Plan Review Details - Permit 04110927
Plan Review Stops For Permit 04110927
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2005-07-26 Cont ID  
Sent By rbrown Date 2005-07-26 Time 10:28 Rev Time 0.00
Received By rbrown Date 2005-07-26 Time 09:46 Sent To  
Notes
2005-07-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 ARCHITECTURAL REVISION SUBMITTED 7/5/05
 FOR ENTRY PORCH ARCH DETAIL AND REAR
 PORCH BEAM SUPPORT COLUMNS
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 104.2.2ARCHITECT'S SIGNATURE
 AND SEAL.NEITHER THE SUBMITTED LETTER
 OR THE 8.5"X 11" SKETCH SHEETS CARRY
 ORIGINAL SIGNATURE, RAISED SEAL, OR
 PRINTED LICENSE NUMBER OF JAMES E.
 GILGENBACH.
  
 2) 481.219(2) F.S.CERTIFICATE OF
 AUTHORIZATION.JAMES A. GILGENBACH
 ARCHITECTURE & PLANNING DOES NOT HAVE A
 CERTIFICATE OF AUTHORIZATION SO THE
 WORDS "ARCHITECTURE & PLANNING" MUST
 DELETED FROM THE TITLE BLOCK AND
 LETTERHEAD.THEY WERE DELETED ON THE
 PERMIT APPROVED SET OF PLANS.THIS
 COMMENT HAS BEEN MADE THREE TIMES
 ALREADY ON THE PERMIT APPLICATION.THE
 ARCHITECT MUST CEASE USING THE WORDS
 "ARCHITECTURE & PLANNING" IN THIS WAY OR
 THE BOARD OF ARCHITECTURE WILL BE
 INFORMED.
  
 3) FBC* 104.2THE SUBMITTED 8.5"X 11"
 SKETCH SHEET SHOWING A STEEL COLUMN DOES
 NOT CORRELATE WITH THE PERMIT APPROVED
 PLANS.THOSE PLANS DO NOT APPEAR TO
 SHOW A STEEL COLUMN OR INTERIOR PAD BASE
 AND WOULD NEED TO BE REVISED TO SHOW THE
 LOCATION OF THE COLUMN.IF THE LOCATION
 IS NOT SHOWN, THE COLUMN DETAILS CANNOT
 BE REVIEWED/STAMPED.ALSO THE COLUMN
 DETAIL SHEET DOES NOT HAVE A PROJECT
 SPECIFIC TITLE BLOCK OR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE SHEET.IF THAT PERSON IS NOT THE
 ARCHITECT OF RECORD THEN THE ARCHITECT
 MUST REVIEW, STAMP AND INITIAL/DATE THE
 PLAN AS BEING 'REVIEWED'. (REF FBC*
 104.2.1 AND 61G1-16.004FL. ADMIN.
 CODE.)
  
 4) FBC* 104.2.1THE REVISIONS DESCRIBED
 IN THE LETTER MUST BE DRAWN ON THE PLANS
 AND THE REVISED PLANS SUBMITTED FOR
 REVIEW AND RECORDS.
  
 5) FBC* 104.2.1 ON WALL FRAMING DETAILS
 A AND B, SOME OF THE ANCHOR AND STRAP
 REFERENCES DO NOT STATE THE SIZE AND
 NUMBER OF NAILS TO BE USED.ADD NOTES
 TO SPECIFY THE NUMBER AND TYPE OF
 FASTENERS FOR EACH STRAP/TIE.ALSO,
 THESE DETAILS MAKE A TOTAL OF FIVE
 REFERENCES TO EITHER USPRT24T, USP
 RT24F OR USP RT18T TIES.PLEASE NOTE
 THAT WHILE THESE PARTICULAR TIES ARE
 REFERENCED IN THE 2004 USP CATALOGUE,
 THEY DO NOT APPEAR IN THE 2005 CATALOGUE
 SO AVAILABILITY MAY BE LIMITED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-06-24 Cont ID  
Sent By rbrown Date 2005-06-24 Time 17:15 Rev Time 0.00
Received By rbrown Date 2005-06-24 Time 17:15 Sent To  
Notes
2005-06-24 00:00:00REVISION SUBMITTED ON 4/8/05 AND
 RE-SUBMITTED ON 5/23/05 FOR SHEETS
 A1, A2, A3, A4 AND A5
  
 INFORMATIVE:
 JAMES A. GILGENBACH ARCHITECTURE &
 PLANNING DOES NOT HAVE A CERTIFICATE OF
 AUTHORIZATION SO THE WORDS "ARCHITECTURE
 & PLANNING" WERE DELETED FROM THE TITLE
 BLOCK LIKE THEY WERE ON THE PERMIT
 APPROVED SET OF PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-04-21 Cont ID  
Sent By rbrown Date 2005-04-21 Time 10:06 Rev Time 0.00
Received By rbrown Date 2005-04-21 Time 09:59 Sent To  
Notes
2005-04-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 4/8/05 FOR SHEETS
 A1, A2, A3, A4 AND A5
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 104.2.1.3THE USE OF 'WITE-OUT'
 OR ANY OTHER TYPE OF COVER-UP CORRECTION
 FLUID/TAPE IS NOT APPROPRIATE FOR PLANS
 SUBMITTED FOR PERMITTING PURPOSES.
 SUBMIT NEW PLANS.
  
 2) FBC 104.2.2EACH HAND-DRAWN CHANGE
 MADE TO COPIES OF PLANS SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER MUST
 BE SIGNED AND DATED BY THAT DESIGNER OF
 RECORD.
  
 3) FBC 1606.1.3SHEET A3, ROOF FRAMING
 PLAN.THE BEARING WALL DETAIL C/2 ON
 SHEET A2 REFERS TO GALV. METAL ANCHOR
 STRAPS AT EACH TRUSS.THERE ARE NO
 TRUSS ANCHORS SHOWN FOR THIS LOCATION ON
 SHEET A3, ROOF FRAMING PLAN.AMEND THE
 ROOF FRAMING PLAN.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-22 Cont ID  
Sent By rbrown Date 2005-03-22 Time 13:16 Rev Time 0.00
Received By rbrown Date 2005-03-22 Time 13:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-03-22 Cont ID  
Sent By rbrown Date 2005-03-22 Time 13:15 Rev Time 0.00
Received By rbrown Date 2005-02-25 Time 17:05 Sent To  
Notes
2005-02-25 00:00:00IT IS NOTED THAT THE SUBMITTED HURRICANE
 SHUTTER SCHEDULE AND KEY PLAN CALL FOR
 SHUTTERS WITH EGRESS CAPABILITY FOR
 OPENING #18.THE SUBMITTED HURRICANE
 SHUTTER PRODUCT APPROVAL DOES NOT SHOW
 AN OPTION FOR EGRESS SHUTTERS.SUBMIT A
 PRODUCT APPROVAL FOR AN EGRESS CAPABLE
 HURRICANE SHUTTER OR REVISE AT LEAST ONE
 OF THE EXTERIOR DOORS FOR AN IMPACT
 RATED OR NON-GLAZED DOOR.THIS IS TO
 ALLOW ENTRY TO THE HOUSE AFTER
 INSTALLING ALL REQUIRED SHUTTERS.
 SUBMIT PRODUCT APPROVALS APPROPRIATE FOR
 THE CHOSEN SOLUTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-02-08 Cont ID  
Sent By rbrown Date 2005-02-08 Time 18:00 Rev Time 0.00
Received By rbrown Date 2005-02-08 Time 18:00 Sent To  
Notes
2005-02-08 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/14/05:
  
 10) STORM PANELS.SUBMITTAL OF THE
 CORRECT SCHEDULE IS NOTED.SHUTTER
 PANEL #19 HAS A 104" SPAN AND A WIND
 PRESSURE OF -36 PSF.THIS EXCEEDS THE
 MAXIMUM DESIGN PRESSURE LISTED, FOR
 THAT
 SPAN, ON THE 'MAX SPAN TABLE' ON THE
 PRODUCT APPROVAL NOA DRAWINF SHEET 2 OF
 3.AMEND THE SCHEDULE TO SHOW SPAN IN
 THE SHORTER DIRECTION OR SUBMIT A
 PRODUCT APPROVAL FOR PANELS WITH
 ADEQUATE SPAN CAPABILITY.ALSO, THE
 'BUCK OPENING SIZES' STATED ON THE
 SCHEDULE ARE SMALLER THAN THE OPENING
 SIZE GIVEN ON PLAN SHEET A1 FOR THE
 FOLLOWING STORM PANEL NUMBERS:
 PANEL #4 - STATED 54" SHOULD BE 56"
 PANEL #8 - STATED 95" SHOULD BE 120"
 PANEL #10 - STATED 54" SHOULD BE 56".
 THE PROPOSED SHUTTERS WILL STILL WORK
 FOR THESE CORRECTED OPENING SIZES.
 AMEND THE SCHEDULE.
  
 11) EXTERIOR SWINGING DOORS.THIS
 COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED. AT LEAST ONE OF THE EXTERIOR
 DOORS SHALL BE IMPACT RATED OR
 NON-GLAZED SO THAT ENTRY TO THE HOUSE
 IS
 STILL POSSIBLE AFTER INSTALLING ALL
 REQUIRED SHUTTERS. AMEND THE PLANS OR
 SUBMIT PRODUCT APPROVALS FOR IMPACT
 RATED DOORS.
  
 17) FIXED WINDOWS.THIS COMMENT HAS
 NOT
 BEEN ADDRESSED.THE AAMA TEST REPORT
 01-44553.02, ATTACHED TO THE SUBMITTED
 SIMONTON FIXED WINDOW STATEWIDE PRODUCT
 APPROVAL (NUMBER FL178), IS FOR A WINDOW
 WITH A SMALLER DIMENSION OF 3'-11".
 THIS IS LESS THAN THE SIZE OF THE ARCHED
 TRANSOM ABOVE THE FRONT ENTRY DOOR.
 ALSO THE CURRENT STATEWIDE PRODUCT
 APPROVAL LISTING FOR FL178 HAS CHANGED
 SUBSTANTIALLY FROM THE VERSIOPN
 SUBMITTED.IT IS NOW NUMBER FL178-R1.
 SUBMIT TWO UP-TO-DATE COPIES OF
 FL178-R1, MARKED TO SHOW WHICH PRODUCT
 MODEL/NAME IS PROPOSED.
  
 18) 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED AS THE
 DESCRIBED IMPROVEMENT OR CONSTRUCTION
 WAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING.YOU ARE ADVISED TO RECORD
 THE NOTICE OF COMMENCEMENT AT THE TIME
 OF PERMIT ISSUE TO AVOID POSSIBLE
 EXPIRATION.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL
 INFO
  
 TELEPHONE: (561) 805 6716ROBERT
 BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-18 Cont ID  
Sent By rbrown Date 2005-01-14 Time 14:58 Rev Time 0.00
Received By rbrown Date 2005-01-14 Time 14:57 Sent To  
Notes
2005-01-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 12/6/04:
  
 3) 481.219(2) F.S.CERTIFICATE OF
 AUTHORIZATION.THIS COMMENT HAS NOT
 BEEN ADDRESSED.THE ARCHITECT'S
 TITLE BLOCK DOES NOT SHOW A CERTIFICATE
 OF AUTHORIZATION NUMBER FOR THE
 ARCHITECTURAL FIRM.A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, PARTNERSHIP, OR PERSON
 PRACTICING UNDER A FICTITIOUS NAME,
 OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.ADD THE
 NUMBER (MAY BE ADDED BY HAND ON EACH
 SHEET) OR REMOVE THE WORDS
 "ARCHITECTURE
 AND PLANNING" FROM EACH TITLE BLOCK.
  
 4) FBC* 104.2.1MECHANICAL PLAN.THIS
 COMMENT HAS NOT BEEN ADDRESSED.FRED
 MENSCHEL SHALL SIGN THE MECHANICAL PLAN
 AS THE 'PERSON RESPONSIBLE FOR THE
 DESIGN'.
  
 9) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SUBMIT A PRODUCT APPROVAL FOR THE GLASS
 BLOCKS.
  
 10) STORM PANEL SCHEDULE.THIS COMMENT
 HAS NOT BEEN ADDRESSED.THE
 OPENING/SHUTTER SCHEDULE SUBMITTED WITH
 THE SHUTTER PRODUCT APPROVAL IS FOR A
 DIFFERENT MODEL FLOOR PLAN.SUBMIT AN
 APPROPRIATE SCHEDULE.
  
