVED FROM
 PLAN SHEET A4.01 AND REPLACED WITH A
 STORAGE ROOM. THE MECHANICAL PLAN
 (M2.01) DOES NOT REFLECT THE NEW STORAGE
 ROOM.
  
 RESPONSE TO COMMENT #2:FIRE DAMPERS
 WERE ADDED TO THE SEPARATION BETWEEN THE
 GARAGE AND THE DOMESTIC WATER PUMP ROOM
 (S110).FIRE DAMPERS WERE NOT ADDED TO
 THE SEPARATION BETWEEN ROOMS S110 &
 S109.PLAN SHEET A4.01 INDICATES THIS
 PENETRATION AS HAVING A 1 HOUR RATING
 (K1 WALL TYPE), ACCORDING TO THE
 SCHEDULE SHOWN ON PLAN SHEET A9.01.
  
 RESPONSE TO COMMENT #3:INSTALLATION OF
 SHAFT SHALL NOT RESTRICT OR REDUCE THE
 AMOUNT OF RETURN AIR REQUIRED PER 2004
 FMC 918.2.
  
 RESPONSE TO COMMENT #4:NOTE #2 ON PLAN
 SHEET M2.02 INDICATES ALL DRYERS SHALL
 HAVE A 200 CFM MAXIMUM EXHAUST FAN.PER
 2004 FMC 504.5 INSTALLATIONS EXHAUSTING
 MORE THAN 200 CFM SHALL BE PROVIDED WITH
 MAKEUP AIR.WHERE A CLOSET IS DESIGNED
 FOR THE INSTALLATION OF A CLOTHES DRYER,
 AN OPENING HAVING AN AREA OF NOT LESS
 THAN 100 SQUARE INCHES, SHALL BE
 PROVIDED IN THE CLOSET ENCLOSURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2006-03-02 Cont ID  
Sent By pkrauss Date 2006-02-23 Time 07:17 Rev Time 0.00
Received By pkrauss Date 2006-02-23 Time 07:17 Sent To  
Notes
2006-03-02 00:00:00REVIEW CHANGED FROM PASS STATUS TO FAIL
 STATUS.COMMENTS ARE TO BE ADDRESSED
 AND PLANS REVISED TO REFLECT CORRECTIONS
 PRIOR TO PERMIT ISSUANCE.
2006-02-23 00:00:00****************PROVISO***************
  
 PLEASE NOTE, PROVISO'S TO BE ADDRESSED
 AND REVISIONS RESUBMITTED WITHIN 30 DAYS
 OF THE DATE THE PERMIT IS ISSUED.
  
 1.PLAN SHEET A4.01 PLEASE REMOVE THE
 500 GALLON FUEL TANK INDICATED IN THE
 ROOM S105.PER CONVERSATION WITH MATT
 STILL, THE REMOTE FUEL TANK WAS
 ELIMINATED.
  
 2.PLAN SHEET M2.01 MAKE UP AIR AND
 EXHAUST FROM GARAGE THROUGH ROOM S110 TO
 S109, NO DAMPERS INDICATED. PLAN SHEET
 A9.01 INDICATES THESE PENETRATIONS AS 2
 HR & 1 HR RESPECTIVELY.
  
 3.PLAN SHEET M2.01 PLEASE REMOVE NOTE
 THAT INDICATES DRYER EXHAUST LOCATED
 INSIDE R/A PLENUM WILL BE SEALED
 ENCLOSURE.REPONSE FROM ENGINEER
 INDICATES THIS IS FOR UNIT 18 ONLY.
 PLEASE NOTE THIS SHALL BE A RATED
 ENCLOSURE AS DRYER DUCT CONVEYS
 COMBUSTIBLES.PLEASE PROVIDE A DETAIL
 OF RATED ENCLOSURE AND SUBMIT UNDER
 ALTERNATE MATERAILS & MEDTHODS 2001 FMC
 103.7.1.
  
 4.PLAN SHEET M2.02 UNIT 1 ALSO
 INDICATES DRYER DUCT THROUGH A PLENUM.
 PLEASE ALSO CORRECT NOTE #2.
  
 5.PLAN SHEET M2.03, 16" X 10" DUCT
 THROUGH THE WALL AT THE ENTRANCE FROM
 THE GARAGE, A FIRE DAMPER IS NOT
 INDICATED AT THIS LOCATION.DRYER DUCT
 RUNNING THROUGH RETURN AIR PLENUM UNIT 5
 & UNIT 8.
  
 6.PLAN SHEET M2.05 SUPPLY DUCT FROM
 MECHANICAL ROOM (HPU-P1-5), FIRE DAMPER
 REQUIRED.ALSO DUCT INTO FIRE CONTROL
 ROOM SHALL COMPLY WITH 2001 FMC 607.1.3
 ITEM #3 OR FIRE DAMPER WILL BE REQUIRED.
 PLEASE ANNOTATE IN THE SEQUENCE OF
 OPERATION HOW THIS UNIT WILL BE
 UTILIZED.ACCESS DOOR REQUIRED FOR
 MOTORIZED DAMPERS FOR SERVICE OR
 REPLACEMENT PER 2001 FMC 306.1.
  
 7.PLAN SHEET M2.07 THE MAKE-UP AIR &
 EXHAUST FROM THE ELECTRICAL METER ROOM.
 FIRE DAMPERS ARE NOT INDICATED ON THESE
 PENETRATIONS.
  
 8.PLAN SHEET M2.08 FIRE DAMPER
 REQUIRED IN THE TRANSFER GRILLE BETWEEN
 THE ENRY AREA & THE STORAGE AREA.
 SUPPLY DUCT SHALL COMPLY WITH 2001 FMC
 607.1.3.
  
 9.PLAN SHEET M2.09 8" X 8" TRANSFER
 DUCT HAS DAMPERS INDICATED BUT DOES NOT
 SPECIFY FIRE DAMPER OR FIRE/SMOKE
 DAMPER.
  
 10. PLAN SHEET M2.11 6" X 4" DUCT INTO
 TENANT STORAGE (BY STAIR #6), SHALL
 COMPLY WITH 2001 FMC 607.1.3 OR A FIRE
 DAMPER WILL BE REQUIRED.
  
 11. PLAN SHEET M2.12 TRANSFER GRILLE &
 38" X 16" DUCT PENETRATING THE WALL
 BETWEEN THE TENANT STORAGE & STORAGE RM
 A FIRE DAMPER IS REQUIRED.THE 4" X 4"
 SUPPLY DUCT THROUGH THE SAME PENETRATION
 SHALL COMPLY WITH 2001 FMC 607.1.3.
  
 12. PLAN SHEET M2.13 EXHAUST DUCT
 THROUGH RETURN AIR PLENUM.PER 2001 FMC
 601.3, EXHAUST DUCTS SHALL NOT EXTEND
 INTO OR PASS THROUGH PLENUMS.
  
 13. PLAN SHEET M2.15 TRANSFER GRILLE
 INTO ROOM S121 (TENANT STORAGE) IS
 REQUIRED TO HAVE A FIRE DAMPER.SUPPLY
 DUCT SHALL HAVE NO OPENINGS A MINIMUM OF
 5 FT FROM RATED WALL, 2001 FMC 607.1.3.
  
 14. PLAN SHEET M2.16, SUPPLY DUCT FROM
 HPU-P-4-3 PENETRATES 2 RATED OPENINGS.
 FIRE DAMPERS REQUIRED.
  
 15. PLAN SHEET M2.19 THE PARTITION
 BETWEEN ROOM L114 & THE BATHROOMS
 INDICATE A RATED PENETRATION.ALL DUCTS
 THAT PENETRATE THIS PARTITION IS
 REQUIRED TO HAVE A FIRE DAMPER.
  
 16. PLAN SHEET M2.20 O.A. DUCT INTO
 RESTROOMS PENETRATES RATED CORRIDOR WALL
 WITH NO FIRE DAMPER INDICATED.PLESAE
 ALSO PROVIDE SEQUENCE OF OPERATION FOR
 THIS SYSTEM.
  
 17. PLAN SHEET M2.27 UNIT M, PLAN SHEET
 M2.29 UNIT B4, & M2.32 UNIT N INDICATES
 EXHAUSTDUCT IN RETURN AIR PLENUM.
 PLEASE REVISE.
  
 18. PLEASE NOTE, PLAN SHEET M5.01 IS
 MISSING FROM ONE SET OF PLANS.
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2006-02-23 Cont ID  
Sent By pkrauss Date 2006-02-21 Time 14:00 Rev Time 0.00
Received By pkrauss Date 2006-02-21 Time 14:00 Sent To  
Notes
2006-02-21 00:00:00SUBMITTAL - 2 HOUR ENCLOSURE IN
 STAIRWELL #4 WAS REMOVED IN PRELIMINARY
 DRAWING.PLEASE PROVIDE A REVISED A7.09
 SHEET & REVISED PLUMBING PLAN FOR THIS
 CHANGE.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-02-23 Cont ID  
Sent By pkrauss Date 2006-01-30 Time 06:30 Rev Time 0.00
Received By pkrauss Date 2006-01-26 Time 06:40 Sent To  
Notes
2006-01-30 00:00:00PLEASE CLARIFY THE FOLLOWING:
 COMMENT #1 FROM REVIEW DATED 9-1-05;
 PLAN SHEET M1.13 & A2.15 PAY-1 THROUGH 4
 ARE LOCATED IN AREA THAT IS ENCLOSED.
 PER CONVERSATION WITH MATT, LOUVERS ARE
 NOT INSTALLED AT OPENINGS.PLEASE SHOW
 COMPLIANCE WITH 2001 FMC CHAPTER 11
 SECTIONS 1102, 1103, 1104, & 1105.
  
 COMMENT #5 RESPONSE INDCIATES EXHAUST
 DUCTS THROUGH PLENUMS WILL BE SEPARATED
 BY A NON-RATED SEALED ENCLOSURE AS SHOWN
 IN DETAIL #2 PLANS SHEET A9.02.PLAN
 SHEET M2.01 APPEARS TO HAVE DRYER
 EXHAUST (COMBUSTIBLE) ALSO RUNNING
 THROUGH PLENUM.
  
 ADDITIONAL COMMENTS:
 PLAN SHEET A4.01 INDICATES 500 GAL FUEL
 TANK PER CONVERSATION WITH MATT, THE
 REMOTE FUEL TANK WAS ELIMATED.PLEASE
 REMOVE FROM PLANS.
  
 PLAN SHEET A7.09 DETAIL FOR STAIR #4
 INDICATES "2 HR RATED ENCLOSURE" THROUGH
 THE STAIRWELL.PLEASE CLARIFY WHY THIS
 ENCLOSURE IS NECESSARY.PLEASE NOTE,
 THE ONLY PENETRATIONS ALLOWED THROUGH OR
 INTO A STAIRWAYS ARE THE ITEMS LISTED
 UNDER 2001 FBC 1006.1.3.1.THE CODE
 DOES NOT ALLOW ANY PENETRATIONS WHETHER
 RATED OR NOT, IT STILL IS PENETRATING
 THE STAIRWAY.
  
 PLEASE CLARIFY THE DESIGNATION OF FIRE
 DAMPERS AND FIRE/SMOKE DAMPERS.SOME
 PENETRATIONS ONLY INDICATE FIRE DAMPERS
 WHEN IN FACT THEY SHOULD READ FIRE/SMOKE
 DAMPERS.
  
 PLEASE HAVE THE ADDITIONAL COMMENTS
 ADDRESSED WITH NEXT SUBMITTAL OR
 REVISION.
  
 PLEASE ALSO SEE COMMENTS #19 THROUGH 28
 BY ASST FIRE MARSHALL, MIKE CARSILLO.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-09-01 Cont ID  
Sent By pkrauss Date 2005-09-01 Time 09:53 Rev Time 0.00
Received By pkrauss Date 2005-09-01 Time 07:58 Sent To  
Notes
2005-09-01 00:00:00DENIED:
 1.PLAN SHEET M1.13 & A2.15, PLAN
 INDICATES PAU-1 THROUGH 4 ARE LOCATED IN
 AREA THAT IS ENCLOSED.PLEASE PROVIDE
 MANUFACTURER'S INTALLATION/SUBMITALL
 DATA FOR REVIEW.OA PACKAGE UNITS ARE
 TYPICALLY LOCATED OUTDOORS.
  
 2.PLEASE CLARIFY RATIONALE FOR THE
 SPF-3 (STAIRWELL PRESSURIZATION) IS THIS
 DUCTED TO THE OA LOUVER?PLAN INIDCATES
 EF-R-2 (POOL DECK ATTIC) EXHAUSTING INTO
 THE SAME ROOM AS PAU-1 & SPF-3.PER
 2001 FBC(M)501.3, MECHANICAL EXHAUST
 SYSTEMS SHALL TERMINATE OUTDOORS AT A
 POINT WHERE IT CANNOT BE RECIRCULATED BY
 THE VENTILATING SYSTEM. FRESH AIR IS TO
 BE TAKEN FROM THE OUTDOORS WHICH
 ACCORDING TO THE DEFINITION; OUTDOORS,
 NOT ENCLOSED; HAVING NO ROOF.
 PLEASE VERFIY ALL AREAS WHERE OUTSIDE
  
 AIR LOUVERS ARE LOCATED.
  
 3.PLAN SHEET M2.01, DOMESTIC WATER
 PUMP ROOM AND THE FIRE PUMP ROOM
 INDICATE OUTSIDE AIR FROM THE GARAGE
 AREA & EXHAUST ALSO GOING INTO THE
 GARAGE AREA.PER 2001 FBC(M)401.5.1,
 OUTSIDE AIR INTAKES SHALL BE LOCATED A
 MINIMUM OF 10FT FROM PARKING LOTS,
 STREETS, ALLEYS, AND LOADING DOCKS.
  
 4.PLAN SHEET M2.01 REFERS TO THE ARCH
 DWGS., PLEASE SPECIFY SHEET NUMBER.
 PROVIDE DETAIL OF THE SEALED ENCLOSURE.
  
 5.PLAN SHEET M2.02 UNIT GENERAL NOTES
 #1; AKK TOILET EXHAUST RUNNING INSIDE
 PLENUMS SHALL BE WRAPPED.PLEASE
 CLARIFY, ONLY DRYER EXHAUST DUCTS WILL
 BE ENCLOSED SEPERATELY?PER 2001 FBC(M)
 601.3, EXHAUST DUCTS UNDER POSITIVE
 PRESSURE & VENTING SYSTEMS SHALL NOT
 EXTEND INTO OR PASS THROUGH PLENUMS.
 PLANS STILL INDICATE EXHAUST DUCT
 THROUGH PLENUMS WITHOUT THE NOTE
 INDICATING A SEPERATE ENCLOSURE.
  
 6.PLANS INDICATE DRYER BOOSTER FANS
 WERE DELETED IN LEIU OF A SPECIFIC
 DRYER.PLEASE NOTE, SPECIFIC DRYER TO
 BE INSTALLED AT FINAL INSPECTION.
 DRYERS THAT EXHAUST GREATER THAN 2,000
 CFM SHALL BE PROVIDED WITH MAKE-UP AIR,
 2001 FBC(M)504.5.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-04-20 Cont ID  
Sent By pkrauss Date 2005-04-20 Time 06:49 Rev Time 0.00
Received By pkrauss Date 2005-04-19 Time 16:23 Sent To  
Notes
2005-04-19 00:00:00DENIED:
 RESPONSE COMMENTS FROM REVIEW DATED
 1/18/05:
 COMMENT #3 RESPONSE - SEE M2.01. PLAN
 DOES NOT PROVIDE DISTANCES FROM EXHAUST
 TERMINATION TO FRESH AIR INTAKES,
 WINDOWS, DOORS, LOUVERS, ETC.PROVIDE
 ELEVATION FROM GRADE.PLAN ALSO
 REFERENCES PLAN SHEET M6.01 FOR DETAILS.
 NO DETAILS PROVIDED ON SAID SHEET.
  
 COMMENT #4 - PROVIDE FILL PIPE
 INFORMATION FOR THE FUEL TANK INDICATED
 ON PLAN SHEET M2.01.PLAN SHEET A4.01
 INDICATES THE CAPACITY AS 500 GAL.
 PLEASE NOTE, ADDITIONAL PERMIT REQUIRED
 FOR FUEL.
  
 COMMENT #5 - PROVIDE SUBMITTALS;
 RESPONSE INDICATES SUBMITTALS TO BE
 PROVIDE WITH "SHOP DRAWING" REVIEW.
 EQUIPMENT SUBMITTALS ARE TO BE SUBMITTED
 WITH THE ENGINEERED PLANS.
  
 COMMENTS #10, 11 & 12 - EXHAUST DUCTS
 ARE RUNNING THROUGH THE RETURN AIR
 PLENUM. RESPONSE - REFER TO DRAWING
 M2.02, NOTES INDICATE WRAPPING DUCT.
 PLAN STILL INDICATES THE INSTALLATION OF
 DRYER BOOSTER FANS.THIS WILL NOT BE
 ACCEPTED UNTIL THE AN ENGINEER FROM
 DRYER MANUFACTURER ACCEPTS THIS ASSEMBLY
 AND VERIFIES THAT IT WILL NOT VOID THE
 WARRANTY ON THE DRYER.DUCTS THAT CARRY
 PRODUCTS OF COMBUSTION AND PRODUCE HEAT
 & MOISTURE SHALL NOT RUN THROUGH THE
 PLENUM. 2001FBC/M 504.1, 504.4, 601.3.
  
 COMMENT #14 - PROVIDE SUBMITTALS FOR ALL
 EQUIPMENT - RESPONSE "CORRECTED" BUT NO
 SUBMITTALS WERE PROVIDED.
  
 COMMENT #15 - O.A. CALCULATIONS -
 RESPONSE REFER TO DRAWING M5.04. OUTSIDE
 AIR CALCULATIONS WERE NOT PROVIDED FOR
 THE RESIDENTIAL UNITS.
  
 NEW COMMENTS:
 16. RETURN AIR FROM THE BEDROOM AREAS
 ARE NOT SIZED PROPERLY.PER 2001 FBC/M
 601.4 EXCEPTION 1, WHEN TRANSFER DUCTS
 ARE USED FOR RETURN AIR THE RETURN AIR
 DUCT SHALL BE A MINIMUM OF 1 1/2 TIMES
 THE SQUARE INCHES OF THE SUPPLY AIR INTO
 THAT SPACE.WHEN CALCULATING RETURN AIR
 FROM THE MASTER SUITE ALL AIR INTO THE
 MASTER SUITE IS TO BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-01-18 Cont ID  
Sent By pkrauss Date 2005-01-18 Time 16:34 Rev Time 0.00
Received By pkrauss Date 2005-01-18 Time 16:34 Sent To  
Notes
2005-01-18 00:00:00DENIED:
 1.THE FOLLOWING PLANS ARE INDICATED
 ON THE "INDEX" BUT WERE NOT INCLUDED:
 A1.02, A3.11, A3.12, A3.14, A3.15,
 A3.24, A4.14, A5.01, A5.11, A6.53A,
 A6.56A, A8.12, A8.13, A8.22, A8.23,
 A8.41A, A8.44, A9.22, A10.01, M1.14,
 M2.05, M2.07, M2.11, M2.19, M2.20,
 M2.33, M2.34, M2.35, M3.02, M4.00,
 M4.02, M4.03, M5.04, M6.01 THROUGH
 M6.09, M7.02.PLEASE NOTE, PLAN SHEET
 M7.02 IS MISSING BUT THERE ARE TWO
 M7.01 SHEETS THAT ARE NOT IDENTICAL,
 ONE
 MAY BE JUST MISMARKED.
  
 2.PLANS ARE NOT COMPLETE THEREFORE
 ADDITIONAL COMMENTS MAY ARRISE DUE TO
 THE RESPONSE TO 1ST REVIEW AND ANY NEW
 DETAILS ADDED.
  
 3.PLAN SHEET A1.03 GENERATOR RM.
 PLEASE PROVIDE ELEVATION FOR THE
 TERMINATION OF THE MUFFLER EXHAUST,
 SHOW
 CLEARANCES TO FRESH AIR INTAKES I.E.,
 DOORS, WINDOWS, LOUVERS, ETC.
  
 4.PROVIDE DETAILS FOR VENTILATION FOR
 THE GENERATOR ROOM.PLAN ALSO
 INDICATES
 A FUEL TANK.PROVIDE DETAILS FOR THE
 CAPACITY OF THE FUEL TANK, VENTING
 REQUIREMENTS AND FILL PIPE INFORMATION.
  
 5.PROVIDE SUBMTTIALS FOR THE
 GENERATOR
 AND FUEL TANK.
  
 6.PLAN SHEET 7.14 INDICATES TRASH
 CHUTE WITH THE SMOKE EXHAUST IN THE
 SAME
 SHAFT.PLEASE CLARIFY, INDICATE RATING
 OF SEPARATION.
  
 7.PLAN SHEET M1.05 (AND SUBSEQUENT
 SHEETS), INDICATE HPU-X OR EF-X.THESE
 ARE NOT IDENTIFIED ON THE RESPECTIVE
 EQUIPMENT SCHEDULES.
  
 8.EF-X DOES NOT INDICATE ANY
 TERMINATION, PLEASE CLARIFY.PLEASE
 NOTE, PER 2001 FBC(M)503.1 ARE REMOVED
 BY EVERY MECHANICAL EXHAUST SYSTEM
 SHALL
 BE DICHARGED TO THE OUTDOORS.
  
 9.PLANS DO NOT INDCLUDE DETAILS FOR
 COMMON AREAS.
  
 10. PLAN SHEETS M2.02, 2.03, 2.04, ETC,
 INDICATE DRYER EXHAUST & TOILET EXHAUST
 PENTRATING AND RUNNING THROUGH THE
 RETURN AIR PLENUM.PER 2001
 FBC(M)601.3, EXHAUST DUCTS UNDER
 POSITIVE PRESSURE SHALL NOT EXTEND INTO
 OR PASS THROUGH A RETURN AIR PLENUM.
  
 11.NO COMBUSTIBLES ALLOWED IN THE
 RETURN AIR PLENUM.PLEASE NOTE
 CONSTURCITON OF THE RETURN AIR PLENUM
 SHALL COMPLY WITH 2001 FBC(M) 603.8. THE
 DOOR TO THE MECHANICAL CLOSET HAVING A
 RETURN AIR PLENUM SHALL BE NON
 COMBUSTIBLE.
  
 12. PLANS INDICATE THE USE OF BOOSTER
 FANS FOR THE DRYER.PLEASE SUBMIT ALL
 DOCUMENTATION I.E., DRYER MANUFACTURER,
 BOOSTER FAN SUBMITTAL AND ENGINEERING
 DATA.THIS WILL BE REVIEWED UNDER 2001
 FBC 103.7.1, ALTERNATE MEANS AND
 METHODS
 AND WILL REQUIRE REVIEW AND APPROVAL BY
 THE BUILDING OFFICIAL/DIRECTOR.
  
 13.CW RISERS AND BRANCH LINES ARE NOT
 SIZED.(INCOMPLETE)
  
 14.PROVIDE SUBMITTALS FOR THE PUMPS,
 COOLING TOWERS, HEAT EXCHANGERS, HEAT
 PUMPS, EXHAUST FANS, AIR SEPARATOR,
 EXPANSION TANK AND ALL PERTINANT VALVES
 AND CONTROLS REQUIRED TO COMPLETE AND
 OPERATE SYSTEM.
  
 15.PROVIDE OUTSIDE AIR CALCULATIONS
 FOR ALL COMMON AREAS AS WELL AS THE
 RESIDENCE.SHOW COMPLIANCE WITH 2001
 FBC(M) TABLE 403.3 AND 402.
  
 16. CONDENSATE RISER ON PLAN SHEET
 P3.13
 & P3.14.PLAN SHEET P3.13 IS NOT IN
 THE
 SUBMITTAL AND PLAN SHEET P3.14 SHOWS A
 SANITARY RISER.
  
 17.PROVIDE PLANS FOR VENTILATION FOR
 ALL COMMON HABITABLE AREAS AS WELL AS
 NON HABITABLE (EQUIPMENT RMS,
 MECHANICAL
 ROOMS, ETC.)INDICATE ALL LOUVERS,
 DUCTS, EXAUST AND FRESH AIR INTAKES ON
 THE PLAN AND IDENTIFY ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 39 Status P Date 2008-08-15 Cont ID  
Sent By kstevens Date 2008-08-15 Time 13:34 Rev Time 0.00
Received By kstevens Date 2008-08-15 Time 13:34 Sent To  
Notes
2008-08-15 13:36:19REVISIONS OK--8-1/2" BY 11" REVISIONS TO SHEETS
 P2.03, P2.61 & P6.01 (2).

Review Stop P PLUMBING
Rev No 38 Status F Date 2008-08-07 Cont ID  
Sent By kstevens Date 2008-08-07 Time 14:38 Rev Time 0.00
Received By kstevens Date 2008-08-07 Time 14:38 Sent To E
Notes
2008-08-07 14:42:05REVISION DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1. SHTS LI-1, LI-2, LI-3 & LI-4 SHOW NO REVISIONS FROM
 PREVIOUS REVIEWED PLANS.--IN THE FUTURE SUBMIT ALL
 "REVISIONS" TO THE IRRIGATION UNDER THE IRRIGATION
 PERMIT 08020162. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 37 Status P Date 2008-06-03 Cont ID  
Sent By kstevens Date 2008-06-03 Time 08:54 Rev Time 0.00
Received By kstevens Date 2008-06-03 Time 08:54 Sent To  
Notes
2008-06-03 09:11:19SUBMITTAL APPROVED.--AIR GAP FITTING FOR TRAP
 PRIMER

Review Stop P PLUMBING
Rev No 36 Status P Date 2008-04-21 Cont ID  
Sent By kstevens Date 2008-04-21 Time 11:03 Rev Time 0.00
Received By kstevens Date 2008-04-21 Time 11:03 Sent To  
Notes
2008-04-21 11:04:40REVISION APPROVED. --WATER HEATER DETAIL SHT P601
 CHANGED FROM EXPANSION TANK TO EXPANSION VALVE
 CONNECTING TO PT/PAN DRAIN LINE WITH TRAP AND AIR GAP
 FITTING.

Review Stop P PLUMBING
Rev No 35 Status P Date 2008-02-06 Cont ID  
Sent By kstevens Date 2008-02-06 Time 12:25 Rev Time 0.00
Received By kstevens Date 2008-02-06 Time 12:25 Sent To  
Notes
2008-02-06 12:26:14SUBMITTALS APPROVED--WATER RECIRCULATING PUMP &
 EXPANSION VALVE

Review Stop P PLUMBING
Rev No 34 Status P Date 2008-01-25 Cont ID  
Sent By kstevens Date 2008-01-25 Time 09:04 Rev Time 0.00
Received By kstevens Date 2008-01-25 Time 09:04 Sent To  
Notes
2008-01-25 09:06:25SUBMITTALS APPROVED. TRENCH DRAINS, TERRACE/DECK
 DRAINS, FLOOR DRAINS, ROOF DRAINS, PLANTER DRAINS,
 SHOWER DRAINS.

Review Stop P PLUMBING
Rev No 33 Status F Date 2007-12-04 Cont ID  
Sent By kstevens Date 2007-12-04 Time 07:42 Rev Time 0.00
Received By kstevens Date 2007-12-04 Time 07:42 Sent To  
Notes
2007-12-04 07:45:46REVISION DENIED
 REFERENCE: CITY OF WEST PALM BEACH MUNICIPAL CODE
  
 1. SHTS P2.51 & P3.08 WATER LINES SHALL NOT CROSS
 PROPERTY LINES PER ARTICLE II SECTION 90-131(E). THE
 WATER FOR THE CABANA SHALL CONNECT TO WATER SUPPLY IN
 THE COMMON AREA.
  
 2. SHTS P2.5.1 & P3.08 A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE ICE MACHINE PER SECTION 604.9.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 32 Status P Date 2007-12-04 Cont ID  
Sent By kstevens Date 2007-12-04 Time 07:38 Rev Time 0.00
Received By kstevens Date 2007-12-04 Time 07:38 Sent To  
Notes
2007-12-04 07:42:02REVISIONS OK FOR PARTIAL SHEET P2.57 POOL DECK CABANA
 SINK DWV. FLOOR SINK REQUIRED FOR INDIRECT WASTE.
 PARTIAL SHEET P3.20 SANT. RISER #82 21ST FLOOR ONLY FOR
 THE CABANA SINK ON THE POOL DECK. FLOOR SINK REQUIRED
 FOR INDIRECT WASTE.

Review Stop P PLUMBING
Rev No 31 Status P Date 2007-10-15 Cont ID  
Sent By kstevens Date 2007-10-15 Time 09:53 Rev Time 0.00
Received By kstevens Date 2007-10-15 Time 09:53 Sent To  
Notes
2007-10-15 09:54:55SUBMITTAL OK--OUTDOOR POOL SHOWER FIXTURE

Review Stop P PLUMBING
Rev No 30 Status P Date 2007-10-13 Cont ID  
Sent By kstevens Date 2007-10-13 Time 06:29 Rev Time 0.00
Received By kstevens Date 2007-10-13 Time 06:29 Sent To  
Notes
2007-10-13 06:30:17SUBMITTAL APPROVED--DECO-DRAIN DECK DRAIN

Review Stop P PLUMBING
Rev No 29 Status F Date 2007-08-25 Cont ID  
Sent By kstevens Date 2007-08-25 Time 08:58 Rev Time 0.00
Received By kstevens Date 2007-08-25 Time 08:57 Sent To  
Notes
2007-08-25 09:12:59REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P2.49 WATER SUPPLY FOR TRASH CHUTE WASH DOWN IS
 SHOWN CONNECTING TO THE CONDENSATE RISER DIAGRAM.--
 REVISION #8 NOT FOUND OR APPROVED. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 2. SHT P2.64 DECK DRAINS SHALL BE LOCATED AT AT THE LOW
 POINT OF THE DECK. MANY (APPROX. 14), ARE SHOWN IN
 LOCATIONS OTHER THAN THE LOW POINT. PLEASE CORRELATE
 WITH THE ARCHITECT TO MAKE SURE THE DECKS DRAIN
 PROPERLY. SECTION 1101.7.
  
 3. SHTS P3.01 & P3.02 THE WATER SUPPLY LINES TO THE
 TRASH CHUTE SHALL INCLUDE BACKFLOW PROTECTION PER
 SECTION 608.1 AND TABLE 608.1 AND SHALL HAVE A SHUT OFF
 VALVE AS REQUIRED IN SECTION 606.2(3).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 28 Status P Date 2007-08-25 Cont ID  
Sent By kstevens Date 2007-08-25 Time 08:49 Rev Time 0.00
Received By kstevens Date 2007-08-25 Time 08:49 Sent To  
Notes
2007-08-25 08:57:47REVISIONS OK - SHTS P2.01, P2.03 THRU P2.07, (P2.06 MAX
 6' FROM VENT TABLE 906.1), P2.09 THRU P2.12, P2.15,
 (REVISION 8 NOT FOUND OR APPROVED), P2.18, P2.21, P2.23
 THRU P2.25, P2.27, P2.28, P2.30, P2.52, P2.62, P2.63
 --P3.00, P3.22, P3.32, P3.37, P3.38, P3.39, (10"
 REQUIRED PRIOR OR BRANCH LINE TO 6"DD 2706SF PRIOR TO
 BREAK IN LINE)--P6.01, (REVISION 6 NOT FOUND OR
 APPROVED.

Review Stop P PLUMBING
Rev No 27 Status P Date 2007-04-04 Cont ID  
Sent By kstevens Date 2007-04-04 Time 17:12 Rev Time 0.00
Received By kstevens Date 2007-04-04 Time 17:12 Sent To  
Notes
2007-04-04 17:13:23SUBMITTAL OK - SHOWER DRAIN

Review Stop P PLUMBING
Rev No 26 Status P Date 2007-04-04 Cont ID  
Sent By kstevens Date 2007-04-04 Time 17:10 Rev Time 0.00
Received By kstevens Date 2007-04-04 Time 17:10 Sent To  
Notes
2007-04-04 17:12:36REVISION OK - SHTS P2.52, P2.57, P2.58, P3.00, P3.02,
 P3.05, P3.39.

Review Stop P PLUMBING
Rev No 25 Status P Date 2007-03-06 Cont ID  
Sent By kstevens Date 2007-03-06 Time 11:53 Rev Time 0.00
Received By kstevens Date 2007-03-06 Time 11:53 Sent To  
Notes
2007-03-06 11:54:35FOUR SUBMITTALS OK - TRAP PRIMER TAIL PIECES, SUMP PUMP
 & BASIN,LAUNDRY BOXES, SHOWER PAN MATERIAL

Review Stop P PLUMBING
Rev No 24 Status F Date 2007-02-22 Cont ID  
Sent By kstevens Date 2007-02-22 Time 18:48 Rev Time 0.00
Received By kstevens Date 2007-02-21 Time 18:48 Sent To  
Notes
2007-02-22 18:58:17REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P2.52 UNIT TYPES S1 & R ARE INDICATING SUPPLYING
 WATER TO THE ROOF LEVEL FOR THE SHOWER, DRINKING
 FOUNTAIN AND HOSE BIBB AT THE POOL AREA. THIS IS NOT
 APPROVED AND THE WATER FOR COMMON AREA USAGE SHALL BE
 SUPPLIED FROM COMMON AREA WATER SUPPLY, NOT FROM THE
 DWELLING UNITS. SECTIONS 608.1 & 103.6 AND TABLE
 608.1.
  
 2. SHT P2.58 4" DD & 3" SANT. LINE NOT INDICATED ON
 PREVIOUS REVISIONS. SECOND SHOWER LINE BEHIND ELEVATORS
 AS INDICATED ON SHT P2.52 NOT SHOWN. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 3. SHT P3.05 UNIT S & S1 SHOWS SHOWER, HOSE BIBB &
 DRINKING FOUNTAIN WATER SUPPLY FROM DWELLING UNIT.
 WATER SUPPLY SHALL BE CONNECTED TO THE COMMON AREA
 WATER SUPPLY. SECTIONS 608.1, 103.6 AND TABLE 608.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 23 Status P Date 2007-02-22 Cont ID  
Sent By kstevens Date 2007-02-22 Time 18:45 Rev Time 0.00
Received By kstevens Date 2007-02-21 Time 18:45 Sent To  
Notes
2007-02-22 18:48:17REVISIONS OK.REVISION #9 ON SHEETS P201, P203, P204,
 P205, P207, P209, P210, P212, P214, P217, P218, P220,
 P223, P224, P225, P226, P227, P229, P233, P264, P302,
 P322, P328, P330, P331, P333, P334, P338 & P339.

Review Stop P PLUMBING
Rev No 22 Status P Date 2006-12-06 Cont ID  
Sent By kstevens Date 2006-12-06 Time 10:40 Rev Time 0.00
Received By kstevens Date 2006-12-06 Time 10:40 Sent To  
Notes
2006-12-06 10:42:26SUBMITTALS APPROVED. SOLDER PASTE, (FLUX), EXPANSION
 TANK, BOOSTER PUMP, HAND SHOWER

Review Stop P PLUMBING
Rev No 21 Status P Date 2006-10-30 Cont ID  
Sent By kstevens Date 2006-10-30 Time 17:44 Rev Time 0.00
Received By kstevens Date 2006-10-30 Time 17:44 Sent To  
Notes
2006-10-30 18:08:03SUBMITTALS OK
  
 #15455.01 GARAGE SUMP PUMP, - #15430.05.01 UNIT ELECT
 WATER HEATERS, COMMON AREA WATER HEATERS, - #02520.02
 DECO DRAIN, -#15430.09 RPZV BACKFLOW PREVENTERS, -
 02900.01 IRRIGATION PRODUCTS

Review Stop P PLUMBING
Rev No 20 Status P Date 2006-10-23 Cont ID  
Sent By kstevens Date 2006-10-23 Time 18:03 Rev Time 0.00
Received By kstevens Date 2006-10-23 Time 18:03 Sent To  
Notes
2006-10-23 18:15:25REVISION #8
  
 THE FOLLOWING SHEETS ARE OK.
 P2.01 THRU P2.07, P2.09 THRU P2.12, P2.14, P2.16 THRU
 P2.18, P2.20 THRU P2.35, P2.37 THRU P2.41, P2.43,
 P2.48, P2.50, P2.52, P2.53, P2.55, P2.56, P2.59, P2.61
 THRU P2.64, P300 THRU P3.03, P3.16 THRU P3.19, P3.21,
 P3.23, P3.25 THRU P3.39 & P3.41
  
 THE FOLLOWING SHEETS ARE DENIED:
  
 P2.08, REVISIONS LEFT OF COL. LINE 12/H & BETWEEN COL.
 LNES 11 & 12 ON COL. H. NO REVISIONS NOTED. PLEASE
 CLARIFY. SECTION 104.2.1. - REVISION IN STAIRWELL #1
 APPEARS TO BE A FIRE SPRINKLER REVISION. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 SHT P2.15 PAN DRAIN STILL SHOWN DRAINING INTO THE
 PARKING GARAGE. (NO CHANGE NOTED) SECTION 504.8.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 19 Status P Date 2006-09-07 Cont ID  
Sent By jleech Date 2006-09-07 Time 09:06 Rev Time 0.00
Received By jleech Date 2006-09-07 Time 09:06 Sent To  
Notes
2006-09-07 00:00:00SUBMITAL; CHARLOTTE CAST IRON PIPE TO BE
 USED

Review Stop P PLUMBING
Rev No 18 Status P Date 2006-08-24 Cont ID  
Sent By mperson Date 2006-08-24 Time 08:51 Rev Time 1.00
Received By mperson Date 2006-08-24 Time 08:51 Sent To PC
Notes
2006-08-24 00:00:001. SUBMITTAL #15410.03.01, DUCTILE IRON
 PIPE AND FITTINGS (OK)
 2. SUBMITTAL #15400.05.01, CPVC PIPE AND
 FITTINGS (OK)
 3. SUBMITTAL #15450.01.01, PROPRESS
 RIDGID SYSTEM FOR COPPER PIPE (OK)
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 17 Status N Date 2006-08-23 Cont ID  
Sent By mperson Date 2006-08-23 Time 13:38 Rev Time 4.00
Received By mperson Date 2006-08-23 Time 13:38 Sent To PC
Notes
2006-08-23 00:00:001. SUBMITTAL #15047.01 PIPE
 IDENTIFICATION AND VALVE TAGS (OK)
 2. SUBMITTAL #15181.01 CRETE SLEEVES
 (OK)
 3. SUBMITTAL #15400.04 WASHING MACHINE
 BOX (OK)
 4. SUBMITTAL #15410.04 DUTCH BOY SOLDER
 MSDS SHEETS (OK)
 5. SUBMITTAL #15410.05 SOLDER PASTE FLUX
 (DENIED)
 A) THE SUBMITTAL FOR OATLY PASTE FLUX
 #5 DOES NOT SHOW COMPLIANCE FBC-2004,
 PLUMBING, SECTION 605.14.3 AND 605.15.4
 FLUX CONFORMING TO ASTM B 813 SHALL BE
 APPLIED, PLEASE SUBMIT MANUFACTURER
 SHEET FOR SAID SUBMITTAL CONFORMING TO
 ASTM B 813 OR PLEASE SUBMIT ANOTHER.
 6. SUBMITTAL #15430.07 HOSE BIBBS (OK)
 7. SUBMITTAL #15430.08 TRAP PRIMERS AND
 WATER ARRESTERS (OK)
 "EXCEPTION"
 A)SEMI CAST TRAP PRIMER TLPC (DENIED)
 MORE INFORMATION REQUIRED, PLEASE SUBMIT
 MANUFACTURER SHEETS WITH SAID SUBMITTAL
 CONFORMING TO FBC-2004 PLUMBING, CHAPTER
 10.
 8. SUBMITTAL #15455.02 DRAINAGE PIPE AND
 FITTINGS (OK)
 9. SUBMITTAL #15455.03 VENT THROUGH ROOF
 FLASHINGS (OK)
 10. SUBMITTAL #15484.01 OATLY CHEMICALS
 MSDS SHEETS (OK)
 11. SUBMITTAL #15484.03 HERCULES PIPE
 DOPE (OK)
 12. SUBMITTAL #15499.01 PLUMBING PIPE
 INSULATION (OK)
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 16 Status P Date 2006-08-17 Cont ID  
Sent By kstevens Date 2006-08-17 Time 13:23 Rev Time 0.00
Received By kstevens Date 2006-08-15 Time 13:50 Sent To  
Notes
2006-08-17 00:00:00SUBMITTAL APPROVED. CAST IRON PIPE,
 FITTINGS AND COUPLINGS.

Review Stop P PLUMBING
Rev No 15 Status F Date 2006-08-12 Cont ID  
Sent By kstevens Date 2006-08-12 Time 17:25 Rev Time 0.00
Received By kstevens Date 2006-08-07 Time 18:56 Sent To  
Notes
2006-08-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT P2.01 FLOOR DRAIN NOT APPROVED IN
 THE STAIRWELL. (SEE REVIEW NOTE #1 FROM
 REVIEW #9). NFPA 101, 2003 CHAPTER 7
 SECTION 7.1.3.2.1(6).
  
 2. SHT P2.02 W/H PAN DRAIN NOT APPROVED
 TO TERMINATE IN PARKING GARAGE. SECTION
 504.8.2.
  
 3. SHT P2.03 W/H PAN DRAIN NOT APPROVED
 TO TERMINATE IN THE PARKING GARAGE.
 SECTION 504.8.2. - VENT REQUIRED FOR 2"
 FLOOR DRAIN IN TRASH TERMINATION ROOM.
 SECTION 901.2.1 AND TABLE 906.1.
  
 4. SHT P2.04 REVISION #5 SHOWN ON SHEET
 WAS NOT APPROVED.
  
 5. SHT P2.06 REVISION #5 NOT APPROVED. -
 VENT REQUIRED FOR FLOOR DRAIN THE THE
 TRASH TERMINATION ROOM. SECTION 901.2.1
 AND TABLE 906.1. - UNIT 14 SHOWS NO WASH
 MACHINE & PTR/PD LINES NOT SHOWN TO W/H.
 PLEASE CLARIFY. SECTION 104.2.1. - FLOOR
 DRAIN NOT APPROVED IN THE STAIRWELL.
 NFPA 101, 2003 CHAPTER 7 SECTION
 7.1.3.2.1(6).
  
 6. SHT P2.11 WATER HEATER PAN DRAIN NOT
 APPROVED TO TERMINATE IN THE PARKING
 GARAGE. SECTION 504.8.2.
  
 7. SHT P2.18 UNITS H3 & HD WATER LINE
 OFFSETS FOR RISERS W10 THRU W14 HAVE
 BEEN DELETED, BUT RISER DESIGNATION ARE
 STILL SHOWN. PLEASE CLARIFY. SECTION
 104.2.1. - WATER PIPING LAYOUTS DELETED
 FROM UNITS V1 & HD. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 8. SHT P3.27 FLOOR DRAIN NOT APPROVED IN
 THE STAIRWELL. NFPA 101 2003.
  
 9. SHT P3.28 WASTE REMOVAL SYSTEM. A
 GATE VALVE AND CHECK VALVE ARE REQUIRED
 ON THE DISCHARGE LINE FROM THE PUMP.
 SECTION 712.2. - A VENT IS REQUIRED ON
 THE 2" FLOOR DRAIN. SECTION 901.2.1 AND
 TABLE 906.1. - NOTE READS ALL SANT.
 PIPING TO BE RUN 1/8"/FT. 2-1/2" AND
 SMALLER PIPE TO BE RUN 1/4"/FT PER TABLE
 704.1. - RISER SHOWS ONLY RISERS 10/56
 DOWN, BUT RISER 59 CONNECTS TO THE
 COMMON RISER ALSO. PLEASE CORRELATE.
 SECTION 104.2.1.
  
 10. SHT P3.30 FLOOR DRAIN NOT APPROVED
 IN STAIRWELL. NFPA 101, 2003 SECTION
 7.1.3.2.1(6). - VENT REQUIRED FOR FLOOR
 DRAIN TO SPRINKLER SYSTEM DRAIN. SECTION
 901.2.1 AND TABLE 906.1.
  
 11. SHT P3.31 FLOOR DRAIN NOT APPROVED
 IN THE STAIRWELL. NFPA 101 2003.
  
 12. SHT P3.32 WASTE REMOVAL SYSTEM. (SEE
 COMMENT #8).
  
 13. SHT P3.36 FLOOR DRAIN NOT APPROVED
 IN THE STAIRWELL. NFPA 101, 2003
  
 14. SHT P6.01 TRASH CHUTE PIPING
 SCHEMATIC DETAIL. INDICATE BACKFLOW
 PROTECTION METHOD AND LOCATION. (MINIMUM
 N-36 VACUUM BREAKER.
  
 15. THE FOLLOWING SHEETS WERE APPROVED.
 P0.01, P2.05, P2.07 THRU P2.10, P2.13
 THRU P2.17, P2.19 THRU P2.30, P2.32 THRU
 P2.39, P2.41 THRU P2.54, P2.56 THRU
 P2.60, P2.64, P3.00 THRU P3.04, P3.12,
 P3.17 THRU PE.26, P3.29, P3.33 THRU
 P3.35, P3.37 THRU P3.39.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 14 Status F Date 2006-07-31 Cont ID  
Sent By mperson Date 2006-07-31 Time 13:58 Rev Time 0.00
Received By mperson Date 2006-07-31 Time 13:58 Sent To  
Notes
2006-07-31 00:00:00THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW FOR THE
 FOLLOWING SUBMITTALS:
  
 1. SUBMITTAL #15400.01 THERMAL EXPANSION
 TANK.(DENIED)
 A) WHEN REQUIRED BY TABLE 303.4
 PLUMBING PRODUCTS AND MATERIALS SHALL
 EITHER BE TESTED BY AN APPROVED
 THIRD-PARTY TESTING AGENCY OR CERTIFIED
 BY AN APPROVED THIRD-PARTY CERTIFICATION
 AGENCY.
 B) NEED PRODUCT DATA STATING THE
 THERMAL EXPANSION TANK SUFFICIENT FOR
 THR 80 GALLON WATER HEATER.
 2. SUBMITTAL #15450.03 HOT WATER
 CIRCULATING PUMP. (DENIED)
 A) WHEN REQUIRED BY TABLE 303.4
 PLUMBING PRODUCTS AND MATERIALS SHALL
 EITHER BE TESTED BY AN APPROVED
 THIRD-PARTY TESTING AGENCY OR CERTIFIED
 BY AN APPROVED THIRD-PARTY CERTIFICATION
 AGENCY.
  
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop P PLUMBING
Rev No 13 Status P Date 2006-07-31 Cont ID  
Sent By mperson Date 2006-07-31 Time 13:42 Rev Time 0.00
Received By mperson Date 2006-07-31 Time 13:42 Sent To PC
Notes
2006-07-31 00:00:001. SUBMITTAL #15410.02 COPPER TUBE AND
 FITTING TYPE-L & DWV (OK)
 2. SUBMITTAL 315484.04 STEEL PIPE (OK)
 3. SUBMITTAL #15420.01 NIBCO BALL,
 CHECK, AND GATE VALVES (OK)
 4. SUBMITTAL #15450.02 VICTAULIC COPPER
 SYSTEM (OK)
 5. SUBMITTAL # 15400.03 WATER METER FOR
 COOLING TOWER MAKE UP WATER (OK)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 12 Status P Date 2006-07-21 Cont ID  
Sent By jleech Date 2006-07-21 Time 14:47 Rev Time 0.00
Received By jleech Date 2006-07-21 Time 14:47 Sent To  
Notes
2006-07-21 00:00:00SUBMITAL #15430.01;
 1.SIGMA ROMAN TUB FILLER; NOT ENOUGH
 INFORMATION. CUT SHEET SHOULD BE ON
 MANUFACTURE'S LETTER HEAD. IS SIGMA THE
 MANUFACTURE OR PRODUCT NAME? PRODUCT
 MUST HAVE A BUILT IN CHECK VALVE NOT
 SHOWN ON SHEET PROVIDED.
 2.PUBLIC FIXTURES; HANDICAP TOILET
 SPECIFICATION SHEET NOT PROVIDED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 11 Status P Date 2006-07-21 Cont ID  
Sent By jleech Date 2006-07-21 Time 09:50 Rev Time 0.00
Received By jleech Date 2006-07-21 Time 09:50 Sent To  
Notes
2006-07-21 00:00:00PLUMBING SUBMITAL # 15455.01.01 OK

Review Stop P PLUMBING
Rev No 10 Status P Date 2006-07-20 Cont ID  
Sent By jleech Date 2006-07-20 Time 14:13 Rev Time 0.00
Received By jleech Date 2006-07-20 Time 14:13 Sent To  
Notes
2006-07-20 00:00:00SUBMITAL NO. 15444.01.01
 OK LESS WELL MATE TANK.
  
  
 1. CLEARITY OF DOCUMENT IS REQUIRED ;
 LOCATION OF TANKS NOT SHOWN ON
 PLANS.
 WHAT MODEL NUMBER WILL BE USED.
 PARTS OF SPEC SHEET NOT READABLE.
 PLEASE RESUBMIT WITH THE ABOVE
 INFORMATION.

Review Stop P PLUMBING
Rev No 9 Status P Date 2006-07-03 Cont ID  
Sent By kstevens Date 2006-07-03 Time 17:17 Rev Time 0.00
Received By kstevens Date 2006-06-29 Time 10:27 Sent To  
Notes
2006-07-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
  
  
  
 7-4A. SHT P2.10 CHANGE 10.3 PTR RISER
 SHOWN IS NOT SHOWN ON THE GROUND FLOOR.
 WHERE DOES THIS RISER TERMINATE? PLEASE
 CLARIFY. SECTION 104.2.1.
 ***THIS SHEET HAS NOT BEEN REVISED AS
 REQUIRED IN THE PROVISO.
  
 8-4A. SHT P2.14 CHANGE 13.1 OFFSET TO
 RISER 10 DOES NOT REFLECT THE FLOOR
 PLAN. PLEASE CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1.
 ***THIS SHEET HAS NOT BEEN REVISED AS
 REQUIRED IN THE PROVISO.
  
 11-4A. SHT P2.35 CHANGE 31.1 OFSET NOT
 SHOWN ON THE RISER DIAGRAM. SECTION
 104.2.1.
 ***THIS SHEET HAS NOT BEEN REVISED AS
 REQUIRED IN THE PROVISO.
  
 14-4A. SHT P2.44 CHANGE 37.4 VENT PIPING
 LAYOUT DOES NOT REFLECT RISERS 10A, 11,
 11A AND 12 AS INDICATED. PLEASE
 CORRELATE RISERS AND FLOOR PLAN. SECTION
 104.2.1.
 ***RESPONSE NOTED, BUT NO VENT FROM
 RISER #11 IS SHOWN ON THE FLOOR PLAN.
  
 19-4A. SHT P3.17 NEW SHEET OFFSET VENTS
 REQUIRED ON RISER 54A AT THE 5TH FLOOR
 OFFSET. SECTIONS 915.2 & 915.3.
 ***RESPONSE NOTED, BUT THE UPPER OFFSET
 VENT IS NOT SHOWN. SECTION 915.2. (ALSO
 SEE RISER #6 UPPER OFFSET VENT NOT
 SHOWN).
  
 2-E SHTS P2.11, P2.12, & P2.15 PAN DRAIN
 SHALL NOT TERMINATE IN THE PARKING
 GARAGE. SECTION 504.8.2. - EXPLAIN HOW
 DRAINING THE PTR DISCHARGE LINE INTO THE
 GARAGE PARKING MEETS THE REQUIREMENT FOR
 A SAFE DISCHARGE. SECTION 604.7.1.
 ***RESPONSE NOTED, BUT PAN DRAIN LINE
 STILL SHOWN DISCHARGING INTO THE PARKING
 GARAGE.
  
 *************REVISION NOTES*************
  
 1. SHT P2.01 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101, 2003
 CHAPTER 7 SECTION 7.1.3.2.1(6).
  
 2. SHT P2.02 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6). - PAN DRAIN TO GARAGE NOT
 APPROVED. SECTION 504.8.2.
  
 3. SHT P2.03 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6). - CLOUD AND NUMBER ALL
 REVISIONS. SECTION 104.2.1.3.
  
 4. SHT P2.04 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6). - PAN DRAIN LINE TO GARAGE
 NOT APPROVED. SECTION 504.8.2.
  
 5. SHT P2.06 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6). - PAN DRAIN LINE TO GARAGE
 NOT APPROVED. SECTION 504.8.2.
  
 6. SHT P2.08 FLOOR DRAIN I EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6). - VENT REQUIRED FOR FLOOR
 DRAIN. SECTION 901.2.1.
  
 7. SHT P3.27 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6).
  
 8. SHT P330 2 FLOOR DRAINS IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6).- VENT REQUIRED FOR FLOOR
 DRAIN AT STAIRWELL #3. SECTION 901.2.1.
  
 9. SHT P3.31 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6).
  
 10. SHT P3.36 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6).
  
 11. THE FOLLOWING SHEETS WERE APPROVED:
 P2.05, P2.07, P2.12, P2.17, P2.26,
 P2.27, P2.28, P2.33, P2.36, P2,39,
 P2.4O, P2.45, P2.51, P2.61, P3.00,
 P3.04, P3.16, P3.18, P3.19, P3.20,
 P3.21, P3.22, P3.23, P3.24, P3.25,
 P3.26, P3.28, P3.29, P3.32, P3.33,
 P3.34, P3.35, P3.37, P3.40, & P3.41
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 8 Status P Date 2006-06-27 Cont ID  
Sent By pschmitz Date 2006-06-27 Time 08:55 Rev Time 0.00
Received By pschmitz Date 2006-06-27 Time 08:55 Sent To  
Notes
2006-06-27 00:00:00SUBMITAL FOR MATCO-NORCA NO HUB CAST
 IRON PIPE AND FITTINGS.
 CERTIFIED BY IAMPO TO
 ASTM A-888 & CISPI 301.

Review Stop P PLUMBING
Rev No 7 Status P Date 2006-06-10 Cont ID  
Sent By kstevens Date 2006-06-10 Time 09:55 Rev Time 0.00
Received By kstevens Date 2006-06-10 Time 09:55 Sent To  
Notes
2006-06-10 00:00:00SUBMITTAL OK - CHANGED TO ALTERNATE
 WATER HEATERS

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-03-27 Cont ID  
Sent By kstevens Date 2006-03-27 Time 17:34 Rev Time 0.00
Received By kstevens Date 2006-03-27 Time 17:34 Sent To  
Notes
2006-03-27 00:00:00PASSED PROVISO
  
  
 THE FOLLOWING SHEETS SHALL BE REVISED
 WITH THE COMMENTS FROM REVIEW NUMBER 5
 TO BE ADDRESSED. THESE COMMENTS HAVE
 BEEN GENERATED FROM CHANGES BY THE
 CONTRACTOR & ENGINEER. (4A)
 SHEETS P2.04 - P2.61 - P2.06 - P2.10 -
 P2.14 - P2.26 - P2.27 - P2.35 - P2.36 -
 P2.44 - P2.45 - P2.61 - P3.17 - P3.22 -
 P3.24 - P3.26 - P3.28 - P3.29 - P3.30 -
 P3.31 - P3.32 - P3.33 - P3.34 - P3.36 -
 P3.37 - P3.40 - P3.41. (NOTE FIRE LINE
 DISCHARGE TO STORM SYSTEM NOT APPROVED
 PER CITY CODE SECTION 90-203).
  
 THESE REVISIONS SHALL BE SUBMITTED FOR
 REVIEW AS SOON AS POSSIBLE WITH THE
 MAXIMUM TIME LIMIT OF 30 DAYS AFTER THE
 PERMIT IS ISSUED FOR BLG-COM.

Review Stop P PLUMBING
Rev No 5 Status F Date 2006-03-24 Cont ID  
Sent By kstevens Date 2006-03-24 Time 21:29 Rev Time 0.00
Received By kstevens Date 2006-03-14 Time 18:59 Sent To  
Notes
2006-03-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW: (FROM 1ST REVIEW)
  
 12) SHT A4.41 KITCHEN SINK AND JUICE BAR
 SINK IN COMMON AREAS SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL. RESPONSE NOTED, BUT NO
 DETAIL WAS FOUND. - THIS WILL BE A FIELD
 INSPECTOR APPROVAL. IF COMMON USE AREA
 IS AVAILABLE TO TENANTS AND SUESTS, ALL
 REQUIREMENTS OF SECTION 11-4.24 WILL BE
 ADHERED TO. - DETAIL SUBMITTED IS FOR
 THE DWELLING UNITS. SINKS INDICATED
 SHALL COMPLY AS REQUIRED IN SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.24.2 HEIGHT, 11-4.24.3 KNEE
 CLEARANCE, 11-4.24.4 SINK DEPTH,
 11-4.24.5 CLEAR FLOOR SPACE, (FORWARD
 APPROACH), 11-4.24.6 EXPOSED PIPES AND
 SURFACES, AND 11-4.24.7 FAUCETS.
  
 NEW COMMENTS GENERATED FROM CHANGES TO
 PLANS. 4/A:
 1-4A. SHEET P2.37 MISSING FROM ONE SET
 OF PLANS.
 2-4A. NEW SEAL REQUIRED FOR ENGINEER
 EFFECTIVE 1-1-06. SEE ATTACHED SHEET
 FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS.
 3-4A. SHT P2.04, CHANGE 4.1 CONDENSATE
 DRAIN PIPING SHOWS EXTRA LINES TO UNITS
 11 AND 12. PLEASE CLARIFY. SECTION
 104.2.1.
 4-4A. SHT P2.05 CHANGE 5.3 CONDENSATE
 DRAIN FOR A/C UNIT P1-5 NOT SHOWN ON SHT
 P2.61 AS NOTED. PLEASE CLARIFY. SECTION
 104.2.1.
 5-4A. SHT P2-06 CHANGE 6.4 PLEASE
 INDICATE WHAT IS DRAINING INTO THE 3" FD
 CONNECTED TO RWL'S 7 & 8.
 6-4A. SHT P2.06 CHANGE 6.4 CONDENSATE
 DRAIN 28A DOES NOT CONNECT TO RISER C14,
 15, 16, 24 & 26. RISER SHOWS 24A & 26A
 CONNECTING TO THIS RISER. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
 7-4A. SHT P2.10 CHANGE 10.3 PTR RISER
 SHOWN IS NOT SHOWN ON THE GROUND FLOOR.
 WHERE DOES THIS RISER TERMINATE? PLEASE
 CLARIFY. SECTION 104.2.1.
 8-4A. SHT P2.14 CHANGE 13.1 OFFSET TO
 RISER 10 DOES NOT REFLECT THE FLOOR
 PLAN. PLEASE CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1.
 9-4A. SHT P2.26 CHANGE 24.1 HORIZONTAL
 BRANCH SHALL NOT CONNECT WITHIN THE
 HORIZONTAL STACK OFFSET OR WITH 2 FEET
 ABOVE OR BELOW SUCH OFFSET. SECTION
 711.2
 10-4A. SHT P2.27 CHANGE 25.1 NOT ALL
 VENT PIPING IS SHOWN ON THE FLOOR PLAN.
 SECTION 104.2.1.
 11-4A. SHT P2.35 CHANGE 31.1 OFSET NOT
 SHOWN ON THE RISER DIAGRAM. SECTION
 104.2.1.
 12-4A. SHT P2.36 CHANGE 32.1 VENTING NOT
 SHOWN FOR BATH #2. SECTION 104.2.1.
 13-4A. SHT 2.44 CHANGE 37.3 UNIT P2
 PIPING DOES NOT REFLECT RISER 59. NO
 VENT CONNECTION FROM W/M TO L/SK AND
 FLOOR PLAN SHOWS THE RISER BEHIND THE
 LAUNDRY SINK. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
 14-4A. SHT P2.44 CHANGE 37.4 VENT PIPING
 LAYOUT DOES NOT REFLECT RISERS 10A, 11,
 11A AND 12 AS INDICATED. PLEASE
 CORRELATE RISERS AND FLOOR PLAN. SECTION
 104.2.1.
 15-4A. SHT P2.45 CHANGE 38.3 NOT ALL
 VENT PIPING WAS ADDED TO REFLECT THE
 RISER DIAGRAM. PLEASE CORRELATE. SECTION
 104.2.1.
 16-4A. SHT P2.61 CHANGE 47.1 STORM
 RISERS6, 7 & 8, 9 & 10, AND DOWNSTREAM
 OF 4 & 5 SHOW 3" FLOOR DRAINS. PLEASE
 INDICATE WHAT IS DRAINING INTO THESE
 FD'S. SECTION 104.2.1.
 17-4A. SHT P2.61 CHANGE 47.1 STORM
 PIPING DOWNSTREAM OF WHERE RWL 1 & RWL
 11 TIE TOGETHER SHALL BE 12". 10" SHOWN.
 DOWNSTREAM OF THAT THE STORM DRAIN SHOWS
 16" PIPE BUT IS SHOWN AS 15" ON THE
 RISER DIAGRAM. PLEASE CORRELATE. SECTION
 104.2.1.
 18-4A. SHT P2.61 CHANGE 47.1 CONDENSATE
 LINE LEFT OF RWL 1, PLEASE INDICATE WHAT
 RISERS ARE BEING PICKED UP BY THE 3
 LINES. NO INDICATION OF WHAT IS
 CONNECTING TO THESE LINES. PLEASE
 CLARIFY. SECTION 104.2.1.
 19-4A. SHT P3.17 NEW SHEET OFFSET VENTS
 REQUIRED ON RISER 54A AT THE 5TH FLOOR
 OFFSET. SECTIONS 915.2 & 915.3.
 20-4A. SHT P3.22 NEW SHEET RISERS 28 &
 84 LAV FOR 6TH FLOOR MISSING AND THE W/M
 IS ON THE WRONG STACK. CORRELATE RISER
 AND FLOOR PLAN. SECTION 104.2.1.
 21-4A. SHT P3.24 VENT PIPING DOES NOT
 REFLECT THE ROOF VENT LAYOUTS. VENTING
 ALSO INDICATE "TO 31" WHEN THE VENTS ARE
 COMMING FROM 31. SUBMIT A RISER
 ISOMETRIC DIAGRAM FOR THE VENT PIPING
 SHOWING ALL PIPE SIZES, TOTAL DEVELOPED
 LENGTH AND INDICATE FIXTURE UNITS AS
 THEY ACCUMULATE IN THE VENT SYSTEM.
 TABLE 916.1
 22-4A. SHT P3.26 CHANGE 64.1 WATER
 CLOSET IS NOT VENTED AS CHANGED. SECTION
 901.2.1.
 23-4A. SHT P3.28 CHANGE 66.2SANITARY
 RISER 12 THRU 17 AND 51 DOES NOT REFLECT
 THE FLOOR PLAN WHERE IT CONNECTS TO THE
 BUILDING DRAIN. PLEASE CORRELATE RISER
 AND FLOOR PLAN, AND RECHECK THE FIXTURE
 UNITS AND PIPE SIZE. SECTION 104.2.1.
 24-4A. SHT P3.28 CHANGE 66.5 A
 HORIZONTAL BRANCH SHALL NOT CONNECT
 WITHIN THE HORIZONTAL STACK OFFSET.
 SECTION 711.2.
 25-4A. SHT P3.29 CHANGE 67.1 TABLE
 710.1(1) 1/8"/FT SLOPE REQUIRED.
 INDICATE ON PLANS. (ALSO SEE SHT P3.28
 10 @ 2559FU).
 26-4A. SHT P3.29 CHANGE 67.2 DOES NOT
 CONNECT TO THE BUILDING DRAIN IN THE
 CORRECT LOCATION. CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
 27-4A. SHT P3.30 CHANGE 68.1 INDICATE
 SLOPE OF PIPE (1/8"/FT) FOR WHERE
 REQUIRED. TABLE 710.1(1).
 28-4A. SHT P3.31 CHANGE 69.1 SHOW SLOPE
 AS 1/8"/FT WHERE REQUIRED. TABLE
 710.1(1).
 29-4A. SHT P3.31 RISER 54 5TH FLOOR W/M
 MISSING. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
 30-4A. SHT P3.32 CHANGE 70.1 INDICATE
 SLOPE AT 1/8"/FT AS REQUIRED PER TABLE
 710.1(1).
 31-4A. SHT P3.33 CHANGE 7.1 FIXTURE UNIT
 COUNT AT 8" TO READ 1407FU, NOT 140FU AS
 SHOWN. SECTION 104.2.1.
 32-4A. SHT PP3.34 CHANGE 72.1 PIPE SIZE
 DOWNSTREAM OF RISERS 39/75 TO BE 5"
 203FU OR INDICATE AS 1/4"/FT SLOPE PER
 TABLE 710.1(1).
 33-4A. SHT P3.36 CHANGE 74.1 SHOW SLOPE
 OF PIPE IN BLDG DRAIN AS 1/8"/FT WHERE
 REQUIRED PER TABLE 710.1(1).
 34-4A. SHT P3.36 BRANCH LINE DOWNSTREAM
 OF RISER 37 IS 291FU 5" IS REQUIRED.
 ALSO SEE BASE OF STACK. TABLE 710.1(1).
 - THE SIZE OF THE DRAINAGE PIPING SHALL
 NOT BE REDUCED IN SIZE IN THE DIRECTION
 OF FLOW. SEE DOWNSTREAM OF RISER 37 AND
 WHERE RISERS CONNECT TO THE BLDG DRAIN.
 SECTION 704.2.
 35-4A. SHT P3.36 CHANGE 74.2 RISER 71
 DOES NOT CONNECT TO RISER 33. PLEASE
 CLARIFY. SECTION 104.2.1.
 36-4A. SHT P3.36 CHANGE 74.3 RISER 33 IS
 NOT SHOWN ON THIS SHEET. IT SHOULD BE
 INDICATED THAT THE VENT FROM THE EWC AND
 THE SINK CONNECT TO RISER 33. SECTION
 104.2.1.
 37-4A. SHT P3.37 CHANGE 75.1 PLEASE
 CORRECT PIPE SIZE AND SQUARE FOOTAGE FOR
 PIPE PRIOR TO AND AFTER RISERS RW1 AND
 RW11 CONNECT. SECTION 104.2.1. AND TABLE
 1106.3.
 38-4A SHT P3.37 CHANGE 75.2 RISER STATES
 "SEE P2.02 FOR CONT.", BUT NO PIPING
 SHOWN ON P2.02. PLEASE CLARIFY. SECTION
 104.2.1.
 39-4A SHT P3.40 CHANGE 78.1 SHOWS 1/4"
 CONDENSATE LINE. SHALL BE 1-1/4" AS
 SHOWN UPSTREAM.
 40-4A SHT P3.41 CHANGE 79.1 SHOWS 1"
 CONDENSATE LINE. SHEE BE 1-1/2" AS SHOWN
 UPSTREAM.
  
 NEW COMMENTS:
  
 1-E. SHT P3.21 RISER 26 DOES NOT REFLECT
 THE FLOOR PLAN. NO DRAINAGE LINE FROM
 KITCHEN SINK AND W/M SHOWN ON THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 104.2.1.
 2-E SHTS P2.11, P2.12, & P2.15 PAN DRAIN
 SHALL NOT TERMINATE IN THE PARKING
 GARAGE. SECTION 504.8.2. - EXPLAIN HOW
 DRAINING THE PTR DISCHARGE LINE INTO THE
 GARAGE PARKING MEETS THE REQUIREMENT FOR
 A SAFE DISCHARGE. SECTION 604.7.1
 3-E SHT P2.40 (NEW SHEET) NO DRAINAGE
 SHOWN FOR THE W/M, L/SINK, OR KITCHEN
 SINK. PLEASE CORRELATE WITH RISER
 DIAGRAM. SECTION 104.2.1.
 4-E SHTS P2.59 AND P2.60 PLEASE SHOW
 TOTAL DEVELOPED LENGTH AND TOTAL FIXTURE
 UNITS FOR COMBINED VENTS 31 THRU 45, 46
 THRU 50, 65 & 78. INDICATE ALL VENT PIPE
 SIZES. TABLE 916.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-02-11 Cont ID  
Sent By kstevens Date 2006-02-11 Time 10:31 Rev Time 47.00
Received By kstevens Date 2006-01-31 Time 18:59 Sent To  
Notes
2006-02-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW: (FROM 1ST REVIEW)
  
 12) SHT A4.41 KITCHEN SINK & JUICE BAR
 SINK IN COMMON AREAS SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL. RESPONSE NOTED, BUT NO
 DETAIL WAS FOUND. - THIS WILL BE A FIELD
 INSPECTOR APPROVAL. IF COMMON USE AREA
 IS AVAILABLE TO TENANTS AND GUESTS, ALL
 REQUIREMENTS OF SECTION 11-4.24 WILL BE
 ADHERED TO. - DETAIL SUBMITTED IS FOR
 THE DWELLING UNITS. SINKS INDICATED
 SHALL COMPLY AS REQUIRED IN SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.24.2/HEIGHT, 11-4.24.3/KNEE
 CLEARANCE, 11-4.24.4/SINK DEPTH,
 11-4.24.5/CLEAR FLOOR SPACE (FORWARD
 APPROACH), 11-4.24.6/EXPOSED PIPES &
 SURFACES, & 11-4.24.7/FAUCETS.
  
 SECOND REVIEW
 **************NEW COMMENTS**************
  
 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. SECTION
 104.2.1. - RISER #60 SHOWS W/M'S &
 KITCHEN SINKS, BUT FLOOR PLAN SHOWS
 POWDER ROOMS 2ND, 3RD, & 4TH FLOORS.
 PLEASE CORRELATE RISER & FLOOR PLAN. -
 FLOOR PLAN SHOWS RISER #11 DOWN TO MEZZ.
 LEVEL, THEN CONNECTING TO RISER 60, BUT
 RISERS DO NOT SHOW THIS. PLEASE
 CORRELATE RISERS AND FLOOR PLAN.-
 THERE ARE TWO NUMBER 60 SANT. RISER
 DIAGRAMS. (SEE SHEETS P2.03, P2.09,
 P2.14, P2.20, P2.26, P2.32, & P2.38 FOR
 ONE RISER #60). (SEE SHEETS P2.05,
 P2.11, P2.16, P2.22, P2.29, P2.35, &
 P2.41 FOR THE OTHER RISER #60). THE
 FIRST RISER #60 SHOWS A SHOWER BATH FROM
 THE 6TH FLOOR UP, AND THE SECOND RISER
 #60 SHOWS W/M'S AND KITCHEN SINKS (WHICH
 REFLECT THE RISER DIAGRAM). PLEASE
 CLARIFY. (3.26, P3.29, P3.34, P3.35).
 73B) SHT P2.39 ALL UNITS SHOW PIPING TO
 REFLECT RISERS. SECTION 104.2.1. - RISER
 #54 DOES NOT REFLECT THE FLOOR PLAN.
 (SEE SHT P3.21 SEALED 7-1-5) - THIS USED
 TO SHOW CORRECT FIXTURES, BUT WAS IN
 WRONG LOCATION. IT HAS BEEN CHANGED TO
 BATHROOM FIXTURES. PLEASE CLARIFY. - NOW
 SHEET HAS BEEN CHANGED AND DOES NOT
 REFLECT THE FLOOR PLAN INDICATED IN THE
 KEY PLAN AREA. NOT ALL UNITS ARE SHOWN.
 - NOW RISERS 1 & 2 ARE NOT SHOWN ON SHTS
 P2.02 & P2.08. - OFFSET SHOWN ON THE 5TH
 FLOOR, (P2.25), AND W/C PIPING DOES NOT
 REFLECT RISER 54A. DOES THIS THEN OFFSET
 BACK ON THE NEXT FLOOR?
 94B) SHT P2.64 STORM DRAIN LINE RUNNING
 EAST TO WEST AND CONNECTING TO RISER
 (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE
 LENGTH. SECTION 704.1 - NOT ADDRESSED,
 INDICATE ON PLANS. - PIPE SIZE INCREASED
 TO 12" BUT STILL SHOWS 1/4"FT ON ONE
 LENGTH AND NOT ENTIRE RUN. PLEASE
 CLARIFY.
 103B) SHTS P3.16 THRU P3.25 THE
 FOLLOWING SANITARY RISER DIAGRAMS WERE
 NOT LOCATED ON THE BUILDING DRAIN
 ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN),
 10, 59, 12, 13, 14, 17, 15, 18, 19, 20,
 21, 22, 72, 57, 75, 40, 41, 42, 37. -
 RISERS 12 THRU 22, 40 THRU 42 AND RISER
 75 HAVE NOT BEEN LOCATED ON THE BUILDING
 DRAIN ISOMETRIC AS NOTED IN THE COMMENT
 RESPONSE. - RISERS 19, 20, 72, & 75
 STILL NOT LOCATED ON BLDG DRAIN
 ISOMETRIC. COMMENT RESPONSE REFERS TO
 SHT P2.00. NO SHT P2.00 SUBMITTED.
 PLEASE CLARIFY.
 108B) SHT P3.21 RISER 26/35 KITCHEN SINK
 NOT SHOWN, DOES NOT REFLECT THE FLOOR
 PLAN, WASH MACHINE/LAUNDRY SINK OFFSET
 TO THE RIGHT SIDE NOT TO THE LEFT,
 VENTING FROM LAV DOES NOT REFLECT FLOOR
 PLAN. SECTION 104.2.1. - RISER 26/35 NOT
 SPLIT AND RISER 26 NOT FOUND ABOVE THE
 5TH FLOOR. PLEASE CLARIFY. - RISER 26
 STILL DOES NOT REFLECT THE FLOOR PLAN.
 (P3.31). VENTING FROM LAV NOT ADDRESSED.
 RISER 26 NOT FOUND ABOVE THE 5TH FLOOR.
 SHT P3.31 STATES "FOR CONT. SEE P3.16".
 RISER 26 NOT FOUND ON P3.16. PLEASE
 CLARIFY.
 109B) SHT P3.22 RISER 55 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 - STILL DOES NOT REFLECT FROM THE 6TH
 FLOOR UP. PLEASE CORRELATE RISER & FLOOR
 PLAN. RESPONSE INDICATES RISER 55 HAS
 BEEN CHANGED TO RISER 55A. WHY THE
 CHANGE. RISER IS SHOWN AS 55 & 55A.
 RISER 55 NOT LOCATED FROM THE 6TH FLOOR
 UP. RISER 55A DOES NOT REFLECT THE FLOOR
 PLAN.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIRD REVIEW
 **************NEW COMMENTS**************
  
 4C) SHT P2.39 UNIT B3 RISER 54 FLOOR
 PLAN DOES NOT REFLECT THE RISER DIAGRAM.
 - RISER 55 UNIT B1 NO REVENT TO RISER 27
 SHOWN ON FLOOR PLAN. SECTION 104.2.1.
 5C) SHT P2.40 UNABLE TO LOCATE RISER 56.
 SECTION 104.2.1. - NOW SHT P2.39 DOES
 NOT SHOW ALL UNITS.
  
 19C) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
 THIS IS GIVEN AS A NOTICE ONLY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 FORTH REVIEW
 ***************NEW COMMENTS*************
  
 1D. SHTS P2.05, P2.11, & P2.16 SHOW
 RISER 76 ON ALL FLOORS FROM GROUND FLOOR
 BASE OF STACK. SECTION 104.2.1.
 2D. SHTS P202 & P2.08 SHOW RISERS 1 & 2
 ON ALL FLOORS FROM THE GROUND FLOOR BASE
 OF STACK. SECTION 104.2.1.
 3D. SHT P2.13 VENT SHOWN ON RISER
 DIAGRAM NOT SHOWN ON THE FLOOR PLAN.
 (RISER 3,56,57). RISER AND FLOOR PLAN
 SHALL REFLECT EACH OTHER. SECTION
 104.2.1.
 4D. SHT P2.18 RISER 26 DOES NOT REFLECT
 THE FLOOR PLAN AT THE W/C OF THE POWDER
 ROOM. CORRELATE. SECTION 104.2.1.
 5D. SHTS P2.21, P2.22, P2.23,. P2.50 &
 P2.52 HAVE DIFFERENT DATES ON THE SEAL,
 DIFFERENT INFORMATION. - IT SEEMS THAT
 THE 6-3-5 SHEETS HAVE MORE UP TO DATE
 INFORMATION THAN THE 7-14-5 SHEETS.
 PLEASE CLARIFY. SECTION 104.2.1.
 6D. SHT P2.24 NOTE IN UNIT H6 STATES
 "SEE DRWG P2.20" PIPING LAYOUT NOT SHOWN
 ON SHT P2.20. PLEASE CLARIFY. SECTION
 104.2.1.
 7D. SHT P2.25 OFFSET NOT SHOWN ON THE
 5TH FLOOR FLOOR PLAN AT RISER 54A, BUT
 IS SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
 8D. SHT P2.28 VENTS FOR LAVS NOT SHOWN
 IN M/B UNIT B2. SECTION 104.2.1.
 9D. SHT P2.33 UNIT BE NOTES STATE "FOR
 SANT. LAYOUT SEE UNIT B3 DRAWING P2.39".
 B3 UNIT NOT SHOWN ON P2.39. - SHOW
 KITCHEN SINK PIPING FOR UNITS J & H.
 SECTION 104.2.1.
 10D. SHT. P2.34 SHOW RISER NUMBERS WHERE
 RISERS 30 & 32 DROP DOWN TO THE 5TH
 FLOOR. SECTION 104.2.1.
 11D. SHT P2.35 UNIT B WASH MACHINE
 OFFSET NOT SHOWN ON RISER DIAGRAM.
 PIPING IS NOT SHOWN TO THE LAUNDRY BOX.
 CLARIFY. SECTION 104.2.1.
 12D. SHT P2.39 NEW SHEET DOES NOT SHOW
 ALL UNITS INDICATED ON THE SHEET TITLE
 OF KEY PLAN SECTION. NEW SHEET REQUIRED.
 SECTION 104.2.1.
 13D. SHT P2.43 VENT RISER "FROM" RISER
 53 TO RISER 5 IS SHOWN AS "TO RISER 5E".
 THIS DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CLARIFY/CORRELATE. SECTION
 104.2.1.
 14D. SHT P2.60 SECONDARY ROOF DRAINS ARE
 NOT SHOWN FOR THE DECK AREA. SECTIONS
 104.2.1. & 1107.
 15D. SHT P2.64 PIPE SIZING FOR THE NEW
 OVERFLOW DRAINS IS NOT CORRECT. IF THEY
 ARE SECONDARY DRAINS, THEN THEY SHALL BE
 CALCULATED FOR ALL DRAINS IN EACH AREA
 AND SHALL ALL BE 8". IF THEY ARE SCUPPER
 DRAINS, ALL BUT THE AREAS THAT DRAIN
 3080SF & 3074SF SHALL BE 10". THE OTHER
 TWO SHALL BE 8". PLEASE CLARIFY. SECTION
 1107 & ALL SUBSECTIONS. - 6" DECK DRAIN
 3806SF SHOWS 816SF-A + 3990SF-V WHICH
 ADDS UP TO 4806SF & 6" DECK DRAIN 3619SF
 SHOWS 719A + 2099SF-V WHICH ADDS UP TO
 2818SF. PLEASE RECHECK ADDITION ON
 DRAINS. SECTION 104.2.1. - MUCH OF THE
 VERTICAL CONTRIBUTION OF STORM WATER
 WILL BE DRAINING INTO THE PLANTERS. WILL
 THIS BECOME A NUISANCE PROBLEM. PLEASE
 INDICATE HOW THISWILL WORK.
 16D. SHTS P3.01 THRU P3.16 ARE MISSING
 FROM ONE SET OF PLANS. SECTION 104.2.1.
 17D. SHT P3.28 RISER 54A DOES NOT
 REFLECT THE FLOOR PLAN ON THE 5TH FLOOR.
 - RISER 3 VENT STACK ON THE 16TH FLOOR
 NOT APPROVED AS SHOWN. VENT MAY NOT
 TERMINATE ON THE 15TH FLOOR AND START
 AGAIN ON THE 16TH FLOOR. SECTIONS
 104.2.1. & 903.3.
 18D. SHT P3.26 RISER 64 MISNUMBERED AT
 5TH FLOOR. (62) - INDICATE IF RISERS 48
 & 50 ARE TYPICAL FROM THE 16TH FLOOR
 THRU THE 21ST FLOOR. SECTION 104.2.1.
 19D. SHT P3.30 RISER DIAGRAM 50 DOES NOT
 REFLECT THE FLOOR PLAN 3RD & 4TH FLOORS.
 PLEASE CORRELATE. (P2.21) - RISER
 DIAGRAM 50/48 DOES NOT REFLECT THE FLOOR
 PLAN ON THE 16TH FLOOR. RISER 50 SHOWS
 NO FIXTURES FROM THE 16TH THRU THE 20TH
 FLOORS. - RISER 78 IS NOT INDICATED
 UNTIL THE 16TH FLOOR. SHOW RISER NUMBER
 FROM THE GROUND FLOOR UP. SECTION
 104.2.1.
 20D. SHT P3.39 THE TRENCH DRAINS ON THE
 5TH FLOOR LANAI LEVEL ARE NOT SHOWN ON
 THE RISER DIAGRAM FOR THE STORM. PLEASE
 CORRELATE RISER AND FLOOR PLAN AND
 INDICATE SQUARE FOOTAGE DRAINED BY THE
 TRENCH DRAINS. SECTIONS 104.2.1 & 1106
 AND TABLE 1106.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-10-19 Cont ID  
Sent By kstevens Date 2005-10-14 Time 13:25 Rev Time 64.50
Received By kstevens Date 2005-09-24 Time 03:51 Sent To  
Notes
2005-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 4) SHT A2.10 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY STORM DRAINS FOR
 THE 5TH FLOOR OPEN AREAS PER SECTIONS
 1106 & 1107. SHOW THE LOCATIONS FOR ALL
 PRIMARY AND SECONDARY DRAINS. RESPONSE
 NOTED, BUT NO CALCULATIONS WERE
 INDICATED OR FOUND. SECONDARY DRAINS
 WERE NOT LOCATED FOR ALL AREAS. SECTION
 104.2.1.
 10) ALL SHEETS FOR UNITS, SHOW THE
 OPENING SIZE FOR ALL W/C'S AND SHOW THE
 W/C TO BE 18" FROM THE CENTER LINE OF
 THE FIXTURE TO THE WALL WHERE
 APPLICABLE. RESPONSE NOTED, BUT NOT ALL
 UNITS SHOW THE REQUIREMENT. SECTION
 104.2.1. - ALL SHEETS WHERE NO PIPING
 LAYOUT IS SHOWN, INDICATE WHERE THE
 PIPING LAYOUT CAN BE LOCATED ON THAT
 SHEET. - DOOR SIZE NOT ASKED FOR.
 11) ALL SHEETS FOR UNITS, INDICATE
 SPECIFICATION "A" OR "B" AS REQUIRED BY
 THE FHA-98 DESIGN MANUAL FOR EACH UNIT.
 RESPONSE NOTED, BUT NOT UNITS SHOW
 SPECIFICATION "A" OR "B". SECTION
 104.2.1. - STILL NOT ALL UNITS SHOW THIS
 REQUIREMENT.
 12) SHT A4.41 KITCHEN SINK & JUICE BAR
 SINK IN COMMON AREAS SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL. RESPONSE NOTED, BUT NO
 DETAIL WAS FOUND. - THIS WILL BE A FIELD
 INSPECTOR APPROVAL. IF COMMON USE AREA
 IS AVAILABLE TO TENANTS AND GUESTS, ALL
 REQUIREMENTS OF SECTION 11-4.24 WILL BE
 ADHERED TO.
 5) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW THE
 SQUARE FOOTAGE OF EACH AREA DRAINED WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS SHOWN ADDED TO THE ROOF AREA.
 ALSO SHOW THE AREA OF UPPER ROOFS
 DRAINING ONTO EACH AREA ADDED TO THE SF
 IN CALCULATIONS. SHOW THE LOCATION OF
 EACH SECONDARY ROOF DRAIN OR SCUPPER. -
 RESPONSE NOTED, BUT CALCULATIONS ALL
 SECONDARY DRAINS ECT. NOT FOUND. THESE
 CALCULATIONS WILL BE FOR THE 5TH FLOOR
 PRIMARY DRAINS AND SECONDARY DRAINS AS
 WELL. - PLEASE PROVIDE CALCULATIONS.
 18) SHT A4.71A INDICATE LOCATION OF
 SECONDARY ROOF DRAINS IN AREAS OF ROOF
 WHERE SCUPPERS ARE NOT AVAILABLE.
 SECTION 1107. - RESPONSE NOTED, BUT
 INFORMATION NOT SHOWN. - STILL NO
 SECONDARY ROOF DRAINS SHOWN IN AREAS
 WITHOUT SCUPPERS.
 19) SHT A4.72A INDICATE LOCATION OF
 SECONDARY ROOF DRAINS FOR DECK DRAIN
 AREAS. SECTION 1107. RESPONSE NOTED, BUT
 INFORMATION NOT LOCATED. - STILL NO
 SECONDARY ROOF DRAINS SHOWN IN AREAS
 WITHOUT SCUPPERS.
 20) SHT A4.73A INDICATE LOCATION OF
 SECONDARY ROOF DRAIN FOR ALL AREAS.
 SECTION 1107. - RESPONSE NOTED, BUT ALL
 DRAINS NOT SHOWN. - STILL NO SECONDARY
 ROOF DRAINS SHOWN IN AREAS WITHOUT
 SCUPPERS.
 51) ALL SANT. RISERS WITH WASH MACHINES
 REQUIRE A STANDPIPE, AND THE CLEANOUTS
 SHALL BE LOCATED 4' ABOVE THE FLOOR FOR
 ACCESS. SECTIONS 1002.1, 802.4, &
 708.10. - RESPONSE NOTED, BUT COMMENT
 NOT ADDRESSED. - STANDPIPES FOR W/M'S
 NOT SHOWN.
 SECOND REVIEW
 **************NEW COMMENTS**************
 1B) SHT A4.43 PLANTERS SHOW 8"H OPENINGS
 IN PLANTER WALLS AND REFER TO SHT A8.21
 FOR A DETAIL. NO DETAIL FOR THESE
 OPENINGS WAS LOCATED. PLEASE CLARIFY.
 SECTION 104.2.1. - NO WIDTH INDICATED
 4B) SHTS A4.71, A4.72, A4.73, & A4.74
 SHOW LOCATION OF ALL SECONDARY ROOF
 DRAINS FOR AREAS THAT DO NOT HAVE
 SCUPPERS. SECTION 1107 - STILL AREAS
 WITH NO SECONDARY ROOF DRAINS.
 6B) SHT A5.11 SHOW ELEVATION FOR W/C
 AND LAVS IN USABLE BATHROOMS SHOWING
 OPENINGS FOR W/C, 18" OFF WALL TO
 CENTERLINE OF FIXTURE, AND HEIGHT OF LAV
 COUNTER TOPS AT 34". FHA-98 DESIGN
 MANUAL REQUIREMENT 7. - NOT ALL USABLE
 BATHROOMS SHOW THESE REQUIREMENTS.
 12B) SHT P2.03 UNIT 5 RISER NUMBERS AT
 POWDER ROOM ON THE FLOOR PLAN DO NOT
 REFLECT NUMBERS SHOWN ON RISER DIAGRAM.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1. - RISERS 4,9,10,58,59
 ARE NOT SHOWN. RISER 8A ADDED, BUT NOT
 SHOWN ON SHTS P2.03 OR P-209 WITH RISER
 4,9,10,58,59 (203) & 4 & 9 (209)
 18B) SHT P2.12 UNIT 17 OFFSET DOES NOT
 REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 104.2.1. - STILL DOES
 NOT REFLECT.
 21B) SHT P2.13 UNIT V MASTER BATH
 HORIZONTAL DRY VENT NOT APPROVED.
 SECTIONS 905.3 & 905.4. SANT. OFFSET
 DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CORRELATE. SECTION 104.2.1. - NOW
 THE WATER CLOSET IS NOT VENTED AND THE
 FIXTURES FROM THE FLOOR ABOVE DISCHARGE
 THROUGH THE BATHROOM. THIS IS NOT
 ALLOWED PER SECTIONS 908.3 & 909.1
 26B) SHT P2.16 UNIT B7 DOES NOT REFLECT
 THE RISER DIAGRAM AT THE MASTER BATH.
 PLEASE CORRELATE. SECTION 104.2.1. -
 VENT ROUTING STILL DOES NOT REFLECT
 RISER DIAGRAM VENTING.
 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. SECTION
 104.2.1. - RISER #60 SHOWS W/M'S &
 KITCHEN SINKS, BUT FLOOR PLAN SHOWS
 POWDER ROOMS 2ND, 3RD, & 4TH FLOORS.
 PLEASE CORRELATE RISER & FLOOR PLAN. -
 FLOOR PLAN SHOWS RISER #11 DOWN TO MEZZ.
 LEVEL, THEN CONNECTING TO RISER 60, BUT
 RISERS DO NOT SHOW THIS. PLEASE
 CORRELATE RISERS AND FLOOR PLAN.
 58B) SHT P2.28 UNIT A SHOW ALL PIPING TO
 REFLECT RISERS. SECTION 104.2.1. - NO
 NOTE INDICATING WHERE PIPING CAN BE
 LOCATED FOUND FOR UNIT "A"
 62B) SHT P2.32 UNIT E1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. RISER 11
 - SHOW ALL PIPING TO REFLECT RISER
 DIAGRAM. SECTION 104.2.1. - NO NOTE
 INDICATING WHERE PIPING CAN BE LOCATED
 FOUND FOR UNIT "E1".
 63B) SHT P2.32 UNITS D1 & G1 SHOW ALL
 PIPING TO REFLECT THE RISER DIAGRAMS.
 SECTION 104.2.1. - NO NOTE INDICATING
 WHERE PIPING CAN BE LOCATED FOUND FOR
 UNIT "G1".
 66B) SHT P2.35 ALL UNITS SHOW PIPING TO
 REFLECT RISERS. SHOW THE LOCATION OF
 RISER (45). SECTION 104.2.1. - NO NOTE
 INDICATING WHERE PIPING CAN BE LOCATED
 FOR UNIT "G".
 73B) SHT P2.39 ALL UNITS SHOW PIPING TO
 REFLECT RISERS. SECTION 104.2.1. - RISER
 #54 DOES NOT REFLECT THE FLOOR PLAN.
 (SEE SHT P3.21 SEALED 7-1-5) - THIS USED
 TO SHOW CORRECT FIXTURES, BUT WAS IN
 WRONG LOCATION. IT HAS BEEN CHANGED TO
 BATHROOM FIXTURES. PLEASE CLARIFY.
 74B) SHT P2.40 UNIT B1 SHOW PIPING TO
 REFLECT THE RISERS. SHOW RISER LOCATION
 AND RISER DESIGNATION NUMBERS. SECTION
 104.2.1. - SHOW KITCHEN SINK & W/M
 PIPING.
 77B) SHT P2.44 UNIT G1 SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 - NO NOTE INDICATING THE LOCATION OF THE
 PIPING HAS BEEN FOUND.
 78B) SHT P2.45 UNIT R1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. (26)
 SECTION 104.2.1. - RISER #26 NOT FOUND.
 79B) SHT P2.45 UNITS B4 & G SHOW PIPING
 TO REFLECT RISER DIAGRAMS. SECTION
 104.2.1. - NO NOTES INDICATING THE
 LOCATION OF THE PIPING WAS FOUND.
 85B) SHT P2.55 INDICATE THE LOCATION FOR
 THE SECONDARY ROOF DRAINS. SECTION
 104.2.1. - SECONDARY ROOF DRAINS IN SOME
 LOCATIONS NOT SHOWN.
 88B) SHT P2.56 INDICATE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTIONS 104.2.1
 & 1107. - SECONDARY ROOF DRAINS IN SOME
 LOCATIONS NOT SHOWN.
 89B) SHT P2.57 INDICATE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTIONS 104.2.1
 & 1107. - SECONDARY ROOF DRAINS IN SOME
 LOCATIONS NOT SHOWN.
 93B) SHT P2.64 STORM DRAIN LAYOUT DOES
 NOT REFLECT RISER (2)(3) IN UNIT E,
 RISER (4)(5) IN UNIT B4, AND RISER
 (7)(8) IN UNIT D. SECTION 104.2.1. -
 3"PF 80SF MISSING FROM RISER UNIT E1.
 94B) SHT P2.64 STORM DRAIN LINE RUNNING
 EAST TO WEST AND CONNECTING TO RISER
 (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE
 LENGTH. SECTION 704.1 - NOT ADDRESSED,
 INDICATE ON PLANS.
 103B) SHTS P3.16 THRU P3.25 THE
 FOLLOWING SANITARY RISER DIAGRAMS WERE
 NOT LOCATED ON THE BUILDING DRAIN
 ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN),
 10, 59, 12, 13, 14, 17, 15, 18, 19, 20,
 21, 22, 72, 57, 75, 40, 41, 42, 37. -
 RISERS 12 THRU 22, 40 THRU 42 AND RISER
 75 HAVE NOT BEEN LOCATED ON THE BUILDING
 DRAIN ISOMETRIC AS NOTED IN THE COMMENT
 RESPONSE.
 108B) SHT P3.21 RISER 26/35 KITCHEN SINK
 NOT SHOWN, DOES NOT REFLECT THE FLOOR
 PLAN, WASH MACHINE/LAUNDRY SINK OFFSET
 TO THE RIGHT SIDE NOT TO THE LEFT,
 VENTING FROM LAV DOES NOT REFLECT FLOOR
 PLAN. SECTION 104.2.1. - RISER 26/35 NOT
 SPLIT AND RISER 26 NOT FOUND ABOVE THE
 5TH FLOOR. PLEASE CLARIFY.
 109B) SHT P3.22 RISER 55 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 - STILL DOES NOT REFLECT FROM THE 6TH
 FLOOR UP. PLEASE CORRELATE RISER & FLOOR
 PLAN.
 121B) SHT P3.28 RISER 68 INDICATE SHEET
 NUMBER FOR CONTINUATION OF RISER.
 SECTION 104.2.1. - RISER 54 OFFSET VENT
 REQUIRED, AND 4 FU MAX. ON 2" WET VENT.
 SECTION 915 AND TABLE 909.3. - RISER 7
 OFFSET VENTS REQUIRED. UPPER OFFSET,
 (2ND FLOOR),VENT SHALL BE CONNECTED TO
 THE VERTICAL STACK NOT THE BRANCH LINE.
 SECTION 915. - RISER 3, 56, 57 OFFSET
 VENT REQUIRED SECTION 915 - DOES NOT
 SHOW KITCHEN SINK 5TH FLOOR SECTION
 104.2.1. - MISLABELED AS RISER 51 -
 SECTION 104.2.1. - WASH MACHINE GROUND
 FLOOR REQUIRES THAT CLEANOUT IS 4' AFF.
 SECTION 104.2.1. - RISERS 4, 9, 58, 9 AT
 BASE, HORIZONTAL DRY VENT NOT APPROVED.
 SECTIONS 905.3 & 905.4. VENT SHALL BE
 CONNECTED AT THE BASE OF THE STACK.
 SECTION 903.4 - THESE RISERS ARE
 INDICATED AS 4, 9, 10, 58, & 59. PLEASE
 CORRELATE. SECTION 104.2.1. - OFFSET
 SHALL CONNECT ABOVE THE BRANCH LINE. FIG
 915.2. - RISER 58 SOME FIXTURES ARE
 MISLABELED, ON NOT LABELED AT ALL.
 SECTION 104.2.1. - VENT TERMINATION FOR
 2ND FLOOR BATHROOM NOT SHOWN. SECTION
 104.2.1. - RISER 4/9 MISLABELED FIXTURE.
 SECTION 104.2.1, WASH MACHINES, KITCHEN
 SINKS, AND BATHROOMS SHALL NOT DRAIN
 PAST THE VENT FOR THE BATHROOM ON THE
 MEZZ. LEVEL. SECTION 908.3 - DWV FOR THE
 MEZZ. LEVEL DOES NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1. - SECOND FLOOR
 POWDER ROOM DOES NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1. - BATHROOM GROUPS
 FOR THE THIRD AND FORTH FLOORS NOT SHOWN
 ON RISER 4. SECTION 104.2.1. ** - WASH
 MACHINE GROUND FLOOR STILL REQUIRES THE
 CLEANOUT TO BE LOCATED 4' ABOVE THE
 FLOOR. - NEW RISER 8A VENT SHOWS
 CONNECTING INTO RISER 8. THIS IS NOT
 REFLECTED ON RISER 8. PLEASE CORRELATE
 RISERS.
 124B) SHT P3.30 RISER 77 DOES NOT
 REFLECT THE FLOOR PLAN, WASH MACHINES
 NOT SHOWN. - RISER 47 OFFSET VENTS
 REQUIRED, 5TH FLOOR DOES NOT REFLECT THE
 FLOOR PLAN, NO KITCHEN SINK SHOWN. -
 RISER 49 OFFSET VENTS REQUIRED. - RISER
 49 DOES NOT REFLECT THE FLOOR PLAN, LAV
 MISSING IN MASTER BATH 2ND FLOOR, OFFSET
 VENTS REQUIRED, 2ND FLOOR INDICATED
 DOWNSTREAM OF MEZZ. - RISER 65 DOES NOT
 REFLECT THE FLOOR PLAN. - RISER 50 DOES
 NOT REFLECT THE FLOOR PLAN ON THE 2ND
 FLOOR AND THE 5TH FLOOR, OFFSET VENTS
 REQUIRED, FIXTURE MISLABELED, 4 FU MAX.
 ON 2" WET VENT, DRY HORIZONTAL VENT NOT
 APPROVED. SECTIONS 104.2.1, 915, & TABLE
 909.3 - 5TH FLOOR UPPER OFFSET VENT NOT
 SHOWN.
 125B) SHT P3.31 RISER 24 DOES NOT
 REFLECT THE FLOOR PLAN 4TH FLOOR, 4 FU
 MAX. ON 2" WET VENT, OFFSET VENTS
 REQUIRED, DRY HORIZONTAL VENT NOT
 APPROVED. - RISER 54 OFFSET VENTS
 REQUIRED. - RISER 26 OFFSET VENTS
 REQUIRED. - RISER 27/28 OFFSET VENTS
 REQUIRED, 4 FU MAX. ON 2" WET VENT, DOES
 NOT REFLECT THE FLOOR PLAN AT/BELOW MEZZ
 LEVEL. - RISER 55/28/84 RISER
 DESIGNATION NUMBER DOES NOT REFLECT THE
 FLOOR PLAN, (SHOW AS 55/73/84), PLEASE
 CLARIFY, DOES NOT REFLECT THE FLOOR PLAN
 NO WASH MACHINES SHOWN, OFFSET VENTS
 REQUIRED. SECTIONS 104.2.1, 915, & TABLE
 909.3. ** - RISER 27/28 STILL DOES NOT
 REFLECT THE FLOOR PLAN AS THE MEZZ.
 LEVEL.
 130B) SHT P3.36 GROUND FLOOR DOES NOT
 REFLECT THE FLOOR PLAN, (FD IN TRASH
 ROOM NOT SHOWN, KITCHEN SINK - W/M AREA,
 AND VENTING), INDICATE WHY 10 FU FOR
 CLEANOUT AT END OF RUN. - RISER 71
 OFFSET VENTS REQUIRED, NO PIPING FOR 3RD
 FLOOR, NO KITCHEN SINK ON 4TH FLOOR,
 INDICATE FLOOR LEVEL TOP OF RISER. -
 RISER 37 VENT STACK SHALL CONNECT AT THE
 BASE OF THE STACK, NO HORIZONTAL DRY
 VENT, OFFSET VENT REQUIRED, 5TH FLOOR
 DOES NOT REFLECT THE FLOOR PLAN, FIXTURE
 MISLABELED AND 4 FU MAX. ON 2" WET VENT
 4TH FLOOR, UNABLE TO FIND CONTINUATION
 OF RISER. - RISER 36 SHOWS TYPICAL
 PIPING FOR 3RD & 4TH FLOORS, BUT FLOOR
 PLANS ARE DIFFERENT. SECTIONS 104.2.1.
 915, 903.4, 905.3, 905.4. ** - FLOOR
 DRAIN IN TRASH ROOM NOT SHOWN IN THE
 KITCHEN SINK - W/M AREA. ALSO SHOW
 VENTING. - STILL UNABLE TO LOCATE
 CONTINUATION OF RISER 37.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 **************NEW COMMENTS**************
  
 1C) SHT P2.03 RISER 8A NOT SHOWN WITH
 RISERS 4,9,10,58,59. SECTION 104.2.1.
 2C) SHT P2.09 RISER 8A NOT SHOWN WITH
 RISERS 4,9,10,58,59 DOWN & 4,9 UP.
 SECTION 104.2.1.
 3C) ALL SHEETS FOR UNITS, WHERE THERE IS
 NO PIPING SHOWN IN ANY PORTION OF A
 UNIT, INDICATE, (AT UNIT ON PLANS),
 WHERE THE CAN BE LOCATED. THIS INCLUDES
 ALL PIPING SYSTEMS. SECTION 104.2.1.
 4C) SHT P2.39 UNIT B3 RISER 54 FLOOR
 PLAN DOES NOT REFLECT THE RISER DIAGRAM.
 - RISER 55 UNIT B1 NO REVENT TO RISER 27
 SHOWN ON FLOOR PLAN. SECTION 104.2.1.
 5C) SHT P2.40 UNABLE TO LOCATE RISER 56.
 SECTION 104.2.1.
 6C) SHT P3.16 RISER 5/53 INDICATES ON
 15TH FLOOR VENT FROM RISER 5, BUT NO
 CONNECTION AT 15TH FLOOR SHOWN ON RISER
 5. PLEASE CLARIFY. SECTION 104.2.1.
 7C) SHT P3.19 RISERS 14 & 17 OFFSET
 VENTS REQUIRED. SECTION 915. - SHOWS
 15TH FLOOR W/M ABOVE 21ST FLOOR. PLEASE
 CLARIFY. SECTION 104.2.1.
 8C) SHT P3.28 RISER 1,2,68 & 54,4
 CONNECT VENT STACK TO BASE OF SANT.
 STACK. SECTION 903.4. - RISER 7 3RD &
 4TH FLOOR TUB MISLABELED AS SHOWER.
 SECTION 104.2.1. - RISER 8 VENT STACK
 CHANGED TO SOLID LINE OF A SANT. LINE.
 SECTION 104.2.1. - RISER 56 UPPER OFFSET
 VENT REQUIRED AT 5TH FLOOR OFFSET.
 SECTION 915. - RISER 8A VENT SHOWN TO
 TIE INTO RISER 8 VENT LINE. NOT SHOWN ON
 RISER 8 VENT. PLEASE CLARIFY.
 9C) SHT P3.30 RISER 48/50 CONNECT VENT
 STACK TO THE BASE OF THE SANT. STACK.
 SECTION 903.5. - UPPER OFFSET VENT
 REQUIRED 5TH FLOOR. SECTION 915. - RISER
 48 NOT SHOWN ON PREVIOUS FLOOR PLAN
 SHEET FROM GROUND FLOOR THRU 2ND FLOOR.
 - INDICATE WHAT SHEET THE CONTINUATION
 OF EACH RISER WILL BE FOUND ON. SECTION
 104.2.1.
 10C) SHT P3.21 WERE IS THE CONTINUATION
 OF RISERS 33, 74, & 81 ABOVE THE 6TH
 FLOOR AND RISER 71 BELOW THE 6TH FLOOR?
 SECTION 104.2.1.
 11C) SHT P3.31 RISERS 26 & 27/28 CONNECT
 VENT STACKS TO BASE OF SANT. STACK.
 SECTION 903.5.
 12C) SHT P2.34 OFFSET SHOWN ON FLOOR
 PLAN TO RISERS 81 & 74. PLEASE INDICATE
 WHERE ON THE RISER DIAGRAM THAT IS
 LOCATED. SECTION 104.2.1.
 13C) SHT P3.23 OFFSET AT MEZZ. LEVEL FOR
 RISER 33/55 DOES NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1. - REVENTS FROM
 W/M TO RISER 33/55 ARE MISLABELED.
 SECTION 104.2.1. - REVENT AT TOP OF
 STACK "A" INDICATE "TO STACK VENT 56",
 BUT NOT SHOWN ON STACK VENT 56. PLEASE
 CLARIFY. SECTION 104.2.1.
 14C)SHT P3.34 RISER 61 CONNECT VENT
 STACK TO BASE OF SANT. STACK. SECTION
 903.5. - GROUND FLOOR DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 104.2.1. - RISER
 INDICATES TYPICAL 3RD THRU 5TH FLOORS,
 BUT RISER 43 ONLY CONNECTS ON THE 5TH
 FLOOR. INDICATE ON PLANS. - RISER 43
 CONNECT VENT STACK TO BASE OF SANT.
 STACK. 903.5 - DOES NOT REFLECT FLOOR
 PLAN. - SECTION 104.2.1. - TABLE 909.3
 INDICATE ALL PIPE SIZES. - RISER 64
 RISER INDICATES TYPICAL 3RD THRU 5TH
 FLOOR, BUT RISER 45 ONLY CONNECTS ON 5TH
 FLOOR. INDICATE ON PLANS. SECTION
 104.2.1.
 15C) SHT P3.35 SHOW PIPE SIZES FOR
 TYPECAL 3RD/4TH FLOORS RISER 38.- MAX 10
 BRANCH INTERVALS TO THE RELIEF VENT.
 RECHECK INTERVALS. SECTION 914.
 16C) SHT P3.37 INDICATE 1/4"FT SLOPE
 ENTIRE RUN UPSTREAM OF 10"@1/4"FT SLOPE
 22306SF (RWL 4/5) & UPSTREAM OF 15"
 62210SF (RWL 2/3) TO HORIZONTAL OFFSET.
 SECTION 704.1.
 17C) SHT P3.38 3" PD 80SF MISSING FROM
 RWL 2/3 AT 5TH FLOOR. SECTION 104.2.1.
 18C) SHT P3.39 INDICATE 1/4"/FT SLOPE
 THE ENTIRE RUN UPSTREAM OF 15"@1/4"/FT
 54050SF UP TO HORIZONTAL OFFSET
 DOWNSTREAM OF RWL 7. SECTION 704.1.
 19C) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
 THIS IS GIVEN AS A NOTICE ONLY.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-05-09 Cont ID  
Sent By kstevens Date 2005-05-09 Time 17:16 Rev Time 99.00
Received By kstevens Date 2005-05-09 Time 17:16 Sent To  
Notes
2005-05-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 FROM PREVIOUS REVIEW:
 3) SHT A2.10 SUBMIT CALCULATIONS FOR
 MINIMUM FACILITIES PER TABLES 1003.2 AND
 403.1. SHOW SQUARE FEET FOR EACH COMMON
 USE ROOM. RESPONSE NOTED, BUT NOT
 INDICATED WHERE I CAN FIND THE
 CALCULATIONS. SECTION 104.2.1.
 4) SHT A2.10 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY STORM DRAINS FOR
 THE 5TH FLOOR OPEN AREAS PER SECTIONS
 1106 & 1107. SHOW THE LOCATIONS FOR ALL
 PRIMARY AND SECONDARY DRAINS. RESPONSE
 NOTED, BUT NO CALCULATIONS WERE
 INDICATED OR FOUND. SECONDARY DRAINS
 WERE NOT LOCATED FOR ALL AREAS. SECTION
 104.2.1.
 10) ALL SHEETS FOR UNITS, SHOW THE
 OPENING SIZE FOR ALL W/C'S AND SHOW THE
 W/C TO BE 18" FROM THE CENTER LINE OF
 THE FIXTURE TO THE WALL WHERE
 APPLICABLE. RESPONSE NOTED, BUT NOT ALL
 UNITS SHOW THE REQUIREMENT. SECTION
 104.2.1.
 11) ALL SHEETS FOR UNITS, INDICATE
 SPECIFICATION "A" OR "B" AS REQUIRED BY
 THE FHA-98 DESIGN MANUAL FOR EACH UNIT.
 RESPONSE NOTED, BUT NOT UNITS SHOW
 SPECIFICATION "A" OR "B". SECTION
 104.2.1.
 12) SHT A4.41 KITCHEN SINK & JUICE BAR
 SINK IN COMMON AREAS SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL. RESPONSE NOTED, BUT NO
 DETAIL WAS FOUND.
 13) SHT A4.41 SUBMIT A DETAIL FOR THE
 TOILET ROOM IN THE COMMON AREA. SHOW
 COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, 11-4.21, & 11-4.22 AND ALL
 SUBSECTIONS. ALSO SEE SECTION 2 OF THE
 FHA-98 DESIGN MANUAL. RESPONSE NOTED,
 BUT THE FOLLOWING INFORMATION IS NOT
 SHOWN ON THE DETAIL:
 A. FLUSH CONTROLS 11-4.16.5
 B. EXPOSED PIPES & SURFACES 11-4.19.4
 C. FAUCETS 11-4.19.5
 D. CURBS 11-4.21.7
 14) SHT A4.41 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1 FOR THE COMMON
 AREA. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 ALSO SEE SECTION 410.1. RESPONSE NOTED,
 BUT NOT INDICATED WHERE DETAIL IS
 LOCATED.
 15) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW THE
 SQUARE FOOTAGE OF EACH AREA DRAINED WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS SHOWN ADDED TO THE ROOF AREA.
 ALSO SHOW THE AREA OF UPPER ROOFS
 DRAINING ONTO EACH AREA ADDED TO THE SF
 IN CALCULATIONS. SHOW THE LOCATION OF
 EACH SECONDARY ROOF DRAIN OR SCUPPER. -
 RESPONSE NOTED, BUT CALCULATIONS ALL
 SECONDARY DRAINS ECT. NOT FOUND. THESE
 CALCULATIONS WILL BE FOR THE 5TH FLOOR
 PRIMARY DRAINS AND SECONDARY DRAINS AS
 WELL. - PLEASE PROVIDE CALCULATIONS.
 18) SHT A4.71A INDICATE LOCATION OF
 SECONDARY ROOF DRAINS IN AREAS OF ROOF
 WHERE SCUPPERS ARE NOT AVAILABLE.
 SECTION 1107. - RESPONSE NOTED, BUT
 INFORMATION NOT SHOWN.
 19) SHT A4.72A INDICATE LOCATION OF
 SECONDARY ROOF DRAINS FOR DECK DRAIN
 AREAS. SECTION 1107. RESPONSE NOTED, BUT
 INFORMATION NOT LOCATED.
 20) SHT A4.73A INDICATE LOCATION OF
 SECONDARY ROOF DRAIN FOR ALL AREAS.
 SECTION 1107. - RESPONSE NOTED, BUT ALL
 DRAINS NOT SHOWN.
 32) SHEETS FOR UNIT TYPES ARE INCOMPLETE
 AND REQUIRE MORE INFORMATION. SOME
 SHEETS SHOW SANT., VENTS, WATER, COND.,
 T/P, OR ANOTHER UNIDENTIFIED LINE, BUT
 ALL DO NOT HAVE ALL INFORMATION
 REQUIRED. - RESPONSE NOTED, BUT
 INFORMATION IS STILL MISSING ON MANY
 SHEETS. SOME EXAMPLES NO SANT SHOWN TO
 WASH MACHINE IN UNIT 1, RISER NUMBERS
 ARE MISSING OR MISLABLED, SOME SANT.
 LINES NOT SHOWN, WATER LINES MISSING,
 ECT. RECHECK ALL UNITS TO MAKE SURE ALL
 PIPING, (SANT., WATER, COND, VENTS, P/T,
 PAN DRAINS, WASTE ARMS ECT ARE SHOWN)
 33) SHOW STACK NUMBERS FOR EACH STACK IN
 ALL UNIT SHEETS. SECTION 104.2.1.
 RESPONSE NOTED, BUT NOT ALL STACK
 NUMBERS ARE SHOWN, AND SOME STACK
 NUMBERS ARE NOT IN THE CORRECT LOCATION
 AS THE STACK.
 45) SHT P2.21 UNITS A1 & VV1 BATH #2
 SHOWERS ARE NOT VENTED. SECTION 901.2.1
 UNIT A1 WHAT TYPE OF VENT IS KITCHEN
 SINK UTILIZING. SECTION 901.2.1 -
 RESPONSE NOTED, BUT SHOWERS ARE NOT
 VENTED AND NO INFORMATION FOR THE
 KITCHEN VENT HAS BEEN GIVEN.
 46) SHT P2.39 HAS A REFERENCE TO SHT P2.
 NO SHT P2 IS LOCATED. PLEASE CLARIFY
 SECTION 104.2.1. - RESPONSE NOTED, BUT
 THE REFERENCE IS STILL THERE. IN FACT
 THERE ARE AT LEAST 2 REFERENCES TO SHEET
 P2 ON THIS SHEET.
 50) SHT P2.57 WOMEN'S BATHROOM DOES NOT
 REFLECT THE SANT. RISER DIAGRAM. W/C IN
 WOMEN'S STALL MAX. 10' FROM POINT OF
 VENT TABLE 906.1. INDICATE THE USE OF
 THE FLOOR DRAIN FOR FIXTURE NEXT TO
 SHOWER IN THE MEN'S BATHROOM. SECTION
 104.2.1. - RESPONSE NOTED, BUT THE W/C
 IN THE WOMEN'S BATHROOM DOES NOT SHOW
 SANITARY PIPING FROM THE BRANCH LINE TO
 THE WATER CLOSET TO THE LAV AS SHOWN ON
 THE RISER DIAGRAM. ALSO THE FLOOR DRAIN
 IN THE MEN'S BATHROOM HAS NOT BEEN
 EXPLAINED BY THE RESPONSE "DRAWING
 CORRECTED"
 51) ALL SANT. RISERS WITH WASH MACHINES
 REQUIRE A STANDPIPE, AND THE CLEANOUTS
 SHALL BE LOCATED 4' ABOVE THE FLOOR FOR
 ACCESS. SECTIONS 1002.1, 802.4, &
 708.10. - RESPONSE NOTED, BUT COMMENT
 NOT ADDRESSED.
 64) BACKFLOW PROTECTION REQUIRED FOR THE
 POOL MAKE UP WATER. SUBMIT A DETAIL.
 SECTION 608.13.2. - RESPONSE NOTED, BUT
 BACKFLOW PROTECTION IS NOT IN THE SCOPE
 OF THE POOL CONTRACTOR UNLESS IT IS AN
 AIR GAP AT THE COLLECTOR TANK. PLEASE
 INDICATE METHOD OF BACKFLOW PROTECTION.
 65) BECAUSE PLANS ARE INCOMPLETE, MORE
 COMMENTS MAY BE FORTHCOMING WHEN PLANS
 ARE RESUBMITTED. - PLEASE RETURN THE
 PLUMBING PLANS WITH THE RED LINE NOTES
 WHEN RESUBMITTING TO HELP REVIEWING
 PLANS FOR THE SECOND TIME. - RESPONSE
 NOTED, BUT PLANS WERE NOT RETURNED. I
 WILL BE KEEPING THE RED LINE SET OF
 PLANS TO ASSIST IN THE THIRD REVIEW.
 ALSO IT SEEM THAT THE PLANS ARE NOT 100%
 COMPLETE AT THIS TIME AND MORE COMMENTS
 MAY FOLLOW ON THE THIRD REVIEW.
 **************NEW COMMENTS**************
 1B) SHT A4.43 PLANTERS SHOW 8"H OPENINGS
 IN PLANTER WALLS AND REFER TO SHT A8.21
 FOR A DETAIL. NO DETAIL FOR THESE
 OPENINGS WAS LOCATED. PLEASE CLARIFY.
 SECTION 104.2.1.
 2B) SHTS A4.41 THRU AR.44A SUBMIT DETAIL
 FOR SCUPPERS FOR TERRACES ON THE 5TH
 FLOOR. INDICATE HEIGHT AND WIDTH.
 SECTIONS 1107 & 104.2.1. - DETAILS #1
 PRECAST SCUPPER ON S.W. CORNER NOT SHOWN
 WHERE INDICATOR IS POINTING. WHERE IS A
 CUT SECTION FOR AREA ADJACENT TO
 STAIRWAY #5. NO SECONDARY DRAIN/SCUPPER
 SHOWN. SECTION 1107. - ALSO DETAIL #2 NO
 SECONDARY DRAIN/SCUPPER IN OPPOSITE
 CORNER.
 3B) A4.60 SUBMIT DETAIL FOR SCUPPERS ON
 THE 16TH FLOOR. SECTION 1107
 4B) SHTS A4.71, A4.72, A4.73, & A4.74
 SHOW LOCATION OF ALL SECONDARY ROOF
 DRAINS FOR AREAS THAT DO NOT HAVE
 SCUPPERS. SECTION 1107
 5B) SHT A5.11 DETAIL #9 INDICATES A
 SHOWER BATHROOM DETAIL NOT SHOWN ON THE
 DETAIL INDEX. PLEASE CLARIFY
 6B) SHT A5.11 SHOW ELEVATION FOR W/C
 AND LAVS IN USABLE BATHROOMS SHOWING
 OPENINGS FOR W/C, 18" OFF WALL TO
 CENTERLINE OF FIXTURE, AND HEIGHT OF LAV
 COUNTER TOPS AT 34". FHA-98 DESIGN
 MANUAL REQUIREMENT 7.
 7B) SHTS P2.01 & P2.02 PAN DRAIN LINES
 FROM THE WATER HEATERS SHALL TERMINATE
 OVER A SUITABLY LOCATED INDIRECT WASTE
 RECEPTOR OR FLOOR SINK OR EXTEND TO THE
 EXTERIOR OF THE BUILDING AND TERMINATE
 NOT LESS THA 6" OR MORE THAN 24" ABOVE
 THE ADJACENT GROUND SURFACE GROUND
 SURFACE. SECTION 504.8.2.
 8B) SHT P2.02 NO SANT. SHOWN TO WASH
 MACHINE FOR UNIT #1. SECTION 104.2.1.
 9B) SHT P2.02 FLOOR PLAN DOES NOT
 REFLECT THE RISER DIAGRAM 54/68 AT UNIT
 #3. SECTION 104.2.1.
 10B) SHT P2.02 UNIT #4 INDICATE RISER
 NUMBERS AT BATH #1. SECTION 104.2.1.
 11B) SHT P2.02UNIT #4 RISER NUMBERS BY
 THE WASH MACHINE DO NOT REFLECT THE
 NUMBERS SHOWN ON THE RISER DIAGRAM.
 PLEASE CORRELATE RISER & FLOOR PLAN
 RISER DESIGNATION. SECTION 104.2.1.
 12B) SHT P2.03 UNIT 5 RISER NUMBERS AT
 POWDER ROOM ON THE FLOOR PLAN DO NOT
 REFLECT NUMBERS SHOWN ON RISER DIAGRAM.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
 13B) SHT P2.03 UNIT 7 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAG. PLEASE
 CORRELATE RISER WITH FLOOR PLAN. SECTION
 104.2.1
 14B) SHT P2.06 RISER SOUTH OF ELEVATOR &
 STAIRWAY DOES NOT SHOW RISER #60.
 SECTION 104.2.1.
 15B) SHT P2.08 UNIT 3 BATH #2 DOES NOT
 REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE RISER & FLOOR PLAN. SECTION
 104.2.1.
 16B) SHT P2.10 UNIT 10 BATHROOM DOES NOT
 REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 104.2.1.
 17B) SHT P2.12 UNIT 19 OFFSET FOR BATH
 #2 DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CORRELATE. SECTION 104.2.1.
 18B) SHT P2.12 UNIT 17 OFFSET DOES NOT
 REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 104.2.1.
 19B) SHT P2.12 UNIT 15 IDENTIFY RISER. -
 FLOOR PLAN DOES NOT REFLECT THE RISER
 DIAGRAM. PLEASE CORRELATE. SEC 104.2.1.
 20B) UNIT 14 BATH #2 VENT DOES NOT
 REFLECT RISER DIAGRAM. PLEASE CORRELATE.
 SECTION 104.2.1.
 21B) SHT P2.13 UNIT V MASTER BATH
 HORIZONTAL DRY VENT NOT APPROVED.
 SECTIONS 905.3 & 905.4. SANT. OFFSET
 DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CORRELATE. SECTION 104.2.1.
 22B) SHT P2.13 UNIT VV VENT AND SANT.
 STACK DO NOT REFLECT THE RISER DIAGRAM.
 VENT IS NOT SHOWN. PLEASE CORRELATE.
 SECTION 104.2.1.
 23B) SHT P2.14 UNIT H7 WHICH RISER DOES
 KITCHEN SINK DRAIN INTO. RISER DOES NOT
 REFLECT FLOOR PLAN AT THE WASH MACHINE.
 PLEASE CORRELATE. SECTION 104.2.1.
 24B) SHT P2.14 UNITS H1 & H2 DO NOT
 REFLECT THE DIAGRAM. PLEASE CORRELATE.
 SECTION 104.2.1.
 25B) UNIT P2.15 UNIT VV1 MASTER BATH
 DOES NOT REFLECT THE RISER DIAGRAM, AND
 DRY HORIZONTAL VENT IS NOT APPROVED.
 COMMENT RESPONSE INDICATES THAT OFFSET
 UNDER TUB IS BELOW THE FLOOR, BUT FLOOR
 PLAN SHOWS THE VENT FROM THE WATER
 CLOSET ABOVE THE SLAB CONNECTING INTO
 THIS VENT OFFSET. PLEASE CLARIFY. PLEASE
 CORRELATE. SECTIONS 905.3, 905.4 &
 104.2.1.
 26B) SHT P2.16 UNIT B7 DOES NOT REFLECT
 THE RISER DIAGRAM AT THE MASTER BATH.
 PLEASE CORRELATE. SECTION 104.2.1.
 27B) SHT P2.17 UNIT H4 TUB DRAIN LINE IS
 NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 104.2.1.
 28B) SHT P2.17 UNIT H3 POWDER ROOM RISER
 SHOWN AS SOIL STACK ON THE RISER
 DIAGRAM, BUT AS A VENT STACK ON THE
 FLOOR PLAN. - MASTER BATH LINE TO RIGHT
 OF WATER CLOSET, (RISER 37), SHOWN AS
 THE VENT LINE ON THE RISER DIAGRAM,
 WHICH WILL MAKE IT A DRY HORIZONTAL
 VENT. THIS IS NOT APPROVED BY SECTIONS
 905.3 & 905.4 - BATH #2 VENT NOT SHOWN
 ON THE FLOOR PLAN. SECTION 104.2.1.
 29B) SHT P2.18 UNIT V1 HORIZONTAL DRY
 VENT NOT APPROVED IN MASTER BATH AND
 POWDER ROOM. SECTIONS 905.3 & 905.4.
 30B) SHT P2.18 UNIT HD POWDER ROOM LAV
 ARM NOT SHOWN. SECTION 104.2.1.
 31B) SHT P2.18 UNIT H3 VENT LINE FOR
 MASTER BATH NOT SHOWN. SECTION 104.2.1.
 32B) SHT P2.18 UNIT H6 VENT LINE FOR
 MASTER BATH NOT SHOWN. SECTION 104.2.1.
 33B) SHT P2.19 UNIT V VENT LAYOUT DOES
 NOT REFLECT THE RISER DIAGRAM AT MASTER
 BATH. SECTION 104.2.1.
 34B) SHT P2.19 UNIT VV STACK & VENT FOR
 KITCHEN MISSING. SECTION 104.2.1.
 35B) SHT P2.19 UNIT B8 NO SANITARY OR
 VENT TO KITCHEN SINK. SECTION 104.2.1.
 36B) SHT P2.20 UNIT HH1 PIPING FOR
 KITCHEN SINK & POWDER ROOM MISSING.
 SECTION 104.2.1.
 37B) SHT P2.20 UNIT H7 INDICATE RISER
 NUMBER AND SANITARY DOES NOT REFLECT THE
 RISER DIAGRAM. SECTION 104.2.1.
 38B) SHT P2.20 UNIT H2 SHOW DWV PIPING
 TO REFLECT RISER DIAGRAM. SECTION
 104.2.1.
 38B) SHT P2.21 UNIT H1 SHOW DWV PIPING
 TO REFLECT RISER DIAGRAM. SECTION
 104.2.1.
 39B) SHT P2.21 UNIT A1 BATH #2 DOES NOT
 REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 40B) SHT P2.22 UNIT B7 SHOW DWV PIPING
 TO REFLECT RISER DIAGRAM. SECTION
 104.2.1.
 41B) SHT P2.22 UNIT B7 BATH #2 DOES NOT
 REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 42B) SHT P2.23 UNIT A1 SHOW DWV PIPING
 TO REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 43B) SHT P2.24 UNIT HD SHOW DWV PIPING
 TO REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 44B) SHT P2.24 UNIT H3 SHOW DWV PIPING
 TO REFLECT THE RISER DIAGRAM. SECTION
 104.2.1. - RISER (24) DESIGNATION IN
 WRONG LOCATION. SECTION 104.2.1.
 45B) SHT P2.24 UNIT H6 SHOW DWV PIPING
 TO REFLECT THE RISER DIAGRAM. SECTION
 104.2.1
 46B) SHT P2.25 UNIT L INDICATE THE
 LOCATION OF THE CONTINUATION OF RISERS
 (67) & (68). SECTION 104.2.1.
 47B) SHT P2.25 UNIT C OFFSET DOES NOT
 REFLECT THE RISER DIAGRAM, (6). SECTION
 104.2.1.
 48B) SHT P2.25 UNIT C SHOW RISER
 DESIGNATION NUMBER FOR RISER #5 BY W/M.
 SECTION 104.2.1.
 49B) SHT P2.25 UNIT C RWL #1 DOES NOT
 REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 50B) SHT P2.25 UNIT B5 RISER (3)(56)(57)
 DOES NOT REFLECT THE RISER DIAGRAM.
 (KITCHEN DRAIN ARM NOT SHOWN). SECTION
 104.2.1.
 51B) SHT P2.25 UNIT B6 MASTER BATH DOES
 NOT REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 53B) SHT P2.26 UNIT E1 RWL #4 DOES NOT
 REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 54B) SHT P2.27 UNIT A BATH #2 NOT VENTED
 NOT SANITARY TO RISER (25). SECTION
 104.2.1.
 55B) SHT P2.27 UNIT B1 SHOW RISER
 DESIGNATION NUMBERS FOR (29)(30)(31)(32)
 - VENT LINES NOT SHOWN - NO SANT. DRAIN
 LINE TO KITCHEN SINK. SECTION 104.2.1.
 56B) SHT P2.28 UNIT B1 NO VENT LINES
 SHOWN. SECTION 104.2.1.
 57B) SHT P2.28 UNIT B2 VENT LINES TO
 REFLECT RISERS DIAGRAM BATH #2 - MASTER
 BATH LAV DRAIN CONNECTION TO BRANCH IS
 SHOWN INSTALLED AGAINST THE FLOW.
 SECTION 706.3. - RISER #37 DESIGNATION
 SHOWN IN THE WRONG LOCATIONS. PLACE NEXT
 TO RISER. SECTION 104.2.1.
 58B) SHT P2.28 UNIT A SHOW ALL PIPING TO
 REFLECT RISERS. SECTION 104.2.1.
 59B) SHT P2.29 BOTH UNITS SHOW ALL
 PIPING TO REFLECT THE RISER DIAGRAMS.
 SECTION 104.2.1.
 60B) SHT P2.30 UNIT A BATH #2 DOES NOT
 REFLECT RISER DIAGRAM. SECTION 104.2.1.
 61B) SHT P2.31 ALL UNITS SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 62B) SHT P2.32 UNIT E1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. RISER 11
 - SHOW ALL PIPING TO REFLECT RISER
 DIAGRAM. SECTION 104.2.1.
 63B) SHT P2.32 UNITS D1 & G1 SHOW ALL
 PIPING TO REFLECT THE RISER DIAGRAMS.
 SECTION 104.2.1.
 64B) SHT P2.33 ALL UNITS SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 65B) SHT P2.34 ALL UNITS SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 66B) SHT P2.35 ALL UNITS SHOW PIPING TO
 REFLECT RISERS. SHOW THE LOCATION OF
 RISER (45). SECTION 104.2.1.
 67B) SHT P2.36 ALL UNITS SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 68B) SHT P2.36 UNIT C1 SHOW RISER
 DESIGNATION #(49). SECTION 104.2.1.
 69B) UNIT E KITCHEN PIPING DOES NOT
 REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 70B) SHT P2.36 UNIT E KITCHEN SINK
 PIPING DOES NOT REFLECT THE RISER
 DIAGRAM. SECTION 104.2.1
 71B) SHT P2.37B) UNITS B5 & B6 MASTER
 BATH DOES NOT REFLECT THE RISER DIAGRAM
 AT LAVS NEXT TO THE WATER CLOSET.
 SECTION 104.2.1.
 72B) SHT P2.38B) UNIT G1 SHOW PIPING TO
 REFLECT RISERS. SECTION 104.2.1.
 73B) SHT P2.39 ALL UNITS SHOW PIPING TO
 REFLECT RISERS. SECTION 104.2.1.
 74B) SHT P2.40 UNIT B1 SHOW PIPING TO
 REFLECT THE RISERS. SHOW RISER LOCATION
 AND RISER DESIGNATION NUMBERS. SECTION
 104.2.1.
 75B) SHT P2.41 UNITS B & D SHOW PIPING
 TO REFLECT THE RISERS. SECTION 104.2.1.
 76B) SHT P2.42 UNIT A SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 77B) SHT P2.44 UNIT G1 SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 78B) SHT P2.45 UNIT R1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. (26)
 SECTION 104.2.1.
 79B) SHT P2.45 UNITS B4 & G SHOW PIPING
 TO REFLECT RISER DIAGRAMS. SECTION
 104.2.1.
 80B) SHT P2.46 UNIT P SHOW PIPING TO
 REFLECT RISER (36) AT BATH #2. SECTION
 104.2.1.
 81B) SHT P2.47 UNIT U DOES NOT REFLECT
 RISER (44) BATH #2. SECTION 104.2.1.
 82B) SHT P2.48 SHOW PIPING FOR 2 LAVS.
 SECTION 104.2.1.
 83B) SHT P2.51 SHOW ALL PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 84B) SHT P2.52 UNIT R VENT MISSING BATH
 #2 LAV. SECTION 104.2.1.
 85B) SHT P2.55 INDICATE THE LOCATION FOR
 THE SECONDARY ROOF DRAINS. SECTION
 104.2.1.
 86B) SHT P2.55 OVERFLOW SHALL DRAIN FROM
 COOLING TOWERS TO STORM - DRAIN FROM
 COOLING TOWERS TO SANITARY. PLEASE
 INDICATE ON PLANS. SECTION 104.2.1.
 87B) SHT P2.55 5" REQUIRED FOR STORM
 DRAIN DOWNSTREAM OF 4" R.D. @ 520 SF.
 TABLE 1106.3
 88B) SHT P2.56 INDICATE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTIONS 104.2.1
 & 1107.
 89B) SHT P2.57 INDICATE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTIONS 104.2.1
 & 1107.
 90B) SHT P2.57 RWL #6 3" PD @ 80 SF NOES
 NOT REFLECT THE RISER DIAGRAM. - 3" PD @
 50 SF DOES NOT REFLECT THE RISER
 DIAGRAM. - PIPE SIZE DOWNSTREAM OF 3" PD
 @ 280 SF REQUIRES A MINIMUM OF 5" PIPE.
 SECTION 104.2.1.
 91B) SHT P2.57 FLOOR PLAN DOES NOT
 REFLECT THE RISER DIAGRAM. WOMENS HDCP
 TOILET LAV. RISER (25) IS A DRY VENT
 WHICH IS NOT APPROVED. SECTIONS 905.3 &
 905.4. SECTION 104.2.1.
 92B) SHT P2.58 RWL #7 DOWNSTREAM OF 3"DD
 @ 125 SF 5" REQUIRED. 4" SHOWN. TABLE
 1106.3. - 3"PD @ 220 SF DOES NOT REFLECT
 RISER SHOWN AND 211 SF. PLEASE CORRELATE
 - RWL #8 3"PD @ 88 SF DOES NOT REFLECT
 RISER DIAGRAM SHOW AS 80 SF. PLEASE
 CORRELATE. SECTION 104.2.1.
 93B) SHT P2.64 STORM DRAIN LAYOUT DOES
 NOT REFLECT RISER (2)(3) IN UNIT E,
 RISER (4)(5) IN UNIT B4, AND RISER
 (7)(8) IN UNIT D. SECTION 104.2.1.
 94B) SHT P2.64 STORM DRAIN LINE RUNNING
 EAST TO WEST AND CONNECTING TO RISER
 (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE
 LENGTH. SECTION 704.1
 95B) SHT P3.00 SANITARY RISER DIAGRAM
 FOR TOILET ROOM POOL DECK, DRY
 HORIZONTAL VENT NOT APPROVED. SECTIONS
 905.3 & 905.4.
 96B) SHT P3.00 SANITARY RISER DIAGRAM
 FOR TOILET ROOM POOL DECK, FLOOR DRAIN
 BY SHOWER NOT APPROVED FOR INDIRECT
 WASTE. A FLOOR SINK OR HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
 97B) SHT P3.00 DOMESTIC WATER RISER
 DIAGRAM POOL DECK TOILET ROOMS, LANAI
 LEVEL PUBLIC TOILETS, & WATER RISER
 DIAGRAM 5TH FLOOR PUBLIC AREA, THE WATER
 SUPPLY IS MISSING FOR 1 LAV, POOL DECK
 TOILET ROOMS, AND FULL OPEN VALVES ARE
 REQUIRED ON EVERY WATER DOWN-FEED PIPE.
 SECTION 606.1(4).
 98B) SHTS P3.05 THRU P3.15 ALL UNIT
 WATER RISER DIAGRAMS, DELETE ALL AIR
 CHAMBERS AS THEY ARE NOT APPROVED.
 SECTION 604.9. - ALL WATER LINES TO THE
 REF. ICE MAKERS ARE REQUIRED TO HAVE A
 WATER HAMMER ARRESTOR. SECTION 604.9. -
 SOME UNITS SHOW A SEPARATE WATER LINE TO
 THE REF. ICE MAKER AND A LINE UNDER THE
 KITCHEN SINK FOR THE REF. ICE MAKER.
 PLEASE CLARIFY AS THEY DO NOT REFLECT
 THE RISER DIAGRAM IN MOST CASES. RISERS
 DO NOT SHOW TWO LINES TO THE ICE MAKER.
 - SOME RISERS ARE MISSING SUPPLY LINES
 TO FIXTURES. SECTION 104.2.1.
 99B) SHT P3.16 RISER (4) OFFSET ON 16TH
 FLOOR NOT SHOWN. - RISER (5) TIE OFFSET
 VENT IN AS SHOWN IN EXAMPLE ON ATTACHED
 SHEET. (FIG. 915.2)
 100B) SHT P3.17 RISER (6) TIE OFFSET
 VENT IN AS SHOWN IN EXAMPLE ON ATTACHED
 SHEET. (FIG 915.2) - 5TH FLOOR PLUMBING
 PIPE LAYOUT IS NOT SHOWN. (DIFFERENT
 FROM TYPICAL - NO OFFSET SHOWN. - RISER
 (56) TIE OFFSET VENT IN AS SHOWN IN
 EXAMPLE ON ATTACHED SHEET. (FIG. 915.2)
 - RISER (8) DOES NOT REFLECT THE FLOOR
 PLAN 5TH FLOOR, NOR DOES IT REFLECT THE
 FLOOR PLAN 6TH THRU 15TH FLOORS FOR THE
 LAVS. SECTION 104.2.1.
 101B) SHT P3.18 RISER (69) DOES NOT
 REFLECT THE FLOOR PLAN. - RISER (10)
 DOES NOT REFLECT THE FLOOR PLAN 17TH
 THRU 21ST FLOOR. - RISER (11) NO BRANCH
 LINES FROM 4TH FLOOR THRU 15TH FLOOR.
 PLEASE CLARIFY. SECTION 104.2.1.
 102B) ALL RISERS THAT HAVE OFFSET VENTS,
 THE CONNECTION FROM THE WASTE STACK TO
 THE VENT STACKS SHALL BE BY AN UPRIGHT
 WYE FITTING NOT A SANT. TEE FITTING AS
 SHOWN ON SOME RISERS, AND SHALL BE
 CONNECTED ON THE UPPER SECTION AS SHOWN
 ON ATTACHED SHEET. (FIG 915.2)
 103B) SHTS P3.16 THRU P3.25 THE
 FOLLOWING SANITARY RISER DIAGRAMS WERE
 NOT LOCATED ON THE BUILDING DRAIN
 ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN),
 10, 59, 12, 13, 14, 17, 15, 18, 19, 20,
 21, 22, 72, 57, 75, 40, 41, 42, 37.
 104B) SHTS P3.27 THRU P3.36 THE
 FOLLOWING RISERS SHOWN ON THE BUILDING
 DRAIN ISOMETRIC WERE NOT FOUND. 67, 83,
 53, 68, 51, 58, 84, 85, 86, 87, 89, 90,
 91, 84, 73, 33, 34, 74, 81.
 105B) SHT P3.21 SANT. RISER #23 SHOWS
 16TH FLOOR THEN 15TH FLOOR ABOVE.
 106B) SHT P3.21 SANT. RISERS 24, & 36
 INDICATE WHERE RISER #25 WILL CONNECT TO
 THESE RISERS. PLEASE CLARIFY AND
 INDICATE SHEET WHERE RISER #25 IS
 LOCATED. SECTION 104.2.1.
 107B) SHT P3.21 RISER 71 INDICATE HOW
 RISER 54 TIES INTO THIS RISER AS IT IS
 NOT SHOWN ON PREVIOUS FLOORS. SECTION
 104.2.1.
 108B) SHT P3.21 RISER 26/35 KITCHEN SINK
 NOT SHOWN, DOES NOT REFLECT THE FLOOR
 PLAN, WASH MACHINE/LAUNDRY SINK OFFSET
 TO THE RIGHT SIDE NOT TO THE LEFT,
 VENTING FROM LAV DOES NOT REFLECT FLOOR
 PLAN. SECTION 104.2.1.
 109B) SHT P3.22 RISER 55 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 110B) SHT P3.22 RISER 29/31, RISER 31
 NOT SHOWN 17TH TO 21ST FLOOR, MASTER
 BATH 15TH FLOOR MAXIMUM 4 FU MAX. ON 2"
 WET VENT. SECTION 104.2.1. & TABLE
 909.3.
 111B) SHT P3.22 RISER 30/32 ONLY RISER
 32 IS SHOWN. NO 16TH FLOOR PIPING SHOWN,
 ONLY 4 FU MAX. ON 2" WET VENT. SECTION
 104.2.1. AND TABLE 909.3.
 112B) SHT P3.23 RISER 38 ONLY 4 FU MAX.
 ON 2" WET VENT. TABLE 909.3.
 113B) SHT P3.24 SANT. RISER 77 16TH
 FLOOR DOES NOT REFLECT THE FLOOR PLAN,
 AND NO FIXTURE BRANCH LINES OR FIXTURES
 SHOWN FOR FLOORS 6 THRU 15. SECTION
 104.2.1.
 114B) SHT P3.24 RISER 76 ONLY 4 FU MAX.
 ON 2" WET VENT. TABLE 909.3
 115B) SHT P3.24 RISER 44 OFFSET VENT
 REQUIRED. SECTION 915
 116B) SHT P3.25 RISER 47 16TH FLOOR DOES
 NOT REFLECT THE FLOOR PLAN. NO SHOWER ON
 RISER. SECTION 104.2.1.
 117B) SHT P3.25 RISER 49 OFFSET VENT
 SHALL BE CONNECTED ABOVE THE BRANCH LINE
 PRIOR TO OFFSET. SECTION 915 - 16TH
 FLOOR 4 FU MAX. ON 2" WET VENT. TABLE
 909.3. - 15TH FLOOR DOES NOT REFLECT THE
 FLOOR PLAN. SECTION 104.2.1.
 118B) SHT P3.26 RISER 66 15TH FLOOR 4 FU
 MAX. ON 2" WET VENT. TABLE 909.3.
 119B) SHT P3.27 DRY HORIZONTAL VENT NOT
 APPROVED. SECTIONS 905.3 & 905.4. - 4 FU
 MAX. ON 2" WET VENT. TABLE 909.3 - NO
 VENT TERMINATION SHOWN FOR AREA AT LEFT
 SIDE OF BLDG DRAIN. - NO VENT SHOWN FOR
 LAV AT MEZZ. LEVEL. SECTION 901.2.1. -
 OFFSET VENT REQUIRED FOR RISER (6).
 SECTION 915. - CLEANOUT REQUIRED 4' AFF
 FOR W/M. SECTION 708.10. - VENTS FOR
 KITCHEN SINKS DO NOT REFLECT THE FLOOR
 PLAN. (NOT SHOWN ON FLOOR PLAN). SECTION
 104.2.1. - INDICATE SHEET NUMBER FOR THE
 CONTINUATION OF RISERS 53, 67/83 UNABLE
 TO LOCATE. SECTION 104.2.1.
 120B) EVERY VENT STACK SHALL CONNECT TO
 THE BASE OF THE DRAINAGE STACK. SECTION
 903.4
 121B) SHT P3.28 RISER 68 INDICATE SHEET
 NUMBER FOR CONTINUATION OF RISER.
 SECTION 104.2.1. - RISER 54 OFFSET VENT
 REQUIRED, AND 4 FU MAX. ON 2" WET VENT.
 SECTION 915 AND TABLE 909.3. - RISER 7
 OFFSET VENTS REQUIRED. UPPER OFFSET,
 (2ND FLOOR),VENT SHALL BE CONNECTED TO
 THE VERTICAL STACK NOT THE BRANCH LINE.
 SECTION 915. - RISER 3, 56, 57 OFFSET
 VENT REQUIRED SECTION 915 - DOES NOT
 SHOW KITCHEN SINK 5TH FLOOR SECTION
 104.2.1. - MISLABELED AS RISER 51 -
 SECTION 104.2.1. - WASH MACHINE GROUND
 FLOOR REQUIRES THAT CLEANOUT IS 4' AFF.
 SECTION 104.2.1. - RISERS 4, 9, 58, 9 AT
 BASE, HORIZONTAL DRY VENT NOT APPROVED.
 SECTIONS 905.3 & 905.4. VENT SHALL BE
 CONNECTED AT THE BASE OF THE STACK.
 SECTION 903.4 - THESE RISERS ARE
 INDICATED AS 4, 9, 10, 58, & 59. PLEASE
 CORRELATE. SECTION 104.2.1. - OFFSET
 SHALL CONNECT ABOVE THE BRANCH LINE. FIG
 915.2. - RISER 58 SOME FIXTURES ARE
 MISLABELED, ON NOT LABELED AT ALL.
 SECTION 104.2.1. - VENT TERMINATION FOR
 2ND FLOOR BATHROOM NOT SHOWN. SECTION
 104.2.1. - RISER 4/9 MISLABELED FIXTURE.
 SECTION 104.2.1, WASH MACHINES, KITCHEN
 SINKS, AND BATHROOMS SHALL NOT DRAIN
 PAST THE VENT FOR THE BATHROOM ON THE
 MEZZ. LEVEL. SECTION 908.3 - DWV FOR THE
 MEZZ. LEVEL DOES NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1. - SECOND FLOOR
 POWDER ROOM DOES NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1. - BATHROOM GROUPS
 FOR THE THIRD AND FORTH FLOORS NOT SHOWN
 ON RISER 4. SECTION 104.2.1.
 122B) ALL SANITARY RISER DIAGRAMS, SHOW
 ALL PIPE SIZES. SIZES ARE MISSING ON
 SOME PIPES. SECTION 104.2.1. & TABLE
 710.1(1).
 123B) SHT P3.29 RISER 69 4 FU MAX. ON 2"
 WET VENT. TABLE 909.3 - RISER 11 DOES
 NOT REFLECT THE FLOOR PLAN - AND NO
 BRANCH LINES FROM 4TH FLOOR THRU 15TH
 FLOOR. - OFFSET VENTS REQUIRED - RISER
 60 OFFSET VENT REQUIRED - GROUND FLOOR
 AT RISER 11/60 DOES NOT REFLECT THE
 FLOOR PLAN - RISER 86 SECOND FLOOR DOES
 NOT REFLECT THE FLOOR PLAN - SHOW
 DESIGNATION NUMBER FOR RISER 88 - RISER
 89 4 FU MAX. ON 2" WET VENT - 89/90/91
 MEZZ. LEVEL BATHROOM DOES NOT REFLECT
 THE FLOOR PLAN. SECTIONS 104.2.1. & 915
 TABLE 909.3.
 124B) SHT P3.30 RISER 77 DOES NOT
 REFLECT THE FLOOR PLAN, WASH MACHINES
 NOT SHOWN. - RISER 47 OFFSET VENTS
 REQUIRED, 5TH FLOOR DOES NOT REFLECT THE
 FLOOR PLAN, NO KITCHEN SINK SHOWN. -
 RISER 49 OFFSET VENTS REQUIRED. - RISER
 49 DOES NOT REFLECT THE FLOOR PLAN, LAV
 MISSING IN MASTER BATH 2ND FLOOR, OFFSET
 VENTS REQUIRED, 2ND FLOOR INDICATED
 DOWNSTREAM OF MEZZ. - RISER 65 DOES NOT
 REFLECT THE FLOOR PLAN. - RISER 50 DOES
 NOT REFLECT THE FLOOR PLAN ON THE 2ND
 FLOOR AND THE 5TH FLOOR, OFFSET VENTS
 REQUIRED, FIXTURE MISLABELED, 4 FU MAX.
 ON 2" WET VENT, DRY HORIZONTAL VENT NOT
 APPROVED. SECTIONS 104.2.1, 915, & TABLE
 909.3
 125B) SHT P3.31 RISER 24 DOES NOT
 REFLECT THE FLOOR PLAN 4TH FLOOR, 4 FU
 MAX. ON 2" WET VENT, OFFSET VENTS
 REQUIRED, DRY HORIZONTAL VENT NOT
 APPROVED. - RISER 54 OFFSET VENTS
 REQUIRED. - RISER 26 OFFSET VENTS
 REQUIRED. - RISER 27/28 OFFSET VENTS
 REQUIRED, 4 FU MAX. ON 2" WET VENT, DOES
 NOT REFLECT THE FLOOR PLAN AT/BELOW MEZZ
 LEVEL. - RISER 55/28/84 RISER
 DESIGNATION NUMBER DOES NOT REFLECT THE
 FLOOR PLAN, (SHOW AS 55/73/84), PLEASE
 CLARIFY, DOES NOT REFLECT THE FLOOR PLAN
 NO WASH MACHINES SHOWN, OFFSET VENTS
 REQUIRED. SECTIONS 104.2.1, 915, & TABLE
 909.3.
 126B) SHT P3.32 RISER 29/30/31/32 OFFSET
 VENTS REQUIRED, FIXTURE MISLABLED,
 FIXTURE BRANCH LINE SHALL NOT CONNECT TO
 THE HORIZONTAL OFFSET. - RISER 34 DOES
 NOT REFLECT THE FLOOR PLAN, OFFSET VENTS
 REQUIRED. - RISER 33/35 OFFSET VENTS
 REQUIRED, LAV VENTS 2ND THRU 4TH FLOOR
 DO NOT REFLECT THE FLOOR PLAN. - RISER
 56/74/81 OFFSET VENTS REQUIRED, KITCHEN
 SINK VENTS DO NOT REFLECT THE FLOOR PLAN
 2ND THRU 4TH FLOORS. - RISER 56 NO
 HORIZONTAL DRY VENT, DOES NOT REFLECT
 THE FLOOR PLAN 2ND & 3RD FLOORS, (W/M'S)
 SECTIONS 104.2.1, AND 711.2.
 127B) SHT P3.33 SANT. ISOMETRIC SHOWS
 TWO HORIZONTAL DRY VENTS, LEFT OF RISER
 61. THESE ARE NOT APPROVED. PER SECTIONS
 905.3 & 905.4. - WASH MACHINE LEFT OF
 RISER 61 DOES NOT REFLECT THE FLOOR
 PLAN, - RISER 61 OFFSET VENT REQUIRED,
 DOES NOT REFLECT THE FLOOR PLAN - RISER
 23 INDICATES TWO 4TH FLOORS, LAV ARMS DO
 NOT REFLECT THE FLOOR PLAN, OFFSET VENTS
 REQUIRED. - RISER 25 EXTRA BRANCH LINE
 CONNECTED TO STACK BELOW 2ND FLOOR NOT
 APPROVED, OFFSET VENTS REQUIRED, DOES
 NOT REFLECT THE FLOOR PLAN 5TH FLOOR, NO
 3RD FLOOR PIPING SHOWN, TUB MISSING 4TH
 FLOOR, 4 FU MAX. ON 2" WET VENT.
 SECTIONS 104.2.1, 915, 905.3, 905.4,
 706.3 & TABLE 909.3.
 128B) SHT P3.34 RISER 60 DOES NOT
 REFLECT THE FLOOR PLAN, UPRIGHT WYE
 REQUIRED AT VENT STACK CONNECTION TO THE
 WASTE STACK. - RISER 62 DOES NOT REFLECT
 THE FLOOR PLAN. - RISER 45 DOES NOT
 REFLECT THE FLOOR PLAN, - RISER 64 DOES
 NOT REFLECT THE FLOOR PLAN. - RISER 44
 VENT SHALL CONNECT TO BASE OF STACK,
 LABEL ALL FIXTURES. - RISER 76 DOES NOT
 REFLECT THE FLOOR PLAN, CONNECT VENT
 STACK TO BASE OF SANT. STACK, RISER
 SHOWS CONDITION ON 2ND FLOOR THAT IS
 ACTUALLY ON THE 5TH FLOOR ONLY, DRY
 HORIZONTAL VENT NOT APPROVED. - RISER 46
 SHOW ALL PIPE SIZES. SECTIONS 104.2.1,
 905.3, 905.4,
 129B) SHT P3.35 RISER 38 OFFSET VENTS
 REQUIRED, RELIEF VENT REQUIRED, RISER
 DOES NOT REFLECT THE FLOOR PLAN, (NO
 PIPING SHOW FOR 3RD THRU 5TH FLOORS -
 SHOWER MISSING IN BATHROOM), - GROUND
 FLOOR WASH MACHINE MISLABELED AS SHOWER,
 CLEANOUT SHALL BE 4' AFF AT W/M. -
 IDENTIFY OTHER RISER AT END OF RUN.
 SECTIONS 104.2.1, 915, 914, 708.10.
 130B) SHT P3.36 GROUND FLOOR DOES NOT
 REFLECT THE FLOOR PLAN, (FD IN TRASH
 ROOM NOT SHOWN, KITCHEN SINK - W/M AREA,
 AND VENTING), INDICATE WHY 10 FU FOR
 CLEANOUT AT END OF RUN. - RISER 71
 OFFSET VENTS REQUIRED, NO PIPING FOR 3RD
 FLOOR, NO KITCHEN SINK ON 4TH FLOOR,
 INDICATE FLOOR LEVEL TOP OF RISER. -
 RISER 37 VENT STACK SHALL CONNECT AT THE
 BASE OF THE STACK, NO HORIZONTAL DRY
 VENT, OFFSET VENT REQUIRED, 5TH FLOOR
 DOES NOT REFLECT THE FLOOR PLAN, FIXTURE
 MISLABELED AND 4 FU MAX. ON 2" WET VENT
 4TH FLOOR, UNABLE TO FIND CONTINUATION
 OF RISER. - RISER 36 SHOWS TYPICAL
 PIPING FOR 3RD & 4TH FLOORS, BUT FLOOR
 PLANS ARE DIFFERENT. SECTIONS 104.2.1.
 915, 903.4, 905.3, 905.4.
 131B) SHT P3.37 CHECK ADDITION FOR
 SQUARE FOOTAGE AT DRAINS. 4" @ 1665 SF
 TO BE A MINIMUM OF 5" PIPE RWL 4 TABLE
 1106.3. SOME FITTINGS NOT DIRECTING
 STORM WATER IN DIRECTION OF FLOW. - SHOW
 SF FOR TD'S GROUND FLOOR DRAINAGE RISER.
 132B) SHT O3.38 CHECK ADDITION ON RWL
 2&3. IS 3" PD 680SF OR 80 SF? PLUS CHECK
 ADDITION OF PD'S & DD'S = 963 SF BUT
 2320 SF SHOWN. 5TH FLOOR RISER 2/3 DOES
 NOT REFLECT THE FLOOR PLAN. DD @603 SF &
 PD @ 1018 SF NOT SHOWN. PLEASE CLARIFY.
 SECTION 104.2.1.
 133B) SHT P3.39 RECHECK ADDITION OF SF
 AS IT ACCUMULATES IN THE SYSTEM, SOME
 DRAIN SF DOES NOT REFLECT ROOF PLAN SF
 AT DECK DRAINS, & PLANTER DRAINS, PIPE
 SIZING NOT CORRECT, SHOW SF AS IT
 ACCUMULATES IN THE SYSTEM, SHOW SLOPE OF
 PIPE REQUIRED. SECTION 104.2.1, 1106, &
 1107.
 134B) THE FOLLOWING UNITS WERE NOT
 LOCATED. "C2", 'D2" & "BT" PLEASE
 INDICATE LOCATION FOR THESE UNITS.
 135B) THE FOLLOWING WATER RISER DIAGRAMS
 WERE NOT FOUND: SHTS P2.16/P2.22 "B7",
 SHTS P2.29 "B", SHT P2.33 "J1", P2.35
 "B", P2.41 "B", P2.46 "S1", P2.52 "S1"
 135B) PLANS STILL SEEM TO BE INCOMPLETE
 AND MORE COMMENTS MAY BE FORTHCOMING
 WHEN PLANS ARE RESUBMITTED. RED LINE
 PLANS WERE REQUESTED TO BE RETURNED TO
 HELP THE REVIEW PROCESS FOR THE SECOND
 REVIEW. THESE WERE NOT RETURNED. I WILL
 BE KEEPING THE RED LINE SET OF PLANS IN
 ORDER TO HELP THE REVIEW PROCESS ON NEXT
 RESUBMIT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 THIS ALSO WAS NOT DONE WHEN PLANS WERE
 RESUBMITTED. MOST RESPONSE NOTES WERE NO
 MORE THAN A FEW WORDS AND NO INDICATION
 OF WHERE CORRECTION COULD BE FOUND,
 RESULTING IN MANY HOURS REVIEWING THE
 PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-01-19 Cont ID  
Sent By kstevens Date 2005-01-19 Time 12:14 Rev Time 34.00
Received By kstevens Date 2005-01-12 Time 18:56 Sent To  
Notes
2005-01-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PLANS SHALL BE SIGNED/SEALED/DATED
 BY
 THE ARCHITECT/ENGINEER OF RECORD, AND
 ALL TITLE BLOCK INFORMATION REQUIRED ON
 ALL SHEETS. FAC 61G1-16.002-.003-.004 &
 61G15-23.002 & FS 481.219-.219 &
 471.025
 2) SHT A2.01 PRIMARY ENTRY LEVEL SHALL
 COMPLY WITH FHA-98 DESIGN MANUAL
 REQUIREMENTS 1 THRU 7.
 3) SHT A2.10 SUBMIT CALCULATIONS FOR
 MINIMUM FACILITIES PER TABLES 1003.2
 AND
 403.1. SHOW SQUARE FEET FOR EACH COMMON
 USE ROOM.
 4) SHT A2.10 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY STORM DRAINS FOR
 THE 5TH FLOOR OPEN AREAS PER SECTIONS
 1106 & 1107. SHOW THE LOCATION FOR ALL
 PRIMARY AND SECONDARY DRAINS.
 5) SHTS A2.14, A2.15, A2.16, & A2.17.
 APPLICATION STATES 20 STORY BLDG., BUT
 PLANS INDICATE 21ST STORY AND HAS A
 ROOF
 LEVEL, POOL DECK LEVEL, ELEVATOR
 MACHINE
 ROOM LEVEL ECT. PLEASE CLARIFY.
 6) SHT A4.11 UNIT 1 DOOR SWING INTO THE
 CLEAR FLOOR SPACE OF THE LAV. SECTION
 11-4.22.2.
 7) SHT A4.12 UNITS 5 & 6 DOOR SWING
 INTO
 THE CLEAR FLOOR SPACE OF THE LAV AND
 W/C
 SECTION 11-4.22.2.
 8) SHT A4.13 UNIT 12 DOOR SWING INTO
 THE
 CLEAR FLOOR SPACE OF THE W/C.
 11-4.22.2.
 9) SHT A4.15 UNIT 17 DOOR SWING INTO
 THE
 CLEAR FLOOR SPACE OF THE LAV.
 11-4.22.2.
 10) ALL SHEETS FOR UNITS. SHOW THE
 OPENING SIZE FOR ALL W/C'S AND SHOW THE
 W/C TO BE 18" FROM THE CENTER LINE OF
 THE FIXTURE TO THE WALL WHERE
 APPLICABLE
 11) ALL SHEETS FOR UNITS. INDICATE
 SPECIFICATION "A" OR "B" AS REQUIRED BY
 THE FHA-98 DESIGN MANUAL FOR EACH UNIT.
 12) SHT A4.41 KITCHEN SINK & JUICE BAR
 SINK IN COMMON AREAS SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL.
 13) SHT A4.41 SUBMIT A DETAIL FOR THE
 TOILET ROOM IN THE COMMON AREA. SHOW
 COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.18, 11-4.19, 11-4.21 & 11-4.22 AND
 ALL SUBSECTIONS. ALSO SEE SECTION 2 OF
 THE FHA-98 DESIGN MANUAL.
 14) SHT A4.41 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1 FOR THE COMMON
 AREA. SUBMIT A DETAIL SHOWING
 COMPLIANCE
 WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS. - ALSO SEE SECTION 410.1.
 15) SHT SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS PER SECTIONS
 1106 & 1107 AND ALL SUBSECTIONS. SHOW
 THE SQUARE FOOTAGE OF EACH AREA DRAINED
 WITH 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS SHOWN ADDED TO THE
 ROOF AREA. ALSO SHOW THE AREA OF UPPER
 ROOFS DRAINING ONTO EACH AREA ADDED TO
 THE SF IN CALCULATIONS. SHOW THE
 LOCATION OF EACH PRIMARY ROOF DRAIN AND
 EACH SECONDARY ROOF DRAIN OR SCUPPER
 FOR
 EACH AREA BEING DRAINED FOR EACH ROOF.
 16) SHT A4.51 A 60" DIA. TURNING AREA
 IS
 REQUIRED IN A "U" SHAPED KITCHEN THAT
 HAS A SINK, RANGE, OR COOKTOP AT IT'S
 BASE. PAGE 7.9 FHA DESIGN MANUAL.
 17) SHTS A4.60 THRU A4.66 MORE
 INFORMATION IS REQUIRED FOR THE
 EXTENDED
 TERRACES. WILL
 A SCUPPER BE REQUIRED OR CAN THE WATER
 DRAIN FROM THE TERRACES IN CASE OF
 BLOCKAGE OF THE TERRACE DRAIN. SECTION
 104.2.1.
 18) SHT A4.71A INDICATE LOCATION OF
 SECONDARY ROOF DRAINS IN AREAS OF ROOF
 WHERE SCUPPERS ARE NOT AVAILABLE.
 SECTION 1107.
 19) SHT A4.72A INDICATE LOCATION OF
 SECONDARY ROOF DRAINS FOR DECK DRAIN
 AREAS. SECTION 1107.
 20) SHT A4.73A INDICATE LOCATION OF
 SECONDARY ROOF DRAINS FOR ALL AREAS.
 SECTION 1107.
 21) SEPARATE PERMITS REQUIRED FOR POOL
 AND SPA. SECTION 104.1.1.
 22) SHT A8.21 DETAIL B/A8.21 INDICATE
 OPENING SIZE REQUIRED PER SECTION
 1107.3
 23) IRRIGATION PLANS & PERMIT REQUIRED.
 SECTION 104.2.1.
 23) SHT L-2 MORE INFORMATION IS
 REQUIRED
 FOR THE WATER FEATURES. INDICATE HOW
 THE
 FEATURES ARE DRAINED AND IF THERE IS A
 WATER SERVICE FOR THESE FEATURES.
 SECTION 104.2.1.
 24) THE FOLLOWING SHEETS SUBMITTED ARE
 NOT SHOWN ON THE DRAWING INDEX. A4.71A,
 A4.74A, A8.41B & A10.03. PLEASE
 CORRELATE THE DRAWING INDEX WITH
 SUBMITTED PLANS.
 25) THE FOLLOWING SHEETS ON THE DRAWING
 INDEX WERE NOT SUBMITTED. A1.02, A3.11,
 A3.12, A3.14, A3.15, A3.24, A4.14,
 A5.01, A5.11, A6.53A, A6.56A, A8.12,
 A8.13, A8.14, A9.22, A10.10, AND
 LS0.00.
 PLEASE SUBMIT ALL SHEETS INDICATED ON
 THE DRAWING INDEX. SECTION 104.2.1.
 26) PLANS SUBMITTED ARE NOT COMPLETE.
 MANY SHEETS APPEAR TO BE INCOMPLETE AND
 THE FOLLOWING SHEETS SHOWN ON THE INDEX
 WERE NOT SUBMITTED. P2.01, P2.05, P2.06,
 P2.27, P2.29, P2.30, P2.31, P2.32,
 P2.34, P2.35, P2.36, P2.62, P2.63,
 P2.64, P2.65, P2.66, P2.67, P2.68,
 P2.69, P3.03, P3.04, P3.05, P3.06,
 P3.07, P3.08, P3.09, P3.10, P3.11,
 P3.12, P3.13, AND P6.02.
 27) SUBMIT A STORM BLDG DRAIN ISOMETRIC
 SHOWING ALL PIPE SIZES, AND SHOW THE
 LOCATION OF ALL STORM RISER DIAGRAMS AS
 THEY CONNECT TO THE BLDG. DRAIN AND SHOW
 SQUARE FOOTAGE AS IT ACCUMULATES IN THE
 SYSTEM. SECTIONS 1106, 1107 & 104.2.1.
 28) SUBMIT STORM RISER DIAGRAMS SHOWING
 ALL PIPE SIZES AND SQ.FT. SECTIONS 1106,
 1107 AND 104.2.1.
 29) SUBMIT A CONDENSATE BLDG DRAIN
 ISOMETRIC SHOWING ALL PIPE SIZES.
 SECTION 104.2.1.
 30) SUBMIT CONDENSATE RISER DIAGRAM.
 SECTION 104.2.1
 31) SUBMIT A SANITARY BLDG. DRAIN
 ISOMETRIC. SHOW ALL PIPE SIZES, LOCATION
 OF EACH RISER CONNECTING TO BLDG. DRAIN,
 AND DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. SECTION 104.3.1.1.
 32) SHEETS FOR UNIT TYPES ARE INCOMPLETE
 AND REQUIRE MORE INFORMATION. SOME
 SHEETS SHOW SANT., VENT, WATER, COND.,
 T/P, OR ANOTHER UNIDENTIFIED LINE, BUT
 ALL DO NOT HAVE ALL INFORMATION
 REQUIRED.
 33) SHOW STACK NUMBERS FOR EACH STACK IN
 ALL UNIT SHEETS. SECTION 104.2.1.
 34) SHT P2.11 IS MISLABELED AS M2.11, OR
 IT IS A MECH. SHEET. PLEASE CLARIFY.
 SECTION 104.2.1.
 34) SHT P2.02 UNIT 2, INDICATE WHERE LAV
 RISER CONNECTS TO THE SANT. BRANCH LINE.
 SECTION 104.2.1.
 UNIT 3, THE VENT LINE IS SHOWN AS
 SANT.
 UNIT 4, NO SANT. TO W.M, NO VENT LINES
 SHOWN. SECTION 104.2.1.
 35) SHT P2.03 ALL UNITS, NO VENT LINES
 SHOWN, NO WATER LINES SHOWN.
 UNIT 5, NO SANT. TO W/M.
 UNIT 8, ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUP SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. THE
 KITCHEN SINK SHALL DISCHARGE DOWNSTREAM
 OF THE WET VENT. SECTION 909.1
 36) SHT P2.04 PIPING INCOMPLETE. SECTION
 104.2.1.
 37) SHT P2.07 PIPING INCOMPLETE.
 104.2.1
 38) SHT P2.08 UNIT 4, LAV VENT SHOWN OUT
 OF THE WALL. SEC 104.2.1.
 39) SHTS P2.09 & P2.10 PIPING
 INCOMPLETE. NO WATER LINES. SEC
 104.2.1.
 40) SHT P2.12 PIPING INCOMPLETE.
 UNIT 15 SHOWER NOT VENTED. SEC
 901.2.1.
 41) SHT P2.13 PIPING NOT COMPLETE.
 SECTION 104.2.1.
 42) SHT P2.14 PIPING INCOMPLETE.
 UNIT HH1 MASTER BATH DOUBLE LAV SHOWS
 SANT PIPING FROM TWO DIFFERENT RISERS.
 PLEASE CLARIFY. SEC 104.2.1.
 TRASH CHUED LABELED AS PRIMARY AIR
 SHAFT #3. PLEASE CLARIFY. 104.2.1.
 43) SHT P2.15 PIPING INCOMPLETE.
 UNIT VV1 SHOWS VENT UNDER M/B TUB.
 PLEASE CLARIFY.
 UNIT A1 IS LAV IN M/B ON A SEPARATE
 RISER STACK FROM OTHER M/B FIXTURES.
 PLEASE CLARIFY. SECTION 104.2.1.
 44) SHTS P2.17 THRU P2.54 PIPING
 INCOMPLETE. SECTION 104.2.1.
 45) P2.21 UNITS A1 & VV1 BATH #2 SHOWER
 NOT VENTED. SECTION 901.2.1.
 UNIT A1 WHAT TYPE OF VENT IS THE
 KITCHEN SINK UTILIZING? SECTION 901.2.1
 46) SHT P2.39 HAS A REFERENCE TO SHT
 P2.
 NO SHT P2. IS LOCATED. PLEASE CLARIFY.
 SECTION 104.2.1.
 47) SHT 2.44 UNIT S MASTER BATH WATER
 CLOSET, MAX 10' FROM POINT OF VENT.
 TABLE 906.1.
 48) SHT P2.50 UNTI P2 LAUNDRY SINK SHALL
 NOT DISCHARGE INTO THE WET VENT FOR THE
 BATHROOM FIXTURES. SECTION 909.1.
 49) SHT P2.53 UNIT 0 BATH #2 KITCHEN
 SINK SHALL NOT DISCHARGE INTO THE WET
 VENT. SECTION 909.1.
 50) SHT 2.57 WOMEN'S BATHROOM DOES NOT
 REFLECT THE SANT. RISER DIAGRAM. W/C IN
 WOMEN'S STALL MAX. 10' FROM POINT OF
 VENT. TABLE 906.1. INDICATE USE OF FLOOR
 DRAIN FOR FIXTURE NEXT TO SHOWER IN
 MEN'S BATHROOM. SECTION 104.2.1.
 51) ALL SANT. RISERS WITH WASH MACHINES,
 REQUIRE A STANDPIPE AND THE CLEANOUT
 SHALL BE LOCATED 4' ABOVE THE FLOOR FOR
 ACCESS. SECTIONS 1002.1, 802.4 &
 708.10.
 52) SHT P3.01 DOMESTIC WATER RISER
 DIAGRAMS. AIR CHAMBERS ARE NOT APPROVED.
 DELETE FROM RISERS. SECTION 604.9.
 53) SHT 3.14 RISER 21 MAX 4 FIXTURE
 UNITS ON 2" WET VENT. TAB 909.3
 54) SHT PE.15 RISERS 27/34 OFFSET VENT
 REQUIRED. SECTION 915.
 RISERS 55/56 IDENTIVY FIXTURE BY
 KITCHEN SINK. SEC 104.2.1
 RISER 28 OFFSET VENT REQUIRED. 915.
 RISERS 29/31 OFFSET VENT REQUIRED. 915
 - MASTER BATH 21ST FLOOR MAX 4 FU ON 2"
 WET VENT. TABLE 909.3. FLOORS 6 THRU 15,
 MAXIMUM 4 FU ON 2" WET VENT. TAB 909.3.
 RISERS 30/32 OFFSET VENT REQUIRED.
 915.
 MAX 4 FU ON 2" WET VENT. TAB 909.3
 RISER 38 OFFSET VENT REQUIRED. SEC 915
 MAX. 4 FU ON 2" WET VENT TAB 909.3.
 55) SHT P3.16 RISERS 39.75 OFFSET VENT
 REQUIRED SEC 915.
 RISER 39 MAX. 4 FU ON 2" WET VENT.
 TABLE 909.3.
 RISER 59 OFFSET VENT REQD. SEC 915.
 RISER 11 OFFSET VENT REQD. SECTION
 915.
 RISER 12 OFFSET VENT REQD. SEC 915. -
 INDICATE WHICH FLOOR/FLOORS THE SANT. IS
 FOR ABOVE THE 15TH FLOOR. - MAX 4 FU ON
 2" WET VENT. TABLE 909.3
 56) SHT P3.17 RISER 23 OFFSET VENT
 REQUIRED. SECTION 915.
 RISER 24 OFFSET VENT REQD. SEC. 915. -
 MAX. 4 FU ON 2" WET VENT. TABLE 909.3
 RISERS 26/35 OFFSET VENT REQD. SEC. 915
 - FIXTURE MISLABELED AS KITCHEN SINK IN
 BATHROOM GROUP. SECTION 104.2.1.
 57) SHT P3.18 RISER 70 OFSET VENT REQD.
 SECTION 915. - MAX 4 FU ON 2" WET VENT.
 TABLE 909.3.
 RISER 15 MAX. 4 FU ON 2" WET VENT.
 TABLE 909.3
 RISER 18 ABOVE 21ST FLOOR STATES VENT
 BACK DOWN TO 15TH FLOOR. PLEASE CLARIFY
 SECTIONS 104.2.1. & 903.1.
 RISER 19 ABOVE 21TH FLOOR STATES VENT
 BACK DOWN TO 15TH FLOOR. PLEASE CLARIFY
 SECTIONS 104.2.1. & 903.1.
 58) SHT P3.19 RISER 1 OFFSET VENT
 REQUIRED. SECTION 915.
 RISERS 2/55 SOIL STACK AND VENT STACK
 ARE CROSSED. - OFFSET VENT REQUIRED.
 SECTION 915.
 RISER 3 VENT STACK SHALL CONTINUE AND
 NOT TIE BACK INTO THE SOIL STACK.
 SECTION 903.1
 RISER 4 MAX 4 FU ON 2" WET VENT.
 909.3.
 RISER 5 OFFSET VENT REQUIRED. SEC 915.
 59) SHT P3.20 RISER 6 OFFSET VENT
 REQUIRED. SECTION 915. - MAX 4 FU ON 2"
 WET VENT. TABLE 909.3.
 RISER 54 MAX 4 FU ON 2" WET VENT. TABLE
 909.3.
 RISER 7 OFFSET VENT REQUIRED. SEC 915.
 MAX. 4 FU ON 2" WET VENT. TABLE 909.3.
 RISER 8 OFFSET VENT REQUIRED. SEC 915.
 MAX 4 FU ON 2" WET VENT. TABLE 909.3.
 60) SHT P3.21 RISER 40 OFFSET VENT
 REQUIRED. SECTION 915.
 RISER 41 OFFSET VENT REQD. SEC 915.
 RISER 44 OFFSET VENT REQD. SEC 915. -
 INDICATE IF THERE ARE BRANCH LINES
 CONNECTING TO STACK ON THE 17TH THRU
 20TH FLOORS. SECTION 104.2.1.
 RISER 76 MAX 4 FU ON 2" WET VENT. TABLE
 909.3.
 61) SHT P3.22 RISER 45 OFFSET VENT REQD.
 SECTION 915. - INDICATE IF THERE ARE
 BRANCH LINES CONNECTING TO THE STACK ON
 THE 17TH THRU 20TH FLOORS. SEC 104.2.1.
 RISER 46 OFFSET VENT REQD. SEC 915. -
 MAXIMUM 4 FU ON 2" WET VENT. TABLE
 909.3
 RISER 47 OFFSEC VENT REQD. SEC 915. -
 MAXIMUM 4 FU ON 2" WET VENT. TABLE
 909.3
 RISER 49 OFFSET VENT REQD. SEC 915. -
 MAXIMUM 4 FU ON 2" WET VENT. TABLE
 909.3
 62) SHT P3.23 RISER 63 MAXIMUM 4 FU ON
 2" WET VENT. TABLE 909.3
 RISER 43 OFFSET VENT REQD. SEC 915. -
 MAXIMUM 4 FU ON 2" WET VENT. TABLE
 909.3
 RISER 60 WASH MACHINE AND KITCHEN SINK
 SHALL CONNECT TO THE SANT. STACK NOT THE
 VENT STACK. SECTION 104.2.1.
 63) SHT P6.01 COOLING TOWER MAKE UP
 DETAIL, INDICATE METHOD FOR REQUIRED
 BACKFLOW PROTECTION. SECTION 608.13.2. -
 WATER HEATER PIPING DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED. SECTION
 607.3.2. - TRASH CHUTE PIPING DIAGRAM.
 INDICATE METHOD FOR REQUIRED BACKFLOW
 PROTECTION. SECTION 608.13.2.
 64) BACKFLOW PROTECTION REQUIRED FOR THE
 POOL MAKE UP WATER. SUBMIT A DETAIL.
 SECTION 608.13.2.
 65) BECAUSE THE PLANS ARE INCOMPLETE,
 MORE COMMENTS MAY BE FOURTHCOMMING WHEN
 THE PLANS ARE RESUBMITTED. - PLEASE
 RETURN THE PLUMBING PLANS WITH THE RED
 LINE NOTES WHEN RESUBMITTING TO HELP
 REVIEWING PLANS FOR SECOND REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 11 Status P Date 2008-07-29 Cont ID  
Sent By mflis Date 2008-07-29 Time 14:35 Rev Time 0.00
Received By mflis Date 2008-07-29 Time 14:35 Sent To P
Notes
2008-07-29 14:39:56ZONING REVIEW: PASSED WITH PROVISO
  
 PROVISO ITEMS:
  
 1) ON LP-1 - PITCH APPLE SPECIES NOT APPROVED AS
 SUBSTITUTE. PLANTING SHALL MATCH CITY PLAZA I PLANT BED
 PROVIDED ACROSS LAKEVIEW.
  
 2) ON LL-1 - LAMP POSTS ON OLIVE AND TRINITY SHALL
 MATCH TYPICAL OLIVE POST (SEE CITY STANDARD), AS
 APPROVED BY ENGINEERING SERVICES
  
 3) ON LL-1 - FOUR LIGHTS INDICATED ALONG DROP-OFF SHALL
 BE REMOVED PER MEETING WITH CITY STAFF, AND AS APPROVED
 BY ENGINEER SERVICES
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 10 Status N Date 2008-05-08 Cont ID  
Sent By aaponte Date 2008-05-08 Time 14:25 Rev Time 0.00
Received By aaponte Date 2008-05-08 Time 14:25 Sent To M
Notes
2008-05-08 14:26:25MECHANICAL ONLY. NOT REQUIRED.

Review Stop Z ZONING
Rev No 9 Status P Date 2008-04-16 Cont ID  
Sent By aaponte Date 2008-04-16 Time 10:48 Rev Time 0.00
Received By aaponte Date 2008-04-16 Time 10:48 Sent To  
Notes
2008-04-16 10:50:06CIVIL DRAWINGS ONLY.REPLACE EXISTING F CURB ALONG OLIVE
 AV. AND HANDICAP RAMP AT THE CORNER OF OLIVE AV. AND
 LAKEVIEW AVE.

Review Stop Z ZONING
Rev No 8 Status N Date 2007-08-03 Cont ID  
Sent By aaponte Date 2007-08-03 Time 13:25 Rev Time 0.00
Received By aaponte Date 2007-08-03 Time 13:25 Sent To  
Notes
2007-08-03 13:25:32STRUCTURAL REVISIONS ONLY

Review Stop Z ZONING
Rev No 7 Status P Date 2007-02-15 Cont ID  
Sent By aaponte Date 2007-02-15 Time 10:51 Rev Time 0.00
Received By aaponte Date 2007-02-15 Time 10:51 Sent To  
Notes
2007-02-15 10:52:15LNADSCAPE CHANGES APPROVED BASED ON COMMENTS FROM
 10/17/05

Review Stop Z ZONING
Rev No 6 Status P Date 2006-07-28 Cont ID  
Sent By aaponte Date 2006-07-28 Time 15:51 Rev Time 0.00
Received By aaponte Date 2006-07-25 Time 15:50 Sent To  
Notes
2006-07-28 00:00:00CHANGES ON ELEVATION APPROVED

Review Stop Z ZONING
Rev No 5 Status P Date 2005-12-23 Cont ID  
Sent By astelly Date 2005-12-23 Time 08:09 Rev Time 0.00
Received By astelly Date 2005-12-23 Time 08:09 Sent To  
Notes
2005-12-23 00:00:0012/23/05 LANDSCAPE PLANS APPROVED BY AMY
 STEELY AND INSERTED IN PACKAGE WAITING
 FOR COMMERICAL BOARD (BY JENNIFER).

Review Stop Z ZONING
Rev No 4 Status P Date 2005-10-17 Cont ID  
Sent By aaponte Date 2005-10-17 Time 16:03 Rev Time 0.00
Received By aaponte Date 2005-10-17 Time 16:39 Sent To  
Notes
2005-10-17 00:00:00PROVISO
 1.HANDICAP PARKING DIMENSIONS
 SHALL BE ADJUSTED ACCORDING TO DAC FINAL
 VARIANCE APPROVAL BEFORE CO ISSUANCE.
 2. PLEASE REPLACE PALMS ALONG TRINITY
 PLACE FOR HIGH RISE OAKS.
 3. PLEASE PLACE STRUCTURAL SOIL
 UNDERNEAD THE SIDEWALK ADJACENT TO THE
 TREE PLANTERS.
 4. TREE HOLE SHALL BE 3 TIMES THE SIZE
 OF THE ROOTBALL AT THE DEPTH OF THE
 ROOTBALL.
 5. PLEASE CONTACT ALAN BARRATA,
 LANDSCAPE ARCHITECT FOR (822-1462) FOR
 PLANTING DETAILS.
 6. SIDEWALK MATERIAL TO BE DETERMINED BY
 THE CITY AND MODIFIED BY THE APPLICANT.

Review Stop Z ZONING
Rev No 3 Status F Date 2005-09-01 Cont ID  
Sent By aaponte Date 2005-09-01 Time 16:24 Rev Time 0.00
Received By aaponte Date 2005-09-01 Time 16:24 Sent To  
Notes
2005-09-01 00:00:001. HANDICAP SPACES SHALL BE 12 FEET WIDE
 MINIMUM WITH A 5 FEET AISLE.
 2. PLEASE SUBMIT LANDSCAPE DRAWINGS TO
 CONFIRM COMPLIANCE WITH REGULATION.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-04-25 Cont ID  
Sent By aaponte Date 2005-04-25 Time 13:54 Rev Time 0.00
Received By aaponte Date 2005-04-25 Time 13:54 Sent To  
Notes
2005-04-25 00:00:001.PLEASE INCLUDE A TABLE CONTAINING THE
 EXACT AMOUNT OF TDR UTILIZED ON THE
 PROJECT.
 2. BASED ON DAC APPROVAL, AN
 ARCHITECTURAL ARTICULATION OF THE RECESS
 LINE SHALL BE CARRIED AROUND THE
 BUILDING, EXCLUDING THE TOWER ELEMENTS.
 3. PLEASE PROVIDE LANDSCAPE DRAWINGS.
 4. PLEASE PROVIDE INFORMATION TO CONFIRM
 COMPLIANCE WITH THE MINIMUM 15%
 LANDSCAPE REQUIRED FOR THE ROOFTOP
 TERRACE.
 5.PLEASE REMOVE THE "LEASABLE SPACE"
 IDENTIFIED ON THE POOL DECK LEVEL AND
 PROVIDE INFORMATION TO CONFIRM
 COMPLIANCE WITH MAXIMUM 30% ALLOWED FOR
 COVERED STRUCTURES ON THE ROOFTOP
 TERRACE.
 6.PLEASE INDICATE THE PARKING SPACES
 ASSIGNED TO THE LIVE/WORK TYPE UNITS.
 7. PLEASE ADJUST HANDICAP PARKING SPACES
 TO MEET REQUIREMENTS ACCORDING WITH
 CITY'S CODE.
 8. PROPOSED AWNING ON OLIVE AVENUE WILL
 REQUIRE AIR-RIGHTS EASEMENT IF IT IS
 PROJECTING OVER THE RIGHT-OF-WAY.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-11-06 Cont ID  
Sent By aaponte Date 2005-01-18 Time 09:39 Rev Time 0.00
Received By aaponte Date 2005-01-18 Time 09:39 Sent To  
Notes
2005-01-18 00:00:001. PLEASE PROVIDE A COPY OF THE TDR
 CERTIFICATE AND A TABLE CONTAINING THE
 AMOUNT OF SQUARE FOOTAGE UTILIZED.
 2. BASED ON DAC APPROVAL, AN
 ARCHITECTURAL ARTICULATION OF THE RECESS
 LINE SHALL BE CARRIED AROUND THE
 BUILDING, EXCLUDING THE TOWER ELEMENTS.
 3. PLEASE CONFIRM COMPLIANCE WITH SIDE
 SETBACK REQUIREMENT. ART IV SEC 94-108
 (B)(3).
 3. SETBACK ON OLIVE AVENUE IS EXCEEDING
 THE MAXIMUM SETBACK OF 8'7" GRANTED BY
 DAC VARIANCE.THE BUILDING IS SETBACK
 15'6" IN FRONT OF THE GRAND LOBBY.
 4. PLEASE PROVIDE A TABLE THAT CONFIRMS
 MEZZANINES ARE IN COMPLIANCE WITH THE
 PERMISSIBLE PERCENTAGE OF FLOOR AREA FOR
 A MEZZANINE AS DEFINED IN THE CITY'S
 BUILDING CODE.
 5.PLEASE CONFIRM 8" SIDEWALK CLEARANCE
 ON THE WESTERN MOST PAR OF LAKEVIEW
 AVENUE.
 6.PLEASE PROVIDE INFORMATION THAT
 CONFIRMS COMPLIANCE WITH RECESS LINE AT
 THE TOP OF 14TH FLOOR ACCORDING WITH DAC
 APPROVAL.
 7. PLEASE PROVIDE INFORMATION TO CONFIRM
 COMPLIANCE WITH THE MINIMUM 15%LANDSCAPE
 REQUIRED FOR THE ROOFTOP TERRACE.
 8. PLEASE PROVIDE INFORMATION TO CONFIRM
 COMPLIANCE WITH MAXIMUM 30% ALLOWED FOR
 COVERED STRUCTURES.
 9. PLEASE CLARIFY WHAT IS THE "LEASEABLE
 SPACE" IDENTIFIED ON THE POOL DECK
 LEVEL.
 10. STREET TREES SHALL BE INSTALLED IN
 THE SIDEWALK ADJACENT TO THE CURB ALONG
 THE FRONTAGE LINE, WITH A REGULAR
 SPACING NO GREATER THAN 40'.
 11. PLANTERS ARE NOT ALLOWED ALONG THE
 CURB.
 12. PLEASE PROVIDE INFORMATION TO
 CONFIRM COMPLIANCE WITH MAXIMUM GLAZED
 AREA PERMITTED.