Plan Review Details - Permit 04110889
Plan Review Stops For Permit 04110889
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-02-17 Cont ID  
Sent By rbrown Date 2005-02-17 Time 17:48 Rev Time 0.00
Received By rbrown Date 2005-02-17 Time 17:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-07 Cont ID  
Sent By rbrown Date 2005-02-07 Time 14:27 Rev Time 0.00
Received By rbrown Date 2005-02-07 Time 17:47 Sent To  
Notes
2005-02-07 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 12/22/04:
  
 1) 713.13 F.S.IT IS NOTED THAT THE
 COMMENT RESPONSE, DATED 1/10/05, STATES
 THAT THE NOTICE OF COMMENCEMENT WILL BE
 FILED BY THE CONTRACTOR.
  
 2) 61G1-16.004FL. ADMIN. CODE.THERE
 IS NO DATE ON THE SEAL/SIGNATURE FOR
 THE
 NEW ARCHITECTURAL PLANS.EACH PLAN
 SHEET PREPARED BY A REGISTERED
 ARCHITECT
 SHALL INCLUDE THE DATE OF
 SEAL/SIGNATURE.
  
 4) FBC 13-103.1.2THE COMMENT RESPONSE
 IS NOTED BUT THE COMMENT HAS NOT BEEN
 ADDRESSED.BEFORE A BUILDING PERMIT
 CAN
 BE ISSUED, THE SUBMITTED ENERGY CODE
 COMPLIANCE FORMS SHALL BE SIGNED BY THE
 BUILDING OWNER, THE OWNER'S ARCHITECT
 OR
 OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER.
  
 5) FBC 1005.7.3SHEET A-1, MEZZANINE.
 THE COMMENT RESPONSE IS NOTED BUT THE
 COMMENT HAS NOT BEEN ADDRESSED.
 CONDITION 1 OF FBC 1005.7.3 HAS NOT
 BEEN
 MET.THE SPACE UNDER THE MEZZANINE IS
 NOT 'TOTALLY OPEN AND UNENCUMBERED BY
 PARTITIONED ROOMS OR SPACES', AS
 REQUIRED BY CONDITION 1.THEREFOR THE
 SPACE SHALL BE PROTECTED THROUGHOUT BY
 SMOKE DETECTION, IN ACCORDANCE WITH NFPA
 72, THAT SOUNDS AN ALARM ON THE
 MEZZANINE. ANNOTATE THE PLAMS TO
 DEMONSTRATE COMPLIANCE.
  
 8)FBC 11-4.24SHEET A-3.THE
 ADDITION OF A BREAKROOM SINK CABINET
 DETAIL IS NOTED.THE DETAIL DOES NOT
 SHOW THE REQUIRED KNEE CLEARANCE DEPTH
 OF MIN. 19" FROM THE FRONT OF THE
 COUNTER. AMEND/ANNOTATE THE DETAIL TO
 DEMONSTRATE COMPLIANCE.
  
 9) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE
 RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL
 INFO
 TELEPHONE: (561) 805 6716ROBERT
 BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-22 Cont ID  
Sent By rbrown Date 2004-12-22 Time 16:33 Rev Time 0.00
Received By rbrown Date 2004-12-22 Time 16:33 Sent To  
Notes
2004-12-22 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 713.13 F.S.A NOTICE OF
 COMMENCEMENT SHALL BE RECORDED AT PALM
 BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT
 CAN BE ISSUED. BLANK FORMS ARE AVAILABLE
 FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST
 BE RE-RECORDED IF THE DESCRIBED
 IMPROVEMENT OR CONSTRUCTION IS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING.
  
 2) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT
 SHALL
 INCLUDE A TITLE BLOCK WITH THE PRINTED
 NAME OF THE ARCHITECT SEALING THE
 PLANS.
 THIS MAY BE ADDED BY HAND.
  
