Plan Review Details - Permit 04110604
Plan Review Stops For Permit 04110604
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-02 Cont ID  
Sent By dpalmer Date 2005-09-02 Time 16:33 Rev Time 0.30
Received By dpalmer Date 2005-09-02 Time 16:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-12-16 Cont ID  
Sent By dpalmer Date 2004-12-16 Time 16:45 Rev Time 1.00
Received By dpalmer Date 2004-12-16 Time 16:45 Sent To  
Notes
2004-12-16 00:00:00*********** PROVISO/REVISION **********
  
 1)NOTE: PLEASE REVISE RISER TO INCLUDE
 NEW PANEL AT MAIN HOUSE.
 PLEASE SEE 225.31 FOR MCB REQUIRED AT
 DETACHED BLDG.
 PLEASE SEE 250.32 FOR GROUNDING AT
 DETACHED BLDG.
  
 2)NOTE: PLEASE SEE SEC'S TO BE INCREASED
 TO 250 MCM PER 310.15B6, 240.4B
  
 3)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250.66 (#2).
  
 PLEASE REVISE PLANS ALONG WITH ANY OTHER
 REVISIONS BEFORE ROUGH.
 IF THERE ARE ANY QUESTIONS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-15 Cont ID  
Sent By dpalmer Date 2004-12-15 Time 13:50 Rev Time 0.50
Received By dpalmer Date   Time   Sent To PC
Notes
2004-12-15 00:00:00*** ON HOLD ***
  
 PLANS UNDER "L" ON HOLD WAITING FOR
 INFORMATION FROM BOARD OF ARCH'S ON
 TITLE BLOCK AND LICENSURE FOR MPERRY
 DESIGN INC.
  
 FS 481.223
 481.219
 FAC 61G1-16.004
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-22 Cont ID  
Sent By dpalmer Date 2004-11-22 Time 10:43 Rev Time 0.70
Received By dpalmer Date 2004-11-22 Time 10:43 Sent To  
Notes
2004-11-22 00:00:00************ UNSAT ***********
  
 1)NOTE: PLEASE SHOW LOCATION OF
 SERVICE.
 PLEASE SEE PLANS DO NOT INDICATE IF
 THESE BLDGS ARE ATTACHED OR DEATCHED?
 IF DETACHED PLEASE INCLUDE COMPLETED
 RISER DIAGRAM SHOWING ALL SERVICE
 EQUIPMENT. PLEASE SEE 225.31,250.32 ETC
 FOR DEATCHED BLDGS.
  
  
 2)NOTE: PLEASE SHOW ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT- -ED PER 210.8A-6
  
  
 3)NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
  
 4)NOTE: PLEASE INCLUDE ALL A/C EQUIPMENT
 ON PLANS. PLEASE INCLUDE ALL DISC'S
 440.11 AND GFI RECEPT(S) PER 210.63.
  
 5)NOTE: PLEASE SEE MISSING FRONT AND
 REAR RECEPTS. 210.52E
  
 6)NOTE: PLEASE SIZE SEC'S PER 310.15B6,
 250 MCM MIN FOR 275A SERVICE. PLEASE
 ALSO SEE 240.4
  
 7)NOTE: PELASE ADJUST GEC PER 250.66.
 #2
  
 8)NOTE: PLEASE SEE 422.17 FOR WATER
 HEATERIN CLOSET. MUST HAVE SEPARATION
 FROM COMBUSTIBLES.
  
 9)NOTE:PLEASE SEE ALL PLANS/DRAWINGS,
 SHEETS MUST CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSONRESPONSIBLE FOR
 PLANS.
 FBC 104.2.1
  
 10)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 ATTACHMENTS, GRND RODS, COLD WATER?
 250.50
  
 11)NOTE: PLEASE SEE UPPER BATH RECEPT TO
 ALSO BE GFI PROTECTED.210.8
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-31 Cont ID  
Sent By adarroug Date 2005-08-31 Time 14:21 Rev Time 0.00
Received By adarroug Date 2005-08-31 Time 14:21 Sent To E
Notes
2005-08-31 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-12-09 Cont ID  
Sent By mjacobs Date 2004-12-09 Time 09:32 Rev Time 0.00
Received By mjacobs Date 2004-12-09 Time 09:32 Sent To E
Notes
2004-12-09 00:00:00SENT TO "DP" DESK./SUBMITTAL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-11-12 Cont ID  
Sent By csiegber Date 2004-11-12 Time 11:16 Rev Time 0.00
Received By csiegber Date 2004-11-12 Time 11:16 Sent To E
Notes
***NONE***