Plan Review Details - Permit 04110662
Plan Review Stops For Permit 04110662
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-12-08 Cont ID  
Sent By dpalmer Date 2004-12-08 Time 13:27 Rev Time 0.25
Received By dpalmer Date 2004-12-08 Time 13:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-22 Cont ID  
Sent By dpalmer Date 2004-11-22 Time 09:03 Rev Time 0.33
Received By dpalmer Date 2004-11-22 Time 09:03 Sent To  
Notes
2004-11-22 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE FOR EACH UNIT.
 NEW PANEL/ EXSITING?
 PLEASE ALSO PROVIDE SIZE OF EACH AND
 LOAD.
 215.5
  
 2)NOTE: PLEASE SEE 220.12B FOR TRACK
 LT-ING LOADS.
 PLEASE SEE ALL CONTINUOS LOADS ARE TO BE
 SHOWN AT 125%.
 215.3,230.42 ETC.
  
 3)NOTE: PLEASE CLARIFY OF THERE ARE ANY
 NEW OR EXISTING EXIT/EM LTS?
 PLEASE ALSO SEE 700.12E FOR CIRCUITINGIF
 TO BE NEW?
  
 4)NOTE: PLEASE VERIFY IF NEW OR EXISTING
 SIGN CIRCUIT PER 600.5?
  
 5)NOTE: PLEASE SEE FBC 104.2.1 WHICH
 REQUIRES A PRINTED NAME AND SIGNATAURE
 FOR PERSON RESPONSIBLE FOR PLANS.
  
 6)NOTE: PLEASE PROVIDE COPY OF CONTRACT
 TO VERUFY VALUE. 104.6.5 FBC.
  
 PLEASE SUBMIT THE ABOVE INFORMATIONFOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 16:30 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 16:30 Sent To E
Notes
***NONE***