 3) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION (COA#)
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
 NOTE:DBPR RECORDS SHOW A COA# OF
 AA26000848 FOR A 'DOING BUSINESS UNDER'
 (DBA) NAME OF NEXUSARCHITECTURE, INC.
 BUT THE PLANS SHOW NEXUS DESIGN GROUP,
 LLC.THE PLANS SHALL REFLECT THE NAME
 OF THE LICENSED FIRM.
  
 4) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 5) FBC 1005.7.3SHEET A-1, MEZZANINE.
 AS THE EGRESS STAIRWAY FROM THE
 MEZZANINE IS OPEN AND DESCENDS INTO THE
 FIRST FLOOR ROOM, THE SPACE BENEATH THE
 MEZZANINE IS ONLY PERMITTED TO BE
 ENCLOSED IF IT IS PROTECTED THOUGHOUT
 BY
 SMOKE DETECTION, IN ACCORDANCE WITH
 NFPA 72, THAT SOUNDS AN ALARM ON THE
 MEZZANINE.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 6) FBC 1608.2.1SHEET A-1, THE
 HANDRAIL SHALL BE DESIGNED AND
 CONSTRUCTED FOR A CONCENTRATED LOAD OF
 200 LB AND A LINE LOAD OF 50 PLF.THESE
 LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY BUT SHALL BE APPLIED
 INDIVIDUALLY AT ANY POINT, AND IN ANY
 DIRECTION, TO PRODUCE MAXIMUM STRESS IN
 EACH OF THE COMPONENTS OR SUPPORTS.
 AMEND/ANNOTATE THE PLANS TO SPECIFY
 THESE LOADS. IT IS NOTED THAT THE
 ARCHITECTURAL PLANS REFER TO THE
 STRUCTURAL PLANS AND VICE VERSA, BUT
 NEITHER PLAN PROVIDES DETAILS.
  
 7) FBC 1608.2.2 SHEET A-1, THE
 GUARDRAIL SHALL BE DESIGNED AND
 CONSTRUCTED FOR A CONCENTRATED LOAD OF
 200 LB APPLIED IN ANY DIRECTION AT THE
 TOP OF THE GUARDRAIL, A CONCENTRATED
 HORIZONTAL LOAD OF 200 LB APPLIED ON A 1
 SQ FT AREA AT ANY POINT, AND A LINE LOAD
 OF 50 PLF APPLIED HORIZONTALLY AT THE
 REQUIRED GUARDRAIL HEIGHT WITH A
 SIMULTANEOUS LINE LOAD OF 100 PLF
 APPLIED VERTICALLY DOWNWARD ON THE TOP
 OF THE GUARDRAIL. THESE LOADS SHALL NOT
 BE APPLIED SIMULTANEOUSLY (UNLESS NOTED
 ABOVE) BUT SHALL BE APPLIED INDIVIDUALLY
 TO PRODUCE MAXIMUM STRESS IN EACH OF
 THE
 COMPONENTS OR SUPPORTS.
 AMEND/ANNOTATE THE PLANS TO SPECIFY
 THESE LOADS. IT IS NOTED THAT THE
 ARCHITECTURAL PLANS REFER TO THE
 STRUCTURAL PLANS AND VICE VERSA, BUT
 NEITHER PLAN PROVIDES DETAILS.
  
 8) FBC 11-4.24SHEET A-1, THE BREAKROOM
 SINK SHALL COMPLY WITH ALL OF THE
 ACCESSIBILTY REQUIREMENTS FOR RIM
 HEIGHT, KNEE CLEARANCE, BOWL DEPTH,
 CLEAR FLOOR SPACE, HOT WATER PIPE
 ISOLATION AND FAUCETS.AMEND THE PLANS
 TO DEMONSTRATE COMPLIANCE.
  
 9) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-06-22 Cont ID  
Sent By dpalmer Date 2005-06-22 Time 16:05 Rev Time 0.25
Received By dpalmer Date 2005-06-22 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-06-08 Cont ID  
Sent By dpalmer Date 2005-06-08 Time 10:27 Rev Time 0.10
Received By dpalmer Date 2005-06-08 Time 10:27 Sent To  
Notes
2005-06-08 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE PLANS DO NOT CONTAIN
 ANY REVISIONS NOTED IN TITLE BLOCKOR
 CLOUDED/TRIANGLES ON PLANS. PLEASE SEE
 PLANS APPEAR TO BE THE SAME SUBMITTED IN
 JANUARY 05
  
  
 PLEASE REVISE PLANS IF NEEDED AND SUBMIT
 FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-13 Cont ID  
Sent By dpalmer Date 2005-01-13 Time 17:02 Rev Time 0.25
Received By dpalmer Date 2005-01-13 Time 16:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-24 Cont ID  
Sent By dpalmer Date 2004-11-24 Time 06:39 Rev Time 0.33
Received By dpalmer Date 2004-11-24 Time 06:39 Sent To  
Notes
2004-11-24 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE VERIFY REQUIRED SHOW
 WINDOW RECEPTS? 210.62
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING FROM PANEL "B" TO "B-1".
 250.110,250.122
  
 3)NOTE: PLEASE SEE MISSING INFORMATION
 ON ARCH'S TITLE BLOCK REQUIRED PER
 FAC 61G1-16.004 . LICENSE #'S REQUIRED
 ALSO PER FS 481.219
 THIS COMMENT IS FOR ALL TRADES AND ALL
 TRADES WHETHER OR NOT COMMENT IS MADE
 BY
 OTHER REVIEWER(S).
  
 4)NOTE: PLEASE SEE PLANS/COVER SHEET
 REFERENCES THE 1999 NEC. PLEASE SEE WE
 ARE UNDER THE 2002 NEC.
 ADOPTED 7/1/2003
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-06-15 Cont ID  
Sent By mwennerg Date 2005-06-15 Time 14:12 Rev Time 0.00
Received By mwennerg Date 2005-06-15 Time 14:12 Sent To  
Notes
2005-06-15 00:00:00REVISION DATED 5/26/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-12-17 Cont ID  
Sent By mcarsill Date 2004-12-17 Time 07:59 Rev Time 0.00
Received By mcarsill Date 2004-12-17 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-21 Cont ID  
Sent By adarroug Date 2005-06-21 Time 16:46 Rev Time 0.00
Received By adarroug Date 2005-06-21 Time 16:46 Sent To E
Notes
2005-06-21 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 15:50 Rev Time 0.00
Received By shill Date 2005-05-31 Time 15:50 Sent To  
Notes
2005-06-07 00:00:00COMM BOARD #4
2005-05-31 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 10:33 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 10:33 Sent To  
Notes
2005-02-11 00:00:00TO "COMM" BD #50

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-11 Cont ID  
Sent By mjacobs Date 2005-01-11 Time 14:02 Rev Time 0.00
Received By mjacobs Date 2005-01-11 Time 14:02 Sent To  
Notes
2005-01-11 00:00:00TO "COMM BD#3"/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-11 Cont ID  
Sent By mjacobs Date 2004-12-22 Time 14:01 Rev Time  
Received By mjacobs Date 2004-11-18 Time 13:35 Sent To  
Notes
2004-11-18 00:00:00SENT TO COMM BD#41

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-06-23 Cont ID  
Sent By pkrauss Date 2005-06-23 Time 07:17 Rev Time 0.40
Received By pkrauss Date 2005-06-23 Time 07:17 Sent To  
Notes
2005-06-23 00:00:00PROVISO:
 PER 2001 FBC 306.3, AHU LOCATED IN THE
 BATHROOM AREA SHALL HAVE PROPER
 CLEARANCE FOR SERVICING, MAINTENANCE OR
 REPLACEMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-02-17 Cont ID  
Sent By pkrauss Date 2005-02-17 Time 15:06 Rev Time 0.30
Received By pkrauss Date 2005-02-17 Time 15:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-14 Cont ID  
Sent By pkrauss Date 2005-01-14 Time 08:31 Rev Time 0.45
Received By pkrauss Date 2005-01-14 Time 07:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-17 Cont ID  
Sent By pkrauss Date 2004-12-17 Time 06:57 Rev Time 0.50
Received By pkrauss Date 2004-12-17 Time 06:32 Sent To  
Notes
2004-12-17 00:00:00DENIED:
 1.RETURN AIR REQUIRED FROM THE OFFICE,
 CONFERENCE ROOM, AND INVENTORY AREAS.
  
