Plan Review Details - Permit 04110624
Plan Review Stops For Permit 04110624
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-01-17 Cont ID  
Sent By jwitmer Date 2006-01-17 Time 07:24 Rev Time 0.44
Received By jwitmer Date 2006-01-17 Time 07:23 Sent To PC
Notes
2006-01-17 00:00:00REVISION# 5 IS CHANGE IN GRADEOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-07-30 Cont ID  
Sent By jwitmer Date 2005-07-30 Time 15:20 Rev Time 1.33
Received By jwitmer Date 2005-07-30 Time 14:52 Sent To MEDGAS
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-04-20 Cont ID  
Sent By jwitmer Date 2005-04-20 Time 16:54 Rev Time 1.55
Received By jwitmer Date 2005-04-20 Time 16:54 Sent To  
Notes
2005-04-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110624
 ADD: 1318 HENRIETTA AV
 CONT:RANDOLPH& DEWDNEY
 TEL: (561)441-1186
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4THREVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT# 7 FROM THE PREVIOUS REVIEW,
 A-2 MULTI PURPOSE ROOM# 2 ENTRY DOOR,
 SEE11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING
 CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3)SHEET A-3 & A-4 GUARD RAIL
 EXTENTIONS:
 1007.5.5. HANDRAILS SHALL EXTEND AT
 LEAST 12 INCHES HORIZONTALLY BEYOND THE
 TOP RISER OF A FLIGHT. .AT THE BOTTOM,
 THE HANDRAIL SHALL CONTINUE TO SLOPE
 FOR
 A DISTANCE OF THE DEPTH OF ONE TREAD
 FROM THE BOTTOM RISER.SEE FIGURE 19
 ATTACHED.
  
 4 THE NEW STAIR DESIGN STILL CREATES A
 SINGLE MEANS OF EGRESS AT THE ONE END OF
 THE BREEZEWAY REQUIRING A 1 HR RATEED
 WALL AND 45 MIN OPENING PROTECTIVES.
 1006.2.4A. SEE ATTACHMENT.
  
 5) COMMENT# 9 FROM THE PREVIOUS
 REVIEW:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-01-26 Cont ID  
Sent By jwitmer Date 2005-01-26 Time 07:23 Rev Time 1.66
Received By jwitmer Date 2005-01-26 Time 07:11 Sent To  
Notes
2005-01-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110624
 ADD: 1318 HENRIETTA AVE
 CONT: RANDOLPH & DEWDNEY
 TEL: (561)441-1186
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT # 1 FROM THE PREVIOUS
 REVIEW,
 SHEET A-2 CORRECT EGRESS WINDOW
 STATEMENT ON THE GROUND FLOOR THE
 MINIMUM CLEAR OPENING SIZE IS 5'-0"
 NOT "THE NET CLEAR OPENING IN NO CASE
 BE
 LESS THAN 4'-0" SQ FT".
 2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL
 HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.
 3) COMMENT# 2 FROM THE PREVIOUS REVIEW,
 DEALS WITH THE HANDICAPPED BATHROOM
 REQUIREMENTS MISSING A COMMENT OR
 DETAIL
 INCLUDING THE REAR GRAB BAR AT THE
 WATER
  
 CLOSET.
 3) COMMENT# 3 FROM THE PREVIOUS REVIEW
 PLANS ARE NOT CLEAR ON THE FRONT ENTRY,
 ELEVATION INDICATE A STOOP OR LANDING
 THEN A STEP INTO THE LOBBY,
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. EXPLAINRATIONAL OR INDICATE
 A COMPLIANT RAMP.
  
 4) COMMENT# 4 FROM THE PREVIOUS REVIEW,
 FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A-2 PROVIDE THE MEAN ROOF HEIGHT.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, SHEET
 A-8DETAIL# 3 INDICATES AN EXTERIOR
 BLOCK
 WALL 4 BAR BEAM AND LEDGERS BUCKET AND
 FLOOR TRUSSES, PLANS LACK THE ATTCHMENT
 OF DOUBLE LEDGER TO BEAM AND TYPE OF
 BUCKET FOR FLOOR TRUSSES. SAME DETAIL
 MISSING APPROVED HANGERS FROM THE 3
 MEMBER GIRDER?
  
 6) COMMENT # 6 FROM THE PREVIOUS
 REVIEW,
 A-2 THE DESIGN OF THE EXTERIOR STAIR
 DOESN'T MET THE REQUIREMENT FOR A
 SINGLE
  
 STAIRWAY IN 1026.1 BECAUSE OF THE 1ST
 REQUIREMENT BEING THE MAXIMUM LENGTH OF
 TRAVEL TO REACH THE EXIT FROM THE
 ENTRANCE DOOR TO ANY UNIT SHALL NOT
 EXCEED 30 FT. SO (2) STAIRWAYS ARE
 REQUIRED.
 THE PROBLEM WITH THE STAIR DESIGN
 IS
 1006.2.2 REQUIRES THE STAIRS SHALL BE
 LOCATED THAT THE ENTRANCES AND ALL
 PORTIONS OF THE STAIRWAYS ON EACH LEVEL
 ARE A DISTANCE APART EQUAL TO NOT LESS
 THAN 1/2 OF THE LENGHT OF THE MAXIMUM
 OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA SERVED.
 SO INFACT THE PLAN MAY INDICATE (2)
 STAIRWAYS IN ELEVATION,BY DEFINITION
 THERE IS ONLY ONE.
  
 7) COMMENT# 7 FROM THE PREVIOUS REVIEW,
 A-2 MULTI PURPOSE ROOM# 2 ENTRY DOOR,
 SEE11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING
 CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 8)SHEET A-3 & A-4 GUARD RAIL
 EXTENTIONS:
 1007.5.5. HANDRAILS SHALL EXTEND AT
 LEAST 12 INCHES HORIZONTALLY BEYOND THE
 TOP RISER OF A FLIGHT. .AT THE BOTTOM,
 THE HANDRAIL SHALL CONTINUE TO SLOPE
 FOR
 A DISTANCE OF THE DEPTH OF ONE TREAD
 FROM THE BOTTOM RISER.
  
 9) COMMENT# 15 FROM THE PREVIOUS
 REVIEW:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B1) ROOFING ASSEMBLIES- A-8 INDICATES
 THE USE OF MONIER VILLA ROLL"S" VS THE
 PRODUCT APPROVAL SUBMITTEDFOR A
 ENTEGRA ESTATE "S" TILE
 B2) A-8 ARCHETECT ALSO PROVIDE A
 OPTION OF TIMBERLINE ASPHALT TILE, THE
 LOADING FOR TILE VS SHINGLES ARE NOT THE
 SAME.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-13 Cont ID  
Sent By jwitmer Date 2004-12-13 Time 14:45 Rev Time 3.33
Received By nmccray Date 2004-12-13 Time 14:45 Sent To  
Notes
2004-12-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04110624
 ADD: 1318 HENRIETTA AV
 CONT: RANDOLPH & DEWDNEYCONST
 TEL: (561)441-1182
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
  
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) SHEET A-2 CORRECT EGRESS WINDOWS
 STATMENT FOR 2ND FLOOR WINDOWS,
 2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL
 HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.
  
 2) HANDICAPPED RESTROOMS- SEE CHAPTER
 11
 FIGURE 30E FOR LENGTH OF REQUIRED GRAB
 BARS FOR SIDE AND REAR LOCATIONS.
  
 3) PLANS ARE NOT CLEAR AS TO LANDING
 LEVELS FOR FRONT AND SIDE ENTRY 1ST FL.
 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. SEE A-2.
  
 4) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, SHEET
 A-2 PROVIDE THE MEAN ROOF HEIGHT.
  
 5) SHEET A-2 COMMENT "STAIRWAYS COMPLY
 WITH THE REQUIREMENTS OF 1026.1"
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL
 TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE
 SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 6) SHEET A-2 THE DESIGN OF THE EXTERIOR
 STAIR, DOESN'T MEET THE DEFINITION OF A
 SINGLE STAIRWAY IN 1026.1 BECAUSE OF
 THE
 1 ST REQUIREMENT BEING THE MAXIMUM OF
 TRAVEL TO REACH THE EXIT FROM THE
 ENTRANCE DOOR TO ANY UNIT SHALL NOT
 EXCEED 30 FEET.
 THE PROBLEM WITH THE DESIGN OF THIS
 STAIRWAY FOR (2) EXIT STAIRS, 1006.2.2,
 REQUIRES, THE STAIRWAYS SHALL BE
 LOCATED
 THAT THE ENTRANCES AND ALL PORTIONS OF
 THE STAIRWAYS ON EACH LEVEL ARE A
 DISTANCE APART EQUAL TO NOT LESS THAN
 1/2 OF THE LENGHT OF THE MAXIMUM
 OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA SERVED.
  
 7) SHEET A-2 MULTI PURPOSE ROOM# 2, SEE
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.REQUIRES 18" ON THE SWING
 SIDE OF LATCH.
  
 8) SHEET A-3 GUARD RAIL EXTENSIONS:
 1007.5.5. HANDRAILS SHALL EXTEND AT
 LEAST 12 INCHES HORIZONTALLY BEYOND THE
 TOP RISER OF A FLIGHT. .AT THE BOTTOM,
 THE HANDRAIL SHALL CONTINUE TO SLOPE FOR
 A DISTANCE OF THE DEPTH OF ONE TREAD
 FROM THE BOTTOM RISER.
  
 9) 1007.5.2 STAIRWAYS SHALL HAVE HAND-
 RAILS ON EACH SIDE.
  
 10) 1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE. SEE A-8.
  
 11)A-4STAIR NOTE " STAIR RAILING
  
 AND STAIRS TO CODE", 104.2.1
 W.P.B. ADMINISTRATIVE CODE DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC AND
 THE TECHNICAL CODES "SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS RQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 12) WALL TO CBS CONNECTION, INDICATES
 THE USE OF HUGHES CONNECTIONS, PLEASE
 CORRECT HUGHES HAS BEEN OUT OF BUSINESS
  
 SINCE 1999.
  
 13) A-8 DROPPED CEILING DETAIL CORRECT,
 BRACING AS REQUIRED AND PROVIDE THE
 INFORMATIONREQUIRED FOR A DROP CEILING,
 ALLOWABLE CEILING SPANS, DEFLECTION
 LIMIT L/240, CEILINGPSF, WILL MIDSPAN
 SUPPORTS BE USED. SIZE & THICKNESS OF
 MATERIAL USED.2504.5.1/ ASTM C 754.
  
 14)1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 15) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 16) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A)TRUSS ANCHOR SCHEDULE
 B) ROOFING ASSEMBLIES- THE REFRENCED
 ROOF TILE BY ARCHITECT DOES NOT
 MATCH SUBMITTAL
  
 17) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-10-27 Cont ID  
Sent By btrobaug Date 2006-10-27 Time 14:59 Rev Time 0.75
Received By btrobaug Date 2006-10-27 Time 15:46 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-10-20 Cont ID  
Sent By btrobaug Date 2006-10-20 Time 13:42 Rev Time 0.33
Received By btrobaug Date 2006-10-20 Time 13:15 Sent To PC
Notes
2006-10-20 13:42:00 
  
 REVISION DENIED/INCOMPLETE
  
  
 THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK MUST
 SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 FAC.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-07-20 Cont ID  
Sent By dpalmer Date 2005-07-20 Time 10:11 Rev Time 0.50
Received By dpalmer Date 2005-07-20 Time 10:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-04-20 Cont ID  
Sent By dpalmer Date 2005-04-20 Time 17:32 Rev Time 2.00
Received By dpalmer Date 2005-04-20 Time 15:33 Sent To  
Notes
2005-04-20 00:00:00********** UNSAT 3RD REVIEW **********
  
 PLEASE SEE COMMENTS FROM PREVIOUS TWO
 REVIEWS WHICH STILL NEED TO BE ADDRESSED
 FOR CODE COMPLIANCE.
  
  
 PLEASE SEE NOTES TAKEN DIRECTLY IN
 NUMBERED ORDER FROM PREVIOUS TWO
 REVIEWS.
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 NO. PLEASE SEE 424.3B
 FOR SIZING OF AHU'S, PLEASE SEE 5KW HEAT
 STRIPS ON 60A OCP . PLEASE ALSO SEE #8
 AWG.310.16, 240.4 ETC.
 PLEASE SEE MORE THAN ONE AHU SHOWN FOR
 UNIT #2.
 PLEASE SEE LOAD CALCULATIONS FOR AHU'S
 IN UNIT #2.
  
 3)NOTE: NOTE#3, NO. PLEASE SEE NEXT NOTE
 FOR LOAD CALCS.
  
 4)NOTE: NOTE #4 NO. SEE PREVIOUS NOTES.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE FEEDERS
 FOR UNITS. PLEASE CORRELATE AND PLEASE
 SEE 310.16,240.4B ETC.
  
 7)NOTE: NOTE #7 NO, PLEASE SE PLANS
 STILL ONLY SHOW ONE SMALL APPLIANCE.
 220.16,210.1C1,210.52B1
  
 8)NOTE: NOTE #8 NO, SEE PREVIOUS NOTES.
  
 9)NOTE: NOTE #9OK.
  
 10)NOTE: NOTE #10 NO, SEE PREVIOUS
 NOTES.
  
 11)NOTE: NOTE #11 NO, SEE PREVIOUS
 REVIEWS.
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE #13 OK, ADDED NOTE.
  
 14)NOTE: NOTE #14 NO, SEE PREVIOUS
 NOTES.
  
 15)NOTE: NOTE #15 OK.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 OK.
  
 19)NOTE: NOTE #19 OK.
  
 20)NOTE: NOTE #20 OK.
  
 21)NOTE: NOTE #21 NO, PLEASE SEE A NOTE
 WAS ADDED FOR CLEARENCE FOR A/C DISC'S
 TO BE 30", HOWEVER, PLEASE SEE MIN PER
 110.26.
 PLEASE SEE WALL ARE STILL SHOWN ON PLANS
 CONFINING DISC'S.
  
 ALSO NOTE FROM PREVIOUS REVIEW #2.
  
 1)NOTE: PLEASE SEE A NOTICE WAS GIVEN
 WITH RESPECT TO DESIGN PROFESSIONAL AND
 FS 553.80(2)(B). PLEASE SEE THAT NOTICE
 WAS GIVEN TO NOTIFY DESIGN PROFESSIONAL
 IF PLANS COME BACK WITH ANY OF THE SAME
 COMMENTS FOR CODE COMPLIANCE NOT
 ADDRESSED THAT A 4X FEE FOR PLAN REVIEW
 PORTION OF PERMIT FEE SHALL BE ACCESSED.
 THIS IS A REQUIRED FEE UNDER FS AND IS
 NOW ACCESSED. PLEASE SEE NUMEROUS
 COMMENTS FROM PREVIOUS TWO REVIEWS WERE
 NOT ADDRESSED.
 PLEASE SEE A FEE OF $6792.00 HAS NOW
 BEEN ATTACHED AND THIS FEE MUST BE PAID
 BEFORE RESUBMITTING PLANS. THIS IS
 REQUIRED UNDER FS 553.80(2)(B).
 PLEASE BE AWARE THE COPY OF ABOVE FS IS
 ATTACHEDONCE AGAIN.
  
 **PLEASE SEE ONE SET OF THE ELECTRICAL
 PLANS ARE BEING RETAINED FOR FILE.
 PLEASE SEE THESE MAY BE SENT TO THE
 BOARD OF ARCH'S FOR REVIEW.
  
 2)NOTE: PLEASE PROVIDE A COMPLETE
 CONTRACT SHOWING VALUATION FOR COMPLETE
 ELECTRICAL WORK AS SET FORTH ON PLANS.
 PLEASE SEE LOCAL ADMINISTRATIVE CODE/FBC
 104.6.5.
 PLEASE SEE FS 471.003, IF VALUE FOR
 ELECTRICAL SCOPE OF WORK IS $50K OR
 MORE, PLANS WILL BE REQUIRED TO BE DONE
 BY A PROFESSIONAL ENGINEER.
  
 3)NOTE: PLEASE SEE ONE SETOF PLANS
 HAVE MANY OF THE ABOVE REDLINED AT
 LOCATIONS OF COMMENTS ONCE AGAIN.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETSFOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-01-26 Cont ID  
Sent By dpalmer Date 2005-01-26 Time 13:32 Rev Time 1.00
Received By dpalmer Date 2005-01-26 Time 13:32 Sent To  
Notes
2005-01-26 00:00:00*********** UNSAT 2ND REVIEW *********
  
 PLEASE SEE MANY OF THE NOTES FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
  
 1)NOTE: NOTE #1 OK, ADDRESSED W/NOTE.
  
 2)NOTE: NOTE #2 NO, SEE 424.3B
  
 3)NOTE: NOTE #3 YES, HOWEVER LOAD CALCS
 FOR PANEL "D" ARE NOT PER 220 FOR
 COMMERICAL SPACE. PLEASE SEE NOTE# 4
 FROM PREVIOUS REVIEW.
 ***NEW***
 PLEASE SEE NOTE THAT LOAD CALCS HAVE
 BEEN SUBMITTED, PLEASE CORRELATE VOLTAGE
 AND LOAD CALCS FROM PANEL SCHEDULES TO
 LOADS ON RISER DIAGRM.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE PREVIOUS
 NOTE.
  
 5)NOTE: NOTE #5, ? PANEL CH SEEMS TO NOW
 BE PANEL "D"> NO COMMENT.
  
 6)NOTE: NOTE #6 NO, SEE PREVIOUS
 COMMENTS. #2 STILL SHOWN ON OCP TOO HIGH
 FOR RATING OF AWG ETC.
  
 7)NOTE: NOTE #7 NO. SEE PREVIOUS NOTE.
  
 8)NOTE: NOTE #8 NO. SEE PREVIOUS NOTE.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 NO SEE PREVIOSU NOTE.
  
 11)NOTE: NOTE #11 NO? SEE LOAD CALCS.
 SEE 240.4B
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE #13 NO, SEE PREVIOUS NOTES
 ABOUT NOTE #21.
  
 14)NOTE: NOTE #14 NO, SEE PREVIOUS.
  
 15)NOTE: NOTE #15 OK.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 ? ADDED AS NOTE,
 INSTEAD OF PANEL SCHEDULE AS PREVIOUS
 REQUEST.
  
 18)NOTE: NOTE #18 OK
  
 19)NOTE: NOTE #19 NO, SEE PREVIOUS
 NOTES.
  
 20)NOTE: NOTE #20 OK.
  
 21)NOTE: NOTE #21 NO, UNCLEAR, PLEASE
 ADD NOTE FOR CLEARENCE OF DISC'S PER
 110.26.
  
 **** NEW NOTE****
  
 1)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B). PLEASE SEE IF PLANS COME
 BACK WITH ANY OF THE SAME COMMENTS FROM
 TWO PREVIOUS REVIEWS NOT ADDRESSED, A 4X
 FEEFOR PLAN REVIEW PORTION OF PERMIT
 MUST BE ACCESSED PER FS. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD PLANS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-19 Cont ID  
Sent By dpalmer Date 2004-11-19 Time 06:39 Rev Time 1.25
Received By dpalmer Date 2004-11-19 Time 06:39 Sent To  
Notes
2004-11-19 00:00:00*********** UNSAT ************
  
 PLEASE SEE SOME OF THE NOTES FROM
 REVIEW
 UNDER PERMIT #03011199 ARE THE SAME.
  
  
 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO
 BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SEE OCP FOR AHU'S PER
 424.3B, CLUBHOUSE UNIT. PLEASE ALSO SEE
 50A OCP FOR UNIT #3 FOR A 5KW UNIT.?
 PLEASE CORRELATE SIZES OF ALL A/C UNITS
 WITH MECHANICAL PLANS.
  
 3)NOTE: PLEASE SEE ALL PANEL SCHEDULES
 DO NOT INCLUDE LOAD INFORMATION AT THE
 BOTTOM.?
 215.5
  
  
 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE INDICATE WITH THE MIXED USE.
 NO LOAD CALCS SHOWN FOR CLUBHOUSE
 PANEL?
 215.5
  
 5)NOTE: PLEASE IDENTIFY CH PANEL.
  
 6)NOTE: PLEASE CORRELATE OCP ON METER
 CENTER AND ALL PANELS. SOME SHOW 150A,
 100A PANELS ALL WITH 200A BREAKERS
 FEEDING THEM??
 310.16,240.4B
 PLEASE ALSO SEE #2 AWG ON 200A BRKR. #2
 PER 310.16 IS RATED AT 115A'S??
  
 7)NOTE: PLEASE SEE THERE IS ONLY ONE
 SMALL APPLIANCE LOAD ON PANEL SCHEDULE?
 PLEASE SEE TWO MIN AS INDICATE IN LOAD
 CALCS FOR UNITS. 220.16,210.11C1,
 210.52B1
  
 8)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL
 SCHEDULES.
 PLEASE SEE SD'S ETC.OUTSIDE LTS?
 PLEASE SEE CIRCUITING FOR CU FOR
 CLUBHOUSE, DOES NOT CORRELATE W/ PANEL
 SCHEDULE. SHOWN ON TWO DIFFERENT SIDES
 OF THE PANEL.
  
 9)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPT ON 2' OF WALL, UNIT #1
  
 10)NOTE: PLEASE SEE CIRCUITING FOR
 DINING RM RECEPTS.210.52B1, 220.16
  
 11)NOTE: PLEASE SEE SEC'S TO BE SIZED
 PER 310.16, 240.4B
  
 12)NOTE: PLEASE SEE 250.50, THIS ALSO
 REQUIRES FOOTER STEEL. RISER INDICATES
 BLDG STEEL?
  
  
 13)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
 PLEASE SEE NOTE#21 ON PLANS. PLEASE
 ADJUST.
  
 14)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS.PLEASE ALSO
 ADJUST PANEL SCHEDULE.
  
 15)NOTE: PLEASE INCLUDE ALL INFORMATION
 ON TITLE BLOCK AS REQUIRED UNDER FAC
 61G1-16.004.
 PLEASE SEE THAT THIS IS REQUIRED ON ALL
 SHEETS WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWER(S).
 PLEASE SEE FBC 104.2.1 FOR ALL PLANS,
 INCLUDING MECHANICAL.
  
 16)NOTE: PLEASE SEE SOME PANEL
 SCHEDULES INDICATE PANEL LOCATIONS AS
 BEING A"GARAGE"? HOWEVER , COULD NOT
 LOCATE ANY GARAGES ON PLANS? MISPRINT??
  
  
 17)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE(S). PER 210.52D, 210.11C3
 MUST BE 20A #12
  
 18)NOTE: PLEASE SHOW LOCATION OF CH
 PANEL ON PLANS. THIS COULD NOT BE
 LOCATED.
  
 19)NOTE: PLEASE SEE SOME LTS ARE SHOWN
 ON PLANS ON THE SAME SWITCH LEG,HOWEVER
 THEY ARE ON TWO SEPARATE CIRCUITS??
 THIS WILL NOT WORK, THESE MUST BE ONTHE
 SAME CIRCUIT OR SEPARATE SWITCHES.
  
 20)NOTE: PLEASE SEE WF/WATER COOLER IS
 SHOWN ON GEN LT CIRCUIT. PLEASE VERIFY
 THISAS IT MAY BE REQUIRED TO BE ON A
 SEPARATE CIRCUIT.
  
 21)NOTE: PLEASE SHOW CLEARENCE FOR A/C
 DISCONNECTS PER 110.26
  
 22)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD SHEETS
 FOR REFERENCE ONLY.
  
 23)NOTE: PLEASE SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWERS WHICH MAY
 HAVE AN AFFECT ON ELECTRICAL PLANS.
 PLEASE SEE ANY FIRE REVIEW COMMENTS.
  
 PLEASE SEE ONE SET HAS MOST OF THE
 ABOVE COMMENTS REDLINED IN THE AREAS AS
 NOTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-01-13 Cont ID  
Sent By mamini Date 2006-01-13 Time 10:50 Rev Time 0.50
Received By mamini Date 2006-01-13 Time 10:50 Sent To B
Notes
2006-01-13 00:00:00PASSED:
  
 1. REVIEWED FOR REVISION.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-01-21 Cont ID  
Sent By mamini Date 2005-01-21 Time 10:08 Rev Time 0.50
Received By mamini Date 2005-01-21 Time 10:08 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-11-17 Cont ID  
Sent By mamini Date 2004-11-17 Time 15:00 Rev Time 0.00
Received By dpalmer Date 2005-07-20 Time 10:11 Sent To  
Notes
2004-11-17 00:00:00FAILED:
  
 1. PLEASE NOTE THAT CIVIL' PLAN SHEETS
 MUST HAVE THE ORIGINAL RAISED SEAL AND
 SIGNATURE OF THE CIVIL ENGINEER OF THE
 RECORD.
  
 2. PLEASE SUBMIT CIVIL PLANS TO PUBLIC
 UTILITIES & ENGINEERING FOR APPROVAL OF
 ALL THE CONNECTIONS TO THE CITY
 SERVICES, ATT:MANNY GONZALEZ, 494-1085.
  
 3. EROSION/SEDIMENTATION CONTROL
 DEVICES MUST BE INSTALLED IN FIELD
 PRIOR TO BEGINNING ANY WORK AND
 MAINTAINED DURING THE CONSTRUCTION
 ACTIVITIES.
  
 4. PLEASE VERIFY THE DIRECTION OF NORTH
 ARROWS ON ARCHITECTURAL, LANDSCAPING
 PLANS.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-07-29 Cont ID  
Sent By mwennerg Date 2005-07-29 Time 14:42 Rev Time 0.00
Received By mwennerg Date 2005-07-29 Time 14:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-04-26 Cont ID  
Sent By mwennerg Date 2005-04-26 Time 15:36 Rev Time 0.00
Received By mwennerg Date 2005-04-26 Time 15:36 Sent To  
Notes
2005-04-26 00:00:001) AN ADDRESS NUMBER IS SHOWN ON THE
 ELEVATION DRAWING. PLEASE PROVIDE THE
 REQUIREMENT OF NUMBERS THAT ARE A
 MINIMUM OF 6" IN HEIGHT AND CONTRASTING
 TO THE BACKGROUND.
  
 2) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION OF THE WALLS AND CEILING.
  
 3) THE PREVIOUS COMMENT REGARDING THE
 RANGE AND HOOD IN THE KITCHEN HAS NOT
 BEEN ADDRESSED. PLEASE BE ADVISED THAT A
 HOOD DUCT AND SUPPRESSION SYSTEM IS
 REQUIRED IF COOKING PRODUCES SMOKE OR
 GREASE LADEN VAPORS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2910 OR 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-02-08 Cont ID  
Sent By mcarsill Date 2005-02-08 Time 16:35 Rev Time 0.00
Received By mcarsill Date 2005-02-08 Time 16:35 Sent To  
Notes
2005-02-08 00:00:001. BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 2. INTERIOR FINISH CLASSIFICATIONS
 FOR WALLS AND CEILINGS IN EXITS SHALL
 BE CLASS A OR B.
  
 3. RANGE WITH HOOD IN KITCHEN WILL
 BE USED FOR WHAT. ANY COOKING THAT
 PRODUCES SMOKE OR GREASE LADEN
 VAPORS SHALL BE PROTECTED BY A HOOD,
 DUCT, AND SUPPRESSION SYSTEM.
  
 4. PLEASE SEE BUILDING PLAN REVEIWER
 NOTES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-12-16 Cont ID  
Sent By nmccray Date 2004-12-16 Time 16:27 Rev Time 0.00
Received By nmccray Date 2004-12-16 Time 16:06 Sent To  
Notes
2004-12-16 00:00:00FIRE REVIEW PLEASE REF NFPA 101 LIFE
 SAFETY CODE 2000 EDITION
  
 1) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3) BUILDING ADDRESSES ARE REQUIRED.
 COULD NOT LOCATE THEM ON ELEVATION
 DRAWINGS.
  
 4) PLEASE INDICATE THE INTERIOR WALL AND
 CEILING FINISH CLASS "A", CLASS "B", OR
 CLASS "C".
  
 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR BALCONY RAILINGS.
  
 6) STAIRS SHALL HAVE HANDRAILS ON EACH
 SIDE.
  
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 16:21 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 16:21 Sent To P
Notes
2006-09-09 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-05-15 Cont ID  
Sent By adarroug Date 2006-05-15 Time 12:52 Rev Time 0.00
Received By adarroug Date 2006-05-15 Time 12:52 Sent To P
Notes
2006-05-15 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-05-12 Cont ID  
Sent By adarroug Date 2006-05-12 Time 17:07 Rev Time 0.00
Received By adarroug Date 2006-05-12 Time 17:07 Sent To  
Notes
2006-05-12 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-26 Cont ID  
Sent By adarroug Date 2006-04-26 Time 08:26 Rev Time 0.00
Received By adarroug Date 2006-04-26 Time 08:26 Sent To M
Notes
2006-04-26 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-11 Cont ID  
Sent By adarroug Date 2005-07-11 Time 15:53 Rev Time 0.00
Received By adarroug Date 2005-07-11 Time 15:53 Sent To  
Notes
2005-07-19 00:00:00TO "COMM" BD#54
2005-07-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-06 Cont ID  
Sent By adarroug Date 2005-04-06 Time 13:19 Rev Time 0.00
Received By adarroug Date 2005-04-06 Time 13:19 Sent To  
Notes
2005-04-06 00:00:00TO "COMM" BD#53

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 12:49 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 12:49 Sent To  
Notes
2005-01-20 00:00:00TO "COMM BD#35/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-16 Cont ID  
Sent By jwitmer Date 2004-12-16 Time 14:50 Rev Time 0.00
Received By jwitmer Date 2004-11-12 Time 11:36 Sent To  
Notes
2004-11-12 00:00:00TO COMM BD#18

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-06-05 Cont ID  
Sent By hmoser Date 2006-06-05 Time 10:22 Rev Time 0.00
Received By hmoser Date 2006-06-05 Time 10:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-05-22 Cont ID  
Sent By tgordon Date 2006-05-22 Time 14:51 Rev Time 0.30
Received By tgordon Date 2006-05-22 Time 14:51 Sent To B
Notes
2006-05-22 00:00:00REVISION TO MECH. PLANS PAGE M-1, M-2,
 M-3.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-04-27 Cont ID  
Sent By tgordon Date 2006-04-27 Time 14:48 Rev Time 1.30
Received By tgordon Date 2006-04-27 Time 14:48 Sent To  
Notes
2006-04-27 00:00:00*** DENIED ***
 1) DUCTS GOING THRU THE FIRE RATED WALL
 IN THE FILE STOR. ROOM MUST BE METAL
 WITH FIRE DAMPERS, PER 2004 FBC/M
 607.5.3 SEE ATTACHED A-2 .
  
 2) DUCTS GOING THRU THE FIRE RATED WALL
 FROM LIVING ROOM #3 TO DINING ROOM MUST
 BE METAL WITH FIRE DAMPERS, SEE ATTACHED
 A-3 .
  
 3) PLEASE EXPLAIN RETURN AIR FOR GROUND
 FLOOR PG. M-2AHU #1 & # OVER BATHROOMS
 IS THAT TO BE A ENCLOSED WALL AROUND FOR
 A PLENUM OR IS THE ENTIRE FIRST FLOOR
 ATTIC THE PLENUM.
  
 4) PAGE M-2 GROUND FLOOR, MOST RETURN
 AIR TRANSFER DUCTS ARE UNDRE SIZED, SEE
 NOTE #5(A).
  
 5) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-07-26 Cont ID  
Sent By pkrauss Date 2005-07-26 Time 19:55 Rev Time 1.00
Received By pkrauss Date 2005-07-26 Time 19:36 Sent To  
Notes
2005-07-26 00:00:00PROVISO:
 BI-FOLD DOORS TO THE AHU CLOSETS SHALL
 BE NON-COMBUSTIBLE IN ACCORDANCE WITH
 2001 FBC(M)602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2005-05-03 Cont ID  
Sent By pkrauss Date 2005-05-03 Time 09:28 Rev Time 1.45
Received By pkrauss Date 2005-04-29 Time 14:32 Sent To  
Notes
2005-04-29 00:00:00DENIED:3RD REQUEST
 1.PROVIDE DDETAIL FOR PENETRATIONS -
 RESPONSE IS TO REFERENCE A4 OF A5, PLAN
 SHEET A5 INDICATES PENETRATION FOR
 "CABLES" BUT NO DETAIL FOR THE FIRE
 DAMPERS.PLEASE NOTE FIRE DAMEPRS ARE
 MISSING FOR DUCTS PENETRATING RATED WALL
 FROM THE FILE ROOM INTO THE
 "MULTI-PURPOSE" ROOM.PLEASE NOTE FLEX
 DUCT IS PROHIBITED FROM PENETRATING A
 RATED WALL, 2001 FBC(M)603.5.5.
  
 2.OUTSIDE AIR CALCULATIONS ACCORDING
 TO THE RESPONSE ARE NOTED ON PLAN SHEET
 M1.NO O.A. CALUCALTIONS INIDCATED.
 PROVIDE O.A. CALCS FOR THE COMMON AREAS
 AS WELL AS THE RESIDENCE.
  
 4. INDICATE O.A. DUCT SIZE, MATERIAL,
 LAYOUT AND INTAKE.
  
 5.RETURN AIR JUMPERS WERE NOT
 INCREASED TO 1 1/2 TIMES THE SQUARE
 INCHES OF THE SUPPLY AIR.
  
 7.DUCT SMOKE DETECTOR IS NOT INDICATED
 ON THE PLAN.
  
 8.PROVIDE SUBMITTAL FOR THE HOOD,
 EXHAUST SHALL NOT TERMINATE ONTO
 WALKWAYS.RESPONSE INDICATES
 TERMINATION TO EXTERIOR WALL BUT IS NOT
 IDENTIFIED ON THE PLAN.MECHANICAL PLAN
 CONFLICTS WITH THE ELECTRICAL PLAN.THE
 1ST FLOOR KITCHEN AREA SHOWS A MICROWAVE
 OVEN ON THE ELECTRICAL PLAN & A RANGE
 W/HOOD ON THE MECHANICAL PLAN.PLEASE
 CLARIFY.
  
 9.EQUIPMENT SCHEDULE NOT GIVEN FOR THE
 EXHAUST FANS.
  
 10.LOCATION OF THE AHU ON THE FIRST
 FLOOR.PLEASE NOTE RETURN AIR DUCT
 SHALL BE DUCTED INTO THE AHU IN THIS
 FIRE RATED ROOM.WHY WOULD THE AHU BE
 LOCATED IN THE ONLY "FIRE RATED" ROOM IN
 THE BUILDING?
  
 11.LINE SIZES FOR THE LIQUID, SUCTION
 AND CONDENSATE ARE NOT INDICATED.
  
 12 & 13. CONDENSATE TERMINATION IS NOT
 INDICATED.
  
 NEW COMMENT:
 PLAN SHEET A-2 INDICATED BUILDING
 CATEGORY AS R-3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-02-03 Cont ID  
Sent By pkrauss Date 2005-02-03 Time 15:41 Rev Time 1.00
Received By pkrauss Date 2005-02-03 Time 14:56 Sent To  
Notes
2005-02-03 00:00:00DENIED:
 PLEASE NOTE COMMENTS NOT ADDRESSED FROM
 PREVIOUS REVIEW DATED 12-4-04.PROVIDE
 A RESPONSE LETTER TO COMMENTS TO HELP
 EXPEDITE PLANS.
  
 2ND REQUEST:
 1.PROVIDE DETAIL FOR PENETRATIONS
 THROUGH RATED ASSEMBLIES.
  
 2.PROVIDE OUTSIDE AIR CALCULATIONS
 PER 2001 FBC(M) TABLE 403.3 OR 402.
 PROVIDE CALCULATIONS FOR ALL AREAS,
 COMMON AND RESIDENTIAL.
  
 4.PROVIDE OUTSIDE AIR INTAKE, DUCT
 LAYOUT, SIZE AND MATERIAL.
  
 5.RETURN AIR JUMPERS SHALL BE A
 MINIMUM OF 1 1/2 TIMES THE SQUARE
 INCHES OF THE SUPPLY AIR INTO THAT
 SPACE.ALL AIR INTO THE MASTER SUITE IS
 TO BE INCLUDED PER 2001 FBC(M)601.4
 EXCEPTION #1 & 3.
  
 6.INDICATE VENTILATION FOR THE
 STORAGE
 AREA ON THE SECOND FLOOR IN ACCORDANCE
 WITH 2001 FBC(M) TABLE 403.3.PLEASE
 INDICATE WHAT WILL BE STORED IN THE
 STORAGE AREA.
  
 7.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS REQUIRED.2001
 FBC(M)606.2.1 & 606.4.1 #2.
  
 8.PROVIDE SUBMITTAL FOR THE HOOD TO
 THE RANGE & HOOD INDICATED ON THE 1ST
 FLOOR KITCHEN.PLEASE NOTE, EXHAUST
 SHALL NOT TERMINATE ONTO THE WALKWAY.
  
 9.PROVIDE EQUIPMENT SCHEDULE FOR THE
 ALL OF THE EXHAUST FANS.
  
 10. IDENTIFY LOCATION OF THE AHU ON THE
 FIRST FLOOR.
  
 11. INDICATE LINE SIZE FOR THE LIQUID,
 SUCTION AND CONDENSATE LINES.
  
 12. CONDENSATE TO TERMINATE A MINIMUM
 OF
 12" AWAY FROM THE BUILDING STRUCTURE
 PER
 2001 FBC(M)1503.4.4.
  
 13. INDICATE TERMINATION OF ALL
 CONDENSATE LINES.CONDENSATE FROM THE
 7.5 TON SYSTEM ON THE 1ST FLOOR SHALL
 TERMINATE INTO THE STORM OR AN APPROVED
 DRYWELL PER CITY CODE SEC.90-125 (5).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-04 Cont ID  
Sent By pkrauss Date 2004-12-04 Time 09:55 Rev Time 1.20
Received By pkrauss Date 2004-12-04 Time 09:33 Sent To  
Notes
2004-12-04 00:00:00DENIED:
 1.PROVIDE DETAIL FOR PENETRATIONS
 THROUGH RATED ASSEMBLIES, I.E.
 CEILING/FLOOR & WALL.
  
 2.PLAN DOES NOT INDICATE LOCATION
 AND
 DETAIL OF FIRE DAMPERS AS REQUIRED PER
 2001 FBC(M)607.6.
  
 3.PROVIDE OUTSIDE AIR CALCULATIONS
 PER
 2001 FBC(M) 403.3.PROVIDE CALCS FOR
 RESIDENTIAL AND COMMERCIAL AREA.
  
 4.INDICATE OUTSIDE AIR INTAKE, DUCT
 LAYOUT, SIZE AND MATERIAL.
  
 5.RETURN AIR JUMPERS SHALL BE A
 MINIUM
 OF 1 1/2 TIMES THE SQUARE INCHES OF THE
 SUPPLY AIR INTO THAT SPACE.
  
 6.INDICATE MINIMUM VENTILATION FOR
 THE
 STORAGE AREA INDICATED ON THE 2ND
 FLOOR.
  
 7.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR THE 1ST FLOOR 7.5 TON
 UNIT.
 INDICATE LOCATION OF DUCT SMOKE
 DETECTOR.
  
 8.NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS REQUIRED FOR
 DUCT SMOKE DETECTORS PER NFPA 90A.
  
 9.PROVIDE SUBMITTAL FOR THE
 RANGE/HOOD
 INDICATED ON THE 1ST FLOOR COMMON AREA
 KITCHEN.
  
 10. PLANS ARE TO BE SIGNED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN PER CITY
 AMENDMENTS TO THE 2001 FBC 104.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-09-21 Cont ID  
Sent By pschmitz Date 2006-09-21 Time 13:49 Rev Time 0.00
Received By pschmitz Date 2006-09-21 Time 13:48 Sent To PC
Notes
2006-09-21 00:00:00REVISION SANITARY ISOMETRIC.
 APPROVED

Review Stop P PLUMBING
Rev No 5 Status F Date 2006-05-27 Cont ID  
Sent By pschmitz Date 2006-05-27 Time 10:55 Rev Time 0.00
Received By pschmitz Date 2006-05-27 Time 10:55 Sent To PC
Notes
2006-05-27 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
  
 UNSAT
 1) ALL REVISIONS TO PLANS SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINER, SHALL
 BE SIGNED AND SEALED BY THAT ARCHITECT
 OR ENGINEER.
  
 END OF COMMENTS QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-08-01 Cont ID  
Sent By kstevens Date 2005-08-01 Time 09:44 Rev Time 1.50
Received By kstevens Date 2005-08-01 Time 09:44 Sent To  
Notes
2005-08-01 00:00:00PASSED/PROVISO
  
 3/4" REQUIRED TO EACH HEATER.
 AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE.
 A FULL OPEN VALVE IS REQUIRED ON THE
 WATER DISTRIBUTION SUPPLY PIPE AT THE
 ENTRANCE TO THE STRUCTURE.
 SECOND FLOOR WATER RISER SHALL BE
 UPSTREAM OF VALVE TO WATER HEATER FIRST
 FLOOR.
 A FULL OPEN VALVE IS REQUIRED ON THE
 ENTRANCE TO EVERY WATER SUPPLY PIPE TO
 EVERY DWELLING UNIT & ON THE WATER
 SUPPLY PIPE TO EVERY WATER HEATER.
 606.1(5) & (7).
 A FULL OPEN VALVE IS REQUIRED ON THE
 BASE OF THE WATER RISER. 606.1(3).
 KITCHEN SINK HEIGHT 11-44.24.2 AND KNEE
 CLEARANCE 11-4.24.3 SHALL COMPLY.

Review Stop P PLUMBING
Rev No 3 Status F Date 2005-04-27 Cont ID  
Sent By kstevens Date 2005-04-27 Time 17:07 Rev Time 1.25
Received By kstevens Date 2005-04-27 Time 17:07 Sent To  
Notes
2005-04-27 00:00:00 
 DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA STATUTES
  
 A) FROM PREVIOUS REVIEWS:
 1) SHT A-2 KITCHEN SINK SHALL COMPLY
 WITH SECTION 4.24 ALL ALL SUBMSECTIONS.
 PLEASE SUBMIT A DETAIL. THE FOLLOWING
 INFORMATION IS STILL REQUIRED:
 A) HEIGHT 11-4.24.2
 B) CLEAR FLOOR SPACE 11-4.24.5 SHALL BE
 PROVIDED TO ALLOW FORWARD APPROACH AND
 SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH
 THE SINK. (FIG. 32)
 C) EXPOSED PIPES & SURFACES 11-4.24.6
 D) FAUCETS 11-4.24.7
 4) SUBMIT A WATER RISER DIAGRAM REQUIRED
 BY SECTION 104.3.1.1. SHOW ALL PIPE
 SIZES.
 6) THERMAL EXPANSION CONTROL IS REQUIRED
 ON ALL WATER HEATERS. SHOW ON THE DETAIL
 FOR THE W/HEATERS. SECTION 607.3.2.
 1B) FOR ACCESSIBLE TOILET ROOMS SHOW THE
 FOLLOWING INFORMATION:
 C) FLUSH CONTROLS 11-4.16.5
 F) EXPOSED PIPES & SURFACES 11-4.19.4
 H) LAV SHALL BE SHOWN A MINIMUM 15" OFF
 THE WAALL TO THE CENTERLINE OF THE
 FIXTURE TO BE CENTERED ON THE 30" OF THE
 CLEAR FLOOR SPACE.
 ******NEW COMMENTS********
 1C) HAND DRAWN CORRECTIONS TO A SIGNED,
 SEALED & DATED SET OF PLANS IS NOT
 APPROVED UNLESS EACH CORRECTIONS IS
 SIGNED & DATED BY THE ARCHITECT OF
 RECORD. - ALSO WHITE OUT IS NOT APPROVED
 FOR CHANGES ON SIGNED/SEALED DRAWINGS.
 SECTION 104.2.1.3
 2C) SEE ELECTRICAL REVIEW COMMENT
 ADDRESSING 553.80(2)(B) AND 4 X FEE
 REQUIRED TO BE PAID PRIOR TO
 RESUBMITTING PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-02-14 Cont ID  
Sent By kstevens Date 2005-02-14 Time 17:21 Rev Time 0.66
Received By kstevens Date 2005-02-14 Time 17:21 Sent To  
Notes
2005-02-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 A) FROM PREVIOUS REVIEW:
 1) SHT A-2 KITCHEN SINK SHALL COMPLY
 WITH SECTION 4.24 AND ALL SUBSECTIONS.
 PLEASE SUBMIT A DETAIL. NO SUBMITTAL HAS
 BEEN SUBMITTED.
 2) SHT A-2 DRINKING FOUNTAIN SHALL
 COMPLY WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS. SUBMIT A DETAIL. ALSO SHOW
 COMPLIANCE WITH SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING. NO SUBMITTAL HAS
 BEEN SUBMITTED.
 3) TABLE 403.1 AUTOMATIC CLOTHES WASHER
 CONNECTIONS ARE REQUIRED. SHOW ON THE
 FLOOR PLAN, SANT. RISER DIAGRAM AND THE
 WATER RISER DIAGRAM. NOT ADDRESSED.
 4) SUBMIT A WATER RISER DIAGRAM REQUIRED
 BY SECTION 104.3.1.1. SHOW ALL PIPE
 SIZES, VALVES AND WATER HAMMER ARRESTORS
 PER SECTION 606 & 604.9. NOT ADDRESSED.
 6) THERMAL EXPANSION CONTROL IS REQUIRED
 AT ALL WATER HEATERS PER SECTION
 607.3.2. SUBMIT A HEATER DETAIL SHOWING
 COMPLIANCE.
 8) PLEASE NOTE THAT MOST OF THESE
 COMMENTS WERE STATED IN THE REVIEW OF
 PERMIT NUMBER 03011199.
 *************NEW COMMENTS*********
 1B) FOR ACCESSIBLE TOILET ROOM SHOW THE
 FOLLOWING INFORMATION:
 A) CLEAR FLOOR SPACE 11-4.16.2
 B) GRAB BARS PER FIG 29. 11-4.16.4
 C) FLUSH CONTROLS 11-4.16.5
 D) HEIGHT & CLEARANCES 11-4.19.2
 E) CLEAR FLOOR SPACE 11-4.19.3
 F) EXPOSED PIPES & SURFACES 11-4.19.4
 G) TOILETS SHALL BE 18" FROM THE
 CENTERLINE OF THE FIXTURE TO THE WALL.
 FIGURE 28.
 H) LAV SHALL BE MINIMUM 15" FROM THE
 CENTERLINE OF THE FIXTURE TO THE WALL.
 SHALL BE CENTERED ON THE 30" OF THE
 CLEAR FLOOR SPACE.
 2B) SHT A-3 SANITARY RISER DIAGRAM, THE
 TUBS IN ALL UNITS ARE NOT VENTED AS
 SHOWN. SECTION 901.2.1.
 3B) DRAWINGS SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A
 WHOLE OR IN PART, NOR SHALL THE TERM
 "LEGAL" OR ITS EQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION.
 SECTION 104.2.1.
 4B) SEE SHEET ATTACHED TO BUILDING PLAN
 REVIEWER'S NOTES CONCERNING DESIGN
 PROFESSIONAL & FS 553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-11 Cont ID  
Sent By kstevens Date 2004-12-11 Time 17:43 Rev Time 1.50
Received By kstevens Date 2004-12-11 Time 17:43 Sent To  
Notes
2004-12-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 KITCHEN SINK SHALL COMPLY
 WITH SECTION 4.24 AND ALL SUBSECTIONS.
 PLEASE SUBMIT A DETAIL.
 2) SHT A-2 DRINKING FOUNTAIN SHALL
 COMPLY WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS. SUBMIT A DETAIL. ALSO SHOW
 COMPLIANCE WITH SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 3) TABLE 403.1 AUTOMATIC CLOTHS WASHER
 CONNECTIONS ARE REQUIRED. SHOW ON THE
 FLOOR PLAN, SANT. RISER DIAGRAM AND THE
 WATER RISER DIAGRAM.
 4) SUBMIT A WATER RISER DIAGRAM REQUIRED
 BY SECTION 104.3.1.1. SHOW ALL PIPE
 SIZES, VALVES AND WATER HAMMER ARRESTORS
 PER SECTION 606 & 604.9.
 5) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
 6) THERMAL EXPANSION CONTROL IS REQUIRED
 AT ALL WATER HEATERS PER SECTION
 607.3.2
 7) SECTION 909.1 THE KITCHEN SINK SHALL
 NOT DRAIN THROUGH THE WET-VENTED
 HORIZONTAL DRAIN OF THE BATHROOM
 FIXTURES. THE KITCHEN SINKS SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM
 FIXTURES.
 8) PLEASE NOTE THAT MOST OF THESE
 COMMENTS WERE STATED IN THE REVIEW OF
 PERMIT NUMBER 03011199.
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-12-15 Cont ID  
Sent By mmclean Date 2004-12-15 Time 15:31 Rev Time 0.00
Received By mmclean Date 2004-12-15 Time 15:31 Sent To  
Notes
2004-12-15 00:00:00RETURNED TO COMMERCIAL BOARD #18


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved