| Plan Review Stops For Permit 04110638 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2005-02-08 |
Time |
09:49 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
2005-02-08 |
Time |
09:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-11-29 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2004-11-29 |
Time |
12:13 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
2004-11-29 |
Time |
12:13 |
Sent To |
|
|
| Notes |
| 2004-11-29 00:00:00 | BUILDING PLAN REVIEW FAILED | | | | | | 1. SHOW DETAIL FOR ANCHORING POOL | | | EQUIPMENT ON PLAN PER FBC 2001 SEC | | | 424.2.7.2. | | | | | | 2. FOOTER DETAIL SHOWN ON PLANS. | | | | | | 3. SCREEN ENCLOSURE MUST BE BY SEPARATE | | | PERMIT WITH ENGINEERED DRAWINGS. | | | | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-01-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-13 |
Time |
11:17 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-01-13 |
Time |
11:17 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-11-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-23 |
Time |
06:15 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-11-23 |
Time |
06:13 |
Sent To |
P |
|
| Notes |
| 2004-11-23 00:00:00 | ******* UNSAT ******* | | | | | | 1)NOTE: PLEASE SEE PLANS INDICATE A NEW | | | PANEL YET NO INFORMATION FOR FEED TO NEW | | | PANEL. | | | PLEASE SHOW SIZE OF NEW PANEL. | | | PLEASE SHOW SIZE OF FEED, OCP, CONDUITM | | | CONDUCTORS ETC. | | | 215.5,240.4,310.16,250 | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-01-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-28 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-28 |
Time |
14:27 |
Sent To |
P |
|
| Notes |
| 2005-01-28 00:00:00 | TO "P" BOX/RESUB. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-01-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-10 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-10 |
Time |
12:01 |
Sent To |
E |
|
| Notes |
| 2005-01-10 00:00:00 | TO "DP" DESK./RESUB. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-11-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-12 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-12 |
Time |
11:38 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-02-08 |
Time |
10:32 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2005-02-08 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-01-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-01-21 |
Time |
08:40 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2005-01-21 |
Time |
08:40 |
Sent To |
B1 |
|
| Notes |
| 2005-01-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING | | | POOLS | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) COMMENT RESPONSE FOR ITEMS 1 THRU 6 | | | SHALL BE SIGNED & SEALED BY THE | | | ENGINEER | | | OF RECORD. TITLE BLOCK WITH ALL | | | REQUIRED | | | INFORMATION IS REQUIRED ON THE SIGNED, | | | SEALED, AND DATED SHEET. | | | 61G15-23.002(1)(2) & FS 471.025 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-11-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-11-27 |
Time |
06:57 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2004-11-27 |
Time |
06:57 |
Sent To |
B1 |
|
| Notes |
| 2004-11-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING | | | POOLS | | | | | | | | | A) THE FOLLOWING INFORMATION IS REQUIRED | | | ON THE PLANS FOR POOL PERMIT. PLEASE | | | SUBMIT A DETAIL, MANUF. SPECIFICATIONS | | | OR ADD INFORMATION TO NOTES AS | | | REQUIRED. | | | 1) COMPLY WITH FBC-2001 SEC 424.2 | | | PRIVATE SWIMMING POOLS. | | | 2) FBC-2001 SEC 424.2.6.1 ENGINEERING | | | DESIGN, CONSTRUCTION AND WORKMANSHIP. | | | ANSI/NSPI-5. (ADD TO NOTES) | | | 3) FBC-2001 424.2.7.2 PUMPS AND | | | EQUIPMENT SHALL BE MOUNTED ON A | | | SUBSTANTIAL BASE IN A MANNER THAT WILL | | | ELIMINATE STRAIN ON PIPING.SLAB SHALL | | | BE A NOMINAL 4" THICK. (DETAIL) | | | 4) FBC-2001 424.2.9 WATER SUPPLY, LOCAL | | | ORD #2938-95, BACKFLOW REQUIRED ON THE | | | WATER SERVICE. (ADD TO NOTES) | | | 5) FBC-2001 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | 6) FBC-2001 424.2.13.2 JOINTS AND | | | CONNECTIONS, FBC PLMG SEC 605.21, PURPLE | | | PRIMER REQUIRED ON PVC PIPING AND | | | FITTINGS. (ADD TO NOTES) | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-11-16 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-11-16 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-11-16 |
Time |
16:29 |
Sent To |
I |
|
| Notes |
|
|