 11) EXTERIOR SWINGING DOORS.THIS
 COMMENT HAS NOT BEEN PROPERLY
 ADDRESSED.
 AT LEAST ONE OF THE EXTERIOR DOORS
 SHALL BE IMPACT RATED OR NON-GLAZED.
 AMEND THE PLANS OR SUBMIT PRODUCT
 APPROVALS FOR IMPACT RATED DOORS.THE
 FRONT ENTRY DOOR IS SHOWN AS A GLAZED
 INSWING DOUBLE DOOR BUT NO PRODUCT
 APPROVAL HAS BEEN SUBMITTED FOR THIS
 TYPE OF DOOR. SUBMIT A PRODUCT
 APPROVAL.
 ALSO, THE SUBMITTED MIAMI-DADE NOA FOR
 THE COVERED PATIO DOORS IS FOR A
 'PREMDOR' FIBERGLASS GLAZED OUTSWING
 DOOR.THIS WAS ATTACHED TO A STATEWIDE
 PRODUCT APPROVAL FOR A 'MASONITE
 INTERNATIONAL' FIBERGLASS DOOR UNIT.
 IS
 THE LATER A GLAZED OR NON-GLAZED DOOR
 AND HOW IS A 'MASONITE INTERNATIONAL'
 PRODUCT APPROVAL LISTING RELEVANT TO A
 'PREMDOR' NOA.IF THE TWO COMPANIES
 ARE
 AFFILIATED, SUBMIT A MANUFACTURER'S
 LETTER OR OTHER DOCUMENTATION TO SHOW
 THAT THE TWO PRODUCT APPROVALS APPLY TO
 THE SAME FIBERGLASS GLAZED OUTSWING
 DOOR
 PRODUCT.
  
 12) THIS COMMENT HAS NOT BEEN
 ADDRESSED.
 THE PRODUCT APPROVAL SHEETS HAVE STILL
 NOT BEEN MARKED, AS APPROPRIATE, TO
 IDENTIFY WHICH PRODUCT
 OPTIONS/MATERIALS/SIZES ARE TO BE USED.
  
 16) THE SUBMITTED SLIDING GLASS DOOR
 PRODUCT APPROVAL IS NOT APPLICABLE AS
 THERE ARE NO DOORS OF THIS TYPE
 SPECIFIED ON THE PLANS.
  
 17) THE AAMA TEST REPORT 01-44553.02,
 ATTACHED TO THE SUBMITTED SIMONTON
 FIXED
 WINDOW STATEWIDE PRODUCT APPROVAL, IS
 FOR A WINDOW WITH A SMALLER DIMENSION
 OF
 3'-11".THIS IS LESS THAN THE SIZE OF
 THE ARCHED TRANSOM ABOVE THE FRONT
 ENTRY
 DOOR.ALSO THE CURRENT STATEWIDE
 PRODUCT APPROVAL LISTING FOR FL178 HAS
 CHANGED SUBSTANTIALLY.SUBMIT AN
 UP-TO-DATE COPY OF FL178 MARKED TO SHOW
 WHICH PRODUCT MODEL/NAME IS PROPOSED.
  
 18) 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED AS THE
 DESCRIBED IMPROVEMENT OR CONSTRUCTION
 WAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING.YOU ARE ADVISED TO RECORD
 THE NOTICE OF COMMENCEMENT AT THE TIME
 OF PERMIT ISSUE TO AVOID POSSIBLE
 EXPIRATION.
  
 19) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE
 RESUBMITTED
 PLANS.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL
 INFO
 TELEPHONE: (561) 805 6716ROBERT
 BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-06 Cont ID  
Sent By pkrauss Date 2004-12-06 Time 08:55 Rev Time 0.00
Received By rbrown Date 2004-12-06 Time 08:55 Sent To  
Notes
2004-12-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 104.6.5BUILDING PERMIT
 VALUATION.THE STATED VALUE OF THE
 PROJECT HAS BEEN UNDER-ESTIMATED AT
 $215,000.THE VALUE, CALCULATED USING
 THE SOUTHERN BUILDING CODE CONGRESS
 INTERNATIONAL (SBCCI) VALUATION TABLES,
 IS $293,249.THE PERMIT APPLICATION
 FEE HAS BEEN ADJUSTED ACCORDINGLY, SO
 THERE IS AN OUTSTANDING BALANCE
 (INCLUDING THE ASSESSED RADON FEES) OF
 $832.03.THE REQUIRED AMOUNT SHALL BE
 PAID BEFORE THE PLANS CAN BE
 RESUBMITTED.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) 481.219(2) F.S.THE ARCHITECT'S
 TITLE BLOCK DOES NOT SHOW A CERTIFICATE
 OF AUTHORIZATION NUMBER FOR THE
 ARCHITECTURAL FIRM.A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, PARTNERSHIP, OR PERSON
 PRACTICING UNDER A FICTITIOUS NAME,
 OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.ADD THE
 NUMBER (MAY BE ADDED BY HAND ON EACH
 SHEET) OR REMOVE THE WORDS
 "ARCHITECTURE
 AND PLANNING" FROM EACH TITLE BLOCK.
  
 4) FBC* 104.2.1MECHANICAL PLAN.FRED
 MENSCHEL SHALL SIGN THE MECHANICAL PLAN
 AS THE 'PERSON RESPONSIBLE FOR THE
 DESIGN'.
  
 5) FBC 13-103.0THE ENERGY CODE
 COMPLIANCE FORMS HAVE BEEN REDLINED TO
 SHOW THE CORRECT PROJECT INFORMATION.
  
 6) FBC 2309.6ACCESS TO ATTIC SPACE
 EACH ATTIC SPACE WITH A CLEAR HEIGHT OF
 24" OR GREATER SHALL BE PROVIDED WITH
 AN INTERIOR ATTIC ACCESS OPENING NOT
 LESS THAN 20"X 36".AMEND THE PLAN.
  
 7) FBC TABLE 1604.1SHEET A3, ROOF
 LOADS TABLE.FOR 'ATTICS WITH STORAGE'
 IN DWELLINGS, THE MINIMUM BOTTOM CHORD
 LIVE LOAD IS 30 PSF.AMEND THE TABLE.
  
 8) FBC TABLE 600THE GLASS BLOCK IN
 THE WEST WALL ARE ON A ZERO LOT LINE
 AND SHALL BE A MINIMUM OF 1-HOUR
 FIRE-RATED ASSEMBLIES.ANNOTATE THE
 PLAN.
  
 9) SUBMIT A PRODUCT APPROVAL FOR THE
 GLASS BLOCKS.
  
 10) THE OPENING/SHUTTER SCHEDULE
 SUBMITTED WITH THE SHUTTER PRODUCT
 APPROVAL IS FOR A DIFFERENT MODEL FLOOR
 PLAN.SUBMIT AN APPROPRIATE SCHEDULE.
  
 11) THE PRODUCT APPROVALS SUBMITTED FOR
 THE FRONT ENTRY DOOR AND COVERED PATIO
 DOORS ARE FOR PRODUCTS WITH NO IMPACT
 RATING.SUBMIT PRODUCT APPROVALS FOR
 DOORS WITH HURRICANE MISSILE IMPACT
 RATING.NOTE THAT AT LEAST ONE DOOR
 MUST BE IMPACT RATED, WITHOUT THE NEED
 FOR SHUTTERS, TO ALLOW ENTRY/EXIT AFTER
 SHUTTER INSTALLATION.
  
 12) THE PRODUCT APPROVAL SHEETS SHALL
 BE MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED.AS AN EXAMPLE, THE
 SUBMITTED GARAGE DOOR PRODUCT APPROVAL
 HAS BEEN MARKED TO SHOW THE PRODUCTS
 THAT SATISFY THE REQUIREMENTS FOR THIS
 PROJECT.
  
