| Plan Review Stops For Permit 04110624 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2006-01-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-01-17 |
Time |
07:24 |
Rev Time |
0.44 |
| Received By |
jwitmer |
Date |
2006-01-17 |
Time |
07:23 |
Sent To |
PC |
|
| Notes |
| 2006-01-17 00:00:00 | REVISION# 5 IS CHANGE IN GRADEOK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-07-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-07-30 |
Time |
15:20 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2005-07-30 |
Time |
14:52 |
Sent To |
MEDGAS |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-04-20 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-04-20 |
Time |
16:54 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2005-04-20 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2005-04-20 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04110624 | | | ADD: 1318 HENRIETTA AV | | | CONT:RANDOLPH& DEWDNEY | | | TEL: (561)441-1186 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 4THREVIEW | | | ACTION: DENIED | | | | | | 1)PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) COMMENT# 7 FROM THE PREVIOUS REVIEW, | | | A-2 MULTI PURPOSE ROOM# 2 ENTRY DOOR, | | | SEE11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING | | | CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 3)SHEET A-3 & A-4 GUARD RAIL | | | EXTENTIONS: | | | 1007.5.5. HANDRAILS SHALL EXTEND AT | | | LEAST 12 INCHES HORIZONTALLY BEYOND THE | | | TOP RISER OF A FLIGHT. .AT THE BOTTOM, | | | THE HANDRAIL SHALL CONTINUE TO SLOPE | | | FOR | | | A DISTANCE OF THE DEPTH OF ONE TREAD | | | FROM THE BOTTOM RISER.SEE FIGURE 19 | | | ATTACHED. | | | | | | 4 THE NEW STAIR DESIGN STILL CREATES A | | | SINGLE MEANS OF EGRESS AT THE ONE END OF | | | THE BREEZEWAY REQUIRING A 1 HR RATEED | | | WALL AND 45 MIN OPENING PROTECTIVES. | | | 1006.2.4A. SEE ATTACHMENT. | | | | | | 5) COMMENT# 9 FROM THE PREVIOUS | | | REVIEW: | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 6) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) TRUSS ANCHORS | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-01-26 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-01-26 |
Time |
07:23 |
Rev Time |
1.66 |
| Received By |
jwitmer |
Date |
2005-01-26 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2005-01-26 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04110624 | | | ADD: 1318 HENRIETTA AVE | | | CONT: RANDOLPH & DEWDNEY | | | TEL: (561)441-1186 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT | | | NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR | | | SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE | | | FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) COMMENT # 1 FROM THE PREVIOUS | | | REVIEW, | | | SHEET A-2 CORRECT EGRESS WINDOW | | | STATEMENT ON THE GROUND FLOOR THE | | | MINIMUM CLEAR OPENING SIZE IS 5'-0" | | | NOT "THE NET CLEAR OPENING IN NO CASE | | | BE | | | LESS THAN 4'-0" SQ FT". | | | 2001 FL BLD CODE, 1005.4: | | | PROVIDE EMERGENCY EGRESS WINDOWS IN | | | SLEEPING ROOMS WITH A MINIMUM NET CLEAR | | | OPENING HEIGTH OF 24" AND NET CLEAR | | | OPENING WIDTH OF 20" AND A NET CLEAR | | | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR | | | OPENINGS ARE PERMITTED TO HAVE A NET | | | CLEAR OPENING OF 5.0 SQ. FT. SILL | | | HEIGTH | | | SHALL NOT BE MORE THAN 44 " ABOVE THE | | | FINISH FLOOR. | | | 3) COMMENT# 2 FROM THE PREVIOUS REVIEW, | | | DEALS WITH THE HANDICAPPED BATHROOM | | | REQUIREMENTS MISSING A COMMENT OR | | | DETAIL | | | INCLUDING THE REAR GRAB BAR AT THE | | | WATER | | | | | | CLOSET. | | | 3) COMMENT# 3 FROM THE PREVIOUS REVIEW | | | PLANS ARE NOT CLEAR ON THE FRONT ENTRY, | | | ELEVATION INDICATE A STOOP OR LANDING | | | THEN A STEP INTO THE LOBBY, | | | 11-4.1.3(1) AT LEAST ONE ACCESSIBLE | | | ROUTE COMPLYING WITH 11-4.3 SHALL | | | CONNECT ACCESSIBLE BUILDING OR FACILITY | | | ENETRANCES WITH ALL ACCESSIBLE SPACES | | | AND ELEMENTS WITHIN THE BUILDING OR | | | FACILITY. EXPLAINRATIONAL OR INDICATE | | | A COMPLIANT RAMP. | | | | | | 4) COMMENT# 4 FROM THE PREVIOUS REVIEW, | | | FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | A-2 PROVIDE THE MEAN ROOF HEIGHT. | | | | | | 5)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, SHEET | | | A-8DETAIL# 3 INDICATES AN EXTERIOR | | | BLOCK | | | WALL 4 BAR BEAM AND LEDGERS BUCKET AND | | | FLOOR TRUSSES, PLANS LACK THE ATTCHMENT | | | OF DOUBLE LEDGER TO BEAM AND TYPE OF | | | BUCKET FOR FLOOR TRUSSES. SAME DETAIL | | | MISSING APPROVED HANGERS FROM THE 3 | | | MEMBER GIRDER? | | | | | | 6) COMMENT # 6 FROM THE PREVIOUS | | | REVIEW, | | | A-2 THE DESIGN OF THE EXTERIOR STAIR | | | DOESN'T MET THE REQUIREMENT FOR A | | | SINGLE | | | | | | STAIRWAY IN 1026.1 BECAUSE OF THE 1ST | | | REQUIREMENT BEING THE MAXIMUM LENGTH OF | | | TRAVEL TO REACH THE EXIT FROM THE | | | ENTRANCE DOOR TO ANY UNIT SHALL NOT | | | EXCEED 30 FT. SO (2) STAIRWAYS ARE | | | REQUIRED. | | | THE PROBLEM WITH THE STAIR DESIGN | | | IS | | | 1006.2.2 REQUIRES THE STAIRS SHALL BE | | | LOCATED THAT THE ENTRANCES AND ALL | | | PORTIONS OF THE STAIRWAYS ON EACH LEVEL | | | ARE A DISTANCE APART EQUAL TO NOT LESS | | | THAN 1/2 OF THE LENGHT OF THE MAXIMUM | | | OVERALL DIAGONAL DIMENSION OF THE | | | BUILDING OR AREA SERVED. | | | SO INFACT THE PLAN MAY INDICATE (2) | | | STAIRWAYS IN ELEVATION,BY DEFINITION | | | THERE IS ONLY ONE. | | | | | | 7) COMMENT# 7 FROM THE PREVIOUS REVIEW, | | | A-2 MULTI PURPOSE ROOM# 2 ENTRY DOOR, | | | SEE11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING | | | CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. | | | | | | 8)SHEET A-3 & A-4 GUARD RAIL | | | EXTENTIONS: | | | 1007.5.5. HANDRAILS SHALL EXTEND AT | | | LEAST 12 INCHES HORIZONTALLY BEYOND THE | | | TOP RISER OF A FLIGHT. .AT THE BOTTOM, | | | THE HANDRAIL SHALL CONTINUE TO SLOPE | | | FOR | | | A DISTANCE OF THE DEPTH OF ONE TREAD | | | FROM THE BOTTOM RISER. | | | | | | 9) COMMENT# 15 FROM THE PREVIOUS | | | REVIEW: | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, | | | 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 10) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) TRUSS ANCHORS | | | B1) ROOFING ASSEMBLIES- A-8 INDICATES | | | THE USE OF MONIER VILLA ROLL"S" VS THE | | | PRODUCT APPROVAL SUBMITTEDFOR A | | | ENTEGRA ESTATE "S" TILE | | | B2) A-8 ARCHETECT ALSO PROVIDE A | | | OPTION OF TIMBERLINE ASPHALT TILE, THE | | | LOADING FOR TILE VS SHINGLES ARE NOT THE | | | SAME. | | | | | | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-12-13 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-12-13 |
Time |
14:45 |
Rev Time |
3.33 |
| Received By |
nmccray |
Date |
2004-12-13 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2004-12-13 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04110624 | | | ADD: 1318 HENRIETTA AV | | | CONT: RANDOLPH & DEWDNEYCONST | | | TEL: (561)441-1182 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1) SHEET A-2 CORRECT EGRESS WINDOWS | | | STATMENT FOR 2ND FLOOR WINDOWS, | | | 2001 FL BLD CODE, 1005.4: | | | PROVIDE EMERGENCY EGRESS WINDOWS IN | | | SLEEPING ROOMS WITH A MINIMUM NET CLEAR | | | OPENING HEIGTH OF 24" AND NET CLEAR | | | OPENING WIDTH OF 20" AND A NET CLEAR | | | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR | | | OPENINGS ARE PERMITTED TO HAVE A NET | | | CLEAR OPENING OF 5.0 SQ. FT. SILL | | | HEIGTH | | | SHALL NOT BE MORE THAN 44 " ABOVE THE | | | FINISH FLOOR. | | | | | | 2) HANDICAPPED RESTROOMS- SEE CHAPTER | | | 11 | | | FIGURE 30E FOR LENGTH OF REQUIRED GRAB | | | BARS FOR SIDE AND REAR LOCATIONS. | | | | | | 3) PLANS ARE NOT CLEAR AS TO LANDING | | | LEVELS FOR FRONT AND SIDE ENTRY 1ST FL. | | | 11-4.1.3(1) AT LEAST ONE ACCESSIBLE | | | ROUTE COMPLYING WITH 11-4.3 SHALL | | | CONNECT ACCESSIBLE BUILDING OR FACILITY | | | ENETRANCES WITH ALL ACCESSIBLE SPACES | | | AND ELEMENTS WITHIN THE BUILDING OR | | | FACILITY. SEE A-2. | | | | | | 4) FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, SHEET | | | A-2 PROVIDE THE MEAN ROOF HEIGHT. | | | | | | 5) SHEET A-2 COMMENT "STAIRWAYS COMPLY | | | WITH THE REQUIREMENTS OF 1026.1" | | | 104.2.1 W.P.B. ADMINISTRATIVE CODE | | | DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR | | | OTHERWISE, AS TO THE QUALITY OF | | | MATERIALS, WHERE QUALITY IS ESSENTIAL | | | TO | | | CONFORMITY WITH THE TECHNICAL CODES. | | | SUCH INFORMATION SHALL BE | | | SPECIFIC | | | AND THE TECHNICAL CODES "SHALL NOT BE | | | CITED AS A WHOLE OR IN PART, NOR THE | | | TERM "LEGAL" OR ITS RQUIVALENT BE USED | | | AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". | | | | | | 6) SHEET A-2 THE DESIGN OF THE EXTERIOR | | | STAIR, DOESN'T MEET THE DEFINITION OF A | | | SINGLE STAIRWAY IN 1026.1 BECAUSE OF | | | THE | | | 1 ST REQUIREMENT BEING THE MAXIMUM OF | | | TRAVEL TO REACH THE EXIT FROM THE | | | ENTRANCE DOOR TO ANY UNIT SHALL NOT | | | EXCEED 30 FEET. | | | THE PROBLEM WITH THE DESIGN OF THIS | | | STAIRWAY FOR (2) EXIT STAIRS, 1006.2.2, | | | REQUIRES, THE STAIRWAYS SHALL BE | | | LOCATED | | | THAT THE ENTRANCES AND ALL PORTIONS OF | | | THE STAIRWAYS ON EACH LEVEL ARE A | | | DISTANCE APART EQUAL TO NOT LESS THAN | | | 1/2 OF THE LENGHT OF THE MAXIMUM | | | OVERALL DIAGONAL DIMENSION OF THE | | | BUILDING OR AREA SERVED. | | | | | | 7) SHEET A-2 MULTI PURPOSE ROOM# 2, SEE | | | 11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL.REQUIRES 18" ON THE SWING | | | SIDE OF LATCH. | | | | | | 8) SHEET A-3 GUARD RAIL EXTENSIONS: | | | 1007.5.5. HANDRAILS SHALL EXTEND AT | | | LEAST 12 INCHES HORIZONTALLY BEYOND THE | | | TOP RISER OF A FLIGHT. .AT THE BOTTOM, | | | THE HANDRAIL SHALL CONTINUE TO SLOPE FOR | | | A DISTANCE OF THE DEPTH OF ONE TREAD | | | FROM THE BOTTOM RISER. | | | | | | 9) 1007.5.2 STAIRWAYS SHALL HAVE HAND- | | | RAILS ON EACH SIDE. | | | | | | 10) 1608.2.3 THE GUARDRAIL SYSTEM SHALL | | | BE DESIGNED AND CONSTRUCTED TO RESIST A | | | 200 LB CONCENTRATED HORIZONTAL LOAD | | | APPLIED ON A 1 SQ FT AREA AT ANY POINT | | | IN THE SYSTEM INCLUDING INTERMEDIATE | | | RAILS OR OTHER ELEMENTS SERVING THIS | | | PURPOSE. SEE A-8. | | | | | | 11)A-4STAIR NOTE " STAIR RAILING | | | | | | AND STAIRS TO CODE", 104.2.1 | | | W.P.B. ADMINISTRATIVE CODE DRAWINGS & | | | SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR | | | OTHERWISE, AS TO THE QUALITY OF | | | MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | | CONFORMITY WITH THE TECHNICAL CODES. | | | SUCH INFORMATION SHALL BE SPECIFIC AND | | | THE TECHNICAL CODES "SHALL NOT BE CITED | | | AS A WHOLE OR IN PART, NOR THE TERM | | | "LEGAL" OR ITS RQUIVALENT BE USED AS A | | | SUBSTITUTE FOR SPECIFIC INFORMATION". | | | | | | 12) WALL TO CBS CONNECTION, INDICATES | | | THE USE OF HUGHES CONNECTIONS, PLEASE | | | CORRECT HUGHES HAS BEEN OUT OF BUSINESS | | | | | | SINCE 1999. | | | | | | 13) A-8 DROPPED CEILING DETAIL CORRECT, | | | BRACING AS REQUIRED AND PROVIDE THE | | | INFORMATIONREQUIRED FOR A DROP CEILING, | | | ALLOWABLE CEILING SPANS, DEFLECTION | | | LIMIT L/240, CEILINGPSF, WILL MIDSPAN | | | SUPPORTS BE USED. SIZE & THICKNESS OF | | | MATERIAL USED.2504.5.1/ ASTM C 754. | | | | | | 14)1503.4.4 PROTECTION AGAINST DECAY & | | | TERMITES. CONDENSATE LINES & ROOF DOWN | | | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. | | | AWAY FROM THE STRUCTURE SIDEWALL, | | | WHETHER BY UNDERGROUND PIPING, TAIL EX- | | | TENSIONS, OR SPLASH BLOCKS. | | | | | | 15) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 16) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A)TRUSS ANCHOR SCHEDULE | | | B) ROOFING ASSEMBLIES- THE REFRENCED | | | ROOF TILE BY ARCHITECT DOES NOT | | | MATCH SUBMITTAL | | | | | | 17) BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2006-10-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-10-27 |
