Plan Review Details - Permit 04110666
Plan Review Stops For Permit 04110666
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-14 Cont ID  
Sent By alange Date 2005-01-14 Time 15:50 Rev Time 0.75
Received By alange Date 2005-01-14 Time 15:50 Sent To  
Notes
2005-01-14 00:00:00DENIED
  
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.ADDITIONAL PERMIT FEES OF
 $60.59 ARE DUR PRIOR TO ISSUING OF
 PERMIT.SEE PREVIOUS REVEW FOR BREAK
 DOWN.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-08 Cont ID  
Sent By alange Date 2004-12-08 Time 10:37 Rev Time 1.00
Received By alange Date 2004-12-08 Time 09:20 Sent To  
Notes
2004-12-08 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SHOW WINDOW OVER TUB AREA TO BE
 SAFTEY GLAZING PER FBC 2405.2.1
  
 4.BASED ON SBCCI BUILDING VALUATION
 DATA THE PROJECT VALUE HAS BEEN CHANGED
 TO $56,257ADDTIONAL PERMIT FEES ARE
 DUE PRIOR TO ISSUING OF PERMIT.
  
 5.SHOW ATTIC ACCESS SIZE AND LOCATION
 COMPLYING WITH FBC 2309.6
  
 6.SHOW HOW EXISTING BUILDING WILL
 COMPLY WITH SMOKE DETECTORS AND GFCI
 OUTLETS.FBC 3401.7.1.2.1
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-05 Cont ID  
Sent By dpalmer Date 2005-01-05 Time 13:35 Rev Time 0.33
Received By dpalmer Date 2005-01-05 Time 13:35 Sent To P
Notes
2005-01-05 00:00:00 
 *** PERMIT APPLICATION DID NOT COME BACK
 WITH RESUB. CALLED OWNER,LEFT MESSAGE.
  
 REDLINED PLANS, 22,000 AIC RATED MAIN
 MIN.
  
 REDLINE SD'S IN EXISTING BED RMS PER
 NFPA-72 8-1.4.1.6.2

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-22 Cont ID  
Sent By dpalmer Date 2004-11-22 Time 15:56 Rev Time 0.50
Received By dpalmer Date 2004-11-22 Time 15:56 Sent To P
Notes
2004-11-22 00:00:00******* UNSAT ********
  
 1)NOTE: PLEASE SEE PLANS REFERENCE PALM
 BEACH COUNTY. PLEAS SEE JOBSITE IS IN
 THE CITY OF WEST PALM BEACH.
  
 2)NOTE: PLEASE SEE 210.52D,210.11C3 FOR
 MIN REQUIRED BATH GFI. MUST BE 20A AND
 312 AWG.
  
 3)NOTE: PLEASE SEE 424.3B FOR SIZING OF
 OCP FOR AHU HEAT.
  
 4)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS TO EXISTING DWELLINGS.
 PLEASE PROVIDE LAYOUT OF EXISTING SD'
 AND GFI EITHER EXISTING OR NEW TO MEET
 2002 NEC, NFPA-72 8-1.4.1.6.2
 *** THIS IS ONLY A NOTE***
 PLANS SHOW THREE SD'S IN MASTER BEDRM??
 PLEASE ALSO SEE SD'S IN LOCATIONS NOT
 REQUIRED. ?
 THIS IS NOT A CODE VIOLATION, ONLY NOTED
 FOR AMOUNT ABOVE REQUIRED?
  
 5)NOTE: PLEASE SEE FBC 104.2.1.
 PLEASE HAVE PERSON RESPONSIBLE FOR
 PLANS, SIGN WITH OUT RUBBER STAMP.
  
 6)NOTE: PLEASE SEE A/C DISCONNECT IS
 NOTED AS BEING 50A WHEN REQUIRED TO BE
 60A MIN.?
 424.3.B
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.?
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHOULD BE SUBMITTED FOR
 REFERENCE ONLY.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-01-05 Cont ID  
Sent By mjacobs Date 2005-01-05 Time 08:52 Rev Time 0.00
Received By mjacobs Date 2005-01-05 Time 08:52 Sent To E
Notes
2005-01-05 00:00:00TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-29 Cont ID  
Sent By mjacobs Date 2004-12-29 Time 13:27 Rev Time 0.00
Received By mjacobs Date 2004-12-29 Time 13:27 Sent To Z
Notes
2004-12-29 00:00:00TO "Z" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 16:28 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-01-14 Cont ID  
Sent By prafter Date 2005-01-14 Time 11:24 Rev Time 0.45
Received By prafter Date 2005-01-14 Time 11:23 Sent To B
Notes
2005-01-14 00:00:001. EQUIPMENT REFLECTED ON PLAN SHOWS
 10 SEER RATED A/C EQUIPMENT BUT ENERGY
 CAULKS REFLECT MIN. OF 12 SEER.
 2. A/C EQUIPMENT CONDENSATE MUST
 CONFORM WITH 2001 FBC/M SECTION 307 AND
 307.2.3.
 PAT RAFTER 561/805/6725 OR 8056719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-06 Cont ID  
Sent By pkrauss Date 2004-12-06 Time 08:49 Rev Time 0.35
Received By pkrauss Date 2004-12-06 Time 08:33 Sent To B
Notes
2004-12-06 00:00:00DENIED:
 1.PROVIDE EQUIPMENT SCHEDULE.
 2.INDICATE IF THE EQUIPMENT IS NEW OR
 EXISTING.PLEASE NOTE, THE ENERGY
 CALCULATIONS INDICATE A 1 TON SYSTEM FOR
 THE ADDITION.IT APPEARS THE EXISTING
 SYSTEM IS ALSO SERVING THE ADDITION AS
 WELL AS THE EXISTING LIVING AREA.
 3.PLAN SHEET A-1 DOES NOT INDICATE
 SIZE OF THE DUCT BACK TO THE EXISTING
 DUCT SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-06 Cont ID  
Sent By jleech Date 2005-01-06 Time 15:06 Rev Time 0.25
Received By jleech Date 2005-01-06 Time 15:06 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-27 Cont ID  
Sent By kstevens Date 2004-11-27 Time 07:17 Rev Time 0.25
Received By kstevens Date 2004-11-27 Time 07:17 Sent To M
Notes
2004-11-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) SHT A-3 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. ONLY THE
 FIXTURES WITHIN THE BATHROOMGROUP SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES
 SHALL DISCHARGE DOWNSTREAM OF THE WET
 VENT. SECTION 909.1. (THE KITCHEN SINK
 SHALL CONNECT DOWNSTREAM OF THE BATHROOM
 FIXTURES) - SEE RED LINE CORRECTIONS FOR
 AN EXAMPLE OF HOW THE RISER WILL MEET
 CODE REQUIREMENTS.
 2) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SECTION 104.2.1 - STAMPED
 SIGNATURES ARE NOT APPROVED.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-01-04 Cont ID  
Sent By mmclean Date 2005-01-04 Time 14:59 Rev Time 0.00
Received By mmclean Date 2005-01-04 Time 14:59 Sent To I
Notes
***NONE***