| Plan Review Stops For Permit 04110897 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-05-13 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-13 |
Time |
14:15 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-05-13 |
Time |
13:26 |
Sent To |
PC |
|
| Notes |
| 2005-05-13 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SEE PREVIOUS LIST, ITEM #2. | | | PRESSURES REQUESTED BY PREVIOUS REVIEWER | | | NOT PROVIDED.NO ATTACHMENT DETAIL | | | SHOWN. | | | | | | 2.)SHEET 5 OF 6, GENERAL NOTES, STATES | | | THAT THE CABINET WEIGHT SHALL NOT EXCEED | | | 10962.AREN'T THE CABINETS EXISTING? | | | WHERE IS THE GENERATOR WEIGHT ADDRESSED? | | | | | | 3.)SEE PREVIOUS LIST, ITEM #3. | | | VALUATION IS TOO LOW. | | | | | | 4.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 5.)THE NOTES REFER TO CUTTING OF THE | | | SLAB, CONFIRMING POST TENSION CABLE | | | LOCATIONS, CUTTING AND PATCHING OF THE | | | ROOF.THE PLANS SHOULD INCLUDE ONLY | | | WORK DONE UNDER THIS PERMIT.IF THESE | | | THINGS ARE BEING DONE, PLEASE SHOW ON | | | THE PLAN. | | | | | | 6.)THE APPLICATION REFERS TO A 12 KW | | | GENERATOR, PLANS SHOW 30KW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-12-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-12-15 |
Time |
10:55 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2004-12-15 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2004-12-15 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04110897 | | | ADD: 2800 N FLAGLER DR | | | CONT: JOHNATHAN CROMPTON | | | TEL: (561)722-4020 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE ADDITIONAL INFORMATION, THE | | | PREMIT APPLICATION DOESN'T INDICATE IF | | | THIS IS A REPLACEMENT OR NEW GENERATOR. | | | INDICATE HOW THE GENERATOR WILL TIE INTO | | | THE REQUIRED FIRE CENTRAL COMMAND | | | STATION SEE 412.4.,412.7.1.1 AND | | | 412.7.1.2. | | | | | | 2) THE DRAWING SUBMITTED INDICATES THAT | | | THE GENERATOR WILL SIT ON TOP OF A 10 | | | STORY BLDG. PROVIDE DETAILS ON THE | | | EXISTING STEEL WHICH THE NEW GENERATOR | | | IS TO BE ATTACHED. PROVIDE THE | | | ATTACHMENT TO THE STEEL, WITH ASSOCIATED | | | POSITIVE AND NEGATIVE PRESSURES, THE | | | BLDG IS OVER 60' IN HEIGHT DESIGN TO | | | ASCE 7-98. | | | | | | 3) THE VALUATION ON THE PERMIT IS LOW, | | | THE GENERATOR CAN'T BE BOUGHT FOR THE | | | AMOUNT STATED!!!!!!!!! PROVIDE WHAT WORK | | | IS TO BE COMPLETED? | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-09 |
Time |
17:15 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-05-09 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2005-05-09 00:00:00 | *********** UNSAT 2ND REVIEW ********* | | | | | | PLEASE SEE NEW NOTES AND NOTES FROM | | | PREVIOUS REVIEW WHICH STILL NEED TO BE | | | ADDRESSED. | | | | | | 1)NOTE: PLEASE SEE APPLICATION | | | ORIGINALLY CAME IN SHOWING 12KW GEN. | | | PLEASE SEE APPLICATION NOW INDICATES | | | 20KW, HOWEVER NOW PLANS INDICATE 30KW??? | | | PLEASE CORRELATE. | | | | | | PLEASE SEE NOTES BELOW TAKEN DIRECTLY | | | FROM PREVIOUS REVIEW. | | | | | | | | | 3)NOTE: PELASE SUBMIT COMPLETE PACKAGE | | | ON GENERATOR AND ALL EQUIPMENT.(TRANSFER | | | SWITCH? ETC. | | | ALL SPECS TO SHOW ALL LISTING(S) BY A | | | NRTL. | | | | | | 4)NOTE: PLEASE SEE FBC 104.6.5 FOR | | | VALUATION OF PERMIT. THE VALUE APPLIED | | | AT $2K IS WAY LOW. PLEASE ADJUST. | | | REQUIRED TO INCLUDE VALUE FOR COMPLETE | | | SCOPE OF WORK,ALL LABOR AND MATERIALS | | | WEATHER OWNER SUPPLIED OR NOT. | | | | | | PLEASE SEE IF A VALUE IS NOT PROVIDED | | | FOR SCOPE OF WORK PROPOSED, THEN A VALUE | | | WILL BE APPLIED BY THIS DEPARTMENT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-11-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-09 |
Time |
10:07 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-11-24 |
Time |
05:04 |
Sent To |
|
|
| Notes |
| 2004-11-24 00:00:00 | ************ UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS | | | FOR STRUCTUAL COMMENTS. | | | | | | 2)NOTE: PLEASE SEE | | | 230.70,230.72,230.76,230.79 | | | GENERATOR MAY NOT BE PLACED ON ROOF. | | | MAIN/MEANS IF DISCONNECT MUST BE ON | | | GROUND LEVEL FOR FIRE DEPT SHUT-DOWN AND | | | IN CLOSE PROXIMITY TO EXISTING | | | ELECTRICAL EQUIPMENT. | | | | | | 3)NOTE: PELASE SUBMIT COMPLETE PACKAGE | | | ON GENERATOR AND ALL EQUIPMENT.(TRANSFER | | | SWITCH? ETC. | | | ALL SPECS TO SHOW ALL LISTING(S) BY A | | | NRTL. | | | | | | 4)NOTE: PLEASE SEE FBC 104.6.5 FOR | | | VALUATION OF PERMIT. THE VALUE APPLIED | | | AT $2K IS WAY LOW. PLEASE ADJUST. | | | REQUIRED TO INCLUDE VALUE FOR COMPLETE | | | SCOPE OF WORK,ALL LABOR AND MATERIALS | | | WEATHER OWNER SUPPLIED OR NOT. | | | | | | ** PLEASE SEE COMMENTS FROM OTHER | | | REVIEWER(S) THAT WILL AFFECT THIS | | | PROJECT.*** | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-05-10 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-05-10 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-05-10 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2005-05-10 00:00:00 | 1) PLEASE REFER TO COMMENTS BY | | | ELECTRICAL PLANS REVIEW IN REGARDS TO | | | THE INCONSISTENCY OF GENERATOR SIZE. | | | | | | 2) COMMENTS #3,4,&5 FROM THE FIRST FIRE | | | REVIEW HAVE NOT BEEN ADDRESSED. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-12-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-12-20 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-12-20 |
Time |
17:05 |
Sent To |
|
|
| Notes |
| 2004-12-20 00:00:00 | 1. PLANS DO NOT INDICATE WHAT THE | | | NEW EMERGENCY GENERATOR WILL RUN. | | | | | | 2. PLANS DO NOT INDICATE HOW AND WHERE | | | THE CONDUITS WILL RUN. | | | | | | 3. THE GAS LINE SHOWN ON THE PLANS | | | TERMINATES WHERE. | | | | | | 4. NO PRODUCT APPROVAL GIVEN FOR | | | THE NEW PROPOSED GENERATOR. | | | | | | 5. WHAT SIZE FUEL TANK IS PROPOSED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
|
Date |
2005-05-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-09 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-09 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2005-05-09 00:00:00 | IN INCOMING AWAITING SPACE ON "COMM" BD | | | TO "COMM" BD#11 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-04-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-28 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-28 |
Time |
14:36 |
Sent To |
Z |
|
| Notes |
| 2005-04-28 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-12-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-20 |
Time |
11:05 |
Rev Time |
|
| Received By |
mjacobs |
Date |
2004-11-17 |
Time |
14:40 |
Sent To |
PC |
|
| Notes |
| 2004-11-17 00:00:00 | SENT TO COMM BD #49 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-05-04 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-05-04 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-05-04 |
Time |
15:50 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-12-15 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2004-12-15 |
Time |
14:41 |
Rev Time |
0.15 |
| Received By |
eschneid |
Date |
2004-12-15 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2004-12-15 00:00:00 | CMUD REGULATIONS REQUIRE SCREENING OF | | | MECHANICAL EQUIPMENT. PROVIDE DRAWINGS | | | TO SHOW HOW THE NEW GENERATOR WILL BE | | | SCREENED. | | | | | | CMUD REGULATIONS REQUIRE THAT SITE | | | LANDSCAPING BE BROUGHT INTO CONFORMITY | | | WITH THE LANDSCAPE CODE FOR ANY PERMITS | | | EXCEEDING $5,000. PLEASE BE AWARE OF | | | THIS THRESHOLD IF YOUR PERMIT VALUE | | | INCREASES. | | | | | | CONTACT ERIC SCHNEIDER (561) 822-1435. |
|
|