Plan Review Details - Permit 04111163
Plan Review Stops For Permit 04111163
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2004-12-28 Cont ID  
Sent By jhiggins Date 2004-12-28 Time 16:15 Rev Time 0.00
Received By jhiggins Date 2004-12-28 Time 16:14 Sent To  
Notes
2004-12-28 00:00:00ADDRESS ASSIGNED: 2985 45TH ST

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-14 Cont ID  
Sent By shill Date 2005-03-14 Time 14:53 Rev Time 1.00
Received By shill Date 2005-03-14 Time 14:21 Sent To PC
Notes
2005-03-14 00:00:00TRUSS SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-02-22 Cont ID  
Sent By shill Date 2005-02-22 Time 09:58 Rev Time 1.00
Received By shill Date 2005-02-18 Time 16:11 Sent To PC
Notes
2005-02-22 00:00:00****PROVISO****
  
 SEPARATE PERMIT FOR SHUTTERS
  
 SUBMIT SHUTTER STORAGE BOX DETAIL SIGNED
 & SEALED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-02-18 Cont ID  
Sent By shill Date 2005-02-18 Time 09:53 Rev Time 1.00
Received By shill Date 2005-02-18 Time 09:53 Sent To PC
Notes
2005-02-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDNG PLANS EXAMINER
 [email protected]
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)THE PERMIT WILL BE ISSUED WITH
 PROVISO:
  
 SUBMIT THE DETAIL FOR THE SHUTTER
 STORAGE BOX (NEEDS TO HAVE A TITLE
 BLOCK, ORIGINAL SIGNED & SEALED).
  
 SEPARATE PERMIT FOR THE SHUTTERS
 (SCHEDULE SUBMITTED DOES NOT HAVE ANCHOR
 TYPES OR SPACING).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-31 Cont ID  
Sent By shill Date 2005-01-31 Time 15:44 Rev Time 2.50
Received By shill Date 2005-01-31 Time 13:39 Sent To  
Notes
2005-01-31 00:00:00****CORRECTIONS****
 ****PAID PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)FOR SHUTTERS TO BE INCLUDED IN
 THIS
 PERMIT, AN INSTALLATION SCHEDULE IS
 REQUIRED, SEE ATTACHED.
  
  
  
 ****PROVISO***
  
 1.)REVISE C4, HANDICAP DETAIL FOR
 PARKING.
  
 2.)PROVIDE A DETAIL SHOWING FOR
 ANCHORING OF THE STEEL BOX FOR SHUTTER
 STORAGE. (DUMPSTER ENCLOSURE, C5).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-27 Cont ID  
Sent By shill Date 2004-12-23 Time 15:14 Rev Time 4.00
Received By shill Date 2004-12-23 Time 13:20 Sent To  
Notes
2004-12-23 00:00:00****CORRECTIONS****
 PAID PLAN REVIEW
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY BEFORE A PERMIT CAN BE
 ISSUED.THE PLANS MUST BE STAMPED AND
 THE RECEIPT ATTACHED TO THE
 APPLICATION.
 233-5025
  
 3.)STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO TEST REPORTS
 FAC9B-72.WWW.FLORIDABUILDING.ORG
  
 4.)THE SURVEY SHOWS ONE PARCEL,
 PROPERTY APPRAISER'S SHOWS TWO. HAS A
 UNITY OF TITLE BEEN FILED TO JOIN THE
 TWO PARCELS?IF IT HAS, PLEASE PROVIDE
 EITHER A RECORDED COPY OR SUPPLY THE
 BOOK/PAGE. THE IMPROVEMENTS CROSS OVER
 THE PROPERTY LINE.PLEASE ADDRESS.
  
 5.)NOTE -THIS PROPERTY IS LOCATED
 IN
 A FLOOD ZONE.A FORM BOARD ELEVATION
 CERTIFICATE WILL BE REQUIRED BEFORE
 CONCRETE POUR.
  
 6.)SHEET C4, HANDICAP PARKING IS TO
 COMPLY WITH CITY OF WEST PALM BEACH
 REQUIREMENTS, SEE ATTACHED.
  
 7.)PRIOR TO PERMITTING, PLEASE
 PROVIDE
 A SOILS INVESTIGATION REPORT.
  
 8.)THE NOTE REGARDING STORM SHUTTERS
 ON SHEET A14 IS INCORRECT.IMPACT
 PROTECTION REQUIRED IN WINDBORNE DEBRIS
 REGIONS, FBC1606.1.4.
  
 9.)STUCCO OVER WIRE LATH IN A
 VERTICAL
 APPLICATION IS TO BE A MINIMUM OF 7/8",
 FBC2504.2.2, ASTM C926.REVISE DETAILS
 1-A11, 7-A2.1, ANY OTHER AFFECTED
 DETAILS.
  
 10.)INDICATE THE INSTALLATION METHOD
 IN THE NOA FOR THE MODIFIED ROOF.NOT
 ALL METHODS ARE COMPLIANT WITH THE
 DESIGN PRESSURE SPECIFIED.SHEETS
 WHICH
 ARE NOT APPLICABLE TO THIS APPLICATION
 MAY BE DISCARDED.
  
 11.) STOREFRONT NOTES, ITEM #6, STATES
 THAT PALM BEACH COUNTY IS IN THE HIGH
 VELOCITY HURRICANE ZONE.PALM BEACH
 COUNTY IS NOT IN THE HIGH VELOCITY
 ZONE.
 PLEASE MODIFY THE NOTE TO MAKE CLEAR
 THE
 SPECIFICATION FOR THE STOREFRONT
 OPTION.
 TEST REPORTS AND PRODUCT APPROVALS ARE
 STILL REQUIRED OUTSIDE OF THE HVHZ,
 FBC1707.4, 1707.3.
  
 12.)THE NOA FOR THE NARROW STILE DOOR
 IS LIMITED TO 3'0 PER LEAF; SHEET A16,
 DOOR SCHEDULE, #1, SHOWS A DIMENSION OF
 3'6".IS THIS THE SAME DOOR?
  
 13.)DETAIL 5-S2 AND THE WOOD TRUSS
 TIE
 DOWN SCHEDULE REFER TO A HUGHES
 CONNECTOR.THIS COMPANY HAS BEEN OUT
 OF
 BUSINESS FOR SEVERAL YEARS; PLEASE
 REVISE THE CONNECTOR TO ONE THAT IS
 AVAILABLE.CHECK ALL DETAILS.
  
 14.)THE FASTENING FOR USP TAPL16
 (4-S2, WOOD TRUSS TIE DOWN SCHEDULE)
 CONFLICTS WITH THE CATALOG (SPECIFIES
 11
 NAILS RATHER THAN 13).REVISE AND
 CHECK
 ALL OTHER FASTENING SPECIFICATIONS.
  
 15.)3-S3 SHOWS A FRAME WALL ENCLOSING
 THE ATTIC SPACE.TYPE V CONSTRUCTION
 IS
 TO BE NONCOMBUSTIBLE EXTERIOR WALLS,
 FBC607.
  
 16.)SEPARATE PERMIT REQUIRED FOR
 DUMPSTER ENCLOSURE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-27 Cont ID  
Sent By dpalmer Date 2005-01-27 Time 16:06 Rev Time 1.00
Received By dpalmer Date 2005-01-27 Time 14:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-03 Cont ID  
Sent By dpalmer Date 2004-12-03 Time 13:55 Rev Time 2.50
Received By dpalmer Date 2004-12-03 Time 11:27 Sent To  
Notes
2004-12-03 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS AS REQUIRED UNDER FAC
 61G15-23.002,61G1-16.004.
 FS 471.023,481.219
 PLEASE SEE ALL SHEETS AND FOR ALL TRADES
 WHEATHER OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
 **NOTE** ELECTRICAL ENGINEERS TITLE
 BLOCK IS CORRECT.
  
 2)NOTE: PLEASE SUBMIT WIND LOADING
 CALCUALTIONS FOR SITE LT POLES FOR BLDG
 REVIEW. MUST ALSO BE NOTED ON ELECTRICAL
 PLANS FOR REQUIREMENTS OF FBC 140 MPH
 WIND S.
  
 3)NOTE: PLEASE SEE "SHOW WINDOW" RECEPTS
 WILL BE REQUIRED FOR WINDOW AREAS.
 PLEASE SEE 210.62
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED DIRECTLY ABOVE A SHOW WINDOW
 FOR EACH 3.7 LINEAR M (12 FT) OR MAJOR
 FRACTION THEREOF OF SHOW WINDOW AREA
 MEASURED HORIZONTALLY AT ITS MAXIMUM
 WIDTH.
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAIN
 DISCONNECT TO PANLE DP AND FROM DP TO
 SUB-PANELS.EXPOSED NON?CURRENT-CARRYING
 METAL PARTS OF FIXED EQUIPMENT LIKELY TO
 BECOME ENERGIZED SHALL BE GROUNDED.
 PLEASE ALSO SEE LOCAL AMENDMENTS WHICH
 REQUIRE AN EQUIPMENT GRND PULLED WITH
 OUTSIDE CONDUITS EVEN IF EMT.
 250.110,250.122
  
 5)NOTE: PLEASE SEE CORD AND PLUG
 CONNECT-ED EQUIPMENT ABOVE CEILINGS AND
 RECEPTS ABOVE CEILINGS NOT PERMITTED.
  
  
 6)NOTE: PLEASE PROVIDE A NOTE ON PLANS
 FOR REQUIREMENTS OF GFI PROTECTION IN
 KITCHEN FOR ALL RECEPTS.
 LL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE
 LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
 ALL 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES INSTALLED IN THE
 LOCATIONS SPECIFIED IN (1), (2), AND (3)
 SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL:SECTION 210.8(B)(3) IS NEW
 FOR THE 2002 CODE AND REQUIRES ALL 15-
 AND 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
 210.8B3
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETED SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE REVIEW COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY OR MAY
 NOT AFFECT ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2005-02-11 Cont ID  
Sent By mamini Date 2005-02-11 Time 16:30 Rev Time 0.50
Received By mamini Date 2005-02-11 Time 16:30 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2005-02-01 Cont ID  
Sent By mamini Date 2005-02-01 Time 15:24 Rev Time 0.50
Received By mamini Date 2005-02-01 Time 15:24 Sent To  
Notes
2005-02-01 00:00:00FAILED:
  
 1. PLEASE NOTE THAT ALL THE REVIEW
 COMMENTS BY THE PUBLIC UTILITIES AND
 ENGINEERING SERVICE MUST BE ADDRESSED
 AND IMPLEMENTED PRIOR TO GETTING CIVIL
 PLAN'S APPROVAL FROM CONSTRUCTION
 SERVICES.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-12-08 Cont ID  
Sent By mamini Date 2004-12-08 Time 14:41 Rev Time 1.00
Received By mamini Date 2004-12-08 Time 14:40 Sent To  
Notes
2004-12-08 00:00:00FAILED:
  
 1. PLEASE SUBMIT STORM WATER CALCS. FOR
 OUR REVIEW AND APPROVAL, ALSO PROVIDE
 A COPY OF MODIFIED PERMIT TO THE
 ORIGINAL SFWMD PERMIT.
 2. PLEASE VERIFY IF A STANDARD FDOT
 RAMP INDEX 304 AT WHERE THE SIDEWALK
 INTERSECT THE 31' NON-EXCLUSIVE
 DRIVEWAY/ACCESS EASEMENT IS REQUIRED.
 3. PLEASE STATE IF GARBAGE IS TO BE
 PICKED UP BY THE CITY OR PRIVET, IF
 CITY, THEN A MIN. OF 12'-6" BETWEEN THE
 GATE POST IS REQUIRED.
 4. PLEASE SUBMIT CIVIL PLANS ONLY TO
 THE
 PUBLIC UTILITIES & ENGINEERING FOR
 APPROVAL OF ALL THE CONNECTIONS TO THE
 CITY SERVICES, ATT; MANNY GONZALEZ
 494-1085.
 5. POLLUTION PREVENTION PLANS MUST BE
 INSTALLED IN FIELD PRIOR TO ANY CONST.
 WORK, SHOULD BE ADDED TO THE PLANS.
 6. PLEASE NOTE THAT A SEPARATE R.O.W
 PERMIT FROM PALM BEACH COUNTY AND FROM
 THE CITY OF WEST PALM BEACH'S PUBLIC
 UTILITIES & AND ENGINEERING FOR ALL THE
 WORK IN PUBLIC R. O.W IS REQUIRED,
 494-1086, WINDEL PALMER, MOT PLANS MUST
 BE SUBMITTED AT TIME OF APPLICATION.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-02-03 Cont ID  
Sent By mcarsill Date 2005-02-03 Time 11:43 Rev Time 0.00
Received By mcarsill Date 2005-02-03 Time 11:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-27 Cont ID  
Sent By mcarsill Date 2004-12-27 Time 15:10 Rev Time 0.00
Received By mcarsill Date 2004-12-27 Time 15:10 Sent To  
Notes
2004-12-27 00:00:001. SEPARATE PLANS AND PERMITS
 REQUIRED FOR HOOD, DUCT AND
 SUPPRESSION SYSTEMS.
  
 2. BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION. A MINIMUM OF 6"
 HIGH NUMBERS ARE REQUIRED.
  
 3. PLEASE PROVIDE PRODUCT APPROVALS
 FOR DUCT WRAP.
  
 4. ENSURE COOKING APPLIANCES ARE SET
 UP FOR NATURAL GAS AS NOTED ON PLANS.
  
 5. COULD NOT LOCATE ANY EMERGENCY
 LIGHTS
 IN MAIN DINING ROOM.
  
 6. TILE DIRECTLY OUTSIDE OF EXIT DOORS
 SHALL BE SLIP RESISTANT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 10:37 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 10:37 Sent To B
Notes
2005-03-10 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-18 Cont ID  
Sent By shill Date 2005-02-18 Time 16:16 Rev Time 0.00
Received By shill Date 2005-02-18 Time 16:16 Sent To M
Notes
2005-02-18 00:00:00TO PK DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 15:47 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 15:47 Sent To B
Notes
2005-02-18 00:00:00TO SHILL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 14:03 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 14:03 Sent To  
Notes
2005-02-11 00:00:00TO "COMM" BD#45

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-21 Cont ID  
Sent By mjacobs Date 2005-01-21 Time 09:03 Rev Time 0.00
Received By mjacobs Date 2005-01-21 Time 09:03 Sent To  
Notes
2005-01-21 00:00:00TO "COMM BD#39/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-29 Cont ID  
Sent By pkrauss Date 2004-12-29 Time 07:15 Rev Time 0.00
Received By pkrauss Date 2004-11-23 Time 10:46 Sent To  
Notes
2004-11-23 00:00:00TO COMM BD#8@ADDRESSING FOR NEW
 ADDRESS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-02-22 Cont ID  
Sent By pkrauss Date 2005-02-22 Time 07:33 Rev Time 0.55
Received By pkrauss Date 2005-02-22 Time 07:33 Sent To B
Notes
2005-02-22 00:00:00PROVISO:
 ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION, WALK-IN COOLERS
 AND GAS.(CUT SHEETS FOR THE COOLER,
 HOOD AND FIRE SUPPRESSION PLANS
 SUBMITTED & APPROVED WITH THIS PERMIT).
  
 WELDS ARE TO BE INSPECTED PRIOR TO
 COVERING WITH THE UNIFRAX-FIRE WRAP
 INDICATED ON PLAN SHEET H-1.
  
 PLEASE REFERENCE THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS FOR THE
 PROTECTION FROM UV RAYS TO THE PVC
 CONDENSATE LOCATED ON THE ROOF.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-12-29 Cont ID  
Sent By pkrauss Date 2004-12-29 Time 07:07 Rev Time 0.55
Received By pkrauss Date 2004-12-29 Time 06:34 Sent To  
Notes
2004-12-29 00:00:00PROVISO:PLAN CHECK
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPPRESSION, WALK-IN COOLERS, AND
 GAS.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA AND CUT SHEETS FOR THE
 WALK-IN COOLER/FREEZER WITH PERMIT
 APPLICATION.
  
