| Plan Review Stops For Permit 04111224 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-03-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-03-23 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-03-23 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2005-03-23 00:00:00 | REVISION TO ROOF IS OK. SHEETS A6,A7 AND | | | A8 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-03-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-03-10 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-03-10 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2005-03-10 00:00:00 | MEAN ROOF HEIGHT IS ABOVE 33 FEET. | | | ASPHALT SHINGLES OKED FOR USE ON | | | STRUCTURE BY NEIL MELICK; B.O. ON | | | 3/9/05. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-03-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-03-04 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-03-04 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2005-03-04 00:00:00 | DENIED | | | | | | 1) ON SHEET S4 MARK J SPECIFIES A | | | SIMPSON HDSA HOLD DOWN CONNECTOR. | | | SHOULDN'T THIS BE A HD5A. PLEASE | | | CORRECT. | | | | | | 2) THE GR3 GIRDER IS SHOWN AS A 2PLY ON | | | THE TRUSS DRAWINGS AND THE PLANS SPECIFY | | | A 4PLY. PLEASE CORRECT. | | | | | | 3) SPECIFY THE CONNECTIONS AT EACH END | | | OF THE GR2 GIRDERS. | | | | | | 4) SPECIFY THE CONNECTIONS FOR BOTH ENDS | | | OF THE GR3 GIRDERS. | | | | | | 5)THE UPLIFT FOR THE MG1 GIRDERS AT THE | | | EXTERIOR WALL EXCEEDS THE UPLIFT | | | SPECIFIED IN THE TRUSS SCHEDULE FOR THE | | | MARK F CONNECTOR. | | | | | | 6) THE TRUSS LAYOUT AND ROOF FRAMING | | | PLAN ON S4 SPECIFIES OPENINGS IN THE | | | ROOF TRUSSES FOR A/C, HOWEVER THERE IS | | | NOTHING INDICATED ON THE ELEVATIONS OR | | | THE BUILDING ROOF PLAN ON A6 AT THESE | | | AREAS. PLEASE CLARIFY. | | | | | | 7) THE NOAS FOR THE GLASS BLOCK WERE NOT | | | SUBMITTED. I HAVE ATTACHED ONE COPY FOR | | | YOU. | | | | | | 8) SUBMIT THE INSTALLATION DRAWINGS/ | | | INSTRUCTIONS AND LIMITATIONS FOR THE UL | | | CERTIFICATIONFOR THE OWENS CORNING | | | SHINGLES. NOTE: MIAMI-DADE NOAS LIMIT | | | INSTALLATION TO STRUCTURES WITH A MEAN | | | ROOF HEIGHT OF 33 FEET. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-12-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2004-12-21 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2004-12-21 |
Time |
07:12 |
Sent To |
|
|
| Notes |
| 2004-12-21 00:00:00 | DENIED | | | | | | 1) THE OWNER/AGENT IS REQUIRED TO SIGN | | | THE ENERGY CALC. FORMS. THE ENERGY | | | CALCS.DO NOT SPECIFY THE 2X6 WOOD FRAME | | | EXTERIOR WALLS WITH R-19 INSULATION. THE | | | WALLS ADJACENT TO THE GARAGE ARE | | | SPECIFIED WITH R-19 INSULATION ON THE | | | PLAN AND R-11 ON THE ENERGY CALCS. | | | | | | 2) FBC 2504.2.1 REQUIRES EXTERIOR | | | APPLICATIONS OF PORTLAND CEMENT PLASTER | | | TO COMPLY WITH ASTM C 92. THIS STANDARD | | | REQUIRES PLASTER OVER METAL BASE TO BE | | | 5/8" THICK WHEN APPLIED HORIZONTALLY AND | | | 7/8" THICK WHEN APPLIED VERTICALLY. | | | | | | 3) THE MEAN ROOF HEIGHT FOR THE | | | STRUCTURE IS 38'-5" SUBMIT ENGINEERED | | | CALCULATIONS FOR THE ROOF SHEATHING | | | FASTENING REQUIREMENTS. | | | | | | 4) THEIR IS A TYPO ON SHEET A12. THE | | | TEXT IS PRINTED OVER. | | | | | | 5) THE STRUCTURAL NOTES ON S5 HAS A TYPO | | | THAT REFERS TO THE FBC N1 EDITION. | | | | | | 6) SPECIFY THE REQUIRED SOIL BEARING | | | CAPACITY FOR THE STRUCTURE ON THE | | | PLANS. | | | | | | 7) SUBMIT A SIGNED AND SEALED COPY OF | | | THE SOIL REPORT. | | | | | | 8) THE POSITIVE PRESSURES LISTED IN THE | | | DOOR AND WINDOW WIND PRESSURE TABLE ON | | | S5 DO NOT APPEAR TO HAVE BEEN ADJUSTED | | | FOR HEIGHT BY MULTIPLYING BY THE | | | APPROPRIATE COEFFICENT. SEE FBC TABLE | | | 1606.2D FOR M.R.H. OF 38'-5". | | | | | | 9) PROVIDE CAP DETAILS FOR THE (WP-1) | | | 4X4 WOOD COLUMN AND THE (SC-1) STEEL | | | COLUMN. | | | | | | 10) DETAIL 5 ON S7 SHOWS A 6X6 WOOD POST | | | CAP WHICH IS NOT CALLED OUT ON THE | | | PLANS. PLEASE CLARIFY. | | | | | | 11) SUBMIT PRODUCT APPROVALS FOR ASPHALT | | | ROOF SHINGLES THAT WERE TESTED TO ASTM D | | | 3161M OR PA 107 AND ARE NOT LIMITED TO A | | | 33' M.R.H. | | | | | | 12) THE DOOR SCHEDULE FOR UNIT 2 AND 2R | | | DOES NOT LIST THE 16' WIDE OVERHEAD | | | GARAGE DOOR OR THEIR WIND PRESSURES. | | | | | | 13) THE NOA/ELEVATION REPORT FOR THE | | | GLASS BLOCK IS MISSING. | | | | | | 14) A PRODUCT APPROVAL FOR FIXED GLASS | | | WINDOWS WAS SUBMITTED, HOWEVER, THERE | | | AREN'T ANY SPECIFIED ON THE PLANS. | | | PLEASE CLARIFY. | | | | | | 15) THE TRUSS LAYOUTS AND DRAWINGS ARE | | | REQUIRED TO HAVE THE ORIGINAL WET | | | SIGNATURE OF THE TRUSS ENGINEER PER FAC | | | 61G15-23.002. | | | | | | 16) THE ROOF PLAN ON S4 DOES NOT MATCH | | | THE TRUSS LAYOUT. PLEASE REVISE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-01-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-24 |
Time |
15:51 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-01-24 |
