Plan Review Details - Permit 04110775
Plan Review Stops For Permit 04110775
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-13 Cont ID  
Sent By jwitmer Date 2004-12-13 Time 13:18 Rev Time 1.77
Received By jwitmer Date 2004-12-13 Time 13:18 Sent To  
Notes
2004-12-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110775
 ADD: 501 S OLIVE AV
 CONT: NICK RAICH
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) PROVIDE MINIMUM BLDG TYPE SEE TABLE
 600. ALSO SEE 705.1.1.2 EVERY WALL
 WITHIN 15' OF A PROPERTY LINE SHALL BE
 EQUIPPED WITH OPENING PROTECTIVES. SEE
 EXCEPTION FOR SHOW WINDOWS, ARE THESSE
 TO BE SHOW WINDOWS?
  
 2) 2304.1.2. SOIL TREATMENT FOR TERMITES
 OR OTHER ALTERNATIVES.
 PROVIDE INFORMATION
  
 3)SEE S-1 EXTERIOR WALL SECTION IS
 MISSSING BLOCK WALL RECESS: 2111.1.9
 1 1/2" RECESS WATERSTOP FOR EXTERIOR
 WALLS.
  
 4) S-1 MISSING THE MANSARD ROOF TRUSS
 FRAMING INFORMATION, TIE DOWN,
 MANUFACTURER OF TIE DOWN, MODEL #, LOADS
 TO BE IMPOSED ETC...
  
 5)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) STORM SHUTTERS
 C) SOFFITS
 D) COMPONENTS & CLADDING- TRUSS
 ANCHORS
 E) ROOFING ASSEMBLIES UNDERLAYMENTS,
 & ROOF FINISHES
  
 6) 1503.4.2 OVERFLOW DRAINS SHALL BE THE
 SAME SIZE AS ROOF DRAINS, INSTALLED WITH
 THE INLET FLOW LINE LOCATED 2" ABOVE THE
 LOWEST POINT OF THE ROOF LINE. OVERFLOW
 SCUPPERS SHALL BE A MINIMUM OF 4"IN
 HEIGTH AND SHALL BE PLACED IN WALLS OR
 PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF
 SURFACE.
  
 7) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 8) 1511.7 ROOF MOUNTED MECHANICAL UNIT S
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 9)1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-12-03 Cont ID  
Sent By dpalmer Date 2004-12-03 Time 05:45 Rev Time 0.25
Received By dpalmer Date 2004-12-03 Time 05:44 Sent To  
Notes
2004-12-03 00:00:00*************** UNSAT **************
  
  
 1)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE SEE LOADS SHOWN DO NOT SEE TO ADD
 UP TO THE AMOUNTS SHOWN.
  
 2)NOTE: PLEASE SEE 424.3B FOR A/C OCP.
 THE AMPACITY OF THE BRANCH-CIRCUIT
 CONDUCTORS AND THE RATING OR SETTING OF
 OVERCURRENT PROTECTIVE DEVICES SUPPLYING
 FIXED ELECTRIC SPACE-HEATING EQUIPMENT
 CONSISTING OF RESISTANCE ELEMENTS WITH
 OR WITHOUT A MOTOR SHALL NOT BE LESS
 THAN 125 PERCENT OF THE TOTAL LOAD OF
 THE MOTORS AND THE HEATERS. THE RATING
 OR SETTING OF OVERCURRENT PROTECTIVE
 DEVICES SHALL BE PERMITTED IN ACCORDANCE
 WITH 240.4(B). A CONTACTOR, THERMOSTAT,
 RELAY, OR SIMILAR DEVICE, LISTED FOR
 CONTINUOUS OPERATION AT 100 PERCENT OF
 ITS RATING, SHALL BE PERMITTED TO SUPPLY
 ITS FULL-RATED LOAD AS PROVIDED IN
 210.19(A),
 PLEASE SEE 20A OCP FOR 5200KVA LOAD.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-12-15 Cont ID  
Sent By mcarsill Date 2004-12-15 Time 07:47 Rev Time 0.00
Received By mcarsill Date 2004-12-15 Time 07:47 Sent To  
Notes
2004-12-15 00:00:001. NEW EXIT SIGN SHOULD BE A
 COMBINATION FIXTURE CONTAINING
 AN EMERGENCY LIGHT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By mjacobs Date   Time   Rev Time 0.00
Received By mjacobs Date 2004-11-16 Time 08:36 Sent To  
Notes
2004-11-16 00:00:00SENT TO "COMM BD#10

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-13 Cont ID  
Sent By pkrauss Date 2004-12-13 Time 10:50 Rev Time 0.55
Received By pkrauss Date 2004-12-13 Time 10:50 Sent To  
Notes
2004-12-13 00:00:00DENIED:
 1.PLEASE CLARIFY ACCESS TO NEW
 CONDENSER UNIT LOCATED ON THE ROOF.PER
 2001 FBC(M)306.5, EQUIPMENT LOCATED ON
 ROOF REQUIRING ACCESS AT A HEIGHT
 EXCEEDING 16 FT SHALL HAVE A PERMENANT
 MEANS OF ACCESS.SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES.
  
 2.PLAN SHEET ME-1 INDICATES CONDENSING
 UNIT INSTALLED ON A FACTORY CURB.
 PLEASE PROVIDE PRODUCT APPROVAL.
 INDICATE HEIGHT OF CURB.PER 2001 FBC
 1511.7, ROOF CURBS SHALL BE A MINIMUM OF
 8" ABOVE THE ROOF SURFACE.WHERE
 ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, SUPPORTS SHALL COMPLY WITH TABLE
 1511.7 OF THE 2001 FBC.
  
 3.PROVIDE INFORMATION ON THE
 TERMINATION OF THE CONDENSATE.SHOW
 COMPLIANCE WITH 2001 FBC(M)307.2.1 #2.
 PLEASE NOTE, CONDENSATE SHALL TERMINATE
 A MINIMUM OF 12 INCHES FROM THE BUILDING
 STRUCTURE - 2001 FBC 1503.4.
  
 4.PLAN INDICATES A DUCT SMOKE
 DETECTOR.FAN SHUTDOWN BY DUCT SMOKE
 DETECTOR IS REQUIRED TO HAVE
 NOTIFICATION TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS - 2001 FBC(M)606.4.1
 EXCEPTION #2.
  
 5.PLAN INDICATES O.A. OPENING AND DOES
 NOT INDICATE DUCTWORK.DETAIL SHOWS
 O.A. DUCTED TO THE R/A PLENUM AT THE AHU
 WHICH IS PROPER.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-11-24 Cont ID  
Sent By aaponte Date 2004-11-24 Time 17:11 Rev Time 0.00
Received By aaponte Date 2004-11-24 Time 17:11 Sent To  
Notes
2004-11-24 00:00:001. VEHICULAR ENTRY ON GARDENIA STREET
 CAN NOT EXCEED 24 FEET WIDE.
 2. THE PROPOSED ARCHITECTURAL DESIGN IS
 NOT CONSISTENT WITH THE EXISTING
 BUILDING AND ADDITION APPROVED BY DAC.