| Plan Review Stops For Permit 04120353 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-10-02 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-01-24 |
Time |
18:10 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | ADDRESS MATCHES THE PCN |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-03-29 |
|
|
Cont ID |
|
| Sent By |
jhiggins |
Date |
2006-03-29 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
|
Date |
2008-02-15 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2004-12-13 00:00:00 | PCN CORRECTED TO: 74434322140050010 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
384 |
Status |
N |
Date |
2008-08-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-08-01 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-08-01 |
Time |
08:15 |
Sent To |
FIRE |
|
| Notes |
| 2008-08-07 08:17:49 | THE RESIDENT EMERGENCY PROCEDURE EVACUATION PLAN | | | SUBMITTAL WAS SENT TO FIRE. MJ |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
383 |
Status |
P |
Date |
2008-05-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-05-30 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-05-30 |
Time |
10:40 |
Sent To |
PC |
|
| Notes |
| 2008-05-30 13:35:07 | FBC 2001 | | | SUBMITAL #08810.06 DOOR AT STEAM ROOM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
382 |
Status |
P |
Date |
2008-05-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-05-16 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-05-16 |
Time |
10:24 |
Sent To |
PC |
|
| Notes |
| 2008-05-16 10:40:39 | SUBMITTAL #05500.07 GARAGE PIPE PROTECTION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
381 |
Status |
N |
Date |
2008-04-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-04-30 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-04-30 |
Time |
11:08 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
380 |
Status |
F |
Date |
2008-02-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-02-15 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-02-15 |
Time |
09:40 |
Sent To |
PC |
|
| Notes |
| 2008-02-15 13:51:54 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S. OLIVE AVE | | | CONT: KAST CONST. | | | TEL: (561)329-9396 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND 2-15-08 | | | ACTION: DENIED | | | FBC 2001 SUBMITTAL #05100.02 TRUSS DETAIL | | | CONNECTIONS. | | | | | | 1) THE REPORT SUBMITTED REFERS TO FBC 2004 WITH THE | | | 2006 SUPPLEMENT. THE WIND SPEED INDICATED ON THE | | | SUBMITTAL IS 130MPH (ASCE 7-02 CLOSED). **NOTE** THIS | | | PROJECT HAS A PERMIT WHICH WAS ISSUED UNDER THE FBC | | | 2001 EDITION. THE WIND SPEED PER FBC 2001 TABLE | | | 1606.1.6.1 IS 140MPH 3SEC GUST (ASCE 7-98) SEE SECTION | | | 1606.1.1 FOR THE INFORMATION RELATED TO WIND. ALL | | | CALCULATION AND SPECIFICATIONS SHALL BE IN ACCORDANCE | | | WITH THE FBC 2001. | | | | | | 2)FAC 61G15-23.002A PROFESSIONAL ENGINEER MAY ONLY | | | SEALAN ENGINEERING REPORT, PLAN, PRINT OR | | | SPECIFICATION IF THAT PROFESSIONAL ENGINEER WAS IN | | | RESPONSIBLE CHARGE OF THE PREPARATION AND PRODUCTION OF | | | THE ENGINEERING DOCUMENT AND THE PROFESSIONAL ENGINEER | | | HAS THE EXPERTISE IN THE ENGINEERING DISCIPLINE USED IN | | | PRODUCTION THE ENGINEERING DOCUMENT IN QUESTION.THE | | | TRUSS DESIGN ENGINEER IS SCOTT L. SCHURWAN, HIS LICENSE | | | NUMBER IS 31867. THE ENGINEER WHO SEALS THE TRUSS | | | REPORTS IS RAJAN SOWRI HIS LICENSE NUMBER IS 52083. | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, | | | AND LICENSE NUMBER ON EACH SHEET. IF PRACTICING THROUGH | | | A DULY AUTHORIZE ENGINEERING BUSINESS, ENGINEERS SHALL | | | LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION | | | NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. A | | | TITLE BLOCK SHALL APPEAR ON EACH SHEET CONTAINING THE | | | PRINTED NAME, ADDRESS, AND LICENSE NUMBER OF THE | | | ENGINEER. | | | | | | 3)61G1-16.004 TITLE BLOCK. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
379 |
Status |
P |
Date |
2008-02-13 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2008-02-13 |
Time |
19:22 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2008-02-13 |
Time |
19:22 |
Sent To |
|
|
| Notes |
| 2008-02-13 19:26:43 | SUBMITTAL ON 1/29/08 FOR KOLTER LETTER ON EIFS | | | ATTACHMENT ADHESIVE SUPPORTED BY DOW CHEMICALS COMPANY | | | ENGINEER'S LETTER COMPARING MAXIMUM USE TEMPERATURE | | | RATING OF THE ADHESIVE AND THE EIFS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
378 |
Status |
F |
Date |
2008-02-01 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-02-01 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-02-01 |
Time |
10:17 |
Sent To |
PC |
|
| Notes |
| 2008-02-01 16:07:25 | REVIEW: FBC 2001SUBMITTAL #05100.01 | | | ACTION: DENIED 2-1-08 | | | | | | 1) 106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS THAT | | | ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. SUBMIT PRODUCT | | | APPROVAL FOR THE ?HARDISOFFIT?. IN THE PRODUCT APPROVAL | | | PACKAGE CIRCLE ALL ITEMS AND TABLES APPLICABLE TO THE | | | INSTALLATION OF THE PRODUCT. | | | | | | 2) PROVIDE THE FASTENER SPACING WHICH WILL MEET THE | | | DESIGN PRESSURES FOR THOSE AREAS WHERE THE | | | ?HARDISOFFIT? WILL BE INSTALLED. ALL INFORMATION | | | SUBMITTED FOR OUR RECORD RETENTION PROGRAM SHALL BE | | | CLEAR, LEGIBLE AND NO ?WHITE-OUT? CHANGES ALLOWED. THE | | | INFORMATION FOR THE ?HARDISOFFIT? IS ILLEGIBLE WPB | | | AMENDMENTS 106.1.3. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
377 |
Status |
F |
Date |
2008-02-01 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-02-01 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-01-29 |
Time |
11:13 |
Sent To |
PC |
|
| Notes |
| 2008-01-29 13:00:02 | FBC 2001 | | | SUBMITTAL #02400.06 LIMEROCK BASE. THE INFORMATION | | | SUBMITTED IS ILLEGIBLE AND WAS REJECTED BY CRAVEN, | | | THOMPOSN & ASSOCIATES, ENGINEERS, PLANNERS & SURVEYORS | | | INC. THE REPORT NEES THE APPROVAL OF THE ENGINEERING | | | FIRM. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY. FBC 106.1.1. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
376 |
Status |
P |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-01-29 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-01-29 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2008-01-29 11:03:54 | FBC 2001 | | | SHORING AND GC LETTER FOR THE RESORHING FOR LEVEL 20 | | | POUR B. SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
375 |
Status |
F |
Date |
2008-01-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-01-04 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-01-04 |
Time |
10:22 |
Sent To |
PC |
|
| Notes |
| 2008-01-04 10:22:11 | FBC 2001 | | | SUBMITTAL #05100.02.01 | | | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S. OLIVE AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | 1-4-08 | | | | | | 1)THE DRAWINGS SUBMITTED WITH THE SEAL AND SIGNATURE | | | OF ENGINEER KENNETH J. PAGANO REQUIRES DETAILS AND | | | INFORMATION FROM THE ENGINEER OF RECORD SPECIFIC TO THE | | | OMITTED EMBEDDED PLATES. THE NEW CONNECTION INFORMATION | | | SHALL CONTAIN THE ORIGINAL SIGNATURE OF THE ENGINEER OF | | | RECORD, ALONG WITH HIS/HER SEAL AND DATED ON WHICH THE | | | INFORMATION IS SIGNED. THE 8 X 11 SHEET SUBMITTED | | | REQUIRES MORE INFORMATION TO SHOW WHAT WILL REPLACE THE | | | DELETED AND OMITTED ITEMS SHOWN ON THAT SHEET. SUBMIT A | | | NEW SHEET SHOWING THE ATTACHMENT DETAIL WITH THE SIZE | | | AND TYPE OF STRAPS ALONG WITH THE SPACING AS STATED ON | | | SHEET 2 OF 3. SHEET 2 ALSO REFERS TO DETAIL TS027-30-31 | | | AND 43; I CANNOT FIND THIS DETAIL IN THE SUBMITTED | | | PACKAGES. PLEASE SHOW THIS DETAIL. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
374 |
Status |
P |
Date |
2007-12-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-15 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-15 |
Time |
08:43 |
Sent To |
PC |
|
| Notes |
| 2007-12-15 09:01:37 | FBC 2001 | | | SUBMITTAL #03100.31- HIGH ROOF SHORING/ RE- SHORING |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
373 |
Status |
P |
Date |
2007-12-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-15 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-15 |
Time |
08:06 |
Sent To |
PC |
|
| Notes |
| 2007-12-15 08:41:14 | FBC 2001 | | | SUBMITTA;L #10536.01 AWNINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
372 |
Status |
P |
Date |
2007-12-01 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-01 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-01 |
Time |
11:06 |
Sent To |
PC |
|
| Notes |
| 2007-12-01 11:14:46 | FBC 2001 | | | SUBMITTAL #03460.09 SECOND FLOORBALCONY STONE PANEL | | | ATTATCHMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
371 |
Status |
P |
Date |
2007-12-01 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-01 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-01 |
Time |
10:44 |
Sent To |
E |
|
| Notes |
| 2007-12-01 10:50:43 | FBC 2001 | | | SUBMITTAL #13032.01 SAUNA AND STEAN ROOM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
370 |
Status |
F |
Date |
2007-11-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-11-16 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-11-16 |
Time |
06:07 |
Sent To |
PC |
|
| Notes |
| 2007-11-16 07:35:35 | BUILDING PLAN REVIEW | | | PERMIT: | | | ADD: | | | CONT: | | | TEL: (561)###-#### | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW:1ST | | | ACTION: DENIED | | | | | | 1A) INDICATE ON THE DRAWINGS HOWTHE"STONE VENEER" | | | WILLL MEET REQUIREMENTS OF FBC 1405.FL 61G1-23.015 | | | (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND | | | REVIEWING ALL PROJECT DATA, REPORTS,SHOP DRAWINGS | | | ETC...THE ARCHITECT OR ENGINEER SHALL "SIGN, SEAL AND | | | DATE THE DRAWING. | | | | | | ANY HAND WRITTEN INFORMATION SHALL BE SIGN AND DATED | | | BY THE ARCHITECT OR ENGINEER WHO IS MAKING THE CHANGES. | | | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH | | | DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND | | | SPECIFICATIONS, FOR RECORD RETENTION PROGRAM. PROVIDE | | | NEW DRAWINGS WITH OUT THE HAND WRITTEN CHANGES. | | | 106.1.3* | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
369 |
Status |
P |
Date |
2007-11-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-11-05 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-11-05 |
Time |
10:12 |
Sent To |
PC |
|
| Notes |
| 2007-11-05 10:20:54 | FBC 2001 | | | SUBMITTAL #09100.07 ACOUSTICAL CEILING PLAN AND | | | DETAILS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
368 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-25 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-25 |
Time |
12:50 |
Sent To |
PC |
|
| Notes |
| 2007-10-25 12:52:24 | FBC 2001 | | | SUBMITTAL #07551.02 HEAT | | | WELDED (TORCH DOWN) MODIVIED BITEMEN ROOFING SYSTEM. | | | CHANGE FROM HOT MOP TO TORCH DOWN. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
367 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-25 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-25 |
Time |
12:00 |
Sent To |
PC |
|
| Notes |
| 2007-10-25 12:23:25 | FBC 2001 | | | SUBMITTAL #07551.01.01 ROOFING SUBMITTALS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
366 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-19 |
Time |
18:01 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-19 |
Time |
11:00 |
Sent To |
PC |
|
| Notes |
| 2007-10-19 18:01:11 | FBC 2001 | | | SUBMITTAL #05520.07.02 / #05520.08.02 / #05520.09.02 | | | TWO OF THE PLANS HAVE THE SAME NUMBER HOWEVER THE | | | INFORMATIOON SHEET INDICATES THAT EACH DRAWING SHALL | | | HAVE A DIFFERENT NUMBER. CLARIFY. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
365 |
Status |
P |
Date |
2007-10-19 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-19 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-19 |
Time |
08:05 |
Sent To |
PC |
|
| Notes |
| 2007-10-19 08:12:08 | FBC 2001 | | | SUBMITTA #15430.01 ACCESS DOORS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
364 |
Status |
P |
Date |
2007-10-19 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-19 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-19 |
Time |
07:47 |
Sent To |
PC |
|
| Notes |
| 2007-10-19 07:58:58 | FBC 2001 | | | SUBMITTAL #03200.53HIGH ROOF POUR D AND E MACHINE | | | ROOM AND BEANS,SLABS AND MISC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
363 |
Status |
F |
Date |
2007-10-19 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-19 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-19 |
Time |
06:24 |
Sent To |
PC |
|
| Notes |
| 2007-10-19 07:43:11 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S. OLIVE AVE | | | CONT: KAST CONST. | | | TEL: (561)329-9396 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST OF SUBMITTAL #05100.02 | | | ACTION: DENIED | | | | | | 1)FLORIDA STATUTES 471.025. (1)ALL FINAL DRAWINGS, | | | SPECIFICATIONS, PLANS OR DOCUMENTS PREPARED OR ISSUED | | | BY THE LICENSEE AND BEING FILED FOR PUBLIC RECORD AND | | | ALL FINAL DOCUMENTS PROVIDED TO THE OWNER OR THE | | | OWNER'S REPRESENTATIVE SHALL BE SIGNED BY THE LICENSEE, | | | DATED, AND SEALED WITH SAID SEAL.SUCH SIGNATURE, | | | DATE, DATE AND SEAL SHALL BE EVIDENCE OF THE | | | AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED. THE | | | SIGNATURE ON THE REPORS SHALL BE ORIGINAL, THE REPORTS | | | SUBMITTED CONTAIN EITHER A RUBBER STAMP OR PHOTO-COPY | | | SIGNATURE OF THE ENGINEER. THIS IS NOT ACCEPTABLE. | | | REPORTS BEING FILED FOR PUBLIC RECORS SHALL BE | | | ORIGINAL. | | | | | | 2)FAC 61G15-23.002 (2)A COVER OR INDEX SHEET FOR | | | ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET | | | MUST BE ORIGINALY SIGNED, SEALED AND DATED BY THOSE | | | PROFESSINOL ENGINEERS RESPONSIBLE FOR THE DOCUMENT. THE | | | COVER OR INDEX SHEET SHALL REFERENCE EACH SHEET OF THE | | | DOCUMENT. | | | | | | FBC 2001 | | | SUBMITTAL #05100.02DETAIL TRUSS CONNECTIONS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
362 |
Status |
P |
Date |
2007-10-19 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-19 |
Time |
06:24 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-19 |
Time |
05:53 |
Sent To |
PC |
|
| Notes |
| 2007-10-19 06:05:12 | FBC 2001 | | | SUBMITTAL #05100.04.01GAZEEBO AND SUPPLYAIR SHAFT | | | STEEL TRUSSES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
361 |
Status |
P |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-18 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-18 |
Time |
12:45 |
Sent To |
PC |
|
| Notes |
| 2007-10-18 14:07:30 | FBC 2001 | | | SUBMITTAL #05100.05.01STEEL TRUSSES FOR EXHAUST | | | SHAFT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
360 |
Status |
P |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-18 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-18 |
Time |
11:29 |
Sent To |
PC |
|
| Notes |
| 2007-10-18 12:14:35 | FBC 2001 | | | SUBMITTAL #05100.03.01 4TH FL MANSARD STEEL TRUSSEES | | | CONNECTION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
359 |
Status |
P |
Date |
2007-10-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-13 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-13 |
Time |
08:39 |
Sent To |
PC |
|
| Notes |
| 2007-10-13 08:45:02 | FBC 2001 | | | SUBMITTAL #03100.30 POOL DECK SHORING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
358 |
Status |
P |
Date |
2007-10-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-10-06 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-10-06 |
Time |
05:53 |
Sent To |
PC |
|
| Notes |
| 2007-10-06 07:00:53 | FBC 2001 | | | SUBMITTAL #07212.04.01 THERMAX HEAVY DUTY INSULATION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
357 |
Status |
P |
Date |
2007-09-30 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-09-30 |
Time |
23:05 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-09-30 |
Time |
23:05 |
Sent To |
|
|
| Notes |
| 2007-09-30 23:05:31 | STRUCTURAL REVISION SUBMITTED 7/11/07 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
356 |
Status |
P |
Date |
2007-09-30 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-09-30 |
Time |
23:03 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-09-30 |
Time |
23:03 |
Sent To |
|
|
| Notes |
| 2007-09-30 23:04:43 | ARCHITECTURAL AND STRUCTURAL REVISION SUBMITTED 7/6/07 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
355 |
Status |
P |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-15 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-15 |
Time |
11:05 |
Sent To |
PC |
|
| Notes |
| 2007-09-15 11:31:13 | FBC 2001 | | | SUBMITTAL #11011.03 WINDOW CLEANING & FACADE | | | MAINTENANCE SAFETYSYSTEM LAYOUT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
354 |
Status |
P |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-15 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-15 |
Time |
09:57 |
Sent To |
PC |
|
| Notes |
| 2007-09-15 10:34:02 | FBC 2001 | | | SUBMITTAL #03460.04WEST ELEVATION "F1"SICKER BAND | | | PRECAST. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
353 |
Status |
P |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-15 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-15 |
Time |
09:41 |
Sent To |
PC |
|
| Notes |
| 2007-09-15 09:56:48 | FBC 2001 | | | SUBMITTAL #03460.06WINDOW SILL AT LANI LEVEL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
352 |
Status |
P |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-15 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-15 |
Time |
09:16 |
Sent To |
PC |
|
| Notes |
| 2007-09-15 09:41:23 | FBC 2001 | | | SUBMITTAL #13152.07.02POOL & FOUNTAIN WATERPROOFING | | | SPEC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
351 |
Status |
P |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-15 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-15 |
Time |
08:08 |
Sent To |
PC |
|
| Notes |
| 2007-09-15 09:15:59 | FBC 2001 | | | SUBMITTAL #03200.52HIGH ROOF BEAMS, ARCH BEAMS, SLABS | | | AND MISC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
350 |
Status |
F |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-15 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-15 |
Time |
07:32 |
Sent To |
PC |
|
| Notes |
| 2007-09-15 08:04:27 | BUILDING PLAN REVIEW | | | PERMIT:04120353 | | | ADD: 717 S.OLIVE AVE. | | | CONT: KAST CONST. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW1ST | | | ACTION: DENIED | | | | | | 1)AWNINGS SHALL BE DESIGNED SO THAT FABRIC OR | | | MEMBRANE COVER CAN BE QUICKLY AND EASILY REMOVED PER | | | 3105.4.2.1 TIGHTLY WRAPED OR WOVEN CORDS ARE | | | ACCEPTABLE, WHEN 2 COPIES OF A DETAILED INSTRUCTION | | | GUIDE FOR REMOVAL ARE INCLUDED IN THE SUBMITTAL (PHOTOS | | | SHOWING THE DIFFERENT STEPS WITH INSTRUCTIONS CAN ALSO | | | BE SUBMITTED). IN ADDITION 2 COPIES OF A NOTORIZED | | | LETTER OF INTENT TO REMOVE AT 75 MPH ARE REQUIRED. SEE | | | GENERAL NOTE #7 FROM ENGINEERING EXPRESS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
349 |
Status |
P |
Date |
2007-09-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-21 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-15 |
Time |
07:03 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
348 |
Status |
P |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-15 |
Time |
07:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-15 |
Time |
06:31 |
Sent To |
PC |
|
| Notes |
| 2007-09-15 07:01:24 | FBC 2001 | | | SUBMITTAL #04220.09VERTICOAT REMEDIAL @ BLOCK WALLS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
347 |
Status |
P |
Date |
2007-09-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-15 |
Time |
06:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-15 |
Time |
05:44 |
Sent To |
PC |
|
| Notes |
| 2007-09-15 06:31:21 | FBC 2001 | | | SUBMITTAL #03200.42MAIN ROOF POUR B |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
346 |
Status |
F |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-11 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-11 |
Time |
11:24 |
Sent To |
PC |
|
| Notes |
| 2007-09-11 11:27:55 | FBC 2001 | | | SUBMITTALS #03200.50 WALLS REBAR AMENITY DECK POUR D. | | | | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S.OLIVE AVE | | | CONT: KAST CONST. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)AT LEAST ONE OF THE DRAWINGS SHALL HAVE THE | | | ORIGINAL STAMPS AND SIGNATURE OF APPROVAL OF THE | | | ENGINEER OF RECORD. CONSTRUCTION DOCUMENTS BEING FILED | | | FOR PUBLIC RECORD SHALL HAVE THE ORIGINAL SIGNATURE/ | | | DATE AND SEAL OF THE ARCHITECT OR ENGINEER WHO DESIGN | | | THE PROJECT. FBC. 106. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
345 |
Status |
P |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-11 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-11 |
Time |
10:55 |
Sent To |
PC |
|
| Notes |
| 2007-09-11 11:03:56 | FBC 2001 | | | SUBMITTAL #03200.51 POUR E AMENITY DECK/WALLS AND | | | REBAR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
344 |
Status |
F |
Date |
2007-09-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-10 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-10 |
Time |
06:49 |
Sent To |
PC |
|
| Notes |
| 2007-09-10 10:36:24 | FBC 2001 | | | SUBMITTALS #03200.47 REBAR AMENITY DECK POUR B. | | | | | | | | | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S.OLIVE AVE | | | CONT: KAST CONST. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)AT LEAST ONE OF THE DRAWINGS SHALL HAVE THE | | | ORIGINAL STAMPS AND SIGNATURE OF APPROVAL OFTHE | | | ENGINEER OF RECORD. CONSTRUCTION DOCUMENTS BEING FILED | | | FOR PUBLIC RECORD SHALL HAVE THE ORIGINAL SIGNATURE/ | | | DATE AND SEAL OF THE ARCHITECT OR ENGINEER WHO DESIGN | | | THE PROJECT. FBC. 106. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
343 |
Status |
P |
Date |
2007-09-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-10 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-10 |
Time |
06:01 |
Sent To |
PC |
|
| Notes |
| 2007-09-10 06:47:06 | FBC 2001 | | | SUBMITTAL #03200.49 REBAR- AMENITY DECK AND WALLS POUR | | | C. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
342 |
Status |
P |
Date |
2007-09-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-04 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-04 |
Time |
07:46 |
Sent To |
PC |
|
| Notes |
| 2007-09-04 07:53:05 | FBC 2001 | | | SUBMITTAL #07830.04MULTIPLE CONDUIT & METALLIC PIPE | | | PENETRATIONS THRU CONCRETE WALL AND FLOOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
341 |
Status |
P |
Date |
2007-09-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-04 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-04 |
Time |
07:14 |
Sent To |
PC |
|
| Notes |
| 2007-09-04 07:16:14 | FBC 2001 | | | SUBMITTAL #05520.11POWDER COAT PRODUCT DATA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
340 |
Status |
P |
Date |
2007-09-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-04 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-04 |
Time |
06:01 |
Sent To |
PC |
|
| Notes |
| 2007-09-04 06:09:55 | FBC 2001 | | | SUBMITTAL #05520.04.02TRELLIS DETAIL @ POOL DECK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
339 |
Status |
P |
Date |
2007-08-25 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-25 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-25 |
Time |
14:07 |
Sent To |
PC |
|
| Notes |
| 2007-08-25 14:25:39 | FBC 2001 | | | SUBMITTAL #03200.48POOL DECK SLAB POUR B |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
338 |
Status |
P |
Date |
2007-08-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-24 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-24 |
Time |
07:12 |
Sent To |
PC |
|
| Notes |
| 2007-08-24 07:31:41 | FBC 2001 | | | SUBMITTAL #03200.45MAIN ROOF DECK REBAR POUR E. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
337 |
Status |
P |
Date |
2007-08-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-24 |
Time |
07:08 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-24 |
Time |
06:44 |
Sent To |
PC |
|
| Notes |
| 2007-08-24 07:08:53 | FBC 2001 | | | SUBMITTAL #03365.17.03 22ND FLOOR ROOF PRE-STRESS | | | CALCS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
336 |
Status |
P |
Date |
2007-08-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-24 |
Time |
06:44 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-24 |
Time |
05:59 |
Sent To |
PC |
|
| Notes |
| 2007-08-24 06:05:52 | FBC 2001 | | | SUBMITTAL #03200.46 ABOVE ROOF WALLS COLUMNS AND POOL | | | DECK SLAB. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
335 |
Status |
P |
Date |
2007-08-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-23 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-23 |
Time |
18:44 |
Sent To |
PC |
|
| Notes |
| 2007-08-23 18:47:08 | FBC 2001 | | | SUBMITTAL #03100.28 MAIN ROOF SHORING PLAN. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
334 |
Status |
P |
Date |
2007-08-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-23 |
Time |
18:43 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-23 |
Time |
18:26 |
Sent To |
PC |
|
| Notes |
| 2007-08-23 18:43:12 | FBC 2001 | | | SUBMITTAL #03100.29 METAL DECK PLANTER LOCATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
333 |
Status |
P |
Date |
2007-08-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-23 |
Time |
18:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-23 |
Time |
18:08 |
Sent To |
PC |
|
| Notes |
| 2007-08-23 18:25:52 | FBC: 2001 | | | SUBMITTAL #03200.43 MAIN ROOF POUR C |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
332 |
Status |
P |
Date |
2007-08-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-23 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-23 |
Time |
17:38 |
Sent To |
PC |
|
| Notes |
| 2007-08-23 18:08:20 | FBC: 2001 | | | SUBMITTAL #0320.44 MAIN ROOF POUR D |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
331 |
Status |
P |
Date |
2007-08-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-23 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-23 |
Time |
17:05 |
Sent To |
PC |
|
| Notes |
| 2007-08-23 17:08:41 | FBC: 2001 | | | SHORING AND GC LETTER FOR POUR #126, LEVEL 22 POUR E. | | | SENT TO JERALD INBOX |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
330 |
Status |
P |
Date |
2007-08-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-23 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-23 |
Time |
16:50 |
Sent To |
PC |
|
| Notes |
| 2007-08-23 16:55:00 | FBC:2001 | | | SHOORING AND GC LETTER FOR POUR #125. ROOF LEVEL 22 | | | POUR D. SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
329 |
Status |
P |
Date |
2007-08-01 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-01 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-01 |
Time |
17:13 |
Sent To |
PC |
|
| Notes |
| 2007-08-01 17:16:06 | FBC 2001 | | | SHORING AND GC LETTER #22 FOR ROOF LEVEL 22 POUR C. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
328 |
Status |
F |
Date |
2007-08-01 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-01 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-07-26 |
Time |
08:21 |
Sent To |
|
|
| Notes |
| 2007-07-26 09:22:51 | BUILDING PLAN REVIEW | | | PERMIT:04120353 | | | ADD: 717 S.OLIVE AVE | | | CONT: KAST | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW:1ST | | | ACTION: DENIED | | | | | | 1)FBC 2001 SUBMITTAL #03100.27MAIN ROOF RESHORING. | | | ONE OF THE PAGES IN THE SET CONTAINS A PHOTO-COPY STAMP | | | OF THE STRUCTURAL ENGINEER. ALL INFORMATION BEING | | | STORED FOR PUBLIC RECORD SHALL HAVE THE ORIGINAL STAMP | | | AND SIGNATURE OF THE PERSON TAKING RESPONSIBILITY. FAC | | | 61G15-23.002. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
327 |
Status |
P |
Date |
2007-07-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-07-26 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-07-26 |
Time |
07:40 |
Sent To |
PC |
|
| Notes |
| 2007-07-26 08:17:46 | FBC 2001 | | | | | | SUBMITTAL #03200.41 ROOF DECK POUR 'A' |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
326 |
Status |
P |
Date |
2007-07-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-07-20 |
Time |
07:09 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-07-20 |
Time |
07:06 |
Sent To |
PC |
|
| Notes |
| 2007-07-20 07:08:57 | FBC. 2001 | | | | | | SHORING AND GC LETTER FOR POUR#122 LEVEL 22 POUR A. | | | SENT JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
325 |
Status |
P |
Date |
2007-07-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-07-12 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-07-12 |
Time |
07:30 |
Sent To |
PC |
|
| Notes |
| 2007-07-12 07:35:43 | FBC 2001 | | | RECEIVE 7/06/07 | | | | | | SUBMITTAL #03300.293000 PSI. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
324 |
Status |
P |
Date |
2007-07-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-07-12 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-07-12 |
Time |
07:11 |
Sent To |
PC |
|
| Notes |
| 2007-07-12 07:30:21 | FBC 2001 | | | RECEIVE 7/6/07 | | | SUBMITTAL #03100.25MAIN ROOF SHORING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
323 |
Status |
P |
Date |
2007-07-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-07-12 |
Time |
07:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-07-12 |
Time |
06:56 |
Sent To |
PC |
|
| Notes |
| 2007-07-12 07:05:52 | FBC 2001 | | | RECEIVE 7/2/07 | | | SHORING AND GC LETTER FOR POUR #121 LEVEL 21 POUR E. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
322 |
Status |
P |
Date |
2007-07-01 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-07-01 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-07-01 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2007-07-01 13:41:24 | ARCHITECTURAL REVISION SUBMITTED 6/5/07 FOR SHEETS | | | A4.32, A4.35, A3.36, A4.42, A4.53, A7.01, A7.05, | | | A7.05A, A7.09, AND A7.12.THE SAME SHEETS WERE DENIED | | | ON 4/26/07 BUT HAVE BEEN RE-SUBMITTED WITH A COMMENT | | | RESPONSE FROM BC ARCHITECTS CLARIFYING THAT 3/4" STEP | | | IN SLAB IS STRUCTURAL SLAB LEVEL ONLY, TO ACCOMMODATE | | | DIFFERENCE IN THICKNESS OF FINISHES.FINISHED FLOOR | | | WILL BE LEVEL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
321 |
Status |
F |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
12:30 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 13:29:40 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S.OLIVE AVE | | | CONT: KAST CONST. | | | TEL: (561)835-3852 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST | | | ACTION: DENIED | | | | | | FBC 2001 | | | IN 6/26/07 | | | SUBMITTAL #11011.02 WINDOW CLEANING & FACADE | | | MAINTENANCE SAFETY SYSTEM LAYOUT. | | | | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2)ENGINEER HO SIK HOL HAS A DELIQUENT STATUS.THE | | | STATE WEB-SITE SHOWS THAT HIS LICENSE EXPIRED ON | | | 02/28/07. THIS ISSUE SHALL BE RESOLVED BEFORE | | | RESUBMITTING. | | | | | | 3)FAC. 61G15-23.002ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH SHEET. | | | IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING | | | BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME | | | LICENSE NUMBER, AS WESS AS, THE NAME, ADDRESS, AND | | | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. | | | A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND AFFIX | | | HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS, FINAL | | | BID DOCUMENTS OR OTHER DOCUMENTS PREPARED OR ISSUED BY | | | SAID REGISTRANT AND GEING FILED FOR PUBLIC RECORD. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
320 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
11:08 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 12:22:48 | FBC 2001 | | | IN 6/19/07 | | | SUBMITTAL #03200.41 SHEAR WALL #1-6 TOWER 21 TO MAIN | | | ROOF. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
319 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
10:39 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 11:06:52 | FBC 2001 | | | IN 6/21/0 | | | SUBMITTAL #03365.1621ST FL POST TENSIONING | | | CALCULATIONS PAGES 1-90 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
318 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
10:13 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 10:37:00 | FBC 2001 | | | IN 6/19/07 | | | SUBMITTAL #03200.40 TOWER COLUMN SCHEDULE LEVEL 20 TO | | | MAIN ROOF. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
317 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
09:21 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 10:11:25 | FBC 2001 | | | IN 6/19/07 | | | SUBMITTAL #03460.01 PRE-CAST SHOP DRAWINGS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
316 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
09:06 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 09:19:25 | FBC 2001 | | | IN 6/26/07 | | | SUBMITTAL #03100.24 TOWER LEVEL 17-21 SHORING AND SHOP | | | DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
315 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
08:50 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 09:02:23 | FBC 2001 | | | IN 6/21/07 | | | SUBMITTAL #03300.293000 PSI PEARROCK PUMPMIX WITH | | | HRWR AND FIBER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
314 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
08:45 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 08:47:34 | FBC 2001 | | | IN 6/28/07 | | | SHORING AND GC LETTER FOR POUR #120 LEVEL 21 POUR D. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
313 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
08:40 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 08:44:43 | FBC 2001 | | | IN 6/26/07 | | | SHORING AND GC LETTER FOR POUR #119 LEVEL 21 POU C. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
312 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
08:33 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 08:38:12 | FBC 2001 | | | IN 6/21/07 | | | SHORING AND GC LETTER FOR POUR #118 LEVEL 21 POUR B. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
311 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
08:29 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 08:32:00 | FBC 2001 | | | IN 6/19/07 | | | SHORING AND GC LETTER FOR POUR #117 LEVEL 21 POUR A. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
310 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-30 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-30 |
Time |
08:18 |
Sent To |
PC |
|
| Notes |
| 2007-06-30 08:26:15 | FBC 2001 | | | IN 6/15/07 | | | SHORING AND GC LETTER FOR POUR #116 LEVEL 20 POUR E. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
309 |
Status |
F |
Date |
2007-06-24 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-06-24 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-06-24 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2007-06-24 16:39:54 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6652 | | | E-MAIL: [email protected] | | | | | | SUBMITTAL ON 6/5/07 FOR ENGINEERING CALCS FOR | | | ADDITIONAL FASTENERS, WITHOUT SHIMS, TO ADDRESS FIELD | | | VARIATIONS ON WINDOW AND SGD HEAD AND JAMB GAPS. | | | | | | 1)FBC 1606.1ALL FASTENER LOCATIONS SHALL | | | INCORPORATE SHIMS TO REDUCE FASTENER ROTATION, AND | | | REDUCE THE RISK OF FASTENERS BACKING OUT DUE TO CYCLIC | | | WIND LOADING. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | | (561) 805 6652ROBERT BROWN | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
308 |
Status |
P |
Date |
2007-06-24 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-06-24 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-06-24 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2007-06-24 16:30:06 | SUBMITTAL ON 5/30/07 FOR ENGINEERING CALCS FOR | | | ADDITIONAL FASTENERS, WITH SHIMS, TO ADDRESS FIELD | | | VARIATIONS ON WINDOW AND SGD HEAD AND JAMB GAPS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
307 |
Status |
P |
Date |
2007-06-24 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-06-24 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-06-24 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2007-06-24 15:52:41 | SUBMITTAL ON 6/19/07 FOR ARCITECT'S LETTER DATED | | | 6/18/07 EXPLAINING INTENT OF LIVE/WORK UNITS: | | | -MEZZANINE LEVEL IS INTENDED FOR PRIVATE DWELLING | | | PURPOSES AND IS NOT SUBJECT TO FLORIDA ACCESSIBILITY | | | CODE REQUIREMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
306 |
Status |
P |
Date |
2007-06-24 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-06-24 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-06-24 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2007-06-24 15:46:00 | SUBMITTAL ON 6/1/07 FOR EXTERIOR SYNERGY | | | NON-COMBUSTIBLE FOAM ARCHITECTURAL TRIM PACKAGE AND | | | SIGNED AND SEALED COVER LETTER FORM ARCHITECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
305 |
Status |
F |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-18 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-18 |
Time |
07:54 |
Sent To |
PC |
|
| Notes |
| 2007-06-18 09:47:17 | FBC 2001 | | | | | | SUBMITTAL #05100.02. ONLY SOME OF THE INFORMATION | | | SUBMITTED WILL BE APPROVED. THOSE ITEMS WHICH ARE | | | APPROVED WILL BE STAMPED. THE OTHER ITEMS WILL BE | | | RETUNED. THE SUBMITTALS BY KENNETH J. PAGANO, PE #58131 | | | ARE OK.THE INFORMATION BY SCOTT L. SCHURWAN PE | | | #31867, IS MISSING THE PRINTED NAME AND NUMBER/THE DATE | | | AND THE SIGNATURE ON SOME OF THE SUBMITTALS WERE | | | STAMPED WHICH IS NOT ACCEPTABLE. SEE F.A.C. | | | 61G15-23.002(1)A PROFESSIONAL ENGINEER SHALL SIGN HIS | | | NAME AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, | | | REPORTS, FINAL BID DOCUMENTS BEING FILED FOR PUBLIC | | | RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED | | | AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, | | | SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY | | | UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. | | | | | | (2) A COVER OR INDEX SHEET FOR ENGINEERING | | | SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE | | | SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL | | | ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND | | | PREPARATION OF EACH SECTION OF THE ENGINEERING | | | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER | | | SHEET OR INDEX SO THAT THE USER WILL BE AWARE OF EACH | | | PORTION OF THE SPECIFICATION FOR WHICH EACH | | | PROFESSIONAL ENGINEER IS RESPONSIBLE. SEE F.A.C. | | | 61G15-23.002 | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
304 |
Status |
P |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-18 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-18 |
Time |
07:20 |
Sent To |
PC |
|
| Notes |
| 2007-06-18 07:21:33 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #114. FOR LEVEL 10 POUR | | | D. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
303 |
Status |
P |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-18 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-18 |
Time |
07:07 |
Sent To |
PC |
|
| Notes |
| 2007-06-18 07:15:00 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #114 LEVEL 20 POUR C. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
302 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
11:42 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 12:17:49 | FBC: 2001 | | | | | | SUBMITTAL #03200.39 21ST FLOOR STEEL SHOP DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
301 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
10:36 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 11:34:40 | FBC 2001 | | | | | | SUBMITTAL #03200.38 TOWER: 17TH - 20TH FLRS - POUR A |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
300 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
10:21 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 10:31:01 | FBC: 2001 | | | | | | SHORING AND GC LETTER FOR POUR #112. LEVEL 20POUR A |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
299 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
09:53 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 10:18:30 | FBC 2001 | | | | | | SUBMITTAL #09250.05. MOLD TOUGH GYPSUM PRODUCT DATA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
298 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
09:36 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 09:53:33 | FBC 2001 | | | | | | SUBMITTAL #09300.11 . LIQUID ANTI-FRACTURE & | | | WATERPROOFING MEMBRANE PRODUCT DATA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
297 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
09:08 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 09:32:23 | FBC 2001 | | | | | | SUBMITTAL #08820.01 UNIT MIRROR PRODUCT SPECS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
296 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
08:35 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 09:00:06 | FBC 2001 | | | | | | SUBMITTAL #09300.14MARBLE & TILEGROUT SPECS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
295 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
08:06 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 08:10:22 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #111 LEVEL19 POUR E. | | | SENT TO JERALD INBOX |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
294 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
08:03 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 08:05:41 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #110 LEVEL #19 POUR D. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
293 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
07:56 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 08:02:31 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #109 LEVEL 19 POUR C. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
292 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
07:54 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 07:56:04 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #108 LEVEL 19 POUR B. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
291 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-09 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-09 |
Time |
07:37 |
Sent To |
PC |
|
| Notes |
| 2007-06-09 07:42:01 | FBC: 2001. | | | | | | SHORING AND GC LETTER FOR POUR #107. LEVEL 19 POUR A. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
290 |
Status |
P |
Date |
2007-05-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-05-21 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-05-21 |
Time |
09:16 |
Sent To |
PC |
|
| Notes |
| 2007-05-21 09:35:14 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR 106-E LEVEL 18. SENT TO | | | JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
289 |
Status |
P |
Date |
2007-05-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-05-21 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-05-21 |
Time |
09:02 |
Sent To |
PC |
|
| Notes |
| 2007-05-21 09:07:14 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR 105-D LEVEL 18. SENT TO | | | JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
288 |
Status |
P |
Date |
2007-05-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-05-21 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-05-21 |
Time |
08:55 |
Sent To |
PC |
|
| Notes |
| 2007-05-21 08:58:52 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR 104-C, LEVEL 18. SENT TO | | | JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
287 |
Status |
P |
Date |
2007-05-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-05-21 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-05-21 |
Time |
08:43 |
Sent To |
PC |
|
| Notes |
| 2007-05-21 08:50:55 | FBC 2001 | | | | | | SHORING AND GC LETTERS FOR POUR 103-B, LEVEL 18. SENT | | | TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
286 |
Status |
P |
Date |
2007-05-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-05-21 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-05-21 |
Time |
08:10 |
Sent To |
PC |
|
| Notes |
| 2007-05-21 08:43:02 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR 102-A, LEVEL 18. SENT TO | | | JERALD INBOX. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
285 |
Status |
P |
Date |
2007-05-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-05-21 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-05-21 |
Time |
07:54 |
Sent To |
PC |
|
| Notes |
| 2007-05-21 08:05:06 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR 101-E, LEVEL 17. SENT TO | | | JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
284 |
Status |
P |
Date |
2007-05-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-05-21 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-05-21 |
Time |
07:49 |
Sent To |
PC |
|
| Notes |
| 2007-05-21 07:54:10 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR100-D, LEVEL 17. SENT TO | | | JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
283 |
Status |
P |
Date |
2007-05-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-05-21 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-05-21 |
Time |
06:52 |
Sent To |
PC |
|
| Notes |
| 2007-05-21 06:56:30 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR 99-C, LEVEL 17. SENT TO | | | JERALD DESK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
282 |
Status |
F |
Date |
2007-04-26 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-04-26 |
Time |
19:45 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-04-26 |
Time |
19:44 |
Sent To |
|
|
| Notes |
| 2007-05-01 19:57:18 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6652 | | | E-MAIL: [email protected] | | | | | | ARCHITECTURAL REVISION # 9 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | ALL SHEETS REVIEWED AND STAMPED EXCEPT SHEETS A4.32, | | | A4.35, A3.36, A4.42, A4.53, A7.01, A7.05, A7.05A, | | | A7.09, AND A7.12 WHICH ARE ALL DENIED PER THE COMMENT | | | BELOW: | | | | | | 1) FBC 1012.1.3ELEVATION CHANGE AT ELEVATOR VESTIBULE | | | DOORWAY.SHEETS A4.32, A4.35, A3.36, A4.42, A4.53, | | | A7.01, A7.05, A7.05A, A7.09, AND A7.12 ALL SHOW A 3/4 | | | INCH CHANGE IN FLOOR ELEVATION AT THE ELEVATOR | | | VESTIBULE DOORWAY.THE ELEVATION CHANGE OF THE FLOOR | | | SURFACES ON BOTH SIDES OF A DOOR SHALL NOT VARY BY MORE | | | THAN 1/2 INCH AND ANY FLOOR LEVEL CHANGE MORE THAN 1/4 | | | INCH AT DOORWAYS SHALL BE BEVELED WITH A SLOPE NOT | | | STEEPER THAN 1:2. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | | (561) 805 6652ROBERT BROWN | | | E-MAIL: [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
281 |
Status |
P |
Date |
2007-04-25 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-25 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-25 |
Time |
06:54 |
Sent To |
PC |
|
| Notes |
| 2007-04-25 07:05:14 | FBC:2001 | | | | | | SHORING AND GC LETTER FOR POUR #98-B. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
280 |
Status |
P |
Date |
2007-04-25 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-25 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-25 |
Time |
06:47 |
Sent To |
PC |
|
| Notes |
| 2007-04-25 06:52:58 | FBC. 2001 | | | | | | SHORING AND GC LETTER FOR POUR #97. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
279 |
Status |
P |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-23 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-21 |
Time |
14:30 |
Sent To |
PC |
|
| Notes |
| 2007-04-21 14:41:24 | FBC. 2001 | | | RECEIVED 4/16/07. | | | | | | SUBMITTAL #03200.3716TH FL/ POUR #95 & 96. REBAR AND | | | SHOP DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
278 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-18 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-18 |
Time |
14:51 |
Sent To |
PC |
|
| Notes |
| 2007-04-18 14:55:53 | FBC | | | | | | SHORING AND GC LETTER FOR POUR #96 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
277 |
Status |
F |
Date |
2007-04-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-18 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-18 |
Time |
12:22 |
Sent To |
PC |
|
| Notes |
| 2007-04-18 13:02:54 | BUILDING PLAN REVIEW | | | PERMIT:04120353 | | | ADD: 717 S. OLIVE AVE. | | | CONT: KAST CONST. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: SUBMITTALS. | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)THE DESIGN PRESSURES FOR THE SENERFLEX WALL STATED | | | IN THE NOA #02-1022.17 ARE 65 PSF AND 90 PSF. THE | | | DESIGN PRESSURES STATED ON THE STRUCTURAL DRAWINGS IS | | | 120 PSF. SEE SHEET S-6.2 OF THE STRUCTURAL DRAWINGS. | | | THE ES REPORT FOR THE SENERFLEX WALL SYSTEM (ADHERED) | | | SEC. 4.1 AND 4.1.5 HAVE PRESSURES OF 30 PSF AND 54 PSF | | | WHICH DOES MEET THE 120 PSF STATED ON THE DRAWINGS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
276 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-18 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-18 |
Time |
12:12 |
Sent To |
PC |
|
| Notes |
| 2007-04-18 12:18:04 | FBC.2001 | | | | | | SHORING AND GC LETTER FOR POUR #95 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
275 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-18 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-18 |
Time |
12:02 |
Sent To |
PC |
|
| Notes |
| 2007-04-18 12:11:38 | FBC.2001 | | | | | | SHORING AND GC LETTER FOR POUR #94. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
274 |
Status |
P |
Date |
2007-04-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-12 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-12 |
Time |
06:17 |
Sent To |
PC |
|
| Notes |
| 2007-04-12 06:19:20 | FBC2001 | | | | | | SUBMITTAL #09300.10. SOUND CONTROL CORK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
273 |
Status |
P |
Date |
2007-04-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-11 |
Time |
18:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-11 |
Time |
18:23 |
Sent To |
PC |
|
| Notes |
| 2007-04-11 18:31:22 | FBC2001 | | | | | | SUBMITTAL #09200.07FOR EXTERIOR ACCESS PANEL DOOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
272 |
Status |
P |
Date |
2007-04-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-11 |
Time |
18:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-11 |
Time |
18:17 |
Sent To |
PC |
|
| Notes |
| 2007-04-11 18:19:12 | FBC2001 | | | | | | SHORING AND GC LETTER FOR POUR #92. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
271 |
Status |
P |
Date |
2007-04-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-11 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-11 |
Time |
18:08 |
Sent To |
PC |
|
| Notes |
| 2007-04-11 18:17:25 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #92. SENT TO JERELD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
270 |
Status |
F |
Date |
2007-04-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-05 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-05 |
Time |
07:09 |
Sent To |
PC |
|
| Notes |
| 2007-04-05 07:21:24 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S.OLIVE AVE. | | | CONT: KAST CONST. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | W/ 2003 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW SUBMITTAL #11011.01.01 WINDOW WASHING | | | EQUIPMENT SHOPS | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)THE ENGINEER WHO IS RESPONSIBLE FOR THE DESIGN | | | SHALL SIGN,SEAL AND DATE THE DRAWINGS. THE CHM | | | STRUCTURAL ENGINEER SHALL ALSO SIGN THE 8.5" X 11" | | | SHEETS. F.A.C. 61G15-23.002 AND 471.025. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
269 |
Status |
P |
Date |
2007-04-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-05 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-05 |
Time |
06:21 |
Sent To |
PC |
|
| Notes |
| 2007-04-05 07:08:42 | FBC2001 | | | | | | SUBMITTAL #07212.03 - INSULATION#09100.06 - FRAMING | | | #09250.04 - DRYWALL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
268 |
Status |
P |
Date |
2007-04-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-05 |
Time |
06:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-05 |
Time |
05:55 |
Sent To |
PC |
|
| Notes |
| 2007-04-05 06:06:34 | FBC2001 | | | | | | SHORING AND GC LETTER FOR POUR #91. SENT TO JERALD | | | INBOX |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
267 |
Status |
F |
Date |
2007-04-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-04 |
Time |
18:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-04 |
Time |
16:57 |
Sent To |
PC |
|
| Notes |
| 2007-04-04 18:02:12 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S.OLIVE AVE | | | CONT: KAST CONST. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW SUBMITTAL #05100.05 EXHAUST SHAFT TRUSS | | | DRAWINGS. | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)THE ENGINEER SHALL INDICATE THE BOTTOM CHORD LIVE | | | LOADPER FBC TABLE 1607.1 ON THE TRUSS DRAWINGS. THE | | | BREAK CONNECTION DETAIL DRAWINGS SHALL ALSO BE SIGNED | | | AND SEALED BY THE PERSON TAKING RESPONSIBILITY FOR | | | THOSE DRAWINGS.THE RUBBER SEAL ON THE DRAWINGS ARE | | | NOTORIGINAL SEAL. SEE F.A.C. 61G15-23.002/ FL. | | | STATUTES 471.025. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
266 |
Status |
P |
Date |
2007-04-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-04 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-04 |
Time |
15:34 |
Sent To |
PC |
|
| Notes |
| 2007-04-04 16:55:04 | FBC 2001 | | | | | | SUBMITTAL #09350.01CULTURED MARBLE PROCUCT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
265 |
Status |
P |
Date |
2007-04-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-04 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-04 |
Time |
13:59 |
Sent To |
PC |
|
| Notes |
| 2007-04-04 15:38:20 | FBC. 2001 | | | | | | SUBMITTAL #09200.05SEALANT # EXTERIOR EIFS | | | (SONOLASTIC 150 VLM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
264 |
Status |
P |
Date |
2007-04-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-04 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-04 |
Time |
12:22 |
Sent To |
PC |
|
| Notes |
| 2007-04-04 12:52:37 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUT #90. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
263 |
Status |
P |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-30 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-30 |
Time |
08:19 |
Sent To |
PC |
|
| Notes |
| 2007-03-30 08:52:13 | FBC 2001 | | | | | | SUBMITTAL #03900.01 THIN - TOP SUPREME. FOR FLOOR | | | REPAIRS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
262 |
Status |
F |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-30 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-30 |
Time |
07:39 |
Sent To |
PC |
|
| Notes |
| 2007-03-30 07:46:44 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S. OLIVE AVE | | | CONT: KAST CONST. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW SUBMITTALS #03365.15FLOORS 17-20PT CABLE | | | CALCS | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)SUBMIT AN INDEX SHEET FOR THE CALCULATIONS | | | REFERENCEING EACH PAGE IN THE REPORT. SEE F.A.C. | | | 61G15-23.002(2)A COVER OR INDEX SHEET FOR | | | ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET | | | MUST BE SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL | | | ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND | | | PREPARATION OF EACH SECTION OF THE ENGINEERING | | | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER | | | SHEET OR INDEX SO THAT THE USER WILL BE AWARE OF EACH | | | PORTION OF THE SPECIFICATIONS FOR WHICH EACH | | | PROFESSIONAL ENGINEER IS RESPONSIBLE. | | | | | | 3)THE DRAWINGS SUBMITTED WITH THE PHOTO-COPIES SEAL | | | AND SIGNATURE OF THE ENGINEER IS NOT ACCEPTABLE. A | | | PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND AFFIX HIS | | | SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS BEING FILED | | | FOR PUBLIC RECORD. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
261 |
Status |
F |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-30 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-30 |
Time |
06:25 |
Sent To |
PC |
|
| Notes |
| 2007-03-30 07:29:39 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S. OLIVE AVE | | | CONT: KAST CONST. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW SUBMITTALS #03365.1621ST FLOOR PT CABLE | | | CALCS | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)SUBMIT AN INDEX SHEET FOR THE CALCULATIONS | | | REFERENCEING EACH PAGE IN THE REPORT. SEE F.A.C. | | | 61G15-23.002(2)A COVER OR INDEX SHEET FOR | | | ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET | | | MUST BE SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL | | | ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND | | | PREPARATION OF EACH SECTION OF THE ENGINEERING | | | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER | | | SHEET OR INDEX SO THAT THE USER WILL BE AWARE OF EACH | | | PORTION OF THE SPECIFICATIONS FOR WHICH EACH | | | PROFESSIONAL ENGINEER IS RESPONSIBLE. | | | | | | 3)THE DRAWINGS SUBMITTED WITH THE PHOTO-COPIES SEAL | | | AND SIGNATURE OF THE ENGINEER IS NOT ACCEPTABLE. A | | | PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND AFFIX HIS | | | SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS BEING FILED | | | FOR PUBLIC RECORD. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
260 |
Status |
P |
Date |
2007-03-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-30 |
Time |
06:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-30 |
Time |
06:00 |
Sent To |
PC |
|
| Notes |
| 2007-03-30 06:05:11 | FBC2001 | | | | | | SHORING AND GC LETTER FOR POUR #89. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
259 |
Status |
P |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-29 |
Time |
18:15 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-29 |
Time |
18:09 |
Sent To |
PC |
|
| Notes |
| 2007-03-29 18:09:56 | FBC 2001 | | | | | | SUBMITTAL # 03900.02VINYL CONCRETE PATCHER. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
258 |
Status |
P |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-29 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-29 |
Time |
18:06 |
Sent To |
PC |
|
| Notes |
| 2007-03-29 18:07:24 | FBC 2001 | | | | | | SUBMITTAL #03900.03 BONSAL POLY-MOD CPMCRETE REPAIR | | | MORTAR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
257 |
Status |
P |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-29 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-29 |
Time |
17:47 |
Sent To |
|
|
| Notes |
| 2007-03-29 17:48:53 | FBC2001 | | | | | | SHORING AND GC LETTER FOR POUR #88. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
256 |
Status |
F |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-29 |
Time |
17:40 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-29 |
Time |
17:38 |
Sent To |
PC |
|
| Notes |
| 2007-03-29 17:40:27 | BUILDING PLAN REVIEW | | | PERMIT: | | | ADD: | | | CONT: | | | TEL: (561)###-#### | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEWSUBMITTAL/ RFI #517 SECONDARY SLAB | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)SEE NOTES FROM PREVIOUS REVIEW. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
255 |
Status |
P |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-29 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-29 |
Time |
16:52 |
Sent To |
PC |
|
| Notes |
| 2007-03-29 17:10:25 | FBC. 2001 | | | | | | SUBMITTAL #03200.35SHAREWALL SHOP LEVEL 17-20. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
254 |
Status |
F |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-29 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-29 |
Time |
11:32 |
Sent To |
PC |
|
| Notes |
| 2007-03-29 13:57:38 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S. OLIVE AVE | | | CONT: KAST CONST. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW:SUBMITTALS #05100.02 TRUSS STEEL | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)F.A.C.61G15-23.002 (2)A COVER OR INDEX SHEET | | | FOR ENGINEERING SPECIFICATIONS MAY BE USED AND THAT | | | SHEET MUST BE SIGNED, SEALED AND DATED BY THOSE | | | PROFESSIONAL ENGINEERS IN RESPONSIBLE CHARGE OF THE | | | PRODUCTION AND PREPARATION OF EACH SECTION OF THE | | | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION | | | ON THE COVER SHEET OR INDEX SO THAT THE USER WILL BE | | | AWARE OF EACH PORTION OF THE SPECIFICATIONS FOR WHICH | | | EACH PROFESSIONAL ENGINEER IS RESPONSIBLE. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
253 |
Status |
F |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-29 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-29 |
Time |
10:19 |
Sent To |
PC |
|
| Notes |
| 2007-03-29 10:52:11 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S.OLIVE AVE. | | | CONT: KAST CONST. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW. SUBMITTALS | | | ACTION: DENIED | | | | | | 1)THE LETTER SUBMITTED FROM CECO DOOR PRODUCTS FOR | | | THE FIRE DOORS AND WINDOWS SHALL REFERENCE THE CODES | | | STANDARDS UNDER WHICH THE PERMIT WAS ISSUED. SEE FBC. | | | 2001 CH.35. (35.10) NFPA 80-95. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
252 |
Status |
N |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-27 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-27 |
Time |
11:52 |
Sent To |
PC |
|
| Notes |
| 2007-03-27 12:21:29 | FBC 2001 | | | | | | SUBMITTAL #03200.36FLOORS 16 - 20 COLUMN,REBAR | | | SHOPS DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
251 |
Status |
F |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-27 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-27 |
Time |
09:53 |
Sent To |
PC |
|
| Notes |
| 2007-03-27 11:27:49 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S. OLIVE AVE | | | CONT: KAST CONSTRUCTION | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST | | | ACTION: DENIED | | | | | | SUBMITTAL #09100.05 | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) THESE DRAWINGS HAS BEEN ALTERED, THEREFORE,THIS IS A | | | REVISION AND NOT A SUBMITTAL. WHEN RESUBMITTION, PLEASE | | | CHECK THE REVISION BOX ON THE SHEET. ALSO INDICATE ALL | | | THE DIMENTIONS ON THE DRAWINGS. SEE PAGE TWO | | | | | | 3) F.A.C. 61G15-23.001(1)THE FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS HAS ELEMINATED THE WORD | | | CERTIFICATE FOR THE SEAL EFFECTIVE FEBRUARY 5, 2004. ON | | | JANUARY 1, 2006, EVERY PROFESSIONAL ENGINEER MUST BE | | | USING A NEW SEAL WITH THE WORD "LICENSE". THE ENGINEER | | | HAS TO UPDATE HIS SEAL. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
250 |
Status |
F |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-27 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-27 |
Time |
06:46 |
Sent To |
PC |
|
| Notes |
| 2007-03-27 07:53:57 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S.OLIVE AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST | | | ACTION: DENIED | | | | | | SUBMITTAL #03365.14 | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)THE NAME OF THE PROJECT IS TWO CITY PLAZA. NOT "TOW | | | CITY PLAZA". | | | | | | 3)F.A.C 61G15-23.002 (2)ENGINEERS SHALL LEGIBLY | | | INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON | | | EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED | | | ENGINEERING BUSINES, ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME, | | | ADDRESS, AND DERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS ON EACH SHEET. | | | | | | 4)STATE THE YEAR OF THE FLORIDA BUILDING CODE. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
249 |
Status |
F |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-27 |
Time |
06:42 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-27 |
Time |
06:00 |
Sent To |
PC |
|
| Notes |
| 2007-03-27 06:42:52 | BUILDING PLAN REVIEW | | | PERMIT: 04120353 | | | ADD: 717 S.OLIVE AVE | | | CONT: KAST CONSTRUCTION | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST | | | ACTION: DENIED | | | | | | SUBMITTAL #03100.24 | | | 1)THE DRAWINGS HAS TO BE SIGNED, DATED AND SEALED BY | | | THE ENGINEER. | | | SEE FAC. 61G15-23.002. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
248 |
Status |
P |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-26 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-26 |
Time |
15:04 |
Sent To |
PC |
|
| Notes |
| 2007-03-26 15:07:18 | FBC2001 | | | | | | SUBMITTAL #07830.03COUPLING THRU WALL ASSEMBLY @ 45 | | | DEGREE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
247 |
Status |
P |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-26 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-26 |
Time |
12:20 |
Sent To |
|
|
| Notes |
| 2007-03-26 12:22:18 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #87. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
246 |
Status |
P |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-26 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-26 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2007-03-26 12:13:27 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #86. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
245 |
Status |
P |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-26 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-26 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2007-03-26 12:09:05 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #85. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
244 |
Status |
P |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-26 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-26 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2007-03-26 11:09:01 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR # 84. SENT TOJERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
243 |
Status |
P |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-16 |
Time |
06:32 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-16 |
Time |
06:27 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
242 |
Status |
P |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-16 |
Time |
06:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-16 |
Time |
06:20 |
Sent To |
PC |
|
| Notes |
| 2007-03-16 06:21:27 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #82. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
241 |
Status |
P |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-16 |
Time |
06:20 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-16 |
Time |
06:14 |
Sent To |
PC |
|
| Notes |
| 2007-03-16 06:15:22 | FBC 2001 | | | | | | SHORING AND GC LETTER FOR POUR #81. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
240 |
Status |
P |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-16 |
Time |
06:13 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-16 |
Time |
06:02 |
Sent To |
PC |
|
| Notes |
| 2007-03-16 06:09:20 | FBC. 2001 | | | | | | SHORING AND GC LETTERFOR POUR #80. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
239 |
Status |
P |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-03 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-03 |
Time |
17:31 |
Sent To |
|
|
| Notes |
| 2007-03-03 17:34:25 | FBC; 2001 | | | | | | SHORING AND FORMWORK LETTER FOR POUR #79. SENT TO | | | JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
238 |
Status |
P |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-03 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-03 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2007-03-03 11:24:18 | FBC 2001 | | | | | | SUBMITTAL #07120.12TREMPROOF 201 / 222 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
237 |
Status |
P |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-03 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-03 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2007-03-03 11:01:01 | FBC : 2001 | | | | | | SUBMITTAL #09200.04SILICONE SEALANTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
236 |
Status |
F |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-03 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-03 |
Time |
09:39 |
Sent To |
PC |
|
| Notes |
| 2007-03-03 10:30:26 | BUILDING PLAN REVIEW | | | PERMIT:04120353 | | | ADD: 717 S. OLIVE AVE | | | CONT: KOLTER CONST CO. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEWSUBMITTALS | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)61G1-16.004 TITLE BLOCK. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | 3) F.S481.221 (8) FINAL CONSTRUCTION DOCUMENTS | | | PREPARED BY A REGISTERED ARCHITECT SHALL BE OF A | | | SUFFICIENTLY HIGH STANDARD TO CLEARLY AND ACCURATELY | | | INDICATE OR ILLUSTRATE ALL ESSENTIAL PARTS OF THE WORK | | | TO WHICH THEY REFER. | | | | | | 4)THESE DRAWINGS SHALL ALSO BE APPROVED BY THE | | | ENGINEER OR ARCHITECT OF RECORD. SHOW A CROSS SECTION | | | OF THE SECONDARY SLAB INDICATING THE THICKNESS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
235 |
Status |
P |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-03 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-03 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2007-03-03 09:38:13 | FBC : 2001 | | | | | | SHORING AND FORMWORK LETTER FOR POUR #78. SENT TO | | | JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
234 |
Status |
P |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-03 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-03 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2007-03-03 09:35:46 | FBC : 2001 | | | | | | SHORING AND FORMWORK LETTER FOR POUR #77. SENT TO | | | JERALD INBOX |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
233 |
Status |
P |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-03-03 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-03-03 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2007-03-03 09:20:47 | FBC: 2001 | | | | | | SHORING AND FORMWORK LETTER FOR POUR #76. SENT TO | | | JERALD INBOX |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
232 |
Status |
P |
Date |
2007-02-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-24 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-24 |
Time |
08:08 |
Sent To |
|
|
| Notes |
| 2007-02-24 08:08:51 | FBC: 2001 | | | | | | SHORING AND FORMWORK LETTER FOR POUR#75. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
231 |
Status |
P |
Date |
2007-02-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-24 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-24 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2007-02-24 07:53:48 | FBC: 2001 | | | | | | SHORING AND FORMWORK LETTER FOR POUR#74. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
230 |
Status |
P |
Date |
2007-02-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-24 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-24 |
Time |
07:47 |
Sent To |
|
|
| Notes |
| 2007-02-24 07:49:18 | FBC: 2001 | | | | | | SHORING AND FORMWORK LETTER FOR POUR#73. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
229 |
Status |
|
Date |
2007-02-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-24 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-24 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2007-02-24 07:42:52 | FBC: 2001 | | | | | | SHORING AND FORMWORK LETTER FOR POUR#72. SENT TO JERALD | | | INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
228 |
Status |
P |
Date |
2007-02-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-12 |
Time |
18:38 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-12 |
Time |
18:32 |
Sent To |
|
|
| Notes |
| 2007-02-12 18:38:20 | FBC 2001 | | | | | | SUBMITTAL #07212.02THERMO CON.SOUND AND | | | CONDENSATION CONTROL |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
227 |
Status |
P |
Date |
2007-02-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-12 |
Time |
18:32 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-12 |
Time |
18:22 |
Sent To |
|
|
| Notes |
| 2007-02-12 18:32:15 | FBC 2001 | | | | | | SHORING AND LETTER FOR POUR #71. SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
226 |
Status |
P |
Date |
2007-02-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-12 |
Time |
18:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-12 |
Time |
18:17 |
Sent To |
|
|
| Notes |
| 2007-02-12 18:19:47 | FBC 2001 | | | | | | SHORING AND LETTER FOR POUR #70 SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
225 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-02-11 |
Time |
22:58 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-02-11 |
Time |
22:58 |
Sent To |
|
|
| Notes |
| 2007-02-11 22:59:41 | STRUCTURAL REVISION SUBMITTED ON 1/11/07.GENERAL | | | REVISION/UPDATE OF STRUCTURAL PLANS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
224 |
Status |
P |
Date |
2007-02-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-05 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-05 |
Time |
07:48 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
223 |
Status |
P |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-03 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-03 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2007-02-03 14:56:49 | FBC 2001 | | | | | | SUBMITTAL #03200.29.01REBAR AND SHOP DRAWINGS FOR | | | FLS 10-15. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
222 |
Status |
P |
Date |
2007-02-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-03 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-03 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2007-02-03 14:39:00 | FBC2001 | | | | | | SUBMITTAL #08815.01SHOWER DOOR ENCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
221 |
Status |
P |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-03 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-03 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2007-02-03 14:23:59 | FBC 2001 | | | | | | SHORING LETTER FOR POUR #66SEND TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
220 |
Status |
P |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-03 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-03 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2007-02-03 14:17:54 | FBC 2001 | | | | | | SUBMITTAL #07830.01TREMCO FIRESTOPPING DEATAILS FOR | | | WATER CLOSETS FA-2136 AND FS-534F | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
219 |
Status |
P |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-03 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-03 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2007-02-03 13:23:25 | FBC : 2001 | | | | | | SUBMITTAL #09900.02AIR PLENUM CONCRETE SEALER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
218 |
Status |
P |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-03 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-03 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2007-02-03 12:53:18 | FBC : 2001 | | | | | | SUBMITTAL #10800.01TOILET ACCESSORIES AND PARTIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
217 |
Status |
P |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-03 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-03 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2007-02-03 11:28:50 | FBC : 2001 | | | | | | SUBMITTAL #07212.01INSULATION SPECIFICATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
216 |
Status |
P |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-03 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-03 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2007-02-03 10:55:11 | FBC : 2001 | | | | | | SHORING LETTER FOR POUR #69. SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
215 |
Status |
P |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-03 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-03 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2007-02-03 10:47:49 | FBC : 2001 | | | | | | SHORING LETTER FOR POUR #67. SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
214 |
Status |
P |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-02-03 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-02-03 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2007-02-03 10:42:19 | FBC :2001 | | | | | | SHOING LETTER FOR POUR #68. SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
213 |
Status |
P |
Date |
2007-02-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-29 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-29 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2007-01-29 14:40:39 | FBC : 2001 | | | | | | SUBMITTAL #03200.34SHEARWALL #1 TOWER 12 TO 17 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
212 |
Status |
P |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-24 |
Time |
18:43 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-24 |
Time |
18:17 |
Sent To |
PC |
|
| Notes |
| 2007-01-24 18:30:03 | FBC : 2001 | | | | | | SUBMITTAL #03200.31POURS FOR LANAI LEVEL/ SECONDARY | | | COURT YARD/ PIERS, WALLS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
211 |
Status |
P |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-24 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-24 |
Time |
18:00 |
Sent To |
PC |
|
| Notes |
| 2007-01-24 18:06:12 | FBC : 2001 | | | | | | SUBMITTAL #03200.3TOWER COLUMNS FOR FLOORS 11-16 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
210 |
Status |
P |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-24 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-24 |
Time |
17:49 |
Sent To |
PC |
|
| Notes |
| 2007-01-24 17:58:08 | FBC : 2001 | | | | | | SUBMITTAL FOR FORMWORK AND SHORING LETTERS FOR POUR #64 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
209 |
Status |
P |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-24 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-24 |
Time |
17:40 |
Sent To |
|
|
| Notes |
| 2007-01-24 17:48:37 | FBC: 2001 | | | | | | SUBMITTAL OF SHORING AND FORMWORK LETTERS FOR DECK POUR | | | #65 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
208 |
Status |
P |
Date |
2007-01-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-20 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-20 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2007-01-20 09:04:57 | FBC: 2001 | | | | | | SUBMITTAL #03300.27.6000 DCI 9" SLUMP |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
207 |
Status |
P |
Date |
2007-01-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-20 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-20 |
Time |
07:28 |
Sent To |
|
|
| Notes |
| 2007-01-20 08:15:42 | FBC : 2001 | | | | | | SUBMITTAL #0330021.01MIX DESIGN #1347563 FOR PT DECK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
206 |
Status |
P |
Date |
2007-01-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-20 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-20 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2007-01-20 07:25:01 | FBC :2001 | | | | | | SHORING AND FORMWORK LETTERS FOR POUR#62 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
205 |
Status |
P |
Date |
2007-01-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-20 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-20 |
Time |
07:16 |
Sent To |
|
|
| Notes |
| 2007-01-20 07:19:12 | FBC:2001 | | | | | | SHORING AND FORMWORK LETTERS FOR POUR#63 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
204 |
Status |
F |
Date |
2007-01-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-18 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-18 |
Time |
07:05 |
Sent To |
PC |
|
| Notes |
| 2007-01-18 08:23:32 | FBC; 2001 | | | | | | SUBMITTAL #07830.01 | | | | | | THE SUBMITTAL FOR THE WATER CLOSET FLOOR ASSEMBLY HAS | | | TO BE REVIEWED BY THE ARCHITECT OF RECORD.PROVIDE A | | | COPY OF THE THE FA-2136 UL LISTING. I SEARCH THE UL | | | BOOK AND CANNOT FIND THIS LISTING NUMBER. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
203 |
Status |
P |
Date |
2007-01-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-18 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-18 |
Time |
06:29 |
Sent To |
|
|
| Notes |
| 2007-01-18 06:46:49 | FBC:2001 | | | | | | SUBMITTAL #04220.05EPOXY PRODUCT DATA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
202 |
Status |
P |
Date |
2007-01-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-18 |
Time |
06:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-18 |
Time |
06:16 |
Sent To |
|
|
| Notes |
| 2007-01-18 06:21:31 | FBC: 2001 | | | | | | SUBMITTA: POUR #61 SHORING AND FORMWORK LETTER FOR | | | ELEVATED DECK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
201 |
Status |
P |
Date |
2007-01-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-18 |
Time |
06:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-16 |
Time |
17:52 |
Sent To |
PC |
|
| Notes |
| 2007-01-18 06:14:52 | FBC; 2001 | | | | | | SUBMITTAL #09200.02- LATH/ STUCCO AND EXTERIOR | | | FRAMING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
200 |
Status |
P |
Date |
2007-01-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-10 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-10 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2007-01-10 13:39:15 | FBC: 2001 | | | | | | SUBMITTAL :SHORING AND FORMWORK FOR ELEVATED DECK | | | POUR #60. SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
199 |
Status |
P |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-09 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-09 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2007-01-09 09:48:01 | FBC : 2001 | | | | | | SUBMITTAL #09900.01.PAINT SUBMITTAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
198 |
Status |
P |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-09 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-09 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2007-01-09 08:11:32 | FBC: 2001 | | | | | | SUBMITTAL #15100.03.01.FP-1 GROUND LEVEL & PARKING | | | LEVEL P1. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
197 |
Status |
P |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-09 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-09 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2007-01-09 07:44:47 | FBC: 2001 | | | | | | SUBMITTAL: SHORING FORMWORK & LETTERS FOR ELEVATED DECK | | | POUR #57. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
196 |
Status |
P |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-09 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-09 |
Time |
07:12 |
Sent To |
|
|
| Notes |
| 2007-01-09 07:33:56 | FBC: 2001 | | | | | | SUBMITTAL #08110.07. FIRELITE SPEC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
195 |
Status |
P |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-09 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-09 |
Time |
06:54 |
Sent To |
|
|
| Notes |
| 2007-01-09 07:07:10 | FBC : 2001 | | | | | | SUBMITTAL #09100.05.DIETRICH ULTRA STEEL FRAMING |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
194 |
Status |
P |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-09 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-09 |
Time |
06:35 |
Sent To |
|
|
| Notes |
| 2007-01-09 06:38:07 | FBC : 2001 | | | | | | SUBMITTAL #05500.06 WIRE MESH PARTITION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
193 |
Status |
P |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-09 |
Time |
06:35 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-08 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2007-01-09 06:07:14 | FBC: 2001 | | | | | | SUBMITTAL #03365.13. POST TENSION SHOP DRAWINGS FOR | | | FLOORS 8-15. REVISED REBAR SHEET (PTT082) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
192 |
Status |
P |
Date |
2007-01-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-08 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-08 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2007-01-08 16:47:03 | FBC. 2001 | | | | | | SUBMITTAL - SHORING AND FORMWORK FOR ELEVATED DECK POUR | | | #58. SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
191 |
Status |
P |
Date |
2007-01-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-01-08 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-01-08 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2007-01-08 16:29:20 | FBC: 2001 | | | | | | SUBMITTAL-SHORING AND FORMWORK LETTERS FOR ELEVATED | | | DECK POUR #59. SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
190 |
Status |
P |
Date |
2006-12-22 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-22 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-22 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2006-12-22 16:39:01 | FBC : 2001 | | | | | | SHORING AND FORMWORK LETTERS FOR POUR #56. SENT TO | | | JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
189 |
Status |
P |
Date |
2006-12-22 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-22 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-22 |
Time |
15:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
188 |
Status |
P |
Date |
2006-12-22 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-22 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-22 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2006-12-22 13:23:59 | FBC: 2001 | | | | | | SUBMITTAL #09200.02LATH, STUCCO AND EXTERIOR FRAMING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
187 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-12-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-22 |
Time |
07:09 |
Sent To |
|
|
| Notes |
| 2006-12-22 07:36:48 | BUILDING PLAN REVIEW | | | PERMIT:04120353 | | | ADD: 717 S. OLIVE AVE. | | | CONT:KAST CONST. | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | | | | FBC:2001 | | | SUBMITTAL #09200.02LATH, STUCCO AND EXTERIORFRAMING. | | | SECTION #8 OF THE PACKAGE | | | | | | ?1404.1.1 ARCHITECTURAL TRIM ON BUILDINGS OF TYPE I, II | | | AND IV | | | CONSTRUCTION NOT MORE THAN THREE STORIES OR 40 FT | | | (12.2 M) HIGH MAY BE OF | | | TYPE VI CONSTRUCTION, AND MAY BE OF TYPE VI | | | CONSTRUCTION ON ALL BUILDINGS | | | OF TYPE III, V AND VI CONSTRUCTION.TRIM SHALL BE | | | SECURED TO THE WALL | | | WITH METAL OR OTHER APPROVED BRACKETS OR FASTENERS. | | | WHEN ARCHITECTURAL | | | TRIM IS LOCATED ALONG THE TOP OF EXTERIOR WALLS, IT | | | SHALL BE COMPLETELY | | | BACKED BY THE EXTERIOR WALL AND SHALL NOT EXTEND OVER | | | THE TOP OF EXTERIOR | | | WALLS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
186 |
Status |
P |
Date |
2006-12-22 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-22 |
Time |
06:28 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-22 |
Time |
06:00 |
Sent To |
|
|
| Notes |
| 2006-12-22 06:27:56 | FBC : 2001 | | | | | | SUBMITTAL #08810.05.SEALANT, PRIMER, GROOUT AND | | | TAPCONS PRODUCT DATA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
185 |
Status |
P |
Date |
2006-12-19 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-19 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-19 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2006-12-19 18:00:08 | FBC:2001 | | | | | | SUBMITTAL #09900.01 PAINT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
184 |
Status |
P |
Date |
2006-12-19 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-19 |
Time |
17:38 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-19 |
Time |
17:28 |
Sent To |
|
|
| Notes |
| 2006-12-19 17:35:02 | FBC :2001 | | | | | | SHORING AND FORMWORK LETTERS FOR POUR #55. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
183 |
Status |
P |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-16 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-16 |
Time |
14:07 |
Sent To |
PC |
|
| Notes |
| 2006-12-16 14:10:10 | FBC : 2001 | | | | | | SUBMITTAL #03365.13.POST TENSION CABLE SHOP | | | DRAWINGS. LEVEL 8 THRU 15. CALCULATIONS ARE ALSO | | | INCLUDED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
182 |
Status |
P |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-16 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-16 |
Time |
13:17 |
Sent To |
PC |
|
| Notes |
| 2006-12-16 13:57:46 | FBC: 2001 | | | | | | SUBMITTAL #03365.12POST TENSION CABLE SHOP DRAWINGS. | | | 7TH LEVEL - TOWER. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
181 |
Status |
P |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-16 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-16 |
Time |
10:31 |
Sent To |
PC |
|
| Notes |
| 2006-12-16 13:04:41 | FBC:2001 | | | | | | SUBMITTAL #09250.03 GOLD BOND GYPSUM WALL BOARD. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
180 |
Status |
P |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-16 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-16 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2006-12-16 10:24:00 | FBC:2001 | | | | | | SUBMITTAL #09250.02SHEETROCK READY MIX COMPOUND. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
179 |
Status |
P |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-16 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-16 |
Time |
09:59 |
Sent To |
|
|
| Notes |
| 2006-12-16 10:05:18 | FBC: 2001 | | | | | | SUBMITTAL #09100.03 RAMSET FASTENING SYSTEMS. ALSO | | | GRABBER PAN HEAD STREAKER, GRABBER COARSE THREAD BLACK | | | PHOSPHATE AND STREAKER FINE THREAD. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
178 |
Status |
P |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-16 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-16 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2006-12-16 09:58:34 | FBC: 2001 | | | | | | SUBMITTAL #09100.02 DIETRICH METAL FRAMING |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
177 |
Status |
P |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-16 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-16 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2006-12-16 09:11:21 | FBC: 2001 | | | | | | SHORING AND FORMWORK LETTERS FOR ELEVATED DECK POUR | | | #54. SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
176 |
Status |
F |
Date |
2006-12-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-14 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-14 |
Time |
08:04 |
Sent To |
PC |
|
| Notes |
| 2006-12-14 08:06:01 | BUILDING PLAN REVIEW | | | PERMIT:04120353 | | | ADD:717 S. OLIVE AVE. | | | CONT:KASTCONSTRUCTION | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 2NDRFI - 396 | | | ACTION: DENIED | | | | | | | | | 1) FBC.2001 SEC. 2101.2.CONSTRUCTION DOCUMENTS. | | | DRAWINGS AND DETAILS SHALL SHOW ALL THE ITEMS REQUIRED | | | TO BE SHOWN ON THE DRAWINGS BY THIS CODE INCLUDINGTHE | | | FOLLOWING: | | | 4. PROVISION FOR DIMENSIONAL CHANGES RESULTING | | | FROM ELASTIC DEFORMATION, CREEP, SHRINKAGE, TEMPERATURE | | | AND MOISTURE.NOTE: CEMENT GROUT IS NOT A MATERIAL | | | WHICH WILL MEET THE ELASTICITY DEFORMATION IN THIS | | | SITUATION.CHOSE A MATERIAL WHICH WILL MEET THE FIRE | | | RESISTANCE RATING OF THE WALL AND ELASTIC DEFORMATION. | | | | | | 2)FBC.2001 SEC. 1604.5INTERIOR WALL LOADS. | | | INTERIOR WALLS, PERMANENT PARTITIONS AND TEMPORARY | | | PARTITIONS SHALL BE DESIGNED TO RESIST ALOADS TO | | | WHICH THEY ARE SUBJECTED BUT NOT LESS THAN 5 PSF | | | APPLIED PERPENDICULAR TO THE WALLS, EXCEPT FOR | | | DECORATIVE SCREEN WALLS. | | | ALSO SEE SEC. 703.2. FOR FIRE RESISTANCE RATINGS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
175 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2006-12-07 11:04:45 | FBC : 2001 | | | | | | SUBMITTAL #03200.32SHEARWALL AND REBAR DRAWINGS FOR | | | LEVEL 8 THRU 11. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
174 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2006-12-07 10:44:20 | FBC : 2001 | | | | | | SUBMITTAL #09100.01BALCONY FRAMING @ LEVELS 1 THRU 4 | | | AND WEST ELEVATION FRAMING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
173 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2006-12-07 10:36:49 | FBC : 2001 | | | | | | SHORING AND FORMWORK LETTERS FOR POUR #53 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
172 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2006-12-07 08:46:24 | FBC : 2001 | | | | | | SUBMITTAL #07830.01FIRESTOP DATA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
171 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2006-12-07 08:13:18 | FBC : 2001 | | | | | | SUBMITTAL # 03200.308TH FLOOR THRU 11TH FLOOR COLOMN | | | SHOP DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
170 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2006-12-07 07:51:57 | FBC : 2001 | | | | | | SHORING AND FORMWORK LETTERS FOR POUR #50. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
169 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2006-12-07 07:49:19 | FBC : 2001 | | | | | | SUBMITTAL #03300.26PERLITE LIGHTWEIGHT CONCRETE. USED | | | AT HOLLOW METAL FRAMES IN CONCRETE WALLS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
168 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
07:14 |
Sent To |
|
|
| Notes |
| 2006-12-07 07:19:15 | FBC : 2001 | | | | | | SHORINGAND FORMWORK LETTERS FOR POUR #51 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
167 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
07:14 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
07:04 |
Sent To |
|
|
| Notes |
| 2006-12-07 07:14:28 | FBC : 2001 | | | | | | SHORING AND FORMWORK LETTERS FOR POUR #48. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
166 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
06:37 |
Sent To |
|
|
| Notes |
| 2006-12-07 07:03:31 | FBC : 2001 | | | | | | SUBMITTAL #03200.29 PARKING LEVEL 7 THRU 15 REBAR SHOP | | | DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
165 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
06:36 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
06:27 |
Sent To |
|
|
| Notes |
| 2006-12-07 06:36:43 | FBC :2001 | | | | | | SUBMITTAL #03400.01.04CRANE SHOP DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
164 |
Status |
P |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-07 |
Time |
06:26 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-07 |
Time |
05:48 |
Sent To |
|
|
| Notes |
| 2006-12-07 06:26:33 | FBC: 2001 | | | | | | SUBMITTAL #05520.09.01 CALCULATIONS FOR STEEL PLATE | | | SPIRAL STAIRS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
163 |
Status |
P |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-06 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-06 |
Time |
18:31 |
Sent To |
|
|
| Notes |
| 2006-12-06 18:56:17 | FBC: 2001 | | | | | | SUBMITTAL #05520.08.01STRAIGHT STAIRS. UNITS 1 THRU | | | 18 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
162 |
Status |
P |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-06 |
Time |
18:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-06 |
Time |
18:00 |
Sent To |
|
|
| Notes |
| 2006-12-06 18:31:12 | FBC: 2001 | | | | | | SUBMITTAL#05520.07.01 FOR SPIRAL STAIRS. UNIT #7 - UNIT | | | #11- UNIT #19 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
161 |
Status |
P |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-06 |
Time |
17:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-06 |
Time |
17:51 |
Sent To |
|
|
| Notes |
| 2006-12-06 17:56:13 | FBC:2001 | | | | | | SUBMITTAL OF SHORING AND RESHORING LETTERS FOR POUR#52. | | | SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
160 |
Status |
P |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-12-06 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-12-06 |
Time |
17:26 |
Sent To |
|
|
| Notes |
| 2006-12-06 17:22:34 | FBC: 2001 | | | | | | SUBMITTAL FOR SHORING AND FORMWORK LETTERS FOR POUR | | | #49.SENT TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
159 |
Status |
F |
Date |
2006-12-03 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2006-12-03 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-12-03 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2006-12-03 14:58:31 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6652 | | | E-MAIL: [email protected] | | | | | | DOOR AND WINDOW CALCULATIONS, PRODUCT APPROVAL AND SHOP | | | DRAWINGS. | | | | | | 1)ALL OF THE SUBMITTED PRODUCT APPROVALS HAVE BEEN | | | REVIEWED AND STAMPED EXCEPT THE FOLLOWING: | | | (A)GAMMA SERIES # 55.3 WINDOW WALL, SMALL MISSILE | | | IMPACT - NO LOCAL/SITE SPECIFIC PRODUCT APPROVAL FORM | | | OR TEST REPORT WAS SUBMITTED.SUBMIT A THREE COPIES OF | | | THE PRODUCT APPROVAL FORM, WITH THE ORIGINAL SIGNATURE | | | OF THE AUTHORIZED GAMMA U.S.A. REPRESENTATIVE, AND | | | THREE COPIES OF THE PRODUCT TEST REPORT.THE SUBMITTED | | | PRODUCT APPROVAL PACKAGE SHOULD BE SIMILAR TO THOSE | | | THAT WERE SUBMITTED FOR THE REST OF THE DOORS/WINDOWS. | | | (B)GAMMA SERIES # 66 SINGLE HUNG WINDOW, SMALL | | | MISSILE IMPACT - NO LOCAL/SITE SPECIFIC PRODUCT | | | APPROVAL FORM WAS SUBMITTED.SUBMIT A THREE COPIES OF | | | THE PRODUCT APPROVAL FORM, WITH THE ORIGINAL SIGNATURE | | | OF THE AUTHORIZED GAMMA U.S.A. REPRESENTATIVE. | | | | | | 2) PROCESSING OF THE SHOP DRAWINGS CANNOT BE COMPLETED | | | UNTIL THE ABOVE ITEMS ARE SUBMITTED.ALL THREE COPIES | | | OF THE PARTIALLY STAMPED SHOP DRAWINGS MUST BE RETURNED | | | WHEN RESUBMITTING. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | | (561) 805 6652ROBERT BROWN | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
158 |
Status |
P |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-16 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-16 |
Time |
07:56 |
Sent To |
PC |
|
| Notes |
| 2006-11-16 08:31:22 | FBC: 2001 | | | | | | SUBMITTAL #03200.26PARKING LEVEL 9 THRUTOWER LEVEL | | | 8 PARKING ANDTOWER COLUMN, REBAR SHOPS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
157 |
Status |
P |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-16 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-16 |
Time |
07:17 |
Sent To |
PC |
|
| Notes |
| 2006-11-16 07:25:47 | FBC: 2001 | | | | | | SUBMITTAL #05520.06.01LOUVERS & GRILLS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
156 |
Status |
P |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-16 |
Time |
07:03 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-16 |
Time |
06:29 |
Sent To |
PC |
|
| Notes |
| 2006-11-16 07:03:22 | FBC : 2001 | | | | | | SUBMITTAL #03200.28.REBAR SHOP DRAWINGS FOR 6TH FL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
155 |
Status |
P |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-16 |
Time |
06:28 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-16 |
Time |
06:18 |
Sent To |
|
|
| Notes |
| 2006-11-16 06:22:57 | FBC: 2001 | | | | | | SUBMITTAL LITTER FOR POUR #42. SEND TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
154 |
Status |
P |
Date |
2006-11-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-16 |
Time |
06:13 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-16 |
Time |
05:57 |
Sent To |
|
|
| Notes |
| 2006-11-16 06:05:51 | FBC:2001 | | | | | | SHORING LETTERS FOR POUR #44. SEND TO JERALD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
153 |
Status |
P |
Date |
2006-11-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-15 |
Time |
18:14 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-15 |
Time |
18:10 |
Sent To |
|
|
| Notes |
| 2006-11-15 18:12:28 | FBC: 2001 | | | | | | SHORING LETTER FOR POUR #43 TO JERELD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
152 |
Status |
P |
Date |
2006-11-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-15 |
Time |
18:10 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-15 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2006-11-15 18:05:46 | FBC: 2001 | | | | | | SHORINGLETTER FOR POUR #45 TO JERELD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
151 |
Status |
P |
Date |
2006-11-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-15 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-15 |
Time |
17:49 |
Sent To |
PC |
|
| Notes |
| 2006-11-15 17:57:52 | FBC:2001 | | | | | | SUBMITTAL #02520.01 PAVER PRODUCT DATA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
150 |
Status |
P |
Date |
2006-11-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-15 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-15 |
Time |
17:37 |
Sent To |
|
|
| Notes |
| 2006-11-15 17:39:15 | FBC: 2001 | | | | | | SHORING LETTER FOR POUR #46.SENT TO JERELD INBOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
149 |
Status |
P |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-14 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-14 |
Time |
18:31 |
Sent To |
PC |
|
| Notes |
| 2006-11-14 18:35:10 | FBC: 2001 | | | | | | SUBMITTAL #03100.22SHORING SHOP DRAWINGS FOR FLOORS | | | 6-16 AND LOAD CALCULATIONS #FMI-1303. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
148 |
Status |
P |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-14 |
Time |
18:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-14 |
Time |
17:46 |
Sent To |
PC |
|
| Notes |
| 2006-11-14 18:00:40 | FBC:2001 | | | | | | SUBMITTAL #03365.10.01POST TENSION SHOP DRAWINGS AND | | | PRESTRESS FRICTION CALCULATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
147 |
Status |
P |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-14 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-14 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2006-11-14 13:17:22 | FBC: 2001 | | | | | | SHORING AND RESHORING LETTERS FOR ELEVATED DECK POUR | | | #47 | | | TO JERELD IN BOX |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
146 |
Status |
P |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-14 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-14 |
Time |
11:00 |
Sent To |
PC |
|
| Notes |
| 2006-11-14 12:55:13 | FBC:2001 | | | | | | SUBMITTAL #03365.11 | | | STUD RAIL SHOP DRAWINGS FOR 6TH FL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
145 |
Status |
P |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-14 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-14 |
Time |
10:43 |
Sent To |
PC |
|
| Notes |
| 2006-11-14 10:54:09 | FBC:2001 | | | | | | SUBMITTAL #03100.21 | | | ARCH BEAM SHORING & SHOPS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
144 |
Status |
P |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-11-14 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-11-14 |
Time |
09:33 |
Sent To |
PC |
|
| Notes |
| 2006-11-14 09:50:22 | FBC:2001 | | | | | | SUBMITTAL #03100.20.01 | | | POST SHORES (BOOM PUMP SHORING SHOPS). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
143 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
|
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-11-12 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2006-11-12 13:34:47 | SUBMITTAL FOR GAMMA U.S.A. DOOR/WINDOW DESIGN AND | | | PRODUCT APPROVAL PACKAGE. | | | | | | GAMMA U.S.A. PLAN SHEET 1.04 STATES THAT NO PRESSURES | | | COULD BE FOUND, IN THE WIND LOAD STUDY REPORT, FOR THE | | | "SOUTH COURTYARD ELEVATION", AND LOADS OF +90/-90 PSF | | | WERE USED.FIGURE 7 AND FIGURE 12 OF THE RWDI REPORT | | | DO SHOW THE LOADS FOR SOUTH COURTYARD ELEVATION, | | | HOWEVER THEY ARE LESS THAN +90/-90 PSF, SO RE-DESIGN IS | | | NOT NECESSARY. | | | | | | ******PLAN REVIEW IN PROGRESS****** |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
142 |
Status |
F |
Date |
2006-10-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-26 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-26 |
Time |
17:04 |
Sent To |
PC |
|
| Notes |
| 2006-10-26 18:15:28 | BUILDING PLAN REVIEW | | | PERMIT:04120353 | | | ADD:717 S. OLIVE AVE. | | | CONT:KASTCONSTRUCTION | | | TEL: (561)835-3890 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW RFI - 396 | | | ACTION: DENIED | | | | | | | | | 1) FBC.2001 SEC. 2101.2.CONSTRUCTION DOCUMENTS. | | | DRAWINGS AND DETAILS SHALL SHOW ALL THE ITEMS REQUIRED | | | TO BE SHOWN ON THE DRAWINGS BY THIS CODE INCLUDINGTHE | | | FOLLOWING: | | | 4. PROVISION FOR DIMENSIONAL CHANGES RESULTING | | | FROM ELASTIC DEFORMATION, CREEP, SHRINKAGE, TEMPERATURE | | | AND MOISTURE.NOTE: CEMENT GROUT IS NOT A MATERIAL | | | WHICH WILL MEET THE ELASTICITY DEFORMATION IN THIS | | | SITUATION.CHOSE A MATERIAL WHICH WILL MEET THE FIRE | | | RESISTANCE RATING OF THE WALL AND ELASTIC DEFORMATION. | | | | | | 2)FBC.2001 SEC. 1604.5INTERIOR WALL LOADS. | | | INTERIOR WALLS, PERMANENT PARTITIONS AND TEMPORARY | | | PARTITIONS SHALL BE DESIGNED TO RESIST ALOADS TO | | | WHICH THEY ARE SUBJECTED BUT NOT LESS THAN 5 PSF | | | APPLIED PERPENDICULAR TO THE WALLS, EXCEPT FOR | | | DECORATIVE SCREEN WALLS. | | | ALSO SEE SEC. 703.2. FOR FIRE RESISTANCE RATINGS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
141 |
Status |
F |
Date |
2006-10-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-13 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-13 |
Time |
07:07 |
Sent To |
PC |
|
| Notes |
| 2006-10-13 07:25:47 | | | | | | | 1) F.S.471.025 AND F.A.C.61G15-23.002 | | | THE REGISTERED PROFESSIONALSHALL AFFIX HIS OR HER | | | OFFICIAL SEAL,SIGNATURE AND DATE TO SAID DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA AS REQUIRED BY | | | FLORIDA STATUTE. HOWEVER, AND INDEX PAGE REFERENCEING | | | ALL PAGES CAN BE SUBMITTED. | | | NOTE: THE INFORMATION SUBMITTED ARE ALL PHOTO-COPIES. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
140 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2006-10-11 16:46:23 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR | | | #39 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
139 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2006-10-11 16:25:29 | FBC: 2001. | | | SHORING AND FORMWORKLETTERS FOR ELEVATED DECK AND | | | POUR #38. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
138 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2006-10-11 16:06:29 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR | | | #37. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
137 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2006-10-11 15:54:52 | FBC:2001 | | | SHORING AND FORMWORK LETTERS FOR ELEVATED DECK AND POUR | | | #36 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
136 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2006-10-11 15:44:23 | FBC:2001 | | | SHORING AND FORMWORK LETTERFOR ELEVATED DECK AND POUR | | | #35 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
135 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2006-10-11 15:34:58 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR | | | #34. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
134 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2006-10-11 14:59:31 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR | | | #33 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
133 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2006-10-11 14:51:50 | FBC:2001. | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR | | | #32 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
132 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2006-10-11 14:38:35 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR | | | #31. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
131 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2006-10-11 14:24:42 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK AND POUR | | | #30. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
130 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2006-10-11 14:15:13 | FBC:2001. | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECKAND POUR | | | #28. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
129 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2006-10-11 14:06:02 | FBC:2001 | | | SHORING AND FORMWORK LETTERFOR ELEVATED DECK POUR | | | #27. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
128 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:58:48 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK AT LEVEL | | | TWO AND POUR #26. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
127 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:49:48 | FBC: 2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK AT LEVEL | | | TWO POUR #25. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
126 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:43:41 | FBC:2001 | | | SHORING AND FORMWORK LETTERS FOR ELEVATED DECK AT LEVEL | | | TWO POUR #24. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
125 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:37:35 | FBC:2001. | | | SHORING AND FORMWORK LETTERS FOR ELEVATED DECK LEVEL | | | TWO AND POUR #23. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
124 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:29:48 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK AT LEVEL | | | TWO POUR #22. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
123 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:26:13 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK AT LEVEL | | | TWO POUR #21. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
122 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:23:59 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO | | | AND POUR #20. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
121 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:20:04 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO | | | POUR #19. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
120 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:14:04 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO | | | AND POUR #17. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
119 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:12:04 | FBC:2001 | | | SHORING AND FORMWORK LETTERFOR ELEVATED DECK LEVEL | | | TWO POUR #16 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
118 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:06:27 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO | | | AND POUR #15 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
117 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:03:16 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO | | | AND POUR #14 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
116 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:02:02 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO | | | AND POUR #14. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
115 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2006-10-11 13:00:30 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO | | | POUR #13. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
114 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2006-10-11 12:57:44 | FBC:2001 | | | SHORING AND FORMWORK LETTERS FOR ELEVATED DECK LEVEL | | | TWO POUR #12 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
113 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2006-10-11 12:52:26 | FBC:2001 | | | SHORINGAND FORMWORK LETTER FOR ELEVATED DECK AT LEVEL | | | TWO POUR #11. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
112 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2006-10-11 12:39:31 | FBC:2001 | | | SHORING AND FORMWORK LETTERS FOR LEVEL TWOELEVATED | | | DECK POUR #10. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
111 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2006-10-11 11:19:10 | FBC:2001 | | | SHORING AND FORMWORK LETTER FOR LEVEL TWO ELEVATED DECK | | | POUR #7. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
110 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
11:15 |
Sent To |
|
|
| Notes |
| 2006-10-11 11:17:30 | FBC:2001 | | | SHORING/FORMWORK LETTER FOR ELEVATED DECK LEVEL TWO | | | POUR #6B |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
109 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2006-10-11 11:15:38 | FBC:2001 | | | SHORING/FORMWORD LETTER FOR ELEVATED DECK LEVEL TWO | | | POUR #6 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
108 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2006-10-11 11:13:12 | FBC:2001 | | | SHORING/FORMWORK LETTER FOR LEVEL TWO POUR #5 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
107 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2006-10-11 11:10:10 | FBC:2001 | | | SHORING LETTER FOR LEVEL TWO POUR #4 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
106 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2006-10-11 08:23:55 | FBC:2001 | | | SUBMITTAL #03100.06.01. MEZZANINE POUR 5 AND 6. SHORING | | | AND SHOP DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
105 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
06:58 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
06:54 |
Sent To |
|
|
| Notes |
| 2006-10-11 06:58:26 | FBC:2001 | | | SUBMITTAL #05500.01.CORNER GUARDS/FPL SUMP PIT FRAME | | | AND COVER. | | | ELEVATOR SUMP PIT FRAME AND COVER. ELEVATOR SEPERATOR | | | BEAMS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
104 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2006-10-11 06:48:14 | FBC:2001 | | | SUBMITTAL #07120.02. THOROSEAL DATA. USED AT | | | FOUNDATION WALLS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
103 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
06:25 |
Sent To |
|
|
| Notes |
| 2006-10-11 06:46:17 | FBC:2001 | | | SUBMITTAL #02400.05 ALUMINUM WEIR SHOP DRAWINGS FOR | | | CONTROL STRUCTURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
102 |
Status |
P |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-11 |
Time |
06:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-11 |
Time |
06:23 |
Sent To |
|
|
| Notes |
| 2006-10-11 06:25:34 | FBC:2001 | | | SUBMITTAL #05500.04 BOLLARD SYSTEM AT PARKING GARAGE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
101 |
Status |
P |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-10 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-10 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2006-10-10 13:44:02 | FBC:2001 | | | SUBMITTAL #03100.08. TYPICAL ELEVATOR BEAM FORMING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
100 |
Status |
P |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-10 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-10 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2006-10-10 13:01:50 | FBC:2001 | | | SUBMITTAL # 04220.01MORTA,MIX DESIGN FOR GROUT-3000 | | | PSI. PRE-CAST LIINTELS/DOVETAILS- 20 GAUGE (MIN) | | | HORIXONTAL REINFORCEMENTS-9 GUAGE, CMU PRODUCT DATA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
99 |
Status |
P |
Date |
2006-10-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-10 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-10 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2006-10-10 07:10:51 | FBC:2001 | | | SUBMITTAL #14210.01 ELEVATORS SHOP DRAWINGS FOR FLOORS | | | 1 THRU 7. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
98 |
Status |
P |
Date |
2006-10-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-09 |
Time |
12:28 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-09 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2006-10-09 12:28:21 | FBC:2001 | | | SUBMITTAL #03200.25. FOR LANAI REBAR SHOP DRAWINGS | | | INCLUDING ARCH BEAMS, MASONRY AND DECK STEEL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
97 |
Status |
P |
Date |
2006-10-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-09 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-09 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2006-10-09 12:17:15 | FBC:2001 | | | SUBMITTAL #03200.24 PARKING LEVEL #9 DECK REBAR AND | | | SHOP DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
96 |
Status |
P |
Date |
2006-10-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-09 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-09 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2006-10-09 12:12:47 | FBC:2001 | | | SUBMITTAL #03200.22FOR TIE COLUMNS/TIE BEAM AND | | | MASONRY REBAR DRAWINGS FOR FLOORS 3 AND 4. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
95 |
Status |
P |
Date |
2006-10-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-09 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-09 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2006-10-09 12:04:21 | FBC:2001 | | | SUBMITTAL #03200.21 FOR PARKING LEVEL 8 TOWER LEVEL 4 | | | REBAR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
94 |
Status |
P |
Date |
2006-10-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-09 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-09 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2006-10-09 11:59:20 | FBC: 2001 | | | SUBMITTAL #03200.20 FOR PARKING LEVEL 7. DECK REBAR AND | | | BEAMS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
93 |
Status |
P |
Date |
2006-10-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-09 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-09 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2006-10-09 11:55:50 | FBC:2001 | | | SUBMITTAL #03200.18 PARKING LEVEL 5 POUR 17. | | | BEAMS/BOTTOM/MISC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
92 |
Status |
P |
Date |
2006-10-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-09 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-09 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2006-10-09 11:38:10 | FBC:2001 | | | SUBMITTAL #03200.23LEVEL 4 TIE COLUMNS-TIE BEAMS AND | | | MASORNRY REBAR |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
91 |
Status |
P |
Date |
2006-10-09 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-09 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-09 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2006-10-09 11:24:40 | FBC:2001 | | | SUBMITTAL #03200.17 SHEAR WALL REBAR. SHOP DRAWINGS | | | POUR 8 TOWER LEVEL 9. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
90 |
Status |
P |
Date |
2006-10-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-06 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-06 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2006-10-06 00:00:00 | FBC:2001 | | | SUBMITTAL #03200.19 PARKING LEVEL P6 AND | | | 3RD FLOOR DECK. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
89 |
Status |
P |
Date |
2006-10-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-06 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-06 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2006-10-06 00:00:00 | FBC:2001 | | | SUBMITTAL #03200.14 TIE COLOMNS TIE | | | BEAMS AND MASONRY FILL CELLS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
88 |
Status |
P |
Date |
2006-10-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-06 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-06 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2006-10-06 00:00:00 | FBC:2001 | | | SUBMITTAL #03200.15 TOWER AND PK6 | | | COLUMNS P5 TO P9 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
87 |
Status |
P |
Date |
2006-10-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-05 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-05 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2006-10-05 00:00:00 | FBC:2001 | | | SUBMITTAL #03200.11.01 FOR TIE COLOMNS/ | | | TIE BEAMS AND MASONRY FILL CELLS | | | FDN-LEVEL 2. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
86 |
Status |
P |
Date |
2006-10-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-05 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-05 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2006-10-05 00:00:00 | FBC:2001 | | | SUBMITTAL #08110.03 FOR COMMON AREA | | | DOORS/FRAMES AND HARDWARE. FLOORS 5 THRU | | | ROOF. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
85 |
Status |
P |
Date |
2006-10-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-05 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-05 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2006-10-05 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.25 FOR 6000 PSI IN 28 | | | DAYS PEAROCK PUMP MIX. MIX CODE 1176167 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
84 |
Status |
P |
Date |
2006-10-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-05 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-05 |
Time |
08:12 |
Sent To |
|
|
| Notes |
| 2006-10-05 00:00:00 | FBC:2001 | | | SUBMITTAL #02361.01.01. SOIL TREATMENT | | | DATA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
83 |
Status |
P |
Date |
2006-10-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-05 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-05 |
Time |
07:40 |
Sent To |
|
|
| Notes |
| 2006-10-05 00:00:00 | FBC:2001 | | | SUBMITTAL #01780.01 SPEFIC PURPOSE | | | SURVEY. BUILDING TIE IN AS-BUILT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
82 |
Status |
P |
Date |
2006-10-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-05 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-05 |
Time |
06:52 |
Sent To |
|
|
| Notes |
| 2006-10-05 00:00:00 | FBC:2001 | | | SUBMITTAL #03100.14. VAPOR BARRIER FOR | | | SLAB ON GRADE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
81 |
Status |
P |
Date |
2006-10-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
18:51 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #09300.02 FOR MATERIAL SPECS | | | AND MSDS SHEETS FOR CERAMIC TILE AND | | | STONE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
80 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
18:50 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
18:17 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #05500.05. FOR HOIST BEAM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
79 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
18:16 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
18:07 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #03100.17. FOR HARE-ROK | | | CEMENT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
78 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
17:58 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #03100.18. FOR SONOGROUT 10K. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
77 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #11170.01.02. FOR CHUTE FED | | | COMPACTORS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
76 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #15500.01M. MECHANICAL ACCESS | | | PANELS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
75 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #07140.01 IRON WATERPELLER |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
74 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #07120.09 ROOT BARRIER LOCATED | | | AT PLANTER AREAS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
73 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #07120.08 TREMDRAIN 1000. | | | DRAIN MAT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
72 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #07120.05 SIKAFLEX -2C NS/SL |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
71 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #07120.06 VULKEM 350/345/346 | | | ELASTOMERIC,WATERPROOF TRAFFIC BEARING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
70 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL SHORING,FORMWORK AND GC | | | LETTERS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
69 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
07:38 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #07120.04 CHEM-TRETE BSM 40 | | | VOC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
68 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
07:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #07120.03 VULKEN 450. FLUID | | | APPLIED WATERPROOFING MEMBRANE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
67 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
07:09 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #08110.01.02 DOOR SCHEDULE & | | | HARDWARE SCHEDULE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
66 |
Status |
P |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-04 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-04 |
Time |
06:21 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | FBC:2001 | | | SUBMITTAL #03200.16 OE SHINY GALV. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
65 |
Status |
P |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-03 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-03 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2006-10-03 00:00:00 | FBC:2001 | | | SUBMITTAL #07120.07. VULKEM 350/351. | | | SLIP-RESISTANT PEDESTRIAN WATEPROOFING | | | SYSTEM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
64 |
Status |
P |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-03 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-03 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2006-10-03 00:00:00 | FBC:2001 | | | SUBMITTAL #03100.12. EXPANSION JOINT | | | MATERIAL PRODUCT DATA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
63 |
Status |
P |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-03 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-03 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2006-10-03 00:00:00 | FBC:2001 | | | SUBMITTAL #03100.10. HILTI DATA SHEETS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
62 |
Status |
P |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-03 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-03 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2006-10-03 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.24. VERTICAL/OVERHEAD | | | CONCRETE REPAIR SYSTEM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
61 |
Status |
P |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-03 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-03 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2006-10-03 00:00:00 | FBC:2001 | | | SUBMITTAL #03100.11 FOAM DATA SHEETS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
60 |
Status |
P |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-03 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-03 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2006-10-03 00:00:00 | FBC:2001 | | | SUBMITTAL SHORING AND FORMWORK FOR | | | ELEVATED DECK POUR #9. LEVEL #2. | | | INSPECTION LETTERS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
59 |
Status |
P |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-03 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-03 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2006-10-03 00:00:00 | FBC:2001 | | | SUBMITTAL #03100.13. DOVETAIL SLOTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
58 |
Status |
P |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-03 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-03 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2006-10-03 00:00:00 | FBC:2001 | | | SUBMITTAL #03200.23. CONCRETE MIX CODE | | | #1163512. 6000 PSI IN 28 DAYS. PARKING | | | TOWER ELEVATED DECKS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
57 |
Status |
P |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-03 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-03 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2006-10-03 00:00:00 | FBC:2001 | | | SUBMITTAL #03365.04. TYPICAL LEVEL | | | 4TH,6TH AND 8TH PARKING SHOP DRAWINGS | | | AND CALCULATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
56 |
Status |
P |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-03 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-03 |
Time |
06:15 |
Sent To |
|
|
| Notes |
| 2006-10-03 00:00:00 | FBC:2001 | | | SUBMITTAL #03365.05. PARKING LEVEL 5TH | | | AND 7TH PRESTRESS FRICTION CALCULATIONS | | | AND DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
55 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-02 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-02 |
Time |
18:22 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | FBC:2001 | | | SUBMITTAL #03365.07. PARKING LEVEL #9 | | | POST TENSION CABLE CALCULATIONS AND SHOP | | | DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
54 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-02 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-02 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | FBC:2001 | | | SUBMITTAL #03365.09 LANAI LEVEL | | | PRESTRESS FRICTION CALCULATIONS AND | | | POSTTENTION SHOP DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
53 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-02 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-02 |
Time |
08:21 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | FBC:2001 | | | SUBMITTAL #03365.03 3RD LEVEL PARKING | | | PRESTRESS FRICTION CALCULATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
52 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-02 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-02 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | FBC:2001 | | | SUBMITTAL #03100.03 SPEED DOWELS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
51 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-02 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-02 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.05 DESIGN MIX 1160713 | | | 3000 PSI IN 28 DAYS. PEAROCK PUMPMIX | | | WITH FIBER. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
50 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-02 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-02 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.04. DESIGN MIX 1179568 | | | 3000 PSI IN 28 DAYS. SIDEWINDER WITH | | | HRWR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
49 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-02 |
Time |
06:55 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-02 |
Time |
06:33 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.03. DESIGN MIX 1313469 | | | 3000 PSI IN 28 DAYS. FINE MASONRY GROUT | | | WITH HRWR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
48 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-10-02 |
Time |
06:30 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-10-02 |
Time |
06:16 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | FBC:2001 | | | SUBMITTAL #04220.02. NON- SHRINK GROUT | | | FOR REPAIRS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
47 |
Status |
P |
Date |
2006-09-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-30 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-30 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2006-09-30 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.23. CURING COMPOUND. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
46 |
Status |
P |
Date |
2006-09-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-30 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-30 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2006-09-30 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.02. DESIGN MIX 1150401 | | | 10000 PSI IN 56 DAYS. PEAROCK WITH | | | HRWR,MODULUS OF ELASTICITY=4200 KSI. | | | VERTICAL COLUMNS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
45 |
Status |
P |
Date |
2006-09-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-30 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-30 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2006-09-30 00:00:00 | FBC:2001 | | | SUBMITTAL #07120.01.01. FLUID APPLIED | | | WATERPROOFING SYSTEM PRODUCT DATA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
44 |
Status |
P |
Date |
2006-09-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-30 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-30 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2006-09-30 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.16. DESIGN MIX 1177204 | | | 3000 PSI IN 28 DAYS. ASTM C-476. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
43 |
Status |
P |
Date |
2006-09-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-30 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-30 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2006-09-30 00:00:00 | FBC:2001 | | | SUBMITTAL #03100.01. NON-SHRINK GROUT | | | FOR REPAIRS- EPOXY ANCHORING SYSTEM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
42 |
Status |
P |
Date |
2006-09-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-30 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-30 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2006-09-30 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.01. DESIGN MIX 1189615 | | | 5000 PSI IN 28 DAYS REGULAR WITH HRWR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
41 |
Status |
P |
Date |
2006-09-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-30 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-30 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2006-09-30 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.13 DESIGN MIX 116537. | | | 4000 PSI IN 28 DAYS REGULAR. SLAB ON | | | GRADE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
40 |
Status |
P |
Date |
2006-09-30 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-30 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-30 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2006-09-30 00:00:00 | FBC:2001 | | | SUBMITTALS #03300.22. 4000 PSI PEAROCK, | | | PUMP MIX WITH HRWR. CRASH WALLS AND TIE | | | COLOMNS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
39 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
18:47 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTAL #03100.04.01 NEOPRENE PPAD @ | | | DETAILS#5/S5.0 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
38 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
18:26 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTALS #03200.04 REVISED 17-PC AND | | | 40-PC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
37 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
18:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
17:53 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.21. 6000 PSI IN 72 | | | HOURS - REGULAR WITH HRWR |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
36 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUUBMITTAL #03300.15. DESIGN MIX | | | 1161529. 5000/6000 PSI IN 28 DAYS- | | | REGULAR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
35 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.14 | | | DESIGN MIX 1163539. 5000 PSI IN 28 | | | DAYS-REGULAR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
34 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTAL: #033300.12 | | | DESIGN MIX 1161404. 3000 PSI IN 28 DAYS- | | | REGULAR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
33 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTALS: #03300.07 | | | DESIGN MIX 1177399. 6000 PSI IN 28 DAYS | | | PEAROCK WITH HRWR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
32 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTAL: # 03300.18 | | | DESIG MIX 1177563. 3000 PSI IN 40 | | | HOURS/6000 PSI IN 28 DAYS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
31 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTAL: #03300.19. | | | MIX CODE 1227928. 300PSI IN | | | 24HOURS/6000PSI IN 28 DAYS-REGULAR |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
30 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTAL: #03300.10. | | | DESIGN MIX 1353717. 8000 PSI IN 56 DAYS. | | | PEAROCK WITH HRWR MODULOS OF | | | ELASTICITY=4200KSI. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
29 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTAL: #03300.11. DESIGN MIX | | | 1353718.9000 PSI IN 56 DAYS. PEAROCK | | | WITH HRWR, MODULUS OF ELASTICITY=4200KSI |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
28 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTAL: #03300.08. DESIGN MIX CODE | | | 1149386. 6000 PSI IN 28 DAYS-REGULAR | | | WITH CORROSION INHIBTORS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
27 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTAL #03300.20. 4000 PSI SIDEWINDER | | | WITH /HRWR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
26 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTAL #03200.12 SECONDARY SLAB AND | | | REBAR SHOP DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
25 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-29 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-29 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | FBC:2001 | | | SUBMITTALS.#03365.01. STUD RAIL SHOP | | | DRAWINGS. FLOORS P2 THRU LANAI. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
24 |
Status |
P |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-28 |
Time |
18:44 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-28 |
Time |
18:28 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | FBC:2001 | | | SUBMITTAL #03200.07. STUB TIE/ COLUMNS | | | TO ELEVATION OF FOUNDAATION WALLS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
23 |
Status |
P |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-28 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-28 |
Time |
18:04 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | FBC: 2001 | | | SUBMITTAL #03200.08 BOOM PUMP | | | FOUNDATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
22 |
Status |
P |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-28 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-28 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | FBC:2001 | | | SUBMITTAL #03200.09. PARKING LEVEL | | | DECK #2 POUR 1-4 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
21 |
Status |
P |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-28 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-28 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | FBC:2001 | | | SUBMITTAL #03200.05. GRADE BEAMS & STRAP | | | BEAMS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
20 |
Status |
P |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-28 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-28 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | FBC:2001 | | | SUBMITTAL #03200.03 PARKING TOWER | | | COLUMNS-PILE CAPS TO PARKING #5. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
19 |
Status |
P |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-28 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-28 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | SUBMITTAL #03100.19.01 LANAI SHORING AND | | | CALCULATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
18 |
Status |
P |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-28 |
Time |
06:59 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-28 |
Time |
06:07 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | SUBMITTAL #05500.02.02. STRUCTURAL STEEL | | | STAIRS AND CALCULATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
17 |
Status |
P |
Date |
2006-09-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-27 |
Time |
18:35 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-27 |
Time |
18:14 |
Sent To |
|
|
| Notes |
| 2006-09-27 00:00:00 | | | | STRUCTURAL SUBMITTAL #05520.01.01 FOR | | | ALUMINUM RAILING @ BALCONIES |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
16 |
Status |
P |
Date |
2006-09-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-27 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-27 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2006-09-27 00:00:00 | SUBMITTAL #03100.16 PARKING LEVEL#4 THRU | | | 9. TOWER LEVEL 2 THRU 4. SHORING | | | CALCULATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
15 |
Status |
P |
Date |
2006-09-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-27 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-27 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2006-09-27 00:00:00 | SUBMITTAL SHORING. #03100.15 PARKING | | | LEVEL 3 SHORING AND CALCULATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
14 |
Status |
P |
Date |
2006-09-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-27 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-27 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2006-09-27 00:00:00 | SUBMITTAL #03100.09STAIR FORMING DETAILS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
13 |
Status |
P |
Date |
2006-09-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-27 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-27 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2006-09-26 00:00:00 | SUBMITTAL # 03400.01.02TOWER CRANE | | | SHOP DRAWINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
P |
Date |
2006-09-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-26 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-26 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2006-09-26 00:00:00 | SUBMITTAL #03365.02 PARKING LEVEL #2 | | | POST TENSION CABLE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
P |
Date |
2006-09-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-26 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-26 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2006-09-26 00:00:00 | SUBMITTAL #03200.06 SHEAR WALLS 1-9 AND | | | PILE CAPS TO PARKING #8. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2006-09-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-26 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-26 |
Time |
08:47 |
Sent To |
|
|
| Notes |
| 2006-09-26 00:00:00 | SUBMITTAL #03100.05 PARKING LEVEL #2. | | | POUR 1-3. SHORING AND CALCULATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-25 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-25 |
Time |
18:36 |
Sent To |
|
|
| Notes |
| 2006-09-25 00:00:00 | SUBMITTAL #03200.10 MEZZANINE AND | | | PARKING LEVEL #3. POUR #5-#10. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2006-09-25 |
Time |
18:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2006-09-25 |
Time |
18:06 |
Sent To |
|
|
| Notes |
| 2006-09-25 00:00:00 | | | | | | | SUBMITTAL ON 4/3/06#03200.13 PARKING | | | LEVEL #4. POUR 11-16. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2006-09-03 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2006-09-03 |
Time |
19:08 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-09-03 |
Time |
19:08 |
Sent To |
|
|
| Notes |
| 2006-09-03 00:00:00 | ARCHITECTURAL AND STRUCTURAL REVISION | | | SUBMITTED ON 6/22/06.ONE COPY OF THE | | | REVIEWED PLANS HAS BEEN RETAINED AS FILE | | | COPY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2006-09-03 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2006-09-03 |
Time |
19:06 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-09-03 |
Time |
19:06 |
Sent To |
|
|
| Notes |
| 2006-09-03 00:00:00 | STRUCTURAL REVISION SUBMITTED 5/9/06 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2006-03-29 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2006-03-29 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-03-29 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2006-03-29 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 805 6652 | | | E-MAIL: [email protected] | | | | | | | | | PRODUCT APPROVAL PROVISOS: | | | | | | | | | -PROVISO- | | | STAIRWELL DOORS S1, R1 AND R15. SHEET | | | A9.11, DOOR SCHEDULE, SHOWS THESE DOORS | | | AS TYPE I, WHICH HAS A 10"X 10" VISION | | | PANEL.THE SUBMITTED STATEWIDE PRODUCT | | | APPROVAL FL2167 GIVES DESIGN WIND | | | PRESSURES OF +65 PSF AND -65 PSF WITH | | | THE RIM EXIT DEVICE (SEE DRAWING SHEET 3 | | | OF THE PRODUCT APPROVAL NOA# 02-0523.06 | | | THAT WAS SUBMITTED WITH THE STATEWIDE | | | APPROVAL).THOSE PRESSURES ARE EXCEEDED | | | BY THE WIND PRESSURES ON THE BUILDING AT | | | THESE LOCATIONS.SUBMIT A PRODUCT | | | APPROVAL FOR DOORS WITH ADEQUATE DESIGN | | | WIND PRESSURES. | | | | | | -PROVISO- | | | LOUVERS, SHEET A8.44.GRILLE/LOUVER | | | TYPE N IS SHOWN AS 10'-3" HIGH ON THE | | | LOUVER AND GRILLE SCHEDULE.THAT | | | HEIGHT EXCEEDS THE MAXIMUM ALLOWED IN | | | BOTH OF THE TWO SUBMITTED PRODUCT | | | APPROVALS (FL4352 AND FL5160).AMEND | | | THE SIZE OR SUBMIT AN APPROPRIATE | | | PRODUCT APPROVALS. | | | | | | -PROVISO- | | | AUTOMATIC SLIDING MAIN ENTRY DOOR.ON | | | SHEET A8.41 THE UNIT HEIGHT IS SHOWN AS | | | 8'-0" WHICH EXCEEDS THE 7'-8" HEIGHT | | | SHOWN IN THE SUBMITTED STANLEY ACCESS | | | TECHNOLOGIES STATEWIDE PRODUCT APPROVAL | | | FL6249 (SEE DRAWING SHEET 1 OF NOA# | | | 04-1026.02, SUBMITTED WITH THE STATEWIDE | | | PRODUCT APPROVAL).EITHER AMEND THE | | | HEIGHT SHOWN ON THE PLANS OR SUBMIT A | | | PRODUCT APPROVAL SHOWING A DOOR HEIGHT | | | NO LESS THAN THAT STATED ON THE PLANS. | | | | | | -PROVISO- | | | SINGLE HUNG WINDOW, SHEET A8.41 SHOWS | | | WINDOW TYPES W-2 AND W-2A AS 10'-1" TALL | | | FROM FLOOR TO HORIZONTAL MULLION.THIS | | | EXCEEDS THE MAXIMUM 9'-2" SHOWN IN THE | | | SUBMITTED RC ALUMINUM STATEWIDE PRODUCT | | | APPROVAL FL3398 (SEE DRAWING SHEET 1 OF | | | NOA# 03-1216.06, SMALL MISSILE IMPACT | | | AND NOA# 03.1216.04, LARGE MISSILE | | | IMPACT).SUBMIT ALTERNATIVE OR | | | ADDITIONAL PRODUCT APPROVALS TO COVER | | | THE PROPOSED MAXIMUM WINDOW HEIGHT. | | | | | | -PROVISO- | | | FIXED WINDOW, SHEET A8.41.DUE TO THEIR | | | LOCATION ON THE BUILDING, WINDOW TYPES | | | W-3 AND W-3.2 WILL BE SUBJECT TO 140 PSF | | | NEGATIVE WIND PRESSURE.THE MAXIMUM | | | NEGATIVE PRESSURE ALLOWED BY THE | | | SUBMITTED EFCO STATEWIDE PRODUCT | | | APPROVAL FL1520 IS 130 PSF (SEE DRAWING | | | SHEET 1 OF NOA# 02-0410.04 SUBMITTED | | | WITH THE STATEWIDE PRODUCT APPROVAL). | | | SUBMIT AN ADDITIONAL OR ALTERNATE | | | PRODUCT APPROVAL TO COVER THE WIND | | | PRESSURES THAT THE WINDOWS WILL BE | | | SUBJECTED TO. | | | | | | -PROVISO- | | | STOREFRONT, SHEET A8.41.ALL THREE OF | | | THE SUBMITTEDTHE SUBMITTED GAMMA | | | U.S.A. WINDOW WALLPRODUCT APPROVALS | | | ARE FOR SMALL MISSILE IMPACT LOCATIONS. | | | NO APPROPRIATE PRODUCT APPROVAL HAS BEEN | | | SUBMITTED FOR THE STOREFRONT WINDOWS | | | (AND DOORS) ON THE FIRST FLOOR WHICH ARE | | | IN THE LARGE MISSILE IMPACT ZONE. SUBMIT | | | PRODUCT APPROVAL(S) FOR LARGE MISSILE | | | IMPACT STOREFRONT WINDOWS (AND DOORS). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2006-02-26 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2006-02-26 |
Time |
22:11 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-02-23 |
Time |
19:02 |
Sent To |
|
|
| Notes |
| 2006-02-23 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 11/11/05: | | | | | | 4) NOTE THAT THE NOTICE OF COMMENCEMENT, | | | IMPACT FEE RECEIPT AND SPECIAL INSPECTOR | | | AGREEMENT WILL BE REQUIRED BEFORE A | | | PERMIT CAN BE ISSUED: | | | (A) THE SUBMITTED NOTICE OF | | | COMMENCEMENTSTATES "...LIMITED TO | | | CONCRETE FOUNDATION PILES ONLY".A NEW | | | ONE MUST BE RECORDED | | | (B) THE IMPACT FEE PAYMENT RECEIPT MUST | | | BE SUBMITTED.THE IMPACT FEE STAMP IS | | | CURRENTLY ON THE VOIDED COPY OF SHEET | | | A0.00 AND HAS BEEN MARKED "KEEP FOR | | | IMPACT FEE STAMP".THAT SHEET SHOULD BE | | | ATTACHED TO ONE OF THE THREE PERMIT PLAN | | | SETS. | | | (C) THE SPECIAL INSPECTOR AGREEMENT WAS | | | SUBMITTED ON A 1994 VERSION OF THE FORM | | | WHICH IS NO LONGER IN USE.THIS WILL BE | | | DISCUSSED WITH WITH THE THRESHOLD | | | INSPECTOR PROGRAM MANAGER, HAROLD | | | PISKURA, TO DETERMINE IF IT ACCEPTABLE. | | | ALTERNATIVELY, PLEASE COLLECT A CURRENT | | | FORM (JULY 1, 2004 VERSION) FROM THIS | | | OFFICE, HAVE IT COMPLETED WITH ORIGINAL | | | SIGNATURES (NOTARIZED OR SEALED AS | | | APPROPRIATE) AND THEN SUBMIT IT. | | | | | | 10) PRODUCT APPROVALS: | | | (A) NONE OF THE SUBMITTED PRODUCT | | | APPROVALS INCLUDE THE STATEWIDE PRODUCT | | | APPROVAL OR LOCAL PRODUCT APPROVAL COVER | | | SHEET REQUIRED TO DEMONSTRATE COMPLIANCE | | | WITH FLORIDA ADMINISTRATIVE CODE RULE | | | 9B-72.FOR MORE DETAILS, SEE THE NOTE | | | AT THE END OF THE PRODUCT APPROVAL | | | COMMENTS. | | | (B) ROOF TILE. THE WIND UPLIFT | | | PRESSURES SHOWN ON ARCHITECTURAL PLAN, | | | SHEET A1.02, FOR THE TILED ROOF AREAS, | | | ARE UP TO 150 PSF (UPLIFT).SHEET 2 OF | | | THE SUBMITTED MONIER LIFETILE SPANISH | | | 'S' CONCRETE ROOF TILE PRODUCT APPROVAL | | | NOA# 02-1205.07 STATES THAT THE PRODUCT | | | IS FOR USE IN LOCATIONS WERE THE DESIGN | | | PRESSURES DO NOT EXCEED THOSE OBTAINED | | | BY CALCULATIONS IN COMPLIANCE WITH RAS | | | 127.SUBMIT CALCULATIONS (SEE RAS 127) | | | TO SHOW THAT THE PROPOSED ROOF TILE IS | | | SUITABLE FOR THE UPLIFT PRESSURES OF | | | THIS APPLICATION. | | | ALSO, SHEET A8.23. DETAILS 3, 4, AND 5 | | | REFER TO THE STRUCTURAL PLANS FOR | | | THICKNESS OF DENSE DECK AND ATTACHMENT | | | OF TILES.THIS INFORMATION COULD NOT BE | | | FOUND ON THE STRUCTURAL PLANS.SUBMIT | | | DETAILS. THE NOTES ON SHEET S-1.25 REFER | | | TO THE USE OF FIRE-RETARDANT TREATED | | | PLYWOOD WHICH IS IN CONFLICT WITH THE | | | ARCHITECTURAL PLANS AND IS NOT A | | | PERMITTED MATERIAL FOR USE IN | | | CONSTRUCTION TYPE I.AMEND THE | | | STRUCTURAL PLANS. | | | EITHER A STATEWIDE PRODUCT APPROVAL, OR | | | LOCAL PRODUCT APPROVAL, COVER SHEET | | | SHALL BE SUBMITTED WITH EACH COPY, SEE | | | COMMENT (A) ABOVE. | | | (C) MODIFIED BITUMEN ROOFING SYSTEM. | | | EITHER A STATEWIDE PRODUCT APPROVAL, OR | | | LOCAL PRODUCT APPROVAL, COVER SHEET | | | SHALL BE INCLUDED WITH EACH COPY OF THE | | | SUBMITTED JOHNS MANVILLE CORP. MODIFIED | | | BITUMEN ROOFING SYSTEM PRODUCT APPROVAL | | | NOA# 04-0401.04, SEE COMMENT (A) ABOVE. | | | (D) LOADING AREA SECTIONAL DOOR S28. | | | NO PRODUCT APPROVAL WAS SUBMITTED FOR | | | THIS DOOR.SUBMIT A PRODUCT APPROVAL | | | FOR THIS 14'-0" X 16'-0" SECTIONAL DOOR. | | | (E) TRASH TERMINATION/HOLDING/WASTE | | | CONTAINER ROOM DOORS.THESE DOORS ARE | | | ON THE PARKING GARAGE VEHICLE ENTRY | | | DRIVEWAY AND SO WILL BE SUBJECT TO WIND | | | PRESSURES.SHEET A9.11, DOOR SCHEDULE, | | | SHOWS EACH OF THESE DOORS AS A PAIR OF | | | 6' WIDE DOORS.NO PRODUCT APPROVAL WAS | | | SUBMITTED FOR A DOOR OF THIS WIDTH. | | | AMEND THE DOOR SCHEDULE OR SUBMIT AN | | | APPROPRIATE PRODUCT APPROVAL. | | | (F) STAIRWELL DOORS S1, R1 AND R15. | | | SHEET A9.11, DOOR SCHEDULE, SHOWS THESE | | | DOORS AS TYPE I, WHICH HAS A 10"X 10" | | | VISION PANEL.NO PRODUCT APPROVAL HAS | | | BEEN SUBMITTED FOR A HOLLOW METAL DOOR | | | WITH VISION PANEL.SUBMIT A PRODUCT | | | APPROVAL. | | | (G) STEAM ROOM DOOR.THIS DOOR IS | | | REFERENCED R14 ON SHEET A9.11 (DOOR | | | SCHEDULE).IS IT THE SAME DOOR THAT IS | | | CALLED UP AS DOOR R4 ON SHEET 4.72?THE | | | DOOR SCHEDULE SHOWS DOOR R14 AS TYPE R, | | | WHICH IS SHOWN AS "SUN-DOR-CO #SD-502". | | | THAT MANUFACTURER AND REFERENCE DOES NOT | | | CORRELATE WITH THE SUBMITTED ARCH | | | ALUMINUM MEDIUM STILE ALUMINUM DOOR | | | PRODUCT APPROVAL NOA# 01-1102.01. | | | CLARIFY THE DOOR REFERENCE NUMBER ON | | | SHEET A9.1 OR A4.72 AND REMOVE THE | | | INCORRECT DOOR MANUFACTURER REFERENCE | | | FOR DOOR R14. | | | (H) LOBBY GARAGE ENTRY DOOR P8.SHEET | | | A9.11, DOOR SCHEDULE, SHOWS THIS DOOR AS | | | TYPE S (SOLID CORE WOOD DOOR).SHEET | | | A4.14 SHOWS THE DOOR LEADING FROM THE | | | GARAGE INTO THE CONDITIONED SPACE.THE | | | GARAGE IS OPEN AT THE VEHICLE ENTRY | | | DRIVEWAYS, SO DOOR P8 WILL BE SUBJECT TO | | | WIND PRESSURES. SUBMIT A PRODUCT | | | APPROVAL FOR THIS DOOR TYPE OR REVISE | | | THE SHEET A4.14 AND THE DOOR SCHEDULE | | | (SHEET A9.11).NOTE THAT THIS DOOR IS | | | ALSO REQUIED TO BE 1-1/2 HOUR FIRE | | | RATED. | | | (I) LOUVERS, SHEET A8.44.NO PRODUCT | | | APPROVALS WERE SUBMITTED FOR THE | | | LOUVERS.SUBMIT APPROPRIATE PRODUCT | | | APPROVALS. | | | (J) WINDOW, STORE FRONT AND SLIDING | | | GLASS DOOR PRODUCT APPROVALS.IN | | | ADDITION TO THE COMMENTS BELOW, PLEASE | | | NOTE THAT, ACCORDING TO THE WIND | | | PRESSURES STATED ON ARCHITECTURAL PLAN | | | SHEET A1.02, SOME OF THESE PRODUCTS WILL | | | BEREQUIRED TO HAVE A DESIGN PRESSURE | | | RATING OF UP TO +100 PSF (POSITIVE) AND | | | -140 PSF (NEGATIVE).IT WOULD APPEAR | | | THAT THE SUBMITTED PRODUCT APPROVALS | | | WERE NOT CHECKED, PRIOR TO SUBMITTAL, TO | | | ENSURE THAT THE PROPOSED PRODUCTS CAN | | | WITHSTAND THE STATED WIND PRESSURES FOR | | | THIS BUILDING.PLEASE CHECK THE DESIGN | | | PRESSURE RATING OF ALL PRODUCT | | | APPROVALS, PRIOR TO SUBMITTAL. | | | (K) WINDOW WALL.THE SUBMITTED GAMMA | | | U.S.A. SERIES 50.2 SMALL MISSILE IMPACT | | | WINDOW WALL PRODUCT APPROVAL NO. 03-0345 | | | AND SERIES 61 LARGE MISSILE IMPACT | | | WINDOW WALL PRODUCT APPROVAL NO. 03-0348 | | | BOTH STATE, ON THEIR RESPECTIVE COVER | | | SHEETS, THAT THEY ARE "ONE-TIME PRODUCT | | | APPROVAL" APPLICATIONS FOR A PROJECT | | | CALLED "JADE RESIDENCE" 1331 BRICKELL | | | BAY DR, MIAMI, FL.THESE PRODUCT | | | APPROVALS ARE NOT VALID FOR OTHER | | | PROJECTS.SUBMIT VALID PRODUCT | | | APPROVALS. | | | (L) WINDOW WALL.THE DRAWING SHEETS 1 | | | TO 8 SUBMITTED AS PART OF THE GAMMA | | | U.S.A. SERIES 50.4A SMALL MISSILE IMPACT | | | WINDOW WALL PRODUCT APPROVAL NOA# | | | 04-1006.01 ARE NOT COPIES OF THE ONES | | | REVIEWED BY MIAMI-DADE CODE | | | COMPLIANCE OFFICE (BCCO).UNLIKE THE | | | DRAWINGS INCLUDED WITH THIS PRODUCT | | | APPROVAL ON THE MIAMI-DADE BCCO WEBSITE, | | | THEY DO NOT HAVE THE MIAMI-DADE BCCO | | | APPROVAL STAMP.SUBMIT PRODUCT | | | APPROVALS WITH DRAWINGS THAT INCLUDE THE | | | PRODUCT CERTIFICATION AGENCY STAMP OF | | | APPROVAL.ALSO, SEE COMMENT (J) ABOVE | | | AND COMMENT (A) ABOVE. | | | (M) WINDOW WALL WITH TILT WINDOW. | | | SUBMITTAL OF FENESTRATION TESTING | | | LABORATORY (FTL) REPORT 02-0729.01, FOR | | | GAMMA U.S.A SERIES 55.2 WINDOW WALL WITH | | | TILT WINDOW, IS NOTED BUT THIS IS NOT A | | | PRODUCT APPROVAL. SUBMIT A PRODUCT | | | APPROVAL FROM AN APPROVED PRODUCT | | | CERTIFICATION AGENCY, SEE COMMENT (A) | | | ABOVE. | | | (N) GAMMA U.S.A SERIES 73 SLIDING GLASS | | | DOOR. SUBMITTAL OF FENESTRATION TESTING | | | LABORATORY (FTL) REPORT 03-0821.01, IS | | | NOTED BUT THIS IS NOT A PRODUCT | | | APPROVAL. SUBMIT A PRODUCT APPROVAL FROM | | | AN APPROVED PRODUCT CERTIFICATION | | | AGENCY, SEE COMMENT (A) ABOVE. | | | (O) GAMMA U.S.A SERIES 76 ALDORA | | | ALUMINUM SLIDING GLASS DOOR.THE | | | DRAWING SHEETS 1 TO 8 SUBMITTED AS PART | | | OF THE PRODUCT APPROVAL NOA# | | | 04-1006.03 ARE NOT COPIES OF THE ONES | | | REVIEWED BY MIAMI-DADE CODE COMPLIANCE | | | OFFICE (BCCO).UNLIKE THE DRAWINGS | | | INCLUDED WITH THIS PRODUCT APPROVAL ON | | | THE MIAMI-DADE BCCO WEBSITE, THEY DO NOT | | | HAVE THE MIAMI-DADE BCCO APPROVAL STAMP. | | | SUBMIT PRODUCT APPROVALS WITH DRAWINGS | | | THAT INCLUDE THE PRODUCT CERTIFICATION | | | AGENCY STAMP OF APPROVAL.ALSO, SEE | | | COMMENT (J) ABOVE AND COMMENT (A) ABOVE. | | | | | | NOTE: FL. ADMIN CODE RULE 9B-72 (IN | | | EFFECT SINCE OCTOBER 1, 2003) REQUIRES | | | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR | | | SITE-SPECIFIC PRODUCT APPROVAL.THE | | | SUBMITTAL SHOULD INCLUDE THE STATEWIDE | | | PRODUCT APPROVAL NUMBER (FL###), | | | AVAILABLE FROM THE DEPT OF COMMUNITY | | | AFFAIRS PRODUCT APPROVAL WEBSITE WWW. | | | FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX | | | FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE | | | PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL | | | CAN BE ACHIEVED IF THERE IS A QUALITY | | | ASSURANCE PROGRAM IN PLACE WITH A STATE | | | APPROVED QUALITY ASSURANCE ENTITY. | | | LOCAL PRODUCT APPROVAL WILL ALLOW A | | | PRODUCT TO BE USED, IN ACCORDANCE WITH | | | THE TEST CRITERIA, THROUGHOUT THE | | | JURISDICTION OF WEST PALM BEACH. | | | LOCAL AND SITE SPECIFIC PRODUCT APPROVAL | | | APPLICATION FORMS ARE AVAILABLE FROM | | | THIS OFFICE.APPROVED QUALITY ASSURANCE | | | ENTITIES ARE LISTED ON THE DCA WEBSITE: | | | FLORIDABUILDING.ORG/PR/PR_ORG_SRCH.ASPX | | | | | | 25) NFPA 823-2.4.3.1REFUSE CHUTE. | | | THIS COMMENT HAS NOT BEEN ADDESSED. THE | | | COMMENT RESPONSE REFERING TO APPROVAL BY | | | THE CONSTRUCTION BOARD OF ADJUSTMENTS | | | AND APPEALS (CBAA) IS NOTED.PLEASE | | | SUBMIT A COPY OF THE CBAA FINAL | | | DECISION, FOR THE PERMIT FILE,SO THAT | | | IT MAY BE DEEMED UNNECESSARY, FOR THIS | | | PROJECT ONLY, TO PROVIDE A MINIMUM 6" | | | CLEARANCE BETWEEN THE OPEN CHUTE LOADING | | | DOOR AND CLOSED SERVICE OPENING ROOM | | | DOOR. | | | | | | 43) TO EXPEDITE REVIEW OF A RESUBMITTAL | | | WHICH REQUIRES NEW PLANS IN ORDER TO | | | ADDRESS THE ABOVE COMMENTS, THE OLD | | | SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHOULD BE STAPLED/CLIPPED TO THE | | | REMAINING OLD SHEETS, TO FORM A SET OF | | | 'OLD/VOID SHEETS', FOR COMPARISON OF | | | REVISIONS WHEN REVIEWING THE RESUBMITTED | | | PLANS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6652ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-11-11 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-11-11 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-10-21 |
Time |
21:14 |
Sent To |
|
|
| Notes |
| 2005-11-11 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 5/19/05: | | | | | | 4) INFORMATIVE. NOTE THAT THE NOTICE OF | | | COMMENCEMENT, IMPACT FEE RECEIPT AND | | | SPECIAL INSPECTOR AGREEMENT WILL BE | | | REQUIRED BEFORE A PERMIT CAN BE ISSUED. | | | | | | 5) FBC* 104.2.4SITE SURVEY. THIS | | | COMMENT HAS NOT BEEN PROPERLY ADDRESSED. | | | THIS TIME NO SURVEY DRAWING WAS | | | SUBMITTED.A SIGNED AND SEALED SURVEY | | | DRAWING PREPARED BY A LICENSED | | | SURVEYOR/MAPPER IS REQUIRED. | | | (REF: 472.025(1) FL. STATUTES). | | | | | | 8) FBC* 1804.2.2SHEET S-0, GENERAL | | | NOTES - FOUNDATIONS.THIS COMMENT HAS | | | NOT BEEN ADDRESSED.SUBMIT THREE | | | COPIES OF ARDAMAN & ASSOCIATES SOIL | | | REPORT DATED 7/28/04 AS REFERENCED | | | UNDER THE 'FOUNDATION' NOTE. | | | | | | 9) FBC 13-103.1.2THIS COMMENT HAS NOT | | | BEEN ADDRESSED.SHEET 2 OF THE | | | SUBMITTED ENERGY CODE COMPLIANCE FORMS | | | MUST BE SIGNED BY THE BUILDING OWNER, | | | THE OWNER'S ARCHITECT OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY | | | THE OWNER.ALSO THE ARCHITECT'S LICENSE | | | NUMBER MUST BE ADDED IN THE SPACE | | | PROVIDED ON SHEET 2 AND ALL OF THE | | | PROJECT INFORMATION ITEMS ON SHEET 1 | | | SHALL BE ENTERED. | | | | | | 10) PRODUCT APPROVALS.THIS COMMENT HAS | | | NOT BEEN ADDRESSED. SUBMIT PRODUCT | | | APPROVALS FOR THE WINDOWS, STOREFRONTS, | | | EXTERIOR DOORS AND ROOFING PRODUCTS. | | | | | | 25) NFPA 823-2.4.3.1THE COMMENT | | | RESPONSE REFERING TO APPROVAL BY THE | | | CONSTRUCTION BOARD OF ADJUSTMENTS AND | | | APPEALS (CBAA) IS NOTED.PLEASE SUBMIT | | | A COPY OF THE CBAA FINAL DECISION, FOR | | | THE PERMIT FILE,SO THAT IT MAY BE | | | DEEMED UNNECESSARY, FOR THIS PROJECT | | | ONLY, TO PROVIDE A MINIMUM 6" CLEARANCE | | | BETWEEN THE OPEN CHUTE LOADING DOOR AND | | | CLOSED SERVICE OPENING ROOM DOOR. | | | | | | 37) FBC 1601.1SHEET A8.24, | | | ARCHITECTURAL TRIM.SUBMITTAL OF | | | DETAILS FOR ATTACHMENT OF MOULDINGS, | | | ORNAMENTAL PANELS AND BANDS, AND OTHER | | | ARCHITECTURAL TRIM IS NOTED BUT THE | | | DETAILS DO NOT STATE THE HORIZONTAL | | | SPACING OF THE 'TAPCONS'.AMEND THE | | | DETAILS TO SHOW THE FASTENER SPACING. | | | | | | 42) FBC 11.4.6.3SHEETS A2.04 THROUGH | | | A2.09.ALL ACCESSIBLE PARKING SPACES | | | SHALL BE MIN. 12'-0" WIDE.THE PLANS | | | ONLY SHOW THE VAN ACCESSIBLE SPACES TO | | | COMPLY WITH THIS REQUIREMENT.ALL OF | | | THE REMAINING ACCESSIBLE SPACES ARE | | | SHOWN AS ONLY 8'-6" WIDE.AMEND THE | | | PLANS. | | | | | | 43) TO EXPEDITE REVIEW OF A RESUBMITTAL | | | WHICH REQUIRES NEW PLANS IN ORDER TO | | | ADDRESS THE ABOVE COMMENTS, THE OLD | | | SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHOULD BE STAPLED/CLIPPED TO THE | | | REMAINING OLD SHEETS, TO FORM A SET OF | | | 'OLD/VOID SHEETS', FOR COMPARISON OF | | | REVISIONS WHEN REVIEWING THE RESUBMITTED | | | PLANS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] | | 2005-10-21 00:00:00 | ****PLAN REVIEW IN PROGRESS**** |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-05-19 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-05-19 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-05-06 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2005-05-17 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 1/20/05: | | | | | | 2) 61G1-16.004FL. ADMIN. CODE.IT IS | | | NOTED THAT THE PLANS ARE NOW SIGNED AND | | | SEALED BUT THE ARCHITECTURAL SHEETS DO | | | NOT INCLUDE THE PRINTED NAME OF THE | | | ARCHITECT OF RECORD. PLANS PREPARED BY A | | | REGISTERED ARCHITECT SHALL INCLUDE A | | | TITLE BLOCK WHICH MUST INCLUDE THE | | | PRINTED NAME OF THE ARCHITECT SEALING | | | THE PLANS. | | | | | | 4) INFORMATIVE. NOTE THAT THE NOTICE OF | | | COMMENCEMENT, IMPACT FEE RECEIPT AND | | | SPECIAL INSPECTOR AGREEMENT WILL BE | | | REQUIRED BEFORE A PERMIT CAN BE ISSUED. | | | | | | 5) FBC* 104.2.4SITE SURVEY.THE | | | SUBMITTED SURVEY DRAWING IS NOT SIGNED | | | AND SEALED AND INCLUDES A NOTE "...NOT | | | VALID WITHOUT THE SIGNATURE AND THE | | | ORIGINAL RAISED SEAL OF..."A SIGNED | | | AND SEALED SURVEY DRAWING PREPARED BY A | | | LICENSED SURVEYOR/MAPPER IS REQUIRED. | | | (REF: 472.025(1) FL. STATUTES). | | | | | | 6) A SEPARATE PERMIT APPLICATION WILL | | | BE REQUIRED FOR THE SWIMMING POOL AND | | | SPA.ADD NOTES ON THE PLANS TO STATE | | | 'UNDER SEPARATE PERMIT'. | | | | | | 7) FBC* 105.13.1SPECIAL INSPECTOR | | | AGREEMENT.BEFORE A PERMIT CAN BE | | | ISSUED IT WILL BE NECESSARY TO ARRANGE A | | | MEETING, WITH HAROLD PISKURA (INSPECTION | | | SERVICES MANAGER - TEL: 561 805 6711), | | | INVOLVING THE OWNER, THRESHOLD | | | INSPECTOR, JOB INSPECTOR, CONTRACTOR | | | AND ENGINEER. | | | | | | 8) FBC* 1804.2.2SHEET S-0, GENERAL | | | NOTES - FOUNDATIONS.THIS COMMENT HAS | | | NOT BEEN ADDRESSED.SUBMIT THREE | | | COPIES OF ARDAMAN & ASSOCIATES SOIL | | | REPORT DATED 7/28/04 AS REFERENCED | | | UNDER THE 'FOUNDATION' NOTE. | | | | | | 9) FBC 13-103.1.2SUBMITTAL OF ENERGY | | | CODE COMPLIANCE FORMS IS NOTED BUT SHEET | | | 2 MUST BE SIGNED BY THE BUILDING OWNER, | | | THE OWNER'S ARCHITECT OR OTHER | | | AUTHORIZED AGENT LEGALLY DESIGNATED BY | | | THE OWNER.ALSO THE ARCHITECT'S LICENSE | | | NUMBER MUST BE ADDED IN THE SPACE | | | PROVIDED ON SHEET 2 AND ALL OF THE | | | PROJECT INFORMATION ITEMS ON SHEET 1 | | | SHALL BE ENTERED. | | | | | | 10) PRODUCT APPROVALS.THIS COMMENT HAS | | | NOT BEEN ADDRESSED. SUBMIT PRODUCT | | | APPROVALS FOR THE WINDOWS, STOREFRONTS, | | | EXTERIOR DOORS AND ROOFING PRODUCTS. | | | | | | 11) FBC 1003.1.1SHEET LS0.01, BUILDING | | | CODE INFORMATION, ITEM 5.10.THE | | | COMBINED POOL DECK AND ROOF TERRACE | | | OCCUPIABLE AREA IS STATED AS JUST | | | 12,849 SQFT.PLEASE CONFIRM THAT THE | | | SQUARE FOOTAGE OF THE RELEVANT SPACES | | | (INCLUDING THE MOONLIGHT THEATRE) MINUS | | | THE POOL WATER SURFACE IS IN FACT | | | 12,849 SQFT.WHAT WILL THE MOONLIGHT | | | THEATRE BE USED FOR AND WHAT IS THE | | | OCCUPANCY RATE (IN SQFT PER PERSON)? | | | | | | 21) PENDING BUILDING OFFICIAL REVIEW OF | | | PROPOSAL FOR APPROVAL UNDER ALTERNATE | | | MATERIALS AND METHODS: | | | FBC* F102.2.7SHEETS A3.01 TO | | | A3.06 ELEVATIONS.SEE ALSO COMMENT 34. | | | THE KEY NOTES REFER TO 'F11'-FOAM COLUMN | | | AND 'A'-MOULDING TYPES SEE SHEETS A??. | | | ARCHITECTURAL TRIM, ON BUILDINGS LOCATED | | | IN THE FIRE DISTRICT, SHALL BE | | | CONSTRUCTED OF APPROVED NON-COMBUSTIBLE | | | MATERIALS OR FIRE RETARDANT TREATED | | | WOOD.ANNOTATE THE PLANS TO DEMONSTRATE | | | COMPLIANCE. RESPONSE NOTED. | | | | | | 25) NFPA 823-2.4.3.1COMMENT RESPONSE | | | IS NOTED BUT 2001 FBC 3502 CITES NFPA | | | 82-99 NOT NFPA 82-04.SHEET A7.14, | | | TRASH CHUTE SERVICE OPENING ROOM. | | | THERE SHALL BE MINIMUM 6" CLEARANCE | | | BETWEEN THE OPEN CHUTE LOADING DOOR AND | | | CLOSED SERVICE OPENING ROOM DOOR. | | | AMEND THE PLANS. | | | | | | 27) FBC 11-4.13.6SHEET A4.42 (AND | | | SHEET A4.02), MANEUVERING CLEARANCES AT | | | DOORS.THE ADDED DIMENSION OF 1'-4" | | | BETWEEN THE WALL AND THE OUTSIDE EDGE OF | | | THE DOOR IS NOTED BUT ADDITIONAL | | | DIMENSIONING IS REQUIRED TO SHOW THAT | | | THERE IS A MIN. 18" CLEARANCE BETWEEN | | | THE STRIKE EDGE OF THE DOOR AND THE | | | ADJACENT PERPENDICULAR WALL. | | | AMEND/ANNOTATE THE PLANS WITH DIMENSIONS | | | TO DEMONSTRATE COMPLIANCE.THE SAME | | | ALSO APPLIES TO DOOR REFERENCE S14, | | | SHOWN ON SHEET A4.02. | | | | | | 28) FBC 411.2.3 AND FBC 1608.2.3SHEETS | | | S-1.02, S-1.04, S-1.06 AND S-1.08.THE | | | PARKING GARAGE WEST WALL BETWEEN COLUMNS | | | P25 AND P28 (OR P27 WHERE APPLICABLE) | | | AND THE CENTRAL WALL BETWEEN COLUMNS P33 | | | AND P69 SHOULD BE ANNOTATED AS IMPACT | | | WALL PW-1 OR PW-2 PER SHEET S-4.3, | | | PARKING GARAGE WALL SCHEDULE.THE SAME | | | APPLIES TO SHEET S-1.02 (PARKING LEVEL | | | 2) FOR ALMOST THE WHOLE PERIMETER OF THE | | | PARKING GARAGE AND SHEETS S-1.06 AND | | | S-1.08 FOR THE NORTH WALL OF THE PERKING | | | GARAGE. | | | | | | 29) FBC 1608.2.2GUARDRAIL STRENGTH. | | | THE COMMENT RESPONSE REFERING TO THE | | | SPECIFICATIONS MANUAL SECTION 05520 IS | | | NOTED. | | | | | | 30) FBC* 104.2.1CONTRARY TO THE | | | COMMENT RESPONSE, THE REQUIRED PLANS | | | WERE NOT SUBMITTED SO THIS COMMENT HAS | | | NOT BEEN ADDRESSED.THE SUBMITTED | | | STRUCTURAL PLAN SET DOES NOT INCLUDE A | | | GROUND FLOOR/PARKING LEVEL 1 REINFORCING | | | PLAN AND THE HIGH ROOF REINFORCING PLAN | | | IS NOT COMPLETE. SUBMIT COMPLETE PLANS | | | FOR REVIEW. | | | | | | 34) FBC* 103.7.1ALTERNATIVE MATERIALS | | | AND METHODS.SHEET LS0.01 INCLUDES | | | THREE ITEMS UNDER THE HEADING | | | 'EQUIVALENCIES AND ALTERNATIVES'.THESE | | | ITEMS WILL NEED TO BE REMOVED FROM THE | | | PERMIT PLAN SET IF THEY ARE NOT APPROVED | | | BY THE BUILDING OFFICIAL.THE | | | ITEMS SHOULD BE SUBMITTED TO THE | | | BUILDING OFFICIAL IN LETTER FORM UNDER | | | FBC 103.7.1 ALTERNATIVE MATERIALS AND | | | METHODS.THE LETTER SHALL CITE THE | | | CODE SECTIONS GIVEN IN THIS PLAN REVIEW | | | COMMENT LIST.ITEM #3, ARCHITECTURAL | | | TRIM IN THE FIRE DISTRICT, IS COVERED BY | | | COMMENT 21 OF THIS PLAN REVIEW COMMENT | | | LIST.ITEM #2, MASONRY WALL WATER STOP, | | | IS ADDRESSED BY COMMENT 35 OF THIS PLAN | | | REVIEW COMMENT LIST.ITEM #1, TEMPORARY | | | WATERPROOFING OF MASONRY WALLS, IS NOT A | | | PLAN REVIEW ISSUE.IT IS AN INSPECTION | | | ISSUE THAT COULD POSSIBLY BE COVERED BY | | | FBC* 105.6 UNDER THE DRY-IN PLAN. | | | PLEASE CONTACT HAROLD PISKURA (ISPECTION | | | SERVICES MANAGER) ON 561-805 6711 TO | | | DISCUSS THIS ITEM. | | | | | | 35)PENDING BUILDING OFFICIAL REVIEW OF | | | PROPOSAL FOR APPROVAL UNDER ALTERNATE | | | MATERIALS AND METHODS: | | | FBC* 2111.1.9SHEET S-5.1,WATER | | | STOP AT CONCRETE SLAB RECESS. SECTION | | | DETAILS 11 TO 15 DO NOT SHOW THE | | | REQUIRED 1.5" RECESS WHERE THE WALL | | | MASONRY UNITS WILL BEAR ON THE CONCRETE | | | SLAB.STATUS IS PENDING THE BUILDING | | | OFFICIAL'S REVIEW OF THE PROPOSAL FOR | | | APPROVAL UNDER FBC* 103.7.1 - ALTERNATE | | | MATERIALS AND METHODS (SEE COMMENT #34). | | | | | | 36) FBC 1606.1.4SHEET A8.41A, GLAZING | | | DETAILS.UNDER THE HEADING 'NOTES' IS | | | THE STATEMENT " 5/8" IMPACT GLASS FIRST | | | 30'-0" ABOVE GROUND".TO COMPLY WITH | | | THE CODE, LARGE MISSILE IMPACT RESISTANT | | | GLAZING IS REQUIRED UPTO 30 FEET AND | | | SMALL MISSILE IMPACT RESISTANT GLAZING | | | IS REQUIRED BETWEEN 30 AND 60 FEET ABOVE | | | GRADE.AMEND THE NOTE TO DEMONSTRATE | | | COMPLIANCE. | | | | | | 37) FBC 1601.1SHEET A8.24, | | | ARCHITECTURAL TRIM.SUBMIT DETAILS FOR | | | ATTACHMENT OF MOULDINGS, ORNAMENTAL | | | PANELS AND BANDS, AND OTHER | | | ARCHITECTURAL TRIM. | | | | | | 38) FBC 11-4.1.3(8)SHEET A4.11 TO | | | A4.15.THE 19 GROUND FLOOR LIVE/WORK | | | UNITS ARE BUSINESS OCCUPANCY CLASS SO | | | THEY ARE REQUIRED TO HAVE ACCESSIBLE | | | ENTRANCE.AS NONE OF THE | | | DETAILS/SECTIONS APPEAR TO ADDRESS THIS, | | | THE PLANS SHOULD BE ANNOTATED TO | | | DEMONSTRATE COMPLIANCE. | | | | | | 39) FBC 11-4.16 AND 11-4.19SHEET A5.11 | | | THIS SHEET HAS INSUFFICIENT/INCORRECT | | | DIMENSIONS TO DEMONSTRATE COMPLIANCE | | | WITH ACCESSIBILTY REQUIREMENTS FOR THE | | | LIVE/WORK UNIT BATHROOMS.THE SHEET | | | SHOULD BE CORRECTED AND REFER TO SHEET | | | A9.14 SO THAT: | | | (A) THE SIDE GRAB BAR AT THE W.C. SHALL | | | BE A MIN. 42" LONG (SHOWN AS 40" ON | | | SHEET A5.11) | | | (B) THE HEIGHT OF THE W.C. PAN RIM | | | SHALL BE BETWEEN 17' AND 19" ABOVE FLOOR | | | LEVEL (NO DIMENSION IS STATED ON SHEET | | | A5.11) | | | (C) THE KNEE AND TOE CLEARANCES UNDER | | | THE LAVATORIES ARE NOT DIMENSIONED ON | | | SHEET A5.11 AND SHOULD BE REFERENCED TO | | | THE DETAIL ON SHEET A9.14 WHICH WAS | | | EXTRACTED FROM FIG 31 OF FLORIDA | | | ACCESSIBILITY CODE. | | | NOTE: IT IS NOTED THAT GENERAL | | | ACCESSIBILTY REQUIREMENTS ARE SHOWN ON | | | SHEET A9.14 BUT SHEET A5.11 GIVES MORE | | | SPECIFIC REFERENCE AND IS NOT CORRECT. | | | | | | 40) TO EXPEDITE REVIEW OF A RESUBMITTAL | | | WHICH REQUIRES NEW PLANS IN ORDER TO | | | ADDRESS THE ABOVE COMMENTS, THE OLD | | | SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHOULD BE STAPLED/CLIPPED TO THE | | | REMAINING OLD SHEETS, TO FORM A SET OF | | | 'OLD/VOID SHEETS', FOR COMPARISON OF | | | REVISIONS WHEN REVIEWING THE RESUBMITTED | | | PLANS. | | | | | | 41) TO EXPEDITE REVIEW OF A RESUBMITTAL | | | WHICH REQUIRES NEW PLANS IN ORDER TO | | | ADDRESS THE ABOVE COMMENTS, THE OLD | | | SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHOULD BE STAPLED/CLIPPED TO THE | | | REMAINING OLD SHEETS, TO FORM A SET OF | | | 'OLD/VOID SHEETS', FOR COMPARISON OF | | | REVISIONS WHEN REVIEWING THE RESUBMITTED | | | PLANS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-01-28 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-01-28 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-01-20 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2005-01-20 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) WORKING DRAWING REVIEW ONLY.NO | | | PERMIT CAN BE ISSUED UNTIL THE PERMIT | | | APPLICATION AND FEES ARE SUBMITTED. | | | | | | 2) FBC* 104.2IT IS NOTED THAT THE | | | PLANS ARE NOT COMPLETE AT THIS STAGE. | | | WHEN THE PLANS ARE SUBMITTED FOR PERMIT | | | THEY SHALL BE COMPLETE AND SIGNED AND | | | SEALED BY THE DESIGNERS OF RECORD. | | | | | | 3) IMPACT FEES. IT IS NOTED THAT THE | | | PLANS HAVE BEEN SUBMITTED FOR WORKING | | | DRAWING REVIEW ONLY.PLEASE NOTE THAT | | | BECAUSE THE PERMIT APPLICATION WILL BE | | | FILED AFTER DECEMBER 30, 2004, THE FEE | | | WILL BE BASED ON THE NEW (HIGHER) | | | IMPACT FEE RATES.FOR MORE INFORMATION | | | ON PALM BEACH COUNTY IMPACT FEES GO TO: | | | | | | HTTP://WWW.CO.PALM-BEACH.FL.US/PZB/ | | | IMPACTFEES/IMPACTFEES.HTM | | | | | | BEFORE A PERMIT CAN BE ISSUED, THE | | | PLANS SHALL BE TAKEN TO PALM BEACH | | | COUNTY BUILDING DEPARTMENT FOR IMPACT | | | FEE ASSESSMENT. THEY SHALL BE STAMPED | | | AT | | | THAT OFFICE AND A COPY OF THE PAID | | | RECEIPT SUBMITTED TO THE CITY OF WEST | | | PALM BEACH DEPT OF CONSTRUCTION | | | SERVICES | | | | | | 4) NOTE THAT THE NOTICE OF | | | COMMENCEMENT, IMPACT FEE RECEIPT AND | | | SPECIAL INSPECTOR AGREEMENT WILL BE | | | REQUIRED BEFORE A PERMIT CAN BE ISSUED. | | | ALSO A DECLARATION OF CONDOMINIUM WILL | | | BE REQUIRED BEFORE CERTIFICATE OF | | | OCCUPANCY. | | | | | | 5) FBC* 104.2.4SITE SURVEY.A SIGNED | | | AND SEALED SURVEY DRAWING PREPARED BY A | | | LICENSED SURVEYOR/MAPPER IS REQUIRED. | | | (REF: 472.025(1) FL. STATUTES).UNITY | | | OF TITLE AND HORIZONTAL SEPARATION | | | REQUIREMENTS CANNOT BE ASSESSED WITHOUT | | | A SITE SURVEY. | | | | | | 6) A SEPARATE PERMIT APPLICATION WILL | | | BE REQUIRED FOR THE SWIMMING POOL AND | | | SPA. | | | | | | 7) FBC* 105.13.1SPECIAL INSPECTOR | | | AGREEMENT.BEFORE A PERMIT CAN BE | | | ISSUED IT WILL BE NECESSARY TO ARRANGE, | | | WITH HAROLD PISKURA (INSPECTION | | | SERVICES | | | MANAGER - TEL: 561 805 6711), A MEETING | | | INVOLVING THE OWNER, THRESHOLD | | | INSPECTOR, JOB INSPECTOR, CONTRACTOR | | | AND ENGINEER. | | | | | | 8) FBC* 1804.2.2SHEET S-0, GENERAL | | | NOTES - FOUNDATIONS.SUBMIT THREE | | | COPIES OF ARDAMAN & ASSOCIATES SOIL | | | REPORT DATED 7/28/04 AS REFERENCED | | | UNDER THE 'FOUNDATION' NOTE. | | | | | | 9) FBC 13-103.0ENERGY CODE COMPLIANCE | | | SHALL BE DEMONSTRATED BY SUBMITTAL OF | | | APPROPRIATE CODE COMPLIANCE FORMS | | | | | | 10) SUBMIT PRODUCT APPROVALS FOR THE | | | WINDOWS, STOREFRONTS, EXTERIOR DOORS | | | AND ROOFING PRODUCTS. | | | | | | 11) FBC TABLE 600SHEET A1.01, FIRE | | | RESISTANCE OF STRUCTURAL ELEMENTS.IT | | | IS NOTED THAT THE INDEX OF DRAWINGS | | | REFERS TO SHEETS LS0.00 - CODE DATA AND | | | LS1.00 - SITE PLAN & LIFE SAFETY NOTES | | | AND THESE SHEETS WERE NOT SUBMITTED. | | | THE REQUIRED FIRE RESISTANCE RATINGS OF | | | STRUCTURAL ELEMENTS (WALLS, COLUMNS, | | | BEAMS, FLOORS ETC) FOR A TYPE I | | | BUILDING ARE NOT STATED ON THE PLANS | | | AND | | | SHOULD BE ADDED TO ONE OF THE | | | ARCHITECTURAL SHEETS OR STRUCTURAL | | | NOTES | | | SHEET S-0.0 | | | | | | 12) FBC TABLE 600SHEET LS1.01, | | | HORIZONTAL SEPARATION.THE GENERAL | | | NOTES AND THE BUILDING ELEVATION SHEETS | | | A3.01 TO A3.04 DO NOT STATE WHETHER THE | | | AREA OF WALL OPENINGS EXCEEDS 40% OF | | | THE WALL AREA.ADD A TABLE OR NOTES TO | | | SHOW THAT THE AREA OF WALL OPENINGS | | | DOES | | | NOT EXCEED THAT ALLOWED BY THE PROVIDED | | | HORIZONTAL SEPARATION.SEE THE ABOVE | | | COMMENT REQUIRING A SURVEY DRAWING. | | | | | | 13) FBC 707.1 SHEET S A9.02 AND A9.12, | | | COMBUSTIBLES IN CONCEALED SPACES.IN | | | TYPE I CONSTRUCTION., ALL WOOD BUCKS, | | | HEADERS, FURRING STRIPS ETC SHALL BE | | | APPROVED FIRE RETARDANT TREATED LUMBER. | | | NOTE 1 ON SHEETA9.13 REFERS TO WOOD | | | BACKING, BLOCKING ETC FOR THE | | | INSTALLATION OF FINISHES. | | | AMEND/ANNOTATE SHEETS A9.02 AND A9.12 | | | TO DEMONSTRATE COMPLIANCE. | | | | | | 14) FBC 704.2.4SHEET LS1.01, EXIT | | | ACCESS CORRIDORS.THE CROSS-CORRIDOR | | | WALL LINKING THE MAIL ROOM TO ELEVATOR | | | VESTIBULE #3, AND THE MECHANICAL ROOM | | | TO THE CONFERENCE ROOM, AND THE WALLS | | | SEPERATING THE CORRIDOR FROM THE | | | JANITOR?S, MECHANICAL AND CONFERENCE | | | ROOM ARE NOT SHOWN AS FIRE-RATED.IT | | | IS NOTED THAT THE DOORS IN THESE WALLS | | | ARE ALREADY SPECIFIED AS FIRE-RATED ON | | | SHEET A9.11, DOOR SCHEDULE. | | | | | | 15) FBC 701.1.1SHEET LS1.01, | | | EMERGENCY GENERATOR ROOM.NO FIRE | | | SEPARATION IS CURRENTLY SHOWN BETWEEN | | | THE GENERATOR ROOM AND THE ADJACENT | | | ENTRY/EXIT. AMEND THE PLAN. | | | | | | 16) FBC 701.1.1SHEET LS1.01,WASTE | | | CONTAINER TOWING EQUIPMENT AREA.THE | | | REQUIRED 2 HOUR FIRE SEPARATION IS NOT | | | SHOWN BETWEEN THIS STORAGE ROOM AND THE | | | PARKING GARAGE.AMEND THE PLAN.ALSO, | | | SHEET A4.11 DOES NOT SHOW ANY DOOR | | | SCHEDULE REFERENCE FOR THE DOOR IN | | | ORDER TO VERIFY THE DOOR FIRE RATING. | | | | | | 17) FBC 701.1.1SHEETS LS1.01 AND | | | LS1.02,BUILDING STORAGE ROOM.THE | | | REQUIRED 2 HOUR FIRE SEPARATION IS NOT | | | SHOWN FOR THE WALL BETWEEN THE PARKING | | | GARAGE AND THE BUILDING STORAGE ROOM AT | | | THE WEST END OF THE PARKING GARAGE. | | | AMEND THE PLAN | | | | | | 18) FBC 704.1.3.2SHEETS LS1.04, | | | LS1.05 AND LS1.06, TENANT STORAGE | | | ROOMS. | | | THESE ARE REQUIRED TO HAVE 2 HOUR FIRE | | | SEPARATION FROM THE PARKING GARAGE. | | | FBC 704.1.2.2 DOES NOT APPLY HERE AS | | | THE | | | STORAGE ROOMS ARE ACCESSORY TO THE | | | RESIDENTIAL OCCUPANCY NOT THE PARKING | | | GARAGE. | | | | | | 19) FBC 704.2.4SHEET LS1.04, WALL | | | BETWEEN TENANT STORAGE ROOM AND PUBLIC | | | CORRIDOR.THE NOTE ON THE PLAN REFERS | | | TO FBC 704.1.2.2 EXCEPTION NO.4 AS | | | JUSTIFICATION FOR NOT FIRE-RATING THIS | | | WALL.THAT SECTION IS NOT APPLICABLE | | | IN THIS CASE BECAUSE THE CORRIDOR IS AN | | | EXIT ACCESS CORRIDOR AND IS REQUIRED TO | | | BE FIRE RATED.AMEND THE PLAN. | | | | | | 20) FBC* 104.2.1SHEETS A2.02, A2.05, | | | A2.07 AND A2.09.ADD NOTES TO THESE | | | SHEETS TO CLARIFY THAT THE UNLABELLED | | | SPACE AROUND THE PARKING GARAGE IS | | | ACTUALLY OCCUPIED BY 'RESIDENTIAL UNIT | | | BELOW' AND 'CORRIDOR BELOW'.THE NOTES | | | SHOULD STATE THAT THE REQUIRED | | | FIRE-RATING FOR THE WALLS IS STATED ON | | | THE PLAN FOR THE FLOOR BELOW. | | | | | | 21) FBC* F102.2.7SHEETS A3.01 TO | | | A3.06 ELEVATIONS.THE KEY NOTES REFER | | | TO 'F11'-FOAM COLUMN AND 'A'-MOULDING | | | TYPES SEE SHEETS A??.ARCHITECTURAL | | | TRIM, ON BUILDINGS LOCATED IN THE FIRE | | | DISTRICT, SHALL BE CONSTRUCTED OF | | | APPROVED NON-COMBUSTIBLE MATERIALS OR | | | FIRE RETARDANT TREATED WOOD.ANNOTATE | | | THE PLANS TO DEMONSTRATE COMPLIANCE. | | | | | | 22) FBC 1012.1.2SHEET A2.16, EXIT | | | DOOR LEADING TO STAIR #2.THIS DOOR | | | SHALL OPEN IN THE DIRECTION OF EGRESS. | | | AMEND THE PLAN. | | | | | | 23) FBC 1012.1.4SHEET A7.12,STAIR | | | #6.DURING ITS SWING, THE EXIT DOOR AT | | | LEVELS P2 TO P9 SHALL LEAVE AT LEAST | | | HALF OF THE REQUIRED STAIR WIDTH | | | UNOBSTRUCTED.AMEND/ANNOTATE THE PLAN | | | WITH DIMENSIONS TO DEMONSTRATE | | | COMPLIANCE. | | | | | | 24) FBC 1015.3SHEET A9.21, DETAIL 10, | | | TYPICAL BALCONY GUARDRAIL.THE | | | ORNAMENTAL PATTERN SHALL BE SUCH THAT A | | | 4? DIAMETER SPHERE CANNOT PASS THROUGH | | | ANY OPENING UP TO A HEIGHT OF 34?.A | | | BOTTOM RAIL OR CURB SHALL BE PROVIDED | | | TO REJECT THE PASSAGE OF A 2? DIAMETER | | | SPHERE.AMEND THE PLANS TO DEMONSTRATE | | | COMPLIANCE.THE NOTE ON SHEET A10.02, | | | DETAIL 1 IS FOR A DIFFERENT | | | SITUATION/LOCATION. | | | | | | 25) NFPA 823-2.4.3.1SHEET A7.14, | | | TRASH CHUTE SERVICE OPENING ROOM. | | | THERE SHALL BE MINIMUM 6" CLEARANCE | | | BETWEEN THE OPEN CHUTE LOADING DOOR AND | | | CLOSED SERVICE OPENING ROOM DOOR. | | | AMEND | | | THE PLANS. | | | | | | 26)FBC 11-4.9.4SHEETS A7.05 AND | | | A7.05A, STAIR #2.THE REQUIRED | | | HANDRAIL EXTENSION LENGTHS AT THE TOP | | | AND BOTTOM OF EACH FLIGHT ARE | | | TRANSPOSED | | | (TOP=BOTTOM, BOTTOM=TOP) AT 6TH LEVEL, | | | 7-14TH LEVEL, 15TH LEVEL AND 16TH | | | LEVEL. | | | AMEND THE PLANS. | | | | | | 27) FBC 11-4.13.6SHEET A4.42, | | | MANEUVERING CLEARANCES AT DOORS.IT IS | | | NOTED THAT THIS SHEET IS NOT COMPLETE. | | | THE DOORS PENCILED IN AS DOORP24 (TO | | | THERAPY ROOM) SHALL HAVE A MIN. 18? | | | CLEARANCE BETWEEN THE STRIKE EDGE OF | | | THE DOOR AND THE ADJACENT PERPENDICULAR | | | WALL.AMEND/ANNOTATE THE PLANS WITH | | | DIMENSIONS TO DEMONSTRATE COMPLIANCE. | | | THE SAME ALSO APPLIES TO DOOR REFERENCE | | | S14, SHOWN ON SHEET A4.02. | | | | | | 28) FBC 411.2.3SHEET A2.02, A2.05, | | | A2.07 AND A2.09, VEHICLE IMPACT | | | WALLS/GUARDRAILS.AMEND THE PLANS TO | | | SHOW THE REQUIRED IMPACT | | | WALLS/GUARDRAILS AT THE PERIMETER WALLS | | | OF THE PARKING GARAGE.THIS ALSO | | | APPLIES TO THE WALL, SHOWN ON SHEET | | | A2.02, BETWEEN THE PARKING GARAGE AND | | | THE VOID ABOVE THE NORTH PARKING GARAGE | | | ENTRY/EXIT, AND TO THE NORTH PORTION OF | | | THE WEST WALL AT ALL PARKING GARAGE | | | LEVELS ABOVE GROUND.IMPACT GUARDRAILS | | | ARE ALSO REQUIRED IN FRONT OF THE | | | GARAGE EXHAUST AIR SHAFT LOUVERS AT THE | | | WEST END OF EACH PARKING GARAGE LEVEL | | | ABOVE GROUND.AMEND THE PLANS. | | | | | | 29) FBC 1608.2.2SHEET A8.21, DETAILS | | | A AND A1 AND SHEET A9.21, DETAIL 10. | | | THE GUARDRAIL SHALL BE DESIGNED | | | AND CONSTRUCTED FOR A CONCENTRATED LOAD | | | OF 200 LB APPLIED IN ANY DIRECTION AT | | | THE TOP OF THE GUARDRAIL, A | | | CONCENTRATED HORIZONTAL LOAD OF 200 LB | | | APPLIED ON A 1 SQ FT AREA AT ANY POINT, | | | AND A LINE LOAD OF 50 PLF APPLIED | | | HORIZONTALLY AT THE REQUIRED GUARDRAIL | | | HEIGHT WITH A SIMULTANEOUS LINE LOAD OF | | | 100 PLF APPLIED VERTICALLY DOWNWARD ON | | | THE TOP OF THE GUARDRAIL. THESE LOADS | | | SHALL NOT BE APPLIED SIMULTANEOUSLY | | | (UNLESS NOTED ABOVE) BUT SHALL BE | | | APPLIED INDIVIDUALLY TO PRODUCE MAXIMUM | | | STRESS IN EACH OF THE COMPONENTS OR | | | SUPPORTS.AMEND/ANNOTATE THE PLANS. | | | | | | 30) FBC* 104.2.1THE SUBMITTED | | | STRUCTURAL PLAN SET DOES INCLUDE A | | | GROUND FLOOR REINFORCING PLAN AND THE | | | HIGH ROOF REINFORCING PLAN IS NOT | | | COMPLETE. SUBMIT COMPLETE PLANS FOR | | | REVIEW. | | | | | | 31) FBC 3502SHEET S-0.0, GENERAL | | | NOTES THE PLANS REFERENCE ACI 530.1-99 | | | AND ACI 318-99 (TWICE) UNDER THE | | | SUB-TITLES 'CODES' AND 'THRESHOLD | | | BUILDING INSPECTION PLAN'.THE | | | VERSIONS | | | OF THESE STANDARDS REFERENCED BY | | | FLORIDA | | | BUILDING CODE ARE ACI 530.1-02 AND ACI | | | 318-02. AMEND THE GENERAL NOTES. | | | | | | 32) FBC 3502SHEET S-0.0, GENERAL | | | NOTES THE PLANS REFERENCE ASTM A 185-85 | | | AND ASTM A 615-84A (TWICE) UNDER THE | | | SUB-TITLES 'WELDED WIRE FABRIC' AND | | | 'REINFORCING STEEL'.THE VERSIONS OF | | | THESE STANDARDS REFERENCED BY FLORIDA | | | BUILDING CODE ARE ASTM A 185-97 AND | | | ASTM A 615-94.AMEND THE GENERAL | | | NOTES. | | | | | | 33) TO EXPEDITE REVIEW OF A RESUBMITTAL | | | WHICH REQUIRES NEW PLANS IN ORDER TO | | | ADDRESS THE ABOVE COMMENTS, THE OLD | | | SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHOULD BE STAPLED/CLIPPED TO THE | | | REMAINING OLD SHEETS, TO FORM A SET OF | | | 'OLD/VOID SHEETS', FOR COMPARISON OF | | | REVISIONS WHEN REVIEWING THE | | | RESUBMITTED | | | PLANS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL | | | INFO | | | TELEPHONE: (561) 805 6716ROBERT | | | BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
35 |
Status |
F |
Date |
2008-09-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-11 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-11 |
Time |
09:23 |
Sent To |
PC |
|
| Notes |
| 2008-09-11 09:23:31 | | | | | | | | | | | | | ** DENIED REVIEW OF REVISION** | | | | | | | | | | | | 1) NOTE: ALL SITE LIGHTING IN RIGHT OF WAY AREAS SHALL | | | NOT BE PERMITTED AS PART OF THE BASE BUILDING. ANY | | | RIGHT OF WAY LIGHTING MAY NOT BE FED FROM BASE BUILDING | | | ELECTRICAL SERVICE. | | | | | | 2) NOTE: ANY ELECTRICAL PART OF THE BASE BUILDING NEEDS | | | TO BE REVISED ON ELECTRICAL PLANS AND TO BE REVISED BY | | | THE BASE BUILDING ELECTRICAL ENGINEER OF RECORD. | | | FS 471 | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
34 |
Status |
N |
Date |
2008-03-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-21 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-21 |
Time |
10:00 |
Sent To |
PC |
|
| Notes |
| 2008-03-21 10:01:03 | SUBMITTAL FOR AIR FILTERS, NA FOR ELEC |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
33 |
Status |
N |
Date |
2008-03-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-21 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-21 |
Time |
09:58 |
Sent To |
PC |
|
| Notes |
| 2008-03-21 09:58:47 | SUBMITTAL FOR PRESSURE SENSORS, NOT FOR ELEC, AND NOT | | | NEEDED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
32 |
Status |
F |
Date |
2008-03-15 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2008-03-15 |
Time |
21:05 |
Rev Time |
3.50 |
| Received By |
jleahy |
Date |
2008-03-15 |
Time |
20:24 |
Sent To |
|
|
| Notes |
| 2008-03-15 21:01:21 | PG. E2.02THE TWO A/CS IN P1 SHOW OCP THAT | | | VIOLATES THE NAMEPLATE OF THE UNITS PLEASE CORRECT OCP | | | FOR UNITS | | | | | | PG. E2.02SHOWS TWO SWITCHES TO FIXTURES ABOVE, | | | ARE THESE FIXTURES IN THE SAME ROOM? PLAN IS | | | CONFUSING. | | | | | | PG. E4.01 COMMUNICATION ROOM SHOW TAILS TO | | | EQUIPMENT, HOW DO YOU KNOW TAILS WILL BE LARGE ENOUGH | | | (AMPEREAGE)? | | | YOU WILL NEED TO SUPPLY | | | EQUIPMENT DETAILS FOR SIZING BRANCH CIRCUITS.ALSOL | | | NEED TO SHOW EQUIPMENT ON PLANS. | | | | | | PG. E6.01LOOKING AT REV1 FOR THE GENERATOR SHOWS | | | TWO BREAKERS BUILTIN, ON JOB ONE WAS ADDED TO | | | GENERATOR, PLEASE HAVE GENERATOR RELISTED TO SHOW ONE | | | INTERNAL | | | AND ONE EXTERNAL. | | | | | | PG. E6.08, E6.09SHOWS TWO 4" CONDUITS STUBBING INTO | | | THE CORIDOOR CEILING, DO YOU WANT ACCESS PANELS IN THE | | | CORIDOOR CEILING TO BE ABLE TO ACCESS PIPES? | | | SHOWS A 20 DEDICATED | | | CIRCUIT TO COMMUNICATIONS PANEL IN BEDROOM CLOSET. THIS | | | NEEDS TO BE AFCI PROTECTED.210.12 | | | SHOWS A CADWELL PLATE FOR | | | GROUNDING, IS THIS JUST A TYPE OR ARE THE WIRES TO BE | | | CADWELDED TO THIS BAR? | | | | | | PG. E7.14TRANSFORMER THAT FEEDS LGHE IS PROTECTED ON | | | PRIMARY BY 3 POLE 25A BREAKER, AND SECONDARY HAS 100A. | | | THERE IS NOT A 100A AVAILABLE ON THE SECONDARY SIDE | | | PRIMARY HAS ROOM FOR 2.7 AMPERES. I WILL LOOK INTO THIS | | | FURTHER AND GET BACK TO YOU BUT I DON'T FEEL THAT THE | | | SECONDARY SHOULD BE PROTECTED BY 100A MAIN | | | WHEN THERE IS NO ROOM FOR FUTURE | | | EXPANSION.IF LOAD GOES TO 100% THE 25AMP MAIN SHOULD | | | TRIP. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
31 |
Status |
P |
Date |
2008-03-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2008-03-10 |
Time |
10:02 |
Rev Time |
2.00 |
| Received By |
jleahy |
Date |
2008-03-10 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2008-03-10 10:02:04 | THIS IS REV #22JL |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
30 |
Status |
F |
Date |
2008-03-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2008-03-10 |
Time |
07:27 |
Rev Time |
2.00 |
| Received By |
jleahy |
Date |
2008-03-10 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2008-03-10 07:23:52 | ONE SET NOT SEALED ONLY A COPY OF SIGNATURE, AND THREE | | | SETS ARE NEEDED FOR THIS JOB. | | | | | | SETS ARE OTHERWISE OK. | | | | | | JAKE LEAHY 644-7291 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
29 |
Status |
F |
Date |
2008-01-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-24 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-24 |
Time |
12:55 |
Sent To |
FIRE |
|
| Notes |
| 2008-01-24 12:55:27 | ** DENIEDREVIEW OF REVISIONS. ** | | | | | | THIS REVIEW STOP WILL REMAIN IN FAIL STATUS EVEN AS | | | SOME SHEETS WERE OK. | | | | | | ** PLEASE KNOW THE FOLLOWING SHEETS SUBMITTED UNDER | | | REVISION 19 ARE OK. | | | SHEETS, 3.11, 7.13 AND 7.16 ARE OK AND STAMPED. | | | RETAINED ONE FOR FILE SET. | | | | | | | | | 1) NOTE: PLEASE SEE SHEETS 1.03A AND 1.04 A ARE NOT | | | PART OF THE BASE BUILDING AND WILL REQUIRE THIS LOW | | | VOLTAGE WORK FOR SOUND SYSTEM TO BE SUBMITTED UNDER | | | SEPARATE PERMIT. | | | | | | 2) NOTE: PLEASE SEE SHEET 3.06 CAN NOT BE STAMPED BASED | | | ON ITEMS FROM FIRE REVIEW COMMENTS ON 1/23/08. | | | THIS SHEET IS OK WITH ELECTRICAL HOWEVER WILL HAVE | | | COMMENTS FROM FIRE REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
28 |
Status |
F |
Date |
2008-01-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-23 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-23 |
Time |
15:46 |
Sent To |
PC |
|
| Notes |
| 2008-01-23 15:47:33 | ELECTRICAL SHEETS WHICH WERE PASSED AND STAMPED HAVE | | | NOW BEEN VOIDED BASED ON FIRE PLAN REVIEW COMMENTS BY | | | FIRE MARSHAL. | | | ELECTRICAL SHEETS FOR PANEL SCHEDULE ARE STILL OK AND | | | ONLY VOIDED UNIT PLANS AND LAYOUTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
27 |
Status |
N |
Date |
2008-01-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-15 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-15 |
Time |
16:21 |
Sent To |
M |
|
| Notes |
| 2008-01-15 16:22:48 | GENRATOR SILENCER SUBMITTAL. N/A. | | | HS BILL 7121 STILL APPLIES FROM PREVIOUS REVIEWS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
26 |
Status |
P |
Date |
2007-12-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-25 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-25 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2007-12-25 11:15:06 | ** PROVISO ** | | | | | | | | | 1) NOTE: PLEASE SEE NOTES FROM REVIEW ON 8/26 WITH | | | RESPECT TO HOUSE BILL 7121 AND BACK UP FULE REQUIRED. | | | THIS IS BEING NOTED ONCE AGAIN FOR INFORMATION. | | | | | | ** REVISED ELECTRICAL SHEETS STAMPED PENDING FIRE | | | REVIEW. IF FIRE REVIEW IS OK, ONE SET WILL BE RETAINED | | | FOR FILE. | | | SHEETS INCLUDE | | | 3.06,3.14,3.23,3.25,3.31,3.32,3.34,7.12,7.15,1705-1. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
25 |
Status |
P |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-03 |
Time |
18:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-03 |
Time |
18:36 |
Sent To |
|
|
| Notes |
| 2007-12-03 18:36:57 | REV'S ON 8 1/2 BY 11'S OK, WILL STILL NEED TO RIVISE ON | | | LARGE FULL SIZED SHEETS FOR FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
24 |
Status |
P |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-03 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-03 |
Time |
08:57 |
Sent To |
PC |
|
| Notes |
| 2007-12-03 08:58:20 | STEAM UNITS ARE LISTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
23 |
Status |
P |
Date |
2007-08-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-26 |
Time |
20:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-26 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2007-08-26 20:28:38 | 2007-08-26 20:28:38 | | | | | | ** TWO CITY PLAZA ** | | | REVISIONS. | | | | | | **PLEASE SEE MANY OF THE SHEETS WERE OK AND WERE | | | STAMPED. THESE ARE OK PENDING FIRE REVIEW. | | | | | | ** PLEASE SEE THE SUBMITTED ELECTRICAL NARRATIVE WAS | | | NOT ACCURATE FOR ALL SHEETS BASED ON THE ELECTRICAL | | | SHEETS SUBMITTED. THERE WERE SEVERAL SHEETS SUBMITTED | | | WHICH WERE NOT ON THE NARRATIVE LIST. | | | PLEASE SEE THE FOLLOWING COMMENTS: | | | | | | | | | 1) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES WITH | | | RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS SIGNED | | | INTO LAW JULY OF 07. | | | PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE | | | AFFECTED. PLEASE SEE THAT AN INDUSTRY BULLETIN IS BEING | | | PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL | | | INFORMATION. | | | *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED, | | | PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND | | | DOCUMENTATION FOR REVIEW. | | | PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE | | | NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS | | | ETC. | | | | | | 2) NOTE: PLEASE SEE REVIEW NOTES DATED 3/10/07 HAVE NOT | | | BEEN FULLY ADDRESSED AS OF YET. | | | PLEASE SEE THE FOLLOWING WHICH WAS STATED ON THAT | | | REVIEW. | | | **** | | | 2) NOTE: PLEASE SEE NFPA-20, 1999 OR 2003. PLEASE KNOW | | | THE AMOUNT OF FUEL FOR THE FIRE PUMP SHALL BE REVISED | | | FOR THE ON-SITE POWER OF THE GENERATOR TO INDICATE THE | | | MINIMUM FUEL AS STATED. PLEASE KNOW THAT THE ACTUAL | | | LOAD ON THE GENERATOR WITH ALL ASSOCIATED OTHER LOADS | | | SHALL BE CONSIDERED THE BASIS FOR THE FUEL CONSUMPTION | | | PER HOUR. THE PLANS INDICATE 92.1 GALS PER HOUR AT THIS | | | TIME. | | | 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT TO | | | PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100 PERCENT | | | OF THE RATED PUMP CAPACITY IN ADDITION TO THE SUPPLY | | | REQUIRED FOR OTHER DEMANDS. | | | | | | 3) NOTE: PLEASE SEE SHEET E3.32 WAS REPEATED IN TWO | | | SETS. | | | | | | 4) NOTE: PLEASE SEE SHEET E-1705.1 IS NOT TO THE | | | MINIMUM SCALE AS REQUIRED UNDER THE FBC ADMIN SECTION. | | | 104.1.2 OR THE CURRENT CODE ADMIN SECTION WHICH STATES | | | THE SAME AS THE ADMIN CODE IN EFFECT AT THE TIME OF | | | PERMIT.106.1.3 | | | | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
22 |
Status |
P |
Date |
2007-08-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-26 |
Time |
18:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-26 |
Time |
17:11 |
Sent To |
PC |
|
| Notes |
| 2007-08-26 18:26:51 | LT SUBMITTAL FROM 8/13 | | | ONE FIXTURE |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
21 |
Status |
P |
Date |
2007-08-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-03 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-03 |
Time |
10:24 |
Sent To |
PC |
|
| Notes |
| 2007-08-03 10:24:39 | I LIGHTING SUBMITTAL CHANGE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
20 |
Status |
N |
Date |
2007-08-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-03 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-03 |
Time |
10:23 |
Sent To |
PC |
|
| Notes |
| 2007-08-03 10:24:00 | TWO SETS OF SUBMITTALS NOT NEEDED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
19 |
Status |
N |
Date |
2007-08-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-19 |
Time |
18:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-19 |
Time |
16:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
18 |
Status |
N |
Date |
2007-08-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-19 |
Time |
18:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-19 |
Time |
16:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
17 |
Status |
F |
Date |
2007-03-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-10 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-10 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2007-03-10 13:03:55 | ** UNSAT** | | | | | | 1) NOTE: PLEASE SEE THE SITE LIGHTING SHEET WITH | | | LIGHTING WHICH IS CONTAINED IN THE *RIGHT OF WAY* SHALL | | | BE UNDER A SEPARATE PERMIT AND CAN NOT BE INCLUDED IN | | | THE BASE BUILDING PLANS. THIS WILL GO THROUGH | | | ENGINEERING, BUILDING AND ELECTRICAL REVIEW ONCE | | | SUBMITTED. | | | * THIS SHEET WAS NOT STAMPED IN SETS AND VOIDED. | | | | | | 2) NOTE: PLEASE SEE NFPA-20, 1999 OR 2003. PLEASE KNOW | | | THE AMOUNT OF FUEL FOR THE FIRE PUMP SHALL BE REVISED | | | FOR THE ON-SITE POWER OF THE GENERATOR TO INDICATE THE | | | MINIMUM FUEL AS STATED. PLEASE KNOW THAT THE ACTUAL | | | LOAD ON THE GENERATOR WITH ALL ASSOCIATED OTHER LOADS | | | SHALL BE CONSIDERED THE BASIS FOR THE FUEL CONSUMPTION | | | PER HOUR. THE PLANS INDICATE 92.1 GALS PER HOUR AT THIS | | | TIME. | | | 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT TO | | | PROVIDE 8 HOURS OF FIRE PUMP OPERATION AT 100 PERCENT | | | OF THE RATED PUMP CAPACITY IN ADDITION TO THE SUPPLY | | | REQUIRED FOR OTHER DEMANDS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
16 |
Status |
P |
Date |
2007-03-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-10 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-06 |
Time |
20:11 |
Sent To |
|
|
| Notes |
| 2007-03-10 13:03:21 | MOST ELECTRICAL SHEETS OK, PLEASE SEE NOTES ADDED ON | | | 3/10/07 FOR SHEETS E1.02 AND SHEET 6.01. | | | STAMPED OTHER SHEETS IN SETS AND VOIDED THE ABOVE | | | SHEETS AS NOT TO BE PART OF THIS REVISION. | | 2007-03-10 11:35:24 | IN PROGRESS | | 2007-03-06 20:10:25 | 2007-03-06 20:10:25 | | | IN ELEC FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
15 |
Status |
N |
Date |
2007-02-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-08 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-08 |
Time |
11:45 |
Sent To |
M |
|
| Notes |
| 2007-02-08 11:46:00 | SUBMITTALS FOR CO SENSORS NOT NEEDED FOR ELECTRICAL | | | REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
14 |
Status |
P |
Date |
2006-11-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-12-29 |
Time |
10:18 |
Rev Time |
1.00 |
| Received By |
jleahy |
Date |
2006-11-06 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2006-11-06 07:20:18 | NO CIRCUITS SHOWN ON DRAWINGS | | | | | | THE FOLLOWING ARE NOT SHOWN AS A LISTED PRODUCT(S) | | | | | | TYPE SE, SH, SJ, SK |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
13 |
Status |
P |
Date |
2006-11-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2006-11-06 |
Time |
07:14 |
Rev Time |
1.30 |
| Received By |
jleahy |
Date |
2006-11-06 |
Time |
07:04 |
Sent To |
|
|
| Notes |
| 2006-11-06 07:12:45 | SUBMITTALS APPROVED ACCEPT AS NOTED | | | | | | FIXTURE TYPE WBT- 232-B11-UNV-LA, TYPE C5 NO OPTION FOR | | | BATTERY BACKUP SHOWN??? | | | | | | NO BATH FIXTURES FOR FLOORS 16-21 SHOWN | | | | | | THE FOLLOWING ARE NOT SHOWN AS A LISTED PRODUCT(S). | | | | | | TYPE AC, AU, TRIMS LA, LB, LE, LF | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
12 |
Status |
F |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-12 |
Time |
18:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-12 |
Time |
18:00 |
Sent To |
B |
|
| Notes |
| 2006-10-12 18:08:21 | ** UNSAT ***** | | | | | | | | | | | | 1) NOTE:PLEASE SEE WIND LOAD CALCULATIONS FOR ANY | | | POLE LTS WILL BE REQUIRED TO CONTAIN THE TITLE BLOCK, | | | SIGNED, DATED AND SEALED BYTHE DESIGN PROFESSIONAL . | | | FS 471.025. FAC 61G15-23.002 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLANREVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
11 |
Status |
P |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-12 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-12 |
Time |
15:30 |
Sent To |
FIRE |
|
| Notes |
| 2006-10-12 15:32:03 | FIRE PUMP SUBMITTIALS OK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
F |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-12 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-12 |
Time |
15:05 |
Sent To |
PC |
|
| Notes |
| 2006-10-12 15:24:53 | **** UNSAT **** | | | | | | 1) NOTE: PLEASE SEE THAT THE "LIGHTING PROTECTION" | | | PLANS MUST BE SUBMITTED UNDER A SEPARATE PERMIT WITH | | | PLANS SIGNED , DATED AND SEALED BY A PE. | | | PLEASE ALSO KNOW, SEPARATE PLANS (3-SETS) AND FEES WILL | | | BE DUE BASED ON VALUEFOR THIS SCOPE OF WORK. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
N |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-12 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-12 |
Time |
15:02 |
Sent To |
PC |
|
| Notes |
| 2006-10-12 15:03:59 | SUBMITTIALS FOR DEVICES/RECEPTS/LTS, NOT NEEDED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
F |
Date |
2006-09-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-22 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-22 |
Time |
17:20 |
Sent To |
PC |
|
| Notes |
| 2006-09-22 00:00:00 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE KNOW THAT IF ALL THE LV/ | | | AV SYSTEMS ARE BEING DONE BY A SUB | | | CONTRACTOR, ALL MUST BE SUBMNITTED UNDER | | | A SEPARATE LV ELECTRICAL PERMIT. | | | PLEASE KNOW, THESE SYSTEMS WERE NOT ON | | | ORIGINAL PLANS AND NOT PART OF THE BASE | | | BUILDING PLANS. | | | | | | | | | 2) NOTE: PLEASE KNOW ANY LV SECURITY | | | MUST ALSO BE UNDER A LV SECURITY PERMIT. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2006-08-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-17 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-17 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2006-08-17 00:00:00 | REV'S FROM 6, 6A IN ELEC FOR REVIEW. | | | REV'S 6 AND 6A OK, | | | REDLINED , 3/4" CONDUIT TO FEED FOR POOL | | | LTS TOO SMALL FOR A TOTAL OF 4-#8'S | | | REDLINED ALUM CONDUCTORS FOR FEEDERS ARE | | | NOT PERMITTED SMALLER THAN #3. | | | NO ALUM EQUIPMENT GROUNDING CONDUCTORS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-07-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-02 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2006-07-02 00:00:00 | IN ELECTRICAL FOR REVIEW, REVIEW ALMOST | | | COMPLETE. | | | PROVISOADDRESSED, HOWEVER | | | NEED TO VERIFY THE SEPARATELY DERIVED | | | GEN SYSTEM. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2006-01-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-01-05 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-01-05 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2006-01-05 00:00:00 | **************************************** | | | PLEASE SEE THE FOLLOWING WILL BE SET UP | | | AS A "PROVISO" WHICH WILL REQUIRE SOME | | | SHEETS TO BE REVISED "BEFORE ANY ROUGH | | | ELECTRICAL INSPECTION" OR 6 MONTHS WHICH | | | EVER COMES FIRST. | | | THESE ITEMS HAVE ALSO BEEN REDLINED ON | | | PLANS. | | | ITEMS FROM PREVIOUS REVIEWS AND | | | INFORMATION TO BE FORTH COMING. | | | | | | | | | ********** PROVISO/REVISION *********** | | | | | | 1)NOTE: PLEASE SEE MISSING RECEPTS IN | | | UNITS | | | "A", "G","D","HD". 210.52 | | | REDLINED | | | | | | 2)NOTE:PLEASE SEE SOME AREAS LABLED AS | | | "FOYER CONTAIN RECEPTS ON SMALL | | | APPLIANCE CIRCUITS. SEE 210.52B1 UNIT | | | G-1,E-1, VV1 | | | REDLINED. | | | | | | 3)NOTE:PLEASE SEE THE FOLLOWING UNITS | | | WHICH SMOKE DETECTORS ARE STILL SHOWN ON | | | MORE THAN ONE CIRCUIT. SEE UNIT #4, C-1 | | | REDLINED. | | | | | | 4)NOTE: PLEASE SEE UNIT "S" DINING RM | | | DESIGNATION REMOVED. | | | REDLINED | | | | | | 5)NOTE: PLEASE SEE SHEET 7.09 DOES NOT | | | CONTAIN THE FEEDER SCHEDULE FOR THE 225A | | | PANEL "N", THIS WAS REVISED ON 7.08. | | | REDLINED. | | | | | | 6)NOTE: PLEASE SEE PANEL SCHEDULE FOR | | | UNIT "D-2" WAS SUBMITTED, HOWEVER | | | CIRCUIT #15 FOR SD'S DOES NOT INDICATE | | | THE REQUIRED ARC FAULT PROTECTION NOTE. | | | REDLINED ON PANEL SCHEDULE, UNIT.210.12 | | | | | | 7)NOTE:POOL AREA LIGHTING TO MEET MIN | | | CLEARENCES PER 680.22 AND 411.4 | | | SOME FIXTURES SHOWN CLOSER THAN | | | PERMITTED. | | | REDLINED. | | | | | | 8)NOTE:PLEASE SEE LS101 7.8.1.3 (1) | | | WHICH REQUIRES A MIN OF 10FT | | | CANDLES(108LUX) IN STAIR TOWERS. THIS | | | LEVEL OF LIGHTING IS REQUIRED ON THE | | | WALKING SURFACES DURING NOMRAL POWER | | | CONDITIONS.(1FT CANDLE IN EMERGENCY | | | CONDITIONS. PHOTO-METRICS WILL BE | | | REQUIRED OF STAIR- | | | TOWERS. | | | | | | PLEASE SEE LS101 7.9.2.2 WHICH MENTIONS | | | IN THE EVENT OF THE TRIPPING OF ANY | | | SINGLE MEANS OF OCP WSHOULD NOT LEAVE | | | ANY EGRESS AREA IN TOTAL DARKNESS. | | | PLEASE ALSO SEE A MIN OF SOME SORT OF | | | BATTERY BACK UP FIXTURE FOR CORRIDOR'S | | | AND PARKING GARAGE WILL BE REQUIRD TO | | | PROVIDE MEANS OF EGRESS AT A LIGHTING | | | LEVEL OF 1FT CANDLE. | | | | | | 9)NOTE: PLEASE SEE 230.95,707.7D,700.26 | | | ETC. | | | PLEASE SEE A 4-POLE ATS WILL BE | | | REQUIRED. | | | PLEASE KNOW, THE GFP IS NOT REQUIRED ON | | | THE EMERGENCY/ GENERATOR SIDE OF THE EM | | | DISTRIBUTION SYSTEM, HOWEVER PLEASE SEE | | | THE ABOVE REFERENCES WHICH DO REQUIRE GF | | | SENSING. PLEASE SEE THE FOLLOWING IS | | | TAKEN DIRECTLY FROM ASCO DOCUMENTS | | | FORWARD TO ME. | | | "WHERE GROUND FAULTPROTECTION IS | | | TRIGGERED BY THE CODE AND AN ALTERNATE | | | POWER SUPPLY IS INCLUDED,SWITCHING OF | | | THE NEUTRAL BECOMES NECESSARY.THE | | | SERVICE IS LARGER THAN 1,000 AMPS. | | | CONSEQUENTLY, GROUNDFAULT PROTECTION | | | IS REQUIRED AT THE MAIN SERVICE | | | DISCONNECT AT A MINIMUM. IF ITIS | | | INSTALLED THERE AND THE GENERATOR | | | NEUTRAL GROUNDING WAS THROUGH A SOLID | | | CONNECTION TO THE MAIN SERVICE NEUTRAL, | | | A GROUND FAULT WHEN THE GENERATOR IS | | | FEEDING THE LOAD WILL CAUSE THE MAIN | | | SERVICE DISCONNECT TO OPEN. THIS WILL | | | NOTDISCONNECT THE ARCING FAULT FROM | | | THE GENERATOR. COORDINATION IS THUS | | | LOST." | | | PLEASE KNOW, IF THE MAIN IS IN THE | | | OPENING POSITION WHEN POWERM COMES BACK | | | ON, THE SENSING OF THE FPL WOULD CAUSE | | | THE ATS TO SWITCH BACK, HOWEVER THERE | | | WOULD NOT BE ANY POWER THROUGH THE | | | ELECTRICAL SYSTEM AS THE MAIN FOR THE EM | | | SYSTEM WOULD HAVE TRIPPED/OPENED. | | | PLEASE REVISE RISER AND REVISE NOTES TO | | | REFERENCE A 4-POLE TRANSFER SWITCH AND | | | INDICATING THE SEPARATELY DERIVED | | | SYSTEM. | | | | | | | | | **PLEASE SEE THE ABOVE REDLINES/PROVISO | | | ITEMS WILL NEED TO BE ADDRESSED BEFORE | | | ANY ROUGH ELECTRICAL INSPECTION IS | | | SCHEDULED. | | | ** PLEASE KNOW, ELECTRICAL PERMIT MAY BE | | | PLACED IN A "HOLD" STATUS UPON 6 MONTHS | | | TIME TABLE AND "PROVISO" HAS NOT BEEN | | | SUBMITTED. | | | | | | ** PLEASE KNOW, ANY OTHER | | | REVISIONS/DESIGN CHANGES MAY ALSO BE | | | SUBMITTED AT THAT TIME. | | | | | | | | | ** PLEASE CALL TO GO OVER SUCH ITEMS | | | LISTED ABOVE TO HELP IN EXPEDITING THIS | | | PROJECT TO A "P" STATUS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2005-12-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-31 |
Time |
12:17 |
Rev Time |
11.00 |
| Received By |
dpalmer |
Date |
2005-12-30 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2005-12-31 00:00:00 | REVIEW STARTED, IN PROGRESS | | | ** SEE ALL NOTES BELOW FOR CONDITIONS ** | | | | | | | | | ** PLANS TO REMAIN IN "F" STATUS UNTILL | | | THE FOLLOWING NOTES ARE ADDRESSED TO | | | CHANGE PROJECT TO "P" (PASSED) STATUS. | | | | | | 1)NOTE: PLEASE SEE ONE SET IS MISSING | | | SHEET E1.05 | | | | | | 2)NOTE: PLEASE SEE ALL THREE SETS ARE | | | MISSING SHEETS E8.06-8.14 AS INDICATED | | | ON COVER SHEET.?? THESE WERE IN PREVIOUS | | | SETS? SEE PROVISO ALSO. | | | | | | 2)NOTE: PLEASE SEE PREVIOUS REVIEWS | | | WHICH REQUESTED ALL SUBMITTALS FOR ALL | | | EQUIPMENT SPECS: | | | PLEASE SEE THE FIRE PUMP AND FIRE PUMP | | | CONTROLLER SPECS WERE SUBMITTED, HOWEVER | | | THERE APPEARS TO BE ONLY ONE SET AND | | | THEY ARE LOCATED IN THE REPSONSE PACKAGE | | | BY THE ENGINEER. PLEASE SEE THE | | | "EQUIPMENT SPEC BOOKS" SHOULD CONTAIN | | | THREE SETS OF SAID SPECS FOR FP AND FPC. | | | | | | 3)NOTE: PLEASE ALSO SEE NOTES PERTAINING | | | TO "COLOR CODING SPEC SHEET" AND | | | BUS-DUCT SPEC SHEET" WHICH WERE TO BE | | | REVISED IN " JOBSITE SPEC BOOKS". THESE | | | SHEETS WERE REVISED, HOWEVER THE ONE | | | COPY OF THESE (BUS-DUCT) WAS SUBMITTED | | | IN THE SAME PACKAGE WITH THE ENGINEER'S | | | RESPONSES AND THE OTHER REVISED COPIES | | | OF COLOR CODING WERE SUBMITTED IN EQUIP | | | SPEC BKS.. | | | PLEASE SEE THREE COPIES OF THE REVISED | | | 16120-2 WERE PLACED IN EQIP SPEC BK | | | INSTEAD IF JOBSITE SPEC BOOK. | | | | | | ** PLEASE BRING IN SHEETSNEEDED TO | | | COMPLETE ALL THREE "JOBSITE SPEC BOOKS" | | | AND THE THREE COPIES OF "EQUIPMENT SPEC | | | BOOKS". | | | THESE BOOKS WILL BE STAMPED AT THAT | | | TIME. | | | | | | **************************************** | | | PLEASE SEE THE FOLLOWING WILL BE SET UP | | | AS A "PROVISO" WHICH WILL REQUIRE SOME | | | SHEETS TO BE REVISED "BEFORE ANY ROUGH | | | ELECTRICAL INSPECTION" OR 6 MONTHS WHICH | | | EVER COMES FIRST. | | | THESE ITEMS HAVE ALSO BEEN REDLINED ON | | | PLANS. | | | ITEMS FROM PREVIOUS REVIEWS AND | | | INFORMATION TO BE FORTH COMING. | | | | | | | | | ********** PROVISO/REVISION *********** | | | | | | 1)NOTE: PLEASE SEE MISSING RECEPTS IN | | | UNITS | | | "A", "G","D","HD". 210.52 | | | REDLINED | | | | | | 2)NOTE:PLEASE SEE SOME AREAS LABLED AS | | | "FOYER CONTAIN RECEPTS ON SMALL | | | APPLIANCE CIRCUITS. SEE 210.52B1 UNIT | | | G-1,E-1, VV1 | | | REDLINED. | | | | | | 3)NOTE:PLEASE SEE THE FOLLOWING UNITS | | | WHICH SMOKE DETECTORS ARE STILL SHOWN ON | | | MORE THAN ONE CIRCUIT. SEE UNIT #4, C-1 | | | REDLINED. | | | | | | 4)NOTE: PLEASE SEE UNIT "S" DINING RM | | | DESIGNATION REMOVED. | | | REDLINED | | | | | | 5)NOTE: PLEASE SEE SHEET 7.09 DOES NOT | | | CONTAIN THE FEEDER SCHEDULE FOR THE 225A | | | PANEL "N", THIS WAS REVISED ON 7.08. | | | REDLINED. | | | | | | 6)NOTE: PLEASE SEE PANEL SCHEDULE FOR | | | UNIT "D-2" WAS SUBMITTED, HOWEVER | | | CIRCUIT #15 FOR SD'S DOES NOT INDICATE | | | THE REQUIRED ARC FAULT PROTECTION NOTE. | | | REDLINED ON PANEL SCHEDULE, UNIT.210.12 | | | | | | 7)NOTE:POOL AREA LIGHTING TO MEET MIN | | | CLEARENCES PER 680.22 AND 411.4 | | | SOME FIXTURES SHOWN CLOSER THAN | | | PERMITTED. | | | REDLINED. | | | | | | 8)NOTE:PLEASE SEE LS101 7.8.1.3 (1) | | | WHICH REQUIRES A MIN OF 10FT | | | CANDLES(108LUX) IN STAIR TOWERS. THIS | | | LEVEL OF LIGHTING IS REQUIRED ON THE | | | WALKING SURFACES DURING NOMRAL POWER | | | CONDITIONS.(1FT CANDLE IN EMERGENCY | | | CONDITIONS. PHOTO-METRICS WILL BE | | | REQUIRED OF STAIR- | | | TOWERS. | | | | | | PLEASE SEE LS101 7.9.2.2 WHICH MENTIONS | | | IN THE EVENT OF THE TRIPPING OF ANY | | | SINGLE MEANS OF OCP WSHOULD NOT LEAVE | | | ANY EGRESS AREA IN TOTAL DARKNESS. | | | PLEASE ALSO SEE A MIN OF SOME SORT OF | | | BATTERY BACK UP FIXTURE FOR CORRIDOR'S | | | AND PARKING GARAGE WILL BE REQUIRD TO | | | PROVIDE MEANS OF EGRESS AT A LIGHTING | | | LEVEL OF 1FT CANDLE. | | | | | | 9)NOTE: PLEASE SEE 230.95,707.7D,700.26 | | | ETC. | | | PLEASE SEE A 4-POLE ATS WILL BE | | | REQUIRED. | | | PLEASE KNOW, THE GFP IS NOT REQUIRED ON | | | THE EMERGENCY/ GENERATOR SIDE OF THE EM | | | DISTRIBUTION SYSTEM, HOWEVER PLEASE SEE | | | THE ABOVE REFERENCES WHICH DO REQUIRE GF | | | SENSING. PLEASE SEE THE FOLLOWING IS | | | TAKEN DIRECTLY FROM ASCO DOCUMENTS | | | FORWARD TO ME. | | | "WHERE GROUND FAULTPROTECTION IS | | | TRIGGERED BY THE CODE AND AN ALTERNATE | | | POWER SUPPLY IS INCLUDED,SWITCHING OF | | | THE NEUTRAL BECOMES NECESSARY.THE | | | SERVICE IS LARGER THAN 1,000 AMPS. | | | CONSEQUENTLY, GROUNDFAULT PROTECTION | | | IS REQUIRED AT THE MAIN SERVICE | | | DISCONNECT AT A MINIMUM. IF ITIS | | | INSTALLED THERE AND THE GENERATOR | | | NEUTRAL GROUNDING WAS THROUGH A SOLID | | | CONNECTION TO THE MAIN SERVICE NEUTRAL, | | | A GROUND FAULT WHEN THE GENERATOR IS | | | FEEDING THE LOAD WILL CAUSE THE MAIN | | | SERVICE DISCONNECT TO OPEN. THIS WILL | | | NOTDISCONNECT THE ARCING FAULT FROM | | | THE GENERATOR. COORDINATION IS THUS | | | LOST." | | | PLEASE KNOW, IF THE MAIN IS IN THE | | | OPENING POSITION WHEN POWERM COMES BACK | | | ON, THE SENSING OF THE FPL WOULD CAUSE | | | THE ATS TO SWITCH BACK, HOWEVER THERE | | | WOULD NOT BE ANY POWER THROUGH THE | | | ELECTRICAL SYSTEM AS THE MAIN FOR THE EM | | | SYSTEM WOULD HAVE TRIPPED/OPENED. | | | PLEASE REVISE RISER AND REVISE NOTES TO | | | REFERENCE A 4-POLE TRANSFER SWITCH AND | | | INDICATING THE SEPARATELY DERIVED | | | SYSTEM. | | | | | | | | | **PLEASE SEE THE ABOVE REDLINES/PROVISO | | | ITEMS WILL NEED TO BE ADDRESSED BEFORE | | | ANY ROUGH ELECTRICAL INSPECTION IS | | | SCHEDULED. | | | ** PLEASE KNOW, ELECTRICAL PERMIT MAY BE | | | PLACED IN A "HOLD" STATUS UPON 6 MONTHS | | | TIME TABLE AND "PROVISO" HAS NOT BEEN | | | SUBMITTED. | | | | | | ** PLEASE KNOW, ANY OTHER | | | REVISIONS/DESIGN CHANGES MAY ALSO BE | | | SUBMITTED AT THAT TIME. | | | | | | | | | ** PLEASE CALL TO GO OVER SUCH ITEMS | | | LISTED ABOVE TO HELP IN EXPEDITING THIS | | | PROJECT TO A "P" STATUS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | ? | | 2005-12-30 00:00:00 | REVIEW IN PROGRESS, FINISH FOR 12/30 | | | WILL CONTINUE ON 12/31 | | 2005-12-25 00:00:00 | IN ELECTRIC FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-09-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-07 |
Time |
07:29 |
Rev Time |
20.00 |
| Received By |
dpalmer |
Date |
2005-09-04 |
Time |
19:26 |
Sent To |
|
|
| Notes |
| 2005-09-07 00:00:00 | ************ UNSAT 3ND REVIEW ********* | | | | | | PLEASE SEENOTES FROM PREVIOUS | | | REVIEW STILL NEED TO BE ADDRESSED. | | | | | | PLEASE ALSO SEESOME NEW NOTES. | | | | | | *************************************** | | | PLEASE SEE FIRST AND SECOND PART OF | | | NOTES IS DIRECTLY TAKEN FROM FIRST TWO | | | REVIEW. PART 3 WILL BE NEW NOTES. | | | *************************************** | | | | | | 1)NOTE: NOTE #1, OK, HOWEVER PLEASE SEE | | | NOTE #19FROM SECOND REVIEW WHICH STILL | | | HAS ONE COMMENT. | | | | | | 2)NOTE: NOTE #2 OK | | | | | | 3)NOTE: NOTE #3 OK | | | | | | 4)NOTE: NOTE #4 OK. | | | | | | 5)NOTE: NOTE #5 OK ON PREVIOUS REVIEW, | | | HOWEVER PLEASE NOW SEE 2.04 WHICH SHOWS | | | BOTH FPL VAULT AND MAIN ELECTRICAL RM | | | BEING THE SAME ROOM? | | | | | | 6)NOTE: NOTE #6 OK, NO, PLEASE SEE | | | RESPONSE LTR FROM ENGINEER STATES | | | SIGNAGE AND LOCATIONS, HOWEVER PLEASE | | | SEE NOTES ADDED TO PLANS SEEMS TO HAV | | | MISSED /OR HAVE FIRE COMMAND ROOM | | | REMOVED FROM NOTE. PLEASE SEE NOTE FOR | | | "ARC FLASH" COULD NOT BE LOCATED. | | | | | | 7)NOTE: NOTE #7,OK | | | | | | 8)NOTE: NOTE #8 OK. CORRECT, ADDED | | | CIRCUITS. | | | | | | 9)NOTE: NOTE #9 OK. | | | | | | 10)NOTE: NOTE #10 OK, | | | PLEASE SEE NEW NOTES PERTAINING TO FIRE | | | ALAEM SHEETS AND CODES REFEERNCED. | | | | | | 11)NOTE: NOTE #11 OK. | | | | | | 12)NOTE: NOTE #12 OK, ARCHITECTURUAL | | | RESPONSE MENTIONS FULL ACCESSIBILTY FROM | | | GARAGE TO UNITS BY WAY OF RAMPS FOR THE | | | ENTIRE LENGTH OF TRAVEL. THIS COMMENT | | | NOW BECOMES A BUILDING COMMENT AS NEC | | | DOES NOT APPLY. IF THERE ARE ANY CHANGES | | | TO DESIGN, PLEASE CORRELATE WITH | | | ELECTRICAL PLANS. | | | | | | 13)NOTE: NOTE: OK | | | | | | 14)NOTE: NOTE: OK. | | | | | | 15)NOTE: NOTE #15 NO,PLEASE SEE NOTE #44 | | | FROM SECOND REVIEW. CIRCUITING FOR SD'S. | | | | | | 16)NOTE: NOTE #16 OK. | | | | | | 17)NOTE: NOTE #17 OK. | | | | | | 18)NOTE: NOTE #18 OK, HOWEVER PLEASE SEE | | | NOTE# 49 FROM 2ND REVIEW. | | | PLEASE ALSO SEE NEW NOTES ABOUT CATV AND | | | TELEPHONE CABINETS. | | | | | | 19)NOTE: NOTE #19 NO, PLEASEUNIT "M" | | | STILL INDICATES AN ADDITIONAL PANEL, | | | SEEM S TO BE A MISPRINT/OVERLAY PROBLEM. | | | PANEL IN "LT GRAY". | | | | | | 20)NOTE: NOTE #20 OK, SEE PREVIOUS NOTE | | | FOR PANEL IN UNIT "M". | | | | | | 21)NOTE: NOTE #21 OK. | | | | | | 22)NOTE: NOTE #22 NO, PLEASE SEE MANY | | | UNITS HAVE BEEN REDLINED FOR AREAS IN | | | QUESTION. PLEASE SEE 210.52C1-5 FOR | | | REQUIRED LOCATIONS OF GFI RECEPTS ALONG | | | KITCHEN COUNTERSPACES, INCLUDING | | | PENINSULARS AND " SEPARATE SPACES". | | | 210.52C2,4 | | | PLEASE SEE MANY OF THESE WERE CORRECTED | | | AND RECEPTS WERE ADDED, HOWEVER PLEASE | | | SEE PLANS WHICH HAVE BEEN REDLINED FOR | | | OTHER LOCATIONS. | | | PLEASE SEE UNITS, V-1,E-1,A,J,H,P,P1,U, | | | O, N. | | | | | | 23)NOTE: NOTE #23 NO, COULD NOT LOCATE | | | NOTE REQUESTED FOR SD PLACEMENT ON | | | PLANS. | | | PLEASE CLARIFY WHERE THIS IS. | | | PLEASE SEE RESPONSE LTR MENTIONS NOTE | | | ADDED TO FIRE ALARM SHEET. | | | PLEASE SEE E0.01, WHICH DID HAVE A NOTE | | | FOR 3' MIN CLEARENCE FROM AIR DIFFUSERS, | | | HOWEVER, PLEASE LIST 3' MIN FROM BATH | | | AND KITCHEN DOORS, 20' FROM COOKING | | | APPLIANCES. PLEASE SEE THERE ARE SD'S | | | SHOWN W/IN 3' OF BATHROOM DOORS. | | | PLEASE SEE REFERENCE TO NFPA-72 WAS | | | INCORRECT. PLEASE SEE PROJECT WAS | | | SUBMITTED FOR PERMIT AFTER JAN 1ST 2005, | | | WHICH BRINGS NFPA-72 TO THE 2002 | | | EDITION.PLEASE SEE CHAPTER 11.8.3.5 | | | INSTALLATION SPEACIFICS. | | | WRONG CODE WAS REFERENCED DUE TO PLANS | | | ONLY BEING SUBMITTED FOR "PLAN REVIEW" | | | BEFORE THE CODE CHANGE. THE REQUIREMENTS | | | HAVE NOT CHANGED FOR THIS, ONLY THE | | | CHAPTER NUMBER. | | | PLEASE SEE NEW COMMENTS PERTAINING TO | | | 2003 NFPA-101 | | | | | | 24)NOTE: NOTE #24 OK. | | | | | | 25)NOTE: NOTE #25 OK, NO JACUZZI TUBS AT | | | THIS TIME PER ENGINNER. | | | | | | 26)NOTE: NOTE #26NO. PLEASE SEE NOTE | | | WAS ADDED FOR FIRE PUMP AND LOCKED | | | ROTOR, HOWEVER PLEASE SEE NO SPECS WERE | | | SUBMITTED FOR FIRE PUMP OR FIRE PUMP | | | CPNTROLLER. PLEASE ALSO SEE OTHER | | | COMMENTS FROMFIRST AND SECOND REVIEW | | | AND THIS REVIEW WHICH REQUESTED THIS | | | WILL BE THE THIRD REVIEW REQUESTING | | | THESE TO BE SUBMITTED IN TO REVIEW THESE | | | DEVICES FOR CODE COMPLIANCE. | | | ********SEE NEW NOTES FOR THIS**** | | | | | | 27)NOTE: NOTE #27 NO, PLEASE SEE ABOVE | | | NOTE. PLEASE SEE NO SPECS FOR GENERATOR, | | | SUB BASE FUEL TANK ATS WERE SUBMITTED. | | | PLEASE SEE ABOVE NOTE AND NEW NOTES FOR | | | 3RD REVIEW. | | | PLEASE SEE NEW NOTES FOLLOWING. | | | | | | 28)NOTE: NOTE #28 OK. | | | | | | | | | 29)NOTE: NOTE #29 OK. | | | | | | 30)NOTE: NOTE #30 OK. | | | PLEASE SEE NEW NOTES: | | | | | | 31)NOTE: NO, PLEASE SEE RESPONSE LTR | | | MENTIONS "WILL COMPLY" HOWEVER PLEASE | | | SEE NEW NOTES PERTAINING TO NOTES ON | | | PLANS AND SPECS. | | | NO SEE NEW NOTES FROM SECOND REVIEW AND | | | NEW FROM THIRD REVIEW. | | | | | | 32)NOTE: NOTE #32 OK, (NO)NOTE ADDED , | | | GENERATOR WILL NOT BE SEPARATELY | | | DERIVED. THIS WILL BE VERIFIED ONCE | | | MANUFACTURE SPECS ARE SUBMITTED. | | | SEE NEW NOTES AND PREVIOUS NOTES WITH | | | RESPECT TO SHEETS FOR ALL REQUESTED | | | EQUIPMENT AND CORRELATING WITH PLANS AND | | | CODE COMPLIANCE. | | | | | | 33)NOTE: NOTE #33 OK. | | | | | | 34)NOTE: NOTE #34 NO, PLEASE SEE RISER | | | DIAGRAM STILLDOES NOT INCLUDE A | | | REDUCED "KEYED NOTES" OR RECDUCED | | | "FEEDER SCHEDULE FOR REFERENCE WITHOUT | | | HAVING TO TURN BACK AND FORTH FROM RISER | | | DIAGRAM PAGE TO E-6.13. | | | PLEASE SEE ONLY "KEYED NOTES ARE ON | | | RISER SHEETS. PLEASE SEE REDLINED SET OF | | | PLANS IN-WHICH A COPY OF THE FEEDER | | | SCHEDULE WAS REDUCED AND PLACED ON RISER | | | SHEETS 6.13. | | | PLEASE MAKE CHANGES TO THIS , PLEASE SEE | | | NEW COMMENTS PERTAINING TO "F" SCHEDULE | | | AND CORRELATION WITH RISER AND PANEL | | | SCHEDULES. | | | 2ND PART TO NOTE#34, NO. PLEASE SEE | | | NEW COMMENTS AS RISERS, BUS DUCT ETC | | | STILL DO NOT CORRELATE. | | | | | | 35)NOTE: NOTE #35 OK. | | | | | | 36)NOTE: NOTE # 36 OK. | | | | | | 37)NOTE: NOTE #37 OK, PLEASE SEE | | | FOLLOWING COMMENT WHICH STILL NEEDS TO | | | BE ADDRESSED. | | | | | | 38)NOTE: NOTE #38 NO, PLEASE SEE | | | PANELS STILL SHOWN AS 200A WITH 225A OCP | | | FEEDING PANEL(S). | | | PLEASE SEE PANEL FOR UNIT "M". | | | | | | 39)NOTE: NOTE #39 NO, PLEASE SEE WATER | | | HEATERS SHOWN WITH 2P50A OCP FOR 4500VA | | | UNITS ON #10 AWG.PLEASE SEE PANEL | | | SCHEDULES, PANEL SCHEDULE "S" STILL | | | SHOWS 50A OCP FOR 4.5KW WATER HEATER. | | | PLEASE SEE NEW COMMENTS PERTAINING TO | | | PANEL FOR UNIT "N". | | | PLEASE SEE 422.13,422.11,240.4, 310.16 | | | ETC. | | | | | | *************************************** | | | NEW NOTES FOR REVIEW ** (2ND REVIEW) **. | | | | | | 40)NOTE: OK. | | | | | | 41)NOTE: OK, PLEASE SEE AN EMERGENCY | | | BATTERY BACK UP TYPE OF FIXTURE WILL BE | | | REQUIRED FOR FIRE COMMAND ROMM. SEE THIS | | | AS NEW NOTE. | | | | | | 42)NOTE: NO, PLEASE SEE SOME UNITS FOR | | | 2' OF WALL SPACE REDLINED AT LOCATIONS. | | | (KITCHENS WALL SPACE 2' OR MORE. MOST | | | BEDRM WERE DONE, PLEASE SEE ANY POSSIBLE | | | LOCATIONS REDLINED FOR THESE. | | | PLEASE SEE P, P1, P2. | | | | | | 43)NOTE: OK, NO FAN FOR DRYER TO BE | | | ADDED PER ENGINEER. | | | | | | 44)NOTE: NO,PLEASE SEE MANY UNITS WHERE | | | CIRCUITING WAS UPDATED DUE TO PREVIOUS | | | COMMENTS FOR ARC FAULT PROTECTION, | | | HOWEVER PLEASE SEE NOW MANY SMOKE | | | DETECTORS ARE BEINGSHOWN TWO DIFFERENT | | | CIRCUITS IN THE SAME UNITS. PLEASE SEE | | | NFPA-72 11.5.1.1 WHICH REQUIRES SD'S TO | | | BE WIRED "IN-LINE". MUTIPLE CIRCUITS FOR | | | SD'S CAN NOT BE DONE. | | | 2002 NEC 210.12 PLEASE BE SURE ARC FAULT | | | CIRCUITS STILL CORRELATE AFTE UPDATING | | | ANY CIRCUITING. | | | PLEASE SEE ALL "OUTLETS" INCLUDING SD'S, | | | LTS, FANS AND RECEPTS REQUIRED THIS. | | | PLEASE SEE MANY OF THESE CIRCUIT #'S | | | HAVE BEEN REDLINED ON PLANS, BUT NOT | | | ALL. SEE UNITS, 15,V, V1, L, K, G, | | | M,J,,, | | | | | | 45)NOTE: OK. FIXTURES REMOVED. | | | | | | 46)NOTE: OK, FIXTURE TYPE NOTED. | | | | | | 47)NOTE: OK. | | | | | | 48)NOTE: OK. | | | | | | 49)NOTE:OK. | | | | | | 49)NOTE:YE/ NO,PLEASE SEE MOST UNITS | | | HAVE BEEN REVISED TO RE-LOCATE THESE | | | PANELS, HOWEVER PLEASE SEE UNIT "Q" | | | WHICH SHOWS THESE INWHAT APPEARS TO BE | | | THE LINEN CLOSET. | | | PLEASE SEE MANY CLOTHES CLOSETS | | | CONTAINING COMBUSTIBLES ARE SHOWN WITH | | | CATV AND TELEPHONE CABINETS. PLEASE SEE | | | IF THESE UNITS WILL REQUIRE ANY "LV | | | PLUG-IN" TYOE TRANSFORMERS THEN THESE | | | RECEPTS WHICH ARE NOT SHOWN AT THIS TIME | | | WOULD ONLY BE ALLOWED DIRECTLY OVER | | | DOORS. | | | | | | 50)NOTE:NO, PLEASE SEE2002 210.8B3 | | | FOR KITCHENS IN OTHER THAN DWELLING | | | UNITS WHICH REQUIRES ALL 15- AND | | | 20-AMPERE, 125-VOLT RECEPTACLES IN | | | NON-DWELLING-TYPE KITCHENS TO BE GFCI | | | PROTECTED. THIS REQUIREMENT APPLIES TO | | | EACH AND EVERY 15- AND 20-AMPERE, | | | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR | | | NOT THE RECEPTACLE SERVES COUNTERTOP | | | APPLIANCES. | | | THIS WOULD BE FOR "HOUSE KITCHEN". | | | | | | 51)NOTE: OK, PLEASE SEE NOTES PERTAING | | | TO 210.52, 210.52C1-5 | | | | | | 52)NOTE: OK. | | | SEE NOTE WHICH WILL REQUIRE THE BATTERY | | | BACK UP FIXTURE. | | | | | | 53)NOTE: OK, HOWEVER NOTES WITH RESPECT | | | TO SPECS,/MANUFACTURE CUT SHEETS. PLEASE | | | ALSO NEW NOTES WITH RESPECT TO DPHE. | | | | | | 54)NOTE: OK. | | | | | | 55)NOTE: OK, DETAIL SUBMITTED WHICH | | | NOTES NEW GROUNDING TO BLDG GROUNDING | | | ELECTRODE SYSTEM. | | | | | | 56)NOTE: OK, PLEASE KNOW, INFORMATION | | | FOR ALL THIS ELEVATOR | | | EQUIPMENT.DISCONNECTS ETC WILL BE | | | REQUIRED TO BE REVISED BEFORE | | | INSPECTIONS. NO CORRECTIONS NEEDED AT | | | THIS TIME. | | | | | | 57)NOTE: OK. | | | | | | 58)NOTE: OK, HOWEVER SEE NEW NOTES TO | | | FIRE PUMP FEEDERS NOW INDICATED. | | | | | | 59)NOTE: NO, PLEASE SEE BUST DUCTKEY | | | NOTES ON 6.02 AND 6.03. PLEASE SEE K-3 | | | WHICH MENTIONS CORRECTION, HOWEVER | | | PLEASE SEE "K-7" WHICH SHOWS OLD. PLEASE | | | SEE "SPEC BOOK", 16465 | | | 2.2C WHICH MENTIONS ALUM BUS-DUCT WAS | | | NOT REVISED. | | | PLEASE SEE PREVIOUS NOTES IN REFERENCE | | | TO EQUIPMENT GROUNDING METHOD OF | | | BUS-DUCT. DOES THIS BUS-DUCT CONTAIN A | | | SEPARATE ALUM BUS FOR GROUNDING? OR IS | | | THE EQUIPMENT GROUNDING THAT IS GOING TO | | | BE USED "PART" OF THE BUS-DUCT. | | | *************************************** | | | PLEASE SEE 2ND PART OF THIS NOTE COULD | | | NOT BE LOCATED ON PLANS? | | | *************************************** | | | PLEASE ALSO PLACE NOTE ON PLANS FOR | | | REQUIRED CURBS FOR FLOOR PENATRATIONS. | | | PER 368.6BFLOOR PENETRATIONS SHALL | | | COMPLY WITH (1) AND (2): | | | BUSWAYS SHALL BE PERMITTED TO BE | | | EXTENDED VERTICALLY THROUGH DRY FLOORS | | | IF TOTALLY ENCLOSED (UNVENTILATED) WHERE | | | PASSING THROUGH AND FOR A MINIMUM | | | DISTANCE OF 1.8 M (6 FT) ABOVE THE FLOOR | | | TO PROVIDE ADEQUATE PROTECTION FROM | | | PHYSICAL DAMAGE. | | | IN OTHER THAN INDUSTRIAL ESTABLISHMENTS, | | | WHERE A VERTICAL RISER PENETRATES TWO OR | | | MORE DRY FLOORS, A MINIMUM 100 MM (4 | | | IN.) HIGH CURB SHALL BE INSTALLED AROUND | | | ALL FLOOR OPENINGS FOR RISER BUSWAYS TO | | | PREVENT LIQUIDS FROM ENTERING THE | | | OPENING. THE CURB SHALL BE INSTALLED | | | WITHIN 300 MM (12 IN.) OF THE FLOOR | | | OPENING. ELECTRICAL EQUIPMENT SHALL BE | | | LOCATED SO THAT IT WILL NOT BE DAMAGED | | | BY LIQUIDS THAT ARE RETAINED BY THE | | | CURB. | | | | | | 60)NOTE: NO, THIS WAS NOT CORRECT. | | | PLEASE SEE "SPEC BOOK" 16120 | | | 2.3A5, PLEASE SEE COLOR CODING FOR | | | 277/480V SHALL BE BROWN, PURPLE, YELLOW. | | | 215.8 LOCAL AMENDMENTS. | | | | | | 61)NOTE:OK. | | | | | | 62)NOTE: OK. | | | HOWEVER PLEASE SEE NEW NOTES. | | | | | | 63)NOTE: OK. | | | HOWEVER SEE NEW NOTES. | | | | | | 64)NOTE:OK. | | | | | | 65)NOTE: OK. | | | SEE NEW NOTES FOR OTHER "F" FEEDER | | | SCHEDULE AND CORRELATION WITH PANE | | | SCHEDULES.L | | | | | | 66)NOTE: OK. | | | | | | 67)NOTE: OK, HOWEVER GEN INFORMATION, | | | FUEL SUB-BASE TANK STILL NOT SUBMITTED. | | | | | | | | | 68)NOTE:NO, SPECS FOR FIRE PUMP | | | CONTROLLER ETCRATING S STILL TO BE | | | VERIFIED.PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | AIC RATINGS SHOULD BE NOTED ON ALL | | | EQUIPMENT. | | | | | | 69)NOTE:OK, ENGINEER'S RESPONSE LETTER | | | MENTIONS, "LIGHTNING PROTECTION SYSTEM" | | | WILL BE UNDER SEPARATE PERMITS. | | | PLEASE SEE ALL INFORMATION FOR | | | | | | 70)NOTE: NO, INFORMATION NEEDS TO BE | | | SUBMITTED FOR VERIFICATION OF CODE | | | COMPLIANCE WITH SAID SYSTEMS.PLEASE ALSO | | | SEEIF ALL INFORMATION FOR FIRE PUMP, | | | FIRE PUMP CONTROLLER,GENERATOR, ATS, | | | ETC WAS NOT SUBMITTED FOR REVIEW WITH | | | BASE BLDG. | | | PLEASE SEE FIRE REVIEW COMMENTS. | | | | | | 71)NOTE: OK, NO RESPONSE NEEDED. | | | | | | 72)NOTE:OK. NO RESPONSE NEEDED. | | | | | | 73)NOTE: PLEASE KNOW, AS NOTED IN SOME | | | NOTES, DUE TO SOME INFORMATION MISSING | | | ON PLANS AND WITH PLANS, SOME COMMENTS | | | ARE NEW AND SOME ARE REPEAT. | | | *************************************** | | | | | | 3RD REVIEW | | | NEW COMMENTS/AND REPEAT COMMENTS WITH | | | FURTHER EXPLANATION IN ORDER FOR | | | COMMENTS TO BE ADDRESSED FOR A FINAL | | | REVIEW. | | | | | | | | | 74) NOTE: PLEASE SEE PREVOUS NOTES | | | PERTAINING TO BUS DUCT. | | | PLEASE CORRELATE BUS-DUCT SIZES ON RISER | | | DIAGRAM AND BLDG RISER UP THROUGH THE | | | BLDG. | | | A) PLEASE SEE MAIN RISER NOW HAS BEEN | | | REVISED FOR BUS-STABS INTO FPL VAULT FOR | | | MAINS, HOWEVER PLEASE NOW SEE 1SMCN AND | | | 2SMCN WHICH SHOWS 4000A BUS-DUCT INTO | | | BOTH 3000A MAINS. (SEE KEY NOTE K-4) | | | THIS OK, HOWEVER PLEASE CORRECT OF | | | INDEED ONLY 3000A BUS IS GOING TO BE | | | USED. | | | B) PLEASE SEE 6.02, AND 6.03 FOR "KEY | | | NOTES". PLEASE SEE 6.02 HAS NOW BEEN | | | REVISED FOR 1SMCN RISER WHICH CONTAINS | | | REVISION "K-3", PLEASE SEE THIS WAS | | | CHANGED TO 4000A ON A 3000A MAIN, THIS | | | IS OK, HOWEVER PLEASE SEE 6.03 "KEY | | | NOTE" FOR SAME BUS DUCT RISER. PLEASE | | | SEE KEY NOTES REF K-7 FOR THE SAME RISER | | | WHICH IS SHOWN AS 3000A'S?? | | | PLEASE VERIFY SIZING OF BUST DUCT 3OR 4K | | | AND IF THERE ARE TWO DIFFERENT SIZES | | | BEING INSTALLED FOR THIS 3K MAIN.? | | | PLEASE SEEFEEDERS AS NOTED ARE FOR | | | 3000A'S. | | | | | | 75)NOTE: PLEASE SEE PREVIOUS NOTED A | | | REQUEST TO PROVIDE "FEEDER SCHEDULE" ON | | | RISER DIAGRAM AND TO NOTES TO CORRELATE | | | FEEDERS. | | | PLEASE SEE THE FOLLOWING: | | | | | | A) DPHREL, SHOWS F-9 ON RISER, F-10 ON | | | PANEL SCHEDULE AND F-10 ON SHE. REDLINED | | | LOCATION. | | | | | | B)DPHRE, SHOWS F-11 ON RISER, F-13 ON | | | PANEL SCHEDULE. REDLINED LOCATION. | | | | | | C)DPHRN, SHOWS F-4 ON RISER, F-5 ON SHN, | | | REDLINED LOCATION. PLEASE NOTE F-4 IS | | | FOR 2500A'S? | | | | | | D)HRHN, SHOWS F-15 ON RISER, F-19 ON | | | SHN, REDLINED LOCATION. | | | | | | E)HGME, SHOWS BLANK ON RISER, SHOWS F-12 | | | ON PANEL SCHEDULE DPHE. | | | | | | F)H5ME, SHOWS F-18 ON RISER, SHOWS F-20 | | | ON DPHE, REDLINED LOCATION. | | | | | | G)FIRE PUMP FEEDERS, F-10 INDICATE AN | | | "EQUIPMENT GROUNDING CONDUCTOR" FROM | | | FPL. PLEASE SEE 250.6 AND EQUIPMENT | | | GROUNDING CONDUCTOR IS ONLY INSTALLED | | | AFTER THE FIRST MEANS OF DISC. | | | (IT IS NOTED, FEEDERS NOT TO HAVE EQP | | | GRND). | | | PLEASE SEE FEEDERS LISTED AS K-24 WHICH | | | INDICATES 6-SETS OF 3-3/0'S AND 3/0 GRND | | | FOR FEEDERS TO FIRE PUMP FROM FIRE PUMP | | | CONTROLLER?? PLEASE VERIFY THE SIZES AND | | | NUMBER OF PARALLEL RUNS. | | | | | | H)SHN AND SHE ON RISER DIAGRAM INDICATES | | | A "BUS-STAB" INOT FPL VAULT, HOWEVER, | | | PANEL SCHEDULES FOR EACH OF THESE ON | | | 7.12 INDICATES "FEEDERS" AS F-3 AND F-6. | | | PLEASE CORRELATE, LOCATION REDLINED. | | | | | | 76)NOTE: PLEASE SEE SPECS FOR ATS NOT | | | SUBMITTED TO VERIFY MEANS OF DISCONNECT, | | | MANUAL, LOCATED ON OUTSIDE OF EQUIPMENT | | | ETC. | | | PLEASE SEE DPHE WILL BE REQUIRED TO HAVE | | | A MAIN CIRCUIT BREAKER FOR SERVICE | | | DISCONNECT FROM FPL AND GENERATOR. | | | THIS WAS REDLINED ON SETS FROM PREVIOUS | | | REVIEW, BUT UNABLE TO VERIFY MEANS OF | | | DISCONNECT FROM OTHER REVIEWS DUE TO NO | | | SPECS ETC SUBMITTED FOR ATS. | | | NO OCP COULD BE LOCATED FOR SEC'S COMING | | | INOT BLDG FROM FPL ON THIS. | | | 230.70,230.76,230.79,230.72,240.4. | | | | | | 77)NOTE: PLEASE KNOW, PLANS WERE | | | SUBMITTED ONLY FOR "PLAN REVIEW" BEFORE | | | JAN 1ST, 2005 AND NOT FOR PERMIT | | | APPLICATION.. PLEASE SEE NFPA-72 AND 101 | | | AND FIRE CODES CHANGE AT THAT TIME. | | | PLEASE SEE NFPA 101 REFERENCES A 1999 | | | EDITION. EVEN IF UNDER THE OLD CODE, | | | THIS WOULD BE 2000 EDITION OF 101, | | | HOWEVER PERMIT APPLICATIONS AFTER JAN | | | 1ST , WOULD PLACE THIS PROJECT UNDER THE | | | 2002 NFPA-72 AND 2003 NFPA-101. | | | | | | 78)NOTE: PLEASE SEE CHANGES TO PREVIOUS | | | NOTES FOR WATER HEATERS SHOWING OCP AT | | | 50A'S FOR A 4.5KW UNIT. PLEASE SEEUNIT | | | "N" WHICH NOW SHOWS SECOND WATER HEATER | | | AS A "BLANK" FOR OCP ETC. | | | PLEASE SEE LOAD CALCULATIONS AND PLANS | | | STILL INDICATE TWO UNITS. | | | PLEASE ADJUST AND CORRELATE. | | | | | | 79)NOTE: PLEASE SEE PANEL SCHEDULE FOR | | | UNIT D-2 COULD NOT BE LOCATED. | | | PLEASE CLARIFY IF THIS IS A DIFFERENT | | | PANEL. UNITS "D" AND D-1 ARE SUBMITTED. | | | | | | 80)NOTE: PLEASE SEELAUNDRY RMS IN SOME | | | UNITS INDICATE THE CIRCUIT PROVIDED FOR | | | WASHER ALSO FEEDING THE ADDITIONAL GFI | | | IN THE SAME RM? PLEASE SEE LOADING FOR | | | CIRCUITING AS A DEDICATED CIRUIT AND NO | | | OTHER RECEPTS ON THAT CIRCUIT SHOULD BE | | | VERIFIED. | | | LOAD FOR WASHER UNIT CAN NOT BE | | | VERIFIED. | | | PLEASE SEE 210.11C2 | | | | | | 81)NOTE: PLEASE SEENFPA-101 7-9 UNDER | | | THE 2003. WHICH WOULD REQUIRE MUTIPLE | | | CIRCUITS FEEDING EM LTS IN STAIR TOWERS. | | | PLEASE KNOW THE AHJ/ FIRE MARSHAL'S | | | OFFICE HAS DETERMIND EITHER EVERY OTHER | | | EM LT TO ALTERNATE CIRUITS OR A BATTERY | | | BACK UP FIXTURE AT EVERY OTHER LEVEL | | | WOULD BE REQUIRED FOR EGRESS IN STAIR | | | TOWER. PLEASE KNOW, IF BLDG IS UNDER | | | GENERATOR/ EM POWER AND A TRIPPING OF A | | | SINGLE BRKR , EITHER BRANCH CIRCUIT OR | | | MAIN, THIS WOULD PLACE STAIR TOWER(S) IN | | | TOTAL DARKNESS. TO ALLEAVIATE ANY OF | | | ALTERNATING CIRCUITS, OR TRIPPING OF ANY | | | OVERCURRENT PROTECTION DEVICE, A BATTERY | | | BACK-UP TYPE OF FIXTURE WOULD BE | | | REQUIRED TO PROVIDE A MIN OF .1 FT | | | CANDLE AS LISTED UNDER 7.9.2.1, | | | 7.9.2.2, 7.8.1.2. | | | THIS COMMENT CAN BE SET UP AS A | | | "PROVISO"TO REVISE BEFORE ROUGH OR CAN | | | BE ADDRESSED AT THIS TIME. PLEASE CALL | | | TO GO OVER. | | | | | | 82)NOTE: PLEASE SEE ATTACHED COPY OF FS | | | 553.80(2)(B) IS GIVEN ASNOTICE ONLY. | | | | | | PLEASE BE SURE TO SEE ANY COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE BE SURE TO REMOVED ALL OLD/ | | | VOIDED SHEETS AND ONLY INSERT NEW | | | REVISED SHEETS INTO TWO COMPLETE SETS | | | FOR REVIEW AND STAMPING. | | | ONE COMPLETE SET OF OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | | | | PLEASE SUBMIT ALL OF THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS, PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | PLEASE SEE ANY COMMENTS FROM O | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 2005-09-06 00:00:00 | PLANS WILL GO INTO A "F" STATUS. | | | | | | PLAN REVIEW NOTES TO FOLLOW, PLAN REVIEW | | | AND NOTES IN PROGRESS. | | 2005-09-04 00:00:00 | ELECTRICAL PLANSONLY ARE AT DP'S DESK | | | FOR REVIEW. | | | REVIEW TO CONTINUE,,,, STOPPED FOR 9/4 | | 2005-08-24 00:00:00 | REVISION TO THE TEMPORARY POWERJL |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-08 |
Time |
09:03 |
Rev Time |
22.00 |
| Received By |
dpalmer |
Date |
2005-04-08 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2005-04-08 00:00:00 | ************ UNSAT 2ND REVIEW ********* | | | | | | PLEASE SEE MANY NOTES FROM PREVIOUS | | | REVIEW STILL NEED TO BE ADDRESSED. | | | | | | PLEASE ALSO SEE NEW NOTES DUE TO PLANS | | | CONTAINING MORE INFORMATION THAN | | | SUBMITTED ON PREVIOUS REVIEW. | | | | | | *************************************** | | | PLEASE SEE FIRST PART OF REVIEW IS A | | | DIRECT OVERVIEW OF PREVIOUS NOTES, NEW | | | NOTES WILL BE FOLLOWING. | | | *************************************** | | | | | | 1)NOTE: NOTE #1, OK, HOWEVER PLEASE SEE | | | NOTE #19 IN THIS AND PREVIOUS REVIEW. | | | | | | 2)NOTE: NOTE #2 NO, PLEASE SEE REQUIRED | | | WIND LOADING INFORMATION IS NOT NOTED ON | | | ELECTRICAL PLANS FOR POLES. IF THIS | | | INFORMATION IS PROVIDED ON ADDITIONAL | | | SHEETS FOR BLDG REVIEW, THIS IS FINE AND | | | REQUIRED, HOWEVER THIS INFORMATION WILL | | | NEED TO BE ELECTRICAL SHEET FOR | | | ELECTRICAL CONTRACTOR ETC. | | | WINB LOADING NOTE(S) SHOULD REFERENCE | | | FBC 140 MPH. | | | | | | 3)NOTE: NOTE #3 NO, PLEASE SEE SHEET | | | ATTACHED WHICH IS A PRINT OUT FROM | | | DBPR'S WEBSITE. PLEASE SEE LICENSE | | | INFORMATION PROVIDED ON TITLE BLOCKS FOR | | | ARCHITECTUAL FIRM DOES NOT APPEAR TO BE | | | ACCURATE. PLEASE SEE ATTACHED SHEET | | | WHICH SHOWS BC ARCHITECTS INC. WITH AN | | | ARCHITECTUAL BUS/FIRM LICENSE NUMBER OF | | | AA#0003360. PLEASE SEE TITLE BLOCKS FOR | | | ALL SHEETS AND FOR ALL TRADES APPEARS TO | | | INDICATE THIS FIRM LICENSE NUMBER AS | | | 0008129???. | | | PLEASE SEE FAC 61G1-16.004, FS 481.219. | | | PLEASE SEE THIS IS REQUIRED ON ALL | | | SHEETS AND FOR ALL TRADES WHEATHER OR | | | NOT COMMENT IS MADE BY OTHER | | | REVIEWER(S). | | | PLEASE SEE ENGINEERING FIRM'S TITLE | | | BLOCK HAS BEEN CORRECTED. | | | | | | 4)NOTE: NOTE #4, OK. NOTE ADDED FOR "NO | | | SWIMMING" AFTER DUSK. | | | | | | 5)NOTE: NOTE #5 OK. | | | | | | 6)NOTE: NOTE #6 OK, FIRE RATING VERIFIED | | | FOR DIRECT ACCESS TO MAIN ELECTRICAL | | | ROOM. HOWEVER, NOTES FOR SIGNAGE, MAPS | | | AND/OR DIRECTORY COULD NOT BE LOCATED ON | | | PLANS. | | | 230.2E 700.8A,701.9,702.8 ETC. | | | A SIGN SHALL BE PLACED AT THE SERVICE | | | ENTRANCE EQUIPMENT INDICATING TYPE AND | | | LOCATION OF ON-SITE EMERGENCY POWER | | | SOURCES. | | | PLEASE SEE ALL SIGNAGE REQUIRED TO BE 1" | | | MIN WITH CONTRASTING BACKGROUND. | | | SIGNAGE/MAPPINGALSO REQUIRED AT FIRE | | | COMMAND RM AND AT ACCESS DOOR CLOSEST TO | | | MAIN ELECTRICAL ROOM. | | | SIGNAGE FOR ALL ELECTRICAL ROOMS. | | | PLEASE ALSO SEE 110.16 | | | 110.16 FLASH PROTECTION. | | | SWITCHBOARDS, PANELBOARDS, INDUSTRIAL | | | CONTROL PANELS, AND MOTOR CONTROL | | | CENTERS THAT ARE IN OTHER THAN DWELLING | | | OCCUPANCIES AND ARE LIKELY TO REQUIRE | | | EXAMINATION, ADJUSTMENT, SERVICING, OR | | | MAINTENANCE WHILE ENERGIZED SHALL BE | | | FIELD MARKED TO WARN QUALIFIED PERSONS | | | OF POTENTIAL ELECTRIC ARC FLASH HAZARDS. | | | THE MARKING SHALL BE LOCATED SO AS TO BE | | | CLEARLY VISIBLE TO QUALIFIED PERSONS | | | BEFORE EXAMINATION, ADJUSTMENT, | | | SERVICING, OR MAINTENANCE OF THE | | | EQUIPMENT. | | | SEE FIRE COMMENTS FOR "KNOW BOX" | | | LOCATIONS. | | | | | | 7)NOTE: NOTE #7,OK HOWEVER PLEASE SEE | | | SHEETS E 2.11,2.12, MANY ELECTRICAL | | | DEVICES/FIXTURES APPEAR TO BE SHOWN WITH | | | OUT CIRCUITS. ARE THESE MISPRINTED AND | | | REPEATED ON OTHER SHEETS. | | | | | | 8)NOTE: NOTE #8 NO, PLEASE SEE 620.23.24 | | | ETC. | | | PLEASE SEE ELEVATOR EQUIPMENT RMS. | | | A SEPARATE BRANCH CIRCUIT SHALL SUPPLY | | | THE MACHINE ROOM OR CONTROL | | | ROOM/MACHINERY SPACE OR CONTROL SPACE | | | LIGHTING AND RECEPTACLE(S). | | | A SEPARATE BRANCH CIRCUIT SHALL SUPPLY | | | THE HOISTWAY PIT LIGHTING AND | | | RECEPTACLE(S). | | | | | | 9)NOTE: NOTE #9 NO, PLEASE SEE RECETPS | | | WERE ADDED HOWEVER, ID SCALE IS CLOSE AS | | | INDICATED, SOME RECEPTS APPEAR TO BE | | | WITHIN THE RESTRICATED 10' AREA. | | | PLEASE SEE 620.22A3 | | | PLEASE ALSO SEE NEW NOTE FOR LIGHTING | | | AROUND POOLS. | | | | | | 10)NOTE: NOTE #10 OK, REFERENCES | | | CHANGED. | | | | | | 11)NOTE: NOTE #11 OK, HOWEVER PLEASE SEE | | | NEW NOTES FOR BATH/TUB/JACUZZI FIX. | | | | | | 12)NOTE: NOTE #12 NO, PLEASE SEE UNITS | | | ARE STILL SHOWN WITHOUT ACCESS TO | | | GARAGE. | | | AS PER CONVERSATION WITH MR. RAPL BAEZA, | | | NO ACCESS WAS GOING TO BE INSTALLED FROM | | | GARAGE IN DESIGN. | | | PLEASE SEE BLDG REVIEW COMMENTS BY MR. | | | ROBERT BROWN, ACCESSIBILTY FROM GARAGE | | | MAY BE REQUIRED. | | | IF SO, PLEASE SEE 210.70 AND LS101 5-8. | | | | | | 13)NOTE: NOTE #13 NO, PLEASE SEE GRADE | | | LEVEL ACCESS REQUIRES MEANS OF EGRESS | | | LIGHTING/CONTROL. PLEASE ALSO SEE | | | EXCEPTIONS. | | | | | | 14)NOTE: NOTE #14, OK, HOWEVER PLEASE | | | SEE NOTE #7. | | | | | | 15)NOTE: NOTE #15 OK FOR SD'S HOWEVER | | | PLEASE SEE NEW COMMENTS FOR CIRCUITING | | | AND ARC FAULT PROTECTION. | | | | | | 16)NOTE: NOTE #16 OK. | | | | | | 17)NOTE: NOTE #17 NO, PLEASE SEE 210.52D | | | FOR GFI REQUIRED WITHIN 3' OF SINK/LAV | | | EDGE. | | | PLEASE SEE PLANS AHVE SOME REDLINED AT | | | LOCATION(S) MISSING. | | | | | | 18)NOTE: NOTE #18 NO, PLEASE SEE | | | ELECTRICLA PANELS NOT PERMITTED ON | | | CLOSETS. PLEASE SEE 110.26,408.7,240.24 | | | ETC. | | | PLEASE SEE 240.24OVER CURRENT | | | PROTECTION IS NOT TO BE LOCATED IN THE | | | VICINITY OF EASILY IGNITIBLE MATERIAL. , | | | SUCH AS IN CLOTHES CLOSETS. | | | PLEASE ALSO SEE NEW NOTES BAOUT CATV AND | | | TELEPHONE CABINETS. | | | | | | 19)NOTE: NOTE #19 NO, PLEASE SEE SOME | | | UNITS STILL SHOW A COUPLE OF ELECTRICAL | | | PANELS IN "LT GRAY". THIS APPEARS TO BE | | | MISPRINTS . PLEASE SEE UNIT HD FOR ONE. | | | | | | 20)NOTE: NOTE #20 OK, HOWEVER PLEASE SEE | | | NOTE #28 FOR 110.26 | | | | | | 21)NOTE: NOTE #21 OK. | | | | | | 22)NOTE: NOTE #22 NO, PLEASE SEE MANY | | | UNITS HAVE BEEN REDLINED FOR AREAS IN | | | QUESTION. PLEASE SEE 210.52C1-5 FOR | | | REQUIRED LOCATIONS OF GFI RECEPTS ALONG | | | KITCHEN COUNTERSPACES, INCLUDING | | | PENINSULARS AND " SEPARATE SPACES". | | | 210.52C2,4 | | | | | | 23)NOTE: NOTE #23 NO, CPULD NOT LOCATE | | | NOTE REQUESTED FOR SD PLACEMENT ON | | | PLANS. | | | PLEASE CLARIFY WHERE THIS IS. | | | PLEASE SEE NFPA-72 8-1.4.2 FOR THESE | | | LOCATIONS. | | | | | | 24)NOTE: NOTE #24 NO, PLEASE SEE GFI | | | RECEPTS WERE ADDED TOLOWER TERRACE | | | LEVELS BUT NONE TO UPPER TERRACES. | | | PLEASE SEE UPPER TERRACE ON ELECTRICAL | | | PLANS APPEAR TO BE SHOWN MUCH LARGER | | | THAN TERRACES SHOWN ON ARCH SHEETS. | | | THIS IS ONLY A NOTE AND LIGHTING OR GFI | | | RECEPTS ARE NOT REQUIRED ON THE SMALLER | | | OR LARGE TERRACES, HOWEVER OF THEY ARE | | | GOING TO BE INSTALLED, PLEASE SHOW ON | | | PLANS AT THIS TIME OR PLANS WILL BE | | | REQUIRED TO BE REVISED AT A LATER DATE. | | | | | | 25)NOTE: NOTE #25 YES/NO , GFI BRKR | | | NOTED AT PANEL SCHEDULES,HOWEVER A | | | POWER/RECEPT COULD NOT BE LOCATED ON | | | PLANS AT THESE UNITS. | | | PLEASE SHOW. | | | | | | 26)NOTE: NOTE #26NO. PLEASE SEE NO | | | INFORMATION EXCEPT THAT FIRE PUMP IS | | | GOING TO BE 250 HP. PLEASE SEE KEYNOTES | | | K-23 DOES NOT PROVIDE ENOUGH | | | INFORMATION. | | | PLEASE ALSO SEE NEW NOTES PERTAINING TO | | | FIRE PUMP/CONTROLLER ETC. | | | PLEASE SEE PREVIOUS REQUEST WAS TO HAVE | | | ALL MANUFACTURE SPEC SHEETS SUBMITTED | | | FOR FIRE PUMP, FIRE PUMP CONTROLLER, ETC | | | NONE COULD BE LOCATED IN SPECS, | | | SUBMITTALS??? | | | SEE NEW NOTES: | | | | | | 27)NOTE: NOTE #27 NO, PLEASE SEE ABOVE | | | NOTE. PLEASE SE NO SPECS FOR GENERATOR, | | | SUB BASE FUEL TANK ATS WERE SUBMITTED. | | | 215.5 | | | PLEASE SEE NEW NOTES FOLLOWING. | | | | | | 28)NOTE: NOTE #28 NO, PLEASE SEE NOTE | | | WAS ADDED TO ONE SHEET ONLY. PLEASE SEE | | | SPECIFICS NOTES FOR 110.26 WILL BE | | | REQUIRED ON ALL SHEETS SHOWING | | | ELECTRICAL ROOMS AND ELECTRICAL CLOSETS. | | | | | | PLEASE SEE THIS NOTE SHOULD REFLECT "ALL | | | ELECTRICAL ROOMSAND ELECTRICAL CLOSETS | | | SHALL MEETS ALL THE REQUIREMENTS OF | | | 110.26 AND ALL OTHER REQUIREMENT OF | | | 2002 NEC" PLEASE SEE WE ARE HAVING MANY | | | ISSUES WHERE WIDTHS ARE BEING MET, | | | HOWEVER HEIGHT REQUIREMENTS ARE NOT. | | | SEE NEW NOTES ALSO. | | | | | | 29)NOTE: NOTE #29 OK. | | | | | | 30)NOTE: NOTE #30 NO, PLEASE SEE MORE | | | THAN ONE "K" NOTE LOCATED ON KEYNOTES DO | | | NOT CORRELATE OR SHOWN "BLANK" OR NOTED | | | AS NOT BEING USED, HOWEVER PLANS DO NOT | | | MATCH THESE. | | | PLEASE SEE K26,K35, ETC. | | | PLEASE SEE NEW NOTES FOR F AND K NOTES | | | WHICH DO NOT CORRELATE WITH PLANS. | | | PLEASE SEE NEW NOTES: | | | | | | 31)NOTE: NO, PLEASE SEE RESPONSE LTR | | | MENTIONS "WILL COMPLY" HOWEVER PLEASE | | | SEE NEW NOTES PERTAINING TO NOTES ON | | | PLANS AND SPECS. | | | | | | 32)NOTE: NOTE #32 OK, NOTE ADDED , GEN | | | WILL NOT BE SEPARATELY DEREVED. THIS | | | WILL BE VERIFIED ONCE MANUFACTURE SPECS | | | ARE SUBMITTED. | | | SEE NEW NOTES ALSO; | | | | | | 33)NOTE: NOTE #33 OK, HOWEVER PLEASE SEE | | | NEW NOTES PERTAINING TO FEEDER SIZES. | | | | | | 34)NOTE: NOTE #34 NO, PLEASE SEE RISER | | | DIAGRAM STILLDOES NOT INCLUDE A | | | REDUCED "KEYED NOTES" OR RECDUCED | | | "FEEDER SCHEDULE FOR REFERENCE WITHOUT | | | HAVING TO TURN BACK AND FORTH FROM RISER | | | DIAGRAM PAGE TO E-6.13. | | | 215.5. | | | PLEASE SEE NEW NOTES FOR250.30 | | | PLEASE SEE RISER INDICATES 3000A | | | BUS-STAB INTO FPL VAULT FEEDING 4000A | | | MAINS?? PLEASE CORRELATE. | | | PLEASE SEE RISER SHOWS 3000A MAIN | | | FEEDING 4000A BUS-DUCT THEN CHANGES BACK | | | TO 3000A BUS DUCT?? | | | | | | 35)NOTE: NOTE #35 OK, HOWEVER SEE NEW | | | NOTES FOR CORRELATIONOF METER CENTERS | | | AND LOAD CALCULATIONS/ EQUIPMENT. | | | | | | 36)NOTE: NOTE # 36 OK, OVEN ADDED, | | | RANGES CHANGED. | | | | | | 37)NOTE: NOTE #37 PLEASE SEE "FEEDER | | | HOME RUN SCHEDULE" WAS ADDED TO MOST | | | SHEETS CONTAINING PANEL SCHEDULE, BUT | | | SEE PLANS FOR MISSING DETAIL. PLEASE | | | ALSO SEE NEW NOTES PERTAINING TO PANELS | | | SIZES. | | | | | | 38)NOTE: NOTE #38 NO, PLEASE SEE | | | PANELS STILL SHOWN AS 200A WITH 225A OCP | | | FEEDING PANEL(S). PLEASE SEE THE 250A | | | OCP WAS REMOVED. | | | | | | 39)NOTE: NOTE #39 NO, PLEASE SEE WATER | | | HEATERS SHOWN WITH 2P50A OCP FOR 4500VA | | | UNITS ON #10 AWG. | | | PLEASE ALSO SEE 6KW WITH 30A OCP. | | | PLEASE SEE MIN OCP IS 125% AND MAX OCP | | | IS 150%. | | | PLEASE SEE 422.13,422.11,240.4, 310.16 | | | ETC. | | | | | | *************************************** | | | NEW NOTES FOR REVIEW. | | | | | | 40)NOTE: PLEASE SEE MIN REQUIREMENTS FOR | | | ELECTRICAL LIGHT FIXTURES FORM SWIMMING | | | POOL. IF SCALE IS USED AS INDICATED ON | | | PLANS, SOME FIXTURES SHOWN AS CLOSE AS | | | 3' FROM WATER'S EDGE. | | | PLEASE SEE 680.22 AND PREVIOUS NOTES FOR | | | RECEPT PLACEMENT. | | | | | | 41)NOTE: PLEASE CLARIFY MANY | | | ELECTRICAL/GENERATOR RMS CONTAIN EM LT | | | FIXTURES ON EM CIRCUIT BUT YET THESE ARE | | | ALSO BATTERY BACK UP? PLEASE SEE THEN | | | ARE MANY ELECTRICAL RMS WHICH DO NOT | | | CONTAIN BATTERY BACK UP? | | | THIS IS ONLY A NOTE. | | | | | | 42)NOTE: PLEASE SEE MANY UNITS, 5,6,8 | | | ETC FOR REQUIRED RECEPTS PER 210.52. | | | PLEASE SEE 2' OF WALL SPACES INT | | | KITCHENS, BEDROOMS(EVEN IF BEHIND | | | DOORS). | | | PLEASE SEE MANY REDLINED AT LOCATIONS ON | | | PLANS. | | | | | | 43)NOTE: PLEASE SEE MOST DRYER LOCATIONS | | | INDICATE A MANUAL SWITCH FOR DRYER | | | "BOOST FAN" YET MANY DO NOT CONTAIN THIS | | | SAME SW? | | | HOWEVER, PLEASE SEE NOTES LOCATED ON | | | EACH SHEET WHICH MENTIONS THAT THESE | | | WILL BE AUTOMATICALLY INTERCONNECTED? | | | PLEASE SEE MECHANICAL NOTES FOR THIS | | | SAME ITEM. IT APPEARS INTERCONNECTING | | | ANY DEVICES IN THESE FANS/ DRYERS MAY | | | VOIDED WARRANTIES AND/OR VOIDED LISTINGS | | | FROM MANUFACTURE. | | | | | | 44)NOTE: PLEASE SEE AS MENTIONED ON | | | ORIGINAL NOTES, ARC FAULT PROTECTION | | | REQUIRED PER 2002 NEC 210.12, HOWEVER | | | THERE ARE NUMEROUS AREAS IN MOST UNITS | | | IN WHICH CIRCUITING FOR LIGHTING ETC | | | DOES NOT HAVE THE "* " ON THE CIRCUIT | | | #'S ON PANEL SCHEDULE FOR THE | | | PROTECTION. | | | PLEASE SEE ALL "OUTLETS" INCLUDING SD'S, | | | LTS, FANS AND RECEPTS REQUIRED THIS. | | | PLEASE SEE MANY OF THESE CIRCUIT #'S | | | HAVE BEEN REDLINED ON PLANS, BUT NOT | | | ALL. | | | | | | 45)NOTE: PLEASE SEE SOME UNITS ARE | | | SHOWING FIXTURES IN SOME UTILITY/CLOTHES | | | CLOSETS WHICH DO NOT APPEAR TO MEET | | | 410.8 FOR MIN CLEARENCE. PLEASE VERIFY. | | | | | | 46)NOTE:PLEASE VERIFY FIXTURE | | | CLEARENCE OVER TUBS/HYDRO ETC. AN | | | ELEVATION IS NOT SHOWN FOR MIN CLEARENCE | | | AND WE HAVE ENCOUNTERED MANY WHICH FALL | | | BELOW MIN CLEARENCE EVEN FOR A RECESSED | | | LT WITH AN ENCLOSED COVER. | | | THIS IS ONLY A NOTE: | | | | | | 47)NOTE: SEE PREVIOUS/UPPER NOTES, UNIT | | | # H-7 FOR MISSING GFI W/IN 3' OF SINK. | | | 210.52 | | | | | | 48)NOTE: PLEASE SEE UNIT A-1 WHICH | | | INDICATES A THIRD SMALL APPL CIRCUIT , | | | HOWEVER THIS COULD NOT BE LOCATED ON | | | PLANS? | | | | | | 49)NOTE: PLEASE SEE UNIT V-1 THIS | | | APPEARS TO HAVE "ALL" DEVICES SHIFTED | | | AND REVIEW FOR PLACEMENT FOR THESE | | | DEVICES CAN NOT BE DONE AT THIS TIME. | | | | | | 49)NOTE: PLEASE SEE MANY CLOTHES CLOSETS | | | CONTAINING COMBUSTIBLES ARE SHOWN WITH | | | CATV AND TELEPHONE CABINETS. PLEASE SEE | | | IF THESE UNITS WILL REQUIRE ANY "LV | | | PLUG-IN" TYOE TRANSFORMERS THEN THESE | | | RECEPTS WHICH ARE NOT SHOWN AT THIS TIME | | | WOULD ONLY BE ALLOWED DIRECTLY OVER | | | DOORS. | | | PLEASE SEE PLANS DO NOT INDICATE ANY LV | | | ALARM PANELS AT THIS TIME AND SAME WOULD | | | BE REQUIED IF LOCATED IN A CLOTHES | | | CLOSET. THIS IS ONLY A NOTE: | | | | | | 50)NOTE: PLEASE SEE 2002 210.8B3 FOR | | | KITCHENS IN OTHER THAN DWELLING UNITS. | | | THIS WOULD BE FOR "HOUSE KITCHEN". | | | | | | 51)NOTE: PLEASE SEE SOME UNITS WHICH DO | | | NOT SHOW DEVICES, MENTIONS TO SEE OTHER | | | SIMILAR UNITS, HOWEVER PLEASE SSE SOME | | | ARE MSSING OR DO NOT CORRELATE. | | | PLEASE SEE "B" UNIT, 3.23, "D-1"AND | | | "D" UNIT ON 3.25. | | | | | | 52)NOTE: PLEASE SEE FIRE COMMAND ROOM | | | LAYOUT DO NOT NOT CORRLETATE FOR LAYOUT | | | AND EQUIPMENT IN ROOMS AS NOTED. | | | 8.05,4.01 | | | | | | 53)NOTE: PLEASE SEE RISER AND PLANS DO | | | NOT INDICATE ANY INFORMATION FOR | | | DISC/BRKRS/OCP LOCATED ON GENERATOR FOR | | | FEED/FEEDS TO GUTTER AND ON TO | | | DISCONNECTS LOCATE DIN GEN RM. | | | 215.5 COMPLIANCE CAN NOT BE VERIFIED AT | | | THIS TIME. | | | | | | 54)NOTE: PLEASE SEE GROUND FUALT | | | PROTECTION FOR SHN CAN NOT BE VERIFIED. | | | CAN NOT LOCATE ON PLANS, RISER OR PANEL | | | DETAIL/SCHEDULE. | | | PLEASE SEE 240, GROUND-FAULT PROTECTION | | | OF EQUIPMENT SHALL BE PROVIDED IN | | | ACCORDANCE WITH THE PROVISIONS OF 230.95 | | | FOR SOLIDLY GROUNDED WYE ELECTRICAL | | | SYSTEMS OF MORE THAN 150 VOLTS TO GROUND | | | BUT NOT EXCEEDING 600 VOLTS | | | PHASE-TO-PHASE FOR EACH INDIVIDUAL | | | DEVICE USED AS A BUILDING OR STRUCTURE | | | MAIN DISCONNECTING MEANS RATED 1000 | | | AMPERES OR MORE. | | | | | | 55)NOTE: PLEASE SEE K-27 MENTIONS TO SEE | | | TRANSFORMER GROUNDING DETAIL, HOWEVER | | | THIS COULD NOT BE LCOATED ON PLANS.? | | | PLEASE SHOW EITHER A TYPICAL DETAIL OR | | | SHOW EACH. 250.30,215.5 | | | | | | 56)NOTE:PLEASE SEE KEYNOTE K-31, | | | MENTIONS PER NAMEPLATE, HOWEVER | | | DISCONNETC SIZES ETC, ARE REQUIRED AT | | | THIS TIME A S MIN. 215.5 | | | PLEASE ALSO SEE K-NOTE FOR ELEVATOR | | | CONTROLLER. | | | | | | 57)NOTE: PLEASE SEE GUTTER SHOWN AT | | | GENERATOR ROOM REFERENCES TO MEET 366. | | | PLEASE SEE FBC 104.2.1, CODES FOR | | | SPECIFIC DESIGNS ARE NOT TO BE REFERNECD | | | IN WHOLE OR IN-PART. PLEASE SHOWN MIN | | | GUTTER SIZE. | | | PLEASE ALSO SEE NO CONDUCTORS SIZES ARE | | | SHOWN, NO CONDUIT SIZES AND NO OCP | | | (PREVIOUS NOTE) ARE SHOWN TO VERIFY | | | COMPLIANCE. 310.16,215.5 240.4 ETC. | | | | | | 58)NOTE: PLEASE SEE K-24, K25, NO SIZE | | | FOR CONDUIT, FEEDER ETC FROM FIRE PUMP | | | CONTROLLER TO FIRE PUMP. PLEASE SEE | | | PLANS INDUCATE A "MAGNETIC TYPE" BRKR, | | | HOWEVER NO SIZE IS GIVEN? | | | 215.5,310.16 ETC. | | | PLEASE SEE PREVIOUS NOTES. | | | | | | 59)NOTE: PLEASE SEE "SPEC BOOK", 16465 | | | 2.2C WHICH MENTIONS ALUM BUS-DUCT. | | | PLEASE SEE PREVIOUS NOTES IN REFERENCE | | | TO EQUIPMENT GROUNDING METHOD OF | | | BUS-DUCT. DOES THIS BUS-DUCT CONTAIN A | | | SEPARATE ALUM BUS FOR GROUNDING? OR IS | | | THE EQUIPMENT GROUNDING THAT IS GOING TO | | | BE USED "PART" OF THE BUS-DUCT. | | | PLEASE ALSO PLACE NOTE ON PLANS FOR | | | REQUIRED CURBS FOR FLOOR PENATRATIONS. | | | PER 368.6BFLOOR PENETRATIONS SHALL | | | COMPLY WITH (1) AND (2): | | | BUSWAYS SHALL BE PERMITTED TO BE | | | EXTENDED VERTICALLY THROUGH DRY FLOORS | | | IF TOTALLY ENCLOSED (UNVENTILATED) WHERE | | | PASSING THROUGH AND FOR A MINIMUM | | | DISTANCE OF 1.8 M (6 FT) ABOVE THE FLOOR | | | TO PROVIDE ADEQUATE PROTECTION FROM | | | PHYSICAL DAMAGE. | | | IN OTHER THAN INDUSTRIAL ESTABLISHMENTS, | | | WHERE A VERTICAL RISER PENETRATES TWO OR | | | MORE DRY FLOORS, A MINIMUM 100 MM (4 | | | IN.) HIGH CURB SHALL BE INSTALLED AROUND | | | ALL FLOOR OPENINGS FOR RISER BUSWAYS TO | | | PREVENT LIQUIDS FROM ENTERING THE | | | OPENING. THE CURB SHALL BE INSTALLED | | | WITHIN 300 MM (12 IN.) OF THE FLOOR | | | OPENING. ELECTRICAL EQUIPMENT SHALL BE | | | LOCATED SO THAT IT WILL NOT BE DAMAGED | | | BY LIQUIDS THAT ARE RETAINED BY THE | | | CURB. | | | | | | 60)NOTE: PLEASE SEE "SPEC BOOK" 16120 | | | 2.3A5, PLEASE SEE COLOR CODING FOR | | | 277/480V SHALL BE BROWN, PURPLE, YELLOW. | | | 215.8 LOCAL AMENDMENTS. | | | | | | 61)NOTE: THIS IS ONLY A NOTE: PLEASE SEE | | | LOAD ON HGMN SHOWN AT 197A'S WITH 200A | | | BRKR FEEDING THIS. | | | | | | 62)NOTE: PLEASE SEE PLANS INDICATE "SHN" | | | FEEDING"H5MN" WITH 125A BRKR, YET H5MN | | | IS ONLY 100A'S.? | | | PLEASE ALSO SEE RISER , APPEARS TO SHOW | | | THIS AS "H5MH"? | | | | | | 63)NOTE: PLEASE SEE DPHRN 150A BRKR TO | | | 100A FEEDERS (F-19). | | | | | | 64)NOTE: PLEASE CORRELATE LOADS SHOWN ON | | | "HRHN" AND TWO OTHER LOADS SHOWN ON | | | "LRHN" | | | 215.5 | | | | | | 65)NOTE: PLEASE CORRELATE F-7, F-9 TO | | | DPHE ON PANEL AND RISER. | | | PLEASE SEE NO FEEDER SHOWN K? FOR HGMN | | | ON RISER. | | | | | | 66)NOTE: PLEASE CORRELATE "P-4" METER | | | CENTER LOAD ANALYSIS AND NOT SHOWN ON | | | ANY "SWITCH BOARD"? | | | PLEASE ALSO SEE 2-W NEEDS TO CORRELATE | | | WITH "SMCW". PLEASE ALSO SEE "MW" NOT | | | SHOWN?? | | | 215.5 | | | | | | 67)NOTE: PLEASE SEE "FUEL NOTE" MENTIONS | | | 277 GALS OF FUEL PER HR??? RUNNING A MIN | | | OF 2.? HRS. | | | PLEASE CLARIFY THIS NOTE: PLEASE SEE | | | SIZING, CONSUMPTION OF GEN ETC CAN NOT | | | BE VERIFIED. PLEASE SEE PREVIOUS NOTES | | | PERTAINNG TO INFORMATION REQUIRED FOR | | | GENERATOR ETC. | | | | | | 68)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | AIC RATINGS SHOULD BE NOTED ON ALL | | | EQUIPMENT. | | | | | | 69)NOTE: PLEASE SEE ALL INFORMATION FOR | | | AS SHOWN ON PLANS FOR LIGHTNING | | | PROTECTION SYSTEMCAN BE INCLUDED UNDER | | | BASE BLDG'S ELECTRICAL PERMIT. HOWEVER | | | ANY CHANGES IN SYSTEM WOULD NEED | | | REVISION. THIS SYSTEM WILL BE THE | | | RESPONSIBILITY OF THE ELECTRICAL | | | CONTRACTOR. IF THIS WORK IS "SUBBED' | | | OUT, A SEPARATE PERMIT MUST BE PULLED BY | | | LIGHTNING PROTECTION CONTRACTOR. SINCE | | | THESE PLANS CONTAIN INFORMATION FOR | | | SYSTEM, SUB CONTRACTOR MAY REFERENCE | | | THESE PLANS AND A MIN $50 PERMIT FEE | | | WILL BE DUE. | | | | | | 70)NOTE: PLEASE ALSO SEEIF ALL | | | INFORMATION FOR FIRE PUMP, FIRE PUMP | | | CONTROLLER,GENERATOR, ATS, ETC IS NOT | | | SUBMITTED FOR REVIEW WITH BASE BLDG | | | PLANS, ALL OF THESE ITEMS WILL BE | | | REQUIRED TO BE UNDER SEPARATE PERMIT | | | ALONG WITH ALL FEES BASED ON VALUE OF | | | ALL OF THOSE ITEMS. | | | PLEASE SEE FIRE REVIEW COMMENTS. | | | | | | 71)NOTE: PLEASE SEE MANY OF THE ABOVE | | | ITEMS ARE REDLINED ON PLANS FOR AREAS OF | | | NOTES. NOT "ALL" ITEMS ARE REDLINED. | | | | | | 72)NOTE: PLEASE REMOVE ALL OLD/VOIDED | | | SHEETS FROM SETS AND ONLY INSERT NEW | | | REVISED SHEETS INTO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | PLEASE SEE "ONE" SET OF ALL OLD/VOIDED | | | REMOVED SHEETS SHOULD BE SUBMITTED FOR | | | REFERENCE ONLY. | | | | | | 73)NOTE: PLEASE KNOW, AS NOTED IN SOME | | | NOTES, DUE TO SOME INFORMATION MISSING | | | ON PLANS AND WITH PLANS, A COMPLETE | | | REVIEW FOR CODE COMPLIANCE CAN NOT BE | | | DONE AT THIS TIME. | | | PLEASE BE SURE TO INCLUDE ALL | | | INFORMATION AS REQUESTED/NEEDED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | DPALMER @WPB.ORG |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-01-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-06 |
Time |
13:43 |
Rev Time |
18.00 |
| Received By |
dpalmer |
Date |
2005-01-03 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2005-01-06 00:00:00 | *************** UNSAT ***************** | | | | | | PLAN REVIEW ONLY FOR "TWO CITY PLAZA" | | | PLANS NOT SUBMITTED FOR PERMIT AT THIS | | | TIME, ONLY IN FOR "PLAN REVIEW". | | | | | | | | | **************************************** | | | *************************************** | | | | | | PLEASE SEE THAT DUE TO PLANS NOT BEING | | | COMPLETE AT THIS TIME, A FULL REVIEW | | | FOR 2002 NEC CODE COMPLIANCE CAN NOT BE | | | DONE. | | | **************************************** | | | *************************************** | | | | | | THE FOLLOWING NOTES ARE ONLY BASED ON | | | WHAT INFORMATION IS AVAIBLAE AT THIS | | | TIME. | | | **************************************** | | | *************************************** | | | | | | 1)NOTE: PLEASE SEE SOME SHEETS HAVE THE | | | ELECTRICAL PRINTED WITH DARKEN LINES | | | AND MANY OF THE SHEETS ARE LT GRAY FOR | | | ELECTRICAL. PLEASE DARKEN FOR EASE OF | | | REVIEW PROCESS. | | | | | | 2)NOTE: PLEASE SUBMIT WIND-LOADING FOR | | | SITE/POLE LIGHTING AT THIS TIME. THIS | | | IS REQUIRED FOR REVIEW AT THIS TIME. | | | WIND LOADS 140MPH PER FBC. | | | | | | 3)NOTE: PLEASE SEE FAC 61G15-23.002, | | | 61G1-16.004 FOR MISSING INFORMATION | | | REQUIRED ON TITLE BLOCKS FOR BOTH | | | ENGIEERING FIRM AND ARCH FIRM. | | | FS 471.023,481.219 | | | PLEASE ALSO SEE PLANS ARE REQUIRED TO | | | BE SIGNED, DATED AND SEALED BY ENGINEER | | | WHEN SUBMITTING FOR PERMIT. | | | | | | 4)NOTE: PLEASE PROVIDE NOTE ON POOL | | | PLANS: POOL TO BE UNDER SEPARATE: | | | PLEASE PROVIDE NOTE FOR HOURS OF | | | SWIMMING. IF AFTER DUSK SWIMMING IS TO | | | TAKE PLACE AND COMPLETE PHOTOMETRICS | | | WILL NEED TO BE SUBMITTED FOR REVIEW | | | AND STAMPING BY THE PALM BEACH COUNTY | | | HEALT DEPT. AND WILL BE REQUIRED TO BE | | | IN THIS PLAN REVIEW. | | | | | | 5)NOTE: PLEASE SEE FPL VAULT ROOM IS | | | ALSO NOTED AS BEING ELECTRICAL ROOM FOR | | | GARAGE. PLEASE SEE FPL VAULT | | | REQUIREMENTS SET FORTH BY FPL AND | | | PERMITTING NO OTHER ELECTRICAL | | | EQUIPMENT | | | IN THEIR VAULT. | | | | | | 6)NOTE: ELECTRICAL PLANS DO NOT CLEARLY | | | SHOW A DIRECT FIRE RATE ACCESS TO MAIN | | | ELECTRICAL RM WHICH APPEARS TO BE | | | LOCATED ABOVE GRADE LEVEL. PLEASE | | | PROVIDE INFORMATION/DIRECTIONAL FOR | | | ACCESS FOR FIRE DEPT PERSONNEL FOR | | | SHUTTING DOWN OF MAINS. PLEASE ALSO | | | PROVIDE NOTE ON PLANS FOR REQUIRED | | | "KNOX BOX" FOR FIRE DEPT. PLEASE SEE | | | FIRE REVIEW NOTES FOR THIS. | | | | | | 7)NOTE: PLEASE SEE MANY AREAS OF PLANS | | | FOR COMMON AREAS/COMMON HALLWAYS ETC DO | | | NOT INDICATE ANY ELECTRICAL FOR | | | LIGHTING, RECEPTS, FIRE DEVICES ETC. | | | PLEASE SUBMIT COMPLETED COMMON AREAS. | | | | | | 8)NOTE: PLEASE SEE 620.23,620.24 FOR | | | REQUIREMENTS IN ELEV RMS/ PITS ETC. | | | | | | 9)NOTE: PLEASE CLARIFY RECEPTS W/IN 20' | | | OF POOL ON ROOF.620.22A3 WHERE A | | | PERMANENTLY INSTALLED POOL IS INSTALLED | | | AT A DWELLING UNIT(S), NO FEWER THAN | | | ONE 125-VOLT 15- OR 20-AMPERE RECEPTACLE | | | ON A GENERAL-PURPOSE BRANCH CIRCUIT | | | SHALL BE LOCATED NOT LESS THAN 3.0 M (10 | | | FT)FROM AND NOT MORE THAN 6.0 M (20 FT) | | | FROM THE INSIDE WALL OF THE POOL. | | | | | | 10)NOTE: PLEASE SEE GENERAL NOTES ON | | | UNIT ELECTRICLA PLANS REFERENCE 1999 | | | NEC. PLEASE SEE AS OF JULY 1ST, 2003, | | | WE ARE UNDER THE 2002 NEC. PLEASE | | | ADJUST | | | NOTES AND PLEASE ALSO ADJUST ALL OTHER | | | SHEETS WHERE CODES ARE REFERENCED. | | | | | | 11)NOTE: PLEASE PROVIDE A COMPLETE | | | FIXTURE SCHEDULE. PLEASE ALSO CORRELATE | | | WITH PLANS. | | | | | | 12)NOTE: PLEASE CLARIFY UNITS, | | | 1,2,3,AND 4. IT APPEARS THERE IS NO | | | ACCESS TO UNITS FROM GARAGE? | | | | | | 13)NOTE: PLEASE SEE 210.70 FOR CONTROL | | | OF EGRESS LIGHTING FOR UNITS W/ ACCESS | | | FROM OUTSIDE WITH WHAT APPEARS TO HAVE | | | NO CONTROL/SWICTHING OF LIGHTING WHEN | | | ENTERING THE UNITS. | | | PLEASE ALSO SEE ANY OTHER GRADE LEVEL | | | ACCESS UNITS WHICH 3-WAY SWITCHING MAY | | | BE REQUIRED. LS-101 5-8 | | | | | | 14)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULES. | | | PLEASE SEE UNITS #6, 17 | | | | | | 15)NOTE: PLEASE SEE SD'S APPEAR TO BE | | | SHOWN ON LITCHEN/BATH LIGHTING | | | CIRCUITS. | | | THIS IS FINE, HOWEVER ARC FAULT | | | PROTECTION WOULD ALSO BE REQUIRED FOR | | | THISE CIRCUITS AND NEED TO BE NOTED ON | | | PANEL SCHEDULES. (NOTE 6) ON PANEL | | | SCHEDULES. | | | PLEASE SEE 2002 NEC 210.12 | | | | | | 16)NOTE: PLEASE SEE SOME UNITS, IN SOME | | | BEDRMS, SD'S ARE MISSING. ( #11) | | | NFPA-72 8-1.4.1.6.2 | | | | | | 17)NOTE: PLEASE SEE 210.52D FOR GFI | | | RECEPTS REQUIRED WITHIN 3' OF THE EDGE | | | OF LAVS. PLEASE SEE AREAS WITH TWO | | | SINKS. GFI MAY BE MOVED TO CENTER OF | | | SINKS OR MAYHAVE AN ADDITIONAL GFI | | | ADDED. | | | | | | 18)NOTE:PLEASE SEE PANEL NOT PERMITTED | | | IN STORAGE/CLOTHES CLOSET. 240.24 | | | OVERCURRENT DEVICES SHALL NOT BE | | | LOCATED IN THE VICINITY OF EASILY | | | IGNITIBLE MATERIAL, SUCH AS IN CLOTHES | | | CLOSETS. | | | PLEASE ALSO SEE 408.7 | | | | | | 19)NOTE:PLEASE SEE SOME UNITS APPEAR TO | | | BE SHOWING TWO PANELS. UNIT VV. | | | | | | 20)NOTE: PLEASE SEE 110.26 FOR MIN | | | CLEARENCE REQUIREMENTS FOR PANELS SHOWN | | | IN SOME UNITS. ONE SHOWN FACING | | | COUNTERSPACE/ DISHWASHER. UNIT M. | | | | | | 21)NOTE: PLEASE SEE 210.70 FOR LT | | | REQUIRED FOR AHU'S IN HALL CLOSETS, | | | PLEASE ALSO SEE 210.63 | | | | | | 22)NOTE: PLEASE SEE 210.52C1-4 | | | PENINSULAR COUNTER SPACES. AT LEAST ONE | | | RECEPTACLE OUTLET SHALL BE INSTALLED AT | | | EACH PENINSULAR COUNTER SPACE WITH A | | | LONG DIMENSION OF 600 MM (24 IN.) OR | | | GREATER AND A SHORT DIMENSION OF 300 MM | | | (12 IN.) OR GREATER. A PENINSULAR | | | COUNTERTOP IS MEASURED FROM THE | | | CONNECTING EDGE.COUNTERTOP SPACES | | | SEPARATED BY RANGE TOPS, REFRIGERATORS, | | | OR SINKS SHALL BE CONSIDERED AS | | | SEPARATE COUNTERTOP SPACES IN APPLYING | | | THE REQUIREMENTS OF 210.52(C)(1), (2), | | | AND (3). UNITS D, G, A ETC. | | | | | | 23)NOTE: PLEASE PLACE NOTE ON PLANS FOR | | | SD LOCATION REQUIREMENTS PER NFPA-72 | | | 8-1.4.2 | | | | | | 24)NOTE: PLEASE VERIFY IF THERE ARE | | | GOING TO BE ANY TERRACE LTS/GFI'S? | | | PLEASE SEE ARCH SHEETS, ELEVATION PLANS | | | SHOWS LTS. PLEASE CORRLELATE. | | | PLEASE ALSO CORRELATE LAYOUT OF TERRACE | | | ON ELECTRICAL PLANS WITH LAYOUT AS | | | SHOWN ON FLR PLANS ON ARCH. | | | | | | 25)NOTE:PLEASE VERIFY IF UNITS WITH | | | JACUZZI/SPA UNITS. PANEL SCHEDULES | | | INDICATE SOME AS FUTURE AND SOME APPEAR | | | TO BE INSTALLED AT THIS TIME, HOWEVER | | | THE FLR LAYOUTS DO NOT INDICATE THIS OR | | | GFI RECEPTS OR GFI BRKRS.680.62A THE | | | OUTLET(S) THAT SUPPLIES A | | | SELF-CONTAINED THERAPEUTIC TUB OR | | | HYDROTHERAPEUTIC TANK, A PACKAGED | | | THERAPEUTIC TUB OR HYDROTHERAPEUTIC | | | TANK, OR A FIELD-ASSEMBLED THERAPEUTIC | | | TUB OR HYDROTHERAPEUTIC TANK SHALL BE | | | PROTECTED BY A GROUND-FAULT CIRCUIT | | | INTERRUPTER. | | | | | | 26)NOTE: PLEASE SEE OCP FOR FIRE PUMP | | | IS TO BE PER LOCKED ROTOR AS NOTED ON | | | RISER. PLEASE SUBMIT ALL INFORMATION | | | FOR FIRE PUMP, FIRE PUMP CONTROLLER. | | | ETC | | | SUBMIT ALL MANUFACT SPECS. | | | PLEASE SPECIFY CODE LTR FOR PUMP. | | | | | | | | | 27)NOTE: PLEASE ALSO SUBMIT ALL | | | MANUFACTURER SPECS FOR GENERATOR, ALL | | | TRANSFER SWITCHES AND FUEL TANK, SHOWING | | | ALL LISTINGS BY THE NRTL. | | | | | | 28)NOTE: PLEASE SEE 110.26 FOR ALL | | | CLEARENCE REQUIREMENTS FOR ELECTRICAL | | | RMS AND CLOSETS. MANY OF THE LAYOUTS | | | SHOWN DO NOT MEET 110.26 FOR CLEARENCE | | | OF EQUIPMENT. | | | PLEASE ALSO SEE 110.26 FOR DOOR SWING, | | | AND REQUIREMENTS FOR PANIC HARDWARE ON | | | DOORS. A NOTE NEEDS TO BE PLACED ON | | | PLANS FOR THIS REQUIREMT. | | | | | | 29)NOTE:PLEASE CORRELATE ELECTRICAL | | | RISER WITH ELECTRICAL EQUIPMENT SHOWN | | | IN | | | ELECTRICAL RMS. PLEASE SEE MISSING | | | "SHE". | | | | | | 30)NOTE: PLEASE CORRELATE "K" NOTES ON | | | RISER WITH THE ACTUAL SCHEDULE OF KEYED | | | NOTES ON PLANS. K-10 ETC. | | | | | | 31)NOTE: PLEASE VERIFY COPPER EQUIPMENT | | | GROUNDING IN BUS-DUCT. PLEASE SEE LOAL | | | AMENDMENTS WHICH DOES NOT PERMIT ALUM | | | FOR GROUNDING OR BONDING.310.2,250.62 | | | | | | 32)NOTE: PLEASE PROVIDE NOTE WHEATHER | | | OR NOT GENERATOR WILL BE SEPARATELY | | | DERIVED OR NOT. IF YES, PLEASE SEE ATS, | | | TO 4-POLE. | | | | | | 33)NOTE: PLEASE SEE RISER FOR ATS SIZES | | | AND OCP FEEDING ATS SWITCHES. PLEASE | | | SEE 900A OCP FEEDING 800A ATS. | | | | | | 34)NOTE: PLEASE COMPLETE RISER DIAGRAM | | | WITH SIZE OF EQUIPMENT SHOWN ON RISER. | | | PLEASE PROVIDE SIZES OF ALL EQUIPMENT , | | | TRANSFORMERS, GROUNDING FOR | | | TRANSFORMERS, KEYED NOTES ON RISER ETC. | | | 215.5,250.30, ETC. | | | PLEASE SUBMIT PANEL SCHEDULES FOR ALL | | | EQUIPMENT SHOWN ON SERVICE RISER. | | | PLEASE SEE RISER/NOTES APPEAR TO HAVE | | | 4000A MAINS/OCP FEEDING 3000A BUS-DUCT. | | | MANY OF THESE ITEMS CAN NOT BE VERIFIED | | | AT THIS TIME, DUE TO NONE OFTHIS | | | INFORMATION SUBMITTED. | | | | | | 35)NOTE: PLEASE SUBMIT COMPLETE LOAD | | | CALCULATIONS FOR BUILDING. THE ONLY | | | LOAD CALCS SUBMITTED WERE FOR | | | INDIVIDUAL | | | UNITS AND METER CNTRS. | | | 215.5,220 | | | | | | 36)NOTE: PLEASE VERIFY MANY UNITS ONLY | | | SHOWING A "COOKTOP". ARE THESE RANGES, | | | CONTAINING AN OVEN ALSO? | | | SOME UNITS SHOW SEPARATE COOKTOPS AND | | | OVENS, BUT IT APPEARS UNITS ONLY WITH | | | "COOKTOP" WILL HAVE NO OVENS?? | | | | | | 37)NOTE: PLEASE SEE FEEDERS SCHEDULE | | | SET UP FOR UNITS SHOWN FOR 125A,150A | | | AND | | | 175A ONLY. PLEASE SEE LOADS CALCS/MTR | | | CNTRS SHOW SOME UNITS FED WITH 200A OCP | | | AND 250A OCP. PLEASE SEE MIN CONDUCTORS | | | FOR 250A PER 310.16 | | | | | | 38)NOTE: PLEASE VERIFY SIZE OF PANELS. | | | PANELS ARE SHOWN AS 200A , HOWEVER SOME | | | SHOWN W/ 250A OCP FROM METER CNTRS. | | | | | | 39)NOTE: PLEASE VERIFY OCP FOR SOME | | | WATER HEATERS ( 6KW) MAX OCP 150%, PER | | | 422.11, MIN 125% 422.13.A BRANCH | | | CIRCUIT | | | SUPPLYING A FIXED STORAGE-TYPE WATER | | | HEATER THAT HAS A CAPACITY OF 450 L | | | (120GAL) OR LESS SHALL HAVE A RATING | | | NOT | | | LESS THAN 125 PERCENT OF THE NAMEPLATE | | | RATING OF THE WATER HEATER. | | | | | | PLEASE SEE MANY OF THESE NOTES ARE | | | REDLINED ON ONE SET OF REVIEWED PLANS | | | FOR AREAS OF CONCERN. | | | | | | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND | | | SUBMIT COMPLETED SETS FOR REVIEW. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY HAVE ANY | | | AFFECT ON ELECTRICAL PLANS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | 2005-01-03 00:00:00 | IN ELECTRICAL FOR REVIEW. | | | NOTES TO FOLLOW. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2008-04-10 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-04-10 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-04-10 |
Time |
11:38 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2005-04-15 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-04-15 |
Time |
11:41 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2005-04-15 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2004-12-10 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-12-10 |
Time |
08:37 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2004-12-10 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2004-12-10 00:00:00 | FAILED: | | | | | | 1. NO CIVIL PLANS WITH THIS SUBMITTAL | | | PACKAGE. PLEASE SUBMIT CIVIL PLANS FOR | | | OUR REVIEW AND APPROVAL UPON COMPLETION. | | | | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
20 |
Status |
P |
Date |
2008-08-11 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-08-11 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-08-11 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2008-08-11 16:25:45 | *****SUBMITTAL***** | | | | | | | | | RESIDENT EMERGENCY PROCEDURES & EVACUATION PLAN.THREE | | | SETS WERE SUBMITTED -(1) TO BE FILED AT CONSTRUCTION | | | SERVICES DEPARTMENT,(1) TO BE FILED AT THE FIRE | | | PREVENTION BUREAU,AND (10 TO BE RETURNED TO THE | | | CONTRACTOR. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
19 |
Status |
P |
Date |
2008-03-14 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-03-14 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-03-14 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2008-03-14 13:13:32 | SMOKE MANAGEMENT PANEL SUBMITTAL. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
18 |
Status |
F |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-02-06 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-06 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2008-02-06 14:23:49 | *****UNSAT***** | | | | | | | | | AS PER WEST PALM BEACH FIRE PREVENTION, DUCT SMOKE | | | DETECTORS SHALL INITIATE GENERAL FIRE ALARM.AMEND | | | SHEET E3.06 TO REFLECT AS SUCH | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
17 |
Status |
F |
Date |
2008-01-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-23 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-23 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2008-01-23 12:04:20 | *****REVISION 18, DATED 12/19/07 , UNSAT***** | | | | | | | | | | | | PLEASE BE ADVISED THAT DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM.AMEND THE APPROPIATE | | | ELECTRICAL SHEETS TO REFLECT THIS AS PER LOCAL | | | REQUIREMENTS | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
16 |
Status |
P |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-28 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-28 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2007-12-28 11:42:20 | *****REVISION APPROVED***** | | | | | | | | | REVIEWED VARIOUS REVISED ELECTRICAL PARTIAL SHEETS;NO | | | FIRE-STAMPING NEEDED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
15 |
Status |
P |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-09-14 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-09-14 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2007-09-14 15:23:19 | REVISION ILLUSTRATING FIRE EXTINGUISHER LOCATIONS. | | | ADDITIONAL EXTINGUISHERS REQUIRED AT POOL LEVEL. LIFE | | | SAFETY SHEETS STAMPED. (2 ROLLS) |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
14 |
Status |
F |
Date |
2007-07-25 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-25 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-07-25 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2007-07-25 15:38:41 | FIRE ALARM EQUIPMENT SUBMITTAL TO BE SUBMITTED UNDER | | | FIRE ALARM PERMIT |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
13 |
Status |
P |
Date |
2007-05-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-05-15 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-05-15 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2007-05-15 09:50:18 | FIRE PROTECTION REVISIONS SHALL BE SUBMITTED UNDER THE | | | FIRE SPRINKLER PERMIT. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
12 |
Status |
P |
Date |
2007-05-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-05-15 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-05-15 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2007-05-15 09:29:00 | FIRE VALVE CABINET SUBMITTAL. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
11 |
Status |
N |
Date |
2007-03-20 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-03-20 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-03-20 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2007-03-20 15:09:45 | FIRE PROTECTION REVISIONS INDICATED BUT NO FIRE | | | PROTECTION SHEETS SUBMITTED. REVISIONS FOR SEPARATE | | | PERMITTED WORK TO BE SUBMITTED UNDER APPLICABLE PERMIT. | | | NO REVISED LIFE SAFETY SHEETS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
10 |
Status |
P |
Date |
2007-01-19 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-19 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-19 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2007-01-19 17:08:47 | *****APPROVED***** | | | | | | | | | DATE STAMPED:HYDRAULIC CALCULATIONS AND SUBMITTAL | | | PACKAGES FROM SUMMERS FIRE SPRINKLERS,INC. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
9 |
Status |
P |
Date |
2006-12-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-29 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-29 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2006-12-29 11:17:02 | *****APPROVED***** | | | | | | | | | | | | OK'DTHE LOCATION OF FIRE SPRINKLERS (EVERY OTHER | | | FLOOR) FOR THE NEWLY INSTALLED TRASH CHUTE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
8 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-10-17 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-10-17 |
Time |
16:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
P |
Date |
2006-07-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-07-21 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-07-21 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2006-07-21 00:00:00 | REVISION DATED 4/6/06 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-04-13 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-04-13 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2006-02-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-02-16 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-02-16 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2006-02-16 00:00:00 | 1. REVISIONS FOR COMMENTS COMPLETED ON | | | 1/6/06 ARE TO BE SUBMITTED WITHIN 30 | | | DAYS OF FEBRUARY 16, 2006. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 | | | PLANS ARE APPROVED PROVISO THAT ALL | | | PREVIOUS COMMENTS ARE ADDRESSED WITH | | | REVISED PLANS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2006-01-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-01-06 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-01-06 |
Time |
12:20 |
Sent To |
|
|
| Notes |
| 2006-01-23 00:00:00 | 19. PLEASE EXPLAIN "OR THROUGH THE | | | ANNUNCIATION OF AT LEAST THREE (3) AREA | | | WIDE SMOKE DETECTORS SERVING A SMOKE | | | CONTROL ZONE". (SMOKE CONTROL OPERATION | | | PAGE M7.01.) WHY WILL IT TAKE THREE | | | SMOKE DETECTORS TO OPERATE. | | | | | | 20. PLEASE INCLUDE NOTE TO PAGE M7.01 | | | "ANTICPATED STACK EFFECT" REGARDING | | | STAIR PRESSURIZATION. | | | | | | 21. FIRE SPRINKLER PROTECTION REQUIRED | | | BELOW DUCTWORK THAT IS GREATER THAN 48" | | | WIDE. | | | | | | 22. THE EMERGENCY GENERATOR TERMINATION | | | EXHAUST DUCT POINT SHALL BE LOCATED WITH | | | RESPECT TO WINDOWS, DOORS OR SUPPLY AIR | | | OPENING. ALSO ARCHITECTURAL FEATURES CAN | | | CAUSE A BACKFEED CONDITION. | | | | | | 23. ALL FIRE DAMPERS ARE TO BE DROP | | | TESTED AND CERTIFIED AFTER INSTALLATION. | | | | | | 24. COOLING TOWERS TO COMPLY WITH NFPA | | | 214. | | | | | | 25. TWO DAMPERS APPEAR TO BE SHOWN ON | | | DRAWING BUT ARE NOT CALLED OUT ON PAGE | | | M2.09. | | | | | | 26. A DAMPER IS SHOWN ON PAGE M2.03 DOES | | | NOT APPEAR TO BE CALLED OUT. | | | | | | 27. WILL THE HORIZONTAL MEMBERS OF THE | | | TRELLIS HAVE AN EFFECT ON SEF-1, SHOWN | | | ON THE SECTION 1, PAGE M1.13. | | | | | | 28. THE SMOKE SYSTEM AND STAIRWELL | | | PRESSURIZATION SYSTEMS SHALL BE TESTED | | | PRIOR TO REQUESTING A TCO OR CO AND BOTH | | | SYSTEMS MUST BE APPROVED BY CITY | | | OFFICIALS. | | 2006-01-06 00:00:00 | 1. ALL EXIT ACCESS AREAS AND EXIT DOORS | | | SHALL BE PROVIDED WITH EXIT SIGNS. SOME | | | ELECTRICAL SHEETS APPEAR TO BE MISSING | | | EXIT SIGNS. | | | | | | 2. NO EXIT SIGNS SHOWN ON MAIN ROOF | | | LEVEL WEST. E2.19. THE SAME CONDITION | | | MAIN ROOF LEVEL EAST. | | | | | | 3. THERE APPEARS TO BE A DISCREPANCY | | | BETWEEN SOME DRAWING SHEETS. ON ONE | | | SHEET THE SMOKE MANAGEMENT PANEL IS | | | MISSING FROM THE FIRE COMMAND ROOM AND | | | ANOTHER PAGE IT IS SHOWN. | | | | | | 4. THE REQUIRED FIRE ALARM SYSTEM SHALL | | | BE MONITORED BY A UL LISTED CENTRAL | | | STATION APPROVED FOR CENTRAL STATION | | | SERVICE. | | | | | | 5. FIRE SPRINKLER HEADS SHALL BE QUICK | | | RESPONSE OR BE RESIDENTIAL TYPES. | | | | | | 6. STANDPIPES SHALL PROVIDE COVERAGE TO | | | ALL ARES OF THE BUILDING. ALL REQUIRED | | | STAIRWELLS ARE REQUIRED TO HAVE | | | STANDPIPES. | | | | | | 7. ALL ELEVATORS THAT CAN BE USED FOR | | | STRETCHERS SHALL BE IDENTIFIED. | | | | | | 8. DOOR MISSING FROM EXIT PATH FROM | | | ELEVATOR VESTIBULE # 3 UP THE STAIRS AND | | | APPEARS TO TRAVEL BEHIND PARKING SPACE. | | | PLEASE SEE PAGE LS1.03. | | | | | | 9. PLEASE VERIFY DOOR SWINGS IN | | | HORIZONTAL EXITS SHOWN ON PAGE LS1.03. | | | | | | 10. EXIT SIGNS ON POOL DECK SHALL NOT | | | EXCEED 100 FEET. PLEASE SEE LS1.10. | | | | | | 11. PLEASE PROVIDE FLAMESPREAD DATA ON | | | "THERMOCON SPRAY -ON INSULATION SHOWN ON | | | PAGE A4.02. | | | | | | 12. THE "3-0 WIDE PEDESTRIAN PASS GATE | | | MUST BE LABELED AS AN EXIT. WHEN THE | | | VEHICULAR SECTIONAL GATE IS DOWN ONLY | | | ONE EXIT APPEAR VISIBLES FROM THE THAT | | | SPECIFIC PARKING AREA. PLEASE SEE A4.11. | | | | | | 13. PLEASE EXPLAIN CARD READERS SHOWN ON | | | PAGE A4.14. WILL THEY POSE ANY PROBLEMS | | | WITH REGARDS TO EXITING. | | | | | | 14. CARD READERS NOTED IN SEVERAL PLACES | | | ON DOOR SCHEDULE. PLEASE NOTE ON THE | | | PLANS HOW THESE DEVICES WILL NOT | | | INTERFERE WITH EXITING REQUIREMENTS. | | | | | | 15. MECHANICAL ACCESS SPACES SHOWN ON | | | SEVERAL A PAGES. PLEASE PROVIDE DETAILS. | | | | | | 16. POOL DECK FLOOR HAS A DOOR THAT | | | OPPOSES ONE OF THE POOL PUMP ROOM DOOR. | | | PLEASE SEE PAGE A7.05A | | | | | | 17. MORE DETAILS NEEDED ON NON-RATED | | | METAL MESH PARTITION SHOWN ON PAGE | | | A7.03. | | | | | | 18. ON SOME OF THE REFLECTED CEILING | | | PLANS, SMOKE DETECTORS APPEAR TO BE | | | DIRECTLY NEXT TO HVAC DIFFUSERS. THE | | | MINIMUM THREE FOOT RULE IS TO APPLY. | | | | | | NOTE: MECHANICAL DRAWINGS WILL BE NEXT | | | SET OF DRAWINGS TO BE REVIEWED BY THIS | | | OFFICE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2005-09-30 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-09-30 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-09-30 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2005-09-30 00:00:00 | ******DENIED****** | | | | | | 1) EXIT SIGN STILL APPEARS TO LEAD | | | PERSONS INTO THE LOADING AREA. SHT | | | E-2.01. PLEASE CLARIFY ARCHITECT'S | | | RESPONSE. | | | | | | 2) FIRE PROTECTION PLANS HAVE BEEN | | | SUBMITTED WITH THIS PERMIT. SEPARATE | | | SHOP DRAWINGS AND PERMITS ARE REQUIRED | | | FOR FIRE SPRINKLER AND FIRE ALARM | | | SYSTEMS. | | | | | | 3) A COPY OF THE FIRST REVIEW HAS BEEN | | | INCLUDED. PLEASE SUBMIT YOU RESPONSE | | | LETTER TO THAT REVIEW THAT WAS COMPLETED | | | ON 1/21/05. A RESPONSE LETTER COULD NOT | | | BE FOUND WITH THIS SUBMITTAL. | | | | | | 4) ELECTRONIC SWITCHES, CHAIN AND LOCK | | | REQUIRED ON DOUBLE CHECK DETECTOR | | | ASSEMBLY. | | | | | | 5) SIGNS ARE REQUIRED IN STAIRWELLS THAT | | | INDICATE TOP, FLOOR# AND ROOF ACCESS. | | | | | | 6) TACTILE SIGNAGE IS REQUIRED FOR EXIT | | | DOORS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-04-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-04-28 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-04-28 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2005-04-28 00:00:00 | 1) NOTE #1- EXIT PATH MAY REQUIRE | | | STRIPING OR SOME OTHER APPROVED METHOD | | | OF MARKING TO MAINTAIN A CLEAR AND | | | UNOBSTRUCTED PATH OF TRAVEL. | | | | | | 2) NOTE #24- DOOR SWINGS ON STAIRS #7&8 | | | APPEAR TO BE SWINGING IN THE WRONG | | | DIRECTION. | | | | | | 3) NOTE #26- NO RESPONSE CAN BE FOUND | | | REGARDING TWO FIRE DEPARTMENT | | | CONNECTIONS. | | | | | | 4) NOTE #37- NO RESPONSE FOUND REGARDING | | | SMOKE DETECTOR IN FIRE COMMAND ROOM. | | | | | | 5) NOTE #57- NO RESPONSE FOUND REGARDING | | | SMOKE MANAGEMENT REQUIREMENTS. | | | | | | 6) NOTE #59- HOW WAS THE COMMENT | | | REGARDING DIRECTION OF EGRESS ADDRESSED? | | | | | | | | | 7) NOTE #58- NO RESPONSE FOUND | | | | | | 8) NOTES #60-64- NO RESPONSES FOUND. | | | | | | NOTE: WHEN RESPONDING TO REVIEW NOTES, | | | PLEASE IDENTIFY THE SHEET NUMBER WITH | | | REVISION CLOUDS TO HELP EXPEDITE THIS | | | PROCESS. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-01-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-01-21 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-01-21 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2005-01-21 00:00:00 | 1. CONSTRUCTION, DEMOLITION, AND | | | RENOVATION TO COMPLY WITH NFPA 241. | | | | | | 2. TEMPORARY STANDPIPES ARE REQUIRED | | | WHEN THE BUILDING REACHES THREE | | | STORIES OR 30 FEET IN HEIGHT. | | | | | | 3. SINCE THE BUILDING WILL BE | | | CONSIDERED HIGH-RISE IT MUST | | | COMPLY WITH APPLICABLE BUILDING AND | | | FIRE CODE REQUIREMENTS FOR HIGH-RISE | | | BUILDINGS. | | | | | | 4. PLEASE EXPLAIN CONTROLLED ENTRY | | | AND EXIT NOTES ON PAGE LS1.01. | | | | | | 5. PLEASE INDICATE WHAT ELEVATORS | | | ARE STRETCHER ACCESSIBLE. | | | | | | 6. EXIT SIGN PLACEMENT SHALL NOT | | | EXCEED 100 FEET. | | | | | | 7. PLEASE ILLUSTRATE ALL EXIT | | | DISCHARGE LOCATIONS FROM THE | | | BUILDING. EXIT DISCHARGE LOCATIONS | | | SHALL COMPLY WITH APPLICABLE FIRE | | | CODE REQUIREMENTS. | | | | | | 8. KNOX-BOXES WILL BE REQUIRED FOR | | | THE BUILDING. | | | | | | 9. ON PAGE LS1.03 PLANS MAKE REFERENCE | | | TO HORIZONTAL EXITS. PLEASE EXPLAIN | | | HOW THE CODE REQUIREMENTS FOR | | | HORIZONTAL EXITS ARE BEING MET. | | | | | | 10. ON PAGE LS1.03 EXITING IS SHOWN | | | THRU TENANT STORAGE ROOM B. PLEASE | | | EXPLAIN WHAT CODE ALLOWS THIS TO | | | OCCUR. | | | | | | 11. EXIT PATH ON LS1.05 IS GOING | | | BETWEEN TWO HANDICAP VEHICLES. PLEASE | | | EXPLAIN. | | | | | | 12. PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND | | | CEILINGS. | | | | | | 13. PLEASE INDICATE OCCUPANT LOAD | | | FOR THE 5TH FLOOR LANAI SHOWN | | | ON PAGE LS1.07. | | | | | | 14. PLEASE VERIFY OCCUPANT LOADS | | | FOR THE HEALTH CLUB AND MULTI-PURPOSE | | | ROOMS TO DETERMINE IF EXIT DOORS | | | SWINGS ARE PROPER. LS1.07. | | | | | | 15. WHAT CODE REQUIREMENTS ARE BEING | | | MET | | | TO EXIT FROM THE DECK OF THE LANAI | | | AREA. | | | | | | 16. IS THE AREA CALLED OUT ON PAGE | | | LS1.10 "EXIT PATH OF TRAVEL-LIGHTED | | | AND PAINTED LINES OF DEMARKATION" | | | ALSO SLIP RESISTANT. | | | | | | 17. NO STORAGE OF ANY KIND WILL BE | | | ALLOWED IN LOCATIONS NOTED FOR | | | INSPECTION AND SERVICE ONLY. | | | | | | 18. THE FIRE PROTECTION FOR THE | | | COOLING TOWERS SHALL COMPLY WITH | | | NFPA 214. | | | | | | 19. PLEASE PROVIDE PRESCRIPTIVE | | | STRENGTH REQUIREMENTS FOR ALL | | | HANDRAILS AND GUARDRAILS. | | | | | | 20. SOME DOOR SWINGS ON THE MEZZANINE | | | LEVEL AND PARKING LEVEL P3 ON | | | PAGE A2.03 MAY NOT SWING IN THE | | | PROPER DIRECTION. | | | | | | 21. PARKING AREA TO COMPLY WITH | | | NFPA 88A. | | | | | | 22. NO NOTE INDICATING THAT STAIR #6 | | | IS PRESSURIZED. | | | | | | 23. PLANS ILLUSTRATE A 21ST FLOOR | | | BUT IT IS BELIEVED THAT THE PERMIT | | | APPLICATION INDICATES A 20 STORY | | | BUILDING. | | | | | | 24. DOOR SWINGS ON STAIR # 2,7,AND 8 | | | ARE SWINGING IN THE WRONG DIRECTION | | | ON PAGE A2.16. | | | | | | 25. WRONG ADDRESS NOTED ON F10 NOTE | | | ON PAGE A3.01. SAME CONDITION EXISTS | | | ON A3.03. | | | | | | 26. TWO FIRE DEPARTMENT CONNECTIONS | | | WILL BE REQUIRED SINCE IT IS A | | | HIGH-RISE BUILDING. | | | | | | 27. NEW FIRE ALARM SYSTEM SHALL BE | | | MONITORED UL LISTED CENTRAL STATION | | | APPROVED FOR CENTRAL STATION SERVICE. | | | | | | 28. IS ANY ACCESS PROVIDED FOR | | | MECHANICAL SPACES SHOWN ON PAGE A3.21. | | | | | | 29. A DOOR IS NOTED WITHIN THE EXIT | | | ENCLOSURE FOR STAIR # 2 NEAR | | | ELEVATOR # 3. PLEASE EXPLAIN CODE | | | PROVISIONS THAT YOU MEET THAT | | | ALLOWS FOR THIS. | | | | | | 30. PLEASE INDICATE SIZE OF PEDESTRIAN | | | PASS DOOR ON PAGE A4.11. | | | | | | 31. KNOX-BOX LOCKING CAPS WILL BE | | | REQUIRED ON FIRE DEPARTMENT | | | CONNECTIONS. | | | | | | 32. ALL SMOKE DETECTORS SHALL BE | | | INSTALLED A MINIMUM OF THREE FEET | | | FROM AC DIFFUSERS. | | | | | | 33. WHAT IS THE ELEVATION OF THE | | | TERRACE SHOWN ON PAGE A4.41. | | | | | | 34. HAND WRITTEN NOTES APPEAR ON | | | SEVERAL PAGES OF THE PLAN. | | | | | | 35. EXIT STAIRS ARE TO BE KEPT UP | | | WITH CONSTRUCTION. | | | | | | 36. NO COMBUSTIBLES ALLOWED IN ANY | | | RETURN AIR PLENUM. NOTES LOCATED IN | | | PLANS. | | | | | | 37. NO SMOKE DETECTOR SHOWN IN FIRE | | | COMMAND ROOM. | | | | | | 38. ELEVATOR WARNING SIGNS REQUIRED | | | AT ELEVATOR LOBBIES. | | | | | | 39. PLEASE INDICATE LOCATIONS OF | | | SPEAKER STROBES FOR APARTMENTS | | | PROVIDED FOR THE HANDICAPPED. | | | | | | 40. ANY SOFFITS THAT ARE PLANNED SHALL | | | NOT INTERFERE WITH ANY FIRE PROTECTION | | | EQUIPMENT OR DEVICES. | | | | | | 41. PLEASE PROVIDE FLAMESPREAD DETAILS | | | ON HIGH-DENSITY STYROFOAM BLOCK | | | SHOWN ON A7.02. PLEASE EXPLAIN | | | PURPOSE OF MATERIAL. | | | | | | 42. STAIR PRESSURIZZATION DUCT SHOWN | | | ON PAGE A7.11 MUST BE A MINIMUM 2 | | | HOUR RATED SHAFT. | | | | | | 43. WHAT ACTIVITIES OCCUR IN OPEN | | | AIR COVERED STRUCTURE SHOWN ON PAGE | | | A8.11. | | | | | | 44. BUILDING IS LOCATED IN THE CITY | | | FIRE LIMITS. CERTAIN RESTRICTIONS | | | WILL APPLY SEE APPENDIX F, LOCAL | | | AMENDMENTS TO THE FLORIDA BUILDING | | | CODE. | | | | | | 45. PLEASE EXPLAIN USE OF CARD READERS | | | FOR THE BUILDING. WHAT ISSUES DO | | | THEY RAISE IF ANY TO EXITING. | | | | | | 46. ALL FIRE DOORS AND WINDOWS TO | | | COMPLY WITH NFPA 80, FIRE DOORS AND | | | WINDOWS. PLEASE ADD NOTE TO | | | DRAWINGS. | | | | | | 47. NO CUTTING OR WELDING OPERATIONS | | | TO OCCUR WITHOUT APPROVAL OF THE | | | FIRE PREVENTION BUREAU AND COMPLIANCE | | | WITH NFPA 51B. | | | | | | 48. ALL SHAFTS THAT ARE LARGE ENOUGH | | | FOR PERSONS TO FALL INTO MUST BE | | | MARKED SHAFTWAY WITH 6" HIGH | | | LETTERS. | | | | | | 49. ALL ARCHITECURAL TRIM LOCATED | | | IN THE FIRE LIMITS SHALL BE | | | NON-COMBUSTIBLE. | | | | | | 50. PAGE E0.01 INSERTED UPSIDE DOWN | | | IN SET. | | | | | | 51. A SITE PLAN DETAILING ALL EXISTING | | | OR NEW FIRE HYDRANTS AND WATER MAINS | | | SHALL BE PROVIDED. | | | | | | 52. PLEASE INDICATE EMERGENCY LIGHTING | | | FOR LANAI DECK, PAGE E1.03. | | | | | | 53. CLASS B FIRE ALARM CIRCUITS SHOWN | | | ON PAGE E8.04. ONLY CLASS A, STYLE D | | | OR FULLY ADDRESSABLE FIRE ALARM | | | CIRCUITS | | | SHALL BE PERMITTED. | | | | | | 54. FIRE ALARM SYSTEM SHALL MEET THE | | | SURVIVABILITY REQUIREMENTS OF NFPA 72. | | | | | | 55. NOTE # 40 ON PAGE E8.04 IS | | | INCORRECT. LIFE SAFETY CODE 2003 | | | EDITION SHOULD BE REFERENCED. | | | | | | 56. BUILDING IS TO COMPLY WITH | | | SECTON 11-8, LIFE SAFETY CODE, 2003 | | | EDITION. | | | | | | 57. THE FIREFIGHTER SMOKE MANAGEMENT | | | PANEL SHALL PROVIDE A GRAPHIC | | | REPRESENTATION OF THE BUILDING. HOA | | | SWITCHES WITH NO OVERLAY OF THE | | | BUILDING WILL NOT BE ACCEPTABLE. | | | | | | 58. MORE DETAILS REQUIRED ON PROPOSED | | | DRYER BOOSTER FANS. SHOWN ON | | | ELECTRICAL PAGES. | | | | | | 59. EXIT SIGN SHOWN ON PAGE E2.01 | | | DIRECTING PERSONS INTO LOADING | | | AREA. PLEASE EXPLAIN. | | | | | | 60. EXIT SIGNS APPEAR TO BE MISSING | | | ON SOME OF THE ELECTRICAL DRAWINGS. | | | | | | 61. MORE EXIT SIGNS APPEAR TO BE | | | NEEDED ON PAGE E2.02. | | | | | | 62. MORE EXIT SIGNS APPEAR TO BE | | | NEEDED ON PAGE E2.08. | | | | | | 63. ONLY TWO EXIT SIGNS SHOWN ON | | | PAGE E2.11. | | | | | | 64. THE ANTICPATED STACK EFFECT NOTE | | | WORDING SHALL BE ADDED TO THE | | | MECHANICAL PLANS. | | | | | | 65. FIRE DAMPERS TO COMPLY WITH | | | UL 555. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
261 |
Status |
N |
Date |
2008-07-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-28 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-28 |
Time |
12:18 |
Sent To |
Z |
|
| Notes |
| 2008-07-28 12:19:18 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
260 |
Status |
N |
Date |
2008-07-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-28 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-28 |
Time |
12:15 |
Sent To |
B |
|
| Notes |
| 2008-07-28 12:15:30 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
259 |
Status |
N |
Date |
2008-07-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-17 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-17 |
Time |
13:15 |
Sent To |
M |
|
| Notes |
| 2008-07-17 13:15:16 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
258 |
Status |
N |
Date |
2008-07-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-16 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-16 |
Time |
15:11 |
Sent To |
M |
|
| Notes |
| 2008-07-16 15:11:43 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
257 |
Status |
N |
Date |
2008-07-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-07-03 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-07-03 |
Time |
17:10 |
Sent To |
E |
|
| Notes |
| 2008-07-03 17:11:10 | TO "DPALMER' DESK/ PER MASTER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
256 |
Status |
N |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-25 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-25 |
Time |
15:51 |
Sent To |
M |
|
| Notes |
| 2008-06-25 15:51:44 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
255 |
Status |
N |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-25 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-25 |
Time |
14:39 |
Sent To |
M |
|
| Notes |
| 2008-06-25 14:39:41 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
254 |
Status |
N |
Date |
2008-05-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-16 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-16 |
Time |
15:54 |
Sent To |
B |
|
| Notes |
| 2008-05-16 15:54:46 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
253 |
Status |
N |
Date |
2008-05-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-16 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-16 |
Time |
15:52 |
Sent To |
P |
|
| Notes |
| 2008-05-16 15:52:46 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
252 |
Status |
N |
Date |
2008-05-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-12 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-12 |
Time |
14:17 |
Sent To |
E |
|
| Notes |
| 2008-05-12 14:17:58 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
251 |
Status |
N |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-06 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-06 |
Time |
14:18 |
Sent To |
M |
|
| Notes |
| 2008-05-06 14:47:10 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
250 |
Status |
N |
Date |
2008-05-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-02 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-02 |
Time |
16:40 |
Sent To |
M |
|
| Notes |
| 2008-05-02 16:41:29 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
249 |
Status |
N |
Date |
2008-05-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-02 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-02 |
Time |
12:52 |
Sent To |
B |
|
| Notes |
| 2008-05-02 12:52:31 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
248 |
Status |
N |
Date |
2008-04-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-04 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-04 |
Time |
14:35 |
Sent To |
ENG |
|
| Notes |
| 2008-04-04 14:36:10 | TO "ENG" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
247 |
Status |
N |
Date |
2008-04-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-04 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-04 |
Time |
14:31 |
Sent To |
P |
|
| Notes |
| 2008-04-04 14:31:55 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
246 |
Status |
N |
Date |
2008-03-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-13 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-13 |
Time |
15:27 |
Sent To |
M |
|
| Notes |
| 2008-03-13 15:28:15 | TO "M" BOX/2 SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
245 |
Status |
N |
Date |
2008-03-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-12 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-12 |
Time |
09:16 |
Sent To |
M |
|
| Notes |
| 2008-03-12 09:17:07 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
244 |
Status |
N |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-06 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-06 |
Time |
08:25 |
Sent To |
FIRE |
|
| Notes |
| 2008-03-06 08:25:26 | TO "F" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
243 |
Status |
N |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-19 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-19 |
Time |
12:45 |
Sent To |
E |
|
| Notes |
| 2008-02-19 12:46:15 | TO "E" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
242 |
Status |
N |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-19 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-19 |
Time |
12:45 |
Sent To |
B |
|
| Notes |
| 2008-02-19 12:45:27 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
241 |
Status |
N |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-19 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-19 |
Time |
11:21 |
Sent To |
M |
|
| Notes |
| 2008-02-19 11:21:33 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
240 |
Status |
N |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-19 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-19 |
Time |
11:11 |
Sent To |
E |
|
| Notes |
| 2008-02-19 11:11:53 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
239 |
Status |
N |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-02-05 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-02-05 |
Time |
10:10 |
Sent To |
B |
|
| Notes |
| 2008-02-05 10:10:41 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
238 |
Status |
N |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-29 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-29 |
Time |
15:31 |
Sent To |
B |
|
| Notes |
| 2008-01-29 15:32:01 | TO "RBROWN" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
237 |
Status |
N |
Date |
2008-01-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-22 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-22 |
Time |
14:06 |
Sent To |
B |
|
| Notes |
| 2008-01-22 14:07:19 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
236 |
Status |
N |
Date |
2008-01-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-22 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-22 |
Time |
10:20 |
Sent To |
M |
|
| Notes |
| 2008-01-22 10:20:43 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
235 |
Status |
N |
Date |
2008-01-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-18 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-18 |
Time |
10:49 |
Sent To |
E |
|
| Notes |
| 2008-01-18 10:50:13 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
234 |
Status |
N |
Date |
2008-01-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-14 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-14 |
Time |
08:52 |
Sent To |
B |
|
| Notes |
| 2008-01-14 08:53:03 | TO "MJACOBS" DESK/SUBMITAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
233 |
Status |
N |
Date |
2008-01-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-14 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-14 |
Time |
08:44 |
Sent To |
E |
|
| Notes |
| 2008-01-14 08:47:03 | TO "DPALMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
232 |
Status |
N |
Date |
2007-12-21 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2007-12-21 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2007-12-21 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2007-12-21 16:51:10 | SENT TO COMMERICAL BOARD #32 MMILLER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
231 |
Status |
N |
Date |
2007-12-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-19 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-19 |
Time |
13:16 |
Sent To |
B |
|
| Notes |
| 2007-12-19 13:16:32 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
230 |
Status |
N |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-10 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-10 |
Time |
09:59 |
Sent To |
B |
|
| Notes |
| 2007-12-10 09:59:36 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
229 |
Status |
N |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-03 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-03 |
Time |
13:15 |
Sent To |
B |
|
| Notes |
| 2007-12-03 13:15:49 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
228 |
Status |
N |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-30 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-30 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2007-11-30 16:29:33 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
227 |
Status |
N |
Date |
2007-11-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-28 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-28 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2007-11-28 11:17:04 | WAITING FOR "COMM" BD--REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
226 |
Status |
N |
Date |
2007-11-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-16 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-16 |
Time |
09:37 |
Sent To |
M |
|
| Notes |
| 2007-11-16 09:38:45 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
225 |
Status |
N |
Date |
2007-11-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-16 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-16 |
Time |
09:34 |
Sent To |
B |
|
| Notes |
| 2007-11-16 09:35:37 | TO "BTROBAUG" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
224 |
Status |
N |
Date |
2007-11-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-13 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-13 |
Time |
10:54 |
Sent To |
B |
|
| Notes |
| 2007-11-13 10:54:54 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
223 |
Status |
N |
Date |
2007-11-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-05 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-05 |
Time |
16:03 |
Sent To |
M |
|
| Notes |
| 2007-11-05 16:03:37 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
222 |
Status |
N |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-30 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-30 |
Time |
11:40 |
Sent To |
B |
|
| Notes |
| 2007-10-30 11:40:36 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
221 |
Status |
N |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-29 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-29 |
Time |
16:46 |
Sent To |
B |
|
| Notes |
| 2007-10-29 16:46:38 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
220 |
Status |
N |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-18 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-18 |
Time |
16:39 |
Sent To |
B |
|
| Notes |
| 2007-10-18 16:39:48 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
219 |
Status |
N |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-18 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-18 |
Time |
10:33 |
Sent To |
M |
|
| Notes |
| 2007-10-18 10:33:28 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
218 |
Status |
N |
Date |
2007-10-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-15 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-15 |
Time |
16:20 |
Sent To |
B |
|
| Notes |
| 2007-10-15 16:21:08 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
217 |
Status |
N |
Date |
2007-10-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-15 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-15 |
Time |
14:56 |
Sent To |
B |
|
| Notes |
| 2007-10-15 14:57:13 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
216 |
Status |
N |
Date |
2007-10-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-09 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-09 |
Time |
11:20 |
Sent To |
M |
|
| Notes |
| 2007-10-09 11:21:14 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
215 |
Status |
N |
Date |
2007-10-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-09 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-09 |
Time |
09:36 |
Sent To |
B |
|
| Notes |
| 2007-10-09 09:37:22 | TO "MJACOBS" DESK/ 2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
214 |
Status |
N |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-03 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-03 |
Time |
08:58 |
Sent To |
B |
|
| Notes |
| 2007-10-03 08:59:14 | TO "MJACOBS" DESK/5 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
213 |
Status |
N |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-25 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-25 |
Time |
09:35 |
Sent To |
B |
|
| Notes |
| 2007-09-25 09:35:36 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
212 |
Status |
N |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-18 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-18 |
Time |
17:00 |
Sent To |
M |
|
| Notes |
| 2007-09-18 17:01:01 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
211 |
Status |
N |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-18 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-18 |
Time |
09:59 |
Sent To |
B |
|
| Notes |
| 2007-09-18 10:00:08 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
210 |
Status |
N |
Date |
2007-09-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-07 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-07 |
Time |
08:46 |
Sent To |
B |
|
| Notes |
| 2007-09-07 08:47:14 | TO "MJACOBS" DESK/6 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
209 |
Status |
N |
Date |
2007-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-06 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-06 |
Time |
16:18 |
Sent To |
B |
|
| Notes |
| 2007-09-06 16:19:13 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
208 |
Status |
N |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-29 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-29 |
Time |
09:26 |
Sent To |
B |
|
| Notes |
| 2007-08-29 09:26:34 | TO "MJACOBS" DESK/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
207 |
Status |
N |
Date |
2007-08-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-28 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-28 |
Time |
08:10 |
Sent To |
B |
|
| Notes |
| 2007-08-28 08:10:33 | TO "MJACOBS" DESK/6 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
206 |
Status |
N |
Date |
2007-08-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-27 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-27 |
Time |
15:28 |
Sent To |
M |
|
| Notes |
| 2007-08-27 15:28:44 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
205 |
Status |
N |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-15 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-15 |
Time |
13:54 |
Sent To |
B |
|
| Notes |
| 2007-08-15 13:54:25 | TO "MJACOBS' DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
204 |
Status |
N |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-15 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-15 |
Time |
13:51 |
Sent To |
M |
|
| Notes |
| 2007-08-15 13:51:49 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
203 |
Status |
N |
Date |
2007-08-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-13 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-13 |
Time |
14:05 |
Sent To |
B |
|
| Notes |
| 2007-08-13 14:06:05 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
202 |
Status |
N |
Date |
2007-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-10 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-10 |
Time |
08:17 |
Sent To |
B |
|
| Notes |
| 2007-08-10 08:18:17 | TO MJ'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
201 |
Status |
N |
Date |
2007-08-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-09 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-09 |
Time |
12:46 |
Sent To |
B |
|
| Notes |
| 2007-08-09 12:46:32 | 4-BLDG SUBMITTALS TO MJ'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
200 |
Status |
N |
Date |
2007-08-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-07 |
Time |
20:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-07 |
Time |
20:10 |
Sent To |
M |
|
| Notes |
| 2007-08-07 20:11:22 | MECH REVISIONS TO RON R DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
199 |
Status |
N |
Date |
2007-08-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-03 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-03 |
Time |
16:24 |
Sent To |
B |
|
| Notes |
| 2007-08-03 16:25:30 | TO "MJACOBS" DESK/4 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
198 |
Status |
N |
Date |
2007-07-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-28 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-28 |
Time |
12:39 |
Sent To |
B |
|
| Notes |
| 2007-07-28 12:39:53 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
197 |
Status |
N |
Date |
2007-07-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-27 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-27 |
Time |
14:44 |
Sent To |
M |
|
| Notes |
| 2007-07-27 14:44:44 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
196 |
Status |
N |
Date |
2007-07-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-23 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-23 |
Time |
10:31 |
Sent To |
B |
|
| Notes |
| 2007-07-23 10:31:42 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
195 |
Status |
N |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-16 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-16 |
Time |
11:24 |
Sent To |
M |
|
| Notes |
| 2007-07-16 11:25:06 | TO "RREGEIRO" DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
194 |
Status |
N |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-13 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-13 |
Time |
16:42 |
Sent To |
B |
|
| Notes |
| 2007-07-13 16:42:51 | TO "MJACOBS' DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
193 |
Status |
N |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-13 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-13 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2007-07-27 11:43:46 | TO "COMM" BD#14 | | 2007-07-13 11:38:23 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
192 |
Status |
N |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-06 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-06 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2007-07-24 08:45:38 | TO "COMM" BD#6/PLANS ON RACK--6 ROLLS | | 2007-07-06 16:57:49 | WAITING FOR "COMM" BD--REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
191 |
Status |
N |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-06 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-06 |
Time |
16:32 |
Sent To |
B |
|
| Notes |
| 2007-07-06 16:32:57 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
190 |
Status |
N |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-06 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-06 |
Time |
16:26 |
Sent To |
FIRE |
|
| Notes |
| 2007-07-06 16:27:19 | TO "F" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
189 |
Status |
N |
Date |
2007-07-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-03 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-03 |
Time |
15:47 |
Sent To |
B |
|
| Notes |
| 2007-07-03 15:48:15 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
188 |
Status |
N |
Date |
2007-06-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-29 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-29 |
Time |
09:28 |
Sent To |
B |
|
| Notes |
| 2007-06-29 09:28:51 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
187 |
Status |
N |
Date |
2007-06-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-28 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-28 |
Time |
15:45 |
Sent To |
M |
|
| Notes |
| 2007-06-28 15:46:09 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
186 |
Status |
N |
Date |
2007-06-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-27 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-27 |
Time |
13:17 |
Sent To |
B |
|
| Notes |
| 2007-06-27 13:18:35 | TO "MJACOBS" DESK/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
185 |
Status |
N |
Date |
2007-06-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-24 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-24 |
Time |
17:39 |
Sent To |
B |
|
| Notes |
| 2007-06-24 17:39:52 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
184 |
Status |
N |
Date |
2007-06-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-24 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-24 |
Time |
14:48 |
Sent To |
B |
|
| Notes |
| 2007-06-24 14:48:33 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
183 |
Status |
N |
Date |
2007-06-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-22 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-22 |
Time |
09:34 |
Sent To |
B |
|
| Notes |
| 2007-06-22 09:35:15 | TO "MJACOBS" DESK/3 SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
182 |
Status |
N |
Date |
2007-06-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-21 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-21 |
Time |
15:30 |
Sent To |
M |
|
| Notes |
| 2007-06-21 15:31:04 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
181 |
Status |
N |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-19 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-19 |
Time |
14:38 |
Sent To |
B |
|
| Notes |
| 2007-06-19 14:38:25 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
180 |
Status |
N |
Date |
2007-06-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-15 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-15 |
Time |
16:36 |
Sent To |
B |
|
| Notes |
| 2007-06-15 16:37:19 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
179 |
Status |
N |
Date |
2007-06-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-13 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-13 |
Time |
16:41 |
Sent To |
B |
|
| Notes |
| 2007-06-13 16:41:28 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
178 |
Status |
N |
Date |
2007-06-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-13 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-13 |
Time |
16:40 |
Sent To |
M |
|
| Notes |
| 2007-06-13 16:40:56 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
177 |
Status |
N |
Date |
2007-06-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-12 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-12 |
Time |
08:55 |
Sent To |
M |
|
| Notes |
| 2007-06-12 08:55:55 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
176 |
Status |
N |
Date |
2007-06-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-08 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-08 |
Time |
16:35 |
Sent To |
B |
|
| Notes |
| 2007-06-08 16:35:39 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
175 |
Status |
N |
Date |
2007-06-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-07 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-07 |
Time |
16:44 |
Sent To |
B |
|
| Notes |
| 2007-06-07 16:45:01 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
174 |
Status |
N |
Date |
2007-06-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-07 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-07 |
Time |
10:10 |
Sent To |
E |
|
| Notes |
| 2007-06-07 10:10:24 | TO "DPALMER" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
173 |
Status |
N |
Date |
2007-06-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-07 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-07 |
Time |
10:09 |
Sent To |
B |
|
| Notes |
| 2007-06-07 10:09:35 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
172 |
Status |
N |
Date |
2007-06-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-06 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-06 |
Time |
08:21 |
Sent To |
B |
|
| Notes |
| 2007-06-06 08:21:38 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
171 |
Status |
N |
Date |
2007-06-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-04 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-04 |
Time |
13:08 |
Sent To |
B |
|
| Notes |
| 2007-06-04 13:10:01 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
170 |
Status |
N |
Date |
2007-06-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-01 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-01 |
Time |
15:03 |
Sent To |
B |
|
| Notes |
| 2007-06-01 15:03:48 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
169 |
Status |
N |
Date |
2007-05-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-30 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-30 |
Time |
10:01 |
Sent To |
B |
|
| Notes |
| 2007-05-30 10:01:33 | TO "MJACOBS" DESK/4 SUBMATTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
168 |
Status |
N |
Date |
2007-05-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-25 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-25 |
Time |
09:07 |
Sent To |
B |
|
| Notes |
| 2007-05-25 09:07:41 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
167 |
Status |
N |
Date |
2007-05-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-24 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-24 |
Time |
11:16 |
Sent To |
B |
|
| Notes |
| 2007-05-24 11:17:00 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
166 |
Status |
N |
Date |
2007-05-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-24 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-24 |
Time |
10:08 |
Sent To |
B |
|
| Notes |
| 2007-05-24 10:09:02 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
165 |
Status |
N |
Date |
2007-05-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-18 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-18 |
Time |
09:12 |
Sent To |
B |
|
| Notes |
| 2007-05-18 09:12:35 | TO "MJACOB" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
164 |
Status |
N |
Date |
2007-05-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-16 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-16 |
Time |
11:43 |
Sent To |
B |
|
| Notes |
| 2007-05-16 11:43:46 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
163 |
Status |
N |
Date |
2007-05-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-15 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-15 |
Time |
14:24 |
Sent To |
B |
|
| Notes |
| 2007-05-15 14:24:40 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
162 |
Status |
N |
Date |
2007-05-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-10 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-10 |
Time |
13:57 |
Sent To |
B |
|
| Notes |
| 2007-05-10 13:57:51 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
161 |
Status |
N |
Date |
2007-05-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-08 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-08 |
Time |
09:21 |
Sent To |
B |
|
| Notes |
| 2007-05-08 09:21:41 | TO "MJACOBS" DESK/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
160 |
Status |
N |
Date |
2007-05-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-04 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-04 |
Time |
11:45 |
Sent To |
M |
|
| Notes |
| 2007-05-04 11:46:12 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
159 |
Status |
N |
Date |
2007-05-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-04 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-04 |
Time |
11:44 |
Sent To |
B |
|
| Notes |
| 2007-05-04 11:44:59 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
158 |
Status |
N |
Date |
2007-05-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-02 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-02 |
Time |
13:10 |
Sent To |
B |
|
| Notes |
| 2007-05-02 13:11:15 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
157 |
Status |
N |
Date |
2007-05-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-02 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-02 |
Time |
13:09 |
Sent To |
FIRE |
|
| Notes |
| 2007-05-02 13:09:40 | TO "F" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
156 |
Status |
N |
Date |
2007-05-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-01 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-01 |
Time |
16:38 |
Sent To |
B |
|
| Notes |
| 2007-05-01 16:38:57 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
155 |
Status |
N |
Date |
2007-04-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-24 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-24 |
Time |
15:09 |
Sent To |
B |
|
| Notes |
| 2007-04-24 15:09:35 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
154 |
Status |
N |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-23 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-23 |
Time |
14:12 |
Sent To |
P |
|
| Notes |
| 2007-04-23 14:12:58 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
153 |
Status |
N |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-23 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-23 |
Time |
14:11 |
Sent To |
B |
|
| Notes |
| 2007-04-23 14:12:02 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
152 |
Status |
N |
Date |
2007-04-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-17 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-17 |
Time |
14:15 |
Sent To |
E |
|
| Notes |
| 2007-04-17 14:16:35 | TO "DPALMER" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
151 |
Status |
N |
Date |
2007-04-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-17 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-17 |
Time |
14:13 |
Sent To |
B |
|
| Notes |
| 2007-04-17 14:13:44 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
150 |
Status |
N |
Date |
2007-04-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-17 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-17 |
Time |
14:11 |
Sent To |
FIRE |
|
| Notes |
| 2007-04-17 14:11:34 | TO "F" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
149 |
Status |
N |
Date |
2007-04-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-13 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-13 |
Time |
15:00 |
Sent To |
B |
|
| Notes |
| 2007-04-13 15:01:19 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
148 |
Status |
N |
Date |
2007-04-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-10 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-10 |
Time |
16:42 |
Sent To |
M |
|
| Notes |
| 2007-04-10 16:43:05 | TO "M" BOX/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
147 |
Status |
N |
Date |
2007-04-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-10 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-10 |
Time |
16:32 |
Sent To |
B |
|
| Notes |
| 2007-04-10 16:33:19 | TO "MJACOBS" DESK/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
146 |
Status |
N |
Date |
2007-04-04 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-04-04 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-04-04 |
Time |
17:22 |
Sent To |
B |
|
| Notes |
| 2007-04-04 17:22:56 | TO MYRON JACOBS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
145 |
Status |
N |
Date |
2007-04-02 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-04-02 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-04-02 |
Time |
18:08 |
Sent To |
B |
|
| Notes |
| 2007-04-02 18:08:54 | SIX SUBMITTALS TO MYRON JACOBS DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
144 |
Status |
N |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-29 |
Time |
20:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-29 |
Time |
20:04 |
Sent To |
B |
|
| Notes |
| 2007-03-29 20:04:21 | SUBMITTAL TO MJ'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
143 |
Status |
N |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-29 |
Time |
20:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-29 |
Time |
20:04 |
Sent To |
B |
|
| Notes |
| 2007-03-29 20:04:48 | SUBMITTAL TO MJ'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
142 |
Status |
N |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-03-27 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-03-27 |
Time |
17:45 |
Sent To |
B |
|
| Notes |
| 2007-03-27 17:46:09 | SIX SUBMITTALS TO MYRON JACOBS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
141 |
Status |
N |
Date |
2007-03-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-25 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-25 |
Time |
12:38 |
Sent To |
B |
|
| Notes |
| 2007-03-25 12:38:44 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
140 |
Status |
N |
Date |
2007-03-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-23 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-23 |
Time |
16:28 |
Sent To |
B |
|
| Notes |
| 2007-03-23 16:29:27 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
139 |
Status |
N |
Date |
2007-03-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-23 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-23 |
Time |
16:27 |
Sent To |
B |
|
| Notes |
| 2007-03-23 16:27:44 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
138 |
Status |
N |
Date |
2007-03-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-23 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-23 |
Time |
16:21 |
Sent To |
B |
|
| Notes |
| 2007-03-23 16:23:48 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
137 |
Status |
N |
Date |
2007-03-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-21 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-21 |
Time |
11:54 |
Sent To |
B |
|
| Notes |
| 2007-03-21 11:55:20 | TO "MJACOBS" DESK/4 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
136 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-16 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-16 |
Time |
14:42 |
Sent To |
P |
|
| Notes |
| 2007-03-16 14:42:52 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
135 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-16 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-16 |
Time |
08:50 |
Sent To |
B |
|
| Notes |
| 2007-03-16 08:50:35 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
134 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-16 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-16 |
Time |
08:23 |
Sent To |
B |
|
| Notes |
| 2007-03-16 08:25:01 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
133 |
Status |
N |
Date |
2007-03-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-15 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-15 |
Time |
15:59 |
Sent To |
B |
|
| Notes |
| 2007-03-15 15:59:59 | TO "MJACOBS' DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
132 |
Status |
N |
Date |
2007-03-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-14 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-14 |
Time |
15:20 |
Sent To |
B |
|
| Notes |
| 2007-03-14 15:21:22 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
131 |
Status |
N |
Date |
2007-03-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-12 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-12 |
Time |
08:21 |
Sent To |
B |
|
| Notes |
| 2007-03-12 08:21:43 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
130 |
Status |
N |
Date |
2007-03-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-08 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-08 |
Time |
15:09 |
Sent To |
B |
|
| Notes |
| 2007-03-08 15:10:09 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
129 |
Status |
N |
Date |
2007-03-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-06 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-06 |
Time |
14:32 |
Sent To |
B |
|
| Notes |
| 2007-03-06 14:33:07 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
128 |
Status |
N |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-03 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-03 |
Time |
16:08 |
Sent To |
B |
|
| Notes |
| 2007-03-03 16:08:22 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
127 |
Status |
N |
Date |
2007-02-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-28 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-28 |
Time |
15:53 |
Sent To |
B |
|
| Notes |
| 2007-02-28 15:53:26 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
126 |
Status |
N |
Date |
2007-02-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-27 |
Time |
17:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-27 |
Time |
17:19 |
Sent To |
B |
|
| Notes |
| 2007-02-27 17:19:54 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
125 |
Status |
N |
Date |
2007-02-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-26 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-26 |
Time |
09:35 |
Sent To |
B |
|
| Notes |
| 2007-02-26 09:36:14 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
124 |
Status |
N |
Date |
2007-02-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-22 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-22 |
Time |
11:39 |
Sent To |
B |
|
| Notes |
| 2007-02-22 11:39:54 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
123 |
Status |
N |
Date |
2007-02-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-15 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-15 |
Time |
13:34 |
Sent To |
P |
|
| Notes |
| 2007-02-15 13:34:49 | TO "P" BOX/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
122 |
Status |
N |
Date |
2007-02-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-15 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-15 |
Time |
13:33 |
Sent To |
B |
|
| Notes |
| 2007-02-15 13:33:44 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
121 |
Status |
N |
Date |
2007-02-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-13 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-13 |
Time |
09:07 |
Sent To |
B |
|
| Notes |
| 2007-02-13 09:09:16 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
120 |
Status |
N |
Date |
2007-02-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-09 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-09 |
Time |
09:53 |
Sent To |
B |
|
| Notes |
| 2007-02-09 09:53:28 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
119 |
Status |
N |
Date |
2007-02-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-06 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-06 |
Time |
15:58 |
Sent To |
B |
|
| Notes |
| 2007-02-06 15:59:29 | TO "MJACOBS" DESK/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
118 |
Status |
N |
Date |
2007-02-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-02 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-02 |
Time |
15:08 |
Sent To |
E |
|
| Notes |
| 2007-02-02 15:09:20 | TO "DPALMER" DESK/SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
117 |
Status |
N |
Date |
2007-02-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-02 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-02 |
Time |
15:07 |
Sent To |
P |
|
| Notes |
| 2007-02-02 15:07:39 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
116 |
Status |
N |
Date |
2007-02-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-02-02 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-02-02 |
Time |
15:03 |
Sent To |
B |
|
| Notes |
| 2007-02-02 15:03:40 | TO "MJACOBS" DESK/2 SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
115 |
Status |
N |
Date |
2007-01-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-31 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-31 |
Time |
13:46 |
Sent To |
B |
|
| Notes |
| 2007-01-31 13:47:16 | TO "MJACOBS" DESK/ 3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
114 |
Status |
N |
Date |
2007-01-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-29 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-29 |
Time |
16:27 |
Sent To |
B |
|
| Notes |
| 2007-01-29 16:27:40 | TO "MJACOBS" DESK/ 3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
113 |
Status |
N |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-24 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-24 |
Time |
13:16 |
Sent To |
M |
|
| Notes |
| 2007-01-24 13:16:42 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
112 |
Status |
N |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-24 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-24 |
Time |
13:13 |
Sent To |
P |
|
| Notes |
| 2007-01-24 13:14:12 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
111 |
Status |
N |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-24 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-24 |
Time |
11:06 |
Sent To |
B |
|
| Notes |
| 2007-01-24 11:06:41 | TO "MJACOBS" DESK/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
110 |
Status |
N |
Date |
2007-01-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-23 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-23 |
Time |
10:11 |
Sent To |
B |
|
| Notes |
| 2007-01-23 10:11:31 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
109 |
Status |
N |
Date |
2007-01-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-19 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-19 |
Time |
08:51 |
Sent To |
B |
|
| Notes |
| 2007-01-19 08:52:26 | TO "MJACOBS" DESK/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
108 |
Status |
N |
Date |
2007-01-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-18 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-18 |
Time |
12:42 |
Sent To |
B |
|
| Notes |
| 2007-01-18 12:43:09 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
107 |
Status |
N |
Date |
2007-01-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-16 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-16 |
Time |
15:04 |
Sent To |
B |
|
| Notes |
| 2007-01-16 15:05:04 | TO "MJACOBS.COM/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
106 |
Status |
N |
Date |
2007-01-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-11 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-11 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2007-01-24 09:00:41 | TO "COMM" BD#23/PLANS ON RACK--7 ROLLS | | 2007-01-11 13:38:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
105 |
Status |
N |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-09 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-09 |
Time |
14:37 |
Sent To |
B |
|
| Notes |
| 2007-01-09 14:38:01 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
104 |
Status |
N |
Date |
2007-01-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-05 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-05 |
Time |
11:20 |
Sent To |
B |
|
| Notes |
| 2007-01-05 11:20:58 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
103 |
Status |
N |
Date |
2007-01-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-03 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-03 |
Time |
11:26 |
Sent To |
B |
|
| Notes |
| 2007-01-03 11:26:33 | TO "MJACOBS" DESK/5 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
102 |
Status |
N |
Date |
2007-01-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-03 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-03 |
Time |
11:23 |
Sent To |
FIRE |
|
| Notes |
| 2007-01-03 11:24:30 | TO "F" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
101 |
Status |
N |
Date |
2006-12-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-27 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-27 |
Time |
15:43 |
Sent To |
B |
|
| Notes |
| 2006-12-27 15:44:14 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
100 |
Status |
N |
Date |
2006-12-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-22 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-22 |
Time |
09:05 |
Sent To |
B |
|
| Notes |
| 2006-12-22 09:06:01 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
99 |
Status |
N |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-16 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-16 |
Time |
16:52 |
Sent To |
B |
|
| Notes |
| 2006-12-16 16:53:07 | TO "MJACOBS" DESK/4 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
98 |
Status |
N |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-16 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-16 |
Time |
16:37 |
Sent To |
B |
|
| Notes |
| 2006-12-16 16:37:35 | TO "MJACOBS" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
97 |
Status |
N |
Date |
2006-12-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-15 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-15 |
Time |
15:16 |
Sent To |
B |
|
| Notes |
| 2006-12-15 15:17:21 | TO "MJACOBS" DESK/7 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
96 |
Status |
N |
Date |
2006-12-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-04 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-04 |
Time |
13:15 |
Sent To |
B |
|
| Notes |
| 2006-12-04 13:16:02 | TO "MJACOBS" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
95 |
Status |
|
Date |
2006-11-29 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2006-11-29 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2006-11-29 |
Time |
18:55 |
Sent To |
B |
|
| Notes |
| 2006-11-29 18:56:07 | SENT TO MYRON JACOB'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
94 |
Status |
N |
Date |
2006-11-29 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2006-11-29 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2006-11-29 |
Time |
17:49 |
Sent To |
B |
|
| Notes |
| 2006-11-29 17:50:21 | SENT TO MYRON JACOB'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
93 |
Status |
N |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-21 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-21 |
Time |
15:20 |
Sent To |
P |
|
| Notes |
| 2006-11-21 15:20:28 | TO "P" BOX/4 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
92 |
Status |
N |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-21 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-21 |
Time |
15:19 |
Sent To |
M |
|
| Notes |
| 2006-11-21 15:19:55 | TO"M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
91 |
Status |
N |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-21 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-21 |
Time |
15:18 |
Sent To |
B |
|
| Notes |
| 2006-11-21 15:19:21 | TO "LMARTINEZ"DESK/7 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
90 |
Status |
N |
Date |
2006-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-21 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-21 |
Time |
14:53 |
Sent To |
B |
|
| Notes |
| 2006-11-21 14:53:54 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
89 |
Status |
N |
Date |
2006-11-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-13 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-13 |
Time |
15:54 |
Sent To |
B |
|
| Notes |
| 2006-11-13 15:54:46 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
88 |
Status |
N |
Date |
2006-11-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-07 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-07 |
Time |
16:33 |
Sent To |
M |
|
| Notes |
| 2006-11-07 16:34:12 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
87 |
Status |
N |
Date |
2006-11-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-07 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-07 |
Time |
09:35 |
Sent To |
B |
|
| Notes |
| 2006-11-07 09:35:23 | TO "LMARTINEZ" DESK/6 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
86 |
Status |
N |
Date |
2006-11-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-07 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-07 |
Time |
09:30 |
Sent To |
M |
|
| Notes |
| 2006-11-07 09:30:49 | TO "M" BOX/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
85 |
Status |
N |
Date |
2006-11-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-03 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-03 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2006-11-03 11:01:52 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