 13) 9B-72 F.A.C.THE SUBMITTED PRODUCT
 APPROVALS SHALL EACH HAVE A STATEWIDE
 OR LOCAL PRODUCT APPROVAL LISTING.AS
 AN EXAMPLE, THE SUBMITTED GARAGE DOOR
 PRODUCT APPROVAL HAS BEEN ATTACHED TO
 THE RELEVANT STATEWIDE LISTING.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 14) PRODUCT APPROVAL.RULE 9B-72 FAC.
 FOR PRODUCTS WHICH DO NOT HAVE
 STATEWIDE PRODUCT APPROVAL, LOCAL
 PRODUCT APPROVAL CAN BE ACHIEVED IF
 THERE IS A QUALITY ASSURANCE PROGRAM IN
 PLACE WITH A STATE APPROVED QUALITY
 ASSURANCE ENTITY.IF NEITHER IS
 APPLICABLE, THEN SITE SPECIFIC APPROVAL
 IS REQUIRED.LOCAL PRODUCT APPROVAL
 WILL ALLOW A PRODUCT TO BE USED, IN
 ACCORDANCE WITH THE TEST CRITERIA,
 THROUGHOUT THE JURISDICTION OF WEST PALM
 BEACH.SITE SPECIFIC PRODUCT APPROVAL
 WILL ALLOW A PRODUCT TO BE USED ONLY ON
 THE PROJECT FOR WHICH THAT SITE SPECIFIC
 APPROVAL IS GRANTED. LOCAL AND SITE
 SPECIFIC PRODUCT APPROVAL APPLICATION
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 APPROVED QUALITY ASSURANCE ENTITIES ARE
 LISTED ON THE DCA WEBSITE:
 WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_
 REGI_SRCH.ASP
  
 15) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE
 RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-02-28 Cont ID  
Sent By btrobaug Date 2006-02-28 Time 08:37 Rev Time 0.50
Received By btrobaug Date 2006-02-28 Time 08:37 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-02-03 Cont ID  
Sent By btrobaug Date 2006-02-03 Time 16:13 Rev Time 0.50
Received By btrobaug Date 2006-02-03 Time 16:04 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-06-07 Cont ID  
Sent By dpalmer Date 2005-06-07 Time 07:10 Rev Time 0.25
Received By dpalmer Date 2005-06-07 Time 07:10 Sent To B
Notes
2005-06-07 00:00:00************** NOTES REDLINED *********
  
  
 *** PLEASE SEE BELOW FOR THE SAME ITEM
 PREVIOUSLY NOTED ON TWO PREVIOUS REVIEWS
 WHICH WAS NOT CORRECTED.
 THIS WAS REDLINED ONCE AGAIN.
  
 1)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTOR SHOWN FROM METER TO MAIN/FIRST
 MEANS OF DISCONNETC. PLEASE SEE
 250.6,250.24, AN EQUIPMENT GROUNDING
 CONDUCTOR SHALL NOT BE INSTALLED FROM
 METER TO FIRST MEANS OF DISCONNECT.
  
 PLEASE SEE REVISION SHEET DID NOT
 CONTAIN A CHECK OFF FOR PLUMB REVSION,
 YET PLUMB RISER IS ON ELEC SHEET. THIS
 WAS CROSSED OUT.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-04-11 Cont ID  
Sent By dpalmer Date 2005-04-11 Time 20:16 Rev Time 0.25
Received By dpalmer Date 2005-04-11 Time 20:16 Sent To B
Notes
2005-04-11 00:00:00******* UNSAT *********
  
 1)NOTE: PLEASE SEE HAND-DRAWN CHANGES
 ARE NOT PERMITTED TO PLANS WHICH ARE
 SIGNED, DATED AND SEALED BY AN ARCHITECT
 OR ENGINEER.
 FS 481.221, 471.025
 PLEASE SEE ONLY HAND DRAWN CHANGES ARE
 PERMITTED, HOWEVER "EACH" CHANGE MUST BE
 SIGNED AND DATED.
 PLEASE ALSO SEE BLDG REVIEW NOTES,
 "WHITE-OUT" IS NOT PERMITTED ON PLANS.
  
  
 2)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTOR SHOWN FROM METER TO MAIN/FIRST
 MEANS OF DISCONNETC. PLEASE SEE
 250.6,250.24, AN EQUIPMENT GROUNDING
 CONDUCTOR SHALL NOT BE INSTALLED.
  
 3)NOTE: PLEASE SEE PLANS INLCUDE PLUMB
 RISER, IF THIS IS NOT PART OF
 CHANGES/REVISION, PLEASE CROSS OUT AS
 "NIC" ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 07:56 Rev Time 0.33
Received By dpalmer Date 2004-12-23 Time 07:56 Sent To P
Notes
2004-12-23 00:00:00SENT TO PLUMB DUE TO NEW SHEETS.
  
 NO EQUIPMENT GROUNDING FROM METER TO
 MAINS. 250.6,250.24

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-23 Cont ID  
Sent By dpalmer Date 2004-11-23 Time 07:26 Rev Time 0.33
Received By dpalmer Date 2004-11-23 Time 07:26 Sent To M
Notes
2004-11-23 00:00:00****** UNSAT ******
  
 1)NOTE: THE LAUNDRY CIRCUIT CALCULATION
 MUST COMPLY WITH 220.116(B).(1500 VA).
  
 2)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC
 NOTE MNETIONS RECEPTS ONLY.
  
 3)NOTE: PLEASE MOVE SD "INTO" MASTER
 BEDRM. NFPA-72 8-1.4.1.6.2
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAINS TO
 PANELS.
 250.110,250.122,250.24.
  
 5)NOTE: PLEASE SEE PANEL "B" INDICATES A
 WHIRLPOOL TUB, YET PLANS DO NOT INDICATE
 ELECTRICAL FOR THIS.
  
 6)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS FOR
 REVIEW AND STAMPING.
 ONE SET/COPY OF OLD SHOULD BE SUBMITTED
 FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 16:32 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 16:32 Sent To B
Notes
2005-07-05 00:00:00TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-05-27 Cont ID  
Sent By adarroug Date 2005-05-27 Time 10:57 Rev Time 0.00
Received By adarroug Date 2005-05-27 Time 10:56 Sent To E
Notes
2005-05-27 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-04-08 Cont ID  
Sent By adarroug Date 2005-04-08 Time 16:45 Rev Time 0.00
Received By adarroug Date 2005-04-08 Time 16:45 Sent To E
Notes
2005-04-08 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-04-05 Cont ID  
Sent By adarroug Date 2005-04-05 Time 10:00 Rev Time 0.00
Received By adarroug Date 2005-04-05 Time 10:00 Sent To E
Notes
2005-04-05 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-22 Cont ID  
Sent By adarroug Date 2005-02-22 Time 10:24 Rev Time 0.00
Received By adarroug Date 2005-02-22 Time 10:24 Sent To B
Notes
2005-02-22 00:00:00TO RB DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-24 Cont ID  
Sent By mjacobs Date 2005-01-24 Time 12:03 Rev Time 0.00
Received By mjacobs Date 2005-01-24 Time 12:03 Sent To B
Notes
2005-01-24 00:00:00TO "RB" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-21 Cont ID  
Sent By mjacobs Date 2004-12-21 Time 08:09 Rev Time 0.00
Received By mjacobs Date 2004-12-21 Time 08:09 Sent To E
Notes
2004-12-21 00:00:00SENT TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-06 Cont ID  
Sent By mjacobs Date 2004-12-06 Time 08:55 Rev Time  
Received By rbrown Date 2004-11-22 Time 12:49 Sent To  
Notes
2004-11-22 00:00:00SENT TO "E" SFD RACK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-18 Cont ID  
Sent By mjacobs Date 2004-11-18 Time 07:29 Rev Time  
Received By mjacobs Date 2004-11-17 Time 16:37 Sent To Z
Notes
2004-11-17 00:00:00SENT TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-11-30 Cont ID  
Sent By pkrauss Date 2004-11-30 Time 10:15 Rev Time 0.35
Received By pkrauss Date 2004-11-30 Time 10:15 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-01 Cont ID  
Sent By jleech Date 2005-01-01 Time 07:10 Rev Time 0.33
Received By jleech Date 2005-01-01 Time 07:10 Sent To B
Notes
2005-01-01 00:00:00NEW SHEETS SUBMITED OK

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-11-29 Cont ID  
Sent By kstevens Date 2004-11-29 Time 06:59 Rev Time 0.33
Received By kstevens Date 2004-11-29 Time 06:58 Sent To M
Notes
***NONE***

Review Stop Z ZONING