Plan Review Details - Permit 04120039
Plan Review Stops For Permit 04120039
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-01-24 Cont ID  
Sent By shill Date 2005-01-24 Time 16:05 Rev Time 1.00
Received By shill Date 2005-01-24 Time 16:05 Sent To  
Notes
2005-01-24 00:00:00"WORK SPACE" IS CLERICAL USE ONLY AS PER
 CONVERSATION WITH ARCHITECT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-28 Cont ID  
Sent By dpalmer Date 2004-12-28 Time 10:43 Rev Time 2.00
Received By shill Date 2004-12-28 Time 10:43 Sent To  
Notes
2004-12-28 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.) PLEASE PROVIDE OCCUPANCY FBC CHAPTER
 3.IT APPEARS TO BE BUSINESS, BUT WHAT
 IS THE WORK AREA FOR?IF IT IS A
 DIFFERENT OCCUPANCY, PROVIDE FIRE
 RESISTANCE RATING INFORMATION COMPLIANT
 WITH FBC CHAPTER 7.
  
 2.)SHOW MANEUVERING CLEARANCE FOR THE
 CONFERENCE ROOM DOOR, PULL SIDE, FBC
 FIGURE 25.
  
 3.)SHOW COMPLIANCE FOR THE BREAK ROOM;
 SINK, FBC11-4.24, TURNING SPACE
 FBC11-4.2.3.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-11 Cont ID  
Sent By dpalmer Date 2005-01-11 Time 13:57 Rev Time 0.30
Received By dpalmer Date 2005-01-11 Time 13:43 Sent To  
Notes
2005-01-11 00:00:00REDLINED 424.3B FOR FIELD VERIFICATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-03 Cont ID  
Sent By dpalmer Date 2004-12-03 Time 06:29 Rev Time 0.33
Received By dpalmer Date 2004-12-03 Time 06:29 Sent To  
Notes
2004-12-03 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE ALL LIGHTING SHOWN
 ON
 ONE CIRCUIT. PLEASE VERIFY.
 FIXTURES ARE SHOWN AS 2X4 LAY-IN TYPE
 BUT NO INFORMATION ON 3-LT, 4LT, 34W,
 40W TYPE.
 PLEASE ALSO SEE RECESSED LTS/EM/ EXT
 LTS
 ARE ALSO ON SAME CIRCUIT?
  
 2)NOTE: PLEASE VERIFY NEW OR EXSITING
 SIGN CIRCUIT PER 600.5 PLEASE SEE EACH
 COMMERCIAL BUILDING AND EACH COMMERCIAL
 OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE
 OUTLET IN AN ACCESSIBLE LOCATION AT
 EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN
 OR OUTLINE LIGHTING SYSTEM USE. THE
 OUTLET(S) SHALL BE SUPPLIED BY A BRANCH
 CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD.
  
 3)NOTE: PLEASE VERIFY LOAD AND OCP FOR
 AHU/HEAT. MECH PLANS INDICATE 45A FOR
 10KW OF HEAT. PLEASE SEE 424.3B FOR MIN
 OCP. THE AMPACITY OF THE BRANCH-CIRCUIT
 CONDUCTORS AND THE RATING OR SETTING OF
 OVERCURRENT PROTECTIVE DEVICES
 SUPPLYING
 FIXED ELECTRIC SPACE-HEATING EQUIPMENT
 CONSISTING OF RESISTANCE ELEMENTS WITH
 OR WITHOUT A MOTOR SHALL NOT BE LESS
 THAN 125 PERCENT OF THE TOTAL LOAD OF
 THE MOTORS AND THE HEATERS. THE RATING
 OR SETTING OF OVERCURRENT PROTECTIVE
 DEVICES SHALL BE PERMITTED IN
 ACCORDANCE
 WITH 240.4(B).
 OCP SHOWN FOR DISC INDICATES XX?
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET/COPY OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-02-07 Cont ID  
Sent By nmccray Date 2005-02-07 Time 13:05 Rev Time 0.00
Received By nmccray Date 2005-02-07 Time 13:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-27 Cont ID  
Sent By mcarsill Date 2004-12-27 Time 14:01 Rev Time 0.00
Received By mcarsill Date 2004-12-27 Time 14:01 Sent To  
Notes
2004-12-27 00:00:001. NO EMERGENCY LIGHTING SHOWN ON
 ELECTRICAL FLOOR PLANS.
  
 2. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND
 CEILINGS.
  
 3. PLEASE ILLUSTRATE PORTABLE FIRE
 EXTINGUISHER LOCATIONS. NOTE # 19
 ON PAGE A-2 NEEDS TO BE FURTHER
 CLARIFIED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 09:01 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 09:01 Sent To  
Notes
2005-01-06 00:00:00TO "COMM BD#41"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-29 Cont ID  
Sent By mjacobs Date 2004-12-29 Time 15:06 Rev Time 0.00
Received By kstevens Date 2004-12-01 Time 18:39 Sent To  
Notes
2004-12-01 00:00:00SENT TO COMM BD#28

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-12-29 Cont ID  
Sent By pkrauss Date 2004-12-29 Time 08:43 Rev Time 0.55
Received By pkrauss Date 2004-12-29 Time 07:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-07 Cont ID  
Sent By kstevens Date 2005-02-07 Time 10:55 Rev Time 0.68
Received By kstevens Date 2005-02-07 Time 10:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-29 Cont ID  
Sent By kstevens Date 2004-12-29 Time 15:05 Rev Time 0.45
Received By kstevens Date 2004-12-29 Time 15:05 Sent To  
Notes
2004-12-29 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) MORE INFORMATION IS REQUIRED. IS THE
 BREAK ROOM SINK EXISTING? ARE NEW
 CABINETS BEING INSTALLED IN THE BREAK
 ROOM? SECTION 104.2.1.
 2) IF NEW CABINETS ARE BEING INSTALLED
 FOR THE BREAK ROOM SINK, THEN THE SINK
 SHALL COMPLY WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. SHOW FORWARD APPROACH
 CLEAR FLOOR SPACE AS REQUIRED. ECT.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]