Plan Review Details - Permit 04110519
Plan Review Stops For Permit 04110519
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-01-27 Cont ID  
Sent By rmcdouga Date 2005-01-27 Time 08:54 Rev Time 0.00
Received By rmcdouga Date 2005-01-27 Time 07:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-07 Cont ID  
Sent By rmcdouga Date 2004-12-07 Time 13:02 Rev Time 0.00
Received By rmcdouga Date 2004-12-07 Time 07:24 Sent To  
Notes
2004-12-07 00:00:00DENIED
  
 1) THE ENERGY CALC. FORMS LIST R19
 INSULATION AND THE PLANS SPECIFY R30.
 PLEASE CORRECT.
  
 2) THE ENERGY CALCS DO NOT LIST THE 2X6
 EXTERIOR WALLS WITH THE RI9 INSULATION.
  
 3) THE BOTTOM OF FOOTING IS REQUIRED TO
 BE A MINIMUM OF 12" BELOW FINISH GRADE
 PER FBC 1804.1.3. REVISE WALL SECTIONS
 ON A11 AND A12.
  
 4) THE CITY OF WPB AMENDMENTS TO THE
 2001 FBC 1804.1.7 REQUIRES THE FLOOR
 ELEVATION OF A MONOLITHIC SLAB AT
 HABITABLE AREAS TO BE 4" ABOVE FINISH
 GRADE AT THE BUILDING PERIMETER.
  
 5) FBC 2504.2.1 AND ASTM C 926 REQUIRES
 EXTERIOR PORTLAND BASED CEMENT PLASTER
 (STUCCO) TO BE 5/8" THICH WHEN APPLIED
 VERTICALLY OVER METAL LATH AND 7/8"
 THICK WHEN APPLIED HORIZONTALLY ON
 METAL
 LATH OVER SOLID BASE. REVISE PLANS.
  
 6) PLEASE CLARIFY THE 4X4 WOOD POST
 (WP-1 ON S1). NOTE 7 UNDER THE
 FOUNDATION PLAN SPECIFIES A SIMPSON
 ABU 44 POST BASE AND DOESN'T SPECIFY
 THE
 FASTENERS. THE MASONRY PIER DETAIL HAS
 A
 SIMPSON EPB 44T BASE, BUT NO ID TAG.
  
 7) THE OPEN AREAS ABOVE THE LIVING
 ROOMS
 ARE NOT REFLECTED ON THE SECOND FLOOR
 FRAMING PLANS ON S1.
  
 8) THE CITY OF WPB AMENDMENTS TO FBC
 TABLE 2306.1 REQUIRES THE ROOF
 SHEATHING
 TO BE NAILED WITH 8DS AT 6"OC AT EDGES
 AND 6"OC INTERMEDIATE IN ZONES 1 AND 2
 & WITH 8D RING SHANKS AT 4" OC AT EDGES
 AND 6"OC INTERMEDIATE IN ZONE 3. REVISE
 SCHEDULE ON S3. THE DIAGRAM DOES NOT
 INDICATE ZONES FOR A GABLE ROOF.
  
 9) TRUSS LAYOUT AND DRAWINGS ARE
 REQUIRED TO HAVE THE WET SIGNATURE OF
 THE TRUSS ENGINEER PER FAC
 61G15-23.002.
  
 10) TRUSS DRAWINGS DO NOT REFLECT THE
 OPEN AREAS ABOVE THE LIVING ROOMS OF THE
 TWO STORY UNITS SHOWN ON THE FLOOR
 PLANS.
  
 11) REVISE THE TRUSS LAYOUTS TO MATCH
 THE "B" ELEVATION COLUMNS AND OTHER
 COMMENTS NOTED BY THE DESIGNER OF
 RECORD.
  
 12) THE MG1 GIRDER AT THE REAR GABLE ON
 THE TRUSS LAYOUT IS NOT INDICATED ON THE
 ARCH.PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-13 Cont ID  
Sent By dpalmer Date 2005-01-13 Time 15:24 Rev Time 0.50
Received By dpalmer Date 2005-01-13 Time 15:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-23 Cont ID  
Sent By dpalmer Date 2004-11-19 Time 09:28 Rev Time 0.75
Received By dpalmer Date 2004-11-19 Time 09:12 Sent To  
Notes
2004-11-23 00:00:00***** UNSAT *****
  
 REVIEW STATUS CHANGED DUE TO "MASTER"
 STATUSAND NOT BEING ABLE TO REDLINED
 PLANS FOR ANY ITEM.
  
  
 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 CONDUCTOR PER 250.66.
 SHOWS #2 FOR A 600A MAIN BUSS/METER
 CENTER.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-11-16 Cont ID  
Sent By mamini Date 2004-11-16 Time 10:25 Rev Time 0.50
Received By mamini Date 2004-11-16 Time 10:25 Sent To  
Notes
2004-11-16 00:00:00PASSED:
 1. SEE # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-12-14 Cont ID  
Sent By rmcdouga Date 2004-12-14 Time 13:06 Rev Time 0.00
Received By rmcdouga Date 2004-12-14 Time 13:06 Sent To  
Notes
2004-12-14 00:00:00OK PER M CARSILLO

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-17 Cont ID  
Sent By adarroug Date 2005-02-17 Time 16:48 Rev Time 0.00
Received By adarroug Date 2005-02-17 Time 16:48 Sent To E
Notes
2005-02-17 00:00:00TO DPALMER DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2005-01-06 Cont ID  
Sent By mjacobs Date 2005-01-06 Time 14:58 Rev Time 0.00
Received By mjacobs Date 2005-01-06 Time 14:58 Sent To  
Notes
2005-01-06 00:00:00TO "COMM BD#38

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-14 Cont ID  
Sent By mjacobs Date 2004-12-14 Time 13:08 Rev Time 0.00
Received By rmcdouga Date 2004-11-15 Time 14:27 Sent To  
Notes
2004-11-15 00:00:00TO COMM BD #56

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-21 Cont ID  
Sent By pkrauss Date 2005-01-21 Time 06:27 Rev Time 0.45
Received By pkrauss Date 2005-01-20 Time 16:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-12-04 Cont ID  
Sent By pkrauss Date 2004-12-04 Time 07:27 Rev Time 0.45
Received By pkrauss Date 2004-12-04 Time 06:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-01-20 Cont ID  
Sent By jleech Date 2005-01-20 Time 10:34 Rev Time 1.00
Received By jleech Date 2005-01-20 Time 10:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-12-10 Cont ID  
Sent By kstevens Date 2004-12-10 Time 13:25 Rev Time 1.25
Received By kstevens Date 2004-12-10 Time 13:25 Sent To  
Notes
2004-12-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHTS P-1 FLOOR PLAN AND P-3 SANT.
 RISER DIAGRAM UNIT A. SHOWER NOT VENTED.
 SECTION 901.2.1.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-01-26 Cont ID  
Sent By eschneid Date 2005-01-26 Time 12:00 Rev Time 0.00
Received By eschneid Date 2005-01-26 Time 11:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-12-13 Cont ID  
Sent By eschneid Date 2004-12-13 Time 15:25 Rev Time 0.50
Received By eschneid Date 2004-12-13 Time 15:00 Sent To  
Notes
***NONE***