Plan Review Details - Permit 04120193
Plan Review Stops For Permit 04120193
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-08-01 Cont ID  
Sent By rmcdouga Date 2006-08-01 Time 10:48 Rev Time 0.00
Received By rmcdouga Date 2006-08-01 Time 10:48 Sent To M
Notes
2006-08-01 00:00:00PLANS REVISED TO SHOW SPRAYED FOAM
 INSULATION IN ATTIC. ENERGY CALCULATIONS
 REVISED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-06-28 Cont ID  
Sent By rmcdouga Date 2006-06-28 Time 07:45 Rev Time 0.00
Received By rmcdouga Date 2006-06-28 Time 07:12 Sent To  
Notes
2006-06-28 00:00:00DENIED
  
 1) BUILDING PROVISO REQUIRED REVISED
 ENERGY CALCULATIONS TO REFLECT THE ICF
 EXTERIOR WALLS. HOWEVER, THE NEW ENERGY
 CLACS. SUBMITTED LISTS THE SINGLE
 ASSEMBLY CEILING AS R-20 AND THE PLANS
 SPECIFY R-30. THE OWNER HAS INDICATED
 THAT THE CEILING WAS INSULATED WITH A
 SPRAYED ON FOAM PRODUCT. THEREFORE, THE
 PLANS MUST BE REVISED TO REFLECT THE
 CHANGES AND THE PRODUCT INFORMATION
 (MANUFACTURERS SPECS. AND INSTALLATION
 INSTRUCTIONS) FOR THE SPRAYED FOAM
 INSULATION SUBMITTED. TWO COPIES OF ALL
 REQUESTED ITEMS ARE REQUIRED. TWO
 SIGNED AND SEALED LETTERS FROM THE
 DESIGNER OF RECORD (ENGINEER) STATING
 THAT THE CEILING INSULATION WAS CHANGED
 FROM R30 BATTS TO R20 SPRAYED FOAM
 INSULATION WILL BE ACCEPTABLE IN LIEU OF
 REVISING THE PLAN PAGES.
  
 2) THE COMMENTS FROM THE MECHANICAL
 PLANS EXAMINER MUST ALSO BE ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-01-04 Cont ID  
Sent By rmcdouga Date 2006-01-04 Time 09:05 Rev Time 0.00
Received By rmcdouga Date 2006-01-04 Time 09:05 Sent To  
Notes
2006-01-04 00:00:00PROVISO
  
 1) SUBMIT REVISED ENERGY CALCULATIONS
 FOR ICF SYSTEM.
  
 2) A SEPARATE PERMIT IS REQUIRED FOR THE
 ROOFING. NO PRODUCT APPROVALS WERE
 SUBMITTED FOR THE ROOF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-05 Cont ID  
Sent By rmcdouga Date 2005-12-05 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2005-12-05 Time 07:40 Sent To  
Notes
2005-12-05 00:00:00DENIED
  
 1) THE NOC HAS EXPIRED WORK MUST
 COMMENCE ON THE PROJECT WITHIN 90 DAYS
 OF RECORDING. A RE-RECORDED COPY OF THE
 NOC WILL BE REQUIRED BEFORE THE PERMIT
 IS ISSUED.
  
 2) THE EXTERIOR WALL SECTION ON SHEET 3
 SPECIFIES AN ARXX WALL SYSTEM (INSULATED
 CONCRETE FORM). SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE ICF SYSTEM. SUBMIT
 WINDLOAD CALCULATIONS FOR THE SYSTEM
 BASED ON 140 MPH WIND SPEED IN EXPOSURE
 B.
  
 3) THE ROOF SHEATHING NAILING PLAN ON
 SHEET 3 DOES NOT INDICATE THAT THE
 CORNERS OF THE FLAT ROOF ARE ZONE 3.
 PLEASE CORRECT. SEE FBC FIGURE 1606.2(C)
  
  
 3) SPECIFY THE LINTELS OR BEAMS OVER
 EXTERIOR WINDOW AND DOOR OPENINGS.
 PROVIDE A LINTEL/BEAM SCHEDULE.
  
 4) SPECIFY THE TYPE OF ANCHOR AND
 MINIMUM EMBED FOR THE 3/4" BOLT THAT IS
 SPECIFIED FOR THE CONNECTION OF THE
 BRACES SUPPORTING THE PORCH ROOF.
  
 5) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 6) SUBMIT TWO COPIES OF PRODUCT
 APPROVALS.
  
 7) SUBMIT STATE/LOCAL PRODUCT APPROVALS
 FOR THE FOLLOWING:
 - SINGLE OUTSWING GLAZED FRENCH DOOR
 - TRUSS ANCHORS
 - TILE AND FLAT ROOF MATERIALS (OR A
 SEPARATE PERMIT AND FEES WILL BE
 REQUIRED)
  
 8) THE FL NUMBERS LISTED ON SHEET 3 FOR
 THE SIMPSON CONNECTORS ARE NOT CORRECT
 FOR THE HETAL 20 ANCHORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
 -

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-22 Cont ID  
Sent By rmcdouga Date 2004-12-22 Time 09:15 Rev Time 0.00
Received By j Date 2004-12-21 Time 15:30 Sent To  
Notes
2004-12-22 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALCULATION FORM PER
 FBC CHAPTER 13.
  
 4) CITY OF WPB AMENDMENTS TO FBC
 2111.1.9 REQUIRES A 1.5 INCH RECESS
 WHERE EXTERIOR MASONRY WALLS BEAR ON A
 CONCRETE FLOOR SURFACE.
  
 5) FBC 1804.1.3 REQUIRES THE BOTTOM OF
 FOOTERS TO BE A MINIMUM OF 12" BELOW
 FINAL GRADE. SPECIFY ON PLANS.
  
 6) SPECIFY THE TRUSS CONNECTORS ON THE
 PLANS.
  
 7) SPECIFY THE WINDOW SIZES ON THE
 PLANS.
  
 8) SPECIFY THE NEGATIVE AND POSITIVE
 WINDLOAD PRESSURES FOR ALL EXTERIOR
 WINDOW AND DOOR OPENINGS.
  
 9) SAFETY GLAZING IS REQUIRED IN THE
 BATHROOM WINDOW AND WINDOWS WITH THE 8"
 SILL HEIGHT PER FBC 2405.2.1.
  
 10) BEDROOM WINDOWS ARE REQUIRED TO
 COMPLY WITH FBC 1005.4 FOR EMERGENCY
 EGRESS.
  
 11) GUTTER DOWNSPOUTS ARE REQUIRD TO
 DISCHARGE AT LEAST 12" AWAY FROM THE
 STRUCTURE PER FBC 1503.4.4.
  
 12) SPECIFY ON THE PLAN THE SLOPE OF THE
 BUILT UP FLAT ROOF. SEE FBC 1508.3.1 FOR
 MINIMUM PITCHES.
  
 13) SPECIFY THE LENGTH/EMBED DEPTH OF
 THE 3/4" EXPANSION BOLTS FASTENING THE
 TRUSS LEDGERS TO THE STRUCTURE.
  
 14) THE ENERGY CALC. FORM LISTS A
 CONCRETE ROOF DECK AND THE PLANS SPECIFY
 A PLYWOOD DECK. PLEASE CORRECT.
  
 15) FBC TABLE 600 IS USED TO DETERMINE
 THE PERCENTAGE OF WALL AREA ALLOWED AS
 OPENINGS BASED ON THE DISTANCE TO THE
 PROPERTY LINE OR ASSUMED PROPERTY LINE
 (WHEN TWO STRUCTURES ARE ON THE SAME
 PROPERTY). SPECIFY THE LOCATION OF THE
 ASSUMED PROPERTY LINE BETWEEN THE TWO
 STRUCTURES BASED ON THE OPENINGS IN THE
 EXISTING AND NEW STRUCTURES.
  
 16) SUBMIT 2 COPIES OF ALL PRODUCT
 APPROVALS.
  
 17) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 WWW.FLORIDABUILDING.ORG
  
 18) SUBMIT STATE/LOCAL PRODUCT APPROVALS
 FOR THE FOLLOWING:
 - ROOFING (OR SEPARATE PERMIT WILL BE
 REQUIRED)
 - TRUSS CONNECTORS
 - OUTSWING GLAZED DOORS (SINGLE AND
 DOUBLE WITH AND WITHOUT SIDELITES)
  
 19) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE FASTENERS, SPACING AND MOUNT TYPE
 THAT WILL BE USED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-11-14 Cont ID  
Sent By btrobaug Date 2006-11-14 Time 14:47 Rev Time 0.50
Received By btrobaug Date 2006-11-14 Time 14:47 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-06 Cont ID  
Sent By jleahy Date 2005-11-06 Time 15:31 Rev Time 0.45
Received By jleahy Date 2005-11-06 Time 15:30 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-12-10 Cont ID  
Sent By jleahy Date 2004-12-10 Time 14:00 Rev Time 0.30
Received By jleahy Date 2004-12-10 Time 14:00 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 08:05 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 08:05 Sent To M
Notes
2006-07-27 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-26 Cont ID  
Sent By adarroug Date 2006-06-26 Time 11:08 Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 11:08 Sent To B
Notes
2006-06-26 00:00:00TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-29 Cont ID  
Sent By adarroug Date 2005-12-29 Time 11:24 Rev Time 0.00
Received By adarroug Date 2005-12-29 Time 11:24 Sent To P
Notes
2005-12-29 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-21 Cont ID  
Sent By adarroug Date 2005-10-21 Time 11:00 Rev Time 0.00
Received By adarroug Date 2005-10-21 Time 11:00 Sent To E
Notes
2005-10-21 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-04 Cont ID  
Sent By adarroug Date 2005-10-04 Time 15:47 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 15:47 Sent To Z
Notes
2005-10-04 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-17 Cont ID  
Sent By mjacobs Date 2004-12-17 Time 16:20 Rev Time 0.00
Received By mjacobs Date 2004-12-17 Time 16:20 Sent To B
Notes
2004-12-17 00:00:00SENT TO "RES" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-06 Cont ID  
Sent By mjacobs Date 2004-12-06 Time 10:57 Rev Time 0.00
Received By mjacobs Date 2004-12-06 Time 10:57 Sent To E
Notes
2004-12-06 00:00:00SENT TO "E" BOX.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-08-08 Cont ID  
Sent By tgordon Date 2006-08-08 Time 14:40 Rev Time 0.45
Received By tgordon Date 2006-08-08 Time 14:40 Sent To  
Notes
2006-08-08 00:00:00REVISION TO MECANICAL PLANS, E-CAL'S,
 AND MANUAL J.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-07-28 Cont ID  
Sent By tgordon Date 2006-07-28 Time 12:06 Rev Time 0.25
Received By tgordon Date 2006-07-28 Time 12:06 Sent To B
Notes
2006-07-28 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW, MECHANICAL
 PLANS NEED TO BE REVISED
 TO SHOW CHANGES TO A/C EQUIPMENT TO
 COINCIDE WITH NEW ENERGY CAL'S. AND NEW
 MANUAL J CAL'S.
  
 2) PLANS THAT WERE SUBMITTED WERE
 BUILDING PLANS, PLEASE REVISE MECHANICAL
 PLANS PAGE M-1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-06-27 Cont ID  
Sent By tgordon Date 2006-06-27 Time 09:55 Rev Time 0.20
Received By tgordon Date 2006-06-27 Time 09:55 Sent To B
Notes
2006-06-27 00:00:00*** DENIED ***
 1) MECHANICAL PLANS NEED TO BE REVISED
 TO SHOW CHANGES TO A/C EQUIPMENT TO
 COINCIDE WITH NEW ENERGY CAL'S. AND NEW
 MANUAL J CAL'S.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-12-15 Cont ID  
Sent By hmoser Date 2004-12-15 Time 11:08 Rev Time 0.00
Received By hmoser Date 2004-12-15 Time 10:52 Sent To P
Notes
2004-12-15 00:00:00REFER TO SECTION 610.ABC.3.5.2 AIR
 HANDLING UNITS.FLORIDA ENERGY CODE.AIR
 HANDLING UNIT MUST BE WITHIN 6FT.OF
 ATTIC ACCESS.PLAN REVIEW BY HAROLD
 MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-08-01 Cont ID  
Sent By rmcdouga Date 2006-08-01 Time 10:50 Rev Time 0.00
Received By rmcdouga Date 2006-08-01 Time 10:50 Sent To  
Notes
2006-08-01 00:00:00REVISED SHEET RESTAMPED FOR PLUMBING. NO
 PLUMBING CHANGES.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-01-03 Cont ID  
Sent By jleech Date 2006-01-03 Time 09:13 Rev Time 0.33
Received By jleech Date 2006-01-03 Time 09:13 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-11-15 Cont ID  
Sent By jleech Date 2005-11-15 Time 18:13 Rev Time 0.50
Received By jleech Date 2005-11-15 Time 18:13 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-16 Cont ID  
Sent By kstevens Date 2004-12-16 Time 12:40 Rev Time 0.95
Received By kstevens Date 2004-12-16 Time 12:40 Sent To Z
Notes
2004-12-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS, NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) DISHWASHER SHALL NOT CONNECT TO THE
 BUILDING SANT. DRAIN. IT SHALL BE TIED
 INTO THE TAILPIECE OF THE KITCHEN SINK
 DRAIN UPSTREAM OF THE TRAP FOR THE
 SINK.
 B) THE WASH MACHINE IS NOT SHOWN ON THE
 SANT. RISER DIAGRAM, A STANDPIPE IS
 REQUIRED AND A CLEANOUT IS REQUIRED 4'
 ABOVE THE FLOOR FOR ACCESS. SECTIONS
 104.2.1, 1002.1, 708.10.
 C) THE BATHTUB REQUIRES A TRAP AND IS
 NOT VENTED PIPED AS SHOWN, SECTION 902.1
 AND 1002.1.
 D) TWO DISHWASHERS ARE SHOWN ON THE
 SANT. RISER DIAGRAM.
 2) SEE ATTACHED SHEET FOR AN EXAMPLE OF
 A SANT. RISER THAT MEETS CODE REQ. AND
 REFLECT THE FLOOR PLAN.
 3)THE PERSONAL SIGNATUREAND THE DATE
 THE PLANS ARE SIGNED AND SEALED ARE
 REQUIRED. INITIALS ARE NOT ACCEPTABLE.
 FAC 61G1-16.003, FS 481,2055. THIS IS
 REQUIRED ON ALL SHEETS.
 4) A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED ON THE TITLE BLOCK PER FAC
 61G1-16.004(2) (FIRM LICENSE NUMBER) AND
 FS 481.219 - THIS IS REQUIRED ON ALL
 SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2005-10-18 Cont ID  
Sent By mmclean Date 2005-10-18 Time 16:23 Rev Time 0.00
Received By mmclean Date 2005-10-18 Time 16:23 Sent To I
Notes
2005-10-18 00:00:00ZONING APPROVED 12/1704, NOTHING HAS
 CHANGED, OWNER IS JUST ADDRESSING
 COMMENTS FROM STRUCTURAL & PLUMBING

Review Stop Z ZONING
Rev No 1 Status P Date 2004-12-17 Cont ID  
Sent By mmclean Date 2004-12-17 Time 15:13 Rev Time 0.00
Received By mmclean Date 2004-12-17 Time 15:13 Sent To I
Notes
***NONE***