Time |
14:59 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2006-10-27 |
Time |
15:46 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2006-10-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-10-20 |
Time |
13:42 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2006-10-20 |
Time |
13:15 |
Sent To |
PC |
|
| Notes |
| 2006-10-20 13:42:00 | | | | | | | REVISION DENIED/INCOMPLETE | | | | | | | | | THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK MUST | | | SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 FAC. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-20 |
Time |
10:11 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-07-20 |
Time |
10:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-04-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-20 |
Time |
17:32 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2005-04-20 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2005-04-20 00:00:00 | ********** UNSAT 3RD REVIEW ********** | | | | | | PLEASE SEE COMMENTS FROM PREVIOUS TWO | | | REVIEWS WHICH STILL NEED TO BE ADDRESSED | | | FOR CODE COMPLIANCE. | | | | | | | | | PLEASE SEE NOTES TAKEN DIRECTLY IN | | | NUMBERED ORDER FROM PREVIOUS TWO | | | REVIEWS. | | | | | | 1)NOTE: NOTE #1 OK. | | | | | | 2)NOTE: NOTE #2 NO. PLEASE SEE 424.3B | | | FOR SIZING OF AHU'S, PLEASE SEE 5KW HEAT | | | STRIPS ON 60A OCP . PLEASE ALSO SEE #8 | | | AWG.310.16, 240.4 ETC. | | | PLEASE SEE MORE THAN ONE AHU SHOWN FOR | | | UNIT #2. | | | PLEASE SEE LOAD CALCULATIONS FOR AHU'S | | | IN UNIT #2. | | | | | | 3)NOTE: NOTE#3, NO. PLEASE SEE NEXT NOTE | | | FOR LOAD CALCS. | | | | | | 4)NOTE: NOTE #4 NO. SEE PREVIOUS NOTES. | | | | | | 5)NOTE: NOTE #5 OK. | | | | | | 6)NOTE: NOTE #6 NO, PLEASE SEE FEEDERS | | | FOR UNITS. PLEASE CORRELATE AND PLEASE | | | SEE 310.16,240.4B ETC. | | | | | | 7)NOTE: NOTE #7 NO, PLEASE SE PLANS | | | STILL ONLY SHOW ONE SMALL APPLIANCE. | | | 220.16,210.1C1,210.52B1 | | | | | | 8)NOTE: NOTE #8 NO, SEE PREVIOUS NOTES. | | | | | | 9)NOTE: NOTE #9OK. | | | | | | 10)NOTE: NOTE #10 NO, SEE PREVIOUS | | | NOTES. | | | | | | 11)NOTE: NOTE #11 NO, SEE PREVIOUS | | | REVIEWS. | | | | | | 12)NOTE: NOTE #12 OK. | | | | | | 13)NOTE: NOTE #13 OK, ADDED NOTE. | | | | | | 14)NOTE: NOTE #14 NO, SEE PREVIOUS | | | NOTES. | | | | | | 15)NOTE: NOTE #15 OK. | | | | | | 16)NOTE: NOTE #16 OK. | | | | | | 17)NOTE: NOTE #17 OK. | | | | | | 18)NOTE: NOTE #18 OK. | | | | | | 19)NOTE: NOTE #19 OK. | | | | | | 20)NOTE: NOTE #20 OK. | | | | | | 21)NOTE: NOTE #21 NO, PLEASE SEE A NOTE | | | WAS ADDED FOR CLEARENCE FOR A/C DISC'S | | | TO BE 30", HOWEVER, PLEASE SEE MIN PER | | | 110.26. | | | PLEASE SEE WALL ARE STILL SHOWN ON PLANS | | | CONFINING DISC'S. | | | | | | ALSO NOTE FROM PREVIOUS REVIEW #2. | | | | | | 1)NOTE: PLEASE SEE A NOTICE WAS GIVEN | | | WITH RESPECT TO DESIGN PROFESSIONAL AND | | | FS 553.80(2)(B). PLEASE SEE THAT NOTICE | | | WAS GIVEN TO NOTIFY DESIGN PROFESSIONAL | | | IF PLANS COME BACK WITH ANY OF THE SAME | | | COMMENTS FOR CODE COMPLIANCE NOT | | | ADDRESSED THAT A 4X FEE FOR PLAN REVIEW | | | PORTION OF PERMIT FEE SHALL BE ACCESSED. | | | THIS IS A REQUIRED FEE UNDER FS AND IS | | | NOW ACCESSED. PLEASE SEE NUMEROUS | | | COMMENTS FROM PREVIOUS TWO REVIEWS WERE | | | NOT ADDRESSED. | | | PLEASE SEE A FEE OF $6792.00 HAS NOW | | | BEEN ATTACHED AND THIS FEE MUST BE PAID | | | BEFORE RESUBMITTING PLANS. THIS IS | | | REQUIRED UNDER FS 553.80(2)(B). | | | PLEASE BE AWARE THE COPY OF ABOVE FS IS | | | ATTACHEDONCE AGAIN. | | | | | | **PLEASE SEE ONE SET OF THE ELECTRICAL | | | PLANS ARE BEING RETAINED FOR FILE. | | | PLEASE SEE THESE MAY BE SENT TO THE | | | BOARD OF ARCH'S FOR REVIEW. | | | | | | 2)NOTE: PLEASE PROVIDE A COMPLETE | | | CONTRACT SHOWING VALUATION FOR COMPLETE | | | ELECTRICAL WORK AS SET FORTH ON PLANS. | | | PLEASE SEE LOCAL ADMINISTRATIVE CODE/FBC | | | 104.6.5. | | | PLEASE SEE FS 471.003, IF VALUE FOR | | | ELECTRICAL SCOPE OF WORK IS $50K OR | | | MORE, PLANS WILL BE REQUIRED TO BE DONE | | | BY A PROFESSIONAL ENGINEER. | | | | | | 3)NOTE: PLEASE SEE ONE SETOF PLANS | | | HAVE MANY OF THE ABOVE REDLINED AT | | | LOCATIONS OF COMMENTS ONCE AGAIN. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETSFOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-01-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-26 |
Time |
13:32 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2005-01-26 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2005-01-26 00:00:00 | *********** UNSAT 2ND REVIEW ********* | | | | | | PLEASE SEE MANY OF THE NOTES FROM | | | PREVIOUS REVIEW STILL NEED TO BE | | | ADDRESSED. | | | | | | 1)NOTE: NOTE #1 OK, ADDRESSED W/NOTE. | | | | | | 2)NOTE: NOTE #2 NO, SEE 424.3B | | | | | | 3)NOTE: NOTE #3 YES, HOWEVER LOAD CALCS | | | FOR PANEL "D" ARE NOT PER 220 FOR | | | COMMERICAL SPACE. PLEASE SEE NOTE# 4 | | | FROM PREVIOUS REVIEW. | | | ***NEW*** | | | PLEASE SEE NOTE THAT LOAD CALCS HAVE | | | BEEN SUBMITTED, PLEASE CORRELATE VOLTAGE | | | AND LOAD CALCS FROM PANEL SCHEDULES TO | | | LOADS ON RISER DIAGRM. | | | | | | 4)NOTE: NOTE #4 NO, PLEASE SEE PREVIOUS | | | NOTE. | | | | | | 5)NOTE: NOTE #5, ? PANEL CH SEEMS TO NOW | | | BE PANEL "D"> NO COMMENT. | | | | | | 6)NOTE: NOTE #6 NO, SEE PREVIOUS | | | COMMENTS. #2 STILL SHOWN ON OCP TOO HIGH | | | FOR RATING OF AWG ETC. | | | | | | 7)NOTE: NOTE #7 NO. SEE PREVIOUS NOTE. | | | | | | 8)NOTE: NOTE #8 NO. SEE PREVIOUS NOTE. | | | | | | 9)NOTE: NOTE #9 OK. | | | | | | 10)NOTE: NOTE #10 NO SEE PREVIOSU NOTE. | | | | | | 11)NOTE: NOTE #11 NO? SEE LOAD CALCS. | | | SEE 240.4B | | | | | | 12)NOTE: NOTE #12 OK. | | | | | | 13)NOTE: NOTE #13 NO, SEE PREVIOUS NOTES | | | ABOUT NOTE #21. | | | | | | 14)NOTE: NOTE #14 NO, SEE PREVIOUS. | | | | | | 15)NOTE: NOTE #15 OK. | | | | | | 16)NOTE: NOTE #16 OK. | | | | | | 17)NOTE: NOTE #17 ? ADDED AS NOTE, | | | INSTEAD OF PANEL SCHEDULE AS PREVIOUS | | | REQUEST. | | | | | | 18)NOTE: NOTE #18 OK | | | | | | 19)NOTE: NOTE #19 NO, SEE PREVIOUS | | | NOTES. | | | | | | 20)NOTE: NOTE #20 OK. | | | | | | 21)NOTE: NOTE #21 NO, UNCLEAR, PLEASE | | | ADD NOTE FOR CLEARENCE OF DISC'S PER | | | 110.26. | | | | | | **** NEW NOTE**** | | | | | | 1)NOTE: PLEASE SEE ATTACHED COPY OF FS | | | 553.80(2)(B). PLEASE SEE IF PLANS COME | | | BACK WITH ANY OF THE SAME COMMENTS FROM | | | TWO PREVIOUS REVIEWS NOT ADDRESSED, A 4X | | | FEEFOR PLAN REVIEW PORTION OF PERMIT | | | MUST BE ACCESSED PER FS. THIS IS ONLY A | | | NOTICE GIVEN AT THIS TIME. | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWS WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE COPY OF OLD PLANS SHOULD BE | | | SUBMITTED FOR REFERENCE ONLY. | | | | | | | | | | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-11-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-19 |
Time |
06:39 |
Rev Time |
1.25 |
| Received By |
dpalmer |
Date |
2004-11-19 |
Time |
06:39 |
Sent To |
|
|
| Notes |
| 2004-11-19 00:00:00 | *********** UNSAT ************ | | | | | | PLEASE SEE SOME OF THE NOTES FROM | | | REVIEW | | | UNDER PERMIT #03011199 ARE THE SAME. | | | | | | | | | 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING | | | INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO | | | BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 2)NOTE: PLEASE SEE OCP FOR AHU'S PER | | | 424.3B, CLUBHOUSE UNIT. PLEASE ALSO SEE | | | 50A OCP FOR UNIT #3 FOR A 5KW UNIT.? | | | PLEASE CORRELATE SIZES OF ALL A/C UNITS | | | WITH MECHANICAL PLANS. | | | | | | 3)NOTE: PLEASE SEE ALL PANEL SCHEDULES | | | DO NOT INCLUDE LOAD INFORMATION AT THE | | | BOTTOM.? | | | 215.5 | | | | | | | | | 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW PER | | | 220.3,220.10,220.11,220.13 ETC. | | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | | AT 125% PER 215.3,230.42 | | | PLEASE INDICATE WITH THE MIXED USE. | | | NO LOAD CALCS SHOWN FOR CLUBHOUSE | | | PANEL? | | | 215.5 | | | | | | 5)NOTE: PLEASE IDENTIFY CH PANEL. | | | | | | 6)NOTE: PLEASE CORRELATE OCP ON METER | | | CENTER AND ALL PANELS. SOME SHOW 150A, | | | 100A PANELS ALL WITH 200A BREAKERS | | | FEEDING THEM?? | | | 310.16,240.4B | | | PLEASE ALSO SEE #2 AWG ON 200A BRKR. #2 | | | PER 310.16 IS RATED AT 115A'S?? | | | | | | 7)NOTE: PLEASE SEE THERE IS ONLY ONE | | | SMALL APPLIANCE LOAD ON PANEL SCHEDULE? | | | PLEASE SEE TWO MIN AS INDICATE IN LOAD | | | CALCS FOR UNITS. 220.16,210.11C1, | | | 210.52B1 | | | | | | 8)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH PANEL | | | SCHEDULES. | | | PLEASE SEE SD'S ETC.OUTSIDE LTS? | | | PLEASE SEE CIRCUITING FOR CU FOR | | | CLUBHOUSE, DOES NOT CORRELATE W/ PANEL | | | SCHEDULE. SHOWN ON TWO DIFFERENT SIDES | | | OF THE PANEL. | | | | | | 9)NOTE: PLEASE SEE 210.52 FOR MISSING | | | RECEPT ON 2' OF WALL, UNIT #1 | | | | | | 10)NOTE: PLEASE SEE CIRCUITING FOR | | | DINING RM RECEPTS.210.52B1, 220.16 | | | | | | 11)NOTE: PLEASE SEE SEC'S TO BE SIZED | | | PER 310.16, 240.4B | | | | | | 12)NOTE: PLEASE SEE 250.50, THIS ALSO | | | REQUIRES FOOTER STEEL. RISER INDICATES | | | BLDG STEEL? | | | | | | | | | 13)NOTE: PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | 2002 NEC 210.12 | | | PLEASE SEE NOTE#21 ON PLANS. PLEASE | | | ADJUST. | | | | | | 14)NOTE: PLEASE SEE 700.12E FOR | | | CIRCUITING OF EM/EXT LTS.PLEASE ALSO | | | ADJUST PANEL SCHEDULE. | | | | | | 15)NOTE: PLEASE INCLUDE ALL INFORMATION | | | ON TITLE BLOCK AS REQUIRED UNDER FAC | | | 61G1-16.004. | | | PLEASE SEE THAT THIS IS REQUIRED ON ALL | | | SHEETS WHEATHER OR NOT COMMENT IS MADE | | | BY OTHER REVIEWER(S). | | | PLEASE SEE FBC 104.2.1 FOR ALL PLANS, | | | INCLUDING MECHANICAL. | | | | | | 16)NOTE: PLEASE SEE SOME PANEL | | | SCHEDULES INDICATE PANEL LOCATIONS AS | | | BEING A"GARAGE"? HOWEVER , COULD NOT | | | LOCATE ANY GARAGES ON PLANS? MISPRINT?? | | | | | | | | | 17)NOTE: PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE(S). PER 210.52D, 210.11C3 | | | MUST BE 20A #12 | | | | | | 18)NOTE: PLEASE SHOW LOCATION OF CH | | | PANEL ON PLANS. THIS COULD NOT BE | | | LOCATED. | | | | | | 19)NOTE: PLEASE SEE SOME LTS ARE SHOWN | | | ON PLANS ON THE SAME SWITCH LEG,HOWEVER | | | THEY ARE ON TWO SEPARATE CIRCUITS?? | | | THIS WILL NOT WORK, THESE MUST BE ONTHE | | | SAME CIRCUIT OR SEPARATE SWITCHES. | | | | | | 20)NOTE: PLEASE SEE WF/WATER COOLER IS | | | SHOWN ON GEN LT CIRCUIT. PLEASE VERIFY | | | THISAS IT MAY BE REQUIRED TO BE ON A | | | SEPARATE CIRCUIT. | | | | | | 21)NOTE: PLEASE SHOW CLEARENCE FOR A/C | | | DISCONNECTS PER 110.26 | | | | | | 22)NOTE: PLEASE REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW SHEETS INTO | | | TWO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | PLEASE SUBMIT ONE COPY OF OLD SHEETS | | | FOR REFERENCE ONLY. | | | | | | 23)NOTE: PLEASE SEE ANY POSSIBLE | | | COMMENTS FROM OTHER REVIEWERS WHICH MAY | | | HAVE AN AFFECT ON ELECTRICAL PLANS. | | | PLEASE SEE ANY FIRE REVIEW COMMENTS. | | | | | | PLEASE SEE ONE SET HAS MOST OF THE | | | ABOVE COMMENTS REDLINED IN THE AREAS AS | | | NOTED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | ME. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2006-01-13 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2006-01-13 |
Time |
10:50 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2006-01-13 |
Time |
10:50 |
Sent To |
B |
|
| Notes |
| 2006-01-13 00:00:00 | PASSED: | | | | | | 1. REVIEWED FOR REVISION. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2005-01-21 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-01-21 |
Time |
10:08 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2005-01-21 |
Time |
10:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2004-11-17 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-11-17 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-07-20 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2004-11-17 00:00:00 | FAILED: | | | | | | 1. PLEASE NOTE THAT CIVIL' PLAN SHEETS | | | MUST HAVE THE ORIGINAL RAISED SEAL AND | | | SIGNATURE OF THE CIVIL ENGINEER OF THE | | | RECORD. | | | | | | 2. PLEASE SUBMIT CIVIL PLANS TO PUBLIC | | | UTILITIES & ENGINEERING FOR APPROVAL OF | | | ALL THE CONNECTIONS TO THE CITY | | | SERVICES, ATT:MANNY GONZALEZ, 494-1085. | | | | | | 3. EROSION/SEDIMENTATION CONTROL | | | DEVICES MUST BE INSTALLED IN FIELD | | | PRIOR TO BEGINNING ANY WORK AND | | | MAINTAINED DURING THE CONSTRUCTION | | | ACTIVITIES. | | | | | | 4. PLEASE VERIFY THE DIRECTION OF NORTH | | | ARROWS ON ARCHITECTURAL, LANDSCAPING | | | PLANS. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-07-29 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-29 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-29 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2005-04-26 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-04-26 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-04-26 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2005-04-26 00:00:00 | 1) AN ADDRESS NUMBER IS SHOWN ON THE | | | ELEVATION DRAWING. PLEASE PROVIDE THE | | | REQUIREMENT OF NUMBERS THAT ARE A | | | MINIMUM OF 6" IN HEIGHT AND CONTRASTING | | | TO THE BACKGROUND. | | | | | | 2) PLEASE INDICATE THE INTERIOR FINISH | | | CLASSIFICATION OF THE WALLS AND CEILING. | | | | | | 3) THE PREVIOUS COMMENT REGARDING THE | | | RANGE AND HOOD IN THE KITCHEN HAS NOT | | | BEEN ADDRESSED. PLEASE BE ADVISED THAT A | | | HOOD DUCT AND SUPPRESSION SYSTEM IS | | | REQUIRED IF COOKING PRODUCES SMOKE OR | | | GREASE LADEN VAPORS. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-02-08 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-02-08 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2005-02-08 00:00:00 | 1. BUILDING ADDRESS REQUIRED. A MINIMUM | | | OF AT LEAST 6" HIGH NUMBERS ARE | | | REQUIRED. | | | | | | 2. INTERIOR FINISH CLASSIFICATIONS | | | FOR WALLS AND CEILINGS IN EXITS SHALL | | | BE CLASS A OR B. | | | | | | 3. RANGE WITH HOOD IN KITCHEN WILL | | | BE USED FOR WHAT. ANY COOKING THAT | | | PRODUCES SMOKE OR GREASE LADEN | | | VAPORS SHALL BE PROTECTED BY A HOOD, | | | DUCT, AND SUPPRESSION SYSTEM. | | | | | | 4. PLEASE SEE BUILDING PLAN REVEIWER | | | NOTES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-12-16 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-12-16 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-12-16 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2004-12-16 00:00:00 | FIRE REVIEW PLEASE REF NFPA 101 LIFE | | | SAFETY CODE 2000 EDITION | | | | | | 1) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 2) DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3) BUILDING ADDRESSES ARE REQUIRED. | | | COULD NOT LOCATE THEM ON ELEVATION | | | DRAWINGS. | | | | | | 4) PLEASE INDICATE THE INTERIOR WALL AND | | | CEILING FINISH CLASS "A", CLASS "B", OR | | | CLASS "C". | | | | | | 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR BALCONY RAILINGS. | | | | | | 6) STAIRS SHALL HAVE HANDRAILS ON EACH | | | SIDE. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-09-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-09 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-09 |
Time |
16:21 |
Sent To |
P |
|
| Notes |
| 2006-09-09 00:00:00 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-05-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-15 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-15 |
Time |
12:52 |
Sent To |
P |
|
| Notes |
| 2006-05-15 00:00:00 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-05-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-12 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-12 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2006-05-12 00:00:00 | WAITING FOR "COMM" BD-REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-04-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-26 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-26 |
Time |
08:26 |
Sent To |
M |
|
| Notes |
| 2006-04-26 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-07-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-11 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-11 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2005-07-19 00:00:00 | TO "COMM" BD#54 | | 2005-07-11 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-04-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-06 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-06 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2005-04-06 00:00:00 | TO "COMM" BD#53 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-01-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-20 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-20 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2005-01-20 00:00:00 | TO "COMM BD#35/RESUB. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-12-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-12-16 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2004-11-12 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2004-11-12 00:00:00 | TO COMM BD#18 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2006-06-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-06-05 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-06-05 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2006-05-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-05-22 |
Time |
14:51 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-05-22 |
Time |
14:51 |
Sent To |
B |
|
| Notes |
| 2006-05-22 00:00:00 | REVISION TO MECH. PLANS PAGE M-1, M-2, | | | M-3. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2006-04-27 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-04-27 |
Time |
14:48 |
Rev Time |
1.30 |
| Received By |
tgordon |
Date |
2006-04-27 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2006-04-27 00:00:00 | *** DENIED *** | | | 1) DUCTS GOING THRU THE FIRE RATED WALL | | | IN THE FILE STOR. ROOM MUST BE METAL | | | WITH FIRE DAMPERS, PER 2004 FBC/M | | | 607.5.3 SEE ATTACHED A-2 . | | | | | | 2) DUCTS GOING THRU THE FIRE RATED WALL | | | FROM LIVING ROOM #3 TO DINING ROOM MUST | | | BE METAL WITH FIRE DAMPERS, SEE ATTACHED | | | A-3 . | | | | | | 3) PLEASE EXPLAIN RETURN AIR FOR GROUND | | | FLOOR PG. M-2AHU #1 & # OVER BATHROOMS | | | IS THAT TO BE A ENCLOSED WALL AROUND FOR | | | A PLENUM OR IS THE ENTIRE FIRST FLOOR | | | ATTIC THE PLENUM. | | | | | | 4) PAGE M-2 GROUND FLOOR, MOST RETURN | | | AIR TRANSFER DUCTS ARE UNDRE SIZED, SEE | | | NOTE #5(A). | | | | | | 5) BALANCED RETURN AIR. | | | THIS MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | (B)TRANSFER GRILLES SHALL USE 50 | | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | | CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND | | | USING AN UNRESTRICTED 1-INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-26 |
Time |
19:55 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2005-07-26 |
Time |
19:36 |
Sent To |
|
|
| Notes |
| 2005-07-26 00:00:00 | PROVISO: | | | BI-FOLD DOORS TO THE AHU CLOSETS SHALL | | | BE NON-COMBUSTIBLE IN ACCORDANCE WITH | | | 2001 FBC(M)602.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2005-05-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-05-03 |
Time |
09:28 |
Rev Time |
1.45 |
| Received By |
pkrauss |
Date |
2005-04-29 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2005-04-29 00:00:00 | DENIED:3RD REQUEST | | | 1.PROVIDE DDETAIL FOR PENETRATIONS - | | | RESPONSE IS TO REFERENCE A4 OF A5, PLAN | | | SHEET A5 INDICATES PENETRATION FOR | | | "CABLES" BUT NO DETAIL FOR THE FIRE | | | DAMPERS.PLEASE NOTE FIRE DAMEPRS ARE | | | MISSING FOR DUCTS PENETRATING RATED WALL | | | FROM THE FILE ROOM INTO THE | | | "MULTI-PURPOSE" ROOM.PLEASE NOTE FLEX | | | DUCT IS PROHIBITED FROM PENETRATING A | | | RATED WALL, 2001 FBC(M)603.5.5. | | | | | | 2.OUTSIDE AIR CALCULATIONS ACCORDING | | | TO THE RESPONSE ARE NOTED ON PLAN SHEET | | | M1.NO O.A. CALUCALTIONS INIDCATED. | | | PROVIDE O.A. CALCS FOR THE COMMON AREAS | | | AS WELL AS THE RESIDENCE. | | | | | | 4. INDICATE O.A. DUCT SIZE, MATERIAL, | | | LAYOUT AND INTAKE. | | | | | | 5.RETURN AIR JUMPERS WERE NOT | | | INCREASED TO 1 1/2 TIMES THE SQUARE | | | INCHES OF THE SUPPLY AIR. | | | | | | 7.DUCT SMOKE DETECTOR IS NOT INDICATED | | | ON THE PLAN. | | | | | | 8.PROVIDE SUBMITTAL FOR THE HOOD, | | | EXHAUST SHALL NOT TERMINATE ONTO | | | WALKWAYS.RESPONSE INDICATES | | | TERMINATION TO EXTERIOR WALL BUT IS NOT | | | IDENTIFIED ON THE PLAN.MECHANICAL PLAN | | | CONFLICTS WITH THE ELECTRICAL PLAN.THE | | | 1ST FLOOR KITCHEN AREA SHOWS A MICROWAVE | | | OVEN ON THE ELECTRICAL PLAN & A RANGE | | | W/HOOD ON THE MECHANICAL PLAN.PLEASE | | | CLARIFY. | | | | | | 9.EQUIPMENT SCHEDULE NOT GIVEN FOR THE | | | EXHAUST FANS. | | | | | | 10.LOCATION OF THE AHU ON THE FIRST | | | FLOOR.PLEASE NOTE RETURN AIR DUCT | | | SHALL BE DUCTED INTO THE AHU IN THIS | | | FIRE RATED ROOM.WHY WOULD THE AHU BE | | | LOCATED IN THE ONLY "FIRE RATED" ROOM IN | | | THE BUILDING? | | | | | | 11.LINE SIZES FOR THE LIQUID, SUCTION | | | AND CONDENSATE ARE NOT INDICATED. | | | | | | 12 & 13. CONDENSATE TERMINATION IS NOT | | | INDICATED. | | | | | | NEW COMMENT: | | | PLAN SHEET A-2 INDICATED BUILDING | | | CATEGORY AS R-3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-02-03 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-02-03 |
Time |
15:41 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2005-02-03 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2005-02-03 00:00:00 | DENIED: | | | PLEASE NOTE COMMENTS NOT ADDRESSED FROM | | | PREVIOUS REVIEW DATED 12-4-04.PROVIDE | | | A RESPONSE LETTER TO COMMENTS TO HELP | | | EXPEDITE PLANS. | | | | | | 2ND REQUEST: | | | 1.PROVIDE DETAIL FOR PENETRATIONS | | | THROUGH RATED ASSEMBLIES. | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS | | | PER 2001 FBC(M) TABLE 403.3 OR 402. | | | PROVIDE CALCULATIONS FOR ALL AREAS, | | | COMMON AND RESIDENTIAL. | | | | | | 4.PROVIDE OUTSIDE AIR INTAKE, DUCT | | | LAYOUT, SIZE AND MATERIAL. | | | | | | 5.RETURN AIR JUMPERS SHALL BE A | | | MINIMUM OF 1 1/2 TIMES THE SQUARE | | | INCHES OF THE SUPPLY AIR INTO THAT | | | SPACE.ALL AIR INTO THE MASTER SUITE IS | | | TO BE INCLUDED PER 2001 FBC(M)601.4 | | | EXCEPTION #1 & 3. | | | | | | 6.INDICATE VENTILATION FOR THE | | | STORAGE | | | AREA ON THE SECOND FLOOR IN ACCORDANCE | | | WITH 2001 FBC(M) TABLE 403.3.PLEASE | | | INDICATE WHAT WILL BE STORED IN THE | | | STORAGE AREA. | | | | | | 7.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS REQUIRED.2001 | | | FBC(M)606.2.1 & 606.4.1 #2. | | | | | | 8.PROVIDE SUBMITTAL FOR THE HOOD TO | | | THE RANGE & HOOD INDICATED ON THE 1ST | | | FLOOR KITCHEN.PLEASE NOTE, EXHAUST | | | SHALL NOT TERMINATE ONTO THE WALKWAY. | | | | | | 9.PROVIDE EQUIPMENT SCHEDULE FOR THE | | | ALL OF THE EXHAUST FANS. | | | | | | 10. IDENTIFY LOCATION OF THE AHU ON THE | | | FIRST FLOOR. | | | | | | 11. INDICATE LINE SIZE FOR THE LIQUID, | | | SUCTION AND CONDENSATE LINES. | | | | | | 12. CONDENSATE TO TERMINATE A MINIMUM | | | OF | | | 12" AWAY FROM THE BUILDING STRUCTURE | | | PER | | | 2001 FBC(M)1503.4.4. | | | | | | 13. INDICATE TERMINATION OF ALL | | | CONDENSATE LINES.CONDENSATE FROM THE | | | 7.5 TON SYSTEM ON THE 1ST FLOOR SHALL | | | TERMINATE INTO THE STORM OR AN APPROVED | | | DRYWELL PER CITY CODE SEC.90-125 (5). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-12-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-12-04 |
Time |
09:55 |
Rev Time |
1.20 |
| Received By |
pkrauss |
Date |
2004-12-04 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2004-12-04 00:00:00 | DENIED: | | | 1.PROVIDE DETAIL FOR PENETRATIONS | | | THROUGH RATED ASSEMBLIES, I.E. | | | CEILING/FLOOR & WALL. | | | | | | 2.PLAN DOES NOT INDICATE LOCATION | | | AND | | | DETAIL OF FIRE DAMPERS AS REQUIRED PER | | | 2001 FBC(M)607.6. | | | | | | 3.PROVIDE OUTSIDE AIR CALCULATIONS | | | PER | | | 2001 FBC(M) 403.3.PROVIDE CALCS FOR | | | RESIDENTIAL AND COMMERCIAL AREA. | | | | | | 4.INDICATE OUTSIDE AIR INTAKE, DUCT | | | LAYOUT, SIZE AND MATERIAL. | | | | | | 5.RETURN AIR JUMPERS SHALL BE A | | | MINIUM | | | OF 1 1/2 TIMES THE SQUARE INCHES OF THE | | | SUPPLY AIR INTO THAT SPACE. | | | | | | 6.INDICATE MINIMUM VENTILATION FOR | | | THE | | | STORAGE AREA INDICATED ON THE 2ND | | | FLOOR. | | | | | | 7.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | REQUIRED FOR THE 1ST FLOOR 7.5 TON | | | UNIT. | | | INDICATE LOCATION OF DUCT SMOKE | | | DETECTOR. | | | | | | 8.NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS REQUIRED FOR | | | DUCT SMOKE DETECTORS PER NFPA 90A. | | | | | | 9.PROVIDE SUBMITTAL FOR THE | | | RANGE/HOOD | | | INDICATED ON THE 1ST FLOOR COMMON AREA | | | KITCHEN. | | | | | | 10. PLANS ARE TO BE SIGNED BY THE PERSON | | | RESPONSIBLE FOR THE DESIGN PER CITY | | | AMENDMENTS TO THE 2001 FBC 104.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2006-09-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-09-21 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-09-21 |
Time |
13:48 |
Sent To |
PC |
|
| Notes |
| 2006-09-21 00:00:00 | REVISION SANITARY ISOMETRIC. | | | APPROVED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2006-05-27 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-05-27 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-05-27 |
Time |
10:55 |
Sent To |
PC |
|
| Notes |
| 2006-05-27 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | REVIEW | | | | | | UNSAT | | | 1) ALL REVISIONS TO PLANS SIGNED AND | | | SEALED BY AN ARCHITECT OR ENGINER, SHALL | | | BE SIGNED AND SEALED BY THAT ARCHITECT | | | OR ENGINEER. | | | | | | END OF COMMENTS QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2005-08-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-08-01 |
Time |
09:44 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2005-08-01 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2005-08-01 00:00:00 | PASSED/PROVISO | | | | | | 3/4" REQUIRED TO EACH HEATER. | | | AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE. | | | A FULL OPEN VALVE IS REQUIRED ON THE | | | WATER DISTRIBUTION SUPPLY PIPE AT THE | | | ENTRANCE TO THE STRUCTURE. | | | SECOND FLOOR WATER RISER SHALL BE | | | UPSTREAM OF VALVE TO WATER HEATER FIRST | | | FLOOR. | | | A FULL OPEN VALVE IS REQUIRED ON THE | | | ENTRANCE TO EVERY WATER SUPPLY PIPE TO | | | EVERY DWELLING UNIT & ON THE WATER | | | SUPPLY PIPE TO EVERY WATER HEATER. | | | 606.1(5) & (7). | | | A FULL OPEN VALVE IS REQUIRED ON THE | | | BASE OF THE WATER RISER. 606.1(3). | | | KITCHEN SINK HEIGHT 11-44.24.2 AND KNEE | | | CLEARANCE 11-4.24.3 SHALL COMPLY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2005-04-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-27 |
Time |
17:07 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2005-04-27 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2005-04-27 00:00:00 | | | | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FLORIDA STATUTES | | | | | | A) FROM PREVIOUS REVIEWS: | | | 1) SHT A-2 KITCHEN SINK SHALL COMPLY | | | WITH SECTION 4.24 ALL ALL SUBMSECTIONS. | | | PLEASE SUBMIT A DETAIL. THE FOLLOWING | | | INFORMATION IS STILL REQUIRED: | | | A) HEIGHT 11-4.24.2 | | | B) CLEAR FLOOR SPACE 11-4.24.5 SHALL BE | | | PROVIDED TO ALLOW FORWARD APPROACH AND | | | SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH | | | THE SINK. (FIG. 32) | | | C) EXPOSED PIPES & SURFACES 11-4.24.6 | | | D) FAUCETS 11-4.24.7 | | | 4) SUBMIT A WATER RISER DIAGRAM REQUIRED | | | BY SECTION 104.3.1.1. SHOW ALL PIPE | | | SIZES. | | | 6) THERMAL EXPANSION CONTROL IS REQUIRED | | | ON ALL WATER HEATERS. SHOW ON THE DETAIL | | | FOR THE W/HEATERS. SECTION 607.3.2. | | | 1B) FOR ACCESSIBLE TOILET ROOMS SHOW THE | | | FOLLOWING INFORMATION: | | | C) FLUSH CONTROLS 11-4.16.5 | | | F) EXPOSED PIPES & SURFACES 11-4.19.4 | | | H) LAV SHALL BE SHOWN A MINIMUM 15" OFF | | | THE WAALL TO THE CENTERLINE OF THE | | | FIXTURE TO BE CENTERED ON THE 30" OF THE | | | CLEAR FLOOR SPACE. | | | ******NEW COMMENTS******** | | | 1C) HAND DRAWN CORRECTIONS TO A SIGNED, | | | SEALED & DATED SET OF PLANS IS NOT | | | APPROVED UNLESS EACH CORRECTIONS IS | | | SIGNED & DATED BY THE ARCHITECT OF | | | RECORD. - ALSO WHITE OUT IS NOT APPROVED | | | FOR CHANGES ON SIGNED/SEALED DRAWINGS. | | | SECTION 104.2.1.3 | | | 2C) SEE ELECTRICAL REVIEW COMMENT | | | ADDRESSING 553.80(2)(B) AND 4 X FEE | | | REQUIRED TO BE PAID PRIOR TO | | | RESUBMITTING PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-02-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-02-14 |
Time |
17:21 |
Rev Time |
0.66 |
| Received By |
kstevens |
Date |
2005-02-14 |
Time |
17:21 |
Sent To |
|
|
| Notes |
| 2005-02-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | A) FROM PREVIOUS REVIEW: | | | 1) SHT A-2 KITCHEN SINK SHALL COMPLY | | | WITH SECTION 4.24 AND ALL SUBSECTIONS. | | | PLEASE SUBMIT A DETAIL. NO SUBMITTAL HAS | | | BEEN SUBMITTED. | | | 2) SHT A-2 DRINKING FOUNTAIN SHALL | | | COMPLY WITH SECTION 11-4.15 AND ALL | | | SUBSECTIONS. SUBMIT A DETAIL. ALSO SHOW | | | COMPLIANCE WITH SECTION 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY | | | BENDING OR STOOPING. NO SUBMITTAL HAS | | | BEEN SUBMITTED. | | | 3) TABLE 403.1 AUTOMATIC CLOTHES WASHER | | | CONNECTIONS ARE REQUIRED. SHOW ON THE | | | FLOOR PLAN, SANT. RISER DIAGRAM AND THE | | | WATER RISER DIAGRAM. NOT ADDRESSED. | | | 4) SUBMIT A WATER RISER DIAGRAM REQUIRED | | | BY SECTION 104.3.1.1. SHOW ALL PIPE | | | SIZES, VALVES AND WATER HAMMER ARRESTORS | | | PER SECTION 606 & 604.9. NOT ADDRESSED. | | | 6) THERMAL EXPANSION CONTROL IS REQUIRED | | | AT ALL WATER HEATERS PER SECTION | | | 607.3.2. SUBMIT A HEATER DETAIL SHOWING | | | COMPLIANCE. | | | 8) PLEASE NOTE THAT MOST OF THESE | | | COMMENTS WERE STATED IN THE REVIEW OF | | | PERMIT NUMBER 03011199. | | | *************NEW COMMENTS********* | | | 1B) FOR ACCESSIBLE TOILET ROOM SHOW THE | | | FOLLOWING INFORMATION: | | | A) CLEAR FLOOR SPACE 11-4.16.2 | | | B) GRAB BARS PER FIG 29. 11-4.16.4 | | | C) FLUSH CONTROLS 11-4.16.5 | | | D) HEIGHT & CLEARANCES 11-4.19.2 | | | E) CLEAR FLOOR SPACE 11-4.19.3 | | | F) EXPOSED PIPES & SURFACES 11-4.19.4 | | | G) TOILETS SHALL BE 18" FROM THE | | | CENTERLINE OF THE FIXTURE TO THE WALL. | | | FIGURE 28. | | | H) LAV SHALL BE MINIMUM 15" FROM THE | | | CENTERLINE OF THE FIXTURE TO THE WALL. | | | SHALL BE CENTERED ON THE 30" OF THE | | | CLEAR FLOOR SPACE. | | | 2B) SHT A-3 SANITARY RISER DIAGRAM, THE | | | TUBS IN ALL UNITS ARE NOT VENTED AS | | | SHOWN. SECTION 901.2.1. | | | 3B) DRAWINGS SHALL BE SPECIFIC, AND THE | | | TECHNICAL CODES SHALL NOT BE CITED AS A | | | WHOLE OR IN PART, NOR SHALL THE TERM | | | "LEGAL" OR ITS EQUIVALENT BE USED AS A | | | SUBSTITUTE FOR SPECIFIC INFORMATION. | | | SECTION 104.2.1. | | | 4B) SEE SHEET ATTACHED TO BUILDING PLAN | | | REVIEWER'S NOTES CONCERNING DESIGN | | | PROFESSIONAL & FS 553.80(2)(B). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-12-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-12-11 |
Time |
17:43 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2004-12-11 |
Time |
17:43 |
Sent To |
|
|
| Notes |
| 2004-12-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-2 KITCHEN SINK SHALL COMPLY | | | WITH SECTION 4.24 AND ALL SUBSECTIONS. | | | PLEASE SUBMIT A DETAIL. | | | 2) SHT A-2 DRINKING FOUNTAIN SHALL | | | COMPLY WITH SECTION 11-4.15 AND ALL | | | SUBSECTIONS. SUBMIT A DETAIL. ALSO SHOW | | | COMPLIANCE WITH SECTION 11-4.1.3(10)(A) | | | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY | | | BENDING OR STOOPING. | | | 3) TABLE 403.1 AUTOMATIC CLOTHS WASHER | | | CONNECTIONS ARE REQUIRED. SHOW ON THE | | | FLOOR PLAN, SANT. RISER DIAGRAM AND THE | | | WATER RISER DIAGRAM. | | | 4) SUBMIT A WATER RISER DIAGRAM REQUIRED | | | BY SECTION 104.3.1.1. SHOW ALL PIPE | | | SIZES, VALVES AND WATER HAMMER ARRESTORS | | | PER SECTION 606 & 604.9. | | | 5) AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE. SECTION 608.13.2. | | | 6) THERMAL EXPANSION CONTROL IS REQUIRED | | | AT ALL WATER HEATERS PER SECTION | | | 607.3.2 | | | 7) SECTION 909.1 THE KITCHEN SINK SHALL | | | NOT DRAIN THROUGH THE WET-VENTED | | | HORIZONTAL DRAIN OF THE BATHROOM | | | FIXTURES. THE KITCHEN SINKS SHALL | | | DISCHARGE DOWNSTREAM OF THE BATHROOM | | | FIXTURES. | | | 8) PLEASE NOTE THAT MOST OF THESE | | | COMMENTS WERE STATED IN THE REVIEW OF | | | PERMIT NUMBER 03011199. | | | | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-12-15 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-12-15 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-12-15 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2004-12-15 00:00:00 | RETURNED TO COMMERCIAL BOARD #18 |
|
|