| 2005-03-02 00:00:00 | DENIED: |
| | 1.LETTER PROVIDED FROM THE OWNER |
| | INDCIATING THE MECHANICAL CONTRACTOR IS |
| | ACCEPTABLE.THE PLANS SUBMITTED HAVE A |
| | TITLE BLOCK BY GORDON F. BUCK, P.E.PER |
| | THE FS 471.025 & FAC 61G15-23.002, WHEN |
| | A TITLE BLOCK IS DISPLAYED ON THE PLANS |
| | THE ENGINEER SHALL SIGN, SEAL AND DATE |
| | SAID PLANS.THE LETTER PROVIDED |
| | INDICATES THE MECHANICAL CONTRACTOR IS |
| | TO PROVIDE PLANS THEREFORE AN ENGINEER |
| | SHOULD NOT BE INDICATED ON THE PLAN. |
| | THE PERSON FROM THE MECHANICAL |
| | CONTRACTOR THAT DESIGNED THE SYSTEM IS |
| | THE PERSON RESPONSIBLE AND SHALL SIGN |
| | AND DATE PLANS. |
| | |
| | 2.PLANS DO NOT INDICATE FIRE DAMPERS. |
| | THE ARCHITECTURAL PLANS INDICATE RATED |
| | WALLS FOR TENANT SEPARATION (A3). |
| | |
| | 3.PLEASE CLARIFY RATING BETWEEN THE |
| | HALL AND TENANT ROOMS. |
| | |
| | 4.THE MECHANICAL PLANS SUBMITTED |
| | INDICATE RETURN AIR JUMPERS FROM THE |
| | TENANT ROOMS INTO THE HALL AREA AND A |
| | FREE RETURN BACK TO THE AHU. PER 2001 |
| | FBC(M)403.2.1, AIR SHALL NOT BE |
| | RECIRCULATED FROM ONE DWELLING TO |
| | ANOTHER OR DISSIMILAR OCCUPANCIES. |
| | |