Plan Review Details - Permit 04110390
Plan Review Stops For Permit 04110390
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-23 Cont ID  
Sent By jgomez Date 2005-03-23 Time 17:39 Rev Time 2.00
Received By jgomez Date 2005-03-23 Time 17:39 Sent To  
Notes
2005-03-23 00:00:00BUILDING REVIEW PROVISO:
 PROVIDE THE FOLLOWING PRIOR TO
 INSTALLATION OR CONSTRUCTION TO AVOID
 CONFLICTS OR DELAYS:
  
 1- FLORIDA OR LOCAL PRODUCT APPROVAL FOR
 FIXED TRANSOM WINDOWS ABOVE SLIDING
 GLASS DOORS. THEY EXCEED THE MAX. SIZE
 ALLOWED ON PRODUCT APPROVAL SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-02-14 Cont ID  
Sent By jgomez Date 2005-02-14 Time 16:50 Rev Time 2.50
Received By jgomez Date 2005-02-14 Time 16:12 Sent To PC
Notes
2005-02-14 00:00:00BUILDING REVIEW CHECKLIST:
 1- EXTERIOR ELEVATIONS STILL DON'T SHOW
 THE CHIMNEY AS REQUESTED ON PREVIOUS
 CHECKLIST. AND, SPECIFY CHIMNEY HEIGHT
 AS REQ'D BY SEC. 2804.2.4 FBC 2001.
  
 2- FIREPLACESPECS SUBMITTED ARE FOR A
 42" WOOD BURNING FIREPLACE. SPECS
 CLEARLY INDICATE THAT ALTERATION OF
 THESE SPECS WILL VOID THE WARRANTY.
 PROVIDE MANUFACTURER'S CERTIFCATION THAT
 WARRANTY WILL NOT BE VOID IF CHIMNEY CAP
 IS INSTALLED AND PROVIDE COMPLETE SPECS
 FOR CAP CONSTRUCTION. EG: MATERIALS,
 CLEARANCES, COMPLETE FRAMING (INCLUDING
 CORNERS), ETC.SECTION 104.2.1.2 CITY
 AMENDEMNTS TO FBC 2001.
 **NOTE: ARCHITECT'S LETTER ALONE DOESN'T
 CLARIFY ISSUE. MANUFACTURER RESPONSE IS
 REQUIRED TO ASSURE PROPER AND SAFE
 FUNCTIONING OFFIREPLACE. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 3- ROOF FRAMING PLAN: A) ENTRY PORCH
 SHOWS INCORRECT TRUSS BEARING HEIHGT.
 SEE DETAILS E/6 AND G1 AND G2 OF A6.
 B) ENTRY PORCH ARE NOT ENGINEERED
 TRUSSES BUT WOOD BEAMS. REVISE AS REQ'D.
 C) DETAIL L/6 SHOWN ON BAY WINDOW WAS
 KEYED WRONG. IT SHOULD BE M/6.
 D) DETAIL M/6 DOESN'T MATCH ROOF FRAMING
 PLAN. ROOF FRAMING PLAN CALLS FOR
 MASONRY BEAM. DETAIL M/6 SHOW WOOD
 FRAMING. SPECIFY CORRECT CONNECTORS: WOD
 TO WOOD OR WOOD TO MASONRY AS REQUIRED.
 REVISE ROOF FRAMING PLAN AND DETAIL AS
 REQUIRED.
 E) SPECIFY FIREBLOCKING ON DETAIL M/6 AS
 REQUIRED. SEC. 2305.1 FBC 2001.
 F) HOW ARE 2X6 WOOD STUDS SPACED AT
 16"0.C TO FORM CHIMNEY AS SHOWN ON FRONT
 ELEVATION.
 G) REVISE ROOF LOADS. ROOF FRAMING PLAN
 CALLS FOR ATTIC STORAGE, THEN, NEED TO
 INCREASE ATTIC LIVE LOAD TO 30PSF AS
 REQ'D BY TABLE 1604.1 FBC 2001.
  
 4- DOUBLE ARCHED WINDOWS AT BEDROOM #2:
 A) SPECIFY HOW IS STEEL TUBE ATTACHED AT
 TOP AND BOTTOM.
 B) HOW IS 2X BLOCKING ATTACHED TO STEEL
 TUBE. SEC. 104.2.1.2 CITY AMENDMENTS TO
 FBC 2001.
  
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) FIXED WINDOWS FOR LARGER WINDOWS AS
 SHOWN ON FAMILY ROOM & LIVING ROOM.
 B) EXTERIOR SWING DOOR AT GARAGE.
  
 6- BBQ SPECS SAY "DO NOT INSTALL A GRILL
 BELOW OVERHEAD UNPROTECTED COMBUSTIBLE
 CONSTRUCTION" HOW IS THIS BBQ GOING TO
 BE INSTALLED IN THE PORCH AND FOLLOW
 MANUFACTURER SPECS.
 **NOTE: I CALLED THE MANUFACTURER AND
 THEY SAID BBQ ARE NOT INTENDED TO BE
 USED IN PORCHES. THEY SAY IS FOR
 OUTDOORS INSTALLATION ONLY.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-12-08 Cont ID  
Sent By jgomez Date 2004-12-08 Time 11:23 Rev Time 0.00
Received By jgomez Date 2004-12-08 Time 11:22 Sent To  
Notes
2004-12-08 00:00:00CHECKLIST:
 1-AREA CALCS ON SHEET A1 DON'T ADD UP
 CORRECTLY. REVISE AS REQUIRED.
  
 2-REVISE DETAILS C1 AND C2 ON SHEET A6
 TO MATCH ACTUAL CONDITIONS SHOWN ON
 ROOF
 FRAMING PLAN. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 3-PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR CANTILEVERED BEAM AT
 BREAKFAST AREA. SPECIFY HOW ARE PRECAST
 LINTELS JOINED AT THE 45 DEGREE ANGLE
 AND HOW ARE THEY ATTACHED TO THE ENDS
 TO
 TRANSFER THE ROOF LOADS TO THE COLUMNS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 4-FOUNDATION PLAN AND FLOOR PLAN DON'T
 MATCH. SEE LOCATION OF BBQ. ALSO, SHOW
 WHERE IS BBQ SUPPORTED ON?. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5-PROVIDE COMPLY SECTION/DETAIL FOR BAY
 WINDOW AT GARAGE AREA. SPECIFY ALL
 MATERIALS AND FASTENERS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 6-SHEET A3: A) REVISE ROOF SHEATHING
 NOTE. SEE FIGURE 1606.2(C) FBC 2001 AND
 CLEARLY IDENTIFY ALL ZONES CONSIDERED
 TO
 BE ZONE 3. (NOT JUST THE 4 CORNERS).
 B) REVISE ROOF LOADS CHART. SEE TABLE
 1604.1 FBC 2001.
 **NOTE: KEEP IN MIND THAT ROOF FRAMING
 PLAN CALLS FOR ATTIC STORAGE.
  
 7-PROVIDE DETAIL/SECTION FOR FRAMING AT
 DOUBLE ARCHED WINDOWS MULLED TOGETHER
 AS
 SHOWN ON BEDROOM #2. SEC. 104.2.1.2
 CITY
 AMENDMENTS TO FBC 2001.
  
 8-A) ELEVATIONS DON'T SHOW CHIMNEY.
 B) ARCHITECT TO CHECK FIREPLACE SPECS
 TO
 VERIFY IF CHIMNEY ROOF CAP IS ALLOWED
 WITHOUT INTERFERING WITH FLUE FUNCTION.
 (NOTE: SOME COMPANIES DON'T ALLOW IT).
  
 9-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) BUTT GLAZING SYSTEM AS SHOWN ON
 PLANS
 B) ENTRY DOORS.
 C) FIREPLACE UL LISTING & COMPLETE
 SPECS
 D) SIZE OF FIXED WINDOWS AS SHOWN ON
 LIVING AND FAMILY ROOM AREAS.
 E) BBQ UL LISTING AND SPECS.
  
 10-PROVIDE STORM SHUTTERS PRODUCT
 APPROVAL AND COMPLETE INFORMATION (KEY
 PLAN, INSTALLATION SCHEDULE AND
 SPECIFIC
 ANCHORS) FOR BUTT GLAZING PROTECTION.
  
 11-OWES $2378.71 FOR UPDATED VALUATION
 AND RADON FEES.
  
 12-SPECIFICATIONS ON ROOF FRAMING PLAN
 FOR CHIMNEY DON'T MATCH DETAIL/SECTION
 ON SHEET A6. REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 11:03 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 11:02 Sent To PC
Notes
2006-03-24 00:00:00REDLINED FEEDERS FOR SUB PANEL "C" TO BE
 AS SHOWN ON RISER. PANEL SCHEDULE IS NOT
 CORRECT. OK PER RISER.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-03-08 Cont ID  
Sent By dpalmer Date 2006-03-08 Time 10:36 Rev Time 0.00
Received By dpalmer Date 2006-03-08 Time 07:56 Sent To PC
Notes
2006-03-08 00:00:00REDLINED FEEDERS FOR SUB PANEL "C" TO BE
 AS SHOWN ON RISER. PANEL SCHEDULE IS NOT
 CORRECT. OK PER RISER.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-02-15 Cont ID  
Sent By dpalmer Date 2006-02-15 Time 14:46 Rev Time 0.00
Received By dpalmer Date 2006-02-15 Time 14:13 Sent To PC
Notes
2006-02-15 00:00:00REDLINED MISSING RECEPT(S) FOR 2' OF
 WALL SPACE. 210.52

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 21:05 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 20:32 Sent To PC
Notes
2006-02-03 00:00:00************ UNSAT ************
  
  
 1)NOTE:*** PLEASE KNOW, A "PROVISO" WAS
 GIVEN ON JAN 31, OF 2005 FOR PLANS AND
 LOAD CALCULATIONS TO BE REVISED ALONG
 WITH ANY OTHER REVISIONS BEFORE ROUGH.
 THIS WAS NOT DONE.
 PLEASE SEE THERE ARE MANY REVISIONS TO
 PLANS WHICH WERE NEVER SUBMITTED.
 PLANS ARE NOW ONLY COMING IN FOR
 REVISIONS ONE YEAR TO DATE.
 ** PLEASE SEE THE FOLLOWING COMMENTS AS
 SOME LOADS HAVE INCREASED, HOWEVER
 SERVICE HAS NOT.
 215.5
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM ,
 PANELS AND PLANS. PLEASE SEE PANEL "A"
 SHOWS A 2-POLE 60A BRKR FEEDING POOL
 PANEL , HOWEVER POOL PANEL IS NOW SHOWN
 AS 80A'S ON PLANS AND RISER??
 PLEASE ALSO SEE LOADS INDICATED ON PANEL
 "C" DO NOT CORRELATE WITH LOADS SHOWN ON
 PANEL "A".
 215.5
  
 3)NOTE: PLEASE SEE 220.18 FOR MIN KW
 RATING WHICH SHALL BE FIGURED FOR THE
 DRYER.
  
 4)NOTE: PLEASE SEE THAT THE MAX OCP FOR
 THE OVEN RECEPT SHALL BE 50A'S.
 PLEASE SEE OVEN IS SHOWN WIHT A RECEPT
 AND NOT HARDWIRED.
 PLEASE SEE 210.21B3
  
 4)NOTE: PLEASE CORRELATE AHU'S #1 AND #2
 KW RATINGS AS LOADS FIGURED INTO LOAD
 CALCULATIONS DO NOT MATCH WITH THE KW
 RAITNG SHOWN ON PANEL SCHEDULE(S)
 FITGURED AT 65%.
 PLEASE ALSO SEE KW RATING FOR AHU#3 DOES
 NOT CORRELATE WITH LOAD CALCULATIONS.
 215.5
  
 5)NOTE: PLEASE SEE TWO A/C COMP #1'S ARE
 SHOWN , HOWEVER A/C COMP #3 IS NOT SHOWN
 ??
 215.5
  
 6)NOTE:PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE ADJUST LOAD CALCS.
  
 7)NOTE: PLEASE SEE WHAT APPEARS TO BE A
 MISSING GFI ON KITCHEN ISLAND AS
 REQUIRED FOR ISLANDS AND SEPARATE SPACES
 SEPARATED BY SINKS ETC.
 210.52C2 AND C4.
  
 8)NOTE: PLEASE VERIFY THREE FULL SIZE
 #6'S AND #8 TO AHU'S.
 PLEASE SEEEQUIPMENT GROUNDING
 CONDUCTORS MAY BE SIZED AS SHOWN ,
 HOWEVER MAY ALSO BE SIZED PER 250.122
 IF PLANS INDICATE A #6 AND #8 FOR THE
 EQUIPMENT GRNDS, THEY WILL BE REQUIRED
 OT BE INSTALLED.
 THIS IS ONLY A NOTE:
  
 9)NOTE: PLEASE SEE CONTINUOUS LOADS
 SHALL BE FIGURED AT 125% IN PANEL
 CALCULATIONS.(POOL PUMP)
 215.3,230.42.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-01-31 Cont ID  
Sent By dpalmer Date 2005-01-31 Time 15:05 Rev Time 0.30
Received By dpalmer Date 2005-01-31 Time 14:48 Sent To P
Notes
2005-01-31 00:00:00********** PROVISO/REVISION *********
  
 210.52MISSING RECEPT IN BEDRM #5(NOTED
 ON PREVIOUS NOTES ).
  
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE ADJUST LOAD CALCS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 ALONG WITH ANY OTHER REVISIONS BEFORE
 ROUGH ELECTRICAL INSPECTION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-11-12 Cont ID  
Sent By dpalmer Date 2004-11-12 Time 22:23 Rev Time 0.30
Received By dpalmer Date 2004-11-12 Time 22:23 Sent To M
Notes
2004-11-12 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE MISSING REQUIRED
 EGRESS LT/ CONTROL BEDRM #5 210.70
  
 2)NOTE: PLEASE ALSO SEE MISSING RECEPT
 FOR 2' OF WALL SPACE. IN BEDRM 5.
 210.52
  
 3)NOTE: PLEASE MOVE SD INTO MASTER BEDRM
 AREA. PLEASE SEE NFPA-72 FOR SD
 PLACEMENT.
 8-1.4.1.6.2
  
 4)NOTE: PLEASE SEE BOTH SETS OF PLANS
 AND ALL SHEETS FOR ALL TRADES ARE SEALED
  
 PHOTO-COPIES OF SIGNATURE.
 PLEASE SEE THIS HAS BEEN COMMENTED ON ON
 PREVIOUS PROJECTS AND PREVIOUS REVIEWS
 FOR THOSE PROJECTS.
 THE SIGNATURE IS REQUIRED TO BE ORIGINAL
 SIGNATURE. FS 481.221 AND FAC
 61G1-16.004
 ONE COPY OF ONE SET IS BEING RETAINED
 FOR FILE AND POSSIBLE REVIEW BY BOARD OF
 ARCH'S.
 THIS NOTE STANDS FOR ALL SHEETS AND ALL
 TRADES WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWERS.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-06 Cont ID  
Sent By adarroug Date 2006-03-06 Time 12:14 Rev Time 0.00
Received By adarroug Date 2006-03-06 Time 12:14 Sent To E
Notes
2006-03-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-06 Cont ID  
Sent By adarroug Date 2006-03-06 Time 12:12 Rev Time 0.00
Received By adarroug Date 2006-03-06 Time 12:11 Sent To  
Notes
2006-03-06 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 16:15 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 16:15 Sent To E
Notes
2006-02-13 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-01 Cont ID  
Sent By adarroug Date 2006-02-01 Time 18:46 Rev Time 0.00
Received By adarroug Date 2006-02-01 Time 18:46 Sent To E
Notes
2006-02-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-10 Cont ID  
Sent By adarroug Date 2005-03-10 Time 11:15 Rev Time 0.00
Received By adarroug Date 2005-03-10 Time 11:15 Sent To B
Notes
2005-03-10 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-01-27 Cont ID  
Sent By mjacobs Date 2005-01-27 Time 10:21 Rev Time 0.00
Received By mjacobs Date 2005-01-27 Time 10:21 Sent To E
Notes
2005-01-27 00:00:00TO "DP" DESK/RESUB.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-01-27 Cont ID  
Sent By mjacobs Date 2004-12-08 Time 10:20 Rev Time 0.00
Received By mjacobs Date 2004-11-12 Time 16:06 Sent To  
Notes
2004-11-12 00:00:00TO SFD RACK/E
2004-11-09 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-02-14 Cont ID  
Sent By prafter Date 2005-02-14 Time 10:28 Rev Time 0.00
Received By prafter Date 2005-02-14 Time 10:30 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-11-18 Cont ID  
Sent By drunnels Date 2004-11-18 Time 14:32 Rev Time 1.00
Received By drunnels Date 2004-11-18 Time 14:31 Sent To P
Notes
2004-11-18 00:00:00PAT RAFTER805 6719
 NOTE; NO SIZE ON R/A GRILL FOR AHU [1]

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-03-09 Cont ID  
Sent By jleech Date 2006-03-09 Time 08:57 Rev Time 0.00
Received By jleech Date 2006-03-09 Time 08:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-02-11 Cont ID  
Sent By kstevens Date 2005-02-11 Time 11:02 Rev Time 0.50
Received By kstevens Date 2005-02-11 Time 11:02 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-11-22 Cont ID  
Sent By kstevens Date 2004-11-22 Time 05:47 Rev Time 0.33
Received By kstevens Date 2004-11-22 Time 05:47 Sent To B1
Notes
2004-11-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1) SHT A4 SANITARY RISER DIAGRAM AT THE
 WASH MACHINE/LAUNDRY SINK DOES NOT MEET
 CODE REQUIREMENTS.
 A) A STANDPIPE IS REQUIRED PER SECTION
 1002.1
 B) THE CLEANOUT SHALL BE LOCATED 4 FEET
 ABOVE THE FLOOR FOR ACCESS SECTION
 708.10
 C) DOUBLE SANITARY TEE PATTERNS SHALL
 NOT RECEIVE THE DISCHARGE OF APPLIANCES
 WITH PUMPING ACTION DISCHARGE. SECTION
 706.3
  
 2) ARCHITECT'S SIGNATURE IS A COPY ON
 ALL SHEETS. COPIES OF SIGNATURES IS NOT
 APPROVED. FAC 61G1-16.004(5) & FS
 481.221
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-11-10 Cont ID  
Sent By mmclean Date 2004-11-10 Time 16:33 Rev Time 0.00
Received By mmclean Date 2004-11-10 Time 16:33 Sent To I
Notes
2004-11-10 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR POOL
 & DECK.