Plan Review Details - Permit 04120064
Plan Review Stops For Permit 04120064
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-28 Cont ID  
Sent By shill Date 2004-12-28 Time 07:49 Rev Time 3.00
Received By shill Date 2004-12-27 Time 16:18 Sent To  
Notes
2004-12-28 00:00:00****CORRECTIONS****
 ****PAID PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)CERTIFICATE OF AUTHORIZATION
 REQUIRED FOR ARCHITECT BUSINESS.
 INFORMATION REQUIRED BY FAC61G1-16.004
 IS TO BE ON THE TITLE BLOCK.
  
 2.)THE OCCUPANT LOAD PROVIDED F7-T1 IS
 NOT CONSISTENT WITH THE FLOOR PLAN A1.
 THE FLOOR PLAN DOES NOT SHOW AN OFFICE;
 SHOWS STORAGE AND A WORKROOM.REVISE SO
 THAT THE TWO ARE CONSISTENT AND PROVIDE
 OCCUPANCY SEPARATION AS NECESSARY
 FBC704.FBC 704.1.2.2(4) DOES NOT
 APPEAR TO APPLY EXEMPTING THE OCCUPANCY
 SEPARATION.
  
 3.)THE AREA CALCS ON F7-T1 APPEAR TO
 BE INCONSISTENT WITH THE FLOOR PLAN.IT
 SEEMS SHORT BY ABOUT 300SF.
  
 4.)WHAT WILL BE STORED IN THE STORAGE
 AREA?DECLARE S1 OR S2.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-03 Cont ID  
Sent By dpalmer Date 2004-12-03 Time 05:36 Rev Time 0.33
Received By dpalmer Date 2004-12-03 Time 05:27 Sent To  
Notes
2004-12-03 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE CLARIFY NEW OR EXISTING
 REQUIRED SIGN CIRCUIT PER 600.5
 PLEASE SEE EACH COMMERCIAL BUILDING AND
 EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT
 LEAST ONE OUTLET IN AN ACCESSIBLE
 LOCATION AT EACH ENTRANCE TO EACH
 TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING
 SYSTEM USE. THE OUTLET(S) SHALL BE
 SUPPLIED BY A BRANCH CIRCUIT RATED AT
 LEAST 20 AMPERES THAT SUPPLIES NO OTHER
 LOAD.
  
 2)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 MISSING INFORMATION ON TITLE BLOCKS FOR
 ENGINEER(S)/FIRM.
 FS 471.023
 PLEASE ALSO SEE FAC 61G1-16.004 FOR
 MISSING INFORMATION ON ARCH'S TITLE
 BLOCK.
 FS 481.219
 THIS IS REQUIRED ON ARCH AND ENG SHEETS
 AND OF ALL TRADES WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONE
 COPY/SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 *** PLEASE SEE THESE PLANS ARE IN FOR
 REVIEW ONLY AND HAVE NOT BEEN SUBMITTED
 FOR PERMIT. ****
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-27 Cont ID  
Sent By mcarsill Date 2004-12-27 Time 14:18 Rev Time 0.00
Received By mcarsill Date 2004-12-27 Time 14:18 Sent To  
Notes
2004-12-27 00:00:001. DEMOLITION, RENOVATION AND
 COSNTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 3. AN MERGENCY LIGHT IS REQUIRED IN
 SALES AREA. THE DEMOLTION PLAN
 INDICATES THE EXISTING ONE WILL
 BE REMOVED.
  
 4. THE LOCATION MAY NOT BE UNDER
 THE CITY OF WEST PALM BEACH
 JURISDICTION. PLEASE VERIFY.
  
 5. HOW IS EXITING MAINTAINED THRU
 THE STORAGE AREA.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-19 Cont ID  
Sent By kstevens Date 2004-12-29 Time 16:25 Rev Time 0.00
Received By kstevens Date 2004-12-01 Time 17:41 Sent To  
Notes
2004-12-01 00:00:00SENT TO COMM BD#15

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2004-12-29 Time   Rev Time 0.00
Received By hmoser Date 2004-12-29 Time 13:27 Sent To  
Notes
2004-12-29 00:00:00PLAN DENIED
 1) REFER TO SECTION 606.2.2 FBC (M)
 COMMON SUPPLY,RETURN AIR AND SUPPLY
 AIR.
 2) REFER TO SECYION 606.4.1 SUPERVISON
 FBC(M)
 3) PLEASE SUPPLY INFORMATION ON GARAGE
 WHAT WILL IT BE USED FOR.
 4) CAN NOT HAVE WORK ROOM IN RETURN AIR
 PLENUM
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-12-24 Cont ID  
Sent By kstevens Date 2004-12-29 Time 16:28 Rev Time 0.33
Received By kstevens Date 2004-12-29 Time 17:32 Sent To  
Notes
2004-12-29 00:00:00THIS ADDRESS IN NOT IN THE CITY OF WPB
 SOUTH SIDE OF OKEECHOBEE BLVD.