Time |
15:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-11-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-30 |
Time |
06:57 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-11-30 |
Time |
06:57 |
Sent To |
|
|
| Notes |
| 2004-11-30 00:00:00 | ********* UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE RECEPT ON 2' OF WALL | | | IN BEDRM #2, APPEARS TO BE "IN" A WALL? | | | 210.52 | | | | | | 2)NOTE: IT HAS COME TO OUR ATTENTION | | | THE | | | SEC'S ARE ACTUALLY BEING INSTALLED BY | | | THE ELECTRICAL CONTRACTOR AND NOT FPL> | | | IF INDEED THIS WILL BE, THEN SEC'S ARE | | | TO BE SHOWN ON RISER DIAGRAM AND MUST | | | MEET 310.16 2002 NEC. | | | | | | 3)NOTE: PLEASE ALSO SEE 250.66 FOR | | | SIZING OF GROUNDING ELECTRODE | | | CONDUCTOR. | | | THIS MAY NEED TO BE CORRECTED ON RISER | | | DUE TO SEC'S CHANGES? | | | SHOWN AS 1/0 NOW, WHICH IS NOT LARGE | | | ENOUGH. | | | PLEASE ADJUST. | | | | | | 4)NOTE: PLEASE SEE TITLE BLOCKS FOR | | | ELECTRICAL AND MECHANICAL SHEETS. | | | THESE STILL INDICATE A "FIRM". | | | PLEASE ADJUST TITLE BLOCK OR INCLUDE | | | LICENSE # AS REQUIRED UNDER FAC | | | 61G15-23.002, FS 471.023. | | | PLEASE SEE THIS IS REQUIRED OF OTHER | | | POSSIBLE SHEETS WHEATHER OR NOT COMMENT | | | OS MADE BY OTHER REVIEWER(S). | | | | | | 5)NOTE: PLEASE SEE PLANS STILL INDICATE | | | A MAIN DISC AND 8-METERS. THIS COMMENT | | | WAS GIVEN ONPREVIOUS REVIEW UNDER | | | #04021360 THIS DOE NOT CORRELATE WITH | | | RISER. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT NEW REVISED SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2004-11-30 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-11-30 |
Time |
14:45 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2004-11-30 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2004-11-30 00:00:00 | PASSED: | | | 1. SEE PERMIT #03101412 FOR UNDERGROUND | | | UTILITIES AND SITE WORK. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2004-12-22 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-12-22 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-12-22 |
Time |
09:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-01-21 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-21 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-21 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2005-01-21 00:00:00 | TO "COMM BD#38/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-03-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-12-23 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-03-10 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2004-11-29 00:00:00 | SENT TO COMM BD#48 | | | PRODUCT APPROVALE ON S.F.R.RACK ABOVE | | | ELEC. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-01-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-01-27 |
Time |
16:36 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2005-01-27 |
Time |
15:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-12-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-12-04 |
Time |
06:12 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2004-12-04 |
Time |
06:11 |
Sent To |
|
|
| Notes |
| 2004-12-04 00:00:00 | ***********PLAN CHECK*********** | | | DENIED: | | | SEE COMMENT #4 BY DEWEY PALMER, FS | | | 471.023 & FAC 61G15-23-0002, TITLE | | | BLOCKS & LICENSE NUMBERS. | | | | | | PLANS ARE OTHER WISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-02-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-02-17 |
Time |
07:49 |
Rev Time |
0.95 |
| Received By |
kstevens |
Date |
2005-02-17 |
Time |
07:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2004-12-23 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-12-23 |
Time |
18:55 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2004-12-23 |
Time |
18:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2005-03-22 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2005-03-22 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2005-03-22 |
Time |
13:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2005-03-22 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2005-03-22 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2005-03-22 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-02-02 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2005-02-02 |
Time |
11:45 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2005-02-02 |
Time |
11:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-12-13 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2004-12-13 |
Time |
15:34 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2004-12-13 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2004-12-13 00:00:00 | BUILDING EXCEEDS MAXIMUM TOWNHOUSE | | | HEIGHT OF 35 FEET PER SECTION | | | 94-307(G)(6)C OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS. | | | FALSE CHIMNEYS EXCEED MAXIMUM ALLOWED | | | HEIGHT OF 38.5 FEET PER SECTION | | | 94-304(A) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS. |
|
|