84 |
Status |
N |
Date |
2006-10-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-27 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-27 |
Time |
08:53 |
Sent To |
B |
|
| Notes |
| 2006-10-27 08:53:49 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
83 |
Status |
N |
Date |
2006-10-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-27 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-27 |
Time |
08:34 |
Sent To |
M |
|
| Notes |
| 2006-10-27 08:35:00 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
82 |
Status |
N |
Date |
2006-10-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-26 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-26 |
Time |
14:47 |
Sent To |
B |
|
| Notes |
| 2006-10-26 14:48:12 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
81 |
Status |
N |
Date |
2006-10-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-24 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-24 |
Time |
14:17 |
Sent To |
B |
|
| Notes |
| 2006-10-24 14:18:13 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
80 |
Status |
N |
Date |
2006-10-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-24 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-24 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2006-10-24 14:17:34 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
79 |
Status |
N |
Date |
2006-10-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-24 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-24 |
Time |
10:00 |
Sent To |
B |
|
| Notes |
| 2006-10-24 10:00:46 | TO JERALD SMITH'S DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
78 |
Status |
N |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-23 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-23 |
Time |
08:39 |
Sent To |
B |
|
| Notes |
| 2006-10-23 08:40:10 | TO "LMARTINEZ" DESK/SUBMITTAL--(SHORING FORMWORK AND GC | | | LETTER POUR#44) |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
77 |
Status |
N |
Date |
2006-10-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-14 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-14 |
Time |
16:16 |
Sent To |
P |
|
| Notes |
| 2006-10-14 16:17:09 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
76 |
Status |
N |
Date |
2006-10-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-14 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-14 |
Time |
16:13 |
Sent To |
B |
|
| Notes |
| 2006-10-14 16:13:35 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
75 |
Status |
N |
Date |
2006-10-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-14 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-14 |
Time |
15:10 |
Sent To |
M |
|
| Notes |
| 2006-10-14 15:10:44 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
74 |
Status |
N |
Date |
2006-10-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-13 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-13 |
Time |
16:23 |
Sent To |
M |
|
| Notes |
| 2006-10-13 16:24:37 | TO "M" BOX/ 4 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
73 |
Status |
N |
Date |
2006-10-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-13 |
Time |
15:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-13 |
Time |
15:25 |
Sent To |
FIRE |
|
| Notes |
| 2006-10-13 15:25:45 | TO "F" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
72 |
Status |
N |
Date |
2006-10-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-06 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-06 |
Time |
11:48 |
Sent To |
B |
|
| Notes |
| 2006-10-06 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
71 |
Status |
N |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-02 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-02 |
Time |
10:20 |
Sent To |
E |
|
| Notes |
| 2006-10-02 00:00:00 | TO "DPALMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
70 |
Status |
N |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-02 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-02 |
Time |
10:19 |
Sent To |
M |
|
| Notes |
| 2006-10-02 00:00:00 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
69 |
Status |
N |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-02 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-02 |
Time |
10:13 |
Sent To |
P |
|
| Notes |
| 2006-10-02 00:00:00 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
68 |
Status |
N |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-02 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-02 |
Time |
10:06 |
Sent To |
B |
|
| Notes |
| 2006-10-02 00:00:00 | TO "LMARTINEZ" DESK/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
67 |
Status |
N |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-19 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-19 |
Time |
09:25 |
Sent To |
B |
|
| Notes |
| 2006-09-19 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
66 |
Status |
N |
Date |
2006-09-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-12 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-12 |
Time |
10:56 |
Sent To |
P |
|
| Notes |
| 2006-09-12 00:00:00 | TO "KSTEVENS" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
65 |
Status |
N |
Date |
2006-09-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-12 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-12 |
Time |
10:53 |
Sent To |
P |
|
| Notes |
| 2006-09-12 00:00:00 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
64 |
Status |
N |
Date |
2006-09-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-12 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-12 |
Time |
10:52 |
Sent To |
B |
|
| Notes |
| 2006-09-12 00:00:00 | TO "LMARTINEZ" DESK/4 BLDG SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
63 |
Status |
N |
Date |
2006-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-06 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-06 |
Time |
15:43 |
Sent To |
B |
|
| Notes |
| 2006-09-06 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
62 |
Status |
N |
Date |
2006-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-06 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-06 |
Time |
09:30 |
Sent To |
B |
|
| Notes |
| 2006-09-06 00:00:00 | TO "LMARTINEZ" DESK/3 BLDG SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
61 |
Status |
N |
Date |
2006-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-06 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-06 |
Time |
09:27 |
Sent To |
P |
|
| Notes |
| 2006-09-06 00:00:00 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
60 |
Status |
N |
Date |
2006-09-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-06 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-06 |
Time |
09:24 |
Sent To |
M |
|
| Notes |
| 2006-09-06 00:00:00 | TO "M" BOX/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
59 |
Status |
N |
Date |
2006-08-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-26 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-26 |
Time |
16:43 |
Sent To |
B |
|
| Notes |
| 2006-08-26 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
58 |
Status |
N |
Date |
2006-08-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-23 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-23 |
Time |
09:00 |
Sent To |
B |
|
| Notes |
| 2006-08-23 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
57 |
Status |
N |
Date |
2006-08-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-18 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-18 |
Time |
11:39 |
Sent To |
B |
|
| Notes |
| 2006-08-18 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
56 |
Status |
N |
Date |
2006-08-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-17 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-17 |
Time |
17:14 |
Sent To |
B |
|
| Notes |
| 2006-08-17 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
55 |
Status |
N |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-11 |
Time |
18:12 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-11 |
Time |
18:12 |
Sent To |
B |
|
| Notes |
| 2006-08-11 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
54 |
Status |
N |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-08 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-08 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2006-08-08 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
53 |
Status |
N |
Date |
2006-08-04 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2006-08-04 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2006-08-07 |
Time |
08:19 |
Sent To |
B |
|
| Notes |
| 2006-08-04 00:00:00 | SENT TO "LMARTINEZ" DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
52 |
Status |
N |
Date |
2006-08-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-02 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-02 |
Time |
15:11 |
Sent To |
B |
|
| Notes |
| 2006-08-02 00:00:00 | TO "LMARTINEZ" DESK/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
51 |
Status |
N |
Date |
2006-08-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-01 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-01 |
Time |
09:43 |
Sent To |
B |
|
| Notes |
| 2006-08-01 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
50 |
Status |
N |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-31 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-31 |
Time |
13:16 |
Sent To |
B |
|
| Notes |
| 2006-07-31 00:00:00 | TO "LMARTINEZ" DESK/6 BLDG SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
49 |
Status |
N |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-31 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-31 |
Time |
13:13 |
Sent To |
P |
|
| Notes |
| 2006-07-31 00:00:00 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
48 |
Status |
N |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-27 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-27 |
Time |
13:35 |
Sent To |
B |
|
| Notes |
| 2006-07-27 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
47 |
Status |
N |
Date |
2006-07-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-22 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-22 |
Time |
13:44 |
Sent To |
B |
|
| Notes |
| 2006-07-22 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
46 |
Status |
N |
Date |
2006-07-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-18 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-18 |
Time |
14:42 |
Sent To |
B |
|
| Notes |
| 2006-07-18 00:00:00 | TO "LMARTINEZ' DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
45 |
Status |
N |
Date |
2006-07-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-14 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-14 |
Time |
14:07 |
Sent To |
P |
|
| Notes |
| 2006-07-14 00:00:00 | TO "P" BOX/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
44 |
Status |
N |
Date |
2006-07-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-14 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-14 |
Time |
13:57 |
Sent To |
E |
|
| Notes |
| 2006-07-14 00:00:00 | TO "DPALMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
43 |
Status |
N |
Date |
2006-07-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-14 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-14 |
Time |
13:56 |
Sent To |
B |
|
| Notes |
| 2006-07-14 00:00:00 | TO "LMARTINEZ" DESK/3 BLDG SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
42 |
Status |
N |
Date |
2006-07-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-06 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-06 |
Time |
15:20 |
Sent To |
B |
|
| Notes |
| 2006-07-06 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
41 |
Status |
N |
Date |
2006-06-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-29 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-29 |
Time |
14:45 |
Sent To |
M |
|
| Notes |
| 2006-06-29 00:00:00 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
40 |
Status |
N |
Date |
2006-06-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-29 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-29 |
Time |
14:45 |
Sent To |
B |
|
| Notes |
| 2006-06-29 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
39 |
Status |
N |
Date |
2006-06-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-29 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-29 |
Time |
14:44 |
Sent To |
P |
|
| Notes |
| 2006-06-29 00:00:00 | TO "P" BOX/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
38 |
Status |
N |
Date |
2006-06-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-23 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-23 |
Time |
13:40 |
Sent To |
B |
|
| Notes |
| 2006-07-06 00:00:00 | 6/23/06-REV TO "COMM" BD#29/PLANS ON | | | RACK | | 2006-06-23 00:00:00 | | | | | | | | | | | | | | | | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
37 |
Status |
N |
Date |
2006-06-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-22 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-22 |
Time |
11:52 |
Sent To |
B |
|
| Notes |
| 2006-06-22 00:00:00 | TO "LMARTINEZ" DESK/4 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
36 |
Status |
N |
Date |
2006-06-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-21 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-21 |
Time |
16:42 |
Sent To |
B |
|
| Notes |
| 2006-06-21 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
35 |
Status |
N |
Date |
2006-06-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-19 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-19 |
Time |
13:45 |
Sent To |
E |
|
| Notes |
| 2006-06-19 00:00:00 | TO "DPALMER" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
34 |
Status |
N |
Date |
2006-06-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-19 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-19 |
Time |
13:31 |
Sent To |
B |
|
| Notes |
| 2006-06-19 00:00:00 | TO "LMARTINEZ" DESK/7 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
33 |
Status |
N |
Date |
2006-06-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-19 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-19 |
Time |
13:29 |
Sent To |
M |
|
| Notes |
| 2006-06-19 00:00:00 | TO "M" BOX/5 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
32 |
Status |
N |
Date |
2006-06-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-19 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-19 |
Time |
13:26 |
Sent To |
P |
|
| Notes |
| 2006-06-19 00:00:00 | TO "P" BOX/12 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
31 |
Status |
N |
Date |
2006-06-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-14 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-14 |
Time |
13:21 |
Sent To |
B |
|
| Notes |
| 2006-06-14 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
30 |
Status |
N |
Date |
2006-06-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-09 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-09 |
Time |
14:20 |
Sent To |
P |
|
| Notes |
| 2006-06-09 00:00:00 | TO "P" BOX/7 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
29 |
Status |
N |
Date |
2006-06-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-09 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-09 |
Time |
14:02 |
Sent To |
B |
|
| Notes |
| 2006-06-09 00:00:00 | TO "LMARTINEZ' DESK/8 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
28 |
Status |
N |
Date |
2006-06-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-07 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-07 |
Time |
18:00 |
Sent To |
B |
|
| Notes |
| 2006-06-07 00:00:00 | TO "LMARTINEZ' DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
27 |
Status |
N |
Date |
2006-06-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-02 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-02 |
Time |
16:39 |
Sent To |
B |
|
| Notes |
| 2006-06-02 00:00:00 | TO "LMARTINEZ' DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
26 |
Status |
N |
Date |
2006-05-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-27 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-27 |
Time |
13:15 |
Sent To |
B |
|
| Notes |
| 2006-05-27 00:00:00 | TO "LMARTINEZ' DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
25 |
Status |
N |
Date |
2006-05-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-23 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-23 |
Time |
15:34 |
Sent To |
B |
|
| Notes |
| 2006-05-23 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
24 |
Status |
N |
Date |
2006-05-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-19 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-19 |
Time |
11:06 |
Sent To |
B |
|
| Notes |
| 2006-05-19 00:00:00 | TO "LMARTINEZ' DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
23 |
Status |
N |
Date |
2006-05-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-19 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-19 |
Time |
10:25 |
Sent To |
M |
|
| Notes |
| 2006-05-19 00:00:00 | TO "M" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
22 |
Status |
N |
Date |
2006-05-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-19 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-19 |
Time |
10:23 |
Sent To |
B |
|
| Notes |
| 2006-05-19 00:00:00 | TO "LMARTINEZ' DESK/6 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
21 |
Status |
N |
Date |
2006-05-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-15 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-15 |
Time |
11:34 |
Sent To |
B |
|
| Notes |
| 2006-05-15 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
20 |
Status |
N |
Date |
2006-05-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-12 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-12 |
Time |
08:46 |
Sent To |
B |
|
| Notes |
| 2006-05-12 00:00:00 | TO "LMARTINEZ" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
19 |
Status |
N |
Date |
2006-05-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-12 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-12 |
Time |
08:39 |
Sent To |
B |
|
| Notes |
| 2006-05-12 00:00:00 | TO "RBROWN" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
18 |
Status |
N |
Date |
2006-05-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-11 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-11 |
Time |
13:19 |
Sent To |
P |
|
| Notes |
| 2006-05-11 00:00:00 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
17 |
Status |
N |
Date |
2006-05-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-11 |
Time |
13:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-11 |
Time |
13:16 |
Sent To |
B |
|
| Notes |
| 2006-05-11 00:00:00 | TO "LMARTINEZ" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
16 |
Status |
N |
Date |
2006-05-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-03 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-03 |
Time |
12:03 |
Sent To |
B |
|
| Notes |
| 2006-05-03 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2006-05-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-01 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-01 |
Time |
15:27 |
Sent To |
B |
|
| Notes |
| 2006-05-01 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2006-05-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-01 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-01 |
Time |
09:30 |
Sent To |
B |
|
| Notes |
| 2006-05-01 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-29 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-29 |
Time |
13:47 |
Sent To |
B |
|
| Notes |
| 2006-06-06 00:00:00 | TO "COMM" BD#32/PLANS ON RACK | | 2006-05-31 00:00:00 | WAITING FOR "COMM" BD-REV--ROLLS IN | | | INCOMING | | 2006-04-29 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2006-04-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-19 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-19 |
Time |
14:15 |
Sent To |
B |
|
| Notes |
| 2006-04-19 00:00:00 | TO "LMARTINEZ" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2006-04-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-17 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-17 |
Time |
12:48 |
Sent To |
B |
|
| Notes |
| 2006-04-17 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2006-04-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-14 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-14 |
Time |
11:24 |
Sent To |
B |
|
| Notes |
| 2006-04-14 00:00:00 | TO "LMARTINEZ" DESK/3 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-04-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-06 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-06 |
Time |
15:39 |
Sent To |
B |
|
| Notes |
| 2006-04-06 00:00:00 | TO "LMARTINEZ" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-04-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-03 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-03 |
Time |
14:57 |
Sent To |
B |
|
| Notes |
| 2006-04-03 00:00:00 | TO "LMARTINEZ" DESK/40 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-01-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-31 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-31 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2006-01-31 00:00:00 | TO "COMM" BD #7 WITH PLANS IN REVIEW. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-11-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-28 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-28 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2005-12-27 00:00:00 | TO "COMM" BD#7 | | 2005-11-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-10-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-19 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-19 |
Time |
10:03 |
Sent To |
Z |
|
| Notes |
| 2005-10-19 00:00:00 | TO "Z" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-08-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-03 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-03 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2005-08-08 00:00:00 | TO "COMM" BD#38/PLANS ON RACK | | 2005-08-03 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-03-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-11 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-11 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2005-03-11 00:00:00 | TO "COMM" BD#40/"COMM" RACK, 12 ROLLS | | | "SEE FRONT SCREEN NOTES" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-02-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-24 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-24 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2005-02-24 00:00:00 | TO "COMM" BD#18/ | | | "COMM" RACK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-01-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-28 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-12-07 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2004-12-07 00:00:00 | SENT TO COMM BD#27 :PLANS ON RACK. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
74 |
Status |
P |
Date |
2008-08-05 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-08-05 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-08-05 |
Time |
08:18 |
Sent To |
P |
|
| Notes |
| 2008-08-05 08:19:43 | 8X11 REVISION FOR DEEP TRAP/PRIMER IN GARAGE FOR WH | | | OVERFLOW. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
73 |
Status |
P |
Date |
2008-08-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-08-04 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-08-04 |
Time |
15:26 |
Sent To |
PC |
|
| Notes |
| 2008-08-04 16:12:58 | REVISION 27 PP: M1.01 THRU M1.09, M1.14, M2.33, M3.02, | | | M5.03 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
72 |
Status |
P |
Date |
2008-07-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-07-15 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-07-15 |
Time |
10:04 |
Sent To |
PC |
|
| Notes |
| 2008-07-15 10:32:05 | REVISION #26 PAGES M1.13, M2.33, M3.02, M3.03, M6.01 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
71 |
Status |
P |
Date |
2008-05-21 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-05-21 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-05-21 |
Time |
14:40 |
Sent To |
PC |
|
| Notes |
| 2008-05-21 14:40:42 | SUBMITTAL # 15051.01.01 - STARTERS FOR HVAC PUMPS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
70 |
Status |
P |
Date |
2008-05-21 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-05-21 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-05-21 |
Time |
14:20 |
Sent To |
PC |
|
| Notes |
| 2008-05-21 14:21:17 | REV.25 PAGES: M1.14, M2.12, M2.33, M2.35 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
69 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-03-20 |
Time |
18:58 |
Sent To |
E |
|
| Notes |
| 2008-03-20 19:09:09 | SUBMITTAL 15930.01- STATIC PRESSURE SENSOR. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
68 |
Status |
P |
Date |
2008-03-20 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-03-20 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-03-20 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2008-03-20 18:58:27 | SUBMITTAL 15762.02.05 TRANE HEAT PUMP UNITS-1,2,3 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
67 |
Status |
P |
Date |
2008-03-20 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-03-20 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-03-20 |
Time |
18:40 |
Sent To |
|
|
| Notes |
| 2008-03-20 18:42:48 | SUBMITTAL 23 MECHANICAL SMOKE ZONE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
66 |
Status |
P |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-03-04 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-03-04 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2008-03-04 14:49:35 | SUBMITTAL # 15815.13.01 WALL CAPS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
65 |
Status |
P |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-03-04 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-03-03 |
Time |
18:00 |
Sent To |
PC |
|
| Notes |
| 2008-03-04 07:52:29 | REV.22 PP: M2.01, M2.07, M2.18, M2.29, M2.30, M2.32C, | | | M2.32D, M5.01, M6.03 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
64 |
Status |
P |
Date |
2008-03-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-03-03 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-26 |
Time |
08:06 |
Sent To |
PC |
|
| Notes |
| 2008-03-03 17:48:50 | REV 20 PP: M2.05, M2.18, M2.32, M2.32F, M3.04, M5.01 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
63 |
Status |
P |
Date |
2008-02-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-02-25 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-25 |
Time |
15:04 |
Sent To |
PC |
|
| Notes |
| 2008-02-25 17:48:04 | REV 20: M2.05, M2.18, M3.04, M5.01 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
62 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-02-05 |
Time |
19:02 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-02-05 |
Time |
19:02 |
Sent To |
|
|
| Notes |
| 2008-02-05 19:04:13 | SUBMITTLE # 15614 COOLING TOWER WATER AND DRAIN | | | CONNECTION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
61 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-02-05 |
Time |
18:37 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-02-05 |
Time |
18:36 |
Sent To |
|
|
| Notes |
| 2008-02-05 18:39:10 | SUBMITTLE # 15840.01 VARIABLE AIR VOLUME |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
60 |
Status |
F |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-02-05 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-02-05 |
Time |
18:07 |
Sent To |
|
|
| Notes |
| 2008-02-05 18:13:27 | SUBMITTLE # 15080.01 DENIED ALUMAGUARD 60 IS A CLOSURE | | | SYSTEM THAT IS NOT A UL 181 LISTED PRODUCT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
59 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-02-05 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-02-05 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2008-02-05 17:23:56 | SUBMITTLE NUMBER 15815.03 LOVERS & GRILLS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
58 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-02-05 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-02-05 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2008-02-05 16:54:29 | SUBMITTLE # 15815.01 FLEX DUCT,EXHAUST WALL CAPS , | | | POWER VENTILATORS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
57 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-02-05 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-02-05 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2008-02-05 16:20:07 | SUBMITTLE 15450.05 AQUASTAT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
56 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-02-05 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-02-05 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2008-02-05 16:14:18 | SUBMITTLE # 15815.14.01 GARAGE SUPPLY FANS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
55 |
Status |
P |
Date |
2008-01-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-01-30 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-01-30 |
Time |
18:49 |
Sent To |
|
|
| Notes |
| 2008-01-30 18:50:14 | SUBMITTLE # 15815.02 LOUVERS AND DAMPERS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
54 |
Status |
P |
Date |
2008-01-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-01-30 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-01-30 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2008-01-30 18:36:23 | SUBMITTLE # 15075.01 IDENTIFICATION AND NAMEPLATES |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
53 |
Status |
P |
Date |
2008-01-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-01-30 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-01-30 |
Time |
17:46 |
Sent To |
|
|
| Notes |
| 2008-01-30 17:48:21 | SUBMITTLE # 15181.03M DESEL ENGINE EXHAUST PIPING |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
52 |
Status |
P |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-03-04 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-03-04 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2008-01-30 17:04:53 | SUBMITTLE # 15181.02M SUCTION DIFFUSER FOR CWP.& TRIPLE | | | DUTY VALVES. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
51 |
Status |
P |
Date |
2008-01-30 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-01-30 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-01-30 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2008-01-30 16:24:57 | 04120353 SUBMITLE 15122.02 READ OUT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
50 |
Status |
P |
Date |
2008-01-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-01-24 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-01-24 |
Time |
18:47 |
Sent To |
|
|
| Notes |
| 2008-01-24 18:49:51 | SUBMITTLE NUMBER 15122.01 THERMOMETERS,GAGES AND TEST | | | PLUGS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
49 |
Status |
P |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-03-04 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-01-24 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2008-01-24 18:42:28 | SUBMITTLE NUMBER 15641.01.02 COOLING TOWER DATA |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
48 |
Status |
P |
Date |
2008-01-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-01-24 |
Time |
18:24 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-01-24 |
Time |
18:24 |
Sent To |
|
|
| Notes |
| 2008-01-24 18:26:32 | SUBMITTLE NUMBER 15110.01 BALL,BUTTERFLY AND CHECK | | | VALVE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
47 |
Status |
P |
Date |
2008-01-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-01-24 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-01-24 |
Time |
18:16 |
Sent To |
|
|
| Notes |
| 2008-01-24 18:18:52 | SUBMITTLE NUMBER 15685.01.02 WATER TREATMENT & | | | CHEMICALS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
45 |
Status |
P |
Date |
2008-01-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-01-24 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-01-24 |
Time |
17:37 |
Sent To |
B |
|
| Notes |
| 2008-01-24 17:39:20 | SUBMITTLE NUMBER 15181.07M EXHAUST PHIMBLES. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
44 |
Status |
P |
Date |
2008-01-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2008-01-24 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2008-01-24 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2008-01-24 17:05:32 | SUBMITTAL NUMBER 16100.10 CARBON MONOXIDE SENSORS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
43 |
Status |
P |
Date |
2008-01-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-01-22 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-01-22 |
Time |
11:43 |
Sent To |
PC |
|
| Notes |
| 2008-01-22 11:44:02 | SUBMITTAL #15181.08 WELDED PIPE NIPPLES |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
42 |
Status |
P |
Date |
2008-01-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-01-22 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-01-22 |
Time |
11:35 |
Sent To |
PC |
|
| Notes |
| 2008-01-22 11:41:13 | SUBMITTAL #16000.16 SILENCER FOR EMERGENCY GENERATOR |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
41 |
Status |
P |
Date |
2008-01-19 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-01-19 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-01-19 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2008-01-19 12:13:22 | REV.18 PAGES M2.08, M2.20, M2.27, M2.29, M2.30, M2.32, | | | M2.32A, M2.32B, M2.32C, M2.32D, M2.32F, M5.01 | | | | | | 1. M2.32C:THE FOLLOWING COMMENT FROM THE 10/25/07 | | | REVIEW OF REV 16 HAS NOT BEEN ADDRESSED "UNIT P1, 12X8 | | | RETURN TRANSFER FOR MASTER BEDROOM IS TOO SMALL TO MEET | | | THE BALANCED RETURN EXCEPTIONS UNDER FBC,M 601.4. IF | | | TRANSFERS ARE NOT DESIGNED TO MEET THESE EXCEPTIONS, A | | | FIELD TEST WILL BE REQUIRED AT FNAL INSPECTION TO | | | VERIFY PRESSURE DIFFERENTIALS ARE LESS THAN 0.01 INCHES | | | W.C AS REQUIRED BY THIS SECTION." THE PAGE WILL PASS | | | REVIEW AS IT IS THE ONLLY OUTSTANDING COMMENT. THERE | | | WILL BE A STAMP ON PLANS CALLING FOR A FIELD TEST TO | | | VERIFY BALANCED RETURN AT FINAL INSPECTION. | | | | | | 2. M2.30 AND M2.32D: SAME COMMENT AS ABOVE APPLIES TO | | | UNIT P ON THIS PAGE FOR 15X6 TRANSFER FROM MASTER | | | BEDROOM. | | | | | | 3. M2.32 AND M2.32F: SAME COMMENT AS ABOVE APPLIES TO | | | UNIT N ON THIS PAGE FOR 10 INCH ROUND TRANSFER FROM | | | BEDROOM 3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
40 |
Status |
P |
Date |
2007-11-24 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-24 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-11-24 |
Time |
13:36 |
Sent To |
PC |
|
| Notes |
| 2007-11-24 15:02:59 | REV 17 M2.27, M2.29, M2.30, M2.31, M2.32 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
39 |
Status |
P |
Date |
2007-11-24 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-11-24 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-11-24 |
Time |
10:08 |
Sent To |
PC |
|
| Notes |
| 2007-11-24 12:31:11 | REV 13 M2.21, M2.23, M2.24, M2.26 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
38 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-10-25 |
Time |
18:29 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-21 |
Time |
18:21 |
Sent To |
PC |
|
| Notes |
| 2007-10-25 18:28:12 | REVISION 16 | | | | | | FBC 2001 CODES W/ 2003 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING PAGE(S) WERE REVIEWED FOR CODE COMPLIANCE | | | AND PASSED: | | | M6.03 | | | | | | THE FOLLOWING PAGES WERE REVIEWED FOR CODE COMPLIANCE | | | AND WERE DENIED WITH COMMENTS: | | | | | | M2.27: UNIT M, HER WALK-IN-CLOSET, THERE IS A RETURN | | | GRILL SHOWN IN THE CEILING AT A LOCATION WHERE THERE IS | | | NO PLENUM. WHAT IS THE PURPOSE OF THE GRILL? ALSO, | | | PLEASE VERIFY THAT IT IS THE INTENDED DESIGN FOR THERE | | | TO BE RETURNS IN CLOSETS AND LAUNDRY ROOM. BALANCED | | | RETURN FROM THESE AREAS IS NOT REQUIRED. THIS CONDITION | | | OCCURS ON OTHER PAGES AS WELL. | | | | | | M2.29: UNIT-S, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO | | | BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3. | | | HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING | | | MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW | | | HOW THIS IS TO BE ACCOMPLISHED. | | | NOTE: UNIT-P1, HPU-1 AND HPU-6 REQUIRE FAN SHUT-DOWN BY | | | SMOKE DETECTOR IN ACCORDANCE WITH FBC,M 606.2.2. | | | | | | M2.32A: NOTE ON PLAN STATES "SHADED AREA IS A RETURN | | | AIR PLENUM (TYPICAL)." HOWEVER, THERE ARE NO SHADED | | | PLENUM AREAS ON PLAN. PLEASE CORRECT. FBC,M 602.2 | | | | | | M2.32C: UNIT P1, 12X8 RETURN TRANSFER FOR MASTER | | | BEDROOM IS TOO SMALL TO MEET THE BALANCED RETURN | | | EXCEPTIONS UNDER FBC,M 601.4. IF TRANSFERS ARE NOT | | | DESIGNED TO MEET THESE EXCEPTIONS, A FIELD TEST WILL BE | | | REQUIRED AT FNAL INSPECTION TO VERIFY PRESSURE | | | DIFFERENTIALS ARE LESS THAN 0.01 INCHES W.C AS REQUIRED | | | BY THIS SECTION. | | | | | | M2.32C: UNIT R1, BEDROOM 3/DEN HAS NO RETURN. SHOW | | | BALANCED RETURN IN ACCORDANCE WITH FBC,M 601.4. | | | | | | M2.32C: UNIT S, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO | | | BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3. | | | HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING | | | MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW | | | HOW THIS IS TO BE ACCOMPLISHED. ALSO, THE BRANCH DUCT | | | FEEDING BEDROOM 2 AND THE BATHROOM IS MISSING SIZE. | | | PLEASE CORRECT. FBC,M 601.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
37 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-10-25 |
Time |
18:10 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-21 |
Time |
18:30 |
Sent To |
PC |
|
| Notes |
| 2007-10-25 18:10:05 | REVISION 15 | | | | | | FBC 2001 CODES W/ 2003 SUPPLEMENTS | | | | | | THE FOLLOWING PAGES WERE NOT REVIEWED AS PART OF REV15 | | | BECAUSE THEY WERE SUPERCEDED PRIOR TO REVIEW: | | | M2.27 SUPERCEDED BY REV16 | | | M2.29 SUPERCEDED BY REV16 | | | M2.32A SUPERCEDED BY REV16 | | | M2.32C SUPERCEDED BY REV16 | | | M6.03 SUPERCEDED BY REV16 | | | | | | THE FOLLOWING PAGES WERE REVIEWED FOR CODE COMPLIANCE | | | AND PASSED: | | | M2.05 | | | M2.06 | | | M2.19 | | | M2.19B | | | M2.20A | | | M2.28 | | | M3.02 | | | M3.03 | | | M3.04 | | | M4.02 | | | | | | THE FOLLOWING PAGE(S) WERE REVIEWED FOR CODE COMPLIANCE | | | AND DENIED WITH COMMENTS: | | | | | | M2.18: TOILET AND DRYER EXHAUST IN UNIT V1 ARE | | | TERMINATING AT "CUBE CORE" GRILLS. ARE THESE LISTED FOR | | | USE ON DRYER EXHAUST? WHERE WILL THE BACKDRAFT DAMPER | | | FOR THE DRYER EXHAUST BE LOCATED? WHY IS THERE AN | | | INLINE BACKDRAFT DAMPER IN THE TOILET EXHAUST DUCT? | | | THERE IS NO DETAIL FOR THIS TYPE OF TERMINATION AT | | | DRYER AND TOILET EXHAUST. THIS IS THE SECOND TIME THIS | | | INFORMATION IS BEING REQUESTED. SHOW COMPLIANCE WITH | | | FBC,M 401.5 AND 504.4. | | | | | | M2.20: MECHANICAL CLOSET FOR HPU-5-3 IS SHOWN AS A | | | PLENUM. DISCHARGE EXHAUST DUCT FOR EF-5-2 IS ROUTED | | | THROUGH THIS PLENUM. EXHAUST DUCTS UNDER POSITIVE | | | PRESSURE SHALL NOT BE LOCATED IN A PLENUM IN ACCORDANCE | | | WITH FBC,M 601.3. SHOW HOW THIS DUCT IS TO BE ISOLATED | | | FROM PLENUM. | | | | | | M2.30: UNIT-P, HPU-1 AND HPU-5 REQUIRE FAN SHUT DOWN BY | | | SMOKE DETECTOR IN ACCORDANCE WITH FBC,M 606.2.2. | | | | | | M2.31: UNIT-T, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO | | | BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3. | | | HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING | | | MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW | | | HOW THIS IS TO BE ACCOMPLISHED. | | | | | | M2.32: UNIT-U, 12X6 RETURN DUCT IN BEDROOM 2 DOES NOT | | | ATTACH TO PLENUM. HOW WILL RETURN AIR GET FROM BEDROOM | | | TO PLENUM? SHOW COMPLIANCE WITH FBC,M 601.4. ALSO, WHY | | | US THERE A RETURN IN THE LAUNDRY ROOM? BALANCED RETURN | | | IS NOT REQUIRED FROM THIS AREA UNDER THIS SECTION. | | | | | | M2.32B: UNIT P2, SUPPLY FLEX IN BEDROOM 2 IS MISSING | | | SIZE. PLEASE CORRECT. FBC,M 601.1 | | | | | | M2.23D: UNIT P, RETURN TRANSFERS FROM MASTER BEDROOM | | | AND BEDROOM 2 ARE TOO SMALL TO MEET THE BALANCED RETURN | | | EXCEPTIONS UNDER FBC,M 601.4. IF TRANSFERS ARE NOT | | | DESIGNED TO MEET THESE EXCEPTIONS, A FIELD TEST WILL BE | | | REQUIRED AT FNAL INSPECTION TO VERIFY PRESSURE | | | DIFFERENTIALS ARE LESS THAN 0.01 INCHES W.C AS REQUIRED | | | BY THIS SECTION. ALSO, NOTE ON PLAN CALLS FOR EXHAUST | | | DUCT TO BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M | | | 601.3. HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE | | | CEILING MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. | | | PLEASE SHOW HOW THIS IS TO BE ACCOMPLISHED. | | | | | | M2.32D: UNIT R, RETURN TRANSFER FOR MASTER BEDROOM IS | | | TOO SMALL TO MEET THE BALANCED RETURN EXCEPTIONS UNDER | | | FBC,M 601.4. IF TRANSFERS ARE NOT DESIGNED TO MEET | | | THESE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED AT FNAL | | | INSPECTION TO VERIFY PRESSURE DIFFERENTIALS ARE LESS | | | THAN 0.01 INCHES W.C AS REQUIRED BY THIS SECTION. | | | | | | M2.32D: UNIT S, THE RETURN TRANSFER FOR BEDROOM 2 IS | | | GOING INTO THE BATHROOM, THEREFORE THE AIR IS NOT BEING | | | RETURNED TO THE HPU. PLEASE CORRECT AND SHOW COMPLIANCE | | | WITH FBC,M 601.3. ALSO, THE PLENUM AREA ABOVE THE | | | CEILING IS NOT DEFINED ON THE FLOOR PLAN. PLEASE | | | CORRECT. FBC,M 602.2 | | | | | | M2.32E: UNIT T, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO | | | BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3. | | | HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING | | | MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW | | | HOW THIS IS TO BE ACCOMPLISHED. | | | | | | M2.32F: UNIT U, 12X6 RETURN DUCT IN BEDROOM 2 IS NOT | | | ATTACHED TO PLENUM. PLEASE CORRECT AND SHOW COMPLIANCE | | | WITH FBC,M 601.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
36 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-10-25 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-21 |
Time |
18:07 |
Sent To |
PC |
|
| Notes |
| 2007-10-25 16:29:37 | MECH REVISION 14 | | | | | | FBC 2001 CODES W/ 2003 SUPPLEMENTS | | | | | | THE FOLLOWING PAGES WERE NOT REVIEWED BECUASE THEY WERE | | | SUPERCEDED PRIOR TO REVIEW OF REV 14: | | | M2.06 SUPERCEDED BY REV15 | | | M4.02 SUPERCEDED BY REV15 | | | M6.03 SUPERCEDED BY REV16 | | | | | | THE FOLLOWING PAGES WERE REVIEWED FOR CODE COMPLIANCE | | | AND PASSED: | | | M2.01 | | | M2.02 | | | M2.03 | | | M2.04 | | | M2.07 | | | M2.09 | | | M2.10 | | | M2.11 | | | M2.12 | | | M2.13 REV.12 | | | M2.17 REV.12 | | | M2.26B | | | M2.26D | | | M2.26F | | | M4.01 | | | M4.03 | | | M5.01 | | | M6.01 | | | | | | THE FOLLOWING PAGE(S) WERE REVIEWED FOR CODE COMPLIANCE | | | AND DENIED WITH COMMENTS: | | | | | | M2.08: 6X6 SUPPLY DUCT FROM HPU-P3-4 IS PASSING THROUGH | | | A RATED WALL. NOTE ON PLAN CLAIMS AN EXCEPTION TO THE | | | REQUIREMENT FOR A FIRE DAMPER PER FBC,M 607.1.3. | | | HOWEVER, UNDER EXCEPTION #3 THE DUCT IS REQUIRED TO BE | | | INSTALLED ABOVE A CEILING. THE STORAGE AREAS DO NOT | | | HAVE A CEILING, THEREFORE A FIRE DAMPER IS REQUIRED AT | | | THIS DUCT PENETRATION OF THE RATED WALL. | | | | | | M2.26A: UNIT C, RETURN TRANSFER (8IN. ROUND) IN BEDROOM | | | 2 IS TOO SMALL TO MEET THE BALANCED RETURN EXCEPTIONS | | | UNDER FBC,M 601.4. IF TRANSFERS ARE NOT DESIGNED TO | | | MEET THESE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED AT | | | FNAL INSPECTION TO VERIFY PRESSURE DIFFERENTIALS ARE | | | LESS THAN 0.01 INCHES W.C AS REQUIRED BY THIS SECTION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
35 |
Status |
P |
Date |
2007-09-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-09-11 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-09-11 |
Time |
17:30 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
34 |
Status |
F |
Date |
2007-08-17 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-08-17 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-08-17 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2007-08-17 11:51:13 | REV 12R PG M2.05 | | | ACTION: DENIED | | | | | | THIS PAGE WAS PREVIOUSLY SUBMMITED AS A REVISION AND | | | DENIED. PLEASE SEE MECHANICAL PLAN REVIEW COMMENTS | | | DATED 7/23/07 RELATED TO PG M2.05. ADDRESS PREVIOUS | | | COMMENTS AND RESUBMIT. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
33 |
Status |
F |
Date |
2007-08-17 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-08-17 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-08-16 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2007-08-17 11:21:58 | REV 13R | | | THE FOLLOWING PAGES WERE REVIEWED AND PASSED: | | | M2.12, M2.25, M2.26C, M2.26E | | | | | | THE FOLLOWING PAGES WERE DENIED WITH COMMENTS: | | | M2.22, M2.26A, M2.26B, M2.26D, M2.26F | | | | | | ONE COPY OF PASSED PAGES WAS RETAINED FOR PERMIT | | | RECORDS. ONE COPY OF DENIDE PAGES WAS RED-LINED TO | | | ASSIST IN UNDERSTANDING THE LOCATION AND NATURE OF | | | WRITTEN REVIEW COMMENTS. | | | | | | 1. M2.22 UNIT D1: THERE IS NO RETURN GRILL IN THE | | | PLENUM. PLEASE CORRECT. | | | | | | 2. M2.26A- | | | UNITS C AND L: MISSING RETURNS IN BEDROOM #2. FBC,M | | | 601.4 | | | UNITS B5 AND B6: PLAN SHOWS 14X14 R/A IN CEILING OF | | | MASTER BEDROOM FOR WHAT PURPOSE? PLEASE CLARIFY. | | | | | | 3. M2.26B- | | | UNIT G1: CONTAINS NOTE FOR FLEX DUCT TO OFFSET DRYER | | | EXHAUST. FLEX DUCT SHALL NOT BE USED IN CONCEALED | | | SPACES. FBC,M 504.6. ALSO IN G1, 16X16 R/A GRILL IN | | | MASTER BEDROOM HAS NO DUCT OR PLENUM OR OTHER WAY FOR | | | AIR TO RETURN FROM ROOM. | | | UNIT D1, THERE IS NO RETURN GRILL IN PLENUM CEILING. | | | UNIT C2, 12X12 R/A FOR MASTER BEDROOM IS NOT LOCATED | | | WITHIN THE CEILING PLENUM SPACE. | | | | | | 4. M2.26D UNIT J: THERE IS NO DEFINED CEILING PLENUM | | | AREA SHOWN ON PLAN. PLEASE CORRECT. | | | | | | 5. M2.26F UNIT C1: NO FIRE RATING OR OPENING | | | PROTECTIVES ARE SHOWN WHERE THE PLENUM EXTENDS INTO THE | | | CORRIDOR. PLEASE CORRECT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
32 |
Status |
N |
Date |
2007-08-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-08-02 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-08-01 |
Time |
18:59 |
Sent To |
|
|
| Notes |
| 2007-08-02 08:31:26 | THIS MECH REVISION WAS DONE UNDER SEPARATE SUBMITTAL | | | REVIEWED 7/23/07 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
31 |
Status |
F |
Date |
2007-07-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-07-23 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-07-22 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2007-07-23 10:13:52 | THE FOLLOWING PAGES WERE REVIEWED AND STAMPED: | | | | | | M1.01 THROUGH M1.12, M2.14, M2.15, M2.16, M2.19A, | | | M2.20B, M3.02, M3.03, M3.04 | | | | | | THE FOLLOWING PAGES WERE DENIED WITH COMMENTS: | | | | | | 1. M2.05: EF-A IN JANITOR'S CLOSET, DUCT PASSES THROUGH | | | MECHANICAL ROOM WHICH IS A PLENUM. EXHAUST DUCTS UNDER | | | POSITIVE PRESSURE SHALL NOT PASS THROUGH A PLENUM. | | | FBC,M 601.3 | | | | | | 2. M2.05: EXHAUST DUCT PENETRATION AT MECHANICAL ROOM | | | RATED WALL REQUIRES A FIRE DAMPER. IT DOES NOT MEET ALL | | | CONDITIONS OF THE EXCEPTION UNDER FBC,M 607.1.3 UNLESS | | | THE DUCT IS INTALLED ABOVE A CEILING. SEE ITEM (4) OF | | | THIS SECTION. | | | | | | 3. M2.13: UNIT VV, THERE IS NO DUCT SHOWN ON PLANS | | | FEEDING THE 8X6 SUPPLY REGISTER IN THE MASTER BEDROOM. | | | PLEASE CORRECT. | | | | | | 4. M2.17: UNIT H4, PORTIONS OF SUPPLY TRUNK ARE MISSING | | | FROM PLAN. PLEASE CORRECT. | | | | | | 5. M2.18: UNIT V1, PLAN SHOWS INLINE BACKDRAFT DAMPER | | | IN EXHAUST DUCT. IS THIS FOR BATH EXHAUST ONLY OR ALSO | | | FOR DRYER? IS THE INLINE BACKDRAFT DAMPER LISTED FOR | | | USE IN A DRYER EXHAUST DUCT? DRYER EXHAUST DUCT IS TO | | | BE FREE OF OBSTRUCTIONS AND HAVE A SMOOTH INTERIOR | | | SURFACE. SEE FBC,M 504.4 AND 504.6. ALSO, HAS THERE | | | BEEN A SUBMITTAL FOR THE "CUBE CORE GRILL" FOR USE ON | | | DRYER EXHAUST? THE GRILL FOR BATH EXHAUST REQUIRES A | | | SCREEN (FBC,M 401.6) AND A SCREEN IS PROHIBITED ON | | | DRYER EXHAUST OUTLETS (FBC,M 504.4). | | | | | | 6. M2.19: MOTORIZED DAMPER 5-1-2 IS NO LONGER SHOWN IN | | | DUCT, BUT THE DESIGNATION AND NOTE ARE STILL ON THE | | | PLAN. IS THE SMOKE CONTROL SYSTEM BEING REVISED OR IS | | | THE DAMPER MISTAKENLY OMITTED? | | | | | | 7. M2.19: GRILL AND DUCT SIZE MISSING FROM TWO DROPS IN | | | MULTI USE ROOM AND KITCHEN. | | | | | | 8. M2.19B: UNIT C2, PROVIDE NOTE REGARDING EXHAUST | | | DUCTS IN RETURN AIR PLENUM. WILL THE SYSTEM WHICH WAS | | | SUBMITTED AS AN ALTERNATE MATERIAL/METHOD FOR EXHAUST | | | IN A PLENUM WORK IN THIS CASE, WHERE THE EXHAUST FAN | | | ITSELF IS LOCATED IN THE PLENUM? PLEASE PROVIDE DETAIL. | | | FBC,M 601.3 | | | | | | 9. M2.20: COMMON AREAS ARE NOT SHOWN ON PLAN AS HAVING | | | BEEN REVISED. HOWEVER, THE AREA CONTAINS SEVERAL | | | CHANGES FROM PREVIOUS APPROVED PLANS. PLEASE INDICATE | | | ALL AREAS WHICH ARE PART OF THIS REVISION. | | | | | | 10. M:20A: SAME AS COMMENT #10. COMMON AREA DUCT | | | SYSTEMS WHICH ARE SHOWN IN THEIR ENTIRETY ON PG M2.20 | | | MAY BE OMITTED FROM THIS PAGE, OR THE AREAS BEING | | | REVISED MUST BE CLEARLY IDENTIFIED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
30 |
Status |
P |
Date |
2007-07-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-07-02 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-06-29 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2007-07-02 15:11:07 | FAN SHUT-DOWN VIA DUCT OR AREA SMOKE DETECTOR IS | | | REQUIRED IN ALL UNITS WHICH HAVE HPU-4 AS SHOWN ON | | | EQUIPMENT SCHEDULE (M5.01) WITH A SUPERVISORY SIGNAL AT | | | A CONSTANTLY ATTENDED LOCATION. | | | ALSO, PLEASE PROVIDE DOCUMENTATION SHOWING HPU-5 WITHIN | | | RANGE OF CFM'S REQUIRED ON FLOOR PLAN BASED ON ACTUAL | | | E.S.P. IN UNTS D AND D1. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
29 |
Status |
F |
Date |
2007-06-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-06-23 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-06-23 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2007-06-23 14:10:17 | -------------------DENIED------------------------- | | | | | | PAGES M2.21 THROUGH M2.26: THESE ARE THE SAME EXACT | | | PAGES WHICH WERE DENIED 6/18/07. THERE ARE NO CHANGES | | | FROM THAT SET AND NONE OF THE COMMENTS FROM PREVIOUS | | | REVIEW HAVE BEEN ADDRESSED. PLEASE SEE ATTACHED | | | PREVIOUS REVIEW COMMENTS. PLEASE RESPOND TO EACH ISSUE | | | IN WRITING AND SHOW ON PLANS WHERE CORRECTIONS HAVE | | | BEEN MADE. ALSO, SEE ATTACHED NOTICE REGARDING | | | ADDITIONAL FEES FOR PLANS WHIC ARE REJECTED REPEATEDLY | | | FOR THE SAME CODE ISSUES. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
28 |
Status |
F |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-06-18 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-06-16 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2007-06-18 10:40:26 | ----------------DENIED----------------- | | | | | | NOTE: AREAS ADDRESSED IN THESE COMMENTS HAVE BEEN | | | MARKED ON ONE SET OF THE SUBMITTED PLANS, WHERE | | | PRACTICAL, FOR THE PURPOSE OF CLARITY. | | | | | | 1. M2.21 UNIT L: FLOOR PLAN SHOWS 1445 CFM SUPPLY. | | | HPU-4 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 2000 CFM. | | | PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND | | | EQUIPMENT SCHEDULE. WHICH IS CORRECT? | | | | | | 2. M2.21 UNIT C: SQUARE 90 DEGREE ELBOW ON 12X10 SUPPLY | | | DUCT REQUIRES TURNING VANES PER FBC,M 603.4, SMACNA OR | | | NAIMA DUCT CONSTRUCTION STANDARDS. | | | | | | 3. M2.21 UNIT C: PLEASE SHOW PROVISIONS FOR BALANCED | | | RETURN PER FBC,M 601.4. | | | | | | 4. M2.21 UNIT K: FLOOR PLAN SHOWS 1030 CFM SUPPLY. | | | HPU-3 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 1250 CFM. | | | PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND | | | EQUIPMENT SCHEDULE. WHICH IS CORRECT? | | | | | | 5. M2.21 UNIT K: TRANSFER DUCT FROM MASTER BEDROOM IS | | | NOT DESIGNED TO MEET THE BALANCED RETURN EXCEPTIONS OF | | | FBC,M 601.4. 10X8 SUPPLY X 1.5 = 120 SQ.IN. THIS IS THE | | | MINIMUM SIZE TRANSFER DUCT PLUS 1" UNDERCUT DOOR. IF | | | TRANSFERS ARE NOT DESIGNED TO THESE EXCEPTIONS, A FIELD | | | TEST WILL BE REQUIRED TO VERIFY BALANCED RETURN | | | PRESSURE DIFFERENTIAL OF 0.01" W.C. OR LESS PER 601.4. | | | | | | 6. M2.21 UNIT B5: FLOOR PLAN SHOWS 1050 CFM SUPPLY. | | | HPU-2 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 950 CFM. | | | PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND | | | EQUIPMENT SCHEDULE. WHICH IS CORRECT? | | | | | | 7. M2.21 UNIT B5: TRANSFER DUCT IN MASTER BEDROOM. 12X8 | | | SUPPLY X 1.5 = 144 SQ.IN. THIS IS THE MINIMUM SIZE | | | REQUIRED FOR TRANSFER DUCT PLUS 1" UNDERCUT DOOR. SEE | | | COMMENT #5 FOR CONDITIONS. | | | | | | 8. M2.21 AND M2.22: PLEASE SHOW ENTIRE DUCT | | | LAYOUT/FLOOR PLAN FOR UNIT B6 ON ONE PAGE OR THE | | | OTHER. | | | | | | 9. M2.21 UNIT B6: SQUARE 90 DEGREE ELBOW REQUIRES | | | TURNING VANES. SEE COMMENT #2. COMMENTS 6 AND 7 ALSO | | | APPLY TO UNIT B6. | | | | | | 10. M2.22 UNIT G1: THE DESIGN OF THE TRANSFER DUCT AND | | | GRILLS FOR THE MASTER BEDROOM IS UNCLEAR DUE TO SOME | | | COMPONENTS NOT BEING SHOWN ON PLAN. FBC 104.3.1.1 | | | | | | 11. M2.22 UNIT D1: PRIMARY RETURN GRILL IS MISSING FROM | | | PLANS. PLEASE CORRECT. | | | | | | 12. M2.22 UNIT D1: FLOOR PLAN SHOWS 845 CFM SUPPLY. | | | HPU-5 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 650 CFM. | | | PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND | | | EQUIPMENT SCHEDULE. WHICH IS CORRECT? | | | | | | 13. M2.22 UNIT E1: SQUARE 90 DEGREE ELBOW NEEDS TURNING | | | VANES. SEE COMMENT #2. | | | | | | 14. M2.22 UNIT E1: PLAN SHOWS 4" BATH EXHAUST PASSIGN | | | THROUGH R/A PLENUM. EXHAUST DUCTS UNDER POSITIVE | | | PRESSURE SHALL NOT EXTEND INTO OR PASS THROUGH DUCTS OR | | | PLENUMS. FBC,M 601.3. | | | | | | 15. M2.22 UNIT C2: PLEASE SHOW ON PLANS THE SIZE OF | | | SUPPLY DUCT FROM A/C CLOSET TO THE TRANSITION AND SHOW | | | THE DUCT LINE IN ITS ENTIRETY. PORTIONS OF THE DUCT ARE | | | MISSING FROM PLAN. | | | | | | 16. M2.22 UNIT C2: FLOOR PLAN SHOWS 1125 CFM SUPPLY. | | | HPU-1 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 11350 CFM. | | | PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND | | | EQUIPMENT SCHEDULE. WHICH IS CORRECT? | | | | | | 17. M2.23 UNIT A: FLOOR PLAN SHOWS 1540 CFM SUPPLY. | | | HPU-4 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 2000 CFM. | | | PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND | | | EQUIPMENT SCHEDULE. WHICH IS CORRECT? | | | | | | 18. M2.23 UNIT B3: SQUARE 90 DEGREE ELBOWS NEED TURNING | | | VANES. SEE COMMENT #2. | | | | | | 19: M2.23 UNIT B4: PLEASE SHOW LOCATION OF PLENUM | | | CEILING AREA ON FLOOR PLAN. | | | | | | 20. M2.23 UNIT B4: SQUARE 90 DEGREE ELBOWS REQUIRE | | | TURNING VANES. SEE COMMENT #2. | | | | | | 21. M2.23 UNIT G: FLOOR PLAN SHOWS 635 CFM SUPPLY. | | | HPU-6 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 800 CFM. | | | PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND | | | EQUIPMENT SCHEDULE. WHICH IS CORRECT? | | | | | | 22. M2.24 UNIT A: PLEASE SEE COMMENT #17 | | | | | | 23. M2.24 UNIT A: TWO 90 DEGREE ELBOWS REQUIRE TURNING | | | VANES. PLEASE SEE COMMENT #2. | | | | | | 24. M2.24 UNIT A: PLEASE SHOW LOCATION OF PLENUM | | | CEILING AREA ON FLOOR PLAN. | | | | | | 25. M2.25 UNIT D: FLOOR PLAN SHOWS 770 CFM SUPPLY. | | | HPU-5IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 650 CFM. | | | PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND | | | EQUIPMENT SCHEDULE. WHICH IS CORRECT? | | | | | | 26. M2.26 UNIT C1; FLOOR PLAN SHOWS AN EXTRA BRANCH | | | DUCT AND REGISTER IN THE KITCHEN. PLEASE CLARIFY. | | | | | | 27. M2.26 UNIT C1: FLOOR PLAN SHOWS 1260 CFM SUPPLY. | | | HPU-1 IS SHOWN ON SCHEDULE (M5.01) TO SUPPLY 1350 CFM. | | | PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN AND | | | EQUIPMENT SCHEDULE. WHICH IS CORRECT? | | | | | | NOTE: ALL APARTMENTS SHOWING HPU-4 AT 2000 CFM WILL | | | REQUIRE DUCT SMOKE DETECTORS WITH FAN SHUT-DOWN AND | | | SHALL BE INTERCONNECTED WITH THE BUILDING FIRE ALARM | | | SYSTEM PER FBC,M 606.2.1 AND 606.4.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
27 |
Status |
F |
Date |
2007-06-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2007-06-13 |
Time |
19:12 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2007-06-13 |
Time |
19:12 |
Sent To |
|
|
| Notes |
| 2007-06-13 19:16:42 | SHOP DROWINGS AND SEALD PLANS DO NOT MATCH | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
26 |
Status |
P |
Date |
2007-06-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2007-06-04 |
Time |
18:27 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2007-06-04 |
Time |
18:27 |
Sent To |
|
|
| Notes |
| 2007-06-04 18:30:38 | 6/4/07 | | | PAGE M4.03 CAN NOT FIND CHANGES ON THE PLANS . | | | PLAN REVIEWBY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
25 |
Status |
P |
Date |
2007-05-09 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2007-05-09 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2007-05-09 |
Time |
08:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
24 |
Status |
P |
Date |
2007-04-24 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2007-04-24 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2007-04-24 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
23 |
Status |
P |
Date |
2007-02-28 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-02-28 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-02-26 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2007-02-28 15:14:00 | REVISIONS SUBMITTED 1/11/07 | | | | | | ONE PAGE DENIED: | | | | | | M2.19 - APT D2, EXHAUST DISCHARGE LOCATION IN CLOSE | | | PROXIMITY TO FRESH AIR INTAKE. SHOW COMPLIANCE WITH | | | FBC,M 401.5 AND 501.3. | | | | | | ALL OUTSTANDING PROVISOS HAVE BEEN ADDRESSED AND | | | SATISFIED WITH THESE REVISIONS. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
22 |
Status |
P |
Date |
2007-01-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2007-01-03 |
Time |
06:45 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2007-01-03 |
Time |
06:45 |
Sent To |
|
|
| Notes |
| 2007-01-03 07:21:16 | SUBMITTAL #15815.13 (BOX WALL CAPS) | | | #15060.03 HEATER FRAMES |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
21 |
Status |
P |
Date |
2006-12-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-12-29 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-12-29 |
Time |
07:32 |
Sent To |
FIRE |
|
| Notes |
| 2006-12-29 07:32:59 | SUBMITTAL / TRASH CHUTES NORTH & SOUTH |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
20 |
Status |
N |
Date |
2006-12-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-12-28 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-12-28 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2006-12-28 10:49:16 | SUBMITTAL #15815.17 - 6TH TO 15TH FLOOR (DUCTWORK SHOP | | | DRAWINGS).PER FS 481.221(1)(A) & 471.025(1), ALL | | | PLANS, SPECIFICATIONS AND REPORTS THAT ARE PREPARED OR | | | ISSUED BY A REGISTERED ARCHITECT/ENGINEER, SHALL BEAR | | | THE SIGNATURE, DATE AND SEAL OF THE SAID | | | ARCHITECT/ENGINEER OF RECORD AND FILED FOR PUBLIC | | | RECORD. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
19 |
Status |
F |
Date |
2006-11-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-11-29 |
Time |
18:37 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-11-29 |
Time |
18:37 |
Sent To |
|
|
| Notes |
| 2006-11-29 18:40:09 | SUBMITTLE MUST BE SUBMITED AS A REVISON BY ENGINEER OF | | | RECORD. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
18 |
Status |
F |
Date |
2006-11-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-11-29 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-11-29 |
Time |
17:28 |
Sent To |
|
|
| Notes |
| 2006-11-29 17:31:07 | THIS SUBMITTAL MUST BE SUBMITED AS A REVISON. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
17 |
Status |
P |
Date |
2006-11-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-11-15 |
Time |
19:51 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-11-15 |
Time |
19:51 |
Sent To |
|
|
| Notes |
| 2006-11-15 19:52:30 | SUBMITTAL #15815.18 | | | | | | PARKING LEVEL 9 DUCTWORK SHOP DRAWINGS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
16 |
Status |
P |
Date |
2006-11-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-11-15 |
Time |
19:08 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-11-15 |
Time |
19:08 |
Sent To |
|
|
| Notes |
| 2006-11-15 19:09:45 | SUBMITTAL #15815.16 | | | | | | PARKING LEVEL 7 DUCTWORK SHOP DRAWINGS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
15 |
Status |
P |
Date |
2006-11-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-11-15 |
Time |
18:53 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-11-15 |
Time |
18:52 |
Sent To |
|
|
| Notes |
| 2006-11-15 18:53:58 | SUBMITTAL #15815.15 | | | | | | PARKING LEVEL 5 DUCTWORK SHOP DRAWING |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
14 |
Status |
P |
Date |
2006-11-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-11-15 |
Time |
18:34 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-11-15 |
Time |
18:36 |
Sent To |
|
|
| Notes |
| 2006-11-15 18:35:10 | SUBMITTAL #15815.15 | | | | | | PARKING LEVEL 2 DUCTWORK SHOP DRAWING. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
13 |
Status |
F |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-11-14 |
Time |
19:23 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-11-14 |
Time |
19:23 |
Sent To |
|
|
| Notes |
| 2006-11-14 19:35:09 | SUBMITTAL # 15815.4 REC'D 9/28/06 | | | SUPPLY AND EXHAUST FANS | | | | | | ERRORS ON SUBMITTAL DATA AS FOLLOWS: | | | | | | 1. GEF-3 MODEL # ON SUBMITTAL DIFFERS FROM MODEL # ON | | | PLAN. | | | 2. GSF-P1 THRU P9 MAXIMUM SOUND LEVEL ON SUBMITTAL | | | EXCEEDS MAXIMUM SOUND LEVEL ON PLAN. | | | 3. SUBMITTALS ARE MISSING PAGES FOR SPF-5 AND SPF-6 4. | | | EF-A AND EF-B SUBMITTAL DATA DOES NOT MATCH PLAN IN ANY | | | CATEGORY. | | | 5. EF-R4 MAXIMUM SOUND LEVEL ON SUBMITTAL EXCEEDS | | | MAXIMUM SOUND LEVEL ON PLAN. | | | 6. EF-P1-3,EF-P3-1,EF-5-1,EF-5-2 MODEL #S ON SUBMITTALS | | | DO NOT MATCH PLAN. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
12 |
Status |
F |
Date |
2006-11-13 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-11-13 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-11-13 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2006-11-13 16:25:01 | PLEASE REFER TO SECTION 1203.1.1 2004 JOINTS BETWEEN | | | DIFFERENT PIPING MATERIALS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
11 |
Status |
F |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-10-04 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-10-04 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | PLAN DENIED | | | PAGE M2.02 PLEASE REFER TO SECTION 601.3 | | | FBC(M) 2001 CONTAMINATION & PREVENTION . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
10 |
Status |
P |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-09-07 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-09-06 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2006-09-07 00:00:00 | PROVISO: | | | | | | 1.PLEASE REVISE CALCULATIONS FOR THE | | | GARAGE VENTILATION.SHOW COMPLIANCE | | | WITH 2001 FBC 411.4.2 & 2001 FMC 501.4. | | | | | | 2.PLEASE INDICATE IF THE CO SENSORS | | | WILL BE TIED TO THE EMERGENCY POWER. | | | | | | 3.PLAN SHEET M2.04 - PLEASE VERIFY THE | | | LENGTH OF THE DRYER EXHAUST, DUE TO THE | | | RE-ROUTING OF THE DUCT.THIS COMMENT IS | | | IN RESPONSE TO NARRATIVE NOTE #15. | | | | | | 4.PLEASE NOTE, AIR HANDLER CLOSETS | | | SERVE AS A PLENUM AND SHALL COMPLY WITH | | | 2001 FMC 602.2.1, MATERIALS EXPOSED | | | WITHIN THE PLENUM SHALL BE | | | NON-COMBUSTIBLE.THIS INCLUDES THE DOOR | | | AND FRAME. | | | | | | 5.DRYER EXHAUST SHALL NOT EXCEED THE | | | MANUFACTURER'S SPECIFIED LENGTH OR | | | COMPLY WITH 2001 FMC 504.6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
9 |
Status |
P |
Date |
2006-06-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-06-02 |
Time |
12:08 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2006-06-02 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2006-06-02 00:00:00 | SUBMITTAL #15685.02 COOLING TOWER | | | FILTRATION SYSTEM. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
P |
Date |
2006-05-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-05-16 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-05-16 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2006-05-16 00:00:00 | SUBMITTAL - UL APPROVED DRYER BOXES; | | | RESIDENTIAL UNIT DRYERS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2006-03-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-03-17 |
Time |
07:14 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-03-17 |
Time |
07:12 |
Sent To |
|
|
| Notes |
| 2006-03-17 00:00:00 | PROVISO: | | | RESPONSE TO COMMENT #1 DATED 03/02/06: | | | 500 GALLON FUEL TANK WAS REMOVED FROM | | | PLAN SHEET A4.01 AND REPLACED WITH A | | | STORAGE ROOM. THE MECHANICAL PLAN | | | (M2.01) DOES NOT REFLECT THE NEW STORAGE | | | ROOM. | | | | | | RESPONSE TO COMMENT #2:FIRE DAMPERS | | | WERE ADDED TO THE SEPARATION BETWEEN THE | | | GARAGE AND THE DOMESTIC WATER PUMP ROOM | | | (S110).FIRE DAMPERS WERE NOT ADDED TO | | | THE SEPARATION BETWEEN ROOMS S110 & | | | S109.PLAN SHEET A4.01 INDICATES THIS | | | PENETRATION AS HAVING A 1 HOUR RATING | | | (K1 WALL TYPE), ACCORDING TO THE | | | SCHEDULE SHOWN ON PLAN SHEET A9.01. | | | | | | RESPONSE TO COMMENT #3:INSTALLATION OF | | | SHAFT SHALL NOT RESTRICT OR REDUCE THE | | | AMOUNT OF RETURN AIR REQUIRED PER 2004 | | | FMC 918.2. | | | | | | RESPONSE TO COMMENT #4:NOTE #2 ON PLAN | | | SHEET M2.02 INDICATES ALL DRYERS SHALL | | | HAVE A 200 CFM MAXIMUM EXHAUST FAN.PER | | | 2004 FMC 504.5 INSTALLATIONS EXHAUSTING | | | MORE THAN 200 CFM SHALL BE PROVIDED WITH | | | MAKEUP AIR.WHERE A CLOSET IS DESIGNED | | | FOR THE INSTALLATION OF A CLOTHES DRYER, | | | AN OPENING HAVING AN AREA OF NOT LESS | | | THAN 100 SQUARE INCHES, SHALL BE | | | PROVIDED IN THE CLOSET ENCLOSURE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2006-03-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-02-23 |