 WELDS ARE TO BE INSPECTED PRIOR TO
 COVERING WITH THE UNIFRAX-FIRE WRAP
 INDICATED ON PLAN SHEET H-1.
  
 PLEASE REFERENCE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS FOR THE
 PROTECTION FROM UV RAYS TO THE PVC
 CONDENSATE LOCATED ON THE ROOF.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-17 Cont ID  
Sent By kstevens Date 2005-02-17 Time 18:35 Rev Time 1.50
Received By kstevens Date 2005-02-17 Time 18:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-02-07 Cont ID  
Sent By kstevens Date 2005-02-07 Time 08:34 Rev Time 3.00
Received By kstevens Date 2005-02-04 Time 16:57 Sent To  
Notes
2005-02-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) TWO SETS OF LANDSCAPE PLANS WERE
 SUBMITTED. PLEASE REMOVE THE OLD/VOIDED
 SHEETS AND SUBMIT TWO COMPLETE SETS OF
 PLANS FOR REVIEW.
 2) LANDSCAPE PLANS SHTS L1, L2, & L3. A
 TITLE BLOCK IS REQUIRED FOR THE
 LANDSCAPE ARCHITECT.THE FOLLOWING
 INFORMATION IS REQUIRED.
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 61G1-16.004(1)(2)(6) & FS
 481.219/481,2055 - SEE COMMENTS 5 & 6
 FROM PREVIOUS REVIEW. - ALSO SEE SHT A-3
 FOR INITIALS AND CERTIFICATE OF
 AUTHORIZATION.
 3) FROM PREVIOUS REVIEW: (FOLLOWING
 INFORMATION REQUIRED FOR GAS PERMIT:
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. MANUAL
 VALVES, UNIONS, AND EMERGENCY HOOD SHUT
 DOWN VALVES SHALL BE SHOWN ON THE RISER
 DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-27 Cont ID  
Sent By kstevens Date 2004-12-27 Time 12:56 Rev Time 8.00
Received By kstevens Date 2004-12-23 Time 18:55 Sent To  
Notes
2004-12-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PLANS SHALL BE ROUTED TO FDBR,
 DIVISION OF BUSINESS REGULATION, HOTEL
 AND RESTURANT DIVISION FOR REVIEW.
 RESUBMIT WITH EACH SET OF PLANS STAMPED
 AND WORKSHEETS ATTACHED. SECTION
 101.4.7
 2) GREASE INTERCEPTORS SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE
 PER WASTE ORD. #2938-96. CONTACT MR.
 COMPO AT (561) 837-4074 OR FAX # (561)
 659-7458. SUBMIT WORKSHEET FROM MR.
 COMPO WITH PLANS WHEN RESUBMITTING.
 3) ALL SHEETS - SIGNATURE REQUIRED ON
 SEAL PER FAC 61G1-16.003,
 61G15-23.002(1)(2) & FS 481.219,
 471.025. INITIALS ARE NOT APPROVED. FULL
 FIRST AND LAST NAME REQUIRED ON THE
 SIGNATURE.
 4) SHTS 1, 2, & 3 OF 3 STATES PALM BEACH
 COUNTY WATER UTILITIES DEPARTMENT. PLANS
 ARE SUBMITTED TO "CITY OF WEST PALM
 BEACH". CHANGE DETAILS TO APPROVED
 DETAILS FOR THE CITY. SECTION 104.2.1
 5) SHTS 1, 2, & 3 OF 3 NO TITLE BLOCKS
 FOR SIGNED, SEALED, DATED PLANS AS
 REQUIRED BY FAC 61G1-16.004,
 61G15-23.002(2). PLEASE SEE ALL
 INFORMATION REQUIRED TO BE IN TITLE
 BLOCK. FS 481.2055, 471.025.
 6) ALL SHEETS, TITLE BLOCK REQUIRES A
 CERTIFICATE OF AUTHROIZATION PER FAC
 61G15-23.002, FAC 61G1-16.004 & FS
 481.219, 471.025.
 7) SHT L-2 TO BE SIGNED,SEALED,DATED AND
 ALL TITLE BLOCK INFORMATION. THIS SHEET
 CALLS FOR A PUMP/LAKE SUPPLY, BUT SHT
 C-3 INDICATES A METER AND BACKFLOW FOR
 IRRIGATION. PLEASE CLARIFY. SEC
 104.2.1.
 8) SHT C-5 DUMPSTER FLOOR DRAIN
 INDICATES CONNECTION TO GREASE SYSTEM.
 STORM WATER SHALL NOT DRAIN INTO THE
 GREASE WASTE SYSTEM. PLEASE INDICATE IF
 THE DUMPSTER PAD WILL BE COVERED.
 SECTION 104.2.1 & CITY CODE SECTION
 90-125(5).
 9) SHT P-1 STORM DRAIN RISER DIAGRAM.
 HORIZONTAL DRAINAGE PIPING SHALL BE
 INSTALLED IN UNIFORM ALIGNMENT AR
 UNIFORM SLOPES. PIPING FROM 1ST ROOF
 DRAIN IS SHOWN AT 1/4"FT AND PIPING
 DOWNSTREAM OF 2ND ROOF DRAIN IS SHOWN AT
 1/2"FT. THE PIPING SHALL BE UNIFORM IN
 SLOPE. SECTION 704.1.
 10) SHT P-1 CONDENSATE LINES TO FLOOR
 DRAIN #2. FLOOR DRAINS ARE NOT APPROVED
 AS AN INDIRECT WASTE RECEPTOR. SAFE
 WASTES ARE NOT APPROVED. EITHER A FLOOR
 SINK OR A HUB DRAIN ARE APPROVED PER
 SECTION 802.3OR 802.3.2. - INDIRECT
 WASTE RECEPTORS SHALL BE LOCATED SO AS
 NOT TO CREATE A TRIPPING HAZARD.
 11) SHT P-1 DETAIL 3/P-1 AND SANT. RISER
 DIAGRAM SHOW A 2" VENT FOR THE LAV IN
 THE WOMENS TOILET ROOM, BUT SANT. PIPING
 PLAN SHOWS A 3" VENT. PLEASE CORRELATE
 PLANS TO SHOW THE SAME INFORMATION.
 SECTION 104.2.1.
 12) SHT P-2 WATER RISER DIAGRAM SHOWS
 VACUUM BREAKERS AT EACH FIXTURE. (SEE
 SHT P-3 PLUMBING LEGEND). PLEASE
 CLARIFY. (INFORMATIONAL) AIR CHAMBERS
 ARE NOT APPROVED. WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9 AT QUICK
 CLOSING VALVES ONLY. - SECTION 606.1(4)
 FULL OPEN VALVES ARE REQUIRED ON THE TOP
 OF EVERY WATER DOWN-FEED PIPE.
 13) SHT P-2 WATER FILTER UNITS MUST MEET
 THE REQUIREMENTS OF NSF-42. SECTION
 611.1. SUBMIT MANUF. SPECIFICATION
 SHEETS.
 14) SHT P-2 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PLANS/PERMIT:
 A. TYPE OF GAS, (LP OR NATURAL)
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 15) SHT P-4 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL IS REQUIRED PER
 SECTION 607.3.2
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-02-01 Cont ID  
Sent By rgranber Date 2004-12-14 Time 08:30 Rev Time 0.00
Received By rgranber Date 2005-02-01 Time 10:02 Sent To I
Notes
2004-12-14 00:00:00HAS NOT BEEN APPROVED BY THE SITE PLAN
 REVIEW PROCESS.APPLICANT MUST SUBMIT A
 LETTER TO CONSTRUCTION SERVICES FROM THE
 PLANNING DEPARTMENT STATING THE PROPOSED
 DEVELOPMENT HAS BEEN REVIEW AND APPROVED
 BY THE PLANNIND DEPARTMENT.