Plan Review Details - Permit 04111131
Plan Review Stops For Permit 04111131
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-12-14 Cont ID  
Sent By rmcdouga Date 2004-12-14 Time 08:01 Rev Time 0.00
Received By rmcdouga Date 2004-12-14 Time 07:11 Sent To  
Notes
2004-12-14 00:00:00REVISIONS TO SHEETS A1,A7,A8 ARE OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-12-07 Cont ID  
Sent By rmcdouga Date 2004-12-07 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2004-12-07 Time 15:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-01 Cont ID  
Sent By rmcdouga Date 2004-12-01 Time 07:38 Rev Time 0.00
Received By rmcdouga Date 2004-12-01 Time 07:09 Sent To Z
Notes
2004-12-01 00:00:00DENIED
  
  
 ADDITIONAL COPY OF SURVEY AND ENERGY
 CALCULATIONS ARE REQUIRED.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 23:47 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 23:47 Sent To PC
Notes
2006-01-20 00:00:00REDLINED PLANS.
  
 GEC HAS BEEN CHANGED TO A #4 WHEN A MIN
 OF #2 AWG IS REQUIRED BASED ON
 250.66,310.15B6
  
 ** PLEASE KNOW, ORIG PLANS AND ALL
 REVISIONS THROUGH REV #10 SHOWED 1/0 AWG
 , 2-COPPER GRND RODS, CWP AND FOOTER
 STEEL BOND WITH #4.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-01-05 Cont ID  
Sent By dpalmer Date 2006-01-05 Time 15:48 Rev Time 0.00
Received By dpalmer Date 2006-01-05 Time 15:42 Sent To  
Notes
2006-01-05 00:00:00REV #10

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-11-16 Cont ID  
Sent By dpalmer Date 2005-11-16 Time 15:00 Rev Time 0.00
Received By dpalmer Date 2005-11-16 Time 15:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-11-08 Cont ID  
Sent By dpalmer Date 2005-11-08 Time 17:02 Rev Time 0.00
Received By dpalmer Date 2005-11-08 Time 17:02 Sent To  
Notes
2005-11-08 00:00:00PLANS NOT SEALED BY ARCH.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-22 Cont ID  
Sent By dpalmer Date 2005-09-22 Time 10:09 Rev Time 0.40
Received By dpalmer Date 2005-09-22 Time 10:09 Sent To  
Notes
2005-09-22 00:00:00REV'S FOR FINAL.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-12-07 Cont ID  
Sent By rmcdouga Date 2004-12-07 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2004-12-07 Time 15:44 Sent To  
Notes
2004-12-07 00:00:00PASSED UNDER MASTER #04041127

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2004-12-07 Cont ID  
Sent By rmcdouga Date 2004-12-07 Time 15:44 Rev Time 0.00
Received By rmcdouga Date 2004-12-07 Time 15:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-12-07 Cont ID  
Sent By rmcdouga Date 2004-12-07 Time 15:41 Rev Time 0.00
Received By rmcdouga Date 2004-12-07 Time 15:41 Sent To  
Notes
2004-12-07 00:00:00PASSED UNDER MASTER # 04041127

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-17 Cont ID  
Sent By adarroug Date 2006-01-17 Time 17:18 Rev Time 0.00
Received By adarroug Date 2006-01-17 Time 17:18 Sent To E
Notes
2006-01-17 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-21 Cont ID  
Sent By adarroug Date 2005-10-21 Time 16:25 Rev Time 0.00
Received By adarroug Date 2005-10-21 Time 16:25 Sent To E
Notes
2005-10-21 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-19 Cont ID  
Sent By adarroug Date 2005-09-19 Time 15:46 Rev Time 0.00
Received By adarroug Date 2005-09-19 Time 15:46 Sent To E
Notes
2005-09-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-02 Cont ID  
Sent By mjacobs Date 2004-12-02 Time 11:20 Rev Time 0.00
Received By mjacobs Date 2004-12-02 Time 11:20 Sent To B
Notes
2004-12-02 00:00:00SENT TO "ROB MCD" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-23 Cont ID  
Sent By mjacobs Date 2004-11-23 Time 08:03 Rev Time 0.00
Received By mjacobs Date 2004-11-23 Time 08:03 Sent To B
Notes
2004-11-23 00:00:00SEMT TO "ROB MCD" DESK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-12-07 Cont ID  
Sent By rmcdouga Date 2004-12-07 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2004-12-07 Time 15:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-12-07 Cont ID  
Sent By rmcdouga Date 2004-12-07 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2004-12-07 Time 15:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-12-06 Cont ID  
Sent By mmclean Date 2004-12-06 Time 12:18 Rev Time 0.00
Received By mmclean Date 2004-12-06 Time 12:18 Sent To B
Notes
2004-12-06 00:00:00NEED ANOTHER SURVEY BEFORE PERMIT IS
 ISSUED. RETURN PLANS TO ROBERT MCD