Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-12-23 Cont ID  
Sent By dpalmer Date 2004-12-23 Time 04:58 Rev Time 0.25
Received By dpalmer Date 2004-12-23 Time 04:50 Sent To B
Notes
2004-12-23 00:00:00**REDLINED **
  
 LOAD CALCS NOT REVISED, DOES NOT SHOW
 LOAD FOR HEAT PUMP AT 125% FOR CONT
 LOAD.
 THIS WAS REDLINED AND SENT TO BLDG FOR
 PROCESSING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-22 Cont ID  
Sent By dpalmer Date 2004-11-22 Time 11:41 Rev Time 0.33
Received By dpalmer Date 2004-11-22 Time 11:41 Sent To P
Notes
2004-11-22 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE LOAD
 CALCULATIONS AND SPEC SHEET SUBMITTED
 FOR NEW HEAT PUMP.
 ONE SHOWS 3.8, THE OTHER 5.6.
 PLEASE ALSO SEE ALL CONTINUOUS LOADS ARE
 TO BE SHOWN AT 125%.(HEAT-PUMP)
 215.3,230.42 ETC
  
 2)NOTE: PLEASE SEE ELECTRICAL WIRING
 DIAGRAM FOR POOL. SHOWS 3/0'S ? IS THIS
 FOR FEED TO NEW POOL PANEL?
 PLEASE INDICATE OCP FOR NEW PANEL, SIZE
 OF NEW PANEL AND ALL CONDUCTORS FOR NEW
 PANEL.
 215.5
  
 3)NOTE: PLEASE CORRELATE WIRING DIAGRMA
 WITH ALL NEW ELECTRICAL/POOL EQUIPMENT
 TO BE HOOK-UP.
  
 4)NOTE: PLEASE SEE ENGINEER MUST ALSO
 DATE PLANS WHEN SIGNING. MAY NOT BE
 STAMPED OR PRINTED.MUST BE ORIG WHEN
 SIGNED.
 FS471.025
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-16 Cont ID  
Sent By mjacobs Date 2004-12-16 Time 11:17 Rev Time 0.00
Received By mjacobs Date 2004-12-16 Time 11:17 Sent To E
Notes
2004-12-16 00:00:00SENT TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-19 Cont ID  
Sent By mjacobs Date 2004-11-19 Time 16:11 Rev Time 0.00
Received By mjacobs Date 2004-11-19 Time 16:11 Sent To E
Notes
2004-11-19 00:00:00SENT TO "E" BOX/POOL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-16 Cont ID  
Sent By mjacobs Date 2004-11-16 Time 14:22 Rev Time 0.00
Received By mjacobs Date 2004-11-16 Time 14:22 Sent To Z
Notes
2004-11-16 00:00:00SENT TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-11-27 Cont ID  
Sent By kstevens Date 2004-11-27 Time 11:43 Rev Time 0.50
Received By kstevens Date 2004-11-27 Time 11:43 Sent To B1
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-11-19 Cont ID  
Sent By mmclean Date 2004-11-19 Time 14:55 Rev Time 0.00
Received By mmclean Date 2004-11-19 Time 14:55 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved