Plan Review Details - Permit 04110897
Plan Review Stops For Permit 04110897
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-05-13 Cont ID  
Sent By shill Date 2005-05-13 Time 14:15 Rev Time 1.00
Received By shill Date 2005-05-13 Time 13:26 Sent To PC
Notes
2005-05-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #2.
 PRESSURES REQUESTED BY PREVIOUS REVIEWER
 NOT PROVIDED.NO ATTACHMENT DETAIL
 SHOWN.
  
 2.)SHEET 5 OF 6, GENERAL NOTES, STATES
 THAT THE CABINET WEIGHT SHALL NOT EXCEED
 10962.AREN'T THE CABINETS EXISTING?
 WHERE IS THE GENERATOR WEIGHT ADDRESSED?
  
 3.)SEE PREVIOUS LIST, ITEM #3.
 VALUATION IS TOO LOW.
  
 4.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 5.)THE NOTES REFER TO CUTTING OF THE
 SLAB, CONFIRMING POST TENSION CABLE
 LOCATIONS, CUTTING AND PATCHING OF THE
 ROOF.THE PLANS SHOULD INCLUDE ONLY
 WORK DONE UNDER THIS PERMIT.IF THESE
 THINGS ARE BEING DONE, PLEASE SHOW ON
 THE PLAN.
  
 6.)THE APPLICATION REFERS TO A 12 KW
 GENERATOR, PLANS SHOW 30KW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By jwitmer Date 2004-12-15 Time 10:55 Rev Time 1.11
Received By jwitmer Date 2004-12-15 Time 10:55 Sent To  
Notes
2004-12-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110897
 ADD: 2800 N FLAGLER DR
 CONT: JOHNATHAN CROMPTON
 TEL: (561)722-4020
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE ADDITIONAL INFORMATION, THE
 PREMIT APPLICATION DOESN'T INDICATE IF
 THIS IS A REPLACEMENT OR NEW GENERATOR.
 INDICATE HOW THE GENERATOR WILL TIE INTO
 THE REQUIRED FIRE CENTRAL COMMAND
 STATION SEE 412.4.,412.7.1.1 AND
 412.7.1.2.
  
 2) THE DRAWING SUBMITTED INDICATES THAT
 THE GENERATOR WILL SIT ON TOP OF A 10
 STORY BLDG. PROVIDE DETAILS ON THE
 EXISTING STEEL WHICH THE NEW GENERATOR
 IS TO BE ATTACHED. PROVIDE THE
 ATTACHMENT TO THE STEEL, WITH ASSOCIATED
 POSITIVE AND NEGATIVE PRESSURES, THE
 BLDG IS OVER 60' IN HEIGHT DESIGN TO
 ASCE 7-98.
  
 3) THE VALUATION ON THE PERMIT IS LOW,
 THE GENERATOR CAN'T BE BOUGHT FOR THE
 AMOUNT STATED!!!!!!!!! PROVIDE WHAT WORK
 IS TO BE COMPLETED?
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-05-09 Cont ID  
Sent By dpalmer Date 2005-05-09 Time 17:15 Rev Time 0.50
Received By dpalmer Date 2005-05-09 Time 17:12 Sent To  
Notes
2005-05-09 00:00:00*********** UNSAT 2ND REVIEW *********
  
 PLEASE SEE NEW NOTES AND NOTES FROM
 PREVIOUS REVIEW WHICH STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: PLEASE SEE APPLICATION
 ORIGINALLY CAME IN SHOWING 12KW GEN.
 PLEASE SEE APPLICATION NOW INDICATES
 20KW, HOWEVER NOW PLANS INDICATE 30KW???
 PLEASE CORRELATE.
  
 PLEASE SEE NOTES BELOW TAKEN DIRECTLY
 FROM PREVIOUS REVIEW.
  
  
 3)NOTE: PELASE SUBMIT COMPLETE PACKAGE
 ON GENERATOR AND ALL EQUIPMENT.(TRANSFER
 SWITCH? ETC.
 ALL SPECS TO SHOW ALL LISTING(S) BY A
 NRTL.
  
 4)NOTE: PLEASE SEE FBC 104.6.5 FOR
 VALUATION OF PERMIT. THE VALUE APPLIED
 AT $2K IS WAY LOW. PLEASE ADJUST.
 REQUIRED TO INCLUDE VALUE FOR COMPLETE
 SCOPE OF WORK,ALL LABOR AND MATERIALS
 WEATHER OWNER SUPPLIED OR NOT.
  
 PLEASE SEE IF A VALUE IS NOT PROVIDED
 FOR SCOPE OF WORK PROPOSED, THEN A VALUE
 WILL BE APPLIED BY THIS DEPARTMENT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-24 Cont ID  
Sent By adarroug Date 2005-05-09 Time 10:07 Rev Time 0.33
Received By dpalmer Date 2004-11-24 Time 05:04 Sent To  
Notes
2004-11-24 00:00:00************ UNSAT ***********
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR STRUCTUAL COMMENTS.
  
 2)NOTE: PLEASE SEE
 230.70,230.72,230.76,230.79
 GENERATOR MAY NOT BE PLACED ON ROOF.
 MAIN/MEANS IF DISCONNECT MUST BE ON
 GROUND LEVEL FOR FIRE DEPT SHUT-DOWN AND
 IN CLOSE PROXIMITY TO EXISTING
 ELECTRICAL EQUIPMENT.
  
 3)NOTE: PELASE SUBMIT COMPLETE PACKAGE
 ON GENERATOR AND ALL EQUIPMENT.(TRANSFER
 SWITCH? ETC.
 ALL SPECS TO SHOW ALL LISTING(S) BY A
 NRTL.
  
 4)NOTE: PLEASE SEE FBC 104.6.5 FOR
 VALUATION OF PERMIT. THE VALUE APPLIED
 AT $2K IS WAY LOW. PLEASE ADJUST.
 REQUIRED TO INCLUDE VALUE FOR COMPLETE
 SCOPE OF WORK,ALL LABOR AND MATERIALS
 WEATHER OWNER SUPPLIED OR NOT.
  
 ** PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) THAT WILL AFFECT THIS
 PROJECT.***
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-05-10 Cont ID  
Sent By mwennerg Date 2005-05-10 Time 10:16 Rev Time 0.00
Received By mwennerg Date 2005-05-10 Time 10:16 Sent To  
Notes
2005-05-10 00:00:001) PLEASE REFER TO COMMENTS BY
 ELECTRICAL PLANS REVIEW IN REGARDS TO
 THE INCONSISTENCY OF GENERATOR SIZE.
  
 2) COMMENTS #3,4,&5 FROM THE FIRST FIRE
 REVIEW HAVE NOT BEEN ADDRESSED.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-20 Cont ID  
Sent By mcarsill Date 2004-12-20 Time 17:05 Rev Time 0.00
Received By mcarsill Date 2004-12-20 Time 17:05 Sent To  
Notes
2004-12-20 00:00:001. PLANS DO NOT INDICATE WHAT THE
 NEW EMERGENCY GENERATOR WILL RUN.
  
 2. PLANS DO NOT INDICATE HOW AND WHERE
 THE CONDUITS WILL RUN.
  
 3. THE GAS LINE SHOWN ON THE PLANS
 TERMINATES WHERE.
  
 4. NO PRODUCT APPROVAL GIVEN FOR
 THE NEW PROPOSED GENERATOR.
  
 5. WHAT SIZE FUEL TANK IS PROPOSED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2005-05-09 Cont ID  
Sent By adarroug Date 2005-05-09 Time 16:30 Rev Time 0.00
Received By adarroug Date 2005-05-09 Time 09:19 Sent To  
Notes
2005-05-09 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD
 TO "COMM" BD#11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-04-28 Cont ID  
Sent By adarroug Date 2005-04-28 Time 14:36 Rev Time 0.00
Received By adarroug Date 2005-04-28 Time 14:36 Sent To Z
Notes
2005-04-28 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2004-12-20 Time 11:05 Rev Time  
Received By mjacobs Date 2004-11-17 Time 14:40 Sent To PC
Notes
2004-11-17 00:00:00SENT TO COMM BD #49

Review Stop Z ZONING
Rev No 2 Status P Date 2005-05-04 Cont ID  
Sent By mmclean Date 2005-05-04 Time 15:51 Rev Time 0.00
Received By mmclean Date 2005-05-04 Time 15:50 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By eschneid Date 2004-12-15 Time 14:41 Rev Time 0.15
Received By eschneid Date 2004-12-15 Time 14:24 Sent To  
Notes
2004-12-15 00:00:00CMUD REGULATIONS REQUIRE SCREENING OF
 MECHANICAL EQUIPMENT. PROVIDE DRAWINGS
 TO SHOW HOW THE NEW GENERATOR WILL BE
 SCREENED.
  
 CMUD REGULATIONS REQUIRE THAT SITE
 LANDSCAPING BE BROUGHT INTO CONFORMITY
 WITH THE LANDSCAPE CODE FOR ANY PERMITS
 EXCEEDING $5,000. PLEASE BE AWARE OF
 THIS THRESHOLD IF YOUR PERMIT VALUE
 INCREASES.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.