Plan Review Details - Permit 04110518
Plan Review Stops For Permit 04110518
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-03 Cont ID  
Sent By rmcdouga Date 2005-02-03 Time 13:31 Rev Time 0.00
Received By rmcdouga Date 2005-02-03 Time 13:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-15 Cont ID  
Sent By rmcdouga Date 2004-12-15 Time 10:55 Rev Time 0.00
Received By rmcdouga Date 2004-12-15 Time 07:05 Sent To  
Notes
2004-12-15 00:00:00DENIED
  
 1) THE THICKNESS OF THE STUCCO FINISH
 OVER THE METAL LATH ON THE SOFFITS IS
 INCORRECTLY SPECIFIED AS 1/2" THICK. FBC
 2504.2.1 AND ASTM C 926 REQUIRES IT TO
 BE 5/8" APPLIED HORIZONTALLY AND 7/8"
 WHEN APPLIED VERTICALLY OVER METAL
 LATH.
  
 2) THE ENERGY CALCS. LIST R-19
 INSULATION IN THE CEILINGS AND THE PLANS
 SPECIFY R-30.
  
 3) THE 2X6 WOOD FRAME EXTERIOR WALLS
 WITH R-19 INSULATION SPECIFIED ON THE
 PLANS ARE NOT INDICATED ON THE ENERGY
 CALCS.
  
 4) ON SHEET S3 A SECTION THROUGH THE
 TENANT SEPARATION WALL OF UNITS 3 L AND
 R IS INCORRECTLY IDENTIFIED AS 8 ON S6.
  
 5) THE LOCATION OF THE COLUMNS ON SHEET
 A9 DOES NOT MATCH THOSE ON S2.
  
 6) SHEET S2 SHOWS HIP ROOFS OVER THE
 COVERED ENTRIES AT THE LEFT AND RIGHT
 SIDES. THE ELEVATIONS AND TRUSS LAYOUT
 INDICATE GABLE ROOFS.
  
 7) THE TRUSS LAYOUTS AND DRAWINGS ARE
 REQUIRED TO HAVE THE ORIGINAL WET
 SIGNATURE OF THE TRUSS ENGINEER PER FAC
 61G15-23.002.
  
 8) MAKE CORRECTIONS TO TRUSS LAYOUTS AS
 NOTED BY THE DESIGNER OF RECORD.
  
 9) THE GR01 AND GRO4 TRUSSES FOR THE
 UPPER ROOF DO NOT HAVE CONNECTORS
 SPECIFIED IN THE SCHEDULE THAT ARE
 ADEQUATE TO RESIST THE UPLIFTS SPECIFIED
 IN THE TRUSS DRAWINGS. PLEASE REVIEW
 TRUSS CONNECTOR SCHEDULE FOR REQUIRED
 RESISTANCES.
  
 10) SUBMIT THE UL TEST REPORT FOR THE
 GAF SHINGLES.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-13 Cont ID  
Sent By dpalmer Date 2005-01-13 Time 15:48 Rev Time 0.50
Received By dpalmer Date 2005-01-13 Time 15:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-19 Cont ID  
Sent By dpalmer Date 2004-11-19 Time 08:42 Rev Time 0.75
Received By dpalmer Date 2004-11-19 Time 07:54 Sent To  
Notes
2004-11-19 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON TITLE BLOCK PER
 FAC 61G15-23.002 , AS REQUIRED UNDER FS
 471.023
  
 2)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR TO BE SIZED PER 250.66
 IF SEC'S FROM FPL CAN NOT BE VERIFIED BY
 FPL, PLEASE PROVIDE NOTE FOR SIZING
 PER 250.66
 THE #2 SHOWN APPEARS TO BE TO SMALL FOR
 600A METER CENTER.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-11-16 Cont ID  
Sent By mamini Date 2004-11-16 Time 11:13 Rev Time 0.50
Received By mamini Date 2004-11-16 Time 11:13 Sent To  
Notes
2004-11-16 00:00:00PASSED:
 1. SEE # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-12-14 Cont ID  
Sent By rmcdouga Date 2004-12-14 Time 13:09 Rev Time 0.00
Received By rmcdouga Date 2004-12-14 Time 13:09 Sent To  
Notes
2004-12-14 00:00:00OK PER M CARSILLO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-11 Cont ID  
Sent By mjacobs Date 2005-01-11 Time 13:01 Rev Time 0.00
Received By mjacobs Date 2005-01-11 Time 13:01 Sent To  
Notes
2005-01-11 00:00:00TO "COMM BD#59"/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-15 Cont ID  
Sent By rmcdouga Date 2004-12-15 Time 10:56 Rev Time 0.00
Received By rmcdouga Date 2004-11-15 Time 14:23 Sent To  
Notes
2004-11-15 00:00:00TO COMM BD#59

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-01-21 Cont ID  
Sent By pkrauss Date 2005-01-21 Time 07:35 Rev Time 0.40
Received By pkrauss Date 2005-01-21 Time 06:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-12-04 Cont ID  
Sent By pkrauss Date 2004-12-04 Time 07:44 Rev Time 0.45
Received By pkrauss Date 2004-12-04 Time 07:37 Sent To  
Notes
2004-12-04 00:00:00DENIED:"MASTER 6 UNIT/B ELEV"
 SEE COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.SHOW COMPLIANCE
 WITH FS 471.023 & FAC 61G15-23.002,
 SIGNATURES 7 TITLE BLOCKS.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-12-11 Cont ID  
Sent By kstevens Date 2004-12-11 Time 09:20 Rev Time 1.00
Received By kstevens Date 2004-12-11 Time 09:20 Sent To B1
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-12-13 Cont ID  
Sent By eschneid Date 2004-12-13 Time 15:27 Rev Time 0.50
Received By eschneid Date 2004-12-13 Time 15:00 Sent To  
Notes
***NONE***