Time |
07:17 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-02-23 |
Time |
07:17 |
Sent To |
|
|
| Notes |
| 2006-03-02 00:00:00 | REVIEW CHANGED FROM PASS STATUS TO FAIL | | | STATUS.COMMENTS ARE TO BE ADDRESSED | | | AND PLANS REVISED TO REFLECT CORRECTIONS | | | PRIOR TO PERMIT ISSUANCE. | | 2006-02-23 00:00:00 | ****************PROVISO*************** | | | | | | PLEASE NOTE, PROVISO'S TO BE ADDRESSED | | | AND REVISIONS RESUBMITTED WITHIN 30 DAYS | | | OF THE DATE THE PERMIT IS ISSUED. | | | | | | 1.PLAN SHEET A4.01 PLEASE REMOVE THE | | | 500 GALLON FUEL TANK INDICATED IN THE | | | ROOM S105.PER CONVERSATION WITH MATT | | | STILL, THE REMOTE FUEL TANK WAS | | | ELIMINATED. | | | | | | 2.PLAN SHEET M2.01 MAKE UP AIR AND | | | EXHAUST FROM GARAGE THROUGH ROOM S110 TO | | | S109, NO DAMPERS INDICATED. PLAN SHEET | | | A9.01 INDICATES THESE PENETRATIONS AS 2 | | | HR & 1 HR RESPECTIVELY. | | | | | | 3.PLAN SHEET M2.01 PLEASE REMOVE NOTE | | | THAT INDICATES DRYER EXHAUST LOCATED | | | INSIDE R/A PLENUM WILL BE SEALED | | | ENCLOSURE.REPONSE FROM ENGINEER | | | INDICATES THIS IS FOR UNIT 18 ONLY. | | | PLEASE NOTE THIS SHALL BE A RATED | | | ENCLOSURE AS DRYER DUCT CONVEYS | | | COMBUSTIBLES.PLEASE PROVIDE A DETAIL | | | OF RATED ENCLOSURE AND SUBMIT UNDER | | | ALTERNATE MATERAILS & MEDTHODS 2001 FMC | | | 103.7.1. | | | | | | 4.PLAN SHEET M2.02 UNIT 1 ALSO | | | INDICATES DRYER DUCT THROUGH A PLENUM. | | | PLEASE ALSO CORRECT NOTE #2. | | | | | | 5.PLAN SHEET M2.03, 16" X 10" DUCT | | | THROUGH THE WALL AT THE ENTRANCE FROM | | | THE GARAGE, A FIRE DAMPER IS NOT | | | INDICATED AT THIS LOCATION.DRYER DUCT | | | RUNNING THROUGH RETURN AIR PLENUM UNIT 5 | | | & UNIT 8. | | | | | | 6.PLAN SHEET M2.05 SUPPLY DUCT FROM | | | MECHANICAL ROOM (HPU-P1-5), FIRE DAMPER | | | REQUIRED.ALSO DUCT INTO FIRE CONTROL | | | ROOM SHALL COMPLY WITH 2001 FMC 607.1.3 | | | ITEM #3 OR FIRE DAMPER WILL BE REQUIRED. | | | PLEASE ANNOTATE IN THE SEQUENCE OF | | | OPERATION HOW THIS UNIT WILL BE | | | UTILIZED.ACCESS DOOR REQUIRED FOR | | | MOTORIZED DAMPERS FOR SERVICE OR | | | REPLACEMENT PER 2001 FMC 306.1. | | | | | | 7.PLAN SHEET M2.07 THE MAKE-UP AIR & | | | EXHAUST FROM THE ELECTRICAL METER ROOM. | | | FIRE DAMPERS ARE NOT INDICATED ON THESE | | | PENETRATIONS. | | | | | | 8.PLAN SHEET M2.08 FIRE DAMPER | | | REQUIRED IN THE TRANSFER GRILLE BETWEEN | | | THE ENRY AREA & THE STORAGE AREA. | | | SUPPLY DUCT SHALL COMPLY WITH 2001 FMC | | | 607.1.3. | | | | | | 9.PLAN SHEET M2.09 8" X 8" TRANSFER | | | DUCT HAS DAMPERS INDICATED BUT DOES NOT | | | SPECIFY FIRE DAMPER OR FIRE/SMOKE | | | DAMPER. | | | | | | 10. PLAN SHEET M2.11 6" X 4" DUCT INTO | | | TENANT STORAGE (BY STAIR #6), SHALL | | | COMPLY WITH 2001 FMC 607.1.3 OR A FIRE | | | DAMPER WILL BE REQUIRED. | | | | | | 11. PLAN SHEET M2.12 TRANSFER GRILLE & | | | 38" X 16" DUCT PENETRATING THE WALL | | | BETWEEN THE TENANT STORAGE & STORAGE RM | | | A FIRE DAMPER IS REQUIRED.THE 4" X 4" | | | SUPPLY DUCT THROUGH THE SAME PENETRATION | | | SHALL COMPLY WITH 2001 FMC 607.1.3. | | | | | | 12. PLAN SHEET M2.13 EXHAUST DUCT | | | THROUGH RETURN AIR PLENUM.PER 2001 FMC | | | 601.3, EXHAUST DUCTS SHALL NOT EXTEND | | | INTO OR PASS THROUGH PLENUMS. | | | | | | 13. PLAN SHEET M2.15 TRANSFER GRILLE | | | INTO ROOM S121 (TENANT STORAGE) IS | | | REQUIRED TO HAVE A FIRE DAMPER.SUPPLY | | | DUCT SHALL HAVE NO OPENINGS A MINIMUM OF | | | 5 FT FROM RATED WALL, 2001 FMC 607.1.3. | | | | | | 14. PLAN SHEET M2.16, SUPPLY DUCT FROM | | | HPU-P-4-3 PENETRATES 2 RATED OPENINGS. | | | FIRE DAMPERS REQUIRED. | | | | | | 15. PLAN SHEET M2.19 THE PARTITION | | | BETWEEN ROOM L114 & THE BATHROOMS | | | INDICATE A RATED PENETRATION.ALL DUCTS | | | THAT PENETRATE THIS PARTITION IS | | | REQUIRED TO HAVE A FIRE DAMPER. | | | | | | 16. PLAN SHEET M2.20 O.A. DUCT INTO | | | RESTROOMS PENETRATES RATED CORRIDOR WALL | | | WITH NO FIRE DAMPER INDICATED.PLESAE | | | ALSO PROVIDE SEQUENCE OF OPERATION FOR | | | THIS SYSTEM. | | | | | | 17. PLAN SHEET M2.27 UNIT M, PLAN SHEET | | | M2.29 UNIT B4, & M2.32 UNIT N INDICATES | | | EXHAUSTDUCT IN RETURN AIR PLENUM. | | | PLEASE REVISE. | | | | | | 18. PLEASE NOTE, PLAN SHEET M5.01 IS | | | MISSING FROM ONE SET OF PLANS. | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
N |
Date |
2006-02-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-02-21 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-02-21 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2006-02-21 00:00:00 | SUBMITTAL - 2 HOUR ENCLOSURE IN | | | STAIRWELL #4 WAS REMOVED IN PRELIMINARY | | | DRAWING.PLEASE PROVIDE A REVISED A7.09 | | | SHEET & REVISED PLUMBING PLAN FOR THIS | | | CHANGE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2006-02-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-01-30 |
Time |
06:30 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-01-26 |
Time |
06:40 |
Sent To |
|
|
| Notes |
| 2006-01-30 00:00:00 | PLEASE CLARIFY THE FOLLOWING: | | | COMMENT #1 FROM REVIEW DATED 9-1-05; | | | PLAN SHEET M1.13 & A2.15 PAY-1 THROUGH 4 | | | ARE LOCATED IN AREA THAT IS ENCLOSED. | | | PER CONVERSATION WITH MATT, LOUVERS ARE | | | NOT INSTALLED AT OPENINGS.PLEASE SHOW | | | COMPLIANCE WITH 2001 FMC CHAPTER 11 | | | SECTIONS 1102, 1103, 1104, & 1105. | | | | | | COMMENT #5 RESPONSE INDCIATES EXHAUST | | | DUCTS THROUGH PLENUMS WILL BE SEPARATED | | | BY A NON-RATED SEALED ENCLOSURE AS SHOWN | | | IN DETAIL #2 PLANS SHEET A9.02.PLAN | | | SHEET M2.01 APPEARS TO HAVE DRYER | | | EXHAUST (COMBUSTIBLE) ALSO RUNNING | | | THROUGH PLENUM. | | | | | | ADDITIONAL COMMENTS: | | | PLAN SHEET A4.01 INDICATES 500 GAL FUEL | | | TANK PER CONVERSATION WITH MATT, THE | | | REMOTE FUEL TANK WAS ELIMATED.PLEASE | | | REMOVE FROM PLANS. | | | | | | PLAN SHEET A7.09 DETAIL FOR STAIR #4 | | | INDICATES "2 HR RATED ENCLOSURE" THROUGH | | | THE STAIRWELL.PLEASE CLARIFY WHY THIS | | | ENCLOSURE IS NECESSARY.PLEASE NOTE, | | | THE ONLY PENETRATIONS ALLOWED THROUGH OR | | | INTO A STAIRWAYS ARE THE ITEMS LISTED | | | UNDER 2001 FBC 1006.1.3.1.THE CODE | | | DOES NOT ALLOW ANY PENETRATIONS WHETHER | | | RATED OR NOT, IT STILL IS PENETRATING | | | THE STAIRWAY. | | | | | | PLEASE CLARIFY THE DESIGNATION OF FIRE | | | DAMPERS AND FIRE/SMOKE DAMPERS.SOME | | | PENETRATIONS ONLY INDICATE FIRE DAMPERS | | | WHEN IN FACT THEY SHOULD READ FIRE/SMOKE | | | DAMPERS. | | | | | | PLEASE HAVE THE ADDITIONAL COMMENTS | | | ADDRESSED WITH NEXT SUBMITTAL OR | | | REVISION. | | | | | | PLEASE ALSO SEE COMMENTS #19 THROUGH 28 | | | BY ASST FIRE MARSHALL, MIKE CARSILLO. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-01 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-09-01 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2005-09-01 00:00:00 | DENIED: | | | 1.PLAN SHEET M1.13 & A2.15, PLAN | | | INDICATES PAU-1 THROUGH 4 ARE LOCATED IN | | | AREA THAT IS ENCLOSED.PLEASE PROVIDE | | | MANUFACTURER'S INTALLATION/SUBMITALL | | | DATA FOR REVIEW.OA PACKAGE UNITS ARE | | | TYPICALLY LOCATED OUTDOORS. | | | | | | 2.PLEASE CLARIFY RATIONALE FOR THE | | | SPF-3 (STAIRWELL PRESSURIZATION) IS THIS | | | DUCTED TO THE OA LOUVER?PLAN INIDCATES | | | EF-R-2 (POOL DECK ATTIC) EXHAUSTING INTO | | | THE SAME ROOM AS PAU-1 & SPF-3.PER | | | 2001 FBC(M)501.3, MECHANICAL EXHAUST | | | SYSTEMS SHALL TERMINATE OUTDOORS AT A | | | POINT WHERE IT CANNOT BE RECIRCULATED BY | | | THE VENTILATING SYSTEM. FRESH AIR IS TO | | | BE TAKEN FROM THE OUTDOORS WHICH | | | ACCORDING TO THE DEFINITION; OUTDOORS, | | | NOT ENCLOSED; HAVING NO ROOF. | | | PLEASE VERFIY ALL AREAS WHERE OUTSIDE | | | | | | AIR LOUVERS ARE LOCATED. | | | | | | 3.PLAN SHEET M2.01, DOMESTIC WATER | | | PUMP ROOM AND THE FIRE PUMP ROOM | | | INDICATE OUTSIDE AIR FROM THE GARAGE | | | AREA & EXHAUST ALSO GOING INTO THE | | | GARAGE AREA.PER 2001 FBC(M)401.5.1, | | | OUTSIDE AIR INTAKES SHALL BE LOCATED A | | | MINIMUM OF 10FT FROM PARKING LOTS, | | | STREETS, ALLEYS, AND LOADING DOCKS. | | | | | | 4.PLAN SHEET M2.01 REFERS TO THE ARCH | | | DWGS., PLEASE SPECIFY SHEET NUMBER. | | | PROVIDE DETAIL OF THE SEALED ENCLOSURE. | | | | | | 5.PLAN SHEET M2.02 UNIT GENERAL NOTES | | | #1; AKK TOILET EXHAUST RUNNING INSIDE | | | PLENUMS SHALL BE WRAPPED.PLEASE | | | CLARIFY, ONLY DRYER EXHAUST DUCTS WILL | | | BE ENCLOSED SEPERATELY?PER 2001 FBC(M) | | | 601.3, EXHAUST DUCTS UNDER POSITIVE | | | PRESSURE & VENTING SYSTEMS SHALL NOT | | | EXTEND INTO OR PASS THROUGH PLENUMS. | | | PLANS STILL INDICATE EXHAUST DUCT | | | THROUGH PLENUMS WITHOUT THE NOTE | | | INDICATING A SEPERATE ENCLOSURE. | | | | | | 6.PLANS INDICATE DRYER BOOSTER FANS | | | WERE DELETED IN LEIU OF A SPECIFIC | | | DRYER.PLEASE NOTE, SPECIFIC DRYER TO | | | BE INSTALLED AT FINAL INSPECTION. | | | DRYERS THAT EXHAUST GREATER THAN 2,000 | | | CFM SHALL BE PROVIDED WITH MAKE-UP AIR, | | | 2001 FBC(M)504.5. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-04-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-04-20 |
Time |
06:49 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-04-19 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2005-04-19 00:00:00 | DENIED: | | | RESPONSE COMMENTS FROM REVIEW DATED | | | 1/18/05: | | | COMMENT #3 RESPONSE - SEE M2.01. PLAN | | | DOES NOT PROVIDE DISTANCES FROM EXHAUST | | | TERMINATION TO FRESH AIR INTAKES, | | | WINDOWS, DOORS, LOUVERS, ETC.PROVIDE | | | ELEVATION FROM GRADE.PLAN ALSO | | | REFERENCES PLAN SHEET M6.01 FOR DETAILS. | | | NO DETAILS PROVIDED ON SAID SHEET. | | | | | | COMMENT #4 - PROVIDE FILL PIPE | | | INFORMATION FOR THE FUEL TANK INDICATED | | | ON PLAN SHEET M2.01.PLAN SHEET A4.01 | | | INDICATES THE CAPACITY AS 500 GAL. | | | PLEASE NOTE, ADDITIONAL PERMIT REQUIRED | | | FOR FUEL. | | | | | | COMMENT #5 - PROVIDE SUBMITTALS; | | | RESPONSE INDICATES SUBMITTALS TO BE | | | PROVIDE WITH "SHOP DRAWING" REVIEW. | | | EQUIPMENT SUBMITTALS ARE TO BE SUBMITTED | | | WITH THE ENGINEERED PLANS. | | | | | | COMMENTS #10, 11 & 12 - EXHAUST DUCTS | | | ARE RUNNING THROUGH THE RETURN AIR | | | PLENUM. RESPONSE - REFER TO DRAWING | | | M2.02, NOTES INDICATE WRAPPING DUCT. | | | PLAN STILL INDICATES THE INSTALLATION OF | | | DRYER BOOSTER FANS.THIS WILL NOT BE | | | ACCEPTED UNTIL THE AN ENGINEER FROM | | | DRYER MANUFACTURER ACCEPTS THIS ASSEMBLY | | | AND VERIFIES THAT IT WILL NOT VOID THE | | | WARRANTY ON THE DRYER.DUCTS THAT CARRY | | | PRODUCTS OF COMBUSTION AND PRODUCE HEAT | | | & MOISTURE SHALL NOT RUN THROUGH THE | | | PLENUM. 2001FBC/M 504.1, 504.4, 601.3. | | | | | | COMMENT #14 - PROVIDE SUBMITTALS FOR ALL | | | EQUIPMENT - RESPONSE "CORRECTED" BUT NO | | | SUBMITTALS WERE PROVIDED. | | | | | | COMMENT #15 - O.A. CALCULATIONS - | | | RESPONSE REFER TO DRAWING M5.04. OUTSIDE | | | AIR CALCULATIONS WERE NOT PROVIDED FOR | | | THE RESIDENTIAL UNITS. | | | | | | NEW COMMENTS: | | | 16. RETURN AIR FROM THE BEDROOM AREAS | | | ARE NOT SIZED PROPERLY.PER 2001 FBC/M | | | 601.4 EXCEPTION 1, WHEN TRANSFER DUCTS | | | ARE USED FOR RETURN AIR THE RETURN AIR | | | DUCT SHALL BE A MINIMUM OF 1 1/2 TIMES | | | THE SQUARE INCHES OF THE SUPPLY AIR INTO | | | THAT SPACE.WHEN CALCULATING RETURN AIR | | | FROM THE MASTER SUITE ALL AIR INTO THE | | | MASTER SUITE IS TO BE INCLUDED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-01-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-01-18 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-01-18 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2005-01-18 00:00:00 | DENIED: | | | 1.THE FOLLOWING PLANS ARE INDICATED | | | ON THE "INDEX" BUT WERE NOT INCLUDED: | | | A1.02, A3.11, A3.12, A3.14, A3.15, | | | A3.24, A4.14, A5.01, A5.11, A6.53A, | | | A6.56A, A8.12, A8.13, A8.22, A8.23, | | | A8.41A, A8.44, A9.22, A10.01, M1.14, | | | M2.05, M2.07, M2.11, M2.19, M2.20, | | | M2.33, M2.34, M2.35, M3.02, M4.00, | | | M4.02, M4.03, M5.04, M6.01 THROUGH | | | M6.09, M7.02.PLEASE NOTE, PLAN SHEET | | | M7.02 IS MISSING BUT THERE ARE TWO | | | M7.01 SHEETS THAT ARE NOT IDENTICAL, | | | ONE | | | MAY BE JUST MISMARKED. | | | | | | 2.PLANS ARE NOT COMPLETE THEREFORE | | | ADDITIONAL COMMENTS MAY ARRISE DUE TO | | | THE RESPONSE TO 1ST REVIEW AND ANY NEW | | | DETAILS ADDED. | | | | | | 3.PLAN SHEET A1.03 GENERATOR RM. | | | PLEASE PROVIDE ELEVATION FOR THE | | | TERMINATION OF THE MUFFLER EXHAUST, | | | SHOW | | | CLEARANCES TO FRESH AIR INTAKES I.E., | | | DOORS, WINDOWS, LOUVERS, ETC. | | | | | | 4.PROVIDE DETAILS FOR VENTILATION FOR | | | THE GENERATOR ROOM.PLAN ALSO | | | INDICATES | | | A FUEL TANK.PROVIDE DETAILS FOR THE | | | CAPACITY OF THE FUEL TANK, VENTING | | | REQUIREMENTS AND FILL PIPE INFORMATION. | | | | | | 5.PROVIDE SUBMTTIALS FOR THE | | | GENERATOR | | | AND FUEL TANK. | | | | | | 6.PLAN SHEET 7.14 INDICATES TRASH | | | CHUTE WITH THE SMOKE EXHAUST IN THE | | | SAME | | | SHAFT.PLEASE CLARIFY, INDICATE RATING | | | OF SEPARATION. | | | | | | 7.PLAN SHEET M1.05 (AND SUBSEQUENT | | | SHEETS), INDICATE HPU-X OR EF-X.THESE | | | ARE NOT IDENTIFIED ON THE RESPECTIVE | | | EQUIPMENT SCHEDULES. | | | | | | 8.EF-X DOES NOT INDICATE ANY | | | TERMINATION, PLEASE CLARIFY.PLEASE | | | NOTE, PER 2001 FBC(M)503.1 ARE REMOVED | | | BY EVERY MECHANICAL EXHAUST SYSTEM | | | SHALL | | | BE DICHARGED TO THE OUTDOORS. | | | | | | 9.PLANS DO NOT INDCLUDE DETAILS FOR | | | COMMON AREAS. | | | | | | 10. PLAN SHEETS M2.02, 2.03, 2.04, ETC, | | | INDICATE DRYER EXHAUST & TOILET EXHAUST | | | PENTRATING AND RUNNING THROUGH THE | | | RETURN AIR PLENUM.PER 2001 | | | FBC(M)601.3, EXHAUST DUCTS UNDER | | | POSITIVE PRESSURE SHALL NOT EXTEND INTO | | | OR PASS THROUGH A RETURN AIR PLENUM. | | | | | | 11.NO COMBUSTIBLES ALLOWED IN THE | | | RETURN AIR PLENUM.PLEASE NOTE | | | CONSTURCITON OF THE RETURN AIR PLENUM | | | SHALL COMPLY WITH 2001 FBC(M) 603.8. THE | | | DOOR TO THE MECHANICAL CLOSET HAVING A | | | RETURN AIR PLENUM SHALL BE NON | | | COMBUSTIBLE. | | | | | | 12. PLANS INDICATE THE USE OF BOOSTER | | | FANS FOR THE DRYER.PLEASE SUBMIT ALL | | | DOCUMENTATION I.E., DRYER MANUFACTURER, | | | BOOSTER FAN SUBMITTAL AND ENGINEERING | | | DATA.THIS WILL BE REVIEWED UNDER 2001 | | | FBC 103.7.1, ALTERNATE MEANS AND | | | METHODS | | | AND WILL REQUIRE REVIEW AND APPROVAL BY | | | THE BUILDING OFFICIAL/DIRECTOR. | | | | | | 13.CW RISERS AND BRANCH LINES ARE NOT | | | SIZED.(INCOMPLETE) | | | | | | 14.PROVIDE SUBMITTALS FOR THE PUMPS, | | | COOLING TOWERS, HEAT EXCHANGERS, HEAT | | | PUMPS, EXHAUST FANS, AIR SEPARATOR, | | | EXPANSION TANK AND ALL PERTINANT VALVES | | | AND CONTROLS REQUIRED TO COMPLETE AND | | | OPERATE SYSTEM. | | | | | | 15.PROVIDE OUTSIDE AIR CALCULATIONS | | | FOR ALL COMMON AREAS AS WELL AS THE | | | RESIDENCE.SHOW COMPLIANCE WITH 2001 | | | FBC(M) TABLE 403.3 AND 402. | | | | | | 16. CONDENSATE RISER ON PLAN SHEET | | | P3.13 | | | & P3.14.PLAN SHEET P3.13 IS NOT IN | | | THE | | | SUBMITTAL AND PLAN SHEET P3.14 SHOWS A | | | SANITARY RISER. | | | | | | 17.PROVIDE PLANS FOR VENTILATION FOR | | | ALL COMMON HABITABLE AREAS AS WELL AS | | | NON HABITABLE (EQUIPMENT RMS, | | | MECHANICAL | | | ROOMS, ETC.)INDICATE ALL LOUVERS, | | | DUCTS, EXAUST AND FRESH AIR INTAKES ON | | | THE PLAN AND IDENTIFY ACCORDINGLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
39 |
Status |
P |
Date |
2008-08-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-15 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-15 |
Time |
13:34 |
Sent To |
|
|
| Notes |
| 2008-08-15 13:36:19 | REVISIONS OK--8-1/2" BY 11" REVISIONS TO SHEETS | | | P2.03, P2.61 & P6.01 (2). |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
38 |
Status |
F |
Date |
2008-08-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-07 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-07 |
Time |
14:38 |
Sent To |
E |
|
| Notes |
| 2008-08-07 14:42:05 | REVISION DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | | | | 1. SHTS LI-1, LI-2, LI-3 & LI-4 SHOW NO REVISIONS FROM | | | PREVIOUS REVIEWED PLANS.--IN THE FUTURE SUBMIT ALL | | | "REVISIONS" TO THE IRRIGATION UNDER THE IRRIGATION | | | PERMIT 08020162. SECTION 106.1.3. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
37 |
Status |
P |
Date |
2008-06-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-06-03 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-06-03 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2008-06-03 09:11:19 | SUBMITTAL APPROVED.--AIR GAP FITTING FOR TRAP | | | PRIMER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
36 |
Status |
P |
Date |
2008-04-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-04-21 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-04-21 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2008-04-21 11:04:40 | REVISION APPROVED. --WATER HEATER DETAIL SHT P601 | | | CHANGED FROM EXPANSION TANK TO EXPANSION VALVE | | | CONNECTING TO PT/PAN DRAIN LINE WITH TRAP AND AIR GAP | | | FITTING. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
35 |
Status |
P |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-06 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-06 |
Time |
12:25 |
Sent To |
|
|
| Notes |
| 2008-02-06 12:26:14 | SUBMITTALS APPROVED--WATER RECIRCULATING PUMP & | | | EXPANSION VALVE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
34 |
Status |
P |
Date |
2008-01-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-01-25 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-01-25 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2008-01-25 09:06:25 | SUBMITTALS APPROVED. TRENCH DRAINS, TERRACE/DECK | | | DRAINS, FLOOR DRAINS, ROOF DRAINS, PLANTER DRAINS, | | | SHOWER DRAINS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
33 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-04 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-04 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2007-12-04 07:45:46 | REVISION DENIED | | | REFERENCE: CITY OF WEST PALM BEACH MUNICIPAL CODE | | | | | | 1. SHTS P2.51 & P3.08 WATER LINES SHALL NOT CROSS | | | PROPERTY LINES PER ARTICLE II SECTION 90-131(E). THE | | | WATER FOR THE CABANA SHALL CONNECT TO WATER SUPPLY IN | | | THE COMMON AREA. | | | | | | 2. SHTS P2.5.1 & P3.08 A WATER HAMMER ARRESTOR IS | | | REQUIRED ON THE ICE MACHINE PER SECTION 604.9. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
32 |
Status |
P |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-04 |
Time |
07:38 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-04 |
Time |
07:38 |
Sent To |
|
|
| Notes |
| 2007-12-04 07:42:02 | REVISIONS OK FOR PARTIAL SHEET P2.57 POOL DECK CABANA | | | SINK DWV. FLOOR SINK REQUIRED FOR INDIRECT WASTE. | | | PARTIAL SHEET P3.20 SANT. RISER #82 21ST FLOOR ONLY FOR | | | THE CABANA SINK ON THE POOL DECK. FLOOR SINK REQUIRED | | | FOR INDIRECT WASTE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
31 |
Status |
P |
Date |
2007-10-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-15 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-15 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2007-10-15 09:54:55 | SUBMITTAL OK--OUTDOOR POOL SHOWER FIXTURE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
30 |
Status |
P |
Date |
2007-10-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-13 |
Time |
06:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-13 |
Time |
06:29 |
Sent To |
|
|
| Notes |
| 2007-10-13 06:30:17 | SUBMITTAL APPROVED--DECO-DRAIN DECK DRAIN |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
29 |
Status |
F |
Date |
2007-08-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-08-25 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-08-25 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2007-08-25 09:12:59 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHT P2.49 WATER SUPPLY FOR TRASH CHUTE WASH DOWN IS | | | SHOWN CONNECTING TO THE CONDENSATE RISER DIAGRAM.-- | | | REVISION #8 NOT FOUND OR APPROVED. PLEASE CLARIFY. | | | SECTION 104.2.1. | | | | | | 2. SHT P2.64 DECK DRAINS SHALL BE LOCATED AT AT THE LOW | | | POINT OF THE DECK. MANY (APPROX. 14), ARE SHOWN IN | | | LOCATIONS OTHER THAN THE LOW POINT. PLEASE CORRELATE | | | WITH THE ARCHITECT TO MAKE SURE THE DECKS DRAIN | | | PROPERLY. SECTION 1101.7. | | | | | | 3. SHTS P3.01 & P3.02 THE WATER SUPPLY LINES TO THE | | | TRASH CHUTE SHALL INCLUDE BACKFLOW PROTECTION PER | | | SECTION 608.1 AND TABLE 608.1 AND SHALL HAVE A SHUT OFF | | | VALVE AS REQUIRED IN SECTION 606.2(3). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
28 |
Status |
P |
Date |
2007-08-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-08-25 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-08-25 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2007-08-25 08:57:47 | REVISIONS OK - SHTS P2.01, P2.03 THRU P2.07, (P2.06 MAX | | | 6' FROM VENT TABLE 906.1), P2.09 THRU P2.12, P2.15, | | | (REVISION 8 NOT FOUND OR APPROVED), P2.18, P2.21, P2.23 | | | THRU P2.25, P2.27, P2.28, P2.30, P2.52, P2.62, P2.63 | | | --P3.00, P3.22, P3.32, P3.37, P3.38, P3.39, (10" | | | REQUIRED PRIOR OR BRANCH LINE TO 6"DD 2706SF PRIOR TO | | | BREAK IN LINE)--P6.01, (REVISION 6 NOT FOUND OR | | | APPROVED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
27 |
Status |
P |
Date |
2007-04-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-04-04 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-04-04 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2007-04-04 17:13:23 | SUBMITTAL OK - SHOWER DRAIN |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
26 |
Status |
P |
Date |
2007-04-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-04-04 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-04-04 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2007-04-04 17:12:36 | REVISION OK - SHTS P2.52, P2.57, P2.58, P3.00, P3.02, | | | P3.05, P3.39. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
25 |
Status |
P |
Date |
2007-03-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-06 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-06 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2007-03-06 11:54:35 | FOUR SUBMITTALS OK - TRAP PRIMER TAIL PIECES, SUMP PUMP | | | & BASIN,LAUNDRY BOXES, SHOWER PAN MATERIAL |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
24 |
Status |
F |
Date |
2007-02-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-02-22 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-02-21 |
Time |
18:48 |
Sent To |
|
|
| Notes |
| 2007-02-22 18:58:17 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHT P2.52 UNIT TYPES S1 & R ARE INDICATING SUPPLYING | | | WATER TO THE ROOF LEVEL FOR THE SHOWER, DRINKING | | | FOUNTAIN AND HOSE BIBB AT THE POOL AREA. THIS IS NOT | | | APPROVED AND THE WATER FOR COMMON AREA USAGE SHALL BE | | | SUPPLIED FROM COMMON AREA WATER SUPPLY, NOT FROM THE | | | DWELLING UNITS. SECTIONS 608.1 & 103.6 AND TABLE | | | 608.1. | | | | | | 2. SHT P2.58 4" DD & 3" SANT. LINE NOT INDICATED ON | | | PREVIOUS REVISIONS. SECOND SHOWER LINE BEHIND ELEVATORS | | | AS INDICATED ON SHT P2.52 NOT SHOWN. PLEASE CLARIFY. | | | SECTION 104.2.1. | | | | | | 3. SHT P3.05 UNIT S & S1 SHOWS SHOWER, HOSE BIBB & | | | DRINKING FOUNTAIN WATER SUPPLY FROM DWELLING UNIT. | | | WATER SUPPLY SHALL BE CONNECTED TO THE COMMON AREA | | | WATER SUPPLY. SECTIONS 608.1, 103.6 AND TABLE 608.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
23 |
Status |
P |
Date |
2007-02-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-02-22 |
Time |
18:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-02-21 |
Time |
18:45 |
Sent To |
|
|
| Notes |
| 2007-02-22 18:48:17 | REVISIONS OK.REVISION #9 ON SHEETS P201, P203, P204, | | | P205, P207, P209, P210, P212, P214, P217, P218, P220, | | | P223, P224, P225, P226, P227, P229, P233, P264, P302, | | | P322, P328, P330, P331, P333, P334, P338 & P339. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
22 |
Status |
P |
Date |
2006-12-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-12-06 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-12-06 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2006-12-06 10:42:26 | SUBMITTALS APPROVED. SOLDER PASTE, (FLUX), EXPANSION | | | TANK, BOOSTER PUMP, HAND SHOWER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
21 |
Status |
P |
Date |
2006-10-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-10-30 |
Time |
17:44 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-10-30 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2006-10-30 18:08:03 | SUBMITTALS OK | | | | | | #15455.01 GARAGE SUMP PUMP, - #15430.05.01 UNIT ELECT | | | WATER HEATERS, COMMON AREA WATER HEATERS, - #02520.02 | | | DECO DRAIN, -#15430.09 RPZV BACKFLOW PREVENTERS, - | | | 02900.01 IRRIGATION PRODUCTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
20 |
Status |
P |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-10-23 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-10-23 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2006-10-23 18:15:25 | REVISION #8 | | | | | | THE FOLLOWING SHEETS ARE OK. | | | P2.01 THRU P2.07, P2.09 THRU P2.12, P2.14, P2.16 THRU | | | P2.18, P2.20 THRU P2.35, P2.37 THRU P2.41, P2.43, | | | P2.48, P2.50, P2.52, P2.53, P2.55, P2.56, P2.59, P2.61 | | | THRU P2.64, P300 THRU P3.03, P3.16 THRU P3.19, P3.21, | | | P3.23, P3.25 THRU P3.39 & P3.41 | | | | | | THE FOLLOWING SHEETS ARE DENIED: | | | | | | P2.08, REVISIONS LEFT OF COL. LINE 12/H & BETWEEN COL. | | | LNES 11 & 12 ON COL. H. NO REVISIONS NOTED. PLEASE | | | CLARIFY. SECTION 104.2.1. - REVISION IN STAIRWELL #1 | | | APPEARS TO BE A FIRE SPRINKLER REVISION. PLEASE | | | CLARIFY. SECTION 104.2.1. | | | | | | SHT P2.15 PAN DRAIN STILL SHOWN DRAINING INTO THE | | | PARKING GARAGE. (NO CHANGE NOTED) SECTION 504.8.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
19 |
Status |
P |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-09-07 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-09-07 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2006-09-07 00:00:00 | SUBMITAL; CHARLOTTE CAST IRON PIPE TO BE | | | USED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
18 |
Status |
P |
Date |
2006-08-24 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-08-24 |
Time |
08:51 |
Rev Time |
1.00 |
| Received By |
mperson |
Date |
2006-08-24 |
Time |
08:51 |
Sent To |
PC |
|
| Notes |
| 2006-08-24 00:00:00 | 1. SUBMITTAL #15410.03.01, DUCTILE IRON | | | PIPE AND FITTINGS (OK) | | | 2. SUBMITTAL #15400.05.01, CPVC PIPE AND | | | FITTINGS (OK) | | | 3. SUBMITTAL #15450.01.01, PROPRESS | | | RIDGID SYSTEM FOR COPPER PIPE (OK) | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
17 |
Status |
N |
Date |
2006-08-23 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-08-23 |
Time |
13:38 |
Rev Time |
4.00 |
| Received By |
mperson |
Date |
2006-08-23 |
Time |
13:38 |
Sent To |
PC |
|
| Notes |
| 2006-08-23 00:00:00 | 1. SUBMITTAL #15047.01 PIPE | | | IDENTIFICATION AND VALVE TAGS (OK) | | | 2. SUBMITTAL #15181.01 CRETE SLEEVES | | | (OK) | | | 3. SUBMITTAL #15400.04 WASHING MACHINE | | | BOX (OK) | | | 4. SUBMITTAL #15410.04 DUTCH BOY SOLDER | | | MSDS SHEETS (OK) | | | 5. SUBMITTAL #15410.05 SOLDER PASTE FLUX | | | (DENIED) | | | A) THE SUBMITTAL FOR OATLY PASTE FLUX | | | #5 DOES NOT SHOW COMPLIANCE FBC-2004, | | | PLUMBING, SECTION 605.14.3 AND 605.15.4 | | | FLUX CONFORMING TO ASTM B 813 SHALL BE | | | APPLIED, PLEASE SUBMIT MANUFACTURER | | | SHEET FOR SAID SUBMITTAL CONFORMING TO | | | ASTM B 813 OR PLEASE SUBMIT ANOTHER. | | | 6. SUBMITTAL #15430.07 HOSE BIBBS (OK) | | | 7. SUBMITTAL #15430.08 TRAP PRIMERS AND | | | WATER ARRESTERS (OK) | | | "EXCEPTION" | | | A)SEMI CAST TRAP PRIMER TLPC (DENIED) | | | MORE INFORMATION REQUIRED, PLEASE SUBMIT | | | MANUFACTURER SHEETS WITH SAID SUBMITTAL | | | CONFORMING TO FBC-2004 PLUMBING, CHAPTER | | | 10. | | | 8. SUBMITTAL #15455.02 DRAINAGE PIPE AND | | | FITTINGS (OK) | | | 9. SUBMITTAL #15455.03 VENT THROUGH ROOF | | | FLASHINGS (OK) | | | 10. SUBMITTAL #15484.01 OATLY CHEMICALS | | | MSDS SHEETS (OK) | | | 11. SUBMITTAL #15484.03 HERCULES PIPE | | | DOPE (OK) | | | 12. SUBMITTAL #15499.01 PLUMBING PIPE | | | INSULATION (OK) | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
16 |
Status |
P |
Date |
2006-08-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-08-17 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-08-15 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2006-08-17 00:00:00 | SUBMITTAL APPROVED. CAST IRON PIPE, | | | FITTINGS AND COUPLINGS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
15 |
Status |
F |
Date |
2006-08-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-08-12 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-08-07 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2006-08-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. SHT P2.01 FLOOR DRAIN NOT APPROVED IN | | | THE STAIRWELL. (SEE REVIEW NOTE #1 FROM | | | REVIEW #9). NFPA 101, 2003 CHAPTER 7 | | | SECTION 7.1.3.2.1(6). | | | | | | 2. SHT P2.02 W/H PAN DRAIN NOT APPROVED | | | TO TERMINATE IN PARKING GARAGE. SECTION | | | 504.8.2. | | | | | | 3. SHT P2.03 W/H PAN DRAIN NOT APPROVED | | | TO TERMINATE IN THE PARKING GARAGE. | | | SECTION 504.8.2. - VENT REQUIRED FOR 2" | | | FLOOR DRAIN IN TRASH TERMINATION ROOM. | | | SECTION 901.2.1 AND TABLE 906.1. | | | | | | 4. SHT P2.04 REVISION #5 SHOWN ON SHEET | | | WAS NOT APPROVED. | | | | | | 5. SHT P2.06 REVISION #5 NOT APPROVED. - | | | VENT REQUIRED FOR FLOOR DRAIN THE THE | | | TRASH TERMINATION ROOM. SECTION 901.2.1 | | | AND TABLE 906.1. - UNIT 14 SHOWS NO WASH | | | MACHINE & PTR/PD LINES NOT SHOWN TO W/H. | | | PLEASE CLARIFY. SECTION 104.2.1. - FLOOR | | | DRAIN NOT APPROVED IN THE STAIRWELL. | | | NFPA 101, 2003 CHAPTER 7 SECTION | | | 7.1.3.2.1(6). | | | | | | 6. SHT P2.11 WATER HEATER PAN DRAIN NOT | | | APPROVED TO TERMINATE IN THE PARKING | | | GARAGE. SECTION 504.8.2. | | | | | | 7. SHT P2.18 UNITS H3 & HD WATER LINE | | | OFFSETS FOR RISERS W10 THRU W14 HAVE | | | BEEN DELETED, BUT RISER DESIGNATION ARE | | | STILL SHOWN. PLEASE CLARIFY. SECTION | | | 104.2.1. - WATER PIPING LAYOUTS DELETED | | | FROM UNITS V1 & HD. PLEASE CLARIFY. | | | SECTION 104.2.1. | | | | | | 8. SHT P3.27 FLOOR DRAIN NOT APPROVED IN | | | THE STAIRWELL. NFPA 101 2003. | | | | | | 9. SHT P3.28 WASTE REMOVAL SYSTEM. A | | | GATE VALVE AND CHECK VALVE ARE REQUIRED | | | ON THE DISCHARGE LINE FROM THE PUMP. | | | SECTION 712.2. - A VENT IS REQUIRED ON | | | THE 2" FLOOR DRAIN. SECTION 901.2.1 AND | | | TABLE 906.1. - NOTE READS ALL SANT. | | | PIPING TO BE RUN 1/8"/FT. 2-1/2" AND | | | SMALLER PIPE TO BE RUN 1/4"/FT PER TABLE | | | 704.1. - RISER SHOWS ONLY RISERS 10/56 | | | DOWN, BUT RISER 59 CONNECTS TO THE | | | COMMON RISER ALSO. PLEASE CORRELATE. | | | SECTION 104.2.1. | | | | | | 10. SHT P3.30 FLOOR DRAIN NOT APPROVED | | | IN STAIRWELL. NFPA 101, 2003 SECTION | | | 7.1.3.2.1(6). - VENT REQUIRED FOR FLOOR | | | DRAIN TO SPRINKLER SYSTEM DRAIN. SECTION | | | 901.2.1 AND TABLE 906.1. | | | | | | 11. SHT P3.31 FLOOR DRAIN NOT APPROVED | | | IN THE STAIRWELL. NFPA 101 2003. | | | | | | 12. SHT P3.32 WASTE REMOVAL SYSTEM. (SEE | | | COMMENT #8). | | | | | | 13. SHT P3.36 FLOOR DRAIN NOT APPROVED | | | IN THE STAIRWELL. NFPA 101, 2003 | | | | | | 14. SHT P6.01 TRASH CHUTE PIPING | | | SCHEMATIC DETAIL. INDICATE BACKFLOW | | | PROTECTION METHOD AND LOCATION. (MINIMUM | | | N-36 VACUUM BREAKER. | | | | | | 15. THE FOLLOWING SHEETS WERE APPROVED. | | | P0.01, P2.05, P2.07 THRU P2.10, P2.13 | | | THRU P2.17, P2.19 THRU P2.30, P2.32 THRU | | | P2.39, P2.41 THRU P2.54, P2.56 THRU | | | P2.60, P2.64, P3.00 THRU P3.04, P3.12, | | | P3.17 THRU PE.26, P3.29, P3.33 THRU | | | P3.35, P3.37 THRU P3.39. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
14 |
Status |
F |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-07-31 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2006-07-31 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2006-07-31 00:00:00 | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR PLUMBING PLAN REVIEW FOR THE | | | FOLLOWING SUBMITTALS: | | | | | | 1. SUBMITTAL #15400.01 THERMAL EXPANSION | | | TANK.(DENIED) | | | A) WHEN REQUIRED BY TABLE 303.4 | | | PLUMBING PRODUCTS AND MATERIALS SHALL | | | EITHER BE TESTED BY AN APPROVED | | | THIRD-PARTY TESTING AGENCY OR CERTIFIED | | | BY AN APPROVED THIRD-PARTY CERTIFICATION | | | AGENCY. | | | B) NEED PRODUCT DATA STATING THE | | | THERMAL EXPANSION TANK SUFFICIENT FOR | | | THR 80 GALLON WATER HEATER. | | | 2. SUBMITTAL #15450.03 HOT WATER | | | CIRCULATING PUMP. (DENIED) | | | A) WHEN REQUIRED BY TABLE 303.4 | | | PLUMBING PRODUCTS AND MATERIALS SHALL | | | EITHER BE TESTED BY AN APPROVED | | | THIRD-PARTY TESTING AGENCY OR CERTIFIED | | | BY AN APPROVED THIRD-PARTY CERTIFICATION | | | AGENCY. | | | | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
13 |
Status |
P |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-07-31 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2006-07-31 |
Time |
13:42 |
Sent To |
PC |
|
| Notes |
| 2006-07-31 00:00:00 | 1. SUBMITTAL #15410.02 COPPER TUBE AND | | | FITTING TYPE-L & DWV (OK) | | | 2. SUBMITTAL 315484.04 STEEL PIPE (OK) | | | 3. SUBMITTAL #15420.01 NIBCO BALL, | | | CHECK, AND GATE VALVES (OK) | | | 4. SUBMITTAL #15450.02 VICTAULIC COPPER | | | SYSTEM (OK) | | | 5. SUBMITTAL # 15400.03 WATER METER FOR | | | COOLING TOWER MAKE UP WATER (OK) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
12 |
Status |
P |
Date |
2006-07-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-21 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-21 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2006-07-21 00:00:00 | SUBMITAL #15430.01; | | | 1.SIGMA ROMAN TUB FILLER; NOT ENOUGH | | | INFORMATION. CUT SHEET SHOULD BE ON | | | MANUFACTURE'S LETTER HEAD. IS SIGMA THE | | | MANUFACTURE OR PRODUCT NAME? PRODUCT | | | MUST HAVE A BUILT IN CHECK VALVE NOT | | | SHOWN ON SHEET PROVIDED. | | | 2.PUBLIC FIXTURES; HANDICAP TOILET | | | SPECIFICATION SHEET NOT PROVIDED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
11 |
Status |
P |
Date |
2006-07-21 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-21 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-21 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2006-07-21 00:00:00 | PLUMBING SUBMITAL # 15455.01.01 OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
10 |
Status |
P |
Date |
2006-07-20 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-20 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-20 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2006-07-20 00:00:00 | SUBMITAL NO. 15444.01.01 | | | OK LESS WELL MATE TANK. | | | | | | | | | 1. CLEARITY OF DOCUMENT IS REQUIRED ; | | | LOCATION OF TANKS NOT SHOWN ON | | | PLANS. | | | WHAT MODEL NUMBER WILL BE USED. | | | PARTS OF SPEC SHEET NOT READABLE. | | | PLEASE RESUBMIT WITH THE ABOVE | | | INFORMATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
P |
Date |
2006-07-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-07-03 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-06-29 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2006-07-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | | | | | | | | | | | | | 7-4A. SHT P2.10 CHANGE 10.3 PTR RISER | | | SHOWN IS NOT SHOWN ON THE GROUND FLOOR. | | | WHERE DOES THIS RISER TERMINATE? PLEASE | | | CLARIFY. SECTION 104.2.1. | | | ***THIS SHEET HAS NOT BEEN REVISED AS | | | REQUIRED IN THE PROVISO. | | | | | | 8-4A. SHT P2.14 CHANGE 13.1 OFFSET TO | | | RISER 10 DOES NOT REFLECT THE FLOOR | | | PLAN. PLEASE CORRELATE RISER AND FLOOR | | | PLAN. SECTION 104.2.1. | | | ***THIS SHEET HAS NOT BEEN REVISED AS | | | REQUIRED IN THE PROVISO. | | | | | | 11-4A. SHT P2.35 CHANGE 31.1 OFSET NOT | | | SHOWN ON THE RISER DIAGRAM. SECTION | | | 104.2.1. | | | ***THIS SHEET HAS NOT BEEN REVISED AS | | | REQUIRED IN THE PROVISO. | | | | | | 14-4A. SHT P2.44 CHANGE 37.4 VENT PIPING | | | LAYOUT DOES NOT REFLECT RISERS 10A, 11, | | | 11A AND 12 AS INDICATED. PLEASE | | | CORRELATE RISERS AND FLOOR PLAN. SECTION | | | 104.2.1. | | | ***RESPONSE NOTED, BUT NO VENT FROM | | | RISER #11 IS SHOWN ON THE FLOOR PLAN. | | | | | | 19-4A. SHT P3.17 NEW SHEET OFFSET VENTS | | | REQUIRED ON RISER 54A AT THE 5TH FLOOR | | | OFFSET. SECTIONS 915.2 & 915.3. | | | ***RESPONSE NOTED, BUT THE UPPER OFFSET | | | VENT IS NOT SHOWN. SECTION 915.2. (ALSO | | | SEE RISER #6 UPPER OFFSET VENT NOT | | | SHOWN). | | | | | | 2-E SHTS P2.11, P2.12, & P2.15 PAN DRAIN | | | SHALL NOT TERMINATE IN THE PARKING | | | GARAGE. SECTION 504.8.2. - EXPLAIN HOW | | | DRAINING THE PTR DISCHARGE LINE INTO THE | | | GARAGE PARKING MEETS THE REQUIREMENT FOR | | | A SAFE DISCHARGE. SECTION 604.7.1. | | | ***RESPONSE NOTED, BUT PAN DRAIN LINE | | | STILL SHOWN DISCHARGING INTO THE PARKING | | | GARAGE. | | | | | | *************REVISION NOTES************* | | | | | | 1. SHT P2.01 FLOOR DRAIN IN EGRESS | | | STAIRWELL NOT APPROVED. NFPA 101, 2003 | | | CHAPTER 7 SECTION 7.1.3.2.1(6). | | | | | | 2. SHT P2.02 FLOOR DRAIN IN EGRESS | | | STAIRWELL NOT APPROVED. NFPA 101 SECTION | | | 7.1.3.2.1(6). - PAN DRAIN TO GARAGE NOT | | | APPROVED. SECTION 504.8.2. | | | | | | 3. SHT P2.03 FLOOR DRAIN IN EGRESS | | | STAIRWELL NOT APPROVED. NFPA 101 SECTION | | | 7.1.3.2.1(6). - CLOUD AND NUMBER ALL | | | REVISIONS. SECTION 104.2.1.3. | | | | | | 4. SHT P2.04 FLOOR DRAIN IN EGRESS | | | STAIRWELL NOT APPROVED. NFPA 101 SECTION | | | 7.1.3.2.1(6). - PAN DRAIN LINE TO GARAGE | | | NOT APPROVED. SECTION 504.8.2. | | | | | | 5. SHT P2.06 FLOOR DRAIN IN EGRESS | | | STAIRWELL NOT APPROVED. NFPA 101 SECTION | | | 7.1.3.2.1(6). - PAN DRAIN LINE TO GARAGE | | | NOT APPROVED. SECTION 504.8.2. | | | | | | 6. SHT P2.08 FLOOR DRAIN I EGRESS | | | STAIRWELL NOT APPROVED. NFPA 101 SECTION | | | 7.1.3.2.1(6). - VENT REQUIRED FOR FLOOR | | | DRAIN. SECTION 901.2.1. | | | | | | 7. SHT P3.27 FLOOR DRAIN IN EGRESS | | | STAIRWELL NOT APPROVED. NFPA 101 SECTION | | | 7.1.3.2.1(6). | | | | | | 8. SHT P330 2 FLOOR DRAINS IN EGRESS | | | STAIRWELL NOT APPROVED. NFPA 101 SECTION | | | 7.1.3.2.1(6).- VENT REQUIRED FOR FLOOR | | | DRAIN AT STAIRWELL #3. SECTION 901.2.1. | | | | | | 9. SHT P3.31 FLOOR DRAIN IN EGRESS | | | STAIRWELL NOT APPROVED. NFPA 101 SECTION | | | 7.1.3.2.1(6). | | | | | | 10. SHT P3.36 FLOOR DRAIN IN EGRESS | | | STAIRWELL NOT APPROVED. NFPA 101 SECTION | | | 7.1.3.2.1(6). | | | | | | 11. THE FOLLOWING SHEETS WERE APPROVED: | | | P2.05, P2.07, P2.12, P2.17, P2.26, | | | P2.27, P2.28, P2.33, P2.36, P2,39, | | | P2.4O, P2.45, P2.51, P2.61, P3.00, | | | P3.04, P3.16, P3.18, P3.19, P3.20, | | | P3.21, P3.22, P3.23, P3.24, P3.25, | | | P3.26, P3.28, P3.29, P3.32, P3.33, | | | P3.34, P3.35, P3.37, P3.40, & P3.41 | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2006-06-27 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-06-27 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-06-27 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2006-06-27 00:00:00 | SUBMITAL FOR MATCO-NORCA NO HUB CAST | | | IRON PIPE AND FITTINGS. | | | CERTIFIED BY IAMPO TO | | | ASTM A-888 & CISPI 301. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2006-06-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-06-10 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-06-10 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2006-06-10 00:00:00 | SUBMITTAL OK - CHANGED TO ALTERNATE | | | WATER HEATERS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2006-03-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-03-27 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-03-27 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2006-03-27 00:00:00 | PASSED PROVISO | | | | | | | | | THE FOLLOWING SHEETS SHALL BE REVISED | | | WITH THE COMMENTS FROM REVIEW NUMBER 5 | | | TO BE ADDRESSED. THESE COMMENTS HAVE | | | BEEN GENERATED FROM CHANGES BY THE | | | CONTRACTOR & ENGINEER. (4A) | | | SHEETS P2.04 - P2.61 - P2.06 - P2.10 - | | | P2.14 - P2.26 - P2.27 - P2.35 - P2.36 - | | | P2.44 - P2.45 - P2.61 - P3.17 - P3.22 - | | | P3.24 - P3.26 - P3.28 - P3.29 - P3.30 - | | | P3.31 - P3.32 - P3.33 - P3.34 - P3.36 - | | | P3.37 - P3.40 - P3.41. (NOTE FIRE LINE | | | DISCHARGE TO STORM SYSTEM NOT APPROVED | | | PER CITY CODE SECTION 90-203). | | | | | | THESE REVISIONS SHALL BE SUBMITTED FOR | | | REVIEW AS SOON AS POSSIBLE WITH THE | | | MAXIMUM TIME LIMIT OF 30 DAYS AFTER THE | | | PERMIT IS ISSUED FOR BLG-COM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2006-03-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-03-24 |
Time |
21:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-03-14 |
Time |
18:59 |
Sent To |
|
|
| Notes |
| 2006-03-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEW: (FROM 1ST REVIEW) | | | | | | 12) SHT A4.41 KITCHEN SINK AND JUICE BAR | | | SINK IN COMMON AREAS SHALL COMPLY WITH | | | SECTION 11-4.24 AND ALL SUBSECTIONS. | | | SUBMIT A DETAIL. RESPONSE NOTED, BUT NO | | | DETAIL WAS FOUND. - THIS WILL BE A FIELD | | | INSPECTOR APPROVAL. IF COMMON USE AREA | | | IS AVAILABLE TO TENANTS AND SUESTS, ALL | | | REQUIREMENTS OF SECTION 11-4.24 WILL BE | | | ADHERED TO. - DETAIL SUBMITTED IS FOR | | | THE DWELLING UNITS. SINKS INDICATED | | | SHALL COMPLY AS REQUIRED IN SECTION | | | 11-4.24 AND ALL SUBSECTIONS. SUBMIT A | | | DETAIL SHOWING COMPLIANCE WITH SECTIONS | | | 11-4.24.2 HEIGHT, 11-4.24.3 KNEE | | | CLEARANCE, 11-4.24.4 SINK DEPTH, | | | 11-4.24.5 CLEAR FLOOR SPACE, (FORWARD | | | APPROACH), 11-4.24.6 EXPOSED PIPES AND | | | SURFACES, AND 11-4.24.7 FAUCETS. | | | | | | NEW COMMENTS GENERATED FROM CHANGES TO | | | PLANS. 4/A: | | | 1-4A. SHEET P2.37 MISSING FROM ONE SET | | | OF PLANS. | | | 2-4A. NEW SEAL REQUIRED FOR ENGINEER | | | EFFECTIVE 1-1-06. SEE ATTACHED SHEET | | | FROM THE FLORIDA BOARD OF PROFESSIONAL | | | ENGINEERS. | | | 3-4A. SHT P2.04, CHANGE 4.1 CONDENSATE | | | DRAIN PIPING SHOWS EXTRA LINES TO UNITS | | | 11 AND 12. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | 4-4A. SHT P2.05 CHANGE 5.3 CONDENSATE | | | DRAIN FOR A/C UNIT P1-5 NOT SHOWN ON SHT | | | P2.61 AS NOTED. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | 5-4A. SHT P2-06 CHANGE 6.4 PLEASE | | | INDICATE WHAT IS DRAINING INTO THE 3" FD | | | CONNECTED TO RWL'S 7 & 8. | | | 6-4A. SHT P2.06 CHANGE 6.4 CONDENSATE | | | DRAIN 28A DOES NOT CONNECT TO RISER C14, | | | 15, 16, 24 & 26. RISER SHOWS 24A & 26A | | | CONNECTING TO THIS RISER. PLEASE | | | CORRELATE RISER AND FLOOR PLAN. SECTION | | | 104.2.1. | | | 7-4A. SHT P2.10 CHANGE 10.3 PTR RISER | | | SHOWN IS NOT SHOWN ON THE GROUND FLOOR. | | | WHERE DOES THIS RISER TERMINATE? PLEASE | | | CLARIFY. SECTION 104.2.1. | | | 8-4A. SHT P2.14 CHANGE 13.1 OFFSET TO | | | RISER 10 DOES NOT REFLECT THE FLOOR | | | PLAN. PLEASE CORRELATE RISER AND FLOOR | | | PLAN. SECTION 104.2.1. | | | 9-4A. SHT P2.26 CHANGE 24.1 HORIZONTAL | | | BRANCH SHALL NOT CONNECT WITHIN THE | | | HORIZONTAL STACK OFFSET OR WITH 2 FEET | | | ABOVE OR BELOW SUCH OFFSET. SECTION | | | 711.2 | | | 10-4A. SHT P2.27 CHANGE 25.1 NOT ALL | | | VENT PIPING IS SHOWN ON THE FLOOR PLAN. | | | SECTION 104.2.1. | | | 11-4A. SHT P2.35 CHANGE 31.1 OFSET NOT | | | SHOWN ON THE RISER DIAGRAM. SECTION | | | 104.2.1. | | | 12-4A. SHT P2.36 CHANGE 32.1 VENTING NOT | | | SHOWN FOR BATH #2. SECTION 104.2.1. | | | 13-4A. SHT 2.44 CHANGE 37.3 UNIT P2 | | | PIPING DOES NOT REFLECT RISER 59. NO | | | VENT CONNECTION FROM W/M TO L/SK AND | | | FLOOR PLAN SHOWS THE RISER BEHIND THE | | | LAUNDRY SINK. PLEASE CORRELATE RISER AND | | | FLOOR PLAN. SECTION 104.2.1. | | | 14-4A. SHT P2.44 CHANGE 37.4 VENT PIPING | | | LAYOUT DOES NOT REFLECT RISERS 10A, 11, | | | 11A AND 12 AS INDICATED. PLEASE | | | CORRELATE RISERS AND FLOOR PLAN. SECTION | | | 104.2.1. | | | 15-4A. SHT P2.45 CHANGE 38.3 NOT ALL | | | VENT PIPING WAS ADDED TO REFLECT THE | | | RISER DIAGRAM. PLEASE CORRELATE. SECTION | | | 104.2.1. | | | 16-4A. SHT P2.61 CHANGE 47.1 STORM | | | RISERS6, 7 & 8, 9 & 10, AND DOWNSTREAM | | | OF 4 & 5 SHOW 3" FLOOR DRAINS. PLEASE | | | INDICATE WHAT IS DRAINING INTO THESE | | | FD'S. SECTION 104.2.1. | | | 17-4A. SHT P2.61 CHANGE 47.1 STORM | | | PIPING DOWNSTREAM OF WHERE RWL 1 & RWL | | | 11 TIE TOGETHER SHALL BE 12". 10" SHOWN. | | | DOWNSTREAM OF THAT THE STORM DRAIN SHOWS | | | 16" PIPE BUT IS SHOWN AS 15" ON THE | | | RISER DIAGRAM. PLEASE CORRELATE. SECTION | | | 104.2.1. | | | 18-4A. SHT P2.61 CHANGE 47.1 CONDENSATE | | | LINE LEFT OF RWL 1, PLEASE INDICATE WHAT | | | RISERS ARE BEING PICKED UP BY THE 3 | | | LINES. NO INDICATION OF WHAT IS | | | CONNECTING TO THESE LINES. PLEASE | | | CLARIFY. SECTION 104.2.1. | | | 19-4A. SHT P3.17 NEW SHEET OFFSET VENTS | | | REQUIRED ON RISER 54A AT THE 5TH FLOOR | | | OFFSET. SECTIONS 915.2 & 915.3. | | | 20-4A. SHT P3.22 NEW SHEET RISERS 28 & | | | 84 LAV FOR 6TH FLOOR MISSING AND THE W/M | | | IS ON THE WRONG STACK. CORRELATE RISER | | | AND FLOOR PLAN. SECTION 104.2.1. | | | 21-4A. SHT P3.24 VENT PIPING DOES NOT | | | REFLECT THE ROOF VENT LAYOUTS. VENTING | | | ALSO INDICATE "TO 31" WHEN THE VENTS ARE | | | COMMING FROM 31. SUBMIT A RISER | | | ISOMETRIC DIAGRAM FOR THE VENT PIPING | | | SHOWING ALL PIPE SIZES, TOTAL DEVELOPED | | | LENGTH AND INDICATE FIXTURE UNITS AS | | | THEY ACCUMULATE IN THE VENT SYSTEM. | | | TABLE 916.1 | | | 22-4A. SHT P3.26 CHANGE 64.1 WATER | | | CLOSET IS NOT VENTED AS CHANGED. SECTION | | | 901.2.1. | | | 23-4A. SHT P3.28 CHANGE 66.2SANITARY | | | RISER 12 THRU 17 AND 51 DOES NOT REFLECT | | | THE FLOOR PLAN WHERE IT CONNECTS TO THE | | | BUILDING DRAIN. PLEASE CORRELATE RISER | | | AND FLOOR PLAN, AND RECHECK THE FIXTURE | | | UNITS AND PIPE SIZE. SECTION 104.2.1. | | | 24-4A. SHT P3.28 CHANGE 66.5 A | | | HORIZONTAL BRANCH SHALL NOT CONNECT | | | WITHIN THE HORIZONTAL STACK OFFSET. | | | SECTION 711.2. | | | 25-4A. SHT P3.29 CHANGE 67.1 TABLE | | | 710.1(1) 1/8"/FT SLOPE REQUIRED. | | | INDICATE ON PLANS. (ALSO SEE SHT P3.28 | | | 10 @ 2559FU). | | | 26-4A. SHT P3.29 CHANGE 67.2 DOES NOT | | | CONNECT TO THE BUILDING DRAIN IN THE | | | CORRECT LOCATION. CORRELATE RISER AND | | | FLOOR PLAN. SECTION 104.2.1. | | | 27-4A. SHT P3.30 CHANGE 68.1 INDICATE | | | SLOPE OF PIPE (1/8"/FT) FOR WHERE | | | REQUIRED. TABLE 710.1(1). | | | 28-4A. SHT P3.31 CHANGE 69.1 SHOW SLOPE | | | AS 1/8"/FT WHERE REQUIRED. TABLE | | | 710.1(1). | | | 29-4A. SHT P3.31 RISER 54 5TH FLOOR W/M | | | MISSING. PLEASE CORRELATE RISER AND | | | FLOOR PLAN. SECTION 104.2.1. | | | 30-4A. SHT P3.32 CHANGE 70.1 INDICATE | | | SLOPE AT 1/8"/FT AS REQUIRED PER TABLE | | | 710.1(1). | | | 31-4A. SHT P3.33 CHANGE 7.1 FIXTURE UNIT | | | COUNT AT 8" TO READ 1407FU, NOT 140FU AS | | | SHOWN. SECTION 104.2.1. | | | 32-4A. SHT PP3.34 CHANGE 72.1 PIPE SIZE | | | DOWNSTREAM OF RISERS 39/75 TO BE 5" | | | 203FU OR INDICATE AS 1/4"/FT SLOPE PER | | | TABLE 710.1(1). | | | 33-4A. SHT P3.36 CHANGE 74.1 SHOW SLOPE | | | OF PIPE IN BLDG DRAIN AS 1/8"/FT WHERE | | | REQUIRED PER TABLE 710.1(1). | | | 34-4A. SHT P3.36 BRANCH LINE DOWNSTREAM | | | OF RISER 37 IS 291FU 5" IS REQUIRED. | | | ALSO SEE BASE OF STACK. TABLE 710.1(1). | | | - THE SIZE OF THE DRAINAGE PIPING SHALL | | | NOT BE REDUCED IN SIZE IN THE DIRECTION | | | OF FLOW. SEE DOWNSTREAM OF RISER 37 AND | | | WHERE RISERS CONNECT TO THE BLDG DRAIN. | | | SECTION 704.2. | | | 35-4A. SHT P3.36 CHANGE 74.2 RISER 71 | | | DOES NOT CONNECT TO RISER 33. PLEASE | | | CLARIFY. SECTION 104.2.1. | | | 36-4A. SHT P3.36 CHANGE 74.3 RISER 33 IS | | | NOT SHOWN ON THIS SHEET. IT SHOULD BE | | | INDICATED THAT THE VENT FROM THE EWC AND | | | THE SINK CONNECT TO RISER 33. SECTION | | | 104.2.1. | | | 37-4A. SHT P3.37 CHANGE 75.1 PLEASE | | | CORRECT PIPE SIZE AND SQUARE FOOTAGE FOR | | | PIPE PRIOR TO AND AFTER RISERS RW1 AND | | | RW11 CONNECT. SECTION 104.2.1. AND TABLE | | | 1106.3. | | | 38-4A SHT P3.37 CHANGE 75.2 RISER STATES | | | "SEE P2.02 FOR CONT.", BUT NO PIPING | | | SHOWN ON P2.02. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | 39-4A SHT P3.40 CHANGE 78.1 SHOWS 1/4" | | | CONDENSATE LINE. SHALL BE 1-1/4" AS | | | SHOWN UPSTREAM. | | | 40-4A SHT P3.41 CHANGE 79.1 SHOWS 1" | | | CONDENSATE LINE. SHEE BE 1-1/2" AS SHOWN | | | UPSTREAM. | | | | | | NEW COMMENTS: | | | | | | 1-E. SHT P3.21 RISER 26 DOES NOT REFLECT | | | THE FLOOR PLAN. NO DRAINAGE LINE FROM | | | KITCHEN SINK AND W/M SHOWN ON THE FLOOR | | | PLAN. PLEASE CORRELATE. SECTION 104.2.1. | | | 2-E SHTS P2.11, P2.12, & P2.15 PAN DRAIN | | | SHALL NOT TERMINATE IN THE PARKING | | | GARAGE. SECTION 504.8.2. - EXPLAIN HOW | | | DRAINING THE PTR DISCHARGE LINE INTO THE | | | GARAGE PARKING MEETS THE REQUIREMENT FOR | | | A SAFE DISCHARGE. SECTION 604.7.1 | | | 3-E SHT P2.40 (NEW SHEET) NO DRAINAGE | | | SHOWN FOR THE W/M, L/SINK, OR KITCHEN | | | SINK. PLEASE CORRELATE WITH RISER | | | DIAGRAM. SECTION 104.2.1. | | | 4-E SHTS P2.59 AND P2.60 PLEASE SHOW | | | TOTAL DEVELOPED LENGTH AND TOTAL FIXTURE | | | UNITS FOR COMBINED VENTS 31 THRU 45, 46 | | | THRU 50, 65 & 78. INDICATE ALL VENT PIPE | | | SIZES. TABLE 916.1 | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2006-02-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-02-11 |
Time |
10:31 |
Rev Time |
47.00 |
| Received By |
kstevens |
Date |
2006-01-31 |
Time |
18:59 |
Sent To |
|
|
| Notes |
| 2006-02-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEW: (FROM 1ST REVIEW) | | | | | | 12) SHT A4.41 KITCHEN SINK & JUICE BAR | | | SINK IN COMMON AREAS SHALL COMPLY WITH | | | SECTION 11-4.24 AND ALL SUBSECTIONS. | | | SUBMIT A DETAIL. RESPONSE NOTED, BUT NO | | | DETAIL WAS FOUND. - THIS WILL BE A FIELD | | | INSPECTOR APPROVAL. IF COMMON USE AREA | | | IS AVAILABLE TO TENANTS AND GUESTS, ALL | | | REQUIREMENTS OF SECTION 11-4.24 WILL BE | | | ADHERED TO. - DETAIL SUBMITTED IS FOR | | | THE DWELLING UNITS. SINKS INDICATED | | | SHALL COMPLY AS REQUIRED IN SECTION | | | 11-4.24 AND ALL SUBSECTIONS. SUBMIT A | | | DETAIL SHOWING COMPLIANCE WITH SECTIONS | | | 11-4.24.2/HEIGHT, 11-4.24.3/KNEE | | | CLEARANCE, 11-4.24.4/SINK DEPTH, | | | 11-4.24.5/CLEAR FLOOR SPACE (FORWARD | | | APPROACH), 11-4.24.6/EXPOSED PIPES & | | | SURFACES, & 11-4.24.7/FAUCETS. | | | | | | SECOND REVIEW | | | **************NEW COMMENTS************** | | | | | | 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES | | | NOT REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. - RISER #60 SHOWS W/M'S & | | | KITCHEN SINKS, BUT FLOOR PLAN SHOWS | | | POWDER ROOMS 2ND, 3RD, & 4TH FLOORS. | | | PLEASE CORRELATE RISER & FLOOR PLAN. - | | | FLOOR PLAN SHOWS RISER #11 DOWN TO MEZZ. | | | LEVEL, THEN CONNECTING TO RISER 60, BUT | | | RISERS DO NOT SHOW THIS. PLEASE | | | CORRELATE RISERS AND FLOOR PLAN.- | | | THERE ARE TWO NUMBER 60 SANT. RISER | | | DIAGRAMS. (SEE SHEETS P2.03, P2.09, | | | P2.14, P2.20, P2.26, P2.32, & P2.38 FOR | | | ONE RISER #60). (SEE SHEETS P2.05, | | | P2.11, P2.16, P2.22, P2.29, P2.35, & | | | P2.41 FOR THE OTHER RISER #60). THE | | | FIRST RISER #60 SHOWS A SHOWER BATH FROM | | | THE 6TH FLOOR UP, AND THE SECOND RISER | | | #60 SHOWS W/M'S AND KITCHEN SINKS (WHICH | | | REFLECT THE RISER DIAGRAM). PLEASE | | | CLARIFY. (3.26, P3.29, P3.34, P3.35). | | | 73B) SHT P2.39 ALL UNITS SHOW PIPING TO | | | REFLECT RISERS. SECTION 104.2.1. - RISER | | | #54 DOES NOT REFLECT THE FLOOR PLAN. | | | (SEE SHT P3.21 SEALED 7-1-5) - THIS USED | | | TO SHOW CORRECT FIXTURES, BUT WAS IN | | | WRONG LOCATION. IT HAS BEEN CHANGED TO | | | BATHROOM FIXTURES. PLEASE CLARIFY. - NOW | | | SHEET HAS BEEN CHANGED AND DOES NOT | | | REFLECT THE FLOOR PLAN INDICATED IN THE | | | KEY PLAN AREA. NOT ALL UNITS ARE SHOWN. | | | - NOW RISERS 1 & 2 ARE NOT SHOWN ON SHTS | | | P2.02 & P2.08. - OFFSET SHOWN ON THE 5TH | | | FLOOR, (P2.25), AND W/C PIPING DOES NOT | | | REFLECT RISER 54A. DOES THIS THEN OFFSET | | | BACK ON THE NEXT FLOOR? | | | 94B) SHT P2.64 STORM DRAIN LINE RUNNING | | | EAST TO WEST AND CONNECTING TO RISER | | | (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE | | | LENGTH. SECTION 704.1 - NOT ADDRESSED, | | | INDICATE ON PLANS. - PIPE SIZE INCREASED | | | TO 12" BUT STILL SHOWS 1/4"FT ON ONE | | | LENGTH AND NOT ENTIRE RUN. PLEASE | | | CLARIFY. | | | 103B) SHTS P3.16 THRU P3.25 THE | | | FOLLOWING SANITARY RISER DIAGRAMS WERE | | | NOT LOCATED ON THE BUILDING DRAIN | | | ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN), | | | 10, 59, 12, 13, 14, 17, 15, 18, 19, 20, | | | 21, 22, 72, 57, 75, 40, 41, 42, 37. - | | | RISERS 12 THRU 22, 40 THRU 42 AND RISER | | | 75 HAVE NOT BEEN LOCATED ON THE BUILDING | | | DRAIN ISOMETRIC AS NOTED IN THE COMMENT | | | RESPONSE. - RISERS 19, 20, 72, & 75 | | | STILL NOT LOCATED ON BLDG DRAIN | | | ISOMETRIC. COMMENT RESPONSE REFERS TO | | | SHT P2.00. NO SHT P2.00 SUBMITTED. | | | PLEASE CLARIFY. | | | 108B) SHT P3.21 RISER 26/35 KITCHEN SINK | | | NOT SHOWN, DOES NOT REFLECT THE FLOOR | | | PLAN, WASH MACHINE/LAUNDRY SINK OFFSET | | | TO THE RIGHT SIDE NOT TO THE LEFT, | | | VENTING FROM LAV DOES NOT REFLECT FLOOR | | | PLAN. SECTION 104.2.1. - RISER 26/35 NOT | | | SPLIT AND RISER 26 NOT FOUND ABOVE THE | | | 5TH FLOOR. PLEASE CLARIFY. - RISER 26 | | | STILL DOES NOT REFLECT THE FLOOR PLAN. | | | (P3.31). VENTING FROM LAV NOT ADDRESSED. | | | RISER 26 NOT FOUND ABOVE THE 5TH FLOOR. | | | SHT P3.31 STATES "FOR CONT. SEE P3.16". | | | RISER 26 NOT FOUND ON P3.16. PLEASE | | | CLARIFY. | | | 109B) SHT P3.22 RISER 55 DOES NOT | | | REFLECT THE FLOOR PLAN. SECTION 104.2.1. | | | - STILL DOES NOT REFLECT FROM THE 6TH | | | FLOOR UP. PLEASE CORRELATE RISER & FLOOR | | | PLAN. RESPONSE INDICATES RISER 55 HAS | | | BEEN CHANGED TO RISER 55A. WHY THE | | | CHANGE. RISER IS SHOWN AS 55 & 55A. | | | RISER 55 NOT LOCATED FROM THE 6TH FLOOR | | | UP. RISER 55A DOES NOT REFLECT THE FLOOR | | | PLAN. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | THIRD REVIEW | | | **************NEW COMMENTS************** | | | | | | 4C) SHT P2.39 UNIT B3 RISER 54 FLOOR | | | PLAN DOES NOT REFLECT THE RISER DIAGRAM. | | | - RISER 55 UNIT B1 NO REVENT TO RISER 27 | | | SHOWN ON FLOOR PLAN. SECTION 104.2.1. | | | 5C) SHT P2.40 UNABLE TO LOCATE RISER 56. | | | SECTION 104.2.1. - NOW SHT P2.39 DOES | | | NOT SHOW ALL UNITS. | | | | | | 19C) SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL AND FS 553.80(2)(B). | | | THIS IS GIVEN AS A NOTICE ONLY. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | FORTH REVIEW | | | ***************NEW COMMENTS************* | | | | | | 1D. SHTS P2.05, P2.11, & P2.16 SHOW | | | RISER 76 ON ALL FLOORS FROM GROUND FLOOR | | | BASE OF STACK. SECTION 104.2.1. | | | 2D. SHTS P202 & P2.08 SHOW RISERS 1 & 2 | | | ON ALL FLOORS FROM THE GROUND FLOOR BASE | | | OF STACK. SECTION 104.2.1. | | | 3D. SHT P2.13 VENT SHOWN ON RISER | | | DIAGRAM NOT SHOWN ON THE FLOOR PLAN. | | | (RISER 3,56,57). RISER AND FLOOR PLAN | | | SHALL REFLECT EACH OTHER. SECTION | | | 104.2.1. | | | 4D. SHT P2.18 RISER 26 DOES NOT REFLECT | | | THE FLOOR PLAN AT THE W/C OF THE POWDER | | | ROOM. CORRELATE. SECTION 104.2.1. | | | 5D. SHTS P2.21, P2.22, P2.23,. P2.50 & | | | P2.52 HAVE DIFFERENT DATES ON THE SEAL, | | | DIFFERENT INFORMATION. - IT SEEMS THAT | | | THE 6-3-5 SHEETS HAVE MORE UP TO DATE | | | INFORMATION THAN THE 7-14-5 SHEETS. | | | PLEASE CLARIFY. SECTION 104.2.1. | | | 6D. SHT P2.24 NOTE IN UNIT H6 STATES | | | "SEE DRWG P2.20" PIPING LAYOUT NOT SHOWN | | | ON SHT P2.20. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | 7D. SHT P2.25 OFFSET NOT SHOWN ON THE | | | 5TH FLOOR FLOOR PLAN AT RISER 54A, BUT | | | IS SHOWN ON THE RISER DIAGRAM. PLEASE | | | CORRELATE RISER AND FLOOR PLAN. SECTION | | | 104.2.1. | | | 8D. SHT P2.28 VENTS FOR LAVS NOT SHOWN | | | IN M/B UNIT B2. SECTION 104.2.1. | | | 9D. SHT P2.33 UNIT BE NOTES STATE "FOR | | | SANT. LAYOUT SEE UNIT B3 DRAWING P2.39". | | | B3 UNIT NOT SHOWN ON P2.39. - SHOW | | | KITCHEN SINK PIPING FOR UNITS J & H. | | | SECTION 104.2.1. | | | 10D. SHT. P2.34 SHOW RISER NUMBERS WHERE | | | RISERS 30 & 32 DROP DOWN TO THE 5TH | | | FLOOR. SECTION 104.2.1. | | | 11D. SHT P2.35 UNIT B WASH MACHINE | | | OFFSET NOT SHOWN ON RISER DIAGRAM. | | | PIPING IS NOT SHOWN TO THE LAUNDRY BOX. | | | CLARIFY. SECTION 104.2.1. | | | 12D. SHT P2.39 NEW SHEET DOES NOT SHOW | | | ALL UNITS INDICATED ON THE SHEET TITLE | | | OF KEY PLAN SECTION. NEW SHEET REQUIRED. | | | SECTION 104.2.1. | | | 13D. SHT P2.43 VENT RISER "FROM" RISER | | | 53 TO RISER 5 IS SHOWN AS "TO RISER 5E". | | | THIS DOES NOT REFLECT THE RISER DIAGRAM. | | | PLEASE CLARIFY/CORRELATE. SECTION | | | 104.2.1. | | | 14D. SHT P2.60 SECONDARY ROOF DRAINS ARE | | | NOT SHOWN FOR THE DECK AREA. SECTIONS | | | 104.2.1. & 1107. | | | 15D. SHT P2.64 PIPE SIZING FOR THE NEW | | | OVERFLOW DRAINS IS NOT CORRECT. IF THEY | | | ARE SECONDARY DRAINS, THEN THEY SHALL BE | | | CALCULATED FOR ALL DRAINS IN EACH AREA | | | AND SHALL ALL BE 8". IF THEY ARE SCUPPER | | | DRAINS, ALL BUT THE AREAS THAT DRAIN | | | 3080SF & 3074SF SHALL BE 10". THE OTHER | | | TWO SHALL BE 8". PLEASE CLARIFY. SECTION | | | 1107 & ALL SUBSECTIONS. - 6" DECK DRAIN | | | 3806SF SHOWS 816SF-A + 3990SF-V WHICH | | | ADDS UP TO 4806SF & 6" DECK DRAIN 3619SF | | | SHOWS 719A + 2099SF-V WHICH ADDS UP TO | | | 2818SF. PLEASE RECHECK ADDITION ON | | | DRAINS. SECTION 104.2.1. - MUCH OF THE | | | VERTICAL CONTRIBUTION OF STORM WATER | | | WILL BE DRAINING INTO THE PLANTERS. WILL | | | THIS BECOME A NUISANCE PROBLEM. PLEASE | | | INDICATE HOW THISWILL WORK. | | | 16D. SHTS P3.01 THRU P3.16 ARE MISSING | | | FROM ONE SET OF PLANS. SECTION 104.2.1. | | | 17D. SHT P3.28 RISER 54A DOES NOT | | | REFLECT THE FLOOR PLAN ON THE 5TH FLOOR. | | | - RISER 3 VENT STACK ON THE 16TH FLOOR | | | NOT APPROVED AS SHOWN. VENT MAY NOT | | | TERMINATE ON THE 15TH FLOOR AND START | | | AGAIN ON THE 16TH FLOOR. SECTIONS | | | 104.2.1. & 903.3. | | | 18D. SHT P3.26 RISER 64 MISNUMBERED AT | | | 5TH FLOOR. (62) - INDICATE IF RISERS 48 | | | & 50 ARE TYPICAL FROM THE 16TH FLOOR | | | THRU THE 21ST FLOOR. SECTION 104.2.1. | | | 19D. SHT P3.30 RISER DIAGRAM 50 DOES NOT | | | REFLECT THE FLOOR PLAN 3RD & 4TH FLOORS. | | | PLEASE CORRELATE. (P2.21) - RISER | | | DIAGRAM 50/48 DOES NOT REFLECT THE FLOOR | | | PLAN ON THE 16TH FLOOR. RISER 50 SHOWS | | | NO FIXTURES FROM THE 16TH THRU THE 20TH | | | FLOORS. - RISER 78 IS NOT INDICATED | | | UNTIL THE 16TH FLOOR. SHOW RISER NUMBER | | | FROM THE GROUND FLOOR UP. SECTION | | | 104.2.1. | | | 20D. SHT P3.39 THE TRENCH DRAINS ON THE | | | 5TH FLOOR LANAI LEVEL ARE NOT SHOWN ON | | | THE RISER DIAGRAM FOR THE STORM. PLEASE | | | CORRELATE RISER AND FLOOR PLAN AND | | | INDICATE SQUARE FOOTAGE DRAINED BY THE | | | TRENCH DRAINS. SECTIONS 104.2.1 & 1106 | | | AND TABLE 1106.3. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-10-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-10-14 |
Time |
13:25 |
Rev Time |
64.50 |
| Received By |
kstevens |
Date |
2005-09-24 |
Time |
03:51 |
Sent To |
|
|
| Notes |
| 2005-10-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEW: | | | | | | 4) SHT A2.10 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY STORM DRAINS FOR | | | THE 5TH FLOOR OPEN AREAS PER SECTIONS | | | 1106 & 1107. SHOW THE LOCATIONS FOR ALL | | | PRIMARY AND SECONDARY DRAINS. RESPONSE | | | NOTED, BUT NO CALCULATIONS WERE | | | INDICATED OR FOUND. SECONDARY DRAINS | | | WERE NOT LOCATED FOR ALL AREAS. SECTION | | | 104.2.1. | | | 10) ALL SHEETS FOR UNITS, SHOW THE | | | OPENING SIZE FOR ALL W/C'S AND SHOW THE | | | W/C TO BE 18" FROM THE CENTER LINE OF | | | THE FIXTURE TO THE WALL WHERE | | | APPLICABLE. RESPONSE NOTED, BUT NOT ALL | | | UNITS SHOW THE REQUIREMENT. SECTION | | | 104.2.1. - ALL SHEETS WHERE NO PIPING | | | LAYOUT IS SHOWN, INDICATE WHERE THE | | | PIPING LAYOUT CAN BE LOCATED ON THAT | | | SHEET. - DOOR SIZE NOT ASKED FOR. | | | 11) ALL SHEETS FOR UNITS, INDICATE | | | SPECIFICATION "A" OR "B" AS REQUIRED BY | | | THE FHA-98 DESIGN MANUAL FOR EACH UNIT. | | | RESPONSE NOTED, BUT NOT UNITS SHOW | | | SPECIFICATION "A" OR "B". SECTION | | | 104.2.1. - STILL NOT ALL UNITS SHOW THIS | | | REQUIREMENT. | | | 12) SHT A4.41 KITCHEN SINK & JUICE BAR | | | SINK IN COMMON AREAS SHALL COMPLY WITH | | | SECTION 11-4.24 AND ALL SUBSECTIONS. | | | SUBMIT A DETAIL. RESPONSE NOTED, BUT NO | | | DETAIL WAS FOUND. - THIS WILL BE A FIELD | | | INSPECTOR APPROVAL. IF COMMON USE AREA | | | IS AVAILABLE TO TENANTS AND GUESTS, ALL | | | REQUIREMENTS OF SECTION 11-4.24 WILL BE | | | ADHERED TO. | | | 5) SUBMIT CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS PER SECTIONS 1106 | | | AND 1107 AND ALL SUBSECTIONS. SHOW THE | | | SQUARE FOOTAGE OF EACH AREA DRAINED WITH | | | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING | | | PARAPETS SHOWN ADDED TO THE ROOF AREA. | | | ALSO SHOW THE AREA OF UPPER ROOFS | | | DRAINING ONTO EACH AREA ADDED TO THE SF | | | IN CALCULATIONS. SHOW THE LOCATION OF | | | EACH SECONDARY ROOF DRAIN OR SCUPPER. - | | | RESPONSE NOTED, BUT CALCULATIONS ALL | | | SECONDARY DRAINS ECT. NOT FOUND. THESE | | | CALCULATIONS WILL BE FOR THE 5TH FLOOR | | | PRIMARY DRAINS AND SECONDARY DRAINS AS | | | WELL. - PLEASE PROVIDE CALCULATIONS. | | | 18) SHT A4.71A INDICATE LOCATION OF | | | SECONDARY ROOF DRAINS IN AREAS OF ROOF | | | WHERE SCUPPERS ARE NOT AVAILABLE. | | | SECTION 1107. - RESPONSE NOTED, BUT | | | INFORMATION NOT SHOWN. - STILL NO | | | SECONDARY ROOF DRAINS SHOWN IN AREAS | | | WITHOUT SCUPPERS. | | | 19) SHT A4.72A INDICATE LOCATION OF | | | SECONDARY ROOF DRAINS FOR DECK DRAIN | | | AREAS. SECTION 1107. RESPONSE NOTED, BUT | | | INFORMATION NOT LOCATED. - STILL NO | | | SECONDARY ROOF DRAINS SHOWN IN AREAS | | | WITHOUT SCUPPERS. | | | 20) SHT A4.73A INDICATE LOCATION OF | | | SECONDARY ROOF DRAIN FOR ALL AREAS. | | | SECTION 1107. - RESPONSE NOTED, BUT ALL | | | DRAINS NOT SHOWN. - STILL NO SECONDARY | | | ROOF DRAINS SHOWN IN AREAS WITHOUT | | | SCUPPERS. | | | 51) ALL SANT. RISERS WITH WASH MACHINES | | | REQUIRE A STANDPIPE, AND THE CLEANOUTS | | | SHALL BE LOCATED 4' ABOVE THE FLOOR FOR | | | ACCESS. SECTIONS 1002.1, 802.4, & | | | 708.10. - RESPONSE NOTED, BUT COMMENT | | | NOT ADDRESSED. - STANDPIPES FOR W/M'S | | | NOT SHOWN. | | | SECOND REVIEW | | | **************NEW COMMENTS************** | | | 1B) SHT A4.43 PLANTERS SHOW 8"H OPENINGS | | | IN PLANTER WALLS AND REFER TO SHT A8.21 | | | FOR A DETAIL. NO DETAIL FOR THESE | | | OPENINGS WAS LOCATED. PLEASE CLARIFY. | | | SECTION 104.2.1. - NO WIDTH INDICATED | | | 4B) SHTS A4.71, A4.72, A4.73, & A4.74 | | | SHOW LOCATION OF ALL SECONDARY ROOF | | | DRAINS FOR AREAS THAT DO NOT HAVE | | | SCUPPERS. SECTION 1107 - STILL AREAS | | | WITH NO SECONDARY ROOF DRAINS. | | | 6B) SHT A5.11 SHOW ELEVATION FOR W/C | | | AND LAVS IN USABLE BATHROOMS SHOWING | | | OPENINGS FOR W/C, 18" OFF WALL TO | | | CENTERLINE OF FIXTURE, AND HEIGHT OF LAV | | | COUNTER TOPS AT 34". FHA-98 DESIGN | | | MANUAL REQUIREMENT 7. - NOT ALL USABLE | | | BATHROOMS SHOW THESE REQUIREMENTS. | | | 12B) SHT P2.03 UNIT 5 RISER NUMBERS AT | | | POWDER ROOM ON THE FLOOR PLAN DO NOT | | | REFLECT NUMBERS SHOWN ON RISER DIAGRAM. | | | PLEASE CORRELATE RISER AND FLOOR PLAN. | | | SECTION 104.2.1. - RISERS 4,9,10,58,59 | | | ARE NOT SHOWN. RISER 8A ADDED, BUT NOT | | | SHOWN ON SHTS P2.03 OR P-209 WITH RISER | | | 4,9,10,58,59 (203) & 4 & 9 (209) | | | 18B) SHT P2.12 UNIT 17 OFFSET DOES NOT | | | REFLECT THE RISER DIAGRAM. PLEASE | | | CORRELATE. SECTION 104.2.1. - STILL DOES | | | NOT REFLECT. | | | 21B) SHT P2.13 UNIT V MASTER BATH | | | HORIZONTAL DRY VENT NOT APPROVED. | | | SECTIONS 905.3 & 905.4. SANT. OFFSET | | | DOES NOT REFLECT THE RISER DIAGRAM. | | | PLEASE CORRELATE. SECTION 104.2.1. - NOW | | | THE WATER CLOSET IS NOT VENTED AND THE | | | FIXTURES FROM THE FLOOR ABOVE DISCHARGE | | | THROUGH THE BATHROOM. THIS IS NOT | | | ALLOWED PER SECTIONS 908.3 & 909.1 | | | 26B) SHT P2.16 UNIT B7 DOES NOT REFLECT | | | THE RISER DIAGRAM AT THE MASTER BATH. | | | PLEASE CORRELATE. SECTION 104.2.1. - | | | VENT ROUTING STILL DOES NOT REFLECT | | | RISER DIAGRAM VENTING. | | | 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES | | | NOT REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. - RISER #60 SHOWS W/M'S & | | | KITCHEN SINKS, BUT FLOOR PLAN SHOWS | | | POWDER ROOMS 2ND, 3RD, & 4TH FLOORS. | | | PLEASE CORRELATE RISER & FLOOR PLAN. - | | | FLOOR PLAN SHOWS RISER #11 DOWN TO MEZZ. | | | LEVEL, THEN CONNECTING TO RISER 60, BUT | | | RISERS DO NOT SHOW THIS. PLEASE | | | CORRELATE RISERS AND FLOOR PLAN. | | | 58B) SHT P2.28 UNIT A SHOW ALL PIPING TO | | | REFLECT RISERS. SECTION 104.2.1. - NO | | | NOTE INDICATING WHERE PIPING CAN BE | | | LOCATED FOUND FOR UNIT "A" | | | 62B) SHT P2.32 UNIT E1 FLOOR PLAN DOES | | | NOT REFLECT THE RISER DIAGRAM. RISER 11 | | | - SHOW ALL PIPING TO REFLECT RISER | | | DIAGRAM. SECTION 104.2.1. - NO NOTE | | | INDICATING WHERE PIPING CAN BE LOCATED | | | FOUND FOR UNIT "E1". | | | 63B) SHT P2.32 UNITS D1 & G1 SHOW ALL | | | PIPING TO REFLECT THE RISER DIAGRAMS. | | | SECTION 104.2.1. - NO NOTE INDICATING | | | WHERE PIPING CAN BE LOCATED FOUND FOR | | | UNIT "G1". | | | 66B) SHT P2.35 ALL UNITS SHOW PIPING TO | | | REFLECT RISERS. SHOW THE LOCATION OF | | | RISER (45). SECTION 104.2.1. - NO NOTE | | | INDICATING WHERE PIPING CAN BE LOCATED | | | FOR UNIT "G". | | | 73B) SHT P2.39 ALL UNITS SHOW PIPING TO | | | REFLECT RISERS. SECTION 104.2.1. - RISER | | | #54 DOES NOT REFLECT THE FLOOR PLAN. | | | (SEE SHT P3.21 SEALED 7-1-5) - THIS USED | | | TO SHOW CORRECT FIXTURES, BUT WAS IN | | | WRONG LOCATION. IT HAS BEEN CHANGED TO | | | BATHROOM FIXTURES. PLEASE CLARIFY. | | | 74B) SHT P2.40 UNIT B1 SHOW PIPING TO | | | REFLECT THE RISERS. SHOW RISER LOCATION | | | AND RISER DESIGNATION NUMBERS. SECTION | | | 104.2.1. - SHOW KITCHEN SINK & W/M | | | PIPING. | | | 77B) SHT P2.44 UNIT G1 SHOW PIPING TO | | | REFLECT RISER DIAGRAMS. SECTION 104.2.1. | | | - NO NOTE INDICATING THE LOCATION OF THE | | | PIPING HAS BEEN FOUND. | | | 78B) SHT P2.45 UNIT R1 FLOOR PLAN DOES | | | NOT REFLECT THE RISER DIAGRAM. (26) | | | SECTION 104.2.1. - RISER #26 NOT FOUND. | | | 79B) SHT P2.45 UNITS B4 & G SHOW PIPING | | | TO REFLECT RISER DIAGRAMS. SECTION | | | 104.2.1. - NO NOTES INDICATING THE | | | LOCATION OF THE PIPING WAS FOUND. | | | 85B) SHT P2.55 INDICATE THE LOCATION FOR | | | THE SECONDARY ROOF DRAINS. SECTION | | | 104.2.1. - SECONDARY ROOF DRAINS IN SOME | | | LOCATIONS NOT SHOWN. | | | 88B) SHT P2.56 INDICATE LOCATION OF ALL | | | SECONDARY ROOF DRAINS. SECTIONS 104.2.1 | | | & 1107. - SECONDARY ROOF DRAINS IN SOME | | | LOCATIONS NOT SHOWN. | | | 89B) SHT P2.57 INDICATE LOCATION OF ALL | | | SECONDARY ROOF DRAINS. SECTIONS 104.2.1 | | | & 1107. - SECONDARY ROOF DRAINS IN SOME | | | LOCATIONS NOT SHOWN. | | | 93B) SHT P2.64 STORM DRAIN LAYOUT DOES | | | NOT REFLECT RISER (2)(3) IN UNIT E, | | | RISER (4)(5) IN UNIT B4, AND RISER | | | (7)(8) IN UNIT D. SECTION 104.2.1. - | | | 3"PF 80SF MISSING FROM RISER UNIT E1. | | | 94B) SHT P2.64 STORM DRAIN LINE RUNNING | | | EAST TO WEST AND CONNECTING TO RISER | | | (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE | | | LENGTH. SECTION 704.1 - NOT ADDRESSED, | | | INDICATE ON PLANS. | | | 103B) SHTS P3.16 THRU P3.25 THE | | | FOLLOWING SANITARY RISER DIAGRAMS WERE | | | NOT LOCATED ON THE BUILDING DRAIN | | | ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN), | | | 10, 59, 12, 13, 14, 17, 15, 18, 19, 20, | | | 21, 22, 72, 57, 75, 40, 41, 42, 37. - | | | RISERS 12 THRU 22, 40 THRU 42 AND RISER | | | 75 HAVE NOT BEEN LOCATED ON THE BUILDING | | | DRAIN ISOMETRIC AS NOTED IN THE COMMENT | | | RESPONSE. | | | 108B) SHT P3.21 RISER 26/35 KITCHEN SINK | | | NOT SHOWN, DOES NOT REFLECT THE FLOOR | | | PLAN, WASH MACHINE/LAUNDRY SINK OFFSET | | | TO THE RIGHT SIDE NOT TO THE LEFT, | | | VENTING FROM LAV DOES NOT REFLECT FLOOR | | | PLAN. SECTION 104.2.1. - RISER 26/35 NOT | | | SPLIT AND RISER 26 NOT FOUND ABOVE THE | | | 5TH FLOOR. PLEASE CLARIFY. | | | 109B) SHT P3.22 RISER 55 DOES NOT | | | REFLECT THE FLOOR PLAN. SECTION 104.2.1. | | | - STILL DOES NOT REFLECT FROM THE 6TH | | | FLOOR UP. PLEASE CORRELATE RISER & FLOOR | | | PLAN. | | | 121B) SHT P3.28 RISER 68 INDICATE SHEET | | | NUMBER FOR CONTINUATION OF RISER. | | | SECTION 104.2.1. - RISER 54 OFFSET VENT | | | REQUIRED, AND 4 FU MAX. ON 2" WET VENT. | | | SECTION 915 AND TABLE 909.3. - RISER 7 | | | OFFSET VENTS REQUIRED. UPPER OFFSET, | | | (2ND FLOOR),VENT SHALL BE CONNECTED TO | | | THE VERTICAL STACK NOT THE BRANCH LINE. | | | SECTION 915. - RISER 3, 56, 57 OFFSET | | | VENT REQUIRED SECTION 915 - DOES NOT | | | SHOW KITCHEN SINK 5TH FLOOR SECTION | | | 104.2.1. - MISLABELED AS RISER 51 - | | | SECTION 104.2.1. - WASH MACHINE GROUND | | | FLOOR REQUIRES THAT CLEANOUT IS 4' AFF. | | | SECTION 104.2.1. - RISERS 4, 9, 58, 9 AT | | | BASE, HORIZONTAL DRY VENT NOT APPROVED. | | | SECTIONS 905.3 & 905.4. VENT SHALL BE | | | CONNECTED AT THE BASE OF THE STACK. | | | SECTION 903.4 - THESE RISERS ARE | | | INDICATED AS 4, 9, 10, 58, & 59. PLEASE | | | CORRELATE. SECTION 104.2.1. - OFFSET | | | SHALL CONNECT ABOVE THE BRANCH LINE. FIG | | | 915.2. - RISER 58 SOME FIXTURES ARE | | | MISLABELED, ON NOT LABELED AT ALL. | | | SECTION 104.2.1. - VENT TERMINATION FOR | | | 2ND FLOOR BATHROOM NOT SHOWN. SECTION | | | 104.2.1. - RISER 4/9 MISLABELED FIXTURE. | | | SECTION 104.2.1, WASH MACHINES, KITCHEN | | | SINKS, AND BATHROOMS SHALL NOT DRAIN | | | PAST THE VENT FOR THE BATHROOM ON THE | | | MEZZ. LEVEL. SECTION 908.3 - DWV FOR THE | | | MEZZ. LEVEL DOES NOT REFLECT THE FLOOR | | | PLAN. SECTION 104.2.1. - SECOND FLOOR | | | POWDER ROOM DOES NOT REFLECT THE FLOOR | | | PLAN. SECTION 104.2.1. - BATHROOM GROUPS | | | FOR THE THIRD AND FORTH FLOORS NOT SHOWN | | | ON RISER 4. SECTION 104.2.1. ** - WASH | | | MACHINE GROUND FLOOR STILL REQUIRES THE | | | CLEANOUT TO BE LOCATED 4' ABOVE THE | | | FLOOR. - NEW RISER 8A VENT SHOWS | | | CONNECTING INTO RISER 8. THIS IS NOT | | | REFLECTED ON RISER 8. PLEASE CORRELATE | | | RISERS. | | | 124B) SHT P3.30 RISER 77 DOES NOT | | | REFLECT THE FLOOR PLAN, WASH MACHINES | | | NOT SHOWN. - RISER 47 OFFSET VENTS | | | REQUIRED, 5TH FLOOR DOES NOT REFLECT THE | | | FLOOR PLAN, NO KITCHEN SINK SHOWN. - | | | RISER 49 OFFSET VENTS REQUIRED. - RISER | | | 49 DOES NOT REFLECT THE FLOOR PLAN, LAV | | | MISSING IN MASTER BATH 2ND FLOOR, OFFSET | | | VENTS REQUIRED, 2ND FLOOR INDICATED | | | DOWNSTREAM OF MEZZ. - RISER 65 DOES NOT | | | REFLECT THE FLOOR PLAN. - RISER 50 DOES | | | NOT REFLECT THE FLOOR PLAN ON THE 2ND | | | FLOOR AND THE 5TH FLOOR, OFFSET VENTS | | | REQUIRED, FIXTURE MISLABELED, 4 FU MAX. | | | ON 2" WET VENT, DRY HORIZONTAL VENT NOT | | | APPROVED. SECTIONS 104.2.1, 915, & TABLE | | | 909.3 - 5TH FLOOR UPPER OFFSET VENT NOT | | | SHOWN. | | | 125B) SHT P3.31 RISER 24 DOES NOT | | | REFLECT THE FLOOR PLAN 4TH FLOOR, 4 FU | | | MAX. ON 2" WET VENT, OFFSET VENTS | | | REQUIRED, DRY HORIZONTAL VENT NOT | | | APPROVED. - RISER 54 OFFSET VENTS | | | REQUIRED. - RISER 26 OFFSET VENTS | | | REQUIRED. - RISER 27/28 OFFSET VENTS | | | REQUIRED, 4 FU MAX. ON 2" WET VENT, DOES | | | NOT REFLECT THE FLOOR PLAN AT/BELOW MEZZ | | | LEVEL. - RISER 55/28/84 RISER | | | DESIGNATION NUMBER DOES NOT REFLECT THE | | | FLOOR PLAN, (SHOW AS 55/73/84), PLEASE | | | CLARIFY, DOES NOT REFLECT THE FLOOR PLAN | | | NO WASH MACHINES SHOWN, OFFSET VENTS | | | REQUIRED. SECTIONS 104.2.1, 915, & TABLE | | | 909.3. ** - RISER 27/28 STILL DOES NOT | | | REFLECT THE FLOOR PLAN AS THE MEZZ. | | | LEVEL. | | | 130B) SHT P3.36 GROUND FLOOR DOES NOT | | | REFLECT THE FLOOR PLAN, (FD IN TRASH | | | ROOM NOT SHOWN, KITCHEN SINK - W/M AREA, | | | AND VENTING), INDICATE WHY 10 FU FOR | | | CLEANOUT AT END OF RUN. - RISER 71 | | | OFFSET VENTS REQUIRED, NO PIPING FOR 3RD | | | FLOOR, NO KITCHEN SINK ON 4TH FLOOR, | | | INDICATE FLOOR LEVEL TOP OF RISER. - | | | RISER 37 VENT STACK SHALL CONNECT AT THE | | | BASE OF THE STACK, NO HORIZONTAL DRY | | | VENT, OFFSET VENT REQUIRED, 5TH FLOOR | | | DOES NOT REFLECT THE FLOOR PLAN, FIXTURE | | | MISLABELED AND 4 FU MAX. ON 2" WET VENT | | | 4TH FLOOR, UNABLE TO FIND CONTINUATION | | | OF RISER. - RISER 36 SHOWS TYPICAL | | | PIPING FOR 3RD & 4TH FLOORS, BUT FLOOR | | | PLANS ARE DIFFERENT. SECTIONS 104.2.1. | | | 915, 903.4, 905.3, 905.4. ** - FLOOR | | | DRAIN IN TRASH ROOM NOT SHOWN IN THE | | | KITCHEN SINK - W/M AREA. ALSO SHOW | | | VENTING. - STILL UNABLE TO LOCATE | | | CONTINUATION OF RISER 37. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | **************NEW COMMENTS************** | | | | | | 1C) SHT P2.03 RISER 8A NOT SHOWN WITH | | | RISERS 4,9,10,58,59. SECTION 104.2.1. | | | 2C) SHT P2.09 RISER 8A NOT SHOWN WITH | | | RISERS 4,9,10,58,59 DOWN & 4,9 UP. | | | SECTION 104.2.1. | | | 3C) ALL SHEETS FOR UNITS, WHERE THERE IS | | | NO PIPING SHOWN IN ANY PORTION OF A | | | UNIT, INDICATE, (AT UNIT ON PLANS), | | | WHERE THE CAN BE LOCATED. THIS INCLUDES | | | ALL PIPING SYSTEMS. SECTION 104.2.1. | | | 4C) SHT P2.39 UNIT B3 RISER 54 FLOOR | | | PLAN DOES NOT REFLECT THE RISER DIAGRAM. | | | - RISER 55 UNIT B1 NO REVENT TO RISER 27 | | | SHOWN ON FLOOR PLAN. SECTION 104.2.1. | | | 5C) SHT P2.40 UNABLE TO LOCATE RISER 56. | | | SECTION 104.2.1. | | | 6C) SHT P3.16 RISER 5/53 INDICATES ON | | | 15TH FLOOR VENT FROM RISER 5, BUT NO | | | CONNECTION AT 15TH FLOOR SHOWN ON RISER | | | 5. PLEASE CLARIFY. SECTION 104.2.1. | | | 7C) SHT P3.19 RISERS 14 & 17 OFFSET | | | VENTS REQUIRED. SECTION 915. - SHOWS | | | 15TH FLOOR W/M ABOVE 21ST FLOOR. PLEASE | | | CLARIFY. SECTION 104.2.1. | | | 8C) SHT P3.28 RISER 1,2,68 & 54,4 | | | CONNECT VENT STACK TO BASE OF SANT. | | | STACK. SECTION 903.4. - RISER 7 3RD & | | | 4TH FLOOR TUB MISLABELED AS SHOWER. | | | SECTION 104.2.1. - RISER 8 VENT STACK | | | CHANGED TO SOLID LINE OF A SANT. LINE. | | | SECTION 104.2.1. - RISER 56 UPPER OFFSET | | | VENT REQUIRED AT 5TH FLOOR OFFSET. | | | SECTION 915. - RISER 8A VENT SHOWN TO | | | TIE INTO RISER 8 VENT LINE. NOT SHOWN ON | | | RISER 8 VENT. PLEASE CLARIFY. | | | 9C) SHT P3.30 RISER 48/50 CONNECT VENT | | | STACK TO THE BASE OF THE SANT. STACK. | | | SECTION 903.5. - UPPER OFFSET VENT | | | REQUIRED 5TH FLOOR. SECTION 915. - RISER | | | 48 NOT SHOWN ON PREVIOUS FLOOR PLAN | | | SHEET FROM GROUND FLOOR THRU 2ND FLOOR. | | | - INDICATE WHAT SHEET THE CONTINUATION | | | OF EACH RISER WILL BE FOUND ON. SECTION | | | 104.2.1. | | | 10C) SHT P3.21 WERE IS THE CONTINUATION | | | OF RISERS 33, 74, & 81 ABOVE THE 6TH | | | FLOOR AND RISER 71 BELOW THE 6TH FLOOR? | | | SECTION 104.2.1. | | | 11C) SHT P3.31 RISERS 26 & 27/28 CONNECT | | | VENT STACKS TO BASE OF SANT. STACK. | | | SECTION 903.5. | | | 12C) SHT P2.34 OFFSET SHOWN ON FLOOR | | | PLAN TO RISERS 81 & 74. PLEASE INDICATE | | | WHERE ON THE RISER DIAGRAM THAT IS | | | LOCATED. SECTION 104.2.1. | | | 13C) SHT P3.23 OFFSET AT MEZZ. LEVEL FOR | | | RISER 33/55 DOES NOT REFLECT THE FLOOR | | | PLAN. SECTION 104.2.1. - REVENTS FROM | | | W/M TO RISER 33/55 ARE MISLABELED. | | | SECTION 104.2.1. - REVENT AT TOP OF | | | STACK "A" INDICATE "TO STACK VENT 56", | | | BUT NOT SHOWN ON STACK VENT 56. PLEASE | | | CLARIFY. SECTION 104.2.1. | | | 14C)SHT P3.34 RISER 61 CONNECT VENT | | | STACK TO BASE OF SANT. STACK. SECTION | | | 903.5. - GROUND FLOOR DOES NOT REFLECT | | | THE FLOOR PLAN. SECTION 104.2.1. - RISER | | | INDICATES TYPICAL 3RD THRU 5TH FLOORS, | | | BUT RISER 43 ONLY CONNECTS ON THE 5TH | | | FLOOR. INDICATE ON PLANS. - RISER 43 | | | CONNECT VENT STACK TO BASE OF SANT. | | | STACK. 903.5 - DOES NOT REFLECT FLOOR | | | PLAN. - SECTION 104.2.1. - TABLE 909.3 | | | INDICATE ALL PIPE SIZES. - RISER 64 | | | RISER INDICATES TYPICAL 3RD THRU 5TH | | | FLOOR, BUT RISER 45 ONLY CONNECTS ON 5TH | | | FLOOR. INDICATE ON PLANS. SECTION | | | 104.2.1. | | | 15C) SHT P3.35 SHOW PIPE SIZES FOR | | | TYPECAL 3RD/4TH FLOORS RISER 38.- MAX 10 | | | BRANCH INTERVALS TO THE RELIEF VENT. | | | RECHECK INTERVALS. SECTION 914. | | | 16C) SHT P3.37 INDICATE 1/4"FT SLOPE | | | ENTIRE RUN UPSTREAM OF 10"@1/4"FT SLOPE | | | 22306SF (RWL 4/5) & UPSTREAM OF 15" | | | 62210SF (RWL 2/3) TO HORIZONTAL OFFSET. | | | SECTION 704.1. | | | 17C) SHT P3.38 3" PD 80SF MISSING FROM | | | RWL 2/3 AT 5TH FLOOR. SECTION 104.2.1. | | | 18C) SHT P3.39 INDICATE 1/4"/FT SLOPE | | | THE ENTIRE RUN UPSTREAM OF 15"@1/4"/FT | | | 54050SF UP TO HORIZONTAL OFFSET | | | DOWNSTREAM OF RWL 7. SECTION 704.1. | | | 19C) SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL AND FS 553.80(2)(B). | | | THIS IS GIVEN AS A NOTICE ONLY. | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-05-09 |
Time |
17:16 |
Rev Time |
99.00 |
| Received By |
kstevens |
Date |
2005-05-09 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2005-05-09 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | | | | FROM PREVIOUS REVIEW: | | | 3) SHT A2.10 SUBMIT CALCULATIONS FOR | | | MINIMUM FACILITIES PER TABLES 1003.2 AND | | | 403.1. SHOW SQUARE FEET FOR EACH COMMON | | | USE ROOM. RESPONSE NOTED, BUT NOT | | | INDICATED WHERE I CAN FIND THE | | | CALCULATIONS. SECTION 104.2.1. | | | 4) SHT A2.10 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY STORM DRAINS FOR | | | THE 5TH FLOOR OPEN AREAS PER SECTIONS | | | 1106 & 1107. SHOW THE LOCATIONS FOR ALL | | | PRIMARY AND SECONDARY DRAINS. RESPONSE | | | NOTED, BUT NO CALCULATIONS WERE | | | INDICATED OR FOUND. SECONDARY DRAINS | | | WERE NOT LOCATED FOR ALL AREAS. SECTION | | | 104.2.1. | | | 10) ALL SHEETS FOR UNITS, SHOW THE | | | OPENING SIZE FOR ALL W/C'S AND SHOW THE | | | W/C TO BE 18" FROM THE CENTER LINE OF | | | THE FIXTURE TO THE WALL WHERE | | | APPLICABLE. RESPONSE NOTED, BUT NOT ALL | | | UNITS SHOW THE REQUIREMENT. SECTION | | | 104.2.1. | | | 11) ALL SHEETS FOR UNITS, INDICATE | | | SPECIFICATION "A" OR "B" AS REQUIRED BY | | | THE FHA-98 DESIGN MANUAL FOR EACH UNIT. | | | RESPONSE NOTED, BUT NOT UNITS SHOW | | | SPECIFICATION "A" OR "B". SECTION | | | 104.2.1. | | | 12) SHT A4.41 KITCHEN SINK & JUICE BAR | | | SINK IN COMMON AREAS SHALL COMPLY WITH | | | SECTION 11-4.24 AND ALL SUBSECTIONS. | | | SUBMIT A DETAIL. RESPONSE NOTED, BUT NO | | | DETAIL WAS FOUND. | | | 13) SHT A4.41 SUBMIT A DETAIL FOR THE | | | TOILET ROOM IN THE COMMON AREA. SHOW | | | COMPLIANCE WITH SECTIONS 11-4.16, | | | 11-4.19, 11-4.21, & 11-4.22 AND ALL | | | SUBSECTIONS. ALSO SEE SECTION 2 OF THE | | | FHA-98 DESIGN MANUAL. RESPONSE NOTED, | | | BUT THE FOLLOWING INFORMATION IS NOT | | | SHOWN ON THE DETAIL: | | | A. FLUSH CONTROLS 11-4.16.5 | | | B. EXPOSED PIPES & SURFACES 11-4.19.4 | | | C. FAUCETS 11-4.19.5 | | | D. CURBS 11-4.21.7 | | | 14) SHT A4.41 A DRINKING FOUNTAIN IS | | | REQUIRED PER TABLE 403.1 FOR THE COMMON | | | AREA. SUBMIT A DETAIL SHOWING COMPLIANCE | | | WITH SECTION 11-4.15 AND ALL SUBSECTIONS | | | ALSO SEE SECTION 410.1. RESPONSE NOTED, | | | BUT NOT INDICATED WHERE DETAIL IS | | | LOCATED. | | | 15) SUBMIT CALCULATIONS FOR PRIMARY AND | | | SECONDARY ROOF DRAINS PER SECTIONS 1106 | | | AND 1107 AND ALL SUBSECTIONS. SHOW THE | | | SQUARE FOOTAGE OF EACH AREA DRAINED WITH | | | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING | | | PARAPETS SHOWN ADDED TO THE ROOF AREA. | | | ALSO SHOW THE AREA OF UPPER ROOFS | | | DRAINING ONTO EACH AREA ADDED TO THE SF | | | IN CALCULATIONS. SHOW THE LOCATION OF | | | EACH SECONDARY ROOF DRAIN OR SCUPPER. - | | | RESPONSE NOTED, BUT CALCULATIONS ALL | | | SECONDARY DRAINS ECT. NOT FOUND. THESE | | | CALCULATIONS WILL BE FOR THE 5TH FLOOR | | | PRIMARY DRAINS AND SECONDARY DRAINS AS | | | WELL. - PLEASE PROVIDE CALCULATIONS. | | | 18) SHT A4.71A INDICATE LOCATION OF | | | SECONDARY ROOF DRAINS IN AREAS OF ROOF | | | WHERE SCUPPERS ARE NOT AVAILABLE. | | | SECTION 1107. - RESPONSE NOTED, BUT | | | INFORMATION NOT SHOWN. | | | 19) SHT A4.72A INDICATE LOCATION OF | | | SECONDARY ROOF DRAINS FOR DECK DRAIN | | | AREAS. SECTION 1107. RESPONSE NOTED, BUT | | | INFORMATION NOT LOCATED. | | | 20) SHT A4.73A INDICATE LOCATION OF | | | SECONDARY ROOF DRAIN FOR ALL AREAS. | | | SECTION 1107. - RESPONSE NOTED, BUT ALL | | | DRAINS NOT SHOWN. | | | 32) SHEETS FOR UNIT TYPES ARE INCOMPLETE | | | AND REQUIRE MORE INFORMATION. SOME | | | SHEETS SHOW SANT., VENTS, WATER, COND., | | | T/P, OR ANOTHER UNIDENTIFIED LINE, BUT | | | ALL DO NOT HAVE ALL INFORMATION | | | REQUIRED. - RESPONSE NOTED, BUT | | | INFORMATION IS STILL MISSING ON MANY | | | SHEETS. SOME EXAMPLES NO SANT SHOWN TO | | | WASH MACHINE IN UNIT 1, RISER NUMBERS | | | ARE MISSING OR MISLABLED, SOME SANT. | | | LINES NOT SHOWN, WATER LINES MISSING, | | | ECT. RECHECK ALL UNITS TO MAKE SURE ALL | | | PIPING, (SANT., WATER, COND, VENTS, P/T, | | | PAN DRAINS, WASTE ARMS ECT ARE SHOWN) | | | 33) SHOW STACK NUMBERS FOR EACH STACK IN | | | ALL UNIT SHEETS. SECTION 104.2.1. | | | RESPONSE NOTED, BUT NOT ALL STACK | | | NUMBERS ARE SHOWN, AND SOME STACK | | | NUMBERS ARE NOT IN THE CORRECT LOCATION | | | AS THE STACK. | | | 45) SHT P2.21 UNITS A1 & VV1 BATH #2 | | | SHOWERS ARE NOT VENTED. SECTION 901.2.1 | | | UNIT A1 WHAT TYPE OF VENT IS KITCHEN | | | SINK UTILIZING. SECTION 901.2.1 - | | | RESPONSE NOTED, BUT SHOWERS ARE NOT | | | VENTED AND NO INFORMATION FOR THE | | | KITCHEN VENT HAS BEEN GIVEN. | | | 46) SHT P2.39 HAS A REFERENCE TO SHT P2. | | | NO SHT P2 IS LOCATED. PLEASE CLARIFY | | | SECTION 104.2.1. - RESPONSE NOTED, BUT | | | THE REFERENCE IS STILL THERE. IN FACT | | | THERE ARE AT LEAST 2 REFERENCES TO SHEET | | | P2 ON THIS SHEET. | | | 50) SHT P2.57 WOMEN'S BATHROOM DOES NOT | | | REFLECT THE SANT. RISER DIAGRAM. W/C IN | | | WOMEN'S STALL MAX. 10' FROM POINT OF | | | VENT TABLE 906.1. INDICATE THE USE OF | | | THE FLOOR DRAIN FOR FIXTURE NEXT TO | | | SHOWER IN THE MEN'S BATHROOM. SECTION | | | 104.2.1. - RESPONSE NOTED, BUT THE W/C | | | IN THE WOMEN'S BATHROOM DOES NOT SHOW | | | SANITARY PIPING FROM THE BRANCH LINE TO | | | THE WATER CLOSET TO THE LAV AS SHOWN ON | | | THE RISER DIAGRAM. ALSO THE FLOOR DRAIN | | | IN THE MEN'S BATHROOM HAS NOT BEEN | | | EXPLAINED BY THE RESPONSE "DRAWING | | | CORRECTED" | | | 51) ALL SANT. RISERS WITH WASH MACHINES | | | REQUIRE A STANDPIPE, AND THE CLEANOUTS | | | SHALL BE LOCATED 4' ABOVE THE FLOOR FOR | | | ACCESS. SECTIONS 1002.1, 802.4, & | | | 708.10. - RESPONSE NOTED, BUT COMMENT | | | NOT ADDRESSED. | | | 64) BACKFLOW PROTECTION REQUIRED FOR THE | | | POOL MAKE UP WATER. SUBMIT A DETAIL. | | | SECTION 608.13.2. - RESPONSE NOTED, BUT | | | BACKFLOW PROTECTION IS NOT IN THE SCOPE | | | OF THE POOL CONTRACTOR UNLESS IT IS AN | | | AIR GAP AT THE COLLECTOR TANK. PLEASE | | | INDICATE METHOD OF BACKFLOW PROTECTION. | | | 65) BECAUSE PLANS ARE INCOMPLETE, MORE | | | COMMENTS MAY BE FORTHCOMING WHEN PLANS | | | ARE RESUBMITTED. - PLEASE RETURN THE | | | PLUMBING PLANS WITH THE RED LINE NOTES | | | WHEN RESUBMITTING TO HELP REVIEWING | | | PLANS FOR THE SECOND TIME. - RESPONSE | | | NOTED, BUT PLANS WERE NOT RETURNED. I | | | WILL BE KEEPING THE RED LINE SET OF | | | PLANS TO ASSIST IN THE THIRD REVIEW. | | | ALSO IT SEEM THAT THE PLANS ARE NOT 100% | | | COMPLETE AT THIS TIME AND MORE COMMENTS | | | MAY FOLLOW ON THE THIRD REVIEW. | | | **************NEW COMMENTS************** | | | 1B) SHT A4.43 PLANTERS SHOW 8"H OPENINGS | | | IN PLANTER WALLS AND REFER TO SHT A8.21 | | | FOR A DETAIL. NO DETAIL FOR THESE | | | OPENINGS WAS LOCATED. PLEASE CLARIFY. | | | SECTION 104.2.1. | | | 2B) SHTS A4.41 THRU AR.44A SUBMIT DETAIL | | | FOR SCUPPERS FOR TERRACES ON THE 5TH | | | FLOOR. INDICATE HEIGHT AND WIDTH. | | | SECTIONS 1107 & 104.2.1. - DETAILS #1 | | | PRECAST SCUPPER ON S.W. CORNER NOT SHOWN | | | WHERE INDICATOR IS POINTING. WHERE IS A | | | CUT SECTION FOR AREA ADJACENT TO | | | STAIRWAY #5. NO SECONDARY DRAIN/SCUPPER | | | SHOWN. SECTION 1107. - ALSO DETAIL #2 NO | | | SECONDARY DRAIN/SCUPPER IN OPPOSITE | | | CORNER. | | | 3B) A4.60 SUBMIT DETAIL FOR SCUPPERS ON | | | THE 16TH FLOOR. SECTION 1107 | | | 4B) SHTS A4.71, A4.72, A4.73, & A4.74 | | | SHOW LOCATION OF ALL SECONDARY ROOF | | | DRAINS FOR AREAS THAT DO NOT HAVE | | | SCUPPERS. SECTION 1107 | | | 5B) SHT A5.11 DETAIL #9 INDICATES A | | | SHOWER BATHROOM DETAIL NOT SHOWN ON THE | | | DETAIL INDEX. PLEASE CLARIFY | | | 6B) SHT A5.11 SHOW ELEVATION FOR W/C | | | AND LAVS IN USABLE BATHROOMS SHOWING | | | OPENINGS FOR W/C, 18" OFF WALL TO | | | CENTERLINE OF FIXTURE, AND HEIGHT OF LAV | | | COUNTER TOPS AT 34". FHA-98 DESIGN | | | MANUAL REQUIREMENT 7. | | | 7B) SHTS P2.01 & P2.02 PAN DRAIN LINES | | | FROM THE WATER HEATERS SHALL TERMINATE | | | OVER A SUITABLY LOCATED INDIRECT WASTE | | | RECEPTOR OR FLOOR SINK OR EXTEND TO THE | | | EXTERIOR OF THE BUILDING AND TERMINATE | | | NOT LESS THA 6" OR MORE THAN 24" ABOVE | | | THE ADJACENT GROUND SURFACE GROUND | | | SURFACE. SECTION 504.8.2. | | | 8B) SHT P2.02 NO SANT. SHOWN TO WASH | | | MACHINE FOR UNIT #1. SECTION 104.2.1. | | | 9B) SHT P2.02 FLOOR PLAN DOES NOT | | | REFLECT THE RISER DIAGRAM 54/68 AT UNIT | | | #3. SECTION 104.2.1. | | | 10B) SHT P2.02 UNIT #4 INDICATE RISER | | | NUMBERS AT BATH #1. SECTION 104.2.1. | | | 11B) SHT P2.02UNIT #4 RISER NUMBERS BY | | | THE WASH MACHINE DO NOT REFLECT THE | | | NUMBERS SHOWN ON THE RISER DIAGRAM. | | | PLEASE CORRELATE RISER & FLOOR PLAN | | | RISER DESIGNATION. SECTION 104.2.1. | | | 12B) SHT P2.03 UNIT 5 RISER NUMBERS AT | | | POWDER ROOM ON THE FLOOR PLAN DO NOT | | | REFLECT NUMBERS SHOWN ON RISER DIAGRAM. | | | PLEASE CORRELATE RISER AND FLOOR PLAN. | | | SECTION 104.2.1. | | | 13B) SHT P2.03 UNIT 7 FLOOR PLAN DOES | | | NOT REFLECT THE RISER DIAG. PLEASE | | | CORRELATE RISER WITH FLOOR PLAN. SECTION | | | 104.2.1 | | | 14B) SHT P2.06 RISER SOUTH OF ELEVATOR & | | | STAIRWAY DOES NOT SHOW RISER #60. | | | SECTION 104.2.1. | | | 15B) SHT P2.08 UNIT 3 BATH #2 DOES NOT | | | REFLECT THE RISER DIAGRAM. PLEASE | | | CORRELATE RISER & FLOOR PLAN. SECTION | | | 104.2.1. | | | 16B) SHT P2.10 UNIT 10 BATHROOM DOES NOT | | | REFLECT THE RISER DIAGRAM. PLEASE | | | CORRELATE. SECTION 104.2.1. | | | 17B) SHT P2.12 UNIT 19 OFFSET FOR BATH | | | #2 DOES NOT REFLECT THE RISER DIAGRAM. | | | PLEASE CORRELATE. SECTION 104.2.1. | | | 18B) SHT P2.12 UNIT 17 OFFSET DOES NOT | | | REFLECT THE RISER DIAGRAM. PLEASE | | | CORRELATE. SECTION 104.2.1. | | | 19B) SHT P2.12 UNIT 15 IDENTIFY RISER. - | | | FLOOR PLAN DOES NOT REFLECT THE RISER | | | DIAGRAM. PLEASE CORRELATE. SEC 104.2.1. | | | 20B) UNIT 14 BATH #2 VENT DOES NOT | | | REFLECT RISER DIAGRAM. PLEASE CORRELATE. | | | SECTION 104.2.1. | | | 21B) SHT P2.13 UNIT V MASTER BATH | | | HORIZONTAL DRY VENT NOT APPROVED. | | | SECTIONS 905.3 & 905.4. SANT. OFFSET | | | DOES NOT REFLECT THE RISER DIAGRAM. | | | PLEASE CORRELATE. SECTION 104.2.1. | | | 22B) SHT P2.13 UNIT VV VENT AND SANT. | | | STACK DO NOT REFLECT THE RISER DIAGRAM. | | | VENT IS NOT SHOWN. PLEASE CORRELATE. | | | SECTION 104.2.1. | | | 23B) SHT P2.14 UNIT H7 WHICH RISER DOES | | | KITCHEN SINK DRAIN INTO. RISER DOES NOT | | | REFLECT FLOOR PLAN AT THE WASH MACHINE. | | | PLEASE CORRELATE. SECTION 104.2.1. | | | 24B) SHT P2.14 UNITS H1 & H2 DO NOT | | | REFLECT THE DIAGRAM. PLEASE CORRELATE. | | | SECTION 104.2.1. | | | 25B) UNIT P2.15 UNIT VV1 MASTER BATH | | | DOES NOT REFLECT THE RISER DIAGRAM, AND | | | DRY HORIZONTAL VENT IS NOT APPROVED. | | | COMMENT RESPONSE INDICATES THAT OFFSET | | | UNDER TUB IS BELOW THE FLOOR, BUT FLOOR | | | PLAN SHOWS THE VENT FROM THE WATER | | | CLOSET ABOVE THE SLAB CONNECTING INTO | | | THIS VENT OFFSET. PLEASE CLARIFY. PLEASE | | | CORRELATE. SECTIONS 905.3, 905.4 & | | | 104.2.1. | | | 26B) SHT P2.16 UNIT B7 DOES NOT REFLECT | | | THE RISER DIAGRAM AT THE MASTER BATH. | | | PLEASE CORRELATE. SECTION 104.2.1. | | | 27B) SHT P2.17 UNIT H4 TUB DRAIN LINE IS | | | NOT SHOWN ON THE RISER DIAGRAM. PLEASE | | | CORRELATE. SECTION 104.2.1. | | | 28B) SHT P2.17 UNIT H3 POWDER ROOM RISER | | | SHOWN AS SOIL STACK ON THE RISER | | | DIAGRAM, BUT AS A VENT STACK ON THE | | | FLOOR PLAN. - MASTER BATH LINE TO RIGHT | | | OF WATER CLOSET, (RISER 37), SHOWN AS | | | THE VENT LINE ON THE RISER DIAGRAM, | | | WHICH WILL MAKE IT A DRY HORIZONTAL | | | VENT. THIS IS NOT APPROVED BY SECTIONS | | | 905.3 & 905.4 - BATH #2 VENT NOT SHOWN | | | ON THE FLOOR PLAN. SECTION 104.2.1. | | | 29B) SHT P2.18 UNIT V1 HORIZONTAL DRY | | | VENT NOT APPROVED IN MASTER BATH AND | | | POWDER ROOM. SECTIONS 905.3 & 905.4. | | | 30B) SHT P2.18 UNIT HD POWDER ROOM LAV | | | ARM NOT SHOWN. SECTION 104.2.1. | | | 31B) SHT P2.18 UNIT H3 VENT LINE FOR | | | MASTER BATH NOT SHOWN. SECTION 104.2.1. | | | 32B) SHT P2.18 UNIT H6 VENT LINE FOR | | | MASTER BATH NOT SHOWN. SECTION 104.2.1. | | | 33B) SHT P2.19 UNIT V VENT LAYOUT DOES | | | NOT REFLECT THE RISER DIAGRAM AT MASTER | | | BATH. SECTION 104.2.1. | | | 34B) SHT P2.19 UNIT VV STACK & VENT FOR | | | KITCHEN MISSING. SECTION 104.2.1. | | | 35B) SHT P2.19 UNIT B8 NO SANITARY OR | | | VENT TO KITCHEN SINK. SECTION 104.2.1. | | | 36B) SHT P2.20 UNIT HH1 PIPING FOR | | | KITCHEN SINK & POWDER ROOM MISSING. | | | SECTION 104.2.1. | | | 37B) SHT P2.20 UNIT H7 INDICATE RISER | | | NUMBER AND SANITARY DOES NOT REFLECT THE | | | RISER DIAGRAM. SECTION 104.2.1. | | | 38B) SHT P2.20 UNIT H2 SHOW DWV PIPING | | | TO REFLECT RISER DIAGRAM. SECTION | | | 104.2.1. | | | 38B) SHT P2.21 UNIT H1 SHOW DWV PIPING | | | TO REFLECT RISER DIAGRAM. SECTION | | | 104.2.1. | | | 39B) SHT P2.21 UNIT A1 BATH #2 DOES NOT | | | REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. | | | 40B) SHT P2.22 UNIT B7 SHOW DWV PIPING | | | TO REFLECT RISER DIAGRAM. SECTION | | | 104.2.1. | | | 41B) SHT P2.22 UNIT B7 BATH #2 DOES NOT | | | REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. | | | 42B) SHT P2.23 UNIT A1 SHOW DWV PIPING | | | TO REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. | | | 43B) SHT P2.24 UNIT HD SHOW DWV PIPING | | | TO REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. | | | 44B) SHT P2.24 UNIT H3 SHOW DWV PIPING | | | TO REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. - RISER (24) DESIGNATION IN | | | WRONG LOCATION. SECTION 104.2.1. | | | 45B) SHT P2.24 UNIT H6 SHOW DWV PIPING | | | TO REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1 | | | 46B) SHT P2.25 UNIT L INDICATE THE | | | LOCATION OF THE CONTINUATION OF RISERS | | | (67) & (68). SECTION 104.2.1. | | | 47B) SHT P2.25 UNIT C OFFSET DOES NOT | | | REFLECT THE RISER DIAGRAM, (6). SECTION | | | 104.2.1. | | | 48B) SHT P2.25 UNIT C SHOW RISER | | | DESIGNATION NUMBER FOR RISER #5 BY W/M. | | | SECTION 104.2.1. | | | 49B) SHT P2.25 UNIT C RWL #1 DOES NOT | | | REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. | | | 50B) SHT P2.25 UNIT B5 RISER (3)(56)(57) | | | DOES NOT REFLECT THE RISER DIAGRAM. | | | (KITCHEN DRAIN ARM NOT SHOWN). SECTION | | | 104.2.1. | | | 51B) SHT P2.25 UNIT B6 MASTER BATH DOES | | | NOT REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. | | | 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES | | | NOT REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. | | | 53B) SHT P2.26 UNIT E1 RWL #4 DOES NOT | | | REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. | | | 54B) SHT P2.27 UNIT A BATH #2 NOT VENTED | | | NOT SANITARY TO RISER (25). SECTION | | | 104.2.1. | | | 55B) SHT P2.27 UNIT B1 SHOW RISER | | | DESIGNATION NUMBERS FOR (29)(30)(31)(32) | | | - VENT LINES NOT SHOWN - NO SANT. DRAIN | | | LINE TO KITCHEN SINK. SECTION 104.2.1. | | | 56B) SHT P2.28 UNIT B1 NO VENT LINES | | | SHOWN. SECTION 104.2.1. | | | 57B) SHT P2.28 UNIT B2 VENT LINES TO | | | REFLECT RISERS DIAGRAM BATH #2 - MASTER | | | BATH LAV DRAIN CONNECTION TO BRANCH IS | | | SHOWN INSTALLED AGAINST THE FLOW. | | | SECTION 706.3. - RISER #37 DESIGNATION | | | SHOWN IN THE WRONG LOCATIONS. PLACE NEXT | | | TO RISER. SECTION 104.2.1. | | | 58B) SHT P2.28 UNIT A SHOW ALL PIPING TO | | | REFLECT RISERS. SECTION 104.2.1. | | | 59B) SHT P2.29 BOTH UNITS SHOW ALL | | | PIPING TO REFLECT THE RISER DIAGRAMS. | | | SECTION 104.2.1. | | | 60B) SHT P2.30 UNIT A BATH #2 DOES NOT | | | REFLECT RISER DIAGRAM. SECTION 104.2.1. | | | 61B) SHT P2.31 ALL UNITS SHOW PIPING TO | | | REFLECT RISER DIAGRAMS. SECTION 104.2.1. | | | 62B) SHT P2.32 UNIT E1 FLOOR PLAN DOES | | | NOT REFLECT THE RISER DIAGRAM. RISER 11 | | | - SHOW ALL PIPING TO REFLECT RISER | | | DIAGRAM. SECTION 104.2.1. | | | 63B) SHT P2.32 UNITS D1 & G1 SHOW ALL | | | PIPING TO REFLECT THE RISER DIAGRAMS. | | | SECTION 104.2.1. | | | 64B) SHT P2.33 ALL UNITS SHOW PIPING TO | | | REFLECT RISER DIAGRAMS. SECTION 104.2.1. | | | 65B) SHT P2.34 ALL UNITS SHOW PIPING TO | | | REFLECT RISER DIAGRAMS. SECTION 104.2.1. | | | 66B) SHT P2.35 ALL UNITS SHOW PIPING TO | | | REFLECT RISERS. SHOW THE LOCATION OF | | | RISER (45). SECTION 104.2.1. | | | 67B) SHT P2.36 ALL UNITS SHOW PIPING TO | | | REFLECT RISER DIAGRAMS. SECTION 104.2.1. | | | 68B) SHT P2.36 UNIT C1 SHOW RISER | | | DESIGNATION #(49). SECTION 104.2.1. | | | 69B) UNIT E KITCHEN PIPING DOES NOT | | | REFLECT THE RISER DIAGRAM. SECTION | | | 104.2.1. | | | 70B) SHT P2.36 UNIT E KITCHEN SINK | | | PIPING DOES NOT REFLECT THE RISER | | | DIAGRAM. SECTION 104.2.1 | | | 71B) SHT P2.37B) UNITS B5 & B6 MASTER | | | BATH DOES NOT REFLECT THE RISER DIAGRAM | | | AT LAVS NEXT TO THE WATER CLOSET. | | | SECTION 104.2.1. | | | 72B) SHT P2.38B) UNIT G1 SHOW PIPING TO | | | REFLECT RISERS. SECTION 104.2.1. | | | 73B) SHT P2.39 ALL UNITS SHOW PIPING TO | | | REFLECT RISERS. SECTION 104.2.1. | | | 74B) SHT P2.40 UNIT B1 SHOW PIPING TO | | | REFLECT THE RISERS. SHOW RISER LOCATION | | | AND RISER DESIGNATION NUMBERS. SECTION | | | 104.2.1. | | | 75B) SHT P2.41 UNITS B & D SHOW PIPING | | | TO REFLECT THE RISERS. SECTION 104.2.1. | | | 76B) SHT P2.42 UNIT A SHOW PIPING TO | | | REFLECT RISER DIAGRAMS. SECTION 104.2.1. | | | 77B) SHT P2.44 UNIT G1 SHOW PIPING TO | | | REFLECT RISER DIAGRAMS. SECTION 104.2.1. | | | 78B) SHT P2.45 UNIT R1 FLOOR PLAN DOES | | | NOT REFLECT THE RISER DIAGRAM. (26) | | | SECTION 104.2.1. | | | 79B) SHT P2.45 UNITS B4 & G SHOW PIPING | | | TO REFLECT RISER DIAGRAMS. SECTION | | | 104.2.1. | | | 80B) SHT P2.46 UNIT P SHOW PIPING TO | | | REFLECT RISER (36) AT BATH #2. SECTION | | | 104.2.1. | | | 81B) SHT P2.47 UNIT U DOES NOT REFLECT | | | RISER (44) BATH #2. SECTION 104.2.1. | | | 82B) SHT P2.48 SHOW PIPING FOR 2 LAVS. | | | SECTION 104.2.1. | | | 83B) SHT P2.51 SHOW ALL PIPING TO | | | REFLECT RISER DIAGRAMS. SECTION 104.2.1. | | | 84B) SHT P2.52 UNIT R VENT MISSING BATH | | | #2 LAV. SECTION 104.2.1. | | | 85B) SHT P2.55 INDICATE THE LOCATION FOR | | | THE SECONDARY ROOF DRAINS. SECTION | | | 104.2.1. | | | 86B) SHT P2.55 OVERFLOW SHALL DRAIN FROM | | | COOLING TOWERS TO STORM - DRAIN FROM | | | COOLING TOWERS TO SANITARY. PLEASE | | | INDICATE ON PLANS. SECTION 104.2.1. | | | 87B) SHT P2.55 5" REQUIRED FOR STORM | | | DRAIN DOWNSTREAM OF 4" R.D. @ 520 SF. | | | TABLE 1106.3 | | | 88B) SHT P2.56 INDICATE LOCATION OF ALL | | | SECONDARY ROOF DRAINS. SECTIONS 104.2.1 | | | & 1107. | | | 89B) SHT P2.57 INDICATE LOCATION OF ALL | | | SECONDARY ROOF DRAINS. SECTIONS 104.2.1 | | | & 1107. | | | 90B) SHT P2.57 RWL #6 3" PD @ 80 SF NOES | | | NOT REFLECT THE RISER DIAGRAM. - 3" PD @ | | | 50 SF DOES NOT REFLECT THE RISER | | | DIAGRAM. - PIPE SIZE DOWNSTREAM OF 3" PD | | | @ 280 SF REQUIRES A MINIMUM OF 5" PIPE. | | | SECTION 104.2.1. | | | 91B) SHT P2.57 FLOOR PLAN DOES NOT | | | REFLECT THE RISER DIAGRAM. WOMENS HDCP | | | TOILET LAV. RISER (25) IS A DRY VENT | | | WHICH IS NOT APPROVED. SECTIONS 905.3 & | | | 905.4. SECTION 104.2.1. | | | 92B) SHT P2.58 RWL #7 DOWNSTREAM OF 3"DD | | | @ 125 SF 5" REQUIRED. 4" SHOWN. TABLE | | | 1106.3. - 3"PD @ 220 SF DOES NOT REFLECT | | | RISER SHOWN AND 211 SF. PLEASE CORRELATE | | | - RWL #8 3"PD @ 88 SF DOES NOT REFLECT | | | RISER DIAGRAM SHOW AS 80 SF. PLEASE | | | CORRELATE. SECTION 104.2.1. | | | 93B) SHT P2.64 STORM DRAIN LAYOUT DOES | | | NOT REFLECT RISER (2)(3) IN UNIT E, | | | RISER (4)(5) IN UNIT B4, AND RISER | | | (7)(8) IN UNIT D. SECTION 104.2.1. | | | 94B) SHT P2.64 STORM DRAIN LINE RUNNING | | | EAST TO WEST AND CONNECTING TO RISER | | | (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE | | | LENGTH. SECTION 704.1 | | | 95B) SHT P3.00 SANITARY RISER DIAGRAM | | | FOR TOILET ROOM POOL DECK, DRY | | | HORIZONTAL VENT NOT APPROVED. SECTIONS | | | 905.3 & 905.4. | | | 96B) SHT P3.00 SANITARY RISER DIAGRAM | | | FOR TOILET ROOM POOL DECK, FLOOR DRAIN | | | BY SHOWER NOT APPROVED FOR INDIRECT | | | WASTE. A FLOOR SINK OR HUB DRAIN IS | | | REQUIRED. SECTIONS 802.3 & 802.3.2. | | | 97B) SHT P3.00 DOMESTIC WATER RISER | | | DIAGRAM POOL DECK TOILET ROOMS, LANAI | | | LEVEL PUBLIC TOILETS, & WATER RISER | | | DIAGRAM 5TH FLOOR PUBLIC AREA, THE WATER | | | SUPPLY IS MISSING FOR 1 LAV, POOL DECK | | | TOILET ROOMS, AND FULL OPEN VALVES ARE | | | REQUIRED ON EVERY WATER DOWN-FEED PIPE. | | | SECTION 606.1(4). | | | 98B) SHTS P3.05 THRU P3.15 ALL UNIT | | | WATER RISER DIAGRAMS, DELETE ALL AIR | | | CHAMBERS AS THEY ARE NOT APPROVED. | | | SECTION 604.9. - ALL WATER LINES TO THE | | | REF. ICE MAKERS ARE REQUIRED TO HAVE A | | | WATER HAMMER ARRESTOR. SECTION 604.9. - | | | SOME UNITS SHOW A SEPARATE WATER LINE TO | | | THE REF. ICE MAKER AND A LINE UNDER THE | | | KITCHEN SINK FOR THE REF. ICE MAKER. | | | PLEASE CLARIFY AS THEY DO NOT REFLECT | | | THE RISER DIAGRAM IN MOST CASES. RISERS | | | DO NOT SHOW TWO LINES TO THE ICE MAKER. | | | - SOME RISERS ARE MISSING SUPPLY LINES | | | TO FIXTURES. SECTION 104.2.1. | | | 99B) SHT P3.16 RISER (4) OFFSET ON 16TH | | | FLOOR NOT SHOWN. - RISER (5) TIE OFFSET | | | VENT IN AS SHOWN IN EXAMPLE ON ATTACHED | | | SHEET. (FIG. 915.2) | | | 100B) SHT P3.17 RISER (6) TIE OFFSET | | | VENT IN AS SHOWN IN EXAMPLE ON ATTACHED | | | SHEET. (FIG 915.2) - 5TH FLOOR PLUMBING | | | PIPE LAYOUT IS NOT SHOWN. (DIFFERENT | | | FROM TYPICAL - NO OFFSET SHOWN. - RISER | | | (56) TIE OFFSET VENT IN AS SHOWN IN | | | EXAMPLE ON ATTACHED SHEET. (FIG. 915.2) | | | - RISER (8) DOES NOT REFLECT THE FLOOR | | | PLAN 5TH FLOOR, NOR DOES IT REFLECT THE | | | FLOOR PLAN 6TH THRU 15TH FLOORS FOR THE | | | LAVS. SECTION 104.2.1. | | | 101B) SHT P3.18 RISER (69) DOES NOT | | | REFLECT THE FLOOR PLAN. - RISER (10) | | | DOES NOT REFLECT THE FLOOR PLAN 17TH | | | THRU 21ST FLOOR. - RISER (11) NO BRANCH | | | LINES FROM 4TH FLOOR THRU 15TH FLOOR. | | | PLEASE CLARIFY. SECTION 104.2.1. | | | 102B) ALL RISERS THAT HAVE OFFSET VENTS, | | | THE CONNECTION FROM THE WASTE STACK TO | | | THE VENT STACKS SHALL BE BY AN UPRIGHT | | | WYE FITTING NOT A SANT. TEE FITTING AS | | | SHOWN ON SOME RISERS, AND SHALL BE | | | CONNECTED ON THE UPPER SECTION AS SHOWN | | | ON ATTACHED SHEET. (FIG 915.2) | | | 103B) SHTS P3.16 THRU P3.25 THE | | | FOLLOWING SANITARY RISER DIAGRAMS WERE | | | NOT LOCATED ON THE BUILDING DRAIN | | | ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN), | | | 10, 59, 12, 13, 14, 17, 15, 18, 19, 20, | | | 21, 22, 72, 57, 75, 40, 41, 42, 37. | | | 104B) SHTS P3.27 THRU P3.36 THE | | | FOLLOWING RISERS SHOWN ON THE BUILDING | | | DRAIN ISOMETRIC WERE NOT FOUND. 67, 83, | | | 53, 68, 51, 58, 84, 85, 86, 87, 89, 90, | | | 91, 84, 73, 33, 34, 74, 81. | | | 105B) SHT P3.21 SANT. RISER #23 SHOWS | | | 16TH FLOOR THEN 15TH FLOOR ABOVE. | | | 106B) SHT P3.21 SANT. RISERS 24, & 36 | | | INDICATE WHERE RISER #25 WILL CONNECT TO | | | THESE RISERS. PLEASE CLARIFY AND | | | INDICATE SHEET WHERE RISER #25 IS | | | LOCATED. SECTION 104.2.1. | | | 107B) SHT P3.21 RISER 71 INDICATE HOW | | | RISER 54 TIES INTO THIS RISER AS IT IS | | | NOT SHOWN ON PREVIOUS FLOORS. SECTION | | | 104.2.1. | | | 108B) SHT P3.21 RISER 26/35 KITCHEN SINK | | | NOT SHOWN, DOES NOT REFLECT THE FLOOR | | | PLAN, WASH MACHINE/LAUNDRY SINK OFFSET | | | TO THE RIGHT SIDE NOT TO THE LEFT, | | | VENTING FROM LAV DOES NOT REFLECT FLOOR | | | PLAN. SECTION 104.2.1. | | | 109B) SHT P3.22 RISER 55 DOES NOT | | | REFLECT THE FLOOR PLAN. SECTION 104.2.1. | | | 110B) SHT P3.22 RISER 29/31, RISER 31 | | | NOT SHOWN 17TH TO 21ST FLOOR, MASTER | | | BATH 15TH FLOOR MAXIMUM 4 FU MAX. ON 2" | | | WET VENT. SECTION 104.2.1. & TABLE | | | 909.3. | | | 111B) SHT P3.22 RISER 30/32 ONLY RISER | | | 32 IS SHOWN. NO 16TH FLOOR PIPING SHOWN, | | | ONLY 4 FU MAX. ON 2" WET VENT. SECTION | | | 104.2.1. AND TABLE 909.3. | | | 112B) SHT P3.23 RISER 38 ONLY 4 FU MAX. | | | ON 2" WET VENT. TABLE 909.3. | | | 113B) SHT P3.24 SANT. RISER 77 16TH | | | FLOOR DOES NOT REFLECT THE FLOOR PLAN, | | | AND NO FIXTURE BRANCH LINES OR FIXTURES | | | SHOWN FOR FLOORS 6 THRU 15. SECTION | | | 104.2.1. | | | 114B) SHT P3.24 RISER 76 ONLY 4 FU MAX. | | | ON 2" WET VENT. TABLE 909.3 | | | 115B) SHT P3.24 RISER 44 OFFSET VENT | | | REQUIRED. SECTION 915 | | | 116B) SHT P3.25 RISER 47 16TH FLOOR DOES | | | NOT REFLECT THE FLOOR PLAN. NO SHOWER ON | | | RISER. SECTION 104.2.1. | | | 117B) SHT P3.25 RISER 49 OFFSET VENT | | | SHALL BE CONNECTED ABOVE THE BRANCH LINE | | | PRIOR TO OFFSET. SECTION 915 - 16TH | | | FLOOR 4 FU MAX. ON 2" WET VENT. TABLE | | | 909.3. - 15TH FLOOR DOES NOT REFLECT THE | | | FLOOR PLAN. SECTION 104.2.1. | | | 118B) SHT P3.26 RISER 66 15TH FLOOR 4 FU | | | MAX. ON 2" WET VENT. TABLE 909.3. | | | 119B) SHT P3.27 DRY HORIZONTAL VENT NOT | | | APPROVED. SECTIONS 905.3 & 905.4. - 4 FU | | | MAX. ON 2" WET VENT. TABLE 909.3 - NO | | | VENT TERMINATION SHOWN FOR AREA AT LEFT | | | SIDE OF BLDG DRAIN. - NO VENT SHOWN FOR | | | LAV AT MEZZ. LEVEL. SECTION 901.2.1. - | | | OFFSET VENT REQUIRED FOR RISER (6). | | | SECTION 915. - CLEANOUT REQUIRED 4' AFF | | | FOR W/M. SECTION 708.10. - VENTS FOR | | | KITCHEN SINKS DO NOT REFLECT THE FLOOR | | | PLAN. (NOT SHOWN ON FLOOR PLAN). SECTION | | | 104.2.1. - INDICATE SHEET NUMBER FOR THE | | | CONTINUATION OF RISERS 53, 67/83 UNABLE | | | TO LOCATE. SECTION 104.2.1. | | | 120B) EVERY VENT STACK SHALL CONNECT TO | | | THE BASE OF THE DRAINAGE STACK. SECTION | | | 903.4 | | | 121B) SHT P3.28 RISER 68 INDICATE SHEET | | | NUMBER FOR CONTINUATION OF RISER. | | | SECTION 104.2.1. - RISER 54 OFFSET VENT | | | REQUIRED, AND 4 FU MAX. ON 2" WET VENT. | | | SECTION 915 AND TABLE 909.3. - RISER 7 | | | OFFSET VENTS REQUIRED. UPPER OFFSET, | | | (2ND FLOOR),VENT SHALL BE CONNECTED TO | | | THE VERTICAL STACK NOT THE BRANCH LINE. | | | SECTION 915. - RISER 3, 56, 57 OFFSET | | | VENT REQUIRED SECTION 915 - DOES NOT | | | SHOW KITCHEN SINK 5TH FLOOR SECTION | | | 104.2.1. - MISLABELED AS RISER 51 - | | | SECTION 104.2.1. - WASH MACHINE GROUND | | | FLOOR REQUIRES THAT CLEANOUT IS 4' AFF. | | | SECTION 104.2.1. - RISERS 4, 9, 58, 9 AT | | | BASE, HORIZONTAL DRY VENT NOT APPROVED. | | | SECTIONS 905.3 & 905.4. VENT SHALL BE | | | CONNECTED AT THE BASE OF THE STACK. | | | SECTION 903.4 - THESE RISERS ARE | | | INDICATED AS 4, 9, 10, 58, & 59. PLEASE | | | CORRELATE. SECTION 104.2.1. - OFFSET | | | SHALL CONNECT ABOVE THE BRANCH LINE. FIG | | | 915.2. - RISER 58 SOME FIXTURES ARE | | | MISLABELED, ON NOT LABELED AT ALL. | | | SECTION 104.2.1. - VENT TERMINATION FOR | | | 2ND FLOOR BATHROOM NOT SHOWN. SECTION | | | 104.2.1. - RISER 4/9 MISLABELED FIXTURE. | | | SECTION 104.2.1, WASH MACHINES, KITCHEN | | | SINKS, AND BATHROOMS SHALL NOT DRAIN | | | PAST THE VENT FOR THE BATHROOM ON THE | | | MEZZ. LEVEL. SECTION 908.3 - DWV FOR THE | | | MEZZ. LEVEL DOES NOT REFLECT THE FLOOR | | | PLAN. SECTION 104.2.1. - SECOND FLOOR | | | POWDER ROOM DOES NOT REFLECT THE FLOOR | | | PLAN. SECTION 104.2.1. - BATHROOM GROUPS | | | FOR THE THIRD AND FORTH FLOORS NOT SHOWN | | | ON RISER 4. SECTION 104.2.1. | | | 122B) ALL SANITARY RISER DIAGRAMS, SHOW | | | ALL PIPE SIZES. SIZES ARE MISSING ON | | | SOME PIPES. SECTION 104.2.1. & TABLE | | | 710.1(1). | | | 123B) SHT P3.29 RISER 69 4 FU MAX. ON 2" | | | WET VENT. TABLE 909.3 - RISER 11 DOES | | | NOT REFLECT THE FLOOR PLAN - AND NO | | | BRANCH LINES FROM 4TH FLOOR THRU 15TH | | | FLOOR. - OFFSET VENTS REQUIRED - RISER | | | 60 OFFSET VENT REQUIRED - GROUND FLOOR | | | AT RISER 11/60 DOES NOT REFLECT THE | | | FLOOR PLAN - RISER 86 SECOND FLOOR DOES | | | NOT REFLECT THE FLOOR PLAN - SHOW | | | DESIGNATION NUMBER FOR RISER 88 - RISER | | | 89 4 FU MAX. ON 2" WET VENT - 89/90/91 | | | MEZZ. LEVEL BATHROOM DOES NOT REFLECT | | | THE FLOOR PLAN. SECTIONS 104.2.1. & 915 | | | TABLE 909.3. | | | 124B) SHT P3.30 RISER 77 DOES NOT | | | REFLECT THE FLOOR PLAN, WASH MACHINES | | | NOT SHOWN. - RISER 47 OFFSET VENTS | | | REQUIRED, 5TH FLOOR DOES NOT REFLECT THE | | | FLOOR PLAN, NO KITCHEN SINK SHOWN. - | | | RISER 49 OFFSET VENTS REQUIRED. - RISER | | | 49 DOES NOT REFLECT THE FLOOR PLAN, LAV | | | MISSING IN MASTER BATH 2ND FLOOR, OFFSET | | | VENTS REQUIRED, 2ND FLOOR INDICATED | | | DOWNSTREAM OF MEZZ. - RISER 65 DOES NOT | | | REFLECT THE FLOOR PLAN. - RISER 50 DOES | | | NOT REFLECT THE FLOOR PLAN ON THE 2ND | | | FLOOR AND THE 5TH FLOOR, OFFSET VENTS | | | REQUIRED, FIXTURE MISLABELED, 4 FU MAX. | | | ON 2" WET VENT, DRY HORIZONTAL VENT NOT | | | APPROVED. SECTIONS 104.2.1, 915, & TABLE | | | 909.3 | | | 125B) SHT P3.31 RISER 24 DOES NOT | | | REFLECT THE FLOOR PLAN 4TH FLOOR, 4 FU | | | MAX. ON 2" WET VENT, OFFSET VENTS | | | REQUIRED, DRY HORIZONTAL VENT NOT | | | APPROVED. - RISER 54 OFFSET VENTS | | | REQUIRED. - RISER 26 OFFSET VENTS | | | REQUIRED. - RISER 27/28 OFFSET VENTS | | | REQUIRED, 4 FU MAX. ON 2" WET VENT, DOES | | | NOT REFLECT THE FLOOR PLAN AT/BELOW MEZZ | | | LEVEL. - RISER 55/28/84 RISER | | | DESIGNATION NUMBER DOES NOT REFLECT THE | | | FLOOR PLAN, (SHOW AS 55/73/84), PLEASE | | | CLARIFY, DOES NOT REFLECT THE FLOOR PLAN | | | NO WASH MACHINES SHOWN, OFFSET VENTS | | | REQUIRED. SECTIONS 104.2.1, 915, & TABLE | | | 909.3. | | | 126B) SHT P3.32 RISER 29/30/31/32 OFFSET | | | VENTS REQUIRED, FIXTURE MISLABLED, | | | FIXTURE BRANCH LINE SHALL NOT CONNECT TO | | | THE HORIZONTAL OFFSET. - RISER 34 DOES | | | NOT REFLECT THE FLOOR PLAN, OFFSET VENTS | | | REQUIRED. - RISER 33/35 OFFSET VENTS | | | REQUIRED, LAV VENTS 2ND THRU 4TH FLOOR | | | DO NOT REFLECT THE FLOOR PLAN. - RISER | | | 56/74/81 OFFSET VENTS REQUIRED, KITCHEN | | | SINK VENTS DO NOT REFLECT THE FLOOR PLAN | | | 2ND THRU 4TH FLOORS. - RISER 56 NO | | | HORIZONTAL DRY VENT, DOES NOT REFLECT | | | THE FLOOR PLAN 2ND & 3RD FLOORS, (W/M'S) | | | SECTIONS 104.2.1, AND 711.2. | | | 127B) SHT P3.33 SANT. ISOMETRIC SHOWS | | | TWO HORIZONTAL DRY VENTS, LEFT OF RISER | | | 61. THESE ARE NOT APPROVED. PER SECTIONS | | | 905.3 & 905.4. - WASH MACHINE LEFT OF | | | RISER 61 DOES NOT REFLECT THE FLOOR | | | PLAN, - RISER 61 OFFSET VENT REQUIRED, | | | DOES NOT REFLECT THE FLOOR PLAN - RISER | | | 23 INDICATES TWO 4TH FLOORS, LAV ARMS DO | | | NOT REFLECT THE FLOOR PLAN, OFFSET VENTS | | | REQUIRED. - RISER 25 EXTRA BRANCH LINE | | | CONNECTED TO STACK BELOW 2ND FLOOR NOT | | | APPROVED, OFFSET VENTS REQUIRED, DOES | | | NOT REFLECT THE FLOOR PLAN 5TH FLOOR, NO | | | 3RD FLOOR PIPING SHOWN, TUB MISSING 4TH | | | FLOOR, 4 FU MAX. ON 2" WET VENT. | | | SECTIONS 104.2.1, 915, 905.3, 905.4, | | | 706.3 & TABLE 909.3. | | | 128B) SHT P3.34 RISER 60 DOES NOT | | | REFLECT THE FLOOR PLAN, UPRIGHT WYE | | | REQUIRED AT VENT STACK CONNECTION TO THE | | | WASTE STACK. - RISER 62 DOES NOT REFLECT | | | THE FLOOR PLAN. - RISER 45 DOES NOT | | | REFLECT THE FLOOR PLAN, - RISER 64 DOES | | | NOT REFLECT THE FLOOR PLAN. - RISER 44 | | | VENT SHALL CONNECT TO BASE OF STACK, | | | LABEL ALL FIXTURES. - RISER 76 DOES NOT | | | REFLECT THE FLOOR PLAN, CONNECT VENT | | | STACK TO BASE OF SANT. STACK, RISER | | | SHOWS CONDITION ON 2ND FLOOR THAT IS | | | ACTUALLY ON THE 5TH FLOOR ONLY, DRY | | | HORIZONTAL VENT NOT APPROVED. - RISER 46 | | | SHOW ALL PIPE SIZES. SECTIONS 104.2.1, | | | 905.3, 905.4, | | | 129B) SHT P3.35 RISER 38 OFFSET VENTS | | | REQUIRED, RELIEF VENT REQUIRED, RISER | | | DOES NOT REFLECT THE FLOOR PLAN, (NO | | | PIPING SHOW FOR 3RD THRU 5TH FLOORS - | | | SHOWER MISSING IN BATHROOM), - GROUND | | | FLOOR WASH MACHINE MISLABELED AS SHOWER, | | | CLEANOUT SHALL BE 4' AFF AT W/M. - | | | IDENTIFY OTHER RISER AT END OF RUN. | | | SECTIONS 104.2.1, 915, 914, 708.10. | | | 130B) SHT P3.36 GROUND FLOOR DOES NOT | | | REFLECT THE FLOOR PLAN, (FD IN TRASH | | | ROOM NOT SHOWN, KITCHEN SINK - W/M AREA, | | | AND VENTING), INDICATE WHY 10 FU FOR | | | CLEANOUT AT END OF RUN. - RISER 71 | | | OFFSET VENTS REQUIRED, NO PIPING FOR 3RD | | | FLOOR, NO KITCHEN SINK ON 4TH FLOOR, | | | INDICATE FLOOR LEVEL TOP OF RISER. - | | | RISER 37 VENT STACK SHALL CONNECT AT THE | | | BASE OF THE STACK, NO HORIZONTAL DRY | | | VENT, OFFSET VENT REQUIRED, 5TH FLOOR | | | DOES NOT REFLECT THE FLOOR PLAN, FIXTURE | | | MISLABELED AND 4 FU MAX. ON 2" WET VENT | | | 4TH FLOOR, UNABLE TO FIND CONTINUATION | | | OF RISER. - RISER 36 SHOWS TYPICAL | | | PIPING FOR 3RD & 4TH FLOORS, BUT FLOOR | | | PLANS ARE DIFFERENT. SECTIONS 104.2.1. | | | 915, 903.4, 905.3, 905.4. | | | 131B) SHT P3.37 CHECK ADDITION FOR | | | SQUARE FOOTAGE AT DRAINS. 4" @ 1665 SF | | | TO BE A MINIMUM OF 5" PIPE RWL 4 TABLE | | | 1106.3. SOME FITTINGS NOT DIRECTING | | | STORM WATER IN DIRECTION OF FLOW. - SHOW | | | SF FOR TD'S GROUND FLOOR DRAINAGE RISER. | | | 132B) SHT O3.38 CHECK ADDITION ON RWL | | | 2&3. IS 3" PD 680SF OR 80 SF? PLUS CHECK | | | ADDITION OF PD'S & DD'S = 963 SF BUT | | | 2320 SF SHOWN. 5TH FLOOR RISER 2/3 DOES | | | NOT REFLECT THE FLOOR PLAN. DD @603 SF & | | | PD @ 1018 SF NOT SHOWN. PLEASE CLARIFY. | | | SECTION 104.2.1. | | | 133B) SHT P3.39 RECHECK ADDITION OF SF | | | AS IT ACCUMULATES IN THE SYSTEM, SOME | | | DRAIN SF DOES NOT REFLECT ROOF PLAN SF | | | AT DECK DRAINS, & PLANTER DRAINS, PIPE | | | SIZING NOT CORRECT, SHOW SF AS IT | | | ACCUMULATES IN THE SYSTEM, SHOW SLOPE OF | | | PIPE REQUIRED. SECTION 104.2.1, 1106, & | | | 1107. | | | 134B) THE FOLLOWING UNITS WERE NOT | | | LOCATED. "C2", 'D2" & "BT" PLEASE | | | INDICATE LOCATION FOR THESE UNITS. | | | 135B) THE FOLLOWING WATER RISER DIAGRAMS | | | WERE NOT FOUND: SHTS P2.16/P2.22 "B7", | | | SHTS P2.29 "B", SHT P2.33 "J1", P2.35 | | | "B", P2.41 "B", P2.46 "S1", P2.52 "S1" | | | 135B) PLANS STILL SEEM TO BE INCOMPLETE | | | AND MORE COMMENTS MAY BE FORTHCOMING | | | WHEN PLANS ARE RESUBMITTED. RED LINE | | | PLANS WERE REQUESTED TO BE RETURNED TO | | | HELP THE REVIEW PROCESS FOR THE SECOND | | | REVIEW. THESE WERE NOT RETURNED. I WILL | | | BE KEEPING THE RED LINE SET OF PLANS IN | | | ORDER TO HELP THE REVIEW PROCESS ON NEXT | | | RESUBMIT. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. - | | | THIS ALSO WAS NOT DONE WHEN PLANS WERE | | | RESUBMITTED. MOST RESPONSE NOTES WERE NO | | | MORE THAN A FEW WORDS AND NO INDICATION | | | OF WHERE CORRECTION COULD BE FOUND, | | | RESULTING IN MANY HOURS REVIEWING THE | | | PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-01-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-01-19 |
Time |
12:14 |
Rev Time |
34.00 |
| Received By |
kstevens |
Date |
2005-01-12 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2005-01-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) PLANS SHALL BE SIGNED/SEALED/DATED | | | BY | | | THE ARCHITECT/ENGINEER OF RECORD, AND | | | ALL TITLE BLOCK INFORMATION REQUIRED ON | | | ALL SHEETS. FAC 61G1-16.002-.003-.004 & | | | 61G15-23.002 & FS 481.219-.219 & | | | 471.025 | | | 2) SHT A2.01 PRIMARY ENTRY LEVEL SHALL | | | COMPLY WITH FHA-98 DESIGN MANUAL | | | REQUIREMENTS 1 THRU 7. | | | 3) SHT A2.10 SUBMIT CALCULATIONS FOR | | | MINIMUM FACILITIES PER TABLES 1003.2 | | | AND | | | 403.1. SHOW SQUARE FEET FOR EACH COMMON | | | USE ROOM. | | | 4) SHT A2.10 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY STORM DRAINS FOR | | | THE 5TH FLOOR OPEN AREAS PER SECTIONS | | | 1106 & 1107. SHOW THE LOCATION FOR ALL | | | PRIMARY AND SECONDARY DRAINS. | | | 5) SHTS A2.14, A2.15, A2.16, & A2.17. | | | APPLICATION STATES 20 STORY BLDG., BUT | | | PLANS INDICATE 21ST STORY AND HAS A | | | ROOF | | | LEVEL, POOL DECK LEVEL, ELEVATOR | | | MACHINE | | | ROOM LEVEL ECT. PLEASE CLARIFY. | | | 6) SHT A4.11 UNIT 1 DOOR SWING INTO THE | | | CLEAR FLOOR SPACE OF THE LAV. SECTION | | | 11-4.22.2. | | | 7) SHT A4.12 UNITS 5 & 6 DOOR SWING | | | INTO | | | THE CLEAR FLOOR SPACE OF THE LAV AND | | | W/C | | | SECTION 11-4.22.2. | | | 8) SHT A4.13 UNIT 12 DOOR SWING INTO | | | THE | | | CLEAR FLOOR SPACE OF THE W/C. | | | 11-4.22.2. | | | 9) SHT A4.15 UNIT 17 DOOR SWING INTO | | | THE | | | CLEAR FLOOR SPACE OF THE LAV. | | | 11-4.22.2. | | | 10) ALL SHEETS FOR UNITS. SHOW THE | | | OPENING SIZE FOR ALL W/C'S AND SHOW THE | | | W/C TO BE 18" FROM THE CENTER LINE OF | | | THE FIXTURE TO THE WALL WHERE | | | APPLICABLE | | | 11) ALL SHEETS FOR UNITS. INDICATE | | | SPECIFICATION "A" OR "B" AS REQUIRED BY | | | THE FHA-98 DESIGN MANUAL FOR EACH UNIT. | | | 12) SHT A4.41 KITCHEN SINK & JUICE BAR | | | SINK IN COMMON AREAS SHALL COMPLY WITH | | | SECTION 11-4.24 AND ALL SUBSECTIONS. | | | SUBMIT A DETAIL. | | | 13) SHT A4.41 SUBMIT A DETAIL FOR THE | | | TOILET ROOM IN THE COMMON AREA. SHOW | | | COMPLIANCE WITH SECTIONS 11-4.16, | | | 11-4.18, 11-4.19, 11-4.21 & 11-4.22 AND | | | ALL SUBSECTIONS. ALSO SEE SECTION 2 OF | | | THE FHA-98 DESIGN MANUAL. | | | 14) SHT A4.41 A DRINKING FOUNTAIN IS | | | REQUIRED PER TABLE 403.1 FOR THE COMMON | | | AREA. SUBMIT A DETAIL SHOWING | | | COMPLIANCE | | | WITH SECTION 11-4.15 AND ALL | | | SUBSECTIONS. - ALSO SEE SECTION 410.1. | | | 15) SHT SUBMIT CALCULATIONS FOR PRIMARY | | | AND SECONDARY ROOF DRAINS PER SECTIONS | | | 1106 & 1107 AND ALL SUBSECTIONS. SHOW | | | THE SQUARE FOOTAGE OF EACH AREA DRAINED | | | WITH 1/2 AREA OF ALL VERTICAL WALLS | | | INCLUDING PARAPETS SHOWN ADDED TO THE | | | ROOF AREA. ALSO SHOW THE AREA OF UPPER | | | ROOFS DRAINING ONTO EACH AREA ADDED TO | | | THE SF IN CALCULATIONS. SHOW THE | | | LOCATION OF EACH PRIMARY ROOF DRAIN AND | | | EACH SECONDARY ROOF DRAIN OR SCUPPER | | | FOR | | | EACH AREA BEING DRAINED FOR EACH ROOF. | | | 16) SHT A4.51 A 60" DIA. TURNING AREA | | | IS | | | REQUIRED IN A "U" SHAPED KITCHEN THAT | | | HAS A SINK, RANGE, OR COOKTOP AT IT'S | | | BASE. PAGE 7.9 FHA DESIGN MANUAL. | | | 17) SHTS A4.60 THRU A4.66 MORE | | | INFORMATION IS REQUIRED FOR THE | | | EXTENDED | | | TERRACES. WILL | | | A SCUPPER BE REQUIRED OR CAN THE WATER | | | DRAIN FROM THE TERRACES IN CASE OF | | | BLOCKAGE OF THE TERRACE DRAIN. SECTION | | | 104.2.1. | | | 18) SHT A4.71A INDICATE LOCATION OF | | | SECONDARY ROOF DRAINS IN AREAS OF ROOF | | | WHERE SCUPPERS ARE NOT AVAILABLE. | | | SECTION 1107. | | | 19) SHT A4.72A INDICATE LOCATION OF | | | SECONDARY ROOF DRAINS FOR DECK DRAIN | | | AREAS. SECTION 1107. | | | 20) SHT A4.73A INDICATE LOCATION OF | | | SECONDARY ROOF DRAINS FOR ALL AREAS. | | | SECTION 1107. | | | 21) SEPARATE PERMITS REQUIRED FOR POOL | | | AND SPA. SECTION 104.1.1. | | | 22) SHT A8.21 DETAIL B/A8.21 INDICATE | | | OPENING SIZE REQUIRED PER SECTION | | | 1107.3 | | | 23) IRRIGATION PLANS & PERMIT REQUIRED. | | | SECTION 104.2.1. | | | 23) SHT L-2 MORE INFORMATION IS | | | REQUIRED | | | FOR THE WATER FEATURES. INDICATE HOW | | | THE | | | FEATURES ARE DRAINED AND IF THERE IS A | | | WATER SERVICE FOR THESE FEATURES. | | | SECTION 104.2.1. | | | 24) THE FOLLOWING SHEETS SUBMITTED ARE | | | NOT SHOWN ON THE DRAWING INDEX. A4.71A, | | | A4.74A, A8.41B & A10.03. PLEASE | | | CORRELATE THE DRAWING INDEX WITH | | | SUBMITTED PLANS. | | | 25) THE FOLLOWING SHEETS ON THE DRAWING | | | INDEX WERE NOT SUBMITTED. A1.02, A3.11, | | | A3.12, A3.14, A3.15, A3.24, A4.14, | | | A5.01, A5.11, A6.53A, A6.56A, A8.12, | | | A8.13, A8.14, A9.22, A10.10, AND | | | LS0.00. | | | PLEASE SUBMIT ALL SHEETS INDICATED ON | | | THE DRAWING INDEX. SECTION 104.2.1. | | | 26) PLANS SUBMITTED ARE NOT COMPLETE. | | | MANY SHEETS APPEAR TO BE INCOMPLETE AND | | | THE FOLLOWING SHEETS SHOWN ON THE INDEX | | | WERE NOT SUBMITTED. P2.01, P2.05, P2.06, | | | P2.27, P2.29, P2.30, P2.31, P2.32, | | | P2.34, P2.35, P2.36, P2.62, P2.63, | | | P2.64, P2.65, P2.66, P2.67, P2.68, | | | P2.69, P3.03, P3.04, P3.05, P3.06, | | | P3.07, P3.08, P3.09, P3.10, P3.11, | | | P3.12, P3.13, AND P6.02. | | | 27) SUBMIT A STORM BLDG DRAIN ISOMETRIC | | | SHOWING ALL PIPE SIZES, AND SHOW THE | | | LOCATION OF ALL STORM RISER DIAGRAMS AS | | | THEY CONNECT TO THE BLDG. DRAIN AND SHOW | | | SQUARE FOOTAGE AS IT ACCUMULATES IN THE | | | SYSTEM. SECTIONS 1106, 1107 & 104.2.1. | | | 28) SUBMIT STORM RISER DIAGRAMS SHOWING | | | ALL PIPE SIZES AND SQ.FT. SECTIONS 1106, | | | 1107 AND 104.2.1. | | | 29) SUBMIT A CONDENSATE BLDG DRAIN | | | ISOMETRIC SHOWING ALL PIPE SIZES. | | | SECTION 104.2.1. | | | 30) SUBMIT CONDENSATE RISER DIAGRAM. | | | SECTION 104.2.1 | | | 31) SUBMIT A SANITARY BLDG. DRAIN | | | ISOMETRIC. SHOW ALL PIPE SIZES, LOCATION | | | OF EACH RISER CONNECTING TO BLDG. DRAIN, | | | AND DFU'S AS THEY ACCUMULATE IN THE | | | SYSTEM. SECTION 104.3.1.1. | | | 32) SHEETS FOR UNIT TYPES ARE INCOMPLETE | | | AND REQUIRE MORE INFORMATION. SOME | | | SHEETS SHOW SANT., VENT, WATER, COND., | | | T/P, OR ANOTHER UNIDENTIFIED LINE, BUT | | | ALL DO NOT HAVE ALL INFORMATION | | | REQUIRED. | | | 33) SHOW STACK NUMBERS FOR EACH STACK IN | | | ALL UNIT SHEETS. SECTION 104.2.1. | | | 34) SHT P2.11 IS MISLABELED AS M2.11, OR | | | IT IS A MECH. SHEET. PLEASE CLARIFY. | | | SECTION 104.2.1. | | | 34) SHT P2.02 UNIT 2, INDICATE WHERE LAV | | | RISER CONNECTS TO THE SANT. BRANCH LINE. | | | SECTION 104.2.1. | | | UNIT 3, THE VENT LINE IS SHOWN AS | | | SANT. | | | UNIT 4, NO SANT. TO W.M, NO VENT LINES | | | SHOWN. SECTION 104.2.1. | | | 35) SHT P2.03 ALL UNITS, NO VENT LINES | | | SHOWN, NO WATER LINES SHOWN. | | | UNIT 5, NO SANT. TO W/M. | | | UNIT 8, ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUP SHALL CONNECT TO THE | | | WET-VENTED HORIZONTAL BRANCH DRAIN. THE | | | KITCHEN SINK SHALL DISCHARGE DOWNSTREAM | | | OF THE WET VENT. SECTION 909.1 | | | 36) SHT P2.04 PIPING INCOMPLETE. SECTION | | | 104.2.1. | | | 37) SHT P2.07 PIPING INCOMPLETE. | | | 104.2.1 | | | 38) SHT P2.08 UNIT 4, LAV VENT SHOWN OUT | | | OF THE WALL. SEC 104.2.1. | | | 39) SHTS P2.09 & P2.10 PIPING | | | INCOMPLETE. NO WATER LINES. SEC | | | 104.2.1. | | | 40) SHT P2.12 PIPING INCOMPLETE. | | | UNIT 15 SHOWER NOT VENTED. SEC | | | 901.2.1. | | | 41) SHT P2.13 PIPING NOT COMPLETE. | | | SECTION 104.2.1. | | | 42) SHT P2.14 PIPING INCOMPLETE. | | | UNIT HH1 MASTER BATH DOUBLE LAV SHOWS | | | SANT PIPING FROM TWO DIFFERENT RISERS. | | | PLEASE CLARIFY. SEC 104.2.1. | | | TRASH CHUED LABELED AS PRIMARY AIR | | | SHAFT #3. PLEASE CLARIFY. 104.2.1. | | | 43) SHT P2.15 PIPING INCOMPLETE. | | | UNIT VV1 SHOWS VENT UNDER M/B TUB. | | | PLEASE CLARIFY. | | | UNIT A1 IS LAV IN M/B ON A SEPARATE | | | RISER STACK FROM OTHER M/B FIXTURES. | | | PLEASE CLARIFY. SECTION 104.2.1. | | | 44) SHTS P2.17 THRU P2.54 PIPING | | | INCOMPLETE. SECTION 104.2.1. | | | 45) P2.21 UNITS A1 & VV1 BATH #2 SHOWER | | | NOT VENTED. SECTION 901.2.1. | | | UNIT A1 WHAT TYPE OF VENT IS THE | | | KITCHEN SINK UTILIZING? SECTION 901.2.1 | | | 46) SHT P2.39 HAS A REFERENCE TO SHT | | | P2. | | | NO SHT P2. IS LOCATED. PLEASE CLARIFY. | | | SECTION 104.2.1. | | | 47) SHT 2.44 UNIT S MASTER BATH WATER | | | CLOSET, MAX 10' FROM POINT OF VENT. | | | TABLE 906.1. | | | 48) SHT P2.50 UNTI P2 LAUNDRY SINK SHALL | | | NOT DISCHARGE INTO THE WET VENT FOR THE | | | BATHROOM FIXTURES. SECTION 909.1. | | | 49) SHT P2.53 UNIT 0 BATH #2 KITCHEN | | | SINK SHALL NOT DISCHARGE INTO THE WET | | | VENT. SECTION 909.1. | | | 50) SHT 2.57 WOMEN'S BATHROOM DOES NOT | | | REFLECT THE SANT. RISER DIAGRAM. W/C IN | | | WOMEN'S STALL MAX. 10' FROM POINT OF | | | VENT. TABLE 906.1. INDICATE USE OF FLOOR | | | DRAIN FOR FIXTURE NEXT TO SHOWER IN | | | MEN'S BATHROOM. SECTION 104.2.1. | | | 51) ALL SANT. RISERS WITH WASH MACHINES, | | | REQUIRE A STANDPIPE AND THE CLEANOUT | | | SHALL BE LOCATED 4' ABOVE THE FLOOR FOR | | | ACCESS. SECTIONS 1002.1, 802.4 & | | | 708.10. | | | 52) SHT P3.01 DOMESTIC WATER RISER | | | DIAGRAMS. AIR CHAMBERS ARE NOT APPROVED. | | | DELETE FROM RISERS. SECTION 604.9. | | | 53) SHT 3.14 RISER 21 MAX 4 FIXTURE | | | UNITS ON 2" WET VENT. TAB 909.3 | | | 54) SHT PE.15 RISERS 27/34 OFFSET VENT | | | REQUIRED. SECTION 915. | | | RISERS 55/56 IDENTIVY FIXTURE BY | | | KITCHEN SINK. SEC 104.2.1 | | | RISER 28 OFFSET VENT REQUIRED. 915. | | | RISERS 29/31 OFFSET VENT REQUIRED. 915 | | | - MASTER BATH 21ST FLOOR MAX 4 FU ON 2" | | | WET VENT. TABLE 909.3. FLOORS 6 THRU 15, | | | MAXIMUM 4 FU ON 2" WET VENT. TAB 909.3. | | | RISERS 30/32 OFFSET VENT REQUIRED. | | | 915. | | | MAX 4 FU ON 2" WET VENT. TAB 909.3 | | | RISER 38 OFFSET VENT REQUIRED. SEC 915 | | | MAX. 4 FU ON 2" WET VENT TAB 909.3. | | | 55) SHT P3.16 RISERS 39.75 OFFSET VENT | | | REQUIRED SEC 915. | | | RISER 39 MAX. 4 FU ON 2" WET VENT. | | | TABLE 909.3. | | | RISER 59 OFFSET VENT REQD. SEC 915. | | | RISER 11 OFFSET VENT REQD. SECTION | | | 915. | | | RISER 12 OFFSET VENT REQD. SEC 915. - | | | INDICATE WHICH FLOOR/FLOORS THE SANT. IS | | | FOR ABOVE THE 15TH FLOOR. - MAX 4 FU ON | | | 2" WET VENT. TABLE 909.3 | | | 56) SHT P3.17 RISER 23 OFFSET VENT | | | REQUIRED. SECTION 915. | | | RISER 24 OFFSET VENT REQD. SEC. 915. - | | | MAX. 4 FU ON 2" WET VENT. TABLE 909.3 | | | RISERS 26/35 OFFSET VENT REQD. SEC. 915 | | | - FIXTURE MISLABELED AS KITCHEN SINK IN | | | BATHROOM GROUP. SECTION 104.2.1. | | | 57) SHT P3.18 RISER 70 OFSET VENT REQD. | | | SECTION 915. - MAX 4 FU ON 2" WET VENT. | | | TABLE 909.3. | | | RISER 15 MAX. 4 FU ON 2" WET VENT. | | | TABLE 909.3 | | | RISER 18 ABOVE 21ST FLOOR STATES VENT | | | BACK DOWN TO 15TH FLOOR. PLEASE CLARIFY | | | SECTIONS 104.2.1. & 903.1. | | | RISER 19 ABOVE 21TH FLOOR STATES VENT | | | BACK DOWN TO 15TH FLOOR. PLEASE CLARIFY | | | SECTIONS 104.2.1. & 903.1. | | | 58) SHT P3.19 RISER 1 OFFSET VENT | | | REQUIRED. SECTION 915. | | | RISERS 2/55 SOIL STACK AND VENT STACK | | | ARE CROSSED. - OFFSET VENT REQUIRED. | | | SECTION 915. | | | RISER 3 VENT STACK SHALL CONTINUE AND | | | NOT TIE BACK INTO THE SOIL STACK. | | | SECTION 903.1 | | | RISER 4 MAX 4 FU ON 2" WET VENT. | | | 909.3. | | | RISER 5 OFFSET VENT REQUIRED. SEC 915. | | | 59) SHT P3.20 RISER 6 OFFSET VENT | | | REQUIRED. SECTION 915. - MAX 4 FU ON 2" | | | WET VENT. TABLE 909.3. | | | RISER 54 MAX 4 FU ON 2" WET VENT. TABLE | | | 909.3. | | | RISER 7 OFFSET VENT REQUIRED. SEC 915. | | | MAX. 4 FU ON 2" WET VENT. TABLE 909.3. | | | RISER 8 OFFSET VENT REQUIRED. SEC 915. | | | MAX 4 FU ON 2" WET VENT. TABLE 909.3. | | | 60) SHT P3.21 RISER 40 OFFSET VENT | | | REQUIRED. SECTION 915. | | | RISER 41 OFFSET VENT REQD. SEC 915. | | | RISER 44 OFFSET VENT REQD. SEC 915. - | | | INDICATE IF THERE ARE BRANCH LINES | | | CONNECTING TO STACK ON THE 17TH THRU | | | 20TH FLOORS. SECTION 104.2.1. | | | RISER 76 MAX 4 FU ON 2" WET VENT. TABLE | | | 909.3. | | | 61) SHT P3.22 RISER 45 OFFSET VENT REQD. | | | SECTION 915. - INDICATE IF THERE ARE | | | BRANCH LINES CONNECTING TO THE STACK ON | | | THE 17TH THRU 20TH FLOORS. SEC 104.2.1. | | | RISER 46 OFFSET VENT REQD. SEC 915. - | | | MAXIMUM 4 FU ON 2" WET VENT. TABLE | | | 909.3 | | | RISER 47 OFFSEC VENT REQD. SEC 915. - | | | MAXIMUM 4 FU ON 2" WET VENT. TABLE | | | 909.3 | | | RISER 49 OFFSET VENT REQD. SEC 915. - | | | MAXIMUM 4 FU ON 2" WET VENT. TABLE | | | 909.3 | | | 62) SHT P3.23 RISER 63 MAXIMUM 4 FU ON | | | 2" WET VENT. TABLE 909.3 | | | RISER 43 OFFSET VENT REQD. SEC 915. - | | | MAXIMUM 4 FU ON 2" WET VENT. TABLE | | | 909.3 | | | RISER 60 WASH MACHINE AND KITCHEN SINK | | | SHALL CONNECT TO THE SANT. STACK NOT THE | | | VENT STACK. SECTION 104.2.1. | | | 63) SHT P6.01 COOLING TOWER MAKE UP | | | DETAIL, INDICATE METHOD FOR REQUIRED | | | BACKFLOW PROTECTION. SECTION 608.13.2. - | | | WATER HEATER PIPING DETAIL, THERMAL | | | EXPANSION CONTROL REQUIRED. SECTION | | | 607.3.2. - TRASH CHUTE PIPING DIAGRAM. | | | INDICATE METHOD FOR REQUIRED BACKFLOW | | | PROTECTION. SECTION 608.13.2. | | | 64) BACKFLOW PROTECTION REQUIRED FOR THE | | | POOL MAKE UP WATER. SUBMIT A DETAIL. | | | SECTION 608.13.2. | | | 65) BECAUSE THE PLANS ARE INCOMPLETE, | | | MORE COMMENTS MAY BE FOURTHCOMMING WHEN | | | THE PLANS ARE RESUBMITTED. - PLEASE | | | RETURN THE PLUMBING PLANS WITH THE RED | | | LINE NOTES WHEN RESUBMITTING TO HELP | | | REVIEWING PLANS FOR SECOND REVIEW. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
11 |
Status |
P |
Date |
2008-07-29 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2008-07-29 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2008-07-29 |
Time |
14:35 |
Sent To |
P |
|
| Notes |
| 2008-07-29 14:39:56 | ZONING REVIEW: PASSED WITH PROVISO | | | | | | PROVISO ITEMS: | | | | | | 1) ON LP-1 - PITCH APPLE SPECIES NOT APPROVED AS | | | SUBSTITUTE. PLANTING SHALL MATCH CITY PLAZA I PLANT BED | | | PROVIDED ACROSS LAKEVIEW. | | | | | | 2) ON LL-1 - LAMP POSTS ON OLIVE AND TRINITY SHALL | | | MATCH TYPICAL OLIVE POST (SEE CITY STANDARD), AS | | | APPROVED BY ENGINEERING SERVICES | | | | | | 3) ON LL-1 - FOUR LIGHTS INDICATED ALONG DROP-OFF SHALL | | | BE REMOVED PER MEETING WITH CITY STAFF, AND AS APPROVED | | | BY ENGINEER SERVICES | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
10 |
Status |
N |
Date |
2008-05-08 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2008-05-08 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2008-05-08 |
Time |
14:25 |
Sent To |
M |
|
| Notes |
| 2008-05-08 14:26:25 | MECHANICAL ONLY. NOT REQUIRED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
9 |
Status |
P |
Date |
2008-04-16 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2008-04-16 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2008-04-16 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2008-04-16 10:50:06 | CIVIL DRAWINGS ONLY.REPLACE EXISTING F CURB ALONG OLIVE | | | AV. AND HANDICAP RAMP AT THE CORNER OF OLIVE AV. AND | | | LAKEVIEW AVE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
8 |
Status |
N |
Date |
2007-08-03 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2007-08-03 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2007-08-03 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2007-08-03 13:25:32 | STRUCTURAL REVISIONS ONLY |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
7 |
Status |
P |
Date |
2007-02-15 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2007-02-15 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2007-02-15 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2007-02-15 10:52:15 | LNADSCAPE CHANGES APPROVED BASED ON COMMENTS FROM | | | 10/17/05 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
P |
Date |
2006-07-28 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2006-07-28 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2006-07-25 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2006-07-28 00:00:00 | CHANGES ON ELEVATION APPROVED |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2005-12-23 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2005-12-23 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
astelly |
Date |
2005-12-23 |
Time |
08:09 |
Sent To |
|
|
| Notes |
| 2005-12-23 00:00:00 | 12/23/05 LANDSCAPE PLANS APPROVED BY AMY | | | STEELY AND INSERTED IN PACKAGE WAITING | | | FOR COMMERICAL BOARD (BY JENNIFER). |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2005-10-17 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2005-10-17 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2005-10-17 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2005-10-17 00:00:00 | PROVISO | | | 1.HANDICAP PARKING DIMENSIONS | | | SHALL BE ADJUSTED ACCORDING TO DAC FINAL | | | VARIANCE APPROVAL BEFORE CO ISSUANCE. | | | 2. PLEASE REPLACE PALMS ALONG TRINITY | | | PLACE FOR HIGH RISE OAKS. | | | 3. PLEASE PLACE STRUCTURAL SOIL | | | UNDERNEAD THE SIDEWALK ADJACENT TO THE | | | TREE PLANTERS. | | | 4. TREE HOLE SHALL BE 3 TIMES THE SIZE | | | OF THE ROOTBALL AT THE DEPTH OF THE | | | ROOTBALL. | | | 5. PLEASE CONTACT ALAN BARRATA, | | | LANDSCAPE ARCHITECT FOR (822-1462) FOR | | | PLANTING DETAILS. | | | 6. SIDEWALK MATERIAL TO BE DETERMINED BY | | | THE CITY AND MODIFIED BY THE APPLICANT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2005-09-01 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2005-09-01 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2005-09-01 00:00:00 | 1. HANDICAP SPACES SHALL BE 12 FEET WIDE | | | MINIMUM WITH A 5 FEET AISLE. | | | 2. PLEASE SUBMIT LANDSCAPE DRAWINGS TO | | | CONFIRM COMPLIANCE WITH REGULATION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2005-04-25 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2005-04-25 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2005-04-25 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2005-04-25 00:00:00 | 1.PLEASE INCLUDE A TABLE CONTAINING THE | | | EXACT AMOUNT OF TDR UTILIZED ON THE | | | PROJECT. | | | 2. BASED ON DAC APPROVAL, AN | | | ARCHITECTURAL ARTICULATION OF THE RECESS | | | LINE SHALL BE CARRIED AROUND THE | | | BUILDING, EXCLUDING THE TOWER ELEMENTS. | | | 3. PLEASE PROVIDE LANDSCAPE DRAWINGS. | | | 4. PLEASE PROVIDE INFORMATION TO CONFIRM | | | COMPLIANCE WITH THE MINIMUM 15% | | | LANDSCAPE REQUIRED FOR THE ROOFTOP | | | TERRACE. | | | 5.PLEASE REMOVE THE "LEASABLE SPACE" | | | IDENTIFIED ON THE POOL DECK LEVEL AND | | | PROVIDE INFORMATION TO CONFIRM | | | COMPLIANCE WITH MAXIMUM 30% ALLOWED FOR | | | COVERED STRUCTURES ON THE ROOFTOP | | | TERRACE. | | | 6.PLEASE INDICATE THE PARKING SPACES | | | ASSIGNED TO THE LIVE/WORK TYPE UNITS. | | | 7. PLEASE ADJUST HANDICAP PARKING SPACES | | | TO MEET REQUIREMENTS ACCORDING WITH | | | CITY'S CODE. | | | 8. PROPOSED AWNING ON OLIVE AVENUE WILL | | | REQUIRE AIR-RIGHTS EASEMENT IF IT IS | | | PROJECTING OVER THE RIGHT-OF-WAY. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-11-06 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2005-01-18 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2005-01-18 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2005-01-18 00:00:00 | 1. PLEASE PROVIDE A COPY OF THE TDR | | | CERTIFICATE AND A TABLE CONTAINING THE | | | AMOUNT OF SQUARE FOOTAGE UTILIZED. | | | 2. BASED ON DAC APPROVAL, AN | | | ARCHITECTURAL ARTICULATION OF THE RECESS | | | LINE SHALL BE CARRIED AROUND THE | | | BUILDING, EXCLUDING THE TOWER ELEMENTS. | | | 3. PLEASE CONFIRM COMPLIANCE WITH SIDE | | | SETBACK REQUIREMENT. ART IV SEC 94-108 | | | (B)(3). | | | 3. SETBACK ON OLIVE AVENUE IS EXCEEDING | | | THE MAXIMUM SETBACK OF 8'7" GRANTED BY | | | DAC VARIANCE.THE BUILDING IS SETBACK | | | 15'6" IN FRONT OF THE GRAND LOBBY. | | | 4. PLEASE PROVIDE A TABLE THAT CONFIRMS | | | MEZZANINES ARE IN COMPLIANCE WITH THE | | | PERMISSIBLE PERCENTAGE OF FLOOR AREA FOR | | | A MEZZANINE AS DEFINED IN THE CITY'S | | | BUILDING CODE. | | | 5.PLEASE CONFIRM 8" SIDEWALK CLEARANCE | | | ON THE WESTERN MOST PAR OF LAKEVIEW | | | AVENUE. | | | 6.PLEASE PROVIDE INFORMATION THAT | | | CONFIRMS COMPLIANCE WITH RECESS LINE AT | | | THE TOP OF 14TH FLOOR ACCORDING WITH DAC | | | APPROVAL. | | | 7. PLEASE PROVIDE INFORMATION TO CONFIRM | | | COMPLIANCE WITH THE MINIMUM 15%LANDSCAPE | | | REQUIRED FOR THE ROOFTOP TERRACE. | | | 8. PLEASE PROVIDE INFORMATION TO CONFIRM | | | COMPLIANCE WITH MAXIMUM 30% ALLOWED FOR | | | COVERED STRUCTURES. | | | 9. PLEASE CLARIFY WHAT IS THE "LEASEABLE | | | SPACE" IDENTIFIED ON THE POOL DECK | | | LEVEL. | | | 10. STREET TREES SHALL BE INSTALLED IN | | | THE SIDEWALK ADJACENT TO THE CURB ALONG | | | THE FRONTAGE LINE, WITH A REGULAR | | | SPACING NO GREATER THAN 40'. | | | 11. PLANTERS ARE NOT ALLOWED ALONG THE | | | CURB. | | | 12. PLEASE PROVIDE INFORMATION TO | | | CONFIRM COMPLIANCE WITH MAXIMUM GLAZED | | | AREA PERMITTED. |
|
|