 2.PLEASE CLARIFY THE MEZZINE LEVEL.
 IT APPEARS TO OPEN TO THE RECEPTION
 AREA.IF THIS IS NOT THE CASE, A RETURN
 AIR WILL BE REQUIRED FROM THE
 RECEPTION/SHOWROOM AREAS.
  
 3.PLAN SHEET M-2 GENERAL HVAC NOTE
 #12, INDICATES A NEW EXHAUST FAN ROUTED
 TO EXTERIOR WALL.PLEASE INDICATE
 LOCATION OF THE NEW FAN AND PROVIDE
 SCHEDULE INDICATING ALL PERTINENT
 INFORMATION.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IS
 REQUIRED PER 2001 FBC(M)606.2.1 AND
 606.4.1 EXCEPTION #2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  

Review Stop P PLUMBING
Rev No 4 Status N Date 2005-06-24 Cont ID  
Sent By kstevens Date 2005-06-24 Time 17:31 Rev Time 0.33
Received By kstevens Date 2005-06-24 Time 17:31 Sent To  
Notes
2005-06-24 00:00:00REVISION: NO PLUMBING REVISION SHOWN

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-17 Cont ID  
Sent By kstevens Date 2005-02-17 Time 10:30 Rev Time 0.35
Received By kstevens Date 2005-02-17 Time 10:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-01-28 Cont ID  
Sent By kstevens Date 2005-01-28 Time 13:50 Rev Time 0.48
Received By kstevens Date 2005-01-28 Time 13:50 Sent To  
Notes
2005-01-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: FOLLOWING
 INFORMATION REQUIRED FOR BREAK AREA
 SINK
 11-4.24.3 KNEE CLEARANCE
 11-4.24.4 SINK DEPTH
 11-4.24.6 EXPOSED PIPES AND SURFACES
 11-4.24.7 FAUCETS
 NEW COMMENTS...............
 1B) SHT M-1 WATER RISER DIAGRAM. FULL
 OPEN VALVES SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS: - ON THE TOP OF
 EVERY WATER DOWN-FEED PIPE. 606.1(4)
 2B) THE PERSONAL SEAL, SIGNATURE AND
 DATE OF THE ARCHITECT SHALL APPEAR ON
 ALL ARCHITECTURAL DOCUMENTS TO BE FILED
 FOR PUBLIC RECORD. FAC 61G1-16.003 AND
 FS 481.2055. (NO DATE ON SEAL SHOWN).
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-14 Cont ID  
Sent By kstevens Date 2004-12-14 Time 07:32 Rev Time 0.59
Received By kstevens Date 2004-12-14 Time 07:32 Sent To  
Notes
2004-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SUBMIT A DETAIL FOR THE BREAK AREA
 SINK PER SECTION 11-4.24 AND ALL
 SUBSECTIONS. SHOW THE FOLLOWING INFO.
 11-4.24.2 HEIGHT
 11-4.24.3 KNEE CLEARANCE
 11-4.24.4 SINK DEPTH
 11-4.24.5 CLEAR FLOOR SPACE - FORWARD
 APPROACH REQUIRED. NO DOORS OR SHELVES.
 11-4.24.6 EXPOSED PIPES AND SURFACES
 11-4.24.7 FAUCETS
 2) SHT M-1 SUBMIT A WATER RISER DIAGRAM
 PER SECTION 104.3.1.1. SHOW ALL PIPE
 SIZES.
 3) ARCHITECT TITLE BLOCK MISSING
 INFORMATION. SEE FAC 61G1-16.004(2)(6)
 FS 481.219 & FS 